Eaton 9130 UPS
Eaton 9130 UPS
Eaton 9130 UPS
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Powerware series<br />
<strong>Eaton</strong> <strong>9130</strong> <strong>UPS</strong><br />
Product snapshot<br />
Product rating: 700 to 6000 VA<br />
Voltage: 220-240 V<br />
Frequency: 50/60 Hz<br />
(auto-sensing)<br />
Configuration: Rackmount or tower<br />
Advanced power protection for:<br />
• IT and networking environments<br />
• Servers, networking gear<br />
• Telecommunications, VoIP, security systems<br />
• Medical systems<br />
• Diagnostics and medical screening<br />
• Patient record archives<br />
• Manufacturing systems<br />
• Chip fabrication<br />
• Pharmaceutical production<br />
• Chemical processing<br />
Features<br />
• Protects against downtime, data loss and process interruption<br />
by providing continuous, clean power<br />
• Offers premium performance with a 0.9 power factor and<br />
>95 percent efficiency<br />
• Increases battery service life and system uptime with-<br />
ABM battery charging technology<br />
• Enables prolonged runtime of essential equipment during<br />
power outages by allowing for orderly, remote shutdown<br />
of non-critical systems or processes by Load Segment<br />
Control<br />
• Provides installation flexibility with a choice of rack or<br />
tower designs, both conserving valuable space<br />
• Enhanced monitoring and configuration capability through<br />
easily navigated multilingual graphical display<br />
The <strong>Eaton</strong> ® <strong>9130</strong> <strong>UPS</strong>, Powerware<br />
® series, resolves utility<br />
power problems and delivers<br />
superior power protection for<br />
IT and networking equipment,<br />
medical systems, manufacturing<br />
process control—or anywhere<br />
critical equipment and<br />
applications require clean,<br />
continuous power.<br />
Double-conversion<br />
design for superior<br />
power protection<br />
The <strong>9130</strong> is constantly monitoring<br />
power conditions—<br />
regulating both voltage and<br />
frequency. Even when presented<br />
with the most severe<br />
power problems, this <strong>UPS</strong>’s<br />
output remains within three<br />
percent of nominal voltage.<br />
With a wide input voltage range,<br />
the <strong>9130</strong> does not depend<br />
on batteries to smooth out<br />
minor power fluctuations. Batteries<br />
are conserved for those<br />
times when utility power is<br />
highly unstable or completely<br />
out. If an outage occurs, the<br />
<strong>9130</strong> transfers to battery with<br />
zero interruption in power,<br />
making this an ideal <strong>UPS</strong> for<br />
sensitive and critical equipment.<br />
More real power for less<br />
cost in less space<br />
More real power. High 0.9<br />
output power factor enables<br />
the <strong>9130</strong> to provide its full<br />
power capability to modern<br />
IT equipment that may have<br />
a wide range of leading and<br />
lagging power factors. With a<br />
0.99 input power factor, this<br />
<strong>UPS</strong> avoids the disturbances<br />
that some energy converters<br />
tend to cause.<br />
High efficiency. The more<br />
efficient the <strong>UPS</strong>, the lower<br />
your utility and cooling bills.<br />
When power conditions are<br />
within acceptable limits, the<br />
<strong>9130</strong> can operate in a highefficiency<br />
mode providing 95<br />
percent or higher efficiency.
