Service and usage information for<br />

Written by Liam Lin<br />

Edited by Anna Huang<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong><br />

<strong>User</strong> <strong>Manual</strong><br />

Version 1.0.1 beta2, April 2010<br />

<strong>ET</strong>-7042 <strong>ET</strong>-7044 <strong>ET</strong>-7050 <strong>ET</strong>-7051 <strong>ET</strong>-7052<br />

<strong>ET</strong>-7053 <strong>ET</strong>-7060 <strong>ET</strong>-7065 <strong>ET</strong>-7066 <strong>ET</strong>-7067<br />

P<strong>ET</strong>-7044 P<strong>ET</strong>-7051 P<strong>ET</strong>-7052<br />

P<strong>ET</strong>-7060<br />

P<strong>ET</strong>-7065 P<strong>ET</strong>-7067


Warranty<br />

All products manufactured by <strong>ICP</strong> <strong>DAS</strong> are under warranty regarding defective<br />

materials for a period of one year, beginning from the date of delivery to the original<br />

purchaser.<br />

Warning<br />

<strong>ICP</strong> <strong>DAS</strong> assumes no liability for any damage resulting from the use of this<br />

product.<strong>ICP</strong> <strong>DAS</strong> reserves the right to change this manual at any time without notice.<br />

The information furnished by <strong>ICP</strong> <strong>DAS</strong> is believed to be accurate and reliable.<br />

However, no responsibility is assumed by <strong>ICP</strong> <strong>DAS</strong> for its use, not for any<br />

infringements of patents or other rights of third parties resulting from its use.<br />

Copyright<br />

Copyright @ 2009 by <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All rights are reserved.<br />

Trademark<br />

The names used for identification only may be registered trademarks of their<br />

respective companies.<br />

Contact US<br />

If you have any problem, please feel free to contact us.<br />

You can count on us for quick response.<br />

Email: service@icpdas.com<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 2<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Table of Contents<br />

1. Introduction ....................................................................................... 7<br />

1.1. Product Information ...................................................................................... 8<br />

1.1.1. <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> AIO <strong>Series</strong> Release Module ................................ 8<br />

1.1.2. <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> Module Naming Convention ................................ 9<br />

1.1.3. <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> Comparison ....................................................... 10<br />

1.2. Features ..................................................................................................... 12<br />

1.3. Specification ............................................................................................... 15<br />

1.3.1. System Specification ........................................................................ 15<br />

1.3.2. I/O Specification ............................................................................... 17<br />

1.3.2.1. <strong>ET</strong>-7042 .................................................................................. 17<br />

1.3.2.2. <strong>ET</strong>-7044/P<strong>ET</strong>-7044 ................................................................. 19<br />

1.3.2.3. <strong>ET</strong>-7050 .................................................................................. 21<br />

1.3.2.4. <strong>ET</strong>-7051/P<strong>ET</strong>-7051 ................................................................. 23<br />

1.3.2.5. <strong>ET</strong>-7052/P<strong>ET</strong>-7052 ................................................................. 25<br />

1.3.2.6. <strong>ET</strong>-7053 .................................................................................. 27<br />

1.3.2.7. <strong>ET</strong>-7060/P<strong>ET</strong>-7060 ................................................................. 29<br />

1.3.2.8. <strong>ET</strong>-7065/P<strong>ET</strong>-7065 ................................................................. 31<br />

1.3.2.9. <strong>ET</strong>-7066 .................................................................................. 33<br />

1.3.2.10. <strong>ET</strong>-7067/P<strong>ET</strong>-7067 ............................................................... 35<br />

1.4. Wiring Connection ...................................................................................... 37<br />

1.4.1. <strong>ET</strong>-7042/<strong>ET</strong>-7044/<strong>ET</strong>-7050/P<strong>ET</strong>-7044 .............................................. 37<br />

1.4.2. <strong>ET</strong>-7044/<strong>ET</strong>-7050/<strong>ET</strong>-7051/P<strong>ET</strong>-7044/P<strong>ET</strong>-7051 ............................. 37<br />

1.4.3. <strong>ET</strong>-7052/P<strong>ET</strong>-7052 ........................................................................... 38<br />

1.4.4. <strong>ET</strong>-7053 ............................................................................................ 39<br />

1.4.5. <strong>ET</strong>-7060/P<strong>ET</strong>-7060 ........................................................................... 39<br />

1.4.6. <strong>ET</strong>-7065/P<strong>ET</strong>-7065 ........................................................................... 40<br />

1.4.7. <strong>ET</strong>-7065/<strong>ET</strong>-7066/P<strong>ET</strong>-7065 ............................................................ 40<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 3<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.4.8. <strong>ET</strong>-7067/P<strong>ET</strong>-7067 ........................................................................... 41<br />

1.5. Overview .................................................................................................... 42<br />

1.5.1. Front Panel ....................................................................................... 42<br />

1.5.2. Back Panel ....................................................................................... 45<br />

1.6. Dimensions ................................................................................................. 47<br />

1.7. Companion CD ........................................................................................... 48<br />

2. Getting Started ................................................................................ 49<br />

2.1. Mounting the Hardware .............................................................................. 49<br />

2.2. Configuring the Boot Mode ......................................................................... 51<br />

2.3. Connecting to Network, PC and Power ...................................................... 52<br />

2.4. Installing the MiniOS7 Utility ....................................................................... 53<br />

2.5. Using MiniOS7 Utility to Assign a new IP ................................................... 54<br />

2.6. Enabling Adobe Flash Player in Browser .................................................... 58<br />

3. Web Applications ............................................................................ 60<br />

3.1. Overview .................................................................................................... 63<br />

3.2. Configuration .............................................................................................. 65<br />

3.2.1. Network Settings .............................................................................. 66<br />

3.2.1.1. Configure the Network Settings .............................................. 67<br />

3.2.1.2. Check the software information .............................................. 69<br />

3.2.2. Basic Settings ................................................................................... 70<br />

3.2.2.1. Configure the Module Information .......................................... 71<br />

3.2.2.2. Configure the Web site Information ........................................ 72<br />

3.2.2.3. Reset All Settings to Default ................................................... 75<br />

3.2.3. Module I/O Settings .......................................................................... 79<br />

3.3. Authentication ............................................................................................. 80<br />

3.3.1. Account Management ....................................................................... 81<br />

3.3.1.1. Configure the user accounts .................................................. 82<br />

3.3.1.2. Load the factory default user accounts................................... 83<br />

3.3.2. Accessible IP Settings ...................................................................... 84<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 4<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.3.2.1. Configuring IP filter ................................................................. 85<br />

3.4. Web HMI .................................................................................................... 87<br />

3.4.1. Web HMI .......................................................................................... 88<br />

3.4.2. Web Edit ........................................................................................... 89<br />

3.5. Pair Connection .......................................................................................... 97<br />

3.6. More Information ........................................................................................ 98<br />

4. Modbus Applications ...................................................................... 99<br />

4.1. What is Modbus TCP/IP? ......................................................................... 100<br />

4.2. Modbus Message Structure ...................................................................... 101<br />

4.2.1. Address .......................................................................................... 102<br />

4.2.2. Function Codes .............................................................................. 103<br />

4.2.3. Data Field ....................................................................................... 103<br />

4.2.4. Error Check .................................................................................... 103<br />

4.3. Modbus Register Map .............................................................................. 104<br />

4.3.1. Common Function .......................................................................... 104<br />

4.3.2. Particular Function ......................................................................... 106<br />

4.3.2.1. <strong>ET</strong>-7042 I/O Address Mapping ............................................. 107<br />

4.3.2.2. <strong>ET</strong>-7044/P<strong>ET</strong>-7044 I/O Address Mapping ............................ 109<br />

4.3.2.3. <strong>ET</strong>-7050 I/O and Counter Address Mapping .......................... 111<br />

4.3.2.4. <strong>ET</strong>-7051/P<strong>ET</strong>-7051 I/O and Counter Address Mapping ......... 115<br />

4.3.2.5. <strong>ET</strong>-7052/P<strong>ET</strong>-7052 I/O and Counter Address Mapping ......... 119<br />

4.3.2.6. <strong>ET</strong>-7053 I/O and Counter Address Mapping ......................... 123<br />

4.3.2.7. <strong>ET</strong>-7060/P<strong>ET</strong>-7060 I/O and Counter Address Mapping ........ 127<br />

4.3.2.8. <strong>ET</strong>-7065/P<strong>ET</strong>-7065 I/O and Counter Address Mapping ........ 131<br />

4.3.2.9. <strong>ET</strong>-7066/P<strong>ET</strong>-7066 I/O Address Mapping ............................ 135<br />

4.3.2.10. <strong>ET</strong>-7067/P<strong>ET</strong>-7067 I/O Address Mapping .......................... 137<br />

5. MiniOS7 Utility Tool ....................................................................... 139<br />

5.1. Establishing a Connection ........................................................................ 139<br />

5.2. Exchanging the Protocol (TCP/IP to UDP) ............................................... 142<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 5<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


5.3. Updating the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> OS........................................................ 144<br />

5.4. Uploading the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> Firmware ............................................ 149<br />

6. External Tools and Tasks .............................................................. 154<br />

6.1. LabVIEW .................................................................................................. 154<br />

6.2. OPC Server .............................................................................................. 155<br />

6.3. SCADA ..................................................................................................... 156<br />

6.3.1. InduSoft .......................................................................................... 157<br />

6.3.2. Citect .............................................................................................. 158<br />

6.3.3. iFix .................................................................................................. 159<br />

Appendix A. Node Information Area ................................................ 160<br />

Appendix B. Modbus Application Notes .......................................... 161<br />

B.1. Dual Watchdog ......................................................................................... 161<br />

B.2. Power ON Value ....................................................................................... 162<br />

B.3. Safe Value ................................................................................................ 163<br />

B.4. AI High/Low Alarm .................................................................................... 164<br />

B.5. AI High/Low Latch .................................................................................... 169<br />

Appendix C. Troubleshooting .......................................................... 173<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 6<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1. Introduction<br />

The <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong>, a web-based Ethernet I/O module, features a built-in web<br />

server, which allows configuration, I/O monitoring and I/O control by simply using a<br />

regular web browser. Besides, with the web HMI function, no more programming or<br />

HTML skills are needed; creating dynamic and attractive web pages for I/O monitoring<br />

and I/O control would be fun to engineers ever after. The <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> offers<br />

easily and safely access for users from anytime and anywhere! In addition,<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> also supports Modbus/TCP protocol that makes perfect<br />

integration to SCADA software.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 7<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.1. Product Information<br />

1.1.1. <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> AIO <strong>Series</strong> Release Module<br />

Either <strong>ET</strong>-<strong>7000</strong> or P<strong>ET</strong>-<strong>7000</strong> has released three different types of analog series<br />

modules, which provides a variety of analog module choice, listed in the following<br />

table.<br />

Type Model Description<br />

DC Digital Output<br />

(Open Collector)<br />

DC Digital Input<br />

DC Digital Input<br />

and Output<br />

Power Relay<br />

Output<br />

Photomos Relay<br />

Output<br />

<strong>ET</strong>-7042<br />

<strong>ET</strong>-7051/<br />

P<strong>ET</strong>-7051<br />

<strong>ET</strong>-7053<br />

<strong>ET</strong>-7044/<br />

P<strong>ET</strong>-7044<br />

<strong>ET</strong>-7050<br />

<strong>ET</strong>-7052/<br />

P<strong>ET</strong>-7052<br />

<strong>ET</strong>-7060/<br />

P<strong>ET</strong>-7060<br />

16-channel Sink Type Open Collector Isolated<br />

DO Module<br />

16-channel Isolated DI Module with 32-bit<br />

Counters<br />

16-channel Isolated DI Module with 32-bit<br />

Counters<br />

8-channel Isolated Sink Type Open Collector<br />

Output<br />

8-channel Isolated DI Module with 32-bit<br />

Counters<br />

6-channel Isolated Sink Type Open Collector<br />

Output<br />

12-channel Isolated DI Module with 32-bit<br />

Counters<br />

8-channel Isolated Source Type Open<br />

Collector Output<br />

8-channel Isolated DI Module with 32-bit<br />

Counters<br />

6-channel Power Relay Output<br />

6-channel Isolation DI module<br />

<strong>ET</strong>-7067 8-channel Power Relay Output<br />

<strong>ET</strong>-7065/<br />

P<strong>ET</strong>-7065<br />

6-channel PhotoMos Relay Output Module<br />

6-channel Isolated DI Module with 32-bit<br />

Counters<br />

<strong>ET</strong>-7066 8-channel PhotoMos Relay Output Module<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 8<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.1.2. <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> Module Naming Convention<br />

As you examine this manual, you‘ll notice there are many different products available.<br />

Sometimes it is difficult to remember the specifications for any given product. However,<br />

if you take a few minutes to understand the module naming conventions, it may save<br />

you some time and confusion. The figure below shows how the module naming<br />

conventions work for each <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> product.<br />

<strong>ET</strong><br />

P<strong>ET</strong><br />

-7 X Y Z<br />

Z: Extension function code<br />

Y: Function code<br />

X: Number of the variance<br />

7: Seventh Generation<br />

<strong>ET</strong>: Ethernet communication interface without PoE<br />

P<strong>ET</strong>: Ethernet communication interface with PoE<br />

X Y Z<br />

Number of variance 1. AI module 4. Transmitter<br />

5. RTD<br />

6. Strain Gauge<br />

7. Analog Input<br />

8. Thermocouple<br />

2. AO module 1. Voltage output<br />

3. Reserved<br />

2. Current output<br />

4. <strong>DIO</strong> module Number of variance<br />

5. <strong>DIO</strong> module Number of variance<br />

6. <strong>DIO</strong> module with relay Number of variance<br />

7. Multi-function 1. General purpose<br />

8. Counter/Frequency Number of variance<br />

9. Motion N: Number of axes<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 9<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.1.3. <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> Comparison<br />

The features of the P<strong>ET</strong>-<strong>7000</strong> differ from the <strong>ET</strong>-<strong>7000</strong><br />

Power over Ethernet + <strong>ET</strong>-<strong>7000</strong> = P<strong>ET</strong>-<strong>7000</strong><br />

P<strong>ET</strong>-<strong>7000</strong> features ―PoE‖ and many other advantages in <strong>ET</strong>-<strong>7000</strong>. Now, not only data<br />

but power is carried through an Ethernet cable. This feature makes installation of<br />

P<strong>ET</strong>-<strong>7000</strong> a piece of cake. Imagine that no more unnecessary wires, only an Ethernet<br />

cable takes care of everything in the field.<br />

P<strong>ET</strong>-<strong>7000</strong> also features a built-in web server and the web HMI function. A built-in web<br />

server allows basic setting configuration, I/O monitoring and I/O control by simply<br />

using a regular web browser. Remote control is as easy as you surf the internet.<br />

As to the web HMI function, no programming or HTML skills are required; creating<br />

dynamic and attractive web pages for I/O monitoring and I/O control would be fun for<br />

engineers ever after.<br />

P<strong>ET</strong>-<strong>7000</strong> also supports Modbus/TCP protocol that makes perfect integration for<br />

