Powerware
®
UPS ProdUctS and acceSSorieS
Power
Configuration
Parts
Qty
Description
12kW
ZC1224010100000
1
Powerware BladeUPS
12 kW 400V w/60A 5W
in/ RPM ONLY w/WEB/
SNMP/4.8 min battery
For additional
battery
103005747-6591
1
Battery increase to 12 minutes 3U
runtime
2
Battery increase to 20 minutes 6U
3
Battery increase to 27 minutes 9U
4
Battery increase to 34 minutes 12U
* Each UPS requires same number of external batteries
UPS ProdUctS and acceSSorieS
Power
Configuration
Parts
Qty
Description
12kW N+1
ZC122P060100000
2
Powerware BladeUPS
12 kW 400V w/parallel cord,
13 min battery @ 12 kW
103005913
1
Powerware 42U enclosure
with BladeBar and
Bottom WW
116750221-001
1
ConnectUPS-X WEB/SNMP
Communications Card
Total U space remaining for UPS expansion to 60 kW N+1
Input power wireway uses bottom 6U of enclosure
For additional 103005747-6591
2
Battery increase to 30 minutes 6U
battery runtime*
4
Battery increase to 44 minutes 12U
6
Battery increase to 59 minutes 18U
8
Battery increase to 76 minutes 24U
* Each UPS requires same number of external batteries
UPS ProdUctS and acceSSorieS
Power
Configuration
Parts
Qty
Description
24kW N+1
ZC122P060100000
3
Powerware BladeUPS
12 kW 400V w/parallel
cord, 9 min battery @ 24 kW
103005913
1
Powerware 42U enclosure
with BladeBar and
Bottom WW
116750221-001
1
ConnectUPS-X WEB/SNMP
Communications Card
Total U space remaining for UPS expansion to 60 kW N+1
Input power wireway uses bottom 6U of enclosure
For additional 103005747-6591
3
Battery increase to 21 minutes 9U
battery runtime*
6
Battery increase to 32 minutes 18U
9
Battery increase to 43 minutes 27U
12
Battery increase to 54 minutes 36U
* Each UPS requires same number of external batteries
BladeUPS
two (2) rackS @ 6 kw Per rack
Rack Space
Required
Parts
6U
Y032420CD100000
PW107BA0UC08
1052736
1052737
1052754
Total U space remaining for IT equipment
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
two (2) rackS @ 6 kw Per rack
Rack Space
Required
Parts
12U
Y032420CD100000
6U
PW107BA0UC08
1052736
-
1052754
24U
Total U space remaining for IT equipment
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
FoUr (4) rackS @ 6 kw Per rack
Rack Space
Required
Parts
18U
Y032420CD100000
6U
Y032440CD100000
-
PW107BA0UC08
1052736
18U
1052754
Total U space remaining for IT equipment
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
configuration Guide
Quick configurations for 12 kW single UPS solutions up to 60 kW N+1
redundant systems.
Step 1
Select UPS based on power configuration.
Step 2
Select desired rack and power configuration.
Step 3
Select appropriate startup and service support.
Note: Typical rack configurations. Other configurations available.
Racks and Power Distribution
Rack Space
Qty
Description
Required
1
Powerware Rack Power Module
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 10 ft
2
Vertical (0U) ePDU 7 kW, 16A 230V
(24 x C13) / (8 x C19)
1
42U Enclosure (Rack) Split Rear &
Casters no Sides
1
42U Enclosure (Rack) Split Rear &
Casters & Sides
1
Powerware Baying Kit,
to attach two racks together
Racks and Power Distribution
Rack Space
Qty
Description
Required
1
Powerware Rack Power Module
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 10 ft
2
Vertical (0U) ePDU 7 kW, 16A 230V
(24 x C13) / (8 x C19)
2
42U Enclosure (Rack) Split Rear &
Casters no Sides
1
Powerware Baying Kit,
to attach two racks together
Racks and Power Distribution
Rack Space
Qty
Description
Required
1
Powerware Rack Power Module
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 10 ft
1
Powerware Rack Power Module (RPM),
12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 20 ft
4
Vertical (0U) ePDU 7 kW, 16A 230V
(24 x C13) / (8 x C19)
4
42U Enclosure (Rack) Split Rear &
Casters no Sides
3
Powerware Baying Kit,
to attach two racks together
one (1) rack @ 12 kw Per rack
Parts
Qty
3U
Y032420CD100000
1
Powerware Rack Power Module
(RPM), 12 kW, (2 x L21-30R),
(6 x C19), BladeUPS Plug, 10 ft
0U
PW107BA0UC08
2
Vertical (0U) ePDU 7 kW, 16A 230V
(24 x C13) / (8 x C19)
-
1052737
1
42U Enclosure (Rack) Split Rear &
Casters & Sides
-
Total U space remaining for IT equipment
Additional batteries can be installed in IT enclosures,
-
subtract from usable space or order additional enclosure(s)
75U
one (1) rack @ 12 kw Per rack
Parts
Qty
3U
Y032420CD100000
1
Powerware Rack Power Module
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 20 ft
0U
PW107BA0UC08
2
Vertical (0U) ePDU 7 kW, 16A 230V
(24 x C13) / (8 x C19)
-
1052736
1
42U Enclosure (Rack) Split Rear &
Casters no Sides
-
Total U space remaining for IT equipment
Additional batteries can be installed in IT enclosures,
81U
subtract from usable space or order additional enclosure(s)
two (2) rackS @ 12 kw Per rack
Parts
Qty
3U
Y032420CD100000
1
Powerware Rack Power Module
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 10 ft
3U
Y032440CD100000
1
Powerware Rack Power Module
(RPM), 12 kW, 12xIEC320-C13 and
6xIEC320-C19 out, BladeUPS Plug, 20 ft
0U
PW107BA0UC08
4
Vertical (0U) ePDU 7 kW, 16A 230V
(24 x C13) / (8 x C19)
-
1052736
2
42U Enclosure (Rack) Split Rear &
Casters no Sides
-
1052754
1
Powerware Baying Kit,
to attach two racks together
162U
Total U space remaining for IT equipment
Additional batteries can be installed in IT enclosures,
subtract from usable space or order additional enclosure(s)
Rack Space
Description
Required
3U
0U
-
33U
Rack Space
Description
Required
3U
0U
-
39U
Rack Space
Description
Required
3U
3U
0U
-
-
78U

Advertisement

loading

Summary of Contents for Eaton Powerware BladeUPS

  • Page 1 Parts Description Required Parts Description Required 12kW ZC1224010100000 Powerware BladeUPS Y032420CD100000 Powerware Rack Power Module Y032420CD100000 Powerware Rack Power Module 12 kW 400V w/60A 5W (RPM), 12 kW, 12xIEC320-C13 and (RPM), 12 kW, (2 x L21-30R), in/ RPM ONLY w/WEB/...
  • Page 2 Tel: +421 2 4463 7046 acukpowerware@eaton. powerware.france@eaton.com InfoSk@Eaton.com GERMANY Tel: +49 7841 6040 infogermany@eaton.com Eaton, Powerware, and BladeUPS are trade names, trademarks, and/or service marks of Eaton Corporation and its subsidiaries or affiliates. © 2008 Eaton Corporation, All Rights Reserved. 1018037 Rev C...