Vertiv Liebert GXT5 Series Installer/User Manual

Vertiv Liebert GXT5 Series Installer/User Manual

Hide thumbs Also See for Liebert GXT5 Series:

Advertisement

Liebert®
GXT5™ UPS
Installer/User Guide
200 V to 240 V, 5000 VA to 20,000 VA

Advertisement

Table of Contents
loading

Summary of Contents for Vertiv Liebert GXT5 Series

  • Page 1 Liebert® GXT5™ UPS Installer/User Guide 200 V to 240 V, 5000 VA to 20,000 VA...
  • Page 2 Vertiv. This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use or disclosure of it without the written permission of Vertiv is strictly prohibited. Names of companies and products are trademarks or registered trademarks of the respective companies.
  • Page 3: Table Of Contents

    2� 1 � Unpacking and Inspection �������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������� 19 2�2� Pre-installation Preparation ��������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������� 20 2�2�1� Installation Clearances ������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������� 20 2�3� Installing the UPS �����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������20 2�3�1� Tower Installation ����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������21 2�3�2� Rack Installation ������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������21 2�4� Installing External Battery Cabinets �������������������������������������������������������������������������������������������������������������������������������������������������������������������22 Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 4 3�2� Starting-up the UPS ���������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������39 3�3� Transferring to Battery Mode ���������������������������������������������������������������������������������������������������������������������������������������������������������������������������������40 3�4� Transferring from Normal to Bypass Mode �����������������������������������������������������������������������������������������������������������������������������������������������40 3�5� Transferring from Bypass to Normal Mode �����������������������������������������������������������������������������������������������������������������������������������������������40 3�6� Shutting-down the UPS Completely �����������������������������������������������������������������������������������������������������������������������������������������������������������������41 Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 5 5�3� Checking UPS Operation ���������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������58 5�4� Cleaning the UPS ����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������58 5�5� Removing the Power-distribution Box ������������������������������������������������������������������������������������������������������������������������������������������������������������58 Chapter 6: Troubleshooting ������������������������������������������������������������������������������������������������������������������������������������������������������ 61 6�1� Symptoms that Require Troubleshooting ����������������������������������������������������������������������������������������������������������������������������������������������������������������� 61 6.2. Audible Alarm (Buzzer) ���������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������� 61 Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 6 6�2�1� Faults ���������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������� 61 6�3� Troubleshooting UPS Issues ������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������62 Chapter 7: Specifications ������������������������������������������������������������������������������������������������������������������������������������������������������������ 63 7�1� Battery Run Times �������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������� 70 Appendix I: Technical Support ����������������������������������������������������������������������������������������������������������������������������������������������73 Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 7: Important Safety Information

    IMPORTANT! This manual contains important safety instructions that must be followed during the installation and maintenance of the UPS and batteries. Read this manual thoroughly and the safety and regulatory information, available at https://www.vertiv.com/ComplianceRegulatoryInfo, before attempting to install, connect to supply, or operate this UPS.
  • Page 8 This page is intentionally left blank. Important Safety Information...
  • Page 9: Chapter 1: Gxt5 Description

    • Innovative design layout and process greatly increase product reliability. • Operation and display panel with model-specific color LCD offers simple configuration and control of the UPS. • ECO power-supply mode and smart-sleep mode help you save the maximum amount of energy. Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 10: 1�2� Front Panels

    Table 1-1 UPS Models and Power Ratings MODEL NUMBER NOMINAL POWER RATING GXT5-5000IRT5UXLN* GXT5-5000IRT5UXLE 5 kVA/5 kW GXT5-5000HVRT5UXLN* GXT5-6000IRT5UXLN* 6 kVA/6 kW GXT5-6000IRT5UXLE GXT5-8000IRT5UXLN* GXT5-8000IRT5UXLE 8 kVA/8 kW GXT5-8000HVRT5UXLN* GXT5-10KIRT5UXLN* GXT5-10KIRT5UXLE 10 kVA/10 kW GXT5-10KHVRT5UXLN* GXT5-16KIRT9UXLN* 16 kVA/16 kW GXT5-16KIRT9UXLE GXT5-20KIRT9UXLN* 20 kVA/20 kW GXT5-20KIRT9UXLE...
  • Page 11: 1�3� Rear Panels