P<strong>ET</strong>-<strong>7000</strong> to SCADA software.<br />

Industrial PoE Solution<br />

When using PoE devices like P<strong>ET</strong>-<strong>7000</strong>, you can choose <strong>ICP</strong> <strong>DAS</strong> ―PoE‖<br />

switch —‖NS-205PSE‖ as the power source, NS-205PSE automatically detects the<br />

connected devices whether they are PoE devices or not. This mechanism ensures<br />

NS-205PSE to work with both PoE and non-PoE devices coordinately at the same<br />

time.<br />

Being as a power source for PoE devices, NS-205PSE requires its power input<br />

ranging from +46 ~ +55VDC.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 10<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


More information about P<strong>ET</strong>-<strong>7000</strong><br />

There are two ways for P<strong>ET</strong>-<strong>7000</strong> getting the power. One is through Ethernet by a<br />

PoE switch; the other is as usual through wiring by an external power. External power<br />

should range from +12 ~ 48 VDC. The reason we keep the second way is because it<br />

might be useful if someday or somehow you have different applications.<br />

There is a LED on P<strong>ET</strong>-<strong>7000</strong>. The LED indicates whether the power comes from the<br />

PoE switch or not.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 11<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.2. Features<br />

� Built in Web Server<br />

Each <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> module has a built-in web server that allows users to<br />

easily configure, monitor and control the module from a remote location using a<br />

regular web browser.<br />

� Web HMI<br />

The Web HMI function allows the users to create dynamic and attractive web<br />

pages to monitor and control the I/O points. <strong>User</strong>s can upload specific I/O layout<br />

pictures (bmp, jpg, gif format) and define a description for each I/O point. No<br />

HTML or Java skills are needed to create the web pages.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 12<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


� Communication Security<br />

Account and password are required when logging into the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong><br />

web server. An IP address filter is also included, which can be used to allow or<br />

deny connections with specific IP addresses.<br />

� Modbus Protocol<br />

The Modbus/TCP slave function on the Ethernet port can be used to provide<br />

data to remote SCADA software.<br />

� Built-in Multi-function I/O<br />

All Digital Output modules provide:<br />

Power on value (On boot up, the DO status is set to the Power-on value)<br />

Safe value (If Modbus/TCP communication is lost for a certain period, the DO<br />

status will be set to the user defined safe value)<br />

All Digital Input modules provide:<br />

High/Low latched status<br />

DI channels can also be used as DI status and 32-bit low speed (100Hz)<br />

counters.<br />

� All-in-one Module<br />

Various I/O components are mixed with multiple channels in a single module,<br />

which provides the most cost effective I/O usage and enhances performance of<br />

the I/O operations<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 13<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


� Automatic MDI / MDI-X Crossover for Plug-and-play<br />

RJ-45 port supports automatic MDI/MDI-x that can automatically detect the type<br />

of connection to the Ethernet device without requiring special straight or<br />

crossover cables.<br />

� Built-in Dual Watchdog<br />

The Dual Watchdog consists of a Module Watchdog and a Host Watchdog.<br />

Module Watchdog is a built-in hardware circuit that can be used to monitor the<br />

operation of the module and will reset the CPU module if a failure occurs in the<br />

hardware or the software.<br />

Host Watchdog is a software function that can be used to monitor the operating<br />

status of the host, and is used to prevent network communication problems or<br />

host failures.<br />

� Ventilated Housing Designed to Operate Between -25 °C to +75 °C<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> is housed in a plastic-based shell/case with a column-like<br />

ventilator that helps to cool the working environment inside the shell/case and<br />

allows <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> to operate at temperatures ranging from -25 °C to<br />

+75 °C.<br />

� I/O Pair Connection<br />

This function is used to<br />

create a DI to DO pair<br />

through the Ethernet.<br />

Once the configuration is<br />

completed,<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong><br />

module can to<br />

continuously poll the<br />

status of remote DI<br />

device using the Modbus/TCP protocol and then write to<br />

local DO channels in the background.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 14<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.3. Specification<br />

1.3.1. System Specification<br />

System<br />

CPU 80186 CPU (80 MHz)<br />

SRAM 512 KB<br />

Flash Memory 512 KB<br />

EEPROM 16 KB<br />

Dual Watchdog Yes<br />

Communication<br />

Ethernet Port 10/100 Base-TX (With Link, Activity LED Indicator)<br />

Isolation<br />

Ethernet -<br />

I/O 2500 VDC<br />

LED Display<br />

Automatic MDI/MDI-X<br />

PoE PoE On (for P<strong>ET</strong>-<strong>7000</strong> series only)<br />

L1 Run indicator<br />

L2 Link/Act indicator<br />

L3 10/100M indicator<br />

Mechanical<br />

Dimensions (W x H x D) 123 mm x 72 mm x 35 mm<br />

Installation DIN Rail or Wall mounting<br />

Environment<br />

Operating Temperature -25 ˚C ~ +75 ˚C<br />

Storage Temperature -30 ˚C ~ +80 ˚C<br />

Humidity 5 ~ 90 % RH, non-condensing<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 15<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Power Requirements (for <strong>ET</strong>-<strong>7000</strong> series only)<br />

Protection Power reverse polarity protection<br />

Required Supply Voltage +10 VDC ~ +30 VDC (non-regulated)<br />

Power Consumption 0.10 A @ 24 VDC Max.<br />

Power Requirements (for P<strong>ET</strong>-<strong>7000</strong> series only)<br />

IEEE 802.3af Class 1<br />

Required Supply Voltage Powered by Power-Over-Ethernet (PoE) or external<br />

LED Indicator Yes<br />

+12~ 48 VDC (non-regulated)<br />

Power consumption 0.08 A @ 24 VDC Max<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 16<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.3.2. I/O Specification<br />

1.3.2.1. <strong>ET</strong>-7042<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 17<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Digital Output<br />

Output Channels 16<br />

Output Type Sink, Open Collector<br />

Output Voltage +5 VDC ~ +30 VDC<br />

Max. Load Current 100 mA/channel at 25 °C<br />

Output Isolation 3750 Vrms<br />

Power Requirements<br />

Direct drive power relay module<br />

Power Consumption 0.1 A @ 24 VDC Max.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 18<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.3.2.2. <strong>ET</strong>-7044/P<strong>ET</strong>-7044<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 19<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Digital Input<br />

Input Channels 8<br />

Input Type Wet Contact (Sink, Source)<br />

On Voltage Level +10 VDC ~ 50 VDC<br />

Off Voltage Level +4 VDC max.<br />

Input Impedance 10 kOhm<br />

Max. Count: 4,294,967,285 (32 bits)<br />

Counters Max. Input Frequency: 500 Hz<br />

Overvoltage Protection +70 VDC<br />

Intra-module Isolation 3750 Vrms<br />

Digital Output<br />

Output Channels 8<br />

Min. Pulse Width: 1ms<br />

Output Type Sink, Open Collector<br />

Output Voltage +10 VDC ~ 40 VDC<br />

Max. Load Current 300 mA/channel at 25 °C<br />

Short Circuit Protection Yes<br />

Output Isolation 3750 Vrms<br />

Power Requirements<br />

Direct drive power relay module<br />

Power Consumption 0.08A @ 24 VDC Max.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 20<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.3.2.3. <strong>ET</strong>-7050<br />

Digital Input<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 21<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Input Channels 12<br />

Input Type Wet Contact (Sink, Source)<br />

On Voltage Level +10 VDC ~ 50 VDC<br />

Off Voltage Level +4 VDC max.<br />

Input Impedance 10 kOhm<br />

Max. Count: 4,294,967,285 (32 bits)<br />

Counters Max. Input Frequency: 500 Hz<br />

Overvoltage Protection +70 VDC<br />

Intra-module Isolation 3750 Vrms<br />

Digital Output<br />

Output Channels 6<br />

Min. Pulse Width: 1ms<br />

Output Type Sink, Open Collector<br />

Output Voltage +5 VDC ~ 30 VDC<br />

Max. Load Current 100 mA/channel at 25 °C<br />

Output Isolation 3750 Vrms<br />

Power Requirements<br />

Direct drive power relay module<br />

Power Consumption 0.13A @ 24 VDC Max.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 22<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.3.2.4. <strong>ET</strong>-7051/P<strong>ET</strong>-7051<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 23<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Digital Input<br />

Input Channels 16<br />

Input Type Wet Contact (Sink, Source)<br />

On Voltage Level +10 VDC ~ 50 VDC<br />

Off Voltage Level +4 VDC max.<br />

Input Impedance 10 kOhm<br />

Max. Count: 4,294,967,285 (32 bits)<br />

Counters Max. Input Frequency: 500 Hz<br />

Overvoltage Protection +70 VDC<br />

Intra-module Isolation 3750 Vrms<br />

Power Requirements<br />

Min. Pulse Width: 1ms<br />

Power Consumption 0.11A @ 24 VDC Max.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 24<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.3.2.5. <strong>ET</strong>-7052/P<strong>ET</strong>-7052<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 25<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Digital Input<br />

Input Channels 8<br />

Input Type Wet Contact (Sink, Source)<br />

On Voltage Level +10 VDC ~ 50 VDC<br />

Off Voltage Level +4 VDC max.<br />

Input Impedance 10 kOhm<br />

Max. Count: 4,294,967,285 (32 bits)<br />

Counters Max. Input Frequency: 500 Hz<br />

Overvoltage Protection +70 VDC<br />

Intra-module Isolation 3750 Vrms<br />

Digital Output<br />

Output Channels 8<br />

Min. Pulse Width: 1ms<br />

Output Type Sink, Open Collector<br />

Output Voltage +10 VDC ~ 40 VDC<br />

Max. Load Current 650 mA/channel at 25 °C<br />

Over-Voltage Protection +48 VDC<br />

Output Isolation 3750 Vrms<br />

Power Requirements<br />

Power Consumption 0.08A @ 24 VDC Max.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 26<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.3.2.6. <strong>ET</strong>-7053<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 27<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Digital Input<br />

Input Channels 16<br />

Input Type Dry Contact<br />

On Voltage Level Open<br />

Off Voltage Level Close to GND<br />

Input Impedance 10 kOhm<br />

Max. Count: 4,294,967,285 (32 bits)<br />

Counters Max. Input Frequency: 500 Hz<br />

Min. Pulse Width: 1ms<br />

Effective Distance 500 m max.<br />

Intra-module Isolation 3750 Vrms<br />

Power Requirements<br />

Power Consumption 0.13A @ 24 VDC Max.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 28<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.3.2.7. <strong>ET</strong>-7060/P<strong>ET</strong>-7060<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 29<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Digital Input<br />

Input Channels 6<br />

Input Type Wet Contact (Sink, Source)<br />

On Voltage Level +10 VDC ~ +50 VDC<br />

Off Voltage Level +4 VDC max.<br />

Input Impedance 10 kOhm<br />

Max. Count: 4,294,967,285 (32 bits)<br />

Counters Max. Input Frequency: 500 Hz<br />

Overvoltage Protection +70 VDC<br />

Intra-module Isolation 3750 Vrms<br />

Digital Output<br />

Output Channels 6<br />

Min. Pulse Width: 1ms<br />

Output Type Power Relay, Form A (SPST N.O.)<br />

Operating Voltage Range 250 VAC/30 VDC<br />

Max. Load Current 5.0 A/channel at 25 °C<br />

Operating Time 6 ms<br />

Release Time 3 ms<br />

VDE 5 A 250 VAC 30,000 ops (10 ops/minute) at 75 °C<br />

Electrical Life 5 A 30 VDC 70,000 ops (10 ops/minute) at 75 °C<br />

(Resistive load) UL 5 A 250 VAC/30 VDC 6,000 ops<br />

3 A 250 VAC/30 VDC 100,000 ops<br />

Mechanical Life 20,000,000 ops. At no load (300 ops./minute)<br />

Relay Output Isolation 3000 Vrms<br />

Power Requirements<br />

Power Consumption 0.12A @ 24 VDC Max.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 30<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.3.2.8. <strong>ET</strong>-7065/P<strong>ET</strong>-7065<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 31<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Digital Input<br />

Input Channels 6<br />

Input Type Wet Contact (Sink, Source)<br />

On Voltage Level +10 VDC ~ +50 VDC<br />

Off Voltage Level +4 VDC max.<br />

Input Impedance 10 kOhm<br />

Max. Count: 4,294,967,285 (32 bits)<br />

Counters Max. Input Frequency: 500 Hz<br />

Overvoltage Protection +70 VDC<br />

Intra-module Isolation 3750 Vrms<br />

Digital Output<br />

Output Channels 6<br />

Min. Pulse Width: 1ms<br />

Output Type PhotoMOS Relay, Form A<br />

Load Voltage 60 VDC/VAC<br />

60 V/1.0A (Operating Temperature -25 °C ~ -40 °C)<br />

Load Current 60 V/0.8A (Operating Temperature +40 °C ~ +60 °C)<br />

Turn On Time 1.3 ms (Typical)<br />

Turn Off Time 0.1 ms (Typical)<br />

Relay Output Isolation 1500 Vrms<br />

Power Requirements<br />

Power Consumption 0.1A @ 24 VDC Max.<br />

60 V/0.7A (Operating Temperature +60 °C ~ +75 °C)<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 32<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.3.2.9. <strong>ET</strong>-7066<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 33<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Digital Output<br />

Output Channels 8<br />

Output Type PhotoMOS Relay, Form A<br />

Load Voltage 60 VDC/VAC<br />

60 V/1.0A (Operating Temperature -25 °C ~ -40 °C)<br />

Load Current 60 V/0.8A (Operating Temperature +40 °C ~ +60 °C)<br />

Turn On Time 1.3 ms (Typical)<br />

Turn Off Time 0.1 ms (Typical)<br />

Relay Output Isolation 1500 Vrms<br />

Power Requirements<br />

Power Consumption 0.1A @ 24 VDC Max.<br />

60 V/0.7A (Operating Temperature +60 °C ~ +75 °C)<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 34<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.3.2.10. <strong>ET</strong>-7067/P<strong>ET</strong>-7067<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 35<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Digital Output<br />

Output Channels 8<br />

Output Type Power Relay, Form A (SPST N.O.)<br />

Operating Voltage Range 250 VAC/30 VDC<br />

Max. Load Current 5.0 A/channel at 25 °C<br />

Operating Time 6 ms<br />

Release Time 3 ms<br />

VDE 5 A 250 VAC 30,000 ops (10 ops/minute) at 75 °C<br />

Electrical Life 5 A 30 VDC 70,000 ops (10 ops/minute) at 75 °C<br />

(Resistive load) UL 5 A 250 VAC/30 VDC 6,000 ops<br />

3 A 250 VAC/30 VDC 100,000 ops<br />

Mechanical Life 20,000,000 ops. At no load (300 ops./minute)<br />

Relay Output Isolation 3000 Vrms<br />

Power Requirements<br />

Power Consumption 0.14A @ 24 VDC Max.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 36<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.4. Wiring Connection<br />

1.4.1. <strong>ET</strong>-7042/<strong>ET</strong>-7044/<strong>ET</strong>-7050/P<strong>ET</strong>-7044<br />

1.4.2. <strong>ET</strong>-7044/<strong>ET</strong>-7050/<strong>ET</strong>-7051/P<strong>ET</strong>-7044/P<strong>ET</strong>-7051<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 37<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.4.3. <strong>ET</strong>-7052/P<strong>ET</strong>-7052<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 38<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.4.4. <strong>ET</strong>-7053<br />