One platform, two form factors, dozens of choices. Up to 3000<br />
VA of <strong>UPS</strong> power is packed into only 2U of rack space. The<br />
tower option is about the size of a modern, compact PC.<br />
ABM technology<br />
Maximum availability for critical systems<br />
Stronger, longer battery life. <strong>Eaton</strong> Advanced Battery Management<br />
(ABM) technology uses sophisticated sensing circuitry<br />
and an innovative three-stage charging technique, that constantly<br />
monitors the battery charging status, and as a result<br />
only recharges when necessary, so ultimately the battery experiences<br />
less corrosion and battery service life is prolonged<br />
by up to 50%.<br />
The <strong>9130</strong> provides up to 60 days’ notice of the end of useful<br />
battery service life. You have ample time to hot-swap batteries<br />
without ever having to shut down connected equipment.<br />
Battery runtime for minutes or hours. During a power outage,<br />
internal batteries in the <strong>9130</strong> keep loads running long enough<br />
to gracefully shut down systems. Add more runtime at any<br />
time, with up to four external hot-swappable battery modules<br />
to run systems for hours if necessary.<br />
Maximum battery runtime for critical equipments. Using Load<br />
Segment Control, you can manage scheduled shutdowns and<br />
sequential startups of protected loads. During a power outage,<br />
you could shut down power to non-critical devices, thereby<br />
extending battery backup time available for critical devices.<br />
You can also use this feature to remotely re-boot locked-up<br />
equipment.<br />
Load segments<br />
Visibility, control and management from anywhere<br />
Continous monitoring for premium availability. The <strong>9130</strong><br />
continually monitors voltage, temperature, internal element<br />
functions, battery health, battery state-of-charge and runtime<br />
remaining. If the <strong>UPS</strong> detects a potential problem with any<br />
of these measures, it sends alarms or takes corrective action,<br />
with no interruption in power. At the end of an alarm condition,<br />
the <strong>9130</strong> automatically reverts from bypass to normal<br />
operation.<br />
Local <strong>UPS</strong> status at a glance. An on-site user can configure<br />
and monitor many features of the <strong>9130</strong> using a large, bright,<br />
backlit display with easy navigation—available in multiple languages.<br />
LEDs provide at-a-glance insight into system status.<br />
Multilingual LCD<br />
Internal batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs<br />
BATTERY RUNTIMES* 75% Load 50% Load 75% Load 50% Load 75% Load 50% Load 75% Load 50% Load 75% Load 50% Load<br />
Rack models<br />
<strong>9130</strong>-1000 VA, 2U 13 22 55 82 103 186 151 250 223 312<br />
<strong>9130</strong>-1500 VA, 2U 11 18 47 81 83 143 126 208 195 262<br />
<strong>9130</strong>-2000 VA, 2U 13 24 63 95 118 190 170 242 221 345<br />
<strong>9130</strong>-3000 VA, 2U 8 14 34 62 70 92 96 156 130 211<br />
Tower models<br />
<strong>9130</strong>-700 VA 12 19 N/A N/A N/A N/A N/A N/A N/A N/A<br />
<strong>9130</strong>-1000 VA 13 22 55 82 103 186 151 250 223 312<br />
<strong>9130</strong>-1500 VA 11 18 47 81 83 143 126 208 195 262<br />
<strong>9130</strong>-2000 VA 21 34 81 130 145 198 184 293 248 431<br />
<strong>9130</strong>-3000 VA 12 20 49 79 90 143 134 180 165 240<br />
<strong>9130</strong>-5000 VA 20 34 81 136 153 232 217 328 273 477<br />
<strong>9130</strong>-6000 VA 16 27 66 107 120 194 178 267 231 372<br />
* Runtimes are shown at a 0.7 power factor. Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.<br />