    External-battery-cabinet connector Output circuit breaker Maintenance-bypass breaker Input circuit breaker Removable POD with cable-entry for hard-wire I/O Overload protector, 10-A (x2) Programmable C13 output receptacles (x2) Overload protector, 15-A (x2) C19 output receptacles (x2) Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 12 Figure 1-3 GXT5-5000HVRT5UXLN (XLE) Rear Panel ITEM DESCRIPTION Liebert® IntelliSlot™ port Terminal-block communication connectors RS-485 port USB port RS-232 port REPO connector External-battery-cabinet connector Output circuit breaker Maintenance-bypass breaker Input circuit breaker Removable POD with knock-outs/cable-entry for hard-wire I/O Programmable output circuit breaker, 10-A (x2) C19 output circuit breaker Programmable C13 output receptacles (x2) C19 output receptacles (x2)
  • Page 13 Output circuit breaker Maintenance-bypass breaker Bypass circuit breaker Input circuit breaker Removable POD with cable-entry for hard-wire I/O Programmable C19 output receptacle Overload protector, 10-A Programmable C13 output receptacles Overload protector, 15-A (x4) Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 14 Figure 1-5 GXT5-8000/10KHVRT5UXLN Rear Panel ITEM DESCRIPTION Liebert® IntelliSlot™ port Terminal-block communication connectors RS-485 port USB port RS-232 port REPO connector External-battery-cabinet connector Output circuit breaker Maintenance-bypass breaker Bypass circuit breaker Input circuit breaker Removable POD with knock-outs/cable-entry for hard-wire I/O Programmable output circuit breaker, 15-A Programmable C19 output receptacle Programmable output circuit breaker, 10-A...
  • Page 15 RS-485 port USB port RS-232 port REPO connector DB9 ports (parallel communication) Input circuit breaker Bypass circuit breaker Knock-outs/cable-entry for hard-wire I/O Output circuit breaker POD breaker Cover for optional POD-installation location External-battery-cabinet connector Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 16: 1�4� Removable Power-Distribution Boxes

    1.4. Removable Power-distribution Boxes The 16-kVA and 20-kVA do not ship with an installed power-distribution box (POD). The optional PODs for the 16-kVA and 20-kVA models are: • PD2-108 for models ending in “N” only (North America) • PD2-200 • PD2-201 •...
  • Page 17 DESCRIPTION POD Panel view (on rear of unit) POD inner-surface view Quick connect Figure 1-9 PD5-CE10HDWRMBS for GXT5-8000/10KIRT5UXLN (XLE) ITEM. DESCRIPTION POD Panel view (on rear of unit) POD inner-surface view Quick connect Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 18: 1�5� Internal Battery Packs

    Figure 1-10 PD5-CE10HDWRMBSU for GXT5-8000/10KHVRT5UXLN ITEM. DESCRIPTION POD Panel view (on rear of unit) POD inner-surface view Quick connect 1.5. Internal Battery Packs The internal battery packs for all GXT5 models, shown in Figure 1-11 below, are located behind the access door on the front of the UPS.
  • Page 19: 1�6� Major Internal Components And Operating Principle

    In the unlikely event of UPS failure such as overload or over-temperature, automatically transfers the connected load to bypass. Internal Bypass To manually transfer the connected load from inverter to bypass, see Transferring from Normal to Bypass Mode page Outlet group Output receptacles. Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 20: 1�6�1� Maintenance Bypass

    1.6.1. Maintenance Bypass On 5-kVA to 10-kVA models, the UPS includes manual maintenance bypass in a removable section of the rear of the UPS. Maintenance bypass keeps connected equipment powered with utility power and allows replacement of the UPS in the event of a UPS malfunction. Figure 1-14 on the next page, shows a diagram of bypass mode.
  • Page 21: 1�7�2� Bypass Mode

    NOTE: The batteries are fully-charged before shipment. However, transportation and storage inevitably cause some loss of capacity. To ensure adequate back-up time, charge the batteries for at least 8 hours before first start-up. Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 22: 1�7�4� Eco Mode