1.4.5. <strong>ET</strong>-7060/P<strong>ET</strong>-7060<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 39<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.4.6. <strong>ET</strong>-7065/P<strong>ET</strong>-7065<br />

1.4.7. <strong>ET</strong>-7065/<strong>ET</strong>-7066/P<strong>ET</strong>-7065<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 40<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.4.8. <strong>ET</strong>-7067/P<strong>ET</strong>-7067<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 41<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.5. Overview<br />

Here is a brief overview of the components and its descriptions for module status.<br />

1.5.1. Front Panel<br />

The <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> front panel contains the Ethernet port, connectors and LEDs.<br />

Ethernet Port<br />

J1 Connector<br />

(Pin 1 ~ 9)<br />

LED Indicators<br />

PoE LED Indicator<br />

(for PoE series only)<br />

J2 Connector<br />

(Pin 10 ~ 23)<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 42<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


� J1 Connector<br />

Depending on the types of the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> modules.<br />

For more detailed information regarding the pin assignments of the J1<br />

Connector, please refer to ―1.3.2. I/O Specification‖<br />

� J2 Connector<br />

Depending on the types of the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> modules.<br />

For more detailed information regarding the pin assignments of the J2<br />

Connector, please refer to ―1.3.2. I/O Specification‖<br />

Tips & Warnings<br />

The definition of pin 8 and pin 0 applies to all types of the<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> modules. The definition of the other pins is<br />

dependent on the particular <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> modules.<br />

Pin number Name Function<br />

8 +VS 10 ~ 30 VDC power input<br />

9 GND Ground connection<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 43<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


� LED Indicators<br />

Name LED Action Function<br />

Run Flashing Firmware is running<br />

Link/ACT<br />

10/100M<br />

Tips & Warnings<br />

� Poe LED Indicator<br />

ON Ethernet link detected<br />

OFF No Ethernet link detected<br />

Flashing Green Ethernet packet received<br />

OFF Speed 10 Mbps<br />

Orange Speed 100 Mbps<br />

If the Run LED does not display the information as above, the<br />

following steps should be taken:<br />

Step 1: Switch the power off<br />

Step 2: Check that the Init/Normal switch is in the Normal position<br />

(Refer to ―1.5.2. Back Panel‖)<br />

Step 3: Switch the power on and double-check the LED indicators<br />

When unit power is supplied via PoE (Power-over-Ethernet), the PoE indicator<br />

will be on.<br />

� Ethernet Port<br />

An Ethernet port is an opening on <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> network equipment that<br />

Ethernet cables plug into. Ethernet ports accept cables with RJ-45 connectors.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 44<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.5.2. Back Panel<br />

The <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> back panel contains the frame ground and<br />

Frame Ground<br />

Operating Mode<br />

Selector Switch<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 45<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


� Operating Mode Selector Switch<br />

Init mode: MiniOS7 configuration mode<br />

Normal mode: Firmware running mode<br />

In the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> series, the Switch is always in the Normal position.<br />

Only when updating the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> firmware or OS, the switch can be<br />

moved from the Normal position to the Init position.<br />

Move the Switch to the Normal position after the update is complete.<br />

� Frame Ground<br />

Electronic circuits are constantly vulnerable to Electro-Static Discharge (ESD),<br />

which become worse in a continental climate area. <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> series<br />

modules feature a new design for the frame ground, which provides a path for<br />

bypassing ESD, allowing enhanced static protection (ESD) capability and<br />

ensures that the module is more reliable.<br />

The following options will provide a better protection for the module:<br />

The <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> controller has a metallic board attached to the back of<br />

the plastic basket as shown in the figure below, point 1.<br />

When mounted to the DIN rail, connect the DIN rail to the earth ground because<br />

the DIN rail is in contact with the upper frame ground as shown in the figure<br />

below, point 2.<br />

2<br />

1<br />

Frame Ground<br />

Frame Ground<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 46<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.6. Dimensions<br />

All dimensions are in millimeters.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 47<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


1.7. Companion CD<br />

This package comes with a CD that provides drivers, software utility, all of the required<br />

documentations…, etc. All of them are listed below.<br />

CD:\Napdos<br />

P<strong>ET</strong><strong>7000</strong>_<strong>ET</strong><strong>7000</strong><br />

Demo<br />

Document<br />

PC_Client<br />

Modbus_TCP<br />

Application<br />

Data_Sheet<br />

ns_205pse<br />

previous_manual_backup<br />

firmware<br />

OS_image<br />

Tools<br />

Readme.txt<br />

quick_start<br />

EZ_Data_Logger<br />

Napopcsvr<br />

Tools for MiniOS7<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 48<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


2. Getting Started<br />

If you are a new user, begin with this chapter, it includes a guided tour that provides a<br />

basic overview of installing, configuring and using the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong>.<br />

2.1. Mounting the Hardware<br />

The <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> can be mounted with the bottom of the chassis on the DIN rail,<br />

the wall or piggyback.<br />

� DIN Rail mounting<br />

The <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> has<br />

simple rail clips for mounting reliably on a<br />

standard 35 mm DIN rail.<br />

Mounting on DIN Rail Remounting from DIN Rail<br />

1<br />

3<br />

2<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 49<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com<br />

3<br />

1<br />

2


Din Rail Mountable Model<br />

Three Din rail mountable models<br />

are available to mount a variety<br />

of <strong>ICP</strong> <strong>DAS</strong> devices. Each is<br />

made of stainless steel and has<br />

a ground wire at the end.<br />

Part number Maximum number of modules Dimensions<br />

DRS-125 2 125 mm x 35 mm<br />

DRS-240 3 240 mm x 35 mm<br />

DRS-360 5 360 mm x 35 mm<br />

� Piggyback Mounting<br />

The <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> has two holes<br />

on both sides for piggyback mounting<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 50<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


2.2. Configuring the Boot Mode<br />

The <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> has two operating modes that can be determined by the<br />

switch mechanism on the chassis.<br />

� Init Mode<br />

Init mode is a way to use MiniOS7<br />

configuration mode.<br />

Init<br />

Normal<br />

� Normal Mode<br />

Normal mode is the default mode of operation and the one you will use most of<br />

the time. Use this mode for more tasks and configurations. Programs also are<br />

executed in this mode.<br />

Init<br />

Normal<br />

Normal mode is the default mode of operation and the one you will use most of the<br />

time. Use this mode for more tasks and configurations. Programs also are executed in<br />

this mode.<br />

Move the switch to the Normal position after the update is complete<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 51<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


2.3. Connecting to Network, PC and Power<br />

The <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> is equipped with an RJ-45 Ethernet port for connection to an<br />

Ethernet hub/switch and PC<br />

Non-PoE<br />

PoE<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 52<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


2.4. Installing the MiniOS7 Utility<br />

The MiniOS7 Utility is a useful tool that provides a quick and easy way to update OS<br />

image or firmware, configure Ethernet settings, and download files to<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> from PC.<br />

Step 1: Get the MiniOS7 Utility tool<br />

The MiniOS7 Utility can be obtained from companion CD or our FTP site:<br />

CD:\Napdos\minios7\utility\minios7_utility\<br />

ftp://ftp.icpdas.com/pub/cd/8000cd/napdos/minios7/utility/minios7_utility/<br />

Step 2: Follow the prompts to complete the installation<br />

After the installation has been<br />

completed, there will be a new<br />

short-cut for MiniOS7 Utility on<br />

the desktop.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 53<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


2.5. Using MiniOS7 Utility to Assign a new IP<br />

The <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> are web-based devices, which comes with a default IP<br />

address, therefore, you must first assign a new IP address to the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong>.<br />

The factory default IP settings are as follows:<br />

Item Default<br />

IP Address 192.168.255.1<br />

Subnet Mask 255.255.0.0<br />

Gateway 192.168.0.1<br />

Step 1: Run the MiniOS7 Utility<br />

Double-click the MiniOS7 Utility shortcut on your desktop.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 54<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Step 2: Press “F12” or choose “Search” from the “Connection”<br />

menu<br />

After pressing F12 or choosing Search from Connection menu, that will<br />

search all of the MiniOS7 modules on your network.<br />

See the status tip, waiting<br />

for the search to be done.<br />

Step 3: Choose the field “192.168.255.1” and then choose “IP<br />

setting” from the toolbar<br />

Choose default value ―192.168.255.1‖ for fields in the list, and then choose IP<br />

setting from the toolbar.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 55<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Step 4: Assign a new IP address and then choose “Set” button<br />

You can manually assign an IP address or use DHCP to dynamically assign IP<br />

addresses<br />

Step 5: Choose “Yes” button<br />

After completing the settings, the Confirm dialog box will appear, and then<br />

choose the Yes button to exit the procedure.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 56<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Step 6: Reboot the module and then press “F12” or choose “Search”<br />

from the “Connection” menu to check the IP setting<br />

After completing the settings, you can reboot the module and then using<br />

MiniOS7 to search module again for making sure that your IP settings are<br />

correct.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 57<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


2.6. Enabling Adobe Flash Player in Browser<br />

Your browser must support the Adobe Flash Player in order to view the<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> web site.<br />

If you do not have it installed, please follow the instructions below.<br />

Step 1: Go to the Adobe Flash Player Download Center<br />

The Adobe Flash Player Download Center:<br />

http://get.adobe.com/flashplayer/<br />

Step 2: Follow the prompts to download the installation file<br />

Step<br />

Click the Agree and install now button and follow the instructions to download<br />

the installation file<br />

3: Verify that the Adobe Flash Player has been installed<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 58<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


You can verify that it has been installed correctly by clicking the link below.<br />

http://get.adobe.com/flashplayer/completion/dlm/<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 59<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3. Web Applications<br />

The <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> contains an advanced web configuration system that<br />

provides users with access <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> applications through a standard web<br />

browser.<br />

Logging in to the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> Web site<br />

You can log in to the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> web site from any computer that has<br />

Internet access.<br />

Step 1: Open a browser<br />

In several browsers, Mozilla Firefox and Internet Explorer are both reliable<br />

and popular internet browsers.<br />

Step 2: Type the URL address of the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong><br />

If you haven‘t changed the default IP address of the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong>,<br />

please refer section ―2.5. Using MiniOS7 Utility to Assign a new IP‖ to<br />

configure it.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 60<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Step 3: Fill out the <strong>User</strong> name and Password<br />

After entering the IP<br />

address, the login dialog<br />

box will appear and prompt<br />

you to enter your<br />

username and password.<br />

The factory default user<br />

name and password are as<br />

follows:<br />

Item Default<br />

<strong>User</strong> name Admin<br />

Password Admin<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 61<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Step 4: Welcome to <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> web site<br />

After logging into the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> web site, the welcome page will<br />

appear.<br />

This site serves several functions. You can<br />

easily access these functions through the<br />

menu on the left side.<br />

The Overview of the Main menu provides a<br />

brief introduction and explanation of this<br />

site.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 62<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.1. Overview<br />

The Overview links to the welcome page that determines two message body parts.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 63<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


The first part of this page provides basic information about the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong><br />

hardware and software.<br />

The second part of this page provides a brief introduction of this web site.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 64<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.2. Configuration<br />

All items below are located under the Configuration menu:<br />

Network Settings: Links to the Ethernet<br />

Settings page that allows you to access<br />

the IP settings and check the software<br />

version.<br />

Basic Settings: Links to the Basic<br />

Settings page that allows you to configure<br />

the basic information of this site.<br />

Module I/O Settings: Links to the<br />

Common Functions page that allows you<br />

to configure the settings of the Modbus<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 65<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.2.1. Network Settings<br />

The Ethernet Settings page provides the following functions:<br />

� Configure the network settings<br />

� Check the software information<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 66<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.2.1.1. Configure the Network Settings<br />

A generally network setting includes the following parameters:<br />

� An IP address: Each <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> on the network must have a unique IP<br />

address. It is used to assign an IP address.<br />

� A default gateway: A gateway (or router) is a system that is used to connect a<br />

network with one or more other networks.<br />

� A subnet mask: The subnet mask indicates which portion of the IP address that<br />

is used to identify the local network or subnet.<br />

There are two ways to configure the network settings:<br />

� Dynamic configuration: Dynamic Host Configuration Protocol (DHCP) is a<br />

network application protocol that automatically assigns IP address to devices.<br />

� <strong>Manual</strong>ly configuration: If you don‘t have a DHCP server in your network, you<br />

can configure network settings manually.<br />

Dynamic Configuration<br />

Dynamic configuration is very easy to configure. If you have a DHCP server, network<br />

address can be configured dynamically by following steps:<br />

Step 1: Enable the DHCP<br />

Step 2: Click MODIFY_S<strong>ET</strong>TING to finished configuring the network settings<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 67<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


<strong>Manual</strong>ly Configuration<br />

In manual configuration, you have to assign all the network settings manually. To<br />

configure network settings manually, follow the following steps:<br />

Step 1: Disable the DHCP<br />

Step 2: Enter the network settings<br />

Step 3: Click MODIFY_S<strong>ET</strong>TING to finished configuring the network settings<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 68<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.2.1.2. Check the software information<br />

The software information includes the following data items:<br />

� Web Server Lib Ver.: The version of the web server library. The web server<br />

library is a collection of web development solutions.<br />

� MiniOS7 Ver.: The version of the MiniOS7 OS image. The MiniOS7 is an<br />

embedded OS designed for <strong>ICP</strong> <strong>DAS</strong> controller.<br />

After updating the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> firmware, you can check the version of the<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> software information.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 69<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.2.2. Basic Settings<br />

The Basic Settings page provides the following functions:<br />

� Configure the module information<br />

� Configure the web site information<br />

� Reset all settings to default<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 70<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.2.2.1. Configure the Module Information<br />

The module information includes the following data items:<br />

� Module Name: The name of the module that can be modified. It has an initial<br />

value depending on the name of the module.<br />

� Module Information: The module information indicates the name of the alias<br />

that is used to identify the module.<br />

To configure the module information, follow the following steps:<br />

Step 1: Enter the module information<br />

Step 2: Click Submit to finished configuring the module information<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 71<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.2.2.2. Configure the Web site Information<br />

The module information includes the following data items:<br />

� Top page Information (First line) and Top page Information (Second line):<br />

�<br />

The title of the website that can be modified, you can view the title information<br />

in the top-left corner. The title information can be determined as follows:<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 72<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


� More Information URL: The URL of the more information menu that can be<br />

modified, you can specify the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> URL for getting additional<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> supports.<br />

� Web Server TCP Port: A port number of the TCP/IP port. A port number is a<br />

16-bit unsigned integer. By default, TCP/IP uses port 80.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 73<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


To configure the web site information, follow the following steps:<br />

Step 1: Enter the web site information<br />

Step 2: Click Submit to finished configuring the module information<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 74<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.2.2.3. Reset All Settings to Default<br />

According to the menu selection of this web, the reset function can be divided into<br />

the following categories. You can use this function to reset the settings to their<br />

factory default.<br />

� Configuration<br />

� Authentication<br />

� Web HMI<br />

� Pair Connection<br />

� All<br />

To reset the settings to their factory default, follow the following steps:<br />

Step 1: Enable the reset selection<br />

Step 2: Click Submit to finished resetting the settings to their factory default<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 75<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.2.2.3.1. Factory Default Settings for Configuration Menu Service<br />