2 EATON CORPORATION <strong>Eaton</strong> <strong>9130</strong> <strong>UPS</strong>
Remote monitoring. The <strong>9130</strong> comes complete with the <strong>Eaton</strong><br />
Software Suite CD including SNMP-compatible power management<br />
software providing control and visibility over all your<br />
<strong>UPS</strong> systems. For example, you can establish a prioritized<br />
shutdown of network devices and client/server applications,<br />
test all networked <strong>UPS</strong> systems from one node, and stay<br />
informed of power problems by email.<br />
Choice of connectivity options. Connectivity options are available<br />
for almost any networking environment. The standard<br />
unit comes with USB and RS-232 serial communication ports.<br />
You can customize your <strong>UPS</strong> by adding communication cards<br />
options that will allow to:<br />
• Integrate the <strong>UPS</strong> to SNMP based Network Management<br />
Systems with a Web/SNMP card and manage it through<br />
standard web browsers<br />
• Monitor and shut down multiple servers with different<br />
operating systems<br />
• Send relay-contact alarm notifications to remote security<br />
systems<br />
Remote Monitoring - IPM<br />
Complementary options<br />
You can complement your <strong>9130</strong> with several options, among<br />
which:<br />
• A maintenance bypass for easy replacement of the <strong>UPS</strong><br />
without powering down critical systems<br />
• Power distribution units streamline the distribution of<br />
power throughout a data center, rack or enclosure<br />
Description<br />
Part Number<br />
Rating<br />
Dimensions<br />
(VA/Watts)<br />
Input connection Output recetacles<br />
H x W x D, mm<br />
Weight, kg<br />
Tower Models 230V, 50/60Hz<br />
<strong>9130</strong>-700i 103006433-6591 700/630 C14 (6) C13 230 x 160 x 350 12.2<br />
<strong>9130</strong>-1000i 103006434-6591 1000/900 C14 (6) C13 230 x 160 x 380 14.5<br />
<strong>9130</strong>-1500i 103006435-6591 1500/1350 C14 (6) C13 230 x 160 x 430 19.0<br />
<strong>9130</strong>-2000i 103006436-6591 2000/1800 C14 (8) C13, (1) C19 325 x 214 x 410 34.5<br />
<strong>9130</strong>-3000i 103006437-6591 3000/2700 C20 (8) C13, (1) C19 325 x 214 x 410 34.5<br />
<strong>9130</strong>-5000i 103007841-6591 5000/4500 Hardwire Hardwire 574 x 244 x 542 75.5<br />
<strong>9130</strong>-6000i 103007842-6591 6000/5400 Hardwire Hardwire 574 x 244 x 542 75.5<br />
Tower Models 120V, 50/60Hz<br />
<strong>9130</strong>-700L 103006426-6591 700/630 5-15P (6) 5-15R 230 x 160 x 350 12.2<br />
<strong>9130</strong>-1000L 103006427-6591 1000/900 5-15P (6) 5-15R 230 x 160 x 380 14.5<br />
<strong>9130</strong>-1500L 103006428-6591 1500/1350 5-15P (6) 5-15R 230 x 160 x 430 19.0<br />
<strong>9130</strong>-2000L 103006429-6591 2000/1800 5-20P (1) L5-20R, (4) 5-20R 325 x 214 x 410 34.5<br />
<strong>9130</strong>-3000L 103006430-6591 3000/2700 L5-30P (4) 5-20R, (1) L5-30R 325 x 214 x 410 34.5<br />
Tower Extended Battery Modules<br />
<strong>9130</strong> EBM 36 (1kVA) 103006438-6591 NA NA NA 230 x 160 x 380 18.5<br />
<strong>9130</strong> EBM 48 (1.5kVA) 103006439-6591 NA NA NA 230 x 160 x 430 24.3<br />
<strong>9130</strong> EBM 96 (2/3kVA) 103006440-6591 NA NA NA 325 x 214 x 410 50.0<br />
<strong>9130</strong> ebm 240 (5/6kVA) 103007843-6591 NA NA NA 574 x 244 x 542 111.0<br />
Rack Models 230V, 50/60Hz<br />
<strong>9130</strong>-1000iRM 2U 103006455-6591 1000/900 C14 (6) C13 86.5 x 438 x 450 16.0<br />
<strong>9130</strong>-1500iRM 2U 103006456-6591 1500/1350 C14 (6) C13 86.5 x 438 x 450 19.0<br />
<strong>9130</strong>-2000iRM 2U 103006457-6591 2000/1800 C14 (8) C13, (1) C19 86.5 x 438 x 600 29.0<br />
<strong>9130</strong>-3000iRM 2U 103006463-6591 3000/2700 C20 (8) C13, (1) C19 86.5 x 438 x 600 29.5<br />