    NOTE: If utility power fails and the batteries are charged, you may cold-start the UPS in battery mode and use battery power to extend system availability for a time. NOTE: Powering-off the UPS when it is in battery mode results in loss of output power to the connected load. Figure 1-15 Battery-mode Operation ITEM.
  • Page 23: 1�7�5� Maintenance Bypass Mode

    NOTE: The UPS has no user-serviceable parts. If the UPS malfunctions and requires service, visit https://www. vertiv.com/support/ or contact your local Vertiv representative. Figure 1-16 Maintenance-bypass Operation ITEM. DESCRIPTION Mains/Utility input (by-pass input) Rectifier/PFC Inverter Battery charger Battery Bypass static switch UPS output Maintenance by-pass Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 24 This page is intentionally left blank.
  • Page 25: Chapter 2: Installation

    • Inspect the UPS for shipping damage. If any shipping damage is found, report it to the carrier and your local Vertiv representative immediately. • Check the accessories included against the packing list. If there is any discrepancy, contact your local Vertiv representative immediately.
  • Page 26: 2�2� Pre-Installation Preparation

    2.2. Pre-installation Preparation • Install the UPS indoors in a controlled environment, where it cannot be accidentally turned Off. The installation environment should meet the specifications listed in Specifications page 63 • Place the UPS in an area of unrestricted air-flow around the unit, away from water, flammable liquids, gases, corrosives, and conductive contaminants.
  • Page 27: 2�3�1� Tower Installation

    The GXT5 is heavy. The UPS must be installed as near the bottom of a rack as possible. If placed too high, it can make the rack top-heavy and prone to tipping over. For unit weights, see Specifications page Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 28: 2�4� Installing External Battery Cabinets