The table below lists the factory default settings of the configuration menu.<br />

Network Settings<br />

Data Item Factory Default Settings<br />

IP 192.168.255.1<br />

Gateway 192.168.0.1<br />

Mask 255.255.0.0<br />

DHCP Disable<br />

Basic Settings<br />

Data Item Factory Default Setting<br />

Module Name Depending on the module name<br />

Module Information Empty<br />

Top page Information (First line) <strong>ICP</strong> <strong>DAS</strong><br />

Top page Information (Second line) http://www.icpdas.com<br />

More Information URL<br />

Web Server TCP Port 80<br />

Configuration Disable<br />

Authentication Disable<br />

Web HMI Disable<br />

Pair Disable<br />

All Disable<br />

http://www.icpdas.com/products/Remote<br />

_IO/et-<strong>7000</strong>/et-<strong>7000</strong>_introduction.htm<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 76<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Module I/O Settings<br />

The default settings of the I/O modules depending on the Modbus function of the<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> module.<br />

For a more detailed description of these Modbus function, please refer to section ―4.3.<br />

Modbus Register Map‖.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 77<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.2.2.3.2. Factory Default Settings for Authentication Menu Service<br />

The table below lists the factory default settings of the Authentication menu.<br />

Account Management<br />

Factory Default Setting<br />

A default user account consists of a account name “Admin” and a password<br />

“Admin”.<br />

Accessible IP Settings<br />

Factory Default Setting<br />

Empty, there is no limit to allow any outgoing access.<br />

3.2.2.3.3. Factory Default Settings for Web HMI Menu Service<br />

The table below lists the factory default settings of the Web HMI menu.<br />

Web HMI<br />

Factory Default Setting<br />

Depending on the Modbus setting function of the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong>.<br />

Web Editing<br />

Factory Default Setting<br />

0 Page<br />

3.2.2.3.4. Factory Default Settings for Pair Connection Menu Service<br />

The table below lists the factory default settings of the Web HMI menu.<br />

Pair Connection<br />

Factory Default Setting<br />

Empty<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 78<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.2.3. Module I/O Settings<br />

The Common Function page provides options to configure the settings of the<br />

Modbus functions. Modbus setting functions differently depending on the type of<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> module, all settings can be divided into either common, DI, DO,<br />

AI and AO settings.<br />

The illustration below shows the Modbus settings for the <strong>ET</strong>-7019 module<br />

This page display different contents depending on the Modbus function of the<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> module.<br />

For a more detailed description of these Modbus function, please refer to section ―4.3.<br />

Modbus Register Map‖.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 79<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.3. Authentication<br />

All items below are located under the Authentication menu:<br />

Account Management: Links to the<br />

Privilege management page that allows<br />

you to manage the user accounts and<br />

their privileges.<br />

Accessible IP Settings: Links to the IP<br />

filter Settings page that allow you to<br />

control access to the web site<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 80<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.3.1. Account Management<br />

The Basic Settings page provides the following functions:<br />

� Configure the user accounts<br />

� Load the factory default user account<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 81<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.3.1.1. Configure the user accounts<br />

The <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> web site supports up to 5 user accounts.<br />

� A built-in administrator account<br />

The built-in Administrator is basically a setup and disaster recovery account<br />

that can be deleted. You can change the administrator account‘s password.<br />

� Four user-defined account<br />

Each user account consists of<br />

� An account name: Specifies the name of This can be your name or another<br />

alias<br />

� A password: The system will ask you to type this in twice to ensure it is correct.<br />

� The authority: that determines what operations the user is allowed to perform.<br />

The authority has the following roles to determine what operations the user is<br />

allowed to perform.<br />

� Admin: Enables access to all <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> website features, functions, and<br />

commands.<br />

� <strong>User</strong>: Enables limited access to <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> website features, functions,<br />

and commands. In general, operators cannot change configuration settings.<br />

When you create user accounts, you can Enable or Disable user accounts.<br />

Step 1: Enter the user account information, and then select the enable checkbox<br />

Step 2: Click Submit to finished configuring the user accounts<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 82<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.3.1.2. Load the factory default user accounts<br />

The <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> has a built-in administrator account named Admin which is<br />

created when it is installed by default. The default account cannot be deleted.<br />

Step 1: Select the Load Setup Default checkbox<br />

Step 2: Click Submit to finished configuring the user accounts<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 83<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.3.2. Accessible IP Settings<br />

The IP filter Settings page provides the following functions:<br />

� Configure connection filtering<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 84<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.3.2.1. Configuring IP filter<br />

The <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> with an IP filter that enables you to restrict or grant user<br />

access based an IP filter list you create.<br />

The filter can be enabled or disable by selecting the Enable the IP filter table<br />

checkbox<br />

Tips & Warnings<br />

By default, there is no limit to allow any outgoing access.<br />

Each list entry can be active or inactive by clicking its Active the rule<br />

� Configure the user accounts<br />

Here we provide two basic methods for configuring the IP filter.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 85<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Method 1: Allows access from a single IP address<br />

Step 1: Select the Enable the IP filter table checkbox<br />

Step 2: Enter the same IP address in the From (IP Address) and To (IP Address)<br />

Step 3: Select the Active the rule checkbox<br />

Step 4: Click Submit to finished configuring the IP filter list<br />

Method 2: Allow access from a group of IP addresses<br />

Step 1: Select the Enable the IP filter table checkbox<br />

Step 2: Enter a range of IP addresses in the From (IP Address) and To (IP Address)<br />

Step 3: Select the Active the rule checkbox<br />

Step 4: Click Submit to finished configuring the IP filter list<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 86<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.4. Web HMI<br />

All items below are located under the Web HMI menu:<br />

Web HMI: Links to the I/O monitor page<br />

that allows you to monitor the<br />

Web Edit: Links to the Web Page<br />

Configuration page that allows you to<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 87<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.4.1. Web HMI<br />

By default, this page displays summary information about I/O channels which are<br />

classified according to the module type.<br />

Here you can add more tabs and set the starting tab by editing the web edit page, for<br />

more details, please refer to 3.4.2. Web Edit.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 88<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.4.2. Web Edit<br />

The Web Editing page provides functions to create the user-defined web pages<br />

which are displayed on the Web HMI page.<br />

Web HMI page<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 89<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


By default, there are no pages to be listed in the Web Page Configuration form.<br />

The <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> supports up to 10 user-defined web pages<br />

A maximum of 10 pages can be created.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 90<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Below is an example of how to create your own page.<br />

Example:<br />

Create a Web page to monitor the I/O of the conveyer system shown below. The I/O<br />

system contains a sensor that are used to detect the products, and a switch that are<br />

used to turn the conveyer motor on and off.<br />

Step 1: Add a new page<br />

Click Add new Page<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 91<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Step 2: Upload a diagram<br />

Click Browse… to select an image, and then click Upload to upload images to the<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> module.<br />

Tips & Warnings<br />

The file type of images can be either of .jpg, .gif, or .bmp. The<br />

recommended resolution for the image to be displayed on the<br />

editing Web page is 340 * 250 pixels.<br />

After the upload is completed, the image information will be displayed and the image<br />

will be added in the Image list box as below shown.<br />

Image information<br />

1. Click Browse… to select an image<br />

2. Click Upload to upload the image<br />

Added in the Image list box<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 92<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Step 3: Set the page name and select the diagram<br />

Type the page name in the Page Name field and then select the diagram from the<br />

Image list box. (After selecting the diagram, the diagram will be shown in the Preview<br />

window)<br />

Step 4: Add the register item for reading selected sensor input<br />

Click Edit in the first row of the Group table and then the Edit Group Register window<br />

will be displayed.<br />

Set the page name and select the diagram<br />

Click Edit to edit the register item<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 93<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Step 5: Add a DI for reading PHS1 input<br />

Set PHS1 to be an input, you can<br />

using the Modbus Register 1,<br />

then select Discrete Input as the<br />

Register Type and type PHS as<br />

the Alias.<br />

Step 6: Save selected sensor settings<br />

Click Save button to complete set up<br />

Step 7: Add the register item for writing selected motor output to turn/<br />

After save the register settings, the new register item will be displayed in the Group<br />

table.<br />

Click Edit in the second row of the Group table and then the Edit Group Register<br />

window will be displayed.<br />

Click Edit to edit the register item<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 94<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Step 8: Add a DO for writing Motor1 output to<br />

turn the conveyer motor on and off<br />

Set Motor to be an output, you can<br />

using the Modbus Register 1, then<br />

select Coil as the Register Type and<br />

type Motor as the Alias.<br />

Step 9: Save selected sensor settings<br />

Click Save button to complete set up<br />

Step 10: Save the editing page.<br />

Click Save button to complete set up<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 95<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Step 11: Browse the Conveyer web page.<br />

After saving the editing page, the editing page named as Conveyer has<br />

been added to the list box on the top-left hand side of the Web Page<br />

Configuration window. Then select the Conveyer item and click Go to<br />

browse to the Conveyer web page.<br />

The conveyer image file and all register items will be displayed on the Conveyer<br />

web page.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 96<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.5. Pair Connection<br />

The Pair Connection links to the configuration page of the pair connection function.<br />

This pair connection function is a particular<br />

feature of <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> that can<br />

enable a pair of DI-to-DO via Modbus/TCP<br />

(Ethernet).<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 97<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


3.6. More Information<br />

The More Information links to the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> web site that provides more<br />

detailed information related to <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> series products.<br />

The default URL of the More Information item is:<br />

You can change the URL of this link by<br />

simply editing the URL, for more details,<br />

please refer to section ―3.2.2.2.<br />

Configure the Web site Information‖<br />

http://www.icpdas.com/products/Remote_IO/et-<strong>7000</strong>/et-<strong>7000</strong>_introduction.htm<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 98<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


4. Modbus Applications<br />

The <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> is a Modbus device that allows you to access terminals data<br />

via Ethernet and communicates using a master-slave technique in which only one<br />

device (the master) can initiate transactions (called queries). The other devices<br />

(slaves) respond by supplying the requested data to the master, or by taking the<br />

action requested in the query.<br />

Most SCADA Supervisor Control And Data Acquisition and HMI software can easily<br />

integrate serial devices via the Modbus protocol, such as Citect, ICONICS, iFIX,<br />

InduSoft, Intouch, Entivity Studio, Entivity Live, Entivity VLC, Trace Mode, Wizcon,<br />

Wonderware, etc.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 99<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


4.1. What is Modbus TCP/IP?<br />

Modbus is a communication protocol developed by Modicon in 1979.<br />

Different versions of Modbus used today include Modbus RTU (based on serial<br />

communication like RS485 and RS232), Modbus ASCII and Modbus TCP, which is<br />

the Modbus RTU protocol embedded into TCP packets.<br />

Modbus TCP is an internet protocol. The protocol embeds a Modbus frame into a TCP<br />

frame so that a connection oriented approach is obtained thereby making it reliable.<br />

The master query‘s the slave and the slave responds with the reply. The protocol is<br />

open and hence highly scalable.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 100<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


4.2. Modbus Message Structure<br />

Modbus devices communicate using a master-slave (client-server) technique in which<br />

only one device (the master/client) can initiate transactions (called queries). The other<br />

devices (slaves/servers) respond by supplying the requested data to the master, or by<br />

taking the action requested in the query.<br />

A master‘s query will consist of a slave address (or broadcast address), a function<br />

code defining the requested action, any required data, and an error checking field. A<br />

slave‘s response consists of fields confirming the action taken, any data to be<br />

returned, and an error checking field.<br />

Address<br />

(1 byte)<br />

Function Code<br />

(1 byte)<br />

Data<br />

Address specifies the address of the receiver.<br />

Function Code specifies the message type.<br />

Data is the data block.<br />

(0 to 252 bytes)<br />

Checksum<br />

(2 bytes)<br />

Checksum specifies the numerical check value for testing the validity of the<br />

protocol.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 101<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


4.2.1. Address<br />

The first byte of information in the message structure of Modbus is the receiver‘s<br />

address. The valid addresses are in the range of 0 to 247. Addresses from 1 to 247<br />

are given to individual Modbus devices and 0 is used for broadcast.<br />

Reference Description<br />

0xxxx<br />

1xxxx<br />

3xxxx<br />

4xxxx<br />

Read/Write Discrete Outputs or Coils. A 0x reference<br />

address is used to device output data to a digital output<br />

channel.<br />

Read Discrete Inputs. The ON/OFF status of a 1x reference<br />

address is controlled by the corresponding digital input<br />

channel.<br />

Read Input Registers. A reference register contains a 16-bit<br />

number received from an external source --- e.g. an analog<br />

signal.<br />

Read/Write Output or Holding Registers. A 4x register is<br />

used to store 16-bits of numerical dada (binary or decimal),<br />

or to send the data from the CPU to an output channel.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 102<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


4.2.2. Function Codes<br />

The second byte in the frame structure is the function code. The function code<br />

describes what the slave is required to do. Valid function codes are between 1 and<br />

255. The slave uses the same function code as the request to answer it. Only when<br />

error occurs in the system, the highest bit of the function code will be made ‗1‘. Hence<br />

the master will know if the message has been transmitted correctly or not.<br />

Code Function Reference<br />

01 (01H) Read Coils (Output) Status 0xxxx<br />

02 (02H) Read Input Status 1xxxx<br />

03 (03H) Read Holding Registers 4xxxx<br />

04 (04H) Read Input Registers 3xxxx<br />

05 (05H) Force Single Coil (Output) 0xxxx<br />

06 (06H) Preset Single Register 4xxxx<br />

15 (0FH) Force Multiple Coils (Outputs) 0xxxx<br />

16 (10H) Preset multiple Registers 4xxxx<br />

4.2.3. Data Field<br />

The data field consists of messages sent between master and slave. The messages<br />

contain additional information about the action to be taken by the slave or any<br />

information requested by the slave. When the slave does not require this information<br />

the data field can be nonexistent.<br />

4.2.4. Error Check<br />

The error check performed in Modbus/RTU is Cyclic Redundancy Check (CRC). Both<br />

the transmitting device and the receiver compute CRC. Two bytes are used for this<br />

purpose and generally one bit errors are detected by this method.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 103<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


4.3. Modbus Register Map<br />

4.3.1. Common Function<br />

� (0xxxx) DO address<br />

Begin<br />

address<br />

Points Description Registers<br />

126 1 Recover all I/O default<br />

settings<br />

127 1 Recover all web default<br />

settings<br />

per Point<br />

Range Access<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 104<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com<br />

Type<br />

1 1=recover W<br />

(Pulse)<br />

1 1=recover W<br />

(Pulse)<br />

128 1 ID default settings 1 1=recover W<br />

(Pulse)<br />

129 1 Web Enable/Disable 1 1=recover W<br />

(Pulse)<br />

133 1 Reboot <strong>ET</strong>-<strong>7000</strong> 1 1=reboot W<br />

� (3xxxx) AI address<br />

Begin<br />

address<br />

Points Description Registers<br />

per Point<br />

150 1 OS image version 1 123 means<br />

version=1.2.3<br />

151 1 Total Firmware version 1 123 means<br />

158 1 Modbus communication<br />

status<br />

version=1.2.3<br />

1 0= No Error<br />

-1= CRC error<br />

-2= Timeout<br />

160 1 Pair Connection 1 0=Normal<br />

1=Timeout<br />

(Pulse)<br />

Range Access<br />

2=Disconnected<br />

Type<br />

R<br />

R<br />

R<br />

R


� (4xxxx) AO address<br />

Begin<br />

address<br />

Points Description Registers<br />

per Point<br />

255 1 CPU reset status 1 1= by power on<br />

Range Access<br />

2= by 0.8 second<br />

WDT<br />

3= by Reset<br />

command<br />

256 1 CPU reset events 1 How many CPU reset<br />

events has<br />

happened?<br />

When CPU is reset by<br />

one of the situations<br />

described in register<br />

555, the event<br />

increases one count.<br />

257 1 Set host watch dog timer 1


4.3.2. Particular Function<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 106<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