Rack Models 120V, 50/60Hz<br />
<strong>9130</strong>-1000RM 2U 103006448-6591 1000/900 5-15P (6) 5-15R 87 x 438 x 450 16.0<br />
<strong>9130</strong>-1500RM 2U 103006449-6591 1500/1350 5-15P (6) 5-15R 87 x 438 x 450 19.5<br />
<strong>9130</strong>-2000RM 2U 103006450-6591 2000/1800 5-20P (6) 5-20R, (1) L5-20R 87 x 438 x 600 29.0<br />
<strong>9130</strong>-3000RM 2U 103006452-6591 3000/2700 L5-30P (6) 5-20R, (1) L5-30R 87 x 438 x 600 29.5<br />
Rack Extended Battery Modules<br />
<strong>9130</strong>RM EBM 36 (1kVA) 103006458-6591 NA NA NA 86.5 x 438 x 450 22.1<br />
<strong>9130</strong>RM EBM 48 (1.5kVA) 103006459-6591 NA NA NA 86.5 x 438 x 450 28.1<br />
<strong>9130</strong>RM EBM 72 (2/3kVA) 103006460-6591 NA NA NA 86.5 x 438 x 600 41.1<br />
www.eaton.com/<strong>9130</strong> 3
<strong>Eaton</strong> <strong>9130</strong> <strong>UPS</strong> Product Focus<br />
TECHNICAL SPECIFICATIONS<br />
General<br />
User interface<br />
LEDs<br />
Topology<br />
Diagnostics<br />
<strong>UPS</strong> bypass<br />
Dimensions<br />
Rail kit<br />
Electrical Input<br />
Nominal voltage 120V, 220–240V<br />
Voltage range<br />
120V: 90–138 Vac<br />
230V: 160–276 Vac<br />
Power drawn from <strong>UPS</strong><br />
Dedicated circuit<br />
breaker rating<br />
<strong>UPS</strong> input rating<br />
Graphical LCD with blue backlight and text in<br />
English, French, German, Russian and Spanish<br />
Four status-indicating LEDs<br />
True online, double-conversion<br />
Full system self-test<br />
Automatic bypass<br />
See models table<br />
Included with all rackmount units<br />
700: 3.0A @230V, 5.8A @120V<br />
1000: 4.3A @230V, 8.3A @120V<br />
1500: 6.5A @230V, 12.5A @120V<br />
2000: 8.7A @230V, 16.6A @120V<br />
3000: 13A @230V, 25A @ 120V<br />
5000: 21.7A @230V<br />
6000: 26A @230V<br />
120V:<br />
700–1500 VA: 15A<br />
2000 VA: 20A<br />
2500–3000 VA: 30A<br />
230V:<br />
700–2000 VA: 10A<br />
3000 VA: 16A<br />
5000 VA: 24A<br />
6000 VA: 32A<br />
50/60 Hz<br />
45–65 Hz<br />
Frequency<br />
Frequency range<br />
Electrical Output<br />
Power factor 0.9<br />
On utility voltage ±3% of nominal regulation<br />
On battery voltage ±3% of nominal regulation<br />
Efficiency<br />
>95% in high-efficiency mode; >86% in online mode<br />
Frequency regulation ±3% Hz online<br />
Load crest factor 3 to 1<br />
Battery<br />
Battery type<br />
VRLA 12V/9 Ah (both internal and external)<br />
Battery runtime See runtime table<br />
Battery replacement Hot-swappable internal and external batteries<br />
Start-on-battery Allows start of <strong>UPS</strong> without utility input<br />
Communications<br />
Serial port<br />
USB port<br />
Relay output<br />
Communications slot<br />
Optional communication<br />
cards<br />
Environmental<br />
Safety markings<br />
EMC markings<br />
Audible noise<br />
Ambient operating<br />
temperature<br />
Storage temperature<br />
RS-232 standard, for interface to power management<br />
software<br />
HID standard, for communicating with Windows XP/<br />
Vista<br />
Common alarm standard<br />
Optional communication slots (BD Slot)<br />
SNMP/Web card for direct control and monitoring<br />
in SNMP-based networks, monitoring of <strong>UPS</strong> status<br />
and meters through Web browser interface.<br />
Relay card for integration to industrial environment<br />
and building management systems, remote shutdown<br />
for IBM AS/400 systems<br />
120V: UL, CUL, VCCI<br />
230V: CE, GS<br />
120V: FCC Class B, EN55022 Class B (1.5 kVA and<br />
below); FCC Class A, EN55022 Class A (2.0 kVA<br />
and above)<br />
230V: CE (per IEC/EN62040-2: Emissions, Category<br />
C1; Immunity, Category C2)<br />