    63. Take proper precautions when lifting them. To install the EBC(s): 1. Inspect the EBC for freight damage. Report damage to the carrier and your local dealer or Vertiv representative. 2. For tower installation: » An additional set of support-base extensions ships with each EBC.
  • Page 29 Figure 2-2 EBCs connected to the UPS ITEM DESCRIPTION EBC-detection dry-contact port (See Table 2-4 page 31, for details.) EBC connector EBC-detection port External battery cabinet External battery cabinet Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 30 2.5. Installing a Power-distribution Box The 5-kVA to 10-kVA models ship with a removable power-distribution box (POD) installed, see Terminal-block Connections page 26, to make the electrical connections to the UPS. For removal, see the appropriate procedures in Maintenance page For 16-kVA to 20-kVA models, the POD ships separately and must be attached to the rear of the UPS.
  • Page 31 Models equipped with a manual bypass breaker pass bypass power directly to the bypass breaker from the input terminal block. The input circuit breaker on the distribution box does not disconnect power from the manual bypass breaker. Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 32 Table 2-2 Branch circuit breaker ratings UNIT RATING MAXIMUM BREAKER RATING 5-kVA, 6-kVA 60 A 8-kVA, 10-kVA 70 A 1-phase: 160 A 16-kVA, 20-kVA 3-phase: 50 A Figure 2-4 Circuit-breakers diagram ITEM DESCRIPTION Mains/Utility External branch CB Input MB CB Output Input CB Output CB...
  • Page 33 Connecting to Terminal Blocks on 8-kVA and 10-kVA models on the facing page • Connecting to Terminal Blocks on 16-kVA and 20-kVA models on page 30 3. Re-install the cable-entry/conduit-box cover, and tighten the screws. Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 34 2.6.3. Connecting to Terminal Blocks on 5-kVA and 6-kVA models These models offer a single type of I/O connection, 1-in 1-out common source. Figure 2-5 below, shows the terminal block. Refer to the details in Terminal-block Connections page 26, when making the connections. Figure 2-5 Terminal Block, 5-kVA and 6-kVA models ITEM DESCRIPTION...
  • Page 35 Figure 2-8 1-in 1-out Split-bypass Connection, 16-kVA and 20-kVA models ITEM DESCRIPTION Output Bypass Input Shorting cable (W02), included with accessories. Figure 2-9 1-in 1-out Common-source Connection, 16-kVA and 20-kVA models ITEM DESCRIPTION Output Bypass Input Shorting cable (W03), included with accessories. Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 36 2.7. Communication Connections The UPS offers several communication interfaces and ports. NOTE: We recommend that signal-cable lengths be less than 10 ft (3 m), and are kept away from power cabling. 2.7.1. Connecting IntelliSlot Communication The IntelliSlot ports accepts two optional cards: The Liebert®...
  • Page 37 Low Battery/On battery/ On Default: UPS fault, can be set via the LCD settings page. When the system has a fault, bypass/UPS fault short Pin 11 and Pin 12 Output 6 Signal Ground Signal Ground Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 38 2.7.3. Connecting a Remote Emergency Power-off (REPO) Switch The UPS includes an EPO connection in the dry-contact port. See the appropriate figure for your model in Rear Panels page 5, for the location of the port. UPS ships with a REPO jumper installed, allowing the UPS to operate as a normally-closed switch system (fail- safe).
  • Page 39 HID protocol from www.vertiv.com. 2.7.5. Connecting CLI Communication Cables The UPS supports the Vertiv command-line interface for operation with ACS and other third-party monitoring protocols. The RJ-45 port is used for CLI connection. See the appropriate figure for your model in...
  • Page 40 10-kVA model connected as a 2 + 1 parallel system connected in a ring configuration. NOTE: 8-kVA models do not support paralleling at this time. NOTE: You must use Vertiv parallel cables for the connection.
  • Page 41 Starting the UPS applies mains/utility power to the output terminals. Make sure that the load power is safe and ready to accept power. If the load is not ready, isolate the load with the output terminal. Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 42 The “Parallel” parameters for each UPS in the system must be set and synchronized at first start-up. To start and set parameters for the parallel system: 1. Make sure that the output MCBs of all units in the parallel system are open, then close the input MCB on each UPS.
  • Page 43 4. On the added UPS, close the external I/O switches, wait about 30 seconds to allow the rectifier start-up to finish, then power-on the inverter. 5. Make sure that there are no alarms and that the UPS and the parallel system are operating normally. Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 44 This page is intentionally left blank.