4.3.2.1. <strong>ET</strong>-7042 I/O Address Mapping<br />

Modbus Address<br />

(Base 0)<br />

00000<br />

00001<br />

00002<br />

00003<br />

00004<br />

00005<br />

00006<br />

00007<br />

00008<br />

00009<br />

00010<br />

00011<br />

DO Channel<br />

(Base 0)<br />

00012<br />

00013<br />

00014<br />

00015<br />

11 10 9 8 7 6 5 4 3 2 1 0<br />

13<br />

14<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 107<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com<br />

12<br />

15<br />

DO Channel<br />

(Base 0)


Detailed Modbus Address Table for <strong>ET</strong>-7042<br />

� (0xxxx) DO address<br />

Begin<br />

address<br />

Points Description Registers<br />

per Point<br />

Range Access<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 108<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com<br />

Type<br />

0 0~15 Digital Output 1 0=Off 1=On R/W<br />

231 1 Write DO Power on value to<br />

EEPROM<br />

232 1 Write DO Safe value to<br />

EEPROM<br />

235 0~15 Power on value for DO 1 0=Off<br />

1 1=Write W<br />

(Pulse)<br />

1 1=Write W<br />

1=On<br />

267 0~15 Safe value for DO 1 0=Off<br />

� (3xxxx) AI address<br />

Begin<br />

address<br />

Points Description Registers<br />

per Point<br />

(Default=0)<br />

1=On<br />

(Default=0)<br />

(Pulse)<br />

R/W/E<br />

R/W/E<br />

Value Access<br />

110 1 DO (channel number) 1 16 R<br />

111 1 Power on value for DO<br />

(channel number)<br />

112 1 Safe value for DO (channel<br />

number)<br />

Type<br />

1 16 R<br />

1 16 R


4.3.2.2. <strong>ET</strong>-7044/P<strong>ET</strong>-7044 I/O Address Mapping<br />

Modbus Address<br />

(Base 0)<br />

00000<br />

00001<br />

00002<br />

00003<br />

00004<br />

00005<br />

00006<br />

00007<br />

10000<br />

10001<br />

10002<br />

DI Channel<br />

(Base 0)<br />

10003<br />

10004<br />

10005<br />

10006<br />

10007<br />

DI Channel<br />

(Base 0)<br />

2 1 0 7 6 5 4 3 2 1 0<br />

3 4 5 6 7<br />

DO Channel<br />

(Base 0)<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 109<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Detailed Modbus Address Table for <strong>ET</strong>-7044/P<strong>ET</strong>-7044<br />

� (0xxxx) DO address<br />

Begin<br />

address<br />

Points Description Registers<br />

per Point<br />

Range Access<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 110<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com<br />

Type<br />

0 0~15 Digital Output 1 0=Off 1=On R/W<br />

231 1 Write DO Power on value to<br />

EEPROM<br />

232 1 Write DO Safe value to<br />

EEPROM<br />

235 0~15 Power on value for DO 1 0=Off<br />

1 1=Write W<br />

(Pulse)<br />

1 1=Write W<br />

1=On<br />

267 0~15 Safe value for DO 1 0=Off<br />

� (3xxxx) AI address<br />

Begin<br />

address<br />

Points Description Registers<br />

per Point<br />

(Default=0)<br />

1=On<br />

(Default=0)<br />

(Pulse)<br />

R/W/E<br />

R/W/E<br />

Value Access<br />

110 1 DO (channel number) 1 16 R<br />

111 1 Power on value for DO<br />

(channel number)<br />

112 1 Safe value for DO (channel<br />

number)<br />

Type<br />

1 16 R<br />

1 16 R


4.3.2.3. <strong>ET</strong>-7050 I/O and Counter Address Mapping<br />

� <strong>ET</strong>-7050 I/O Address Mapping<br />

Modbus Address<br />

(Base 0)<br />

00000<br />

00001<br />

00002<br />

00003<br />

00004<br />

00005<br />

10000<br />

10001<br />

10002<br />

10003<br />

10004<br />

10005<br />

DI Channel<br />

(Base 0)<br />

DI Channel<br />

(Base 0)<br />

10006<br />

10007<br />

10008<br />

10009<br />

10010<br />

10011<br />

543210 543210<br />

6 7 8 9<br />

1011<br />

DO Channel<br />

(Base 0)<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 111<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


� <strong>ET</strong>-7050 Counter Address Mapping<br />

Modbus Address<br />

(Base 0)<br />

30016<br />

30018<br />

30020<br />

30022<br />

30024<br />

30026<br />

Counter Channel<br />

(Base 0)<br />

Counter Channel<br />

30028<br />

30030<br />

30032<br />

30034<br />

30036<br />

30038<br />

(Base 0)<br />

543210<br />

6 7 8 9<br />

1011<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 112<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Detailed Modbus Address Table for <strong>ET</strong>-7050<br />

� (0xxxx) DO address<br />

Begin<br />

address<br />

Points Description Registers<br />

per Point<br />

Range Access<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 113<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com<br />

Type<br />

0 0~5 Digital Output 1 0=Off 1=On R/W<br />

32 1 Clear all DI latched status (high) 1 1=Clear W (Pulse)<br />

33 1 Clear all DI latched status (low) 1 1=Clear W (Pulse)<br />

34 0~5 Clear low speed (500Hz) digital<br />

counter<br />

150 1 Enable all DI latched status<br />

(high/low)<br />

151 0~5 Enable low speed (500Hz) digital<br />

counter<br />

231 1 Write DO Power on value to<br />

EEPROM<br />

1 1=Clear W (Pulse)<br />

1 0=Disable<br />

1=Enable<br />

(Default=0)<br />

1 0=Disable<br />

1=Enable<br />

(Default=0)<br />

R/W/E<br />

R/W/E<br />

1 1=Write W (Pulse)<br />

232 1 Write DO Safe value to EEPROM 1 1=Write W (Pulse)<br />

235 0~5 Power on value for DO 1 0=Off<br />

1=On<br />

267 0~5 Safe value for DO 1 0=Off<br />

(Default=0)<br />

1=On<br />

(Default=0)<br />

R/W/E<br />

R/W/E


� (1xxxx) DI address<br />

Begin<br />

address<br />

Points Description Registers<br />

per Point<br />

0 0~11 Digital Input 1 0=Off<br />

Range Access<br />

1=On<br />

32 0~11 Digital latched status (high) 1 0=no<br />

1=latched<br />

64 0~11 Digital latched status (low) 1 0=no<br />

� (3xxxx) AI address<br />

Begin<br />

address<br />

16 0~11<br />

Points Description<br />

Low speed (500Hz) digital<br />

counter<br />

Registers<br />

per Point<br />

� (3xxxx) AI address (Static Channel Number Value)<br />

Begin<br />

address<br />

Points Description<br />

1=latched<br />

Range<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 114<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com<br />

Type<br />

R<br />

R<br />

R<br />

Access<br />

Type<br />

2 0~4294967296 R<br />

Registers<br />

per Point<br />

Value<br />

100 1 DI (channel number) 1 12 R<br />

101 1 DI high/low latch (channel number) 1 12 R<br />

110 1 DO (channel number) 1 6 R<br />

111 1<br />

Power on value for DO (channel<br />

number)<br />

Access<br />

Type<br />

1 6 R<br />

112 1 Safe value for DO (channel number) 1 6 R<br />

121 1<br />

� (4xxxx) AO address<br />

Begin<br />

address<br />

Low speed counter (500Hz)<br />

(channel number)<br />

Points Description<br />

50 0~11<br />

Preset value for low speed (500Hz)<br />

digital counter<br />

Registers<br />

per Point<br />

2<br />

1 12 R<br />

Range<br />

0~429496729<br />

6 (Default=0)<br />

Access<br />

Type<br />

R/W/E


4.3.2.4. <strong>ET</strong>-7051/P<strong>ET</strong>-7051 I/O and Counter Address Mapping<br />

� <strong>ET</strong>-7051/P<strong>ET</strong>-7051 I/O Address Mapping<br />

Modbus Address<br />

(Base 0)<br />

00008<br />

00009<br />

00010<br />

00011<br />

00012<br />

DI Channel<br />

(Base 0)<br />

00000<br />

00001<br />

00002<br />

00003<br />

00004<br />

00005<br />

00006<br />

00007<br />

9 8<br />

10<br />

11<br />

12<br />

7 6 5 4 3 2 1 0<br />

00013<br />

00014<br />

00015<br />

13<br />

14<br />

15<br />

DI Channel<br />

(Base 0)<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 115<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


� <strong>ET</strong>-7051/P<strong>ET</strong>-7051 Counter Address Mapping<br />

Modbus Address<br />

(Base 0)<br />

Counter Channel<br />

(Base 0)<br />

30016<br />

30018<br />

30020<br />

30022<br />

30024<br />

30026<br />

30028<br />

30030<br />

30032<br />

30034<br />

30036<br />

30038<br />

30040<br />

30042<br />

30044<br />

30046<br />

9 8<br />

10<br />

11<br />

12<br />

7 6 5 4 3 2 1 0<br />

14<br />

15<br />

16<br />

Counter Channel<br />

(Base 0)<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 116<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Detailed Modbus Address Table for <strong>ET</strong>-7051/P<strong>ET</strong>-7051<br />

� (0xxxx) DO address<br />

Begin<br />

address<br />

Points Description<br />

Registers<br />

per Point<br />

Range<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 117<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com<br />

Access<br />

Type<br />

32 1 Clear all DI latched status (high) 1 1=Clear W (Pulse)<br />

33 1 Clear all DI latched status (low) 1 1=Clear W (Pulse)<br />

34 0~15<br />

150 1<br />

151 0~15<br />

Clear low speed (500Hz) digital<br />

counter<br />

Enable all DI latched status<br />

(high/low)<br />

Enable low speed (500Hz) digital<br />

counter<br />

� (1xxxx) DI address<br />

Begin<br />

address<br />

Points Description<br />

Registers<br />

per Point<br />

1 1=Clear W (Pulse)<br />

1<br />

1<br />

0=Disable<br />

1=Enable<br />

(Default=0)<br />

0=Disable<br />

1=Enable<br />

(Default=0)<br />

Range<br />

R/W/E<br />

R/W/E<br />

Access<br />

0 0~15 Digital Input 1 0=Off 1=On R<br />

32 0~15 Digital latched status (high) 1 0=no 1=latched R<br />

64 0~15 Digital latched status (low) 1 0=no 1=latched R<br />

Type


� (3xxxx) AI address<br />

Begin<br />

address<br />

16 0~15<br />

Points Description<br />

Low speed (500Hz) digital<br />

counter<br />

Registers<br />

per Point<br />

� (3xxxx) AI address (Static Channel Number Value)<br />

Begin<br />

address<br />

Points Description<br />

Range<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 118<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com<br />

Access<br />

Type<br />

2 0~4294967296 R<br />

Registers<br />

per Point<br />

Value<br />

Access<br />

100 1 DI (channel number) 1 16 R<br />

101 1<br />

121 1<br />

DI high/low latch (channel<br />

number)<br />

� (4xxxx) AO address<br />

Begin<br />

address<br />

50 0~15<br />

Low speed counter (500Hz)<br />

(channel number)<br />

Points Description<br />

Preset value for low<br />

speed (500Hz) digital<br />

counter<br />

Registers<br />

per Point<br />

2<br />

Type<br />

1 16 R<br />

1 16 R<br />

Range<br />

0~4294967296<br />

(Default=0)<br />

Access<br />

Type<br />

R/W/E


4.3.2.5. <strong>ET</strong>-7052/P<strong>ET</strong>-7052 I/O and Counter Address Mapping<br />

� <strong>ET</strong>-7052/P<strong>ET</strong>-7052 I/O Address Mapping<br />

Modbus Address<br />

(Base 0)<br />

00000<br />

00001<br />

00002<br />

00003<br />

00004<br />

00005<br />

00006<br />

00007<br />

10000<br />

10001<br />

10002<br />

DI Channel<br />

(Base 0)<br />

10003<br />

10004<br />

10005<br />

10006<br />

10007<br />

DI Channel<br />

(Base 0)<br />

2 1 0 7 6 5 4 3 2 1 0<br />

3 4 5 6 7<br />

DO Channel<br />

(Base 0)<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 119<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


� <strong>ET</strong>-7052/P<strong>ET</strong>-7052 Counter Address Mapping<br />

Modbus Address<br />

(Base 0)<br />

30016<br />

30018<br />

30020<br />

Counter Channel<br />

(Base 0)<br />

2 1 0<br />

Counter Channel<br />

30022<br />

30024<br />

30026<br />

30028<br />

30030<br />

(Base 0)<br />

3 4 5 6 7<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 120<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Detailed Modbus Address Table for <strong>ET</strong>-7052/P<strong>ET</strong>-7052<br />

� (0xxxx) DO address<br />

Begin<br />

address<br />

Points Description<br />

Registe<br />

rs per<br />

Point<br />

0 0~7 Digital Output 1<br />

Range<br />

0=Off<br />

1=On<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 121<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com<br />

Access<br />

Type<br />

32 1 Clear all DI latched status (high) 1 1=Clear W (Pulse)<br />

33 1 Clear all DI latched status (low) 1 1=Clear W (Pulse)<br />

34 0~7<br />

Clear low speed (500Hz) digital<br />

counter<br />

150 1 Enable all DI latched status (high/low) 1<br />

151 0~7<br />

Enable low speed (500Hz) digital<br />

counter<br />

R/W<br />

1 1=Clear W (Pulse)<br />

1<br />

0=Disable<br />

1=Enable<br />

(Default=0)<br />

0=Disable<br />

1=Enable<br />

(Default=0)<br />

R/W/E<br />

R/W/E<br />

231 1 Write DO Power on value to EEPROM 1 1=Write W (Pulse)<br />

232 1 Write DO Safe value to EEPROM 1 1=Write W (Pulse)<br />

235 0~7 Power on value for DO 1<br />

267 0~7 Safe value for DO 1<br />

0=Off<br />

1=On<br />

(Default=0)<br />

0=Off<br />

1=On<br />

(Default=0)<br />

R/W/E<br />

R/W/E


� (1xxxx) DI address<br />

Begin<br />

address<br />

Points Description<br />

Registers<br />

per Point<br />

0 0~7 Digital Input 1<br />

32 0~7 Digital latched status (high) 1<br />

64 0~7 Digital latched status (low) 1<br />

� (3xxxx) AI address<br />

Begin<br />

address<br />

16 0~7<br />

Points Description<br />

Low speed (500Hz) digital<br />

counter<br />

Registers<br />

per Point<br />

� (3xxxx) AI address (Static Channel Number Value)<br />

Begin<br />

address<br />

Points Description<br />

0=off<br />

1=on<br />

0=no<br />

Range<br />

1=latched<br />

0=no<br />

1=latched<br />

Range<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 122<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com<br />

Access<br />

Type<br />

R<br />

R<br />

R<br />

Access<br />

Type<br />

2 0~4294967296 R<br />

Registers<br />

per Point<br />

Value<br />

Access<br />

100 1 DI (channel number) 1 8 R<br />

101 1<br />

DI high/low latch (channel<br />

number)<br />

Type<br />

1 8 R<br />

110 1 DO (channel number) 1 8 R<br />

111 1<br />

112 1<br />

121 1<br />

Power on value for DO<br />

(channel number)<br />

Safe value for DO (channel<br />

number)<br />

� (4xxxx) AO address<br />

Begin<br />

address<br />

50 0~7<br />

Low speed counter (500Hz)<br />

(channel number)<br />

Points Description<br />

Preset value for low<br />

speed (500Hz) digital<br />

counter<br />

Registers<br />

per Point<br />

2<br />

1 8 R<br />

1 8 R<br />

1 8 R<br />

Range<br />

0~4294967296<br />

(default=0)<br />

Access<br />

Type<br />

R/W/E


4.3.2.6. <strong>ET</strong>-7053 I/O and Counter Address Mapping<br />

� <strong>ET</strong>-7053 I/O Address Mapping<br />

Modbus Address<br />

(Base 0)<br />

10000<br />

10001<br />

10002<br />

10003<br />

10004<br />

10005<br />

10006<br />

10007<br />

10008<br />

10009<br />

10010<br />

10011<br />

10012<br />

DI Channel<br />

(Base 0)<br />

DI Channel<br />

(Base 0)<br />

00013<br />

00014<br />

00015<br />

12<br />

11 10 9 8 7 6 5 4 3 2 1 0<br />

14<br />

15<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 123<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com<br />

13


� <strong>ET</strong>-7053 Counter Address Mapping<br />

Modbus Address<br />

(Base 0)<br />

30016<br />

30018<br />

30020<br />

30022<br />

30024<br />

30026<br />

30028<br />

30030<br />

30032<br />

30034<br />

30036<br />

30038<br />

30040<br />

Counter Channel<br />

(Base 0)<br />

Counter Channel<br />

(Base 0)<br />

30042<br />

30044<br />

30046<br />

12<br />

11 10 9 8 7 6 5 4 3 2 1 0<br />

14<br />

15<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 124<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com<br />

13


Detailed Modbus Address Table for <strong>ET</strong>-7053<br />

� (0xxxx) DO address<br />

Begin<br />

address<br />

Points Description<br />

Registers<br />

per Point<br />

32 1 Clear all DI latched status (high) 1 1=clear<br />

33 1 Clear all DI latched status (low) 1 1=clear<br />

34 0~15<br />

150 1<br />

151 0~15<br />

Clear low speed (500Hz) digital<br />

counter<br />

Enable all DI latched status<br />

(high/low)<br />

Enable low speed (500Hz) digital<br />

counter<br />

� (1xxxx) DI address<br />

Begin<br />

address<br />

Points Description<br />

1 1=clear<br />

Range<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 125<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com<br />

1<br />

1<br />

Registers<br />

per Point<br />

0=disable<br />

1=enable<br />

(default=0)<br />

0=disable<br />

1=enable<br />

(default=0)<br />

Range<br />

Access<br />

Type<br />

W<br />

(Pulse)<br />

W<br />

(Pulse)<br />

W<br />

(Pulse)<br />

R/W/E<br />

R/W/E<br />

Access<br />

0 0~15 Digital Input 1 0=off 1=on R<br />

32 0~15 Digital latched status (high) 1 0=no 1=latched R<br />

64 0~15 Digital latched status (low) 1 0=no 1=latched R<br />

� (3xxxx) AI address<br />

Begin<br />

address<br />

16 0~15<br />

Points Description<br />

Low speed (500Hz) digital<br />

counter<br />

Registers<br />

per Point<br />

Range<br />

Type<br />

Access<br />

Type<br />

2 0~4294967296 R


� (3xxxx) AI address (Static Channel Number Value)<br />

Begin<br />

address<br />

Points Description<br />

Registers<br />

per Point<br />

Value<br />

100 1 DI (channel number) 1 16 R<br />

101 1<br />

121 1<br />

DI high/low latch (channel<br />

number)<br />

� (4xxxx) AO address<br />

Begin<br />

address<br />

50 0~15<br />

Low speed counter (500Hz)<br />

(channel number)<br />

Points Description<br />

Preset value for low speed<br />

(500Hz) digital counter<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 126<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com<br />

Access<br />

Type<br />

1 16 R<br />

1 16 R<br />

Registers<br />

per Point<br />

2<br />

Range<br />

0~4294967296<br />

(default=0)<br />

Access<br />

Type<br />

R/W/E


4.3.2.7. <strong>ET</strong>-7060/P<strong>ET</strong>-7060 I/O and Counter Address Mapping<br />

� <strong>ET</strong>-7060/P<strong>ET</strong>-7060 I/O Address Mapping<br />

Modbus Address<br />

(Base 0)<br />

00000<br />

00001<br />

00002<br />

00003<br />

00004<br />

00005<br />

DO Channel<br />

(Base 0)<br />

10005<br />

10004<br />

10003<br />

10002<br />

10001<br />

10000<br />

5 4 3 2 1 0<br />

5 4 3 2 1 0<br />

DI Channel<br />

(Base 0)<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 127<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


� <strong>ET</strong>-7060/P<strong>ET</strong>-7060 Counter Address Mapping<br />

Counter Channel<br />

(Base 0)<br />

30026<br />

30024<br />

30022<br />

30020<br />

30018<br />

30016<br />

5 4 3 2 1 0<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 128<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Detailed Modbus Address Table for <strong>ET</strong>-7060<br />

� (0xxxx) DO address<br />

Begin<br />

address<br />

Points Description<br />

Registers<br />

per Point<br />

Range<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 129<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com<br />

Access<br />

Type<br />

0 0~5 Digital Output 1 0=off 1=on R/W<br />

32 1 Clear all DI latched status (high) 1 1=clear<br />

33 1 Clear all DI latched status (low) 1 1=clear<br />

34 0~5<br />

150 1<br />

151 0~5<br />

231 1<br />

Clear low speed (500Hz) digital<br />

counter<br />

Enable all DI latched status<br />

(high/low)<br />

Enable low speed (500Hz) digital<br />

counter<br />

Write DO Power on value to<br />

EEPROM<br />

1 1=clear<br />

1<br />

1<br />

0=disable<br />

1=enable<br />

(default=0)<br />

0=disable<br />

1=enable<br />

(default=0)<br />

1 1=write<br />

232 1 Write DO Safe value to EEPROM 1 1=write<br />

235 0~5 Power on value for DO 1<br />

267 0~5 Safe value for DO 1<br />

� (1xxx) DI address<br />

Begin<br />

address<br />

Points Description<br />

Registers<br />

per Point<br />

0 0~5 Digital Input 1<br />

32 0~5 Digital latched status (high) 1<br />

64 0~5 Digital latched status (low) 1<br />

0=off<br />

1=on<br />

(default=0)<br />

0=off<br />

1=on<br />

(default=0)<br />

0=off<br />

1=on<br />

0=no<br />

Range<br />

1=latched<br />

0=no<br />

1=latched<br />

W<br />

(Pulse)<br />

W<br />

(Pulse)<br />

W<br />

(Pulse)<br />

R/W/E<br />

R/W/E<br />

W<br />

(Pulse)<br />

W<br />

(Pulse)<br />

R/W/E<br />

R/W/E<br />

Access<br />

Type<br />

R<br />

R<br />

R


� (3xxx) AI address<br />

Begin<br />

address<br />

16 0~5<br />

Points Description<br />

Low speed (500Hz) digital<br />

counter<br />

Registers<br />

per Point<br />

� (3xxx) AI address (Static Channel Number Value)<br />

Begin<br />

address<br />

Points Description<br />

Range<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 130<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com<br />

Access<br />

Type<br />

2 0~4294967296 R<br />

Registers<br />

per Point<br />

Value<br />

Access<br />

100 1 DI (channel number) 1 6 R<br />

101 1<br />

DI high/low latch (channel<br />

number)<br />

Type<br />

1 6 R<br />

110 1 DO (channel number) 1 6 R<br />

111 1<br />

112 1<br />

121 1<br />

Power on value for DO<br />

(channel number)<br />

Safe value for DO (channel<br />

number)<br />

� (4xxx) AO address<br />

Begin<br />

address<br />

50 0~5<br />

Low speed counter (500Hz)<br />

(channel number)<br />

Points Description<br />

Preset value for low speed<br />

(500Hz) digital counter<br />

1 6 R<br />

1 6 R<br />

1 6 R<br />

Registers<br />

per Point<br />

2<br />

Range<br />

0~4294967296<br />

(default=0)<br />

Access<br />

Type<br />

R/W/E


4.3.2.8. <strong>ET</strong>-7065/P<strong>ET</strong>-7065 I/O and Counter Address Mapping<br />

� <strong>ET</strong>-7065/P<strong>ET</strong>-7065 I/O Address Mapping<br />

Modbus Address<br />

(Base 0)<br />

00000<br />

00001<br />

00002<br />

00003<br />

00004<br />

00005<br />

DO Channel<br />

(Base 0)<br />

DI Channel<br />

(Base 0)<br />

10005<br />

10004<br />

10003<br />

10002<br />

10001<br />

10000<br />

5 4 3 2 1 0<br />

5 4 3 2 1 0<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 131<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


� <strong>ET</strong>-7065/P<strong>ET</strong>-7065 Counter Address Mapping<br />

Counter Channel<br />

(Base 0)<br />

30016<br />

30018<br />

30020<br />

30022<br />

30024<br />

30026<br />

5 4 3 2 1 0<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 132<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Detailed Modbus Address Table for <strong>ET</strong>-7065/P<strong>ET</strong>-7065<br />

� (0xxxx) DO address<br />

Begin<br />

addres<br />

s<br />

Points Description Register<br />

s per<br />

Point<br />

0 0~5 Digital Output 1 0=off<br />

1=on<br />

32 1 Clear all DI latched status<br />

(high)<br />

33 1 Clear all DI latched status<br />

(low)<br />

34 0~5 Clear low speed (500Hz)<br />

digital counter<br />

150 1 Enable all DI latched status<br />

(high/low)<br />

151 0~5 Enable low speed (500Hz)<br />

digital counter<br />

231 1 Write DO Power on value to<br />

EEPROM<br />

232 1 Write DO Safe value to<br />

EEPROM<br />

Range Access<br />

Type<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 133<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com<br />

R/W<br />

1 1=clear W<br />

(Pulse)<br />

1 1=clear W<br />

(Pulse)<br />

1 1=clear W<br />

(Pulse)<br />

1 0=disable<br />

1=enable<br />

R/W/E<br />

(default=0)<br />

1 0=disable<br />

1=enable<br />

(default=0)<br />

R/W/E<br />

1 1=write W<br />

(Pulse)<br />

1 1=write W<br />

(Pulse)<br />

235 0~5 Power on value for DO 1 0=off<br />

1=on<br />

(default=0)<br />

267 0~5 Safe value for DO 1 0=off<br />

1=on<br />

� (1xxxx) DI address<br />

Begin<br />

addres<br />

s<br />

Points Description<br />

Registers<br />

per Point<br />

(default=0)<br />

Range<br />

R/W/E<br />

R/W/E<br />

Access<br />

Type<br />

0 0~5 Digital Input 1 0=off 1=on R<br />

32 0~5<br />

Digital latched status<br />

(high)<br />

1<br />

0=no<br />

1=latched<br />

R


64 0~5 Digital latched status (low) 1<br />

� (3xxxx) AI address<br />

Begin<br />

addres<br />

s<br />

Points Description Registers<br />

per Point<br />

16 0~5 Low speed (500Hz)<br />

digital counter<br />

� (3xxxx) AI address (Static Channel Number Value)<br />

Begin<br />

address<br />

Points Description<br />

0=no<br />

1=latched<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 134<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com<br />

R<br />

Range Access<br />

Type<br />

2 0~4294967296 R<br />

Registers<br />

per Point<br />

Value<br />

Access<br />

100 1 DI (channel number) 1 8 R<br />

101 1<br />

DI high/low latch (channel<br />

number)<br />

Type<br />

1 8 R<br />

110 1 DO (channel number) 1 8 R<br />

111 1<br />

112 1<br />

121 1<br />

Power on value for DO<br />

(channel number)<br />

Safe value for DO (channel<br />

number)<br />

� (4xxxx) AO address<br />

Begin<br />

address<br />

50 0~5<br />

Low speed counter (500Hz)<br />

(channel number)<br />

Points Description<br />

Preset value for low<br />

speed (500Hz) digital<br />

counter<br />

Registers<br />

per Point<br />

2<br />

1 8 R<br />

1 8 R<br />

1 8 R<br />

Range<br />

0~4294967296<br />

(default=0)<br />

Access<br />

Type<br />

R/W/E


4.3.2.9. <strong>ET</strong>-7066/P<strong>ET</strong>-7066 I/O Address Mapping<br />

Modbus Address<br />

(Base 0)<br />

00000<br />

00001<br />

00002<br />

00003<br />

00004<br />

00005<br />

DO Channel<br />

(Base 0)<br />

DO Channel<br />

(Base 0)<br />

10006<br />

10007<br />

5 4 3 2 1 0<br />

6 7<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 135<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Detailed Modbus Address Table for <strong>ET</strong>-7066/P<strong>ET</strong>-7066<br />

� (0xxxx) DO address<br />

Begin<br />

address<br />

Points Description<br />

Registers<br />

per Point<br />

Range<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 136<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com<br />

Access<br />

Type<br />

0 0~7 Digital Output 1 0=off 1=on R/W<br />

231 1<br />

232 1<br />

Write DO Power on value to<br />

EEPROM<br />

Write DO Safe value to<br />

EEPROM<br />

235 0~7 Power on value for DO 1<br />

267 0~7 Safe value for DO 1<br />

� (3xxxx) AI address (Static Channel Number Value)<br />

Begin<br />

address<br />

Points Description<br />

1 1=write W (Pulse)<br />

1 1=write W (Pulse)<br />

Registers<br />

per Point<br />

0=off<br />

1=on<br />

(default=0)<br />

0=off<br />

1=on<br />

(default=0)<br />

Value<br />

R/W/E<br />

R/W/E<br />

Access<br />

110 1 DO (channel number) 1 8 R<br />

111 1<br />

112 1<br />

Power on value for DO<br />

(channel number)<br />

Safe value for DO (channel<br />

number)<br />

Type<br />

1 8 R<br />

1 8 R


4.3.2.10. <strong>ET</strong>-7067/P<strong>ET</strong>-7067 I/O Address Mapping<br />

Modbus Address<br />

(Base 0)<br />

00000<br />

00001<br />

00002<br />

00003<br />

00004<br />

00005<br />

DO Channel<br />

(Base 0)<br />

DO Channel<br />

(Base 0)<br />

10006<br />

10007<br />

5 4 3 2 1 0<br />

6 7<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 137<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Detailed Modbus Address Table for <strong>ET</strong>-7067/P<strong>ET</strong>-7067<br />

� (0xxxx) DO address<br />

Begin<br />

address<br />

Points Description<br />

Registers<br />

per Point<br />

Range<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 138<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com<br />

Access<br />

Type<br />

0 0~7 Digital Output 1 0=off 1=on R/W<br />

231 1<br />

232 1<br />

Write DO Power on value to<br />

EEPROM<br />

Write DO Safe value to<br />

EEPROM<br />

235 0~7 Power on value for DO 1<br />

267 0~7 Safe value for DO 1<br />

� (3xxxx) AI address (Static Channel Number Value)<br />

Begin<br />

address<br />

Points Description<br />

1 1=write W (Pulse)<br />

1 1=write W (Pulse)<br />

Registers<br />

per Point<br />

0=off<br />

1=on<br />

(default=0)<br />

0=off<br />

1=on<br />

(default=0)<br />

Value<br />

R/W/E<br />

R/W/E<br />

Access<br />

110 1 DO (channel number) 1 8 R<br />

111 1<br />

112 1<br />

Power on value for DO<br />

(channel number)<br />

Safe value for DO (channel<br />

number)<br />

Type<br />

1 8 R<br />

1 8 R


5. MiniOS7 Utility Tool<br />

MiniOS7 Utility is a tool for uploading firmware to flash memory and updating the OS<br />

to <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> module embedded with <strong>ICP</strong> <strong>DAS</strong> MiniOS7 with easiness and<br />

quickness.<br />

If you don‘t have the MiniOS7 Utility installed on your system, installation of the<br />

MiniOS7 Utility should be the first step. Please refer to section ―2.4. Installing the<br />

MiniOS7 Utility‖ to install it.<br />

5.1. Establishing a Connection<br />

To upload firmware or update the OS to <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> module, you must first<br />

establish a connection between PC and the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> module.<br />

Step 1: Run the MiniOS7 Utility<br />

Double-click the MiniOS7 Utility shortcut on your desktop.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 139<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Step 2: Press “F12” or choose “Search” from the “Connection”<br />

menu<br />

After pressing F12 or choosing Search from Connection menu, that will<br />

search all of the MiniOS7 modules on your network.<br />

See the status tip, waiting<br />

for the search to be done.<br />

Step 3: Double-Click the field of your <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> module<br />

Double-Click the field of<br />

your <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong><br />

module in the list to connect<br />

to your <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong>.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 140<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Step 4: The connection has ready been established<br />

Check the connection status in the top right side to make sure the connection<br />

has been established<br />

Connection Status<br />

Disconnected<br />

Connected<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 141<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


5.2. Exchanging the Protocol (TCP/IP to UDP)<br />

MiniOS7 Utility supports both UDP and TCP protocols.<br />

For MiniOS7 Utility, the TCP/IP is the default protocol for communicating with<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong>, and the UDP is used to update the OS. Therefore, if you want to<br />

update the OS, you might need to change protocols to support them.<br />

Step 1: Establish a connection to <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong><br />

For more detailed about this process, please refer to section ―5.1. Establishing<br />

a Connection‖ to establish a connection.<br />

Step 2: Right Click the file list of the right side window, and then<br />

choose “Quit Firmware” to stop the firmware running<br />

Right click the file list of the right side windows, and then choose Quit<br />

Firmware to stop the firmware running and exchange TCP/IP protocol to UDP<br />

protocol.<br />

Right Click the file list<br />

Step 3:<br />

Click “Yes” to continue<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 142<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


After executing the Quick Firmware command, the Confirm dialog will appear,<br />

and then click Yes button to continue and stop the firmware running.<br />

Step 4: Click “Yes” to continue<br />

After confirming the command, the Confirm dialog will appear, and then click<br />

Yes button to exchange UDP protocol for TCP protocol.<br />

Step 5: The changes have been affected<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 143<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


5.3. Updating the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> OS<br />

<strong>ICP</strong> <strong>DAS</strong> will continue to add additional features to <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> OS in the<br />

future, so we advise you to periodically check the <strong>ICP</strong> <strong>DAS</strong> web site for the latest<br />

updates.<br />

Step 1: Get the latest version of the MiniOS7 OS image<br />

The latest version of the MiniOS7 OS image can be obtained from:<br />

CD:\NAPDOS\<strong>ET</strong><strong>7000</strong>\OS_image\<br />

<strong>ET</strong>7K_UDP_YYYYMMDD.img<br />

http://ftp.icpdas.com/pub/cd/6000cd/napdos/et<strong>7000</strong>/os_image/<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 144<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Step 2: Turn the switch to “Init” position<br />

Turn the Init/Normal switch to Init position.<br />

Step 3: Establish a connection to <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong><br />

For more detailed about this process, please refer to section ―5.1. Establishing<br />

a Connection‖ to establish a connection.<br />

Step 4: Exchange the protocol<br />

For more detailed about this process, please refer to section ―5.2. Exchanging<br />

the Protocol (TCP/IP to UDP)‖ to exchange the protocol.<br />

Init<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 145<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Step 5: Choose “Update MiniOS7 Image” from the “File” menu<br />

After exchanging the protocol, then choose Update MiniOS7 Image from File<br />

menu to start the update procedure.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 146<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Step 6: Select the latest version of the MiniOS7 OS image<br />

After choosing the update MiniOS7 Image command, the Select MiniOS7<br />

Image file will appear, and then select the latest version of the MiniOS7 OS<br />

image.<br />

Step 7: Click “OK” to finish the procedure<br />

After confirming the command, you just need to wait awhile until the following<br />

dialog appear, and then click OK button to finish the procedure.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 147<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Step 8: Restart the MiniOS7 Utility, and then exchange the protocol<br />

to UDP<br />

You may need to restart the MiniOS7 Utility for refreshing the settings, and<br />

then exchanging the protocol to UPD<br />

For more detailed about this process, please refer to section ―5.2. Exchanging<br />

the Protocol (TCP/IP to UDP)‖ to exchange the protocol.<br />

Step 9: Press “F7” or choose “Info” from the “Command” menu to<br />

check the OS version<br />

After pressing F7 or choosing info from Command menu to check the OS<br />

version.<br />

Check the Build item<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 148<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


5.4. Uploading the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> Firmware<br />

The firmware is stored in flash memory and can be updated to fix functionality issues<br />

or add additional features, so we advise you to periodically check the <strong>ICP</strong> <strong>DAS</strong> web<br />

site for the latest updates.<br />

Step 1: Get the latest version of the MiniOS7 firmware and the<br />

autoexec.bat file<br />

The latest version of the MiniOS7 firmware and autoexec.bat file can be<br />

obtained from:<br />

CD:\NAPDOS\<strong>ET</strong><strong>7000</strong>\Firmware\<br />

<strong>ET</strong>7026_VXXX.HEX<br />

http://ftp.icpdas.com/pub/cd/6000cd/napdos/et<strong>7000</strong>/Firmware/<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 149<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Step 2: Turn the switch to “Init” position<br />

Turn the Init/Normal switch to Init position.<br />

Step 3: Establish a connection to <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong><br />

For more detailed about this process, please refer to section ―5.1. Establishing<br />

a Connection‖ to establish a connection.<br />

Init<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 150<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Step 4: Choose “Erase Disk” from the “Command” menu<br />

After establishing a connection, then choose Erase Disk from Command<br />

menu to erase the contents of the flash memory.<br />

Tips & Warnings<br />

You have to delete all files existed on the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> before<br />

uploading the firmware.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 151<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Step 5: Click “Yes” to continue<br />

After executing the Erase Disk command, the Confirm dialog will appear, and<br />

then click Yes button to continue erasing the memory contents.<br />

Step 6: Select the latest version of the MiniOS7 firmware and<br />

autoexec.bat file<br />

After confirming the command, all files of the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> will be<br />

deleted Select MiniOS7 Image file will appear, and then select the latest<br />

version of the MiniOS7 OS image.<br />

Drag-and-Drop<br />

Step 7: Click OK to finish and restart the MiniOS7 Utility<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 152<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


After confirming the command, you just need to wait awhile until the following<br />

dialog appear, and then click OK button to finish the procedure.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 153<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


6. External Tools and Tasks<br />

6.1. LabVIEW<br />

LabVIEW is the best way to acquire, analyze, and present data. LabVIEW delivers a<br />

graphical development environment that can be used to quickly build data acquisition<br />

quickly, instrumentation and control systems, boosting productivity and saving<br />

development time. With LabVIEW, it is possible to quickly create user interfaces that<br />

enable interactive control of software systems. To specify your system functionality,<br />

simply assemble block diagram – a natural design notation for scientists and<br />

engineers.<br />

The document containing the detailed instructions for linking to the<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> using the Modbus protocol is located on the shipped<br />

CD:\NAPDOS\P<strong>ET</strong><strong>7000</strong>_<strong>ET</strong><strong>7000</strong>\Document\Application\LabVIEW\ or<br />

ftp://ftp.icpdas.com/pub/cd/6000cd/napdos/pet<strong>7000</strong>_et<strong>7000</strong>/document/application/lab<br />

view/<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 154<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


6.2. OPC Server<br />

OPC (OLE for Process Control) is the first standard resulting from the collaboration of<br />

a number of leading worldwide automation suppliers working in cooperation with<br />

Microsoft. Originally based on Microsoft's OLE COM (Component Object Model) and<br />

DCOM (Distributed Component Object Model) technologies, the specification defines<br />

a standard set of objects, interfaces and methods for use in process control and<br />

manufacturing automation applications to facilitate interoperability.<br />

There are many different mechanisms provided by various vendors that allow access<br />

to a variety of devices via specific applications. However, if an OPC server is provided<br />

for the device, other applications will be able to access the OPC Server via the OPC<br />

interface.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 155<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


6.3. SCADA<br />

SCADA stands for Supervisor Control and Data Acquisition. It is a production<br />

automation and control system based on PCs<br />

SCADA is wildly used in many fields e.g. power generation, water systems, the oil<br />

industry, chemistry, the automobile industry. Different fields require different functions,<br />

but they all have the common features:<br />

� Graphic interface<br />

� Process mimicking<br />

� Real time and historic trend data<br />

� Alarm system<br />

� Data acquisition and recording<br />

� Data analysis<br />

� Report generator<br />

� Accessing <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> module<br />

SCADA software is able to access <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> devices using Modbus<br />

communication protocols, and can communicate without the need for other<br />

software drivers.<br />

� Famous SCADA software<br />

Citect, ICONICS, iFIX, InduSoft, Intouch, Entivity Studio, Entivity Live, Entivity<br />

VLC, Trace Mode, Wizcon, Wonderware ... etc<br />

In the following sections 3 popular brands of SCADA software are introduced<br />

together with the detailed instructions in how use them to communicate with<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> series module using the Modbus/TCP protocol.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 156<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


6.3.1. InduSoft<br />

InduSoft Web Studio is a powerful, integrated<br />

collection of automation tools that includes all<br />

the building blocks needed to develop modern<br />

Human Machine Interfaces (HMI), Supervisory<br />

Control and Data Acquisition (SCADA)<br />

systems, and embedded instrumentation and<br />

control applications. InduSoft Web<br />

Studio‘s application runs in native<br />

Windows NT, 2000, XP, CE and<br />

CE .N<strong>ET</strong> environments and<br />

conforms to industry standards<br />

such as Microsoft .N<strong>ET</strong>, OPC, DDE,<br />

ODBC, XML, and ActiveX.<br />

The document containing detailed instructions for linking to the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong><br />

module using the Modbus protocol is located on the shipped<br />

CD:\NAPDOS\P<strong>ET</strong><strong>7000</strong>_<strong>ET</strong><strong>7000</strong>\Document\Application\InduSoft\<br />

ftp://ftp.icpdas.com/pub/cd/6000cd/napdos/pet<strong>7000</strong>_et<strong>7000</strong>/document/application/ind<br />

usoft/<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 157<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


6.3.2. Citect<br />

CitectSCADA is a fully integrated<br />

Human Machine Interface (HMI) /<br />

SCADA solution that enables<br />

users to increase return on assets<br />

by delivering a highly scalable,<br />

reliable control and monitoring<br />

system. Easy-to-use configuration<br />

tools and powerful features enable<br />

rapid development and<br />

deployment of solutions for any<br />

size application.<br />

The document containing detailed instructions for linking to the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong><br />

module using the Modbus protocol is located on the shipped<br />

CD:\NAPDOS\P<strong>ET</strong><strong>7000</strong>_<strong>ET</strong><strong>7000</strong>\Document\Application\Citect\<br />

ftp://ftp.icpdas.com/pub/cd/6000cd/napdos/pet-<strong>7000</strong>_et<strong>7000</strong>/document/application/cit<br />

ect/<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 158<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


6.3.3. iFix<br />

The document containing detailed instructions for linking to the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong><br />

module using the Modbus protocol is located on the shipped<br />

CD:\NAPDOS\P<strong>ET</strong><strong>7000</strong>_<strong>ET</strong><strong>7000</strong>\Document\Application\iFix\<br />

ftp://ftp.icpdas.com/pub/cd/6000cd/napdos/pet<strong>7000</strong>_et<strong>7000</strong>/document/application/ifix<br />

/<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 159<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Appendix A. Node Information Area<br />

Each <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> module has a built-in EEPROM to store configuration<br />

information such as IP address, type code, etc. One minor drawback is that there are<br />

no visual indications of the configuration of the module. New <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong><br />

modules include node information areas that are protected by a cover, as shown<br />

below, and can be used to make a written record of the node information, such as IP<br />

address, etc. To access the node information areas, first slide the covers outward, as<br />

shown in the figure below.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 160<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Appendix B. Modbus Application Notes<br />

B.1. Dual Watchdog<br />

Dual Watchdog consists of Module Watchdog and Host Watchdog.<br />

1. The Module Watchdog is a built-in hardware circuit that will reset the CPU module if<br />

a failure occurs in either the hardware or the software. If the application does not<br />

refresh the watchdog timer within 0.8 seconds, the watchdog circuit will initiate a<br />

reset of the CPU.<br />

2. The Host Watchdog is a<br />

software function that can<br />

be used to monitor the<br />

operating status of the<br />

host. Its purpose is to<br />

prevent network<br />

communication problems<br />

or a host failure. If the<br />

Watchdog timeout interval<br />

expires, the module will<br />

return all outputs to a<br />

predefined Safe value<br />

(Refer to the Safe Value<br />

application note), which<br />

can prevent the controlled<br />

target from unexpected<br />

situation.<br />

AO address 40557 of the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> series Modbus register is the address of<br />

the Host Watchdog timer, and will be stored into EEPROM. The WDT function will be<br />

disabled if the value is set to less than 5 seconds.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 161<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


B.2. Power ON Value<br />

If the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> series module is reset, the output of the module is set to the<br />

predefined Power ON Value for the DO and AO channels. DO address 00435 of the<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> series Modbus register is the first address of the Power ON value,<br />

and the total number of channels depend on the type of module.<br />

For example:<br />

Addresses 00435 to 00438 records the Power ON value for the 4-Channel<br />

<strong>ET</strong>-7017/P<strong>ET</strong>-7017.<br />

Be careful to set the ON value to DO address 00431 to write the DO Power ON value<br />

to the EEPROM of the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> DO module after using Modbus commands<br />

(05 or 15) to change the Power ON value.<br />

Configuration via Web page<br />

Browse to the homepage of the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong>, and click the ―Modbus I/O<br />

Settings‖ link in the Configuration Section of the Main Menu tree.<br />

Click the ON/OFF radio box to set the power ON/OFF value and then click the button<br />

to enable the settings to take effect.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 162<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


B.3. Safe Value<br />

If the time of the Host PC losing Modbus/TCP communication with the module is<br />

greater than the host WatchDog timer setting (called WDT timeout), the output of the<br />

Digital and Analog channels is set to the Safe Value, and the count of the host WDT<br />

events is increased by one.<br />

AO address 40558 is the address of the Host WDT events. The value of the WDT<br />

events will be not stored into EEPROM, and will return to 0 after the module is<br />

rebooted. DO address 00515 is the first address of the Safe value and the total<br />

number of channels depends on the type of module.<br />

For example:<br />

Address 00515 to 00518 records the Safe value for the 4-Channel<br />

<strong>ET</strong>-7017/P<strong>ET</strong>-7017.<br />

Be careful to set the ON value to DO address 00432 to write the DO Safe value to the<br />

EEPROM of the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> DO module after using Modbus commands (05 or<br />

15) to change the Power ON value.<br />

While the WDT timeout is set, the module can also receive the Modbus/TCP<br />

commands (05, 06, 15 and 16) to change the DO or AO value without needing to clear<br />

the host watchdog timeout value.<br />

Configuration via Web page<br />

Browse to the homepage of the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong>, and click the ―Modbus I/O<br />

Settings‖ link in the Configuration Section of the Main Menu tree.<br />

Click the ON/OFF radio box to set the Safe value and then click the button<br />

to enable the settings to take effect.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 163<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


B.4. AI High/Low Alarm<br />

<strong>ET</strong>-7017/P<strong>ET</strong>-7017 and <strong>ET</strong>-7017-10 module equip with the High/Low Alarm function.<br />

When the alarm function is enabled, the specified registers are the alarm indicator.<br />

The alarm function is to compare the analog input value with given high alarm value<br />

and low alarm value.<br />

Address 00636 to 00667 can be used to enable/disable the AI High Alarm function.<br />

Address 00668 to 00699 can be used enable/disable the AI Low Alarm function.<br />

� <strong>ET</strong>-7017/P<strong>ET</strong>-7017 AI High/Low Alarm Switch Table<br />

Channel<br />

Number<br />

AI High Alarm AI Low Alarm<br />

Register Description Register Description<br />

AI0 00636 0: Disable/1: Enable 00668 0: Disable/1: Enable<br />

AI1 00637 0: Disable/1: Enable 00669 0: Disable/1: Enable<br />

AI2 00638 0: Disable/1: Enable 00670 0: Disable/1: Enable<br />

AI3 00639 0: Disable/1: Enable 00671 0: Disable/1: Enable<br />

AI4 00640 0: Disable/1: Enable 00672 0: Disable/1: Enable<br />

AI5 00641 0: Disable/1: Enable 00673 0: Disable/1: Enable<br />

AI6 00642 0: Disable/1: Enable 00674 0: Disable/1: Enable<br />

AI7 00643 0: Disable/1: Enable 00675 0: Disable/1: Enable<br />

AI8 00644 0: Disable/1: Enable 00676 0: Disable/1: Enable<br />

AI9 00645 0: Disable/1: Enable 00677 0: Disable/1: Enable<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 164<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Address 40296 to 40327 records the High Alarm value. Address 40328 to 40359<br />

records the Low Alarm value. By the default, the High Alarm value is 32767 and the<br />

Low Alarm value is -32768.<br />

� <strong>ET</strong>-7017/P<strong>ET</strong>-7017 AI High/Low Alarm Value Table<br />

Channel<br />

Number<br />

High Alarm Value of AI Low Alarm Value of AI<br />

Register Description Register Description<br />

AI0 40296 -32768 ~ 32767 40328 -32768 ~ 32767<br />

AI1 40297 -32768 ~ 32767 40329 -32768 ~ 32767<br />

AI2 40298 -32768 ~ 32767 40330 -32768 ~ 32767<br />

AI3 40299 -32768 ~ 32767 40331 -32768 ~ 32767<br />

AI4 40270 -32768 ~ 32767 40332 -32768 ~ 32767<br />

AI5 40271 -32768 ~ 32767 40333 -32768 ~ 32767<br />

AI6 40272 -32768 ~ 32767 40334 -32768 ~ 32767<br />

AI7 40273 -32768 ~ 32767 40335 -32768 ~ 32767<br />

AI8 40274 -32768 ~ 32767 40336 -32768 ~ 32767<br />

AI9 40275 -32768 ~ 32767 40337 -32768 ~ 32767<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 165<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


The analog input High/Low Alarm contains two alarm types, Momentary Alarm and<br />

Latch Alarm. Address 00700 of Modbus register can be used to set the High Alarm<br />

type of channel 0 and the total number of channels depends on the type of module.<br />

Address 00732 of Modbus register can be used to set the Low Alarm type of channel<br />

0.<br />

� <strong>ET</strong>-7017/P<strong>ET</strong>-7017 AI High/Low Type Value Table<br />

Channel<br />

Number<br />

AI0 00700<br />

AI1 00701<br />

AI2 00702<br />

AI3 00703<br />

AI4 00704<br />

AI5 00705<br />

AI6 00706<br />

AI7 00707<br />

AI8 00708<br />

AI9 00709<br />

AI High Alarm Type AI Low Alarm Type<br />

Register Description Register Description<br />

0: Momentary Alarm<br />

1: Latch Alarm<br />

0: Momentary Alarm<br />

1: Latch Alarm<br />

0: Momentary Alarm<br />

1: Latch Alarm<br />

0: Momentary Alarm<br />

1: Latch Alarm<br />

0: Momentary Alarm<br />

1: Latch Alarm<br />

0: Momentary Alarm<br />

1: Latch Alarm<br />

0: Momentary Alarm<br />

1: Latch Alarm<br />

0: Momentary Alarm<br />

1: Latch Alarm<br />

0: Momentary Alarm<br />

1: Latch Alarm<br />

0: Momentary Alarm<br />

1: Latch Alarm<br />

00732<br />

The following are the descriptions for two alarm types.<br />

00733<br />

00734<br />

00735<br />

00736<br />

00737<br />

00738<br />

00739<br />

00740<br />

00741<br />

0: Momentary Alarm<br />

1: Latch Alarm<br />

0: Momentary Alarm<br />

1: Latch Alarm<br />

0: Momentary Alarm<br />

1: Latch Alarm<br />

0: Momentary Alarm<br />

1: Latch Alarm<br />

0: Momentary Alarm<br />

1: Latch Alarm<br />

0: Momentary Alarm<br />

1: Latch Alarm<br />

0: Momentary Alarm<br />

1: Latch Alarm<br />

0: Momentary Alarm<br />

1: Latch Alarm<br />

0: Momentary Alarm<br />

1: Latch Alarm<br />

0: Momentary Alarm<br />

1: Latch Alarm<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 166<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


� Momentary Alarm<br />

The alarm status is cleared while the analog input is not exceeding the alarm value.<br />

For example:<br />

If analog input value of channel 0 (30001) > High Alarm value (40296), the address<br />

00764 is 1, else it is 0.<br />

If analog input Value of channel 0 (30001) < Low Alarm value (40328), the address<br />

00796 is 1, else it is 0.<br />

The address 00764 to 00795 is the High alarm indicator. If a High alarm occurred,<br />

the value of register is 1. In normal condition, it will be 0. The address 00796 to<br />

00827 is the Low alarm indicator. If a Low alarm occurred, the value of register is 1.<br />

In normal condition, it will be 0.<br />

� Latch Alarm<br />

When the Latch Alarm mode is enabled, the register stays latched until the specified<br />

registers are cleared.<br />

For example:<br />

If analog input value of channel 0 (30001) > High Alarm value (40296), the address<br />

00764 is 1, else if analog input value of channel 0 (30001) < Low Alarm value<br />

(40328), the address 00796 is 1.<br />

The address 00764 to 00795 is the High alarm indicator. In normal condition, the<br />

value of register is 0. If a High alarm occurred, the value of register stays 1 until the<br />

address 00764 to 00795 is cleared. The address 00796 to 00827 is the Low alarm<br />

indicator. In normal condition, the value of register is 0. If a Low alarm occurred, the<br />

value of register stays 1 until the address 00796 to 00827 is cleared.<br />

The address 00764 to 00795 can be used to clear the High Latch Alarm. The<br />

address 00796 to 00827 can be used to clear the Low Latch Alarm.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 167<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Configuration via Web page<br />

Browse to the homepage of the <strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong>, and click the ―Modbus I/O<br />

Settings‖ link in the Configuration Section of the Main Menu tree.<br />

View the Power ON/Safe Value via Web page<br />

Click the ―Web HMI‖ link in the Web HMI Section of the Main Menu tree.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 168<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


B.5. AI High/Low Latch<br />

The address 30236 to 30267 records the maximum value of analog inputs and stays<br />

the value until another maximum input enters. The address 30268 to 30299 records<br />

the minimum value of analog inputs and stays the value until another minimum input<br />

enters.<br />

View the Power ON/Safe Value via Web page<br />

Click the ―Web HMI‖ link in the Web HMI Section of the Main Menu tree.<br />

Moving average value of one AI channel<br />

AI<br />

VAve_n=(Vn+Vn-1+Vn-1+Vn-3+…+Vn-6) / 7 (7: 7 records)<br />

The average value of each AI can be reached on a regular interval when the moving<br />

average function is enabled.<br />

For example, a five-item simple moving average would be the sum of the reading<br />

value of the five most recent reading value, divided by five; a 20-item moving average<br />

would be the sum of the 20 most recent reading value divided by 20, and so on. Each<br />

item the most recent reading value is added to the equation and the most distant item<br />

is dropped off.<br />

Vn-6 Vn-5 Vn-4<br />

Vn-3 Vn-2 Vn-1<br />

Tn-6 Tn-5 Tn-4 Tn-3 Tn-2 Tn-1 Tn<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 169<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com<br />

Vn<br />

Time


Register Description<br />

00347<br />

40059<br />

Enable the moving value of the AI channels<br />

0=Disabled<br />

1=Enabled<br />

(Default=0)<br />

Average times for each AI channel<br />

0 ~ 40<br />

Address 30144 to 30153 recodes the average value of each AI channel.<br />

� <strong>ET</strong>-7017/P<strong>ET</strong>-7017 Average value of one channel Table<br />

Channel<br />

Number<br />

Register Description<br />

AI0 30144 0 ~65535 or –32768 ~ +32767<br />

AI1 30145 0 ~65535 or –32768 ~ +32767<br />

AI2 30146 0 ~65535 or –32768 ~ +32767<br />

AI3 30147 0 ~65535 or –32768 ~ +32767<br />

AI4 30148 0 ~65535 or –32768 ~ +32767<br />

AI5 30149 0 ~65535 or –32768 ~ +32767<br />

AI6 30150 0 ~65535 or –32768 ~ +32767<br />

AI7 30151 0 ~65535 or –32768 ~ +32767<br />

AI8 30152 0 ~65535 or –32768 ~ +32767<br />

AI9 30153 0 ~65535 or –32768 ~ +32767<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 170<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Average value of all AI channel<br />

The value of all AI channel is obtained on a regular interval. The average of AI<br />

channels can be reached and then stored in the specified registers.<br />

Register Description<br />

00348<br />

30176<br />

AI0<br />

AI1<br />

AI2<br />

AIn<br />

Enable the average value of all enabled channels, High/Low Alarm<br />

value of all AI average value and Average Latched values.<br />

0=Disabled<br />

1=Enabled<br />

(Default=0)<br />

Average value of all enabled AI channel. Address 00595~00626 is<br />

used to enable/disable the AI channel.<br />

0 ~ 65535 or –32768 ~ +32767<br />

V0<br />

T0<br />

V1<br />

V2<br />

Vn<br />

VAve_all=(V0+V1+V2+V3+…+Vn) / n (n: n records)<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 171<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com<br />

Time<br />

Time<br />

Time<br />

Time


High/Low Alarm of the average value of all AI channels<br />

The average value of all AI channels also can equip with the alarm function like the AI<br />

High/Low Alarm. For the detailed description, please refer the AI High/Low Alarm.<br />

Register Description<br />

10336<br />

10337<br />

40198<br />

40199<br />

High alarm for the average value of all AI registers<br />

0=normal<br />

1=alarm<br />

Low alarm for the average value of all AI registers<br />

0=normal<br />

1=alarm<br />

High alarm value for Average value of all AI channels<br />

0 ~ 65535 or –32768 ~ +32767<br />

Low alarm value for Average value of all AI channels<br />

0 ~ 65535 or –32768 ~ +32767<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 172<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com


Appendix C. Troubleshooting<br />

A number of common problems are easy to diagnose and fix if you know the cause.<br />

Symptom/Problem Possible cause Solution<br />

The Run LED doesn‘t light Internal power has failed Return the module for repair.<br />

The Run LED indicator is<br />

ON (light), but not flashing.<br />

Cannot communicate via<br />

the Ethernet port, but the<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> is still<br />

operating.<br />

Able to explore the web<br />

page through port 80 using<br />

a web browser, but the Web<br />

HMI and Modbus/TCP<br />

program cannot access the<br />

module through port 502.<br />

The Web HMI and<br />

Modbus/TCP program can<br />

access the module through<br />

port 502, but Web browser<br />

cannot explore the web<br />

page through port 80 using<br />

a web browser.<br />

The module has possibly<br />

crashed.<br />

The IP/Mask/Gateway<br />

address isn‘t within the IP<br />

address range of the<br />

LAN.<br />

The IP address has<br />

restricted by the IP filter<br />

settings<br />

There are more than 30<br />

TCP/IP connections.<br />

Port 502 has been<br />

restricted by the firewall.<br />

The Port 502 has<br />

restricted by the firewall.<br />

The Web Configuration<br />

function has been<br />

disabled. (Shown on the<br />

Basic Settings page)<br />

The Web server TCP port<br />

has been changed from<br />

port 80 (Shown on the<br />

Basic Settings page)<br />

Reboot the module<br />

Change the<br />

IP/Mask/Gateway address to<br />

match the LAN, or ask the<br />

MIS administrator for<br />

assistance.<br />

Check the IP filter setting<br />

using the Web configuration.<br />

Reboot the module.<br />

Consult your MIS<br />

administrator for assistance.<br />

Consult your MIS<br />

administrator for assistance.<br />

Enable the Web<br />

Configuration function using<br />

either the SMMI or the<br />

console.<br />

Change the TCP port to 80<br />

or reconnect the<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> using the<br />

specific TCP port.<br />

<strong>ET</strong>-<strong>7000</strong>/P<strong>ET</strong>-<strong>7000</strong> <strong>DIO</strong> <strong>Series</strong> <strong>User</strong> <strong>Manual</strong>, version 1.0.1 beta2 Page: 173<br />

Copyright © 2009 <strong>ICP</strong> <strong>DAS</strong> Co., Ltd. All Rights Reserved. E-mail: service@icpdas.com