  • Page 45 8. If this is the first-time start-up of the UPS, the Start-up Guidance wizard opens to set the basic parameters of the UPS. Follow the prompts. For a full description of UPS display functions and settings, see Operation and Display Panel page Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 46 3.3. Transferring to Battery Mode The UPS operates in Normal mode unless the mains/utility power fails or it is performing a battery self-test, then it automatically transfers to Battery mode for the back-up time available or the mains/utility power is restored. Once input power is restored, the UPS returns to Normal mode.
  • Page 47 To manually power-off in an emergency, disconnect the terminal connecting the REPO port on the rear of the UPS. If mains/utility power is present, the UPS control circuit remains active even though output power is disabled. To remove all mains/utility power, disconnect the external main-input MCB. Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 48 This page is intentionally left blank.
  • Page 49 Run indicator LED, see LED Indicators page Alarm indicator LED, see LED Indicators page Power button, see Table 4-1 on the next page. Menu keys, see Table 4-1 on the next page. LCD panel. Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 50 Table 4-1 Display-panel Button Functions and Descriptions BUTTON FUNCTION DESCRIPTION Enter Confirm or enter selection. Move to previous page, increase value, move left. Down Move to next page, decrease value, move right. Escape Go back. Power Power-on the UPS, power-off the UPS, transfer to Bypass Mode. NOTE: While the UPS is operating, the LCD will dim and display a screen saver if there is no active alarm or user interaction for two minutes, see Figure...
  • Page 51 Use the function keys to navigate through the menu, and view statuses or select settings in the screens. 4.2.1. Start-up and Flow Screens At start-up, the UPS executes a system test and displays the Vertiv logo screen for about 10 seconds, shown Figure 4-1 page 43.
  • Page 52 About Product and network information, see About Screen page Maintenance Service-only, service-password protected page for use only by Vertiv service representatives. Figure 4-4 Main Menu ITEM DESCRIPTION ECO-mode indicator Ambient temperature and humidity. Only displays when sensors are connected.
  • Page 53 Editing Display and Operation Settings page 52, for details on entering the password and editing the setting parameters. NOTE: Do not change parameter settings or reset to factory defaults when powering-off the UPS. Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 54 To modify UPS settings: 1. At the main menu, select the Settings icon, and press Enter. 2. Use the arrow buttons to move the cursor left/right and select a tab, then press Enter to display the parameter list for the selected tab. 4.2.5.
  • Page 55 This alarm occurs when the battery reaches the EOD. After the pre-warning, the battery capacity allows two minutes Battery low pre-warning discharge at full load. The user can set the time ranging from 2 min ~ 30 min, (2 min by default). Please shut down the load timely Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 56 Table 4-4 Alarm Messages (Continued) MESSAGE DESCRIPTION When battery is connected, the system checks that the battery voltage exceeds the normal setting range. Check that Battery voltage abnormal the battery terminal voltage exceeds the normal range No battery Check the battery and battery cables connection The battery low voltage is detected when the battery has manual or periodical self-test.
  • Page 57 The alarm will appear when the time (Battery replaced time adds the noted time of battery replacement) later than the timeout current system time. When the users set the noted time of battery replacement as disabled, the alarm will not appear. Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 58 4.2.7. About Screen The About screen offers tabs that list information about the product and the network. To view the product and network information: 1. At the main menu, select the About icon, and press Enter 2. Use the arrow buttons to move the cursor left/right and select a tab, then press Enter to display the information for the selected tab.
  • Page 59 5. Enter the new password, then confirm the new password. A confirmation dialog opens to indicate a successful password change. 6. Press ESC to return to the settings or main menu. Figure 4-10 New and Confirm Password dialogs Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 60 4.3.2. Selecting the Display Language The LCD is multilingual. The available languages are English, French, Portuguese, Spanish, Chinese, German, Japanese, and Russian. To change the language: 1. At the main menu, select the Settings icon, and press Enter. 2. At the password prompt, use the up-arrow to select the first digit, press the down-arrow to move to the next digit, repeat for each digit, then press Enter to access the settings.
  • Page 61 » Do not lay tools or metal parts on top of batteries. » Disconnect charging source prior to connecting or disconnecting battery terminals. » If the battery kit is damaged in any way or shows signs of leakage, contact your Vertiv representative immediately.
  • Page 62 5. Compare the new and old battery pack to make sure they are the same type and model. If so, proceed with step 6. If they are different, stop and contact your Vertiv representative, or Technical Support, http://www.
  • Page 63 If the UPS will be stored for a long time, We recommend connecting the UPS to input power for at least 24 hours every 4 to 6 months to ensure full recharge of the batteries. Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 64 3. Make sure that there are no audible or silenced alarms. 4. Select the Setting menu, and look at the log for alarm and fault history. 5. Check the operating mode for Normal mode. If the UPS is operating in Bypass mode, contact Vertiv Technical Support.
  • Page 65 NOTE: The captive screws and maintenance-bypass breaker cover is similar for all 5- to 10-kVA models. Figure below, shows an example on the 5-kVA/6-kVA model. Figure 5-2 Maintenance-bypass Breaker Cover and Captive Screws ITEM DESCRIPTION Captive screws for POD Maintenance-bypass breaker Connector-cover screws Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 66 This page is intentionally left blank.
  • Page 67 The battery is bad or weak. Replace the battery. Output short The output connection is short-circuited. Shut-down the equipment and contact technical support. DC bus fail The DC bus is faulty. Contact technical support. Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 68 Vertiv Technical Support. Visit the GXT5 product page at www.vertiv.com for contact information. When reporting a UPS issue to Vertiv, include the UPS model and serial number. These are located in several places for your ease of location: » On the top panel (rack mount orientation) »...
  • Page 69 Upper-limit selections +10%, +15%, +20%; default +10%. Lower-limit selections -10%, -15%, -20%; default -15% Disable-bypass operation When the input frequency prevents synchronous operation. *Only these models are available in the ASIA PACIFIC region. Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 70 Table 7-1 UPS Specifications, 5-kVA and 6-kVA models (Continued) MODEL: GXT5- 5000IRT5UXLN* 5000IRT5UXLE 5000HVRT5UXLN* 6000IRT5UXLN* 6000IRT5UXLE RATING 5000 VA/5000 W 6000 VA/6000 W Environmental Parameters Operating Temperature, 0 to 40 (32 to 104) (no derating) °C (°F) Storage Temperature, °C -15 to 40 (5 to 104) (°F) Relative Humidity...
  • Page 71 Main Mode Overload > 150% minimum 200 mS, 125 – 150% for 60 seconds; 105 – 125% for for 5 minutes; ≤ 105% continuous Internal Battery Charger Charger Current, A 2.25default, maximum 8 Amps Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 72 Table 7-2 UPS Specifications, 8-kVA and 10-kVA models (Continued) MODEL: GXT5 8000IRT5UXLN 8000IRT5UXLE 8000HVRT5UXLN 10KIRT5UXLN 10KIRT5UXLE 10KHVRT5UXLN RATING 8000 VA/8000 W 10000 VA/10000 W Battery Parameters Type Valve-regulated, non-spillable, lead acid Quantity x Voltage 16 x 12V x 9.0AH x Rating Battery Mfr./Part # 9AH;...
  • Page 73 0 – 95% non-condensing Operating Elevation Up to 3,000 m (9,842.5 ft) at 25°C (77°F) without derating <58 dBA,at 1 meter from the front, Audible Noise <51 dBA, at 1 meter from rear or sides Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 74 Table 7-3 UPS Specifications, 16-kVA and 20-kVA models (Continued) MODEL: GXT5- 16KIRT9UXLN 16KIRT9UXLE 20KIRT9UXLN 20KIRT9UXLE RATING 16000 VA/16000 W 20000 VA/20000 W Agency Parameters Safety IEC62040-1:2008 version, GS mark; UL1778, c-UL listed IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6); FCC Part 15 (Class A) EMI/EMC/C-Tick EMC CISPR22 Class A (RFI) IEC/EN EN61000-4-2, Level 4, Criteria A...
  • Page 75 -15 to 40 (5 to 104) Relative Humidity 0 – 95% non-condensing Operating Elevation Up to 3,000 m (9,842.5 ft.) at 25°C (77°F) Agency Parameters Safety IEC62040-1:2008version,GS mark; UL1778, c-UL listed Transportation ISTA Procedure 1E Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 76 7.1. Battery Run Times Table 7-6 Battery Run Times, 20-kVA Mode TOTAL BACKUP TIME (MIN) NO. OF EBCS NO. OF 20 KVA 18 KVA 16 KVA 14 KVA 12 KVA 10 KVA 8 KVA 6 KVA 4 KVA 2 KVA 14.5 26.0 62.5...
  • Page 77 56.0 67.0 82.5 105.5 145.0 229.5 471.0 UPS+ 5 EBC 45.5 52.0 59.5 69.5 82.5 101.0 128.5 181.5 283.0 572.5 UPS+ 6 EBC 55.5 62.5 71.5 83.0 98.5 120.0 155.0 218.0 336.5 674.5 Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 78 Table 7-10 Battery Run Time, 6-kVA Models TOTAL BACKUP TIME (MIN) NO. OF NO. OF EBC S 6 KVA 5.4 KVA 4.8 KVA 4.2 KVA 3.6 KVA 3 KVA 2.4 KVA 1.8 KVA 1.2 KVA 0.6 KVA 11.0 14.5 19.5 29.0 48.0 100.0...
  • Page 79 Customer Service Hotline: 4008876510 India Email: vertiv@customercare.com Customer Service Hotline: 1800 209 6070 Asia Australia: auservice@vertiv.com New Zealand: auservice@vertiv.com Philippines: ph.service@vertiv.com Singapore: sg.service@vertiv.com Malaysia: my.service@vertiv.com Version Information V1.0 (July 19, 2019) Initial Release Vertiv | Liebert® GXT5™ | Installer/User Guide...
  • Page 80 This page is intentionally left blank.
  • Page 81 © 2019 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered marks of Vertiv Group Corp. All other names and logos referred to are trade names, trademarks, or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein.