Powerware and X−Slot are registered trademarks of Eaton Electrical Inc. ECopyright 2004-2007 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
You can enhance any of these system configurations by adding optional accessories such as a Remote Monitor Panel (RMP), Relay Interface Module (RIM), Supervisory Contact Module (SCM), or Remote Emergency Power−Off (EPO) control. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 1−1 EATON Powerware ®...
In this manual, the term UPS refers only to the UPS cabinet and its internal elements. The term UPS system refers to the entire power protection system – the UPS cabinet, battery strings, and options or accessories installed. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 1−2 EATON Powerware ®...
UPS system, and information about enabling, disabling, and customizing building alarms. Visit www.powerware.com or contact your Eaton service representative for information on how to obtain copies of this manual. 1.4 Getting Help...
Page 8
Introduction This page intentionally left blank. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 1−4 EATON Powerware ®...
NOTE Startup and operational checks should be performed only by authorized service personnel. This service is usually offered as part of the sales contract for your UPS system. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 2−1 EATON Powerware ®...
Powerware 9315 UPS (200–300 kVA) Operation Manual. If you intend to operate the UPS at an altitude higher than 1500m (5000 ft), contact your Eaton service representative for important information about high altitude operation. The operating environment must meet the size and weight requirements shown in Table N on page A−13.
1. Carefully inspect the outer packaging for evidence of damage during transit. C A U T I O N Do not install a damaged cabinet. Report any damage to the carrier and your Eaton service representative immediately. 2. Use a forklift or other material handling equipment to move the cabinet to a convenient unpacking area.
Page 12
Getting Started This page intentionally left blank. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 2−4 EATON Powerware ®...
The UPS cabinet is bolted to a sheet metal pallet consisting of four supports secured to foam cushions. The foam cushions act as shock absorbers for the cabinet during shipment and movement to the installed location. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 3−1 EATON Powerware ®...
4. Insert the forklift jacks in the forklift slots and raise the UPS cabinet until the foam cushions clear the floor by approximately 3 mm (1/8″). 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 3−2 EATON Powerware ®...
(labeled 2" in Figure 3-2). Discard or recycle the hardware and support brackets in a responsible manner. 8. Repeat Steps 1 through 7 for each cabinet you are preparing to install. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 3−3 EATON Powerware ®...
NOTE A bypass neutral feeder must be supplied when the output neutral is used. If no bypass neutral is supplied, the output neutral is to be bonded to ground through a minimum 3/0 copper conductor. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 3−4 EATON Powerware ®...
NOTE A bypass neutral feeder must be supplied when the output neutral is used. If no bypass neutral is supplied, the output neutral is to be bonded to ground through a minimum 3/0 copper conducter. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 3−5 EATON Powerware ®...
You should make a copy of the installation checklist before filling it out, and retain the original. After the installation is complete, your Eaton service representative will be able to verify the operation of the UPS system and commission it to support the critical load. The service representative cannot perform any installation tasks other than verifying software and operating setup parameters and installing an optional external modem or internal X−Slot...
- System Load Sync Control is mounted in its installation location and wired appropriately. (OPTIONAL) - Maintenance Bypass is mounted in place and wired appropriately. (OPTIONAL) - Circuit breakers with adjustable trip mechanisms are adjusted to match site requirements. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 3−7 EATON Powerware ®...
When replacing batteries, use the same number of sealed, lead-acid batteries. Proper disposal of batteries is required. Refer to your local codes for disposal requirements. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 4−1 EATON Powerware ®...
Page 22
If you are installing battery cabinets not provided by Powerware, refer to the battery cabinet manufacturer’s operating manual for instructions on battery cabinet installation and maintenance. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 4−2 EATON Powerware ®...
C A U T I O N Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 4−3 EATON Powerware ®...
Page 24
Installing Battery Cabinets This page intentionally left blank. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 4−4 EATON Powerware ®...
Front View Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Figure 5-1. Input Transformer Cabinet 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 5−1 EATON Powerware ®...
Installing Input and Output Transformers Customer Input Area (Top) Top View Front View Figure 5-3. Output Transformer Cabinet (480/208V) 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 5−3 EATON Powerware ®...
Page 28
Figure 5-5 for the location of connection points within the cabinets. 4. Close the rectifier input transformer cabinet doors and the bypass input transformer cabinet doors. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 5−4 EATON Powerware ®...
Page 29
Connection point in UPS Phase Input Output ∅ A ∅ B ∅ C Neutral 4. Close the UPS cabinet doors and the output transformer cabinet door. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 5−5 EATON Powerware ®...
Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Front Figure 5-4. Installing an Input Transformer Cabinet 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 5−6 EATON Powerware ®...
Installing Input and Output Transformers AC Output Output AC Input to UPS Input Neutral to Transformer Neutral Front Figure 5-5. Installing a 208/480 Vac Input Transformer Cabinet 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 5−7 EATON Powerware ®...
Installing Input and Output Transformers AC Input to Transformer AC Output to UPS Ground Neutral Front Figure 5-6. Installing a 480/208 Vac Output Transformer Cabinet 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 5−8 EATON Powerware ®...
Distribution Module Installation and Operation Manual for PDM installation and operation. NOTE This option requires a UPS with a 208 Vac output. Figure 6-1. Typical PDM Cabinet 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 6−1 EATON Powerware ®...
Page 34
Installing a Power Distribution Module This page intentionally left blank. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 6−2 EATON Powerware ®...
Figure 7-2. Remote EPO switch wiring must be in accordance with UL Class II requirements. 6. Secure the UPS by reversing all steps taken to prepare it for Remote EPO installation. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 7−2 EATON Powerware ®...
3 (UV trip) must be connected to the DC source disconnect device(s). For battery switch dimensions, see Drawing 164201037−14 on page A−38. Side Front Figure 8-1. Remote Battery Disconnect Enclosure 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 8−1 EATON Powerware ®...
Page 38
UPS Model DC Voltage Circuit Breaker Rating 0.8 load pF 0.9 load pF Powerware 9315 200 Powerware 9315 225 Powerware 9315 250 Powerware 9315 300 1000 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 8−2 EATON Powerware ®...
Installing a Remote Monitor Panel Flush Mount Surface Mount (for Hanging) Wires Must be Twisted Figure 9-1. Remote Monitor Panel 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 9−2 EATON Powerware ®...
Communication Panel. Connect to Port 1 (DB−9) on Communication Panel Fuse Terminal Block (TB3) Figure 9-2. Terminal Block Bracket 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 9−3 EATON Powerware ®...
RMP continues to self-test, replace the fuse with the spare included in the hardware kit. If this does not correct the problem, contact your Eaton service representative for verification that the RMP is working correctly.
Page 43
8. If you are installing an RIM or SCM in addition to an RMP, proceed to Chapter 10 or 11, respectively; otherwise, secure the UPS cabinet by reversing the steps on page 3−4. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 9−5 EATON Powerware ®...
Page 44
Installing a Remote Monitor Panel This page intentionally left blank. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 9−6 EATON Powerware ®...
DB−9 connector on the Communication Panel of the UPS (see Figure 10-3). Use two screws from the spare parts kit to secure the terminal block bracket to the Communication Panel. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 10−1 EATON Powerware ®...
Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Figure 10-3. Wiring an RIM to the UPS 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 10−2 EATON Powerware ®...
Page 47
4. Connect RIM wiring to the terminal block using the terminations shown in Table 10-1. 5. Contact your Eaton service representative for verification and testing of the RIM and its connections prior to making connections with J1 through J4. You can order interface cables separately for connecting to the 15-Pin D-Sub Connectors.
Page 48
Installing a Relay Interface Module This page intentionally left blank. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 10−4 EATON Powerware ®...
DB−9 connector on the Communication Panel of the UPS (see Figure 11-3). Use two screws from the spare parts kit to secure the terminal block bracket to the Communication Panel. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 11−1 EATON Powerware ®...
4. Connect the SCM wiring to the terminal block using the terminations shown in Table 11-1. 5. Contact your Eaton service representative for verification and testing of the SCM and its connections prior to making connections to terminal strip shown in Figure 11-4.
Page 51
TB1−7 TB3−4 From SCM B (if used) To UPS Remarks TB1−4 TB3−5 TB1−5 TB3−6 Twisted wires (4) 1−2 turns per 3″ TB1−6 TB3−7 TB1−7 TB3−8 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 11−3 EATON Powerware ®...
NOTE Supervisory contacts are rated at 2.0A at 28 Vdc or 120 Vac and 0.15A at 115 Vdc. NOTE Supervisory contacts require external an power supply. Internal 24 Vdc is not capable of supplying contact current. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 11−4 EATON Powerware ®...
164201037−9 Maintenance Bypass Module 164201037−10 Remote Emergency Power Off 164201037−11 Remote Monitor Panel 164201037−12 Relay Interface Module 164201037−13 Supervisory Contact Module 164201037−14 Battery Disconnect Switch 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−1 EATON Powerware ®...
Page 54
DESCRIPTION: INSTALLATION NOTES NOTE: Callout letters DRAWING NO: SHEET: map to drawing #164201037−3 164201037−1 1 of 17 400V = 380/400/415 Volt REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−2 EATON Powerware ®...
Page 55
AWG or kcmil(ea) 350(3) 3/0(2) DESCRIPTION: INSTALLATION NOTES NOTE: Callout letters DRAWING NO: SHEET: map to drawing #164201037−3 164201037−1 2 of 17 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−3 EATON Powerware ®...
Page 56
Minimum conductor size (number per O) DESCRIPTION: INSTALLATION NOTES NOTE: Callout letters DRAWING NO: SHEET: 164201037−1 3 of 17 map to drawing #164201037−3 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−4 EATON Powerware ®...
Page 57
250(2) DESCRIPTION: INSTALLATION NOTES NOTE: Callout letters DRAWING NO: SHEET: map to drawing #164201037−3 164201037−1 4 of 17 400V = 380/400/415 Volt REVISION: DATE: 051506 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−5 EATON Powerware ®...
Page 58
AWG or kcmil(ea) 350(3) 3/0(2) DESCRIPTION: INSTALLATION NOTES NOTE: Callout letters DRAWING NO: SHEET: 164201037−1 5 of 17 map to drawing #164201037−3 REVISION: DATE: 051506 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−6 EATON Powerware ®...
Page 59
Minimum conductor size (number per O) DESCRIPTION: INSTALLATION NOTES NOTE: Callout letters DRAWING NO: SHEET: 164201037−1 6 of 17 map to drawing #164201037−3 REVISION: DATE: 051506 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−7 EATON Powerware ®...
Page 60
NOTE: Customer ground, size 2/0, can be run in any conduit listed in Table G DRAWING NO: SHEET: 164201037−1 7 of 17 and Table H. REVISION: C DATE: 121598 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−8 EATON Powerware ®...
Page 61
NOTE: Customer ground, size 2/0, can be run in any conduit listed in Table G. DRAWING NO: SHEET: 164201037−1 8 of 17 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−9 EATON Powerware ®...
Page 62
DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 164201037−1 9 of 17 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−10 EATON Powerware ®...
Page 63
AC output to critical load shown in Table B through Table F. The recommended line-to-line load unbalance is 50% or less. DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 164201037−1 10 of 17 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−11 EATON Powerware ®...
Page 64
0.9 load pF Model 200 Model 225 Model 250 Model 300 1000 DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 164201037−1 11 of 17 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−12 EATON Powerware ®...
Page 65
8 at 214 (471) Series 1085−J47 2178 (4800) 8 at 272 (600) DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 164201037−1 12 of 17 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−13 EATON Powerware ®...
Page 66
Regardless of assignment, alarms display as Building Alarm 1, Building Alarm 2, etc., on the Monitor Panel. Use twisted-pair wires for each alarm input and common. DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 164201037−1 13 of 17 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−14 EATON Powerware ®...
Page 67
RELAY 2 NC General purpose NO and NC relay contacts. NOTICE RTN DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 164201037−1 14 of 17 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−15 EATON Powerware ®...
Page 68
CONTACT RATING: Maximum Switched Voltage 32 VAC 42 VDC Maximum Carrying Current DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 164201037−1 15 of 17 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−16 EATON Powerware ®...
Page 69
NOTE: This switch must be a dedicated switch, and not tied into any other circuits. DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 164201037−1 16 of 17 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−17 EATON Powerware ®...
Page 70
NOTE: For other than Powerware battery cabinets that use UV trip coils, connect to TB4 Pin 3 instead of TB4 Pin 2. DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 164201037−1 17 of 17 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−18 EATON Powerware ®...
Page 71
UPS cabinet. DESCRIPTION: TYPICAL UPS SYSTEM DRAWING NO: SHEET: 164201037−2 1 of 1 REVISION: DATE: 020497 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−19 EATON Powerware ®...
Page 72
Sheet 4 208/208 Auto (Dual Feed) (Wye in, Wye out) DESCRIPTION: UPS SYSTEM ONELINE CONFIGURATIONS DRAWING NO: SHEET: 164201037−3 1 of 1 REVISION: DATE: 041500 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−20 EATON Powerware ®...
Page 73
NOTE 2: See Table U to determine when an input DESCRIPTION: ONELINE DRAWINGS OF UPS SYSTEM transformer is required. DRAWING NO: SHEET: 164201037−4 1 of 4 REVISION: DATE: 082806 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−21 EATON Powerware ®...
Page 74
NOTE 2: See Table U to determine when an input DESCRIPTION: ONELINE DRAWINGS OF UPS SYSTEM transformer is required. DRAWING NO: SHEET: 164201037−4 2 of 4 REVISION: DATE: 082806 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−22 EATON Powerware ®...
Page 75
ONELINE DRAWINGS OF UPS SYSTEM conductor. DRAWING NO: SHEET: 164201037−4 3 of 4 NOTE 2: See Table U to determine when an input REVISION: DATE: transformer is required. 082806 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−23 EATON Powerware ®...
Page 76
ONELINE DRAWINGS OF UPS SYSTEM conductor. DRAWING NO: SHEET: 164201037−4 4 of 4 NOTE 2: See Table U to determine when an input REVISION: DATE: transformer is required. 082806 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−24 EATON Powerware ®...
Page 77
AC OUTPUT RS−232 (E9, E10, E11) COMMUNICATION CONNECTION PANEL DESCRIPTION: LOCATION OF UPS POWER TERMINALS DRAWING NO: SHEET: 164201037−5 1 of 1 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−25 EATON Powerware ®...
Page 78
(65.1) 1866.1 (73.5) (13.1) 484.4 (19.1) (28.9) Dimensions are in millimeters (inches) DESCRIPTION: UPS CABINET DRAWING NO: SHEET: 164201037−6 1 of 2 REVISION: DATE: 020497 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−26 EATON Powerware ®...
Page 79
(9.0) (16.17) (23.15) Dimensions are in millimeters (inches) UPS CABINET DESCRIPTION: BOTTOM UPS CABINET DRAWING NO: SHEET: VIEW 164201037−6 2 of 2 REVISION: DATE: 020497 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−27 EATON Powerware ®...
Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó FRONT VIEW Dimensions are in millimeters (inches) DESCRIPTION: TRANSFORMER CABINETS DRAWING NO: SHEET: 164201037−7 1 of 3 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−28 EATON Powerware ®...
Page 81
(47.2) INPUT ISOLATION TRANSFORMER CABINET (208/480) DESCRIPTION: TRANSFORMER CABINETS DRAWING NO: SHEET: 164201037−7 2 of 3 REVISION: C DATE: Dimensions are in millimeters (inches) 121598 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−29 EATON Powerware ®...
Page 82
(47.2) OUTPUT AUTO TRANSFORMER CABINET (480/208) DESCRIPTION: TRANSFORMER CABINETS DRAWING NO: SHEET: 164201037−7 3 of 3 REVISION: C DATE: Dimensions are in millimeters (inches) 121598 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−30 EATON Powerware ®...
Page 83
POWER DISTRIBUTION MODULE Distribution Module Installation and DRAWING NO: SHEET: Operation Manual 164201061 for 164201037−8 1 of 1 PDM installation and operation. REVISION: D DATE: 041500 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−31 EATON Powerware ®...
Page 84
Module (MBM) Installation and Operation Manual 164201233 for MBM installation and operation. DESCRIPTION: MAINTENANCE BYPASS MODULE DRAWING NO: SHEET: 164201037−9 1 of 1 REVISION: D DATE: 041500 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−32 EATON Powerware ®...
Page 85
TO OTHER TO UPS Dimensions are in millimeters (inches) EQUIPMENT DESCRIPTION: REMOTE EMERGENCY POWER OFF DRAWING NO: SHEET: 164201037−10 1 of 1 REVISION: D DATE: 041500 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−33 EATON Powerware ®...
Page 86
(14−18 gauge) EXCEED 500 FEET. Dimensions are in millimeters (inches) DESCRIPTION: REMOTE MONITOR PANEL DRAWING NO: SHEET: 164201037−11 1 of 1 REVISION: D DATE: 041500 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−34 EATON Powerware ®...
Page 87
MIN WIRE SIZE NO. 18 AWG. Dimensions are in millimeters (inches) DESCRIPTION: RELAY INTERFACE MODULE DRAWING NO: SHEET: 164201037−12 1 of 2 REVISION: D DATE: 041500 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−35 EATON Powerware ®...
Page 88
KNOCKOUTS PROVIDED ON FIVE SURFACES Dimensions are in millimeters (inches) DESCRIPTION: RELAY INTERFACE MODULE DRAWING NO: SHEET: 164201037−12 2 of 2 REVISION: D DATE: 041500 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−36 EATON Powerware ®...
Page 89
REMOTE MONITOR AND UPS NOT TO EXCEED 500 FEET. Dimensions are in millimeters (inches) DESCRIPTION: SUPERVISORY CONTACT MODULE DRAWING NO: SHEET: 164201037−13 1 of 1 REVISION: D DATE: 041500 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−37 EATON Powerware ®...
Page 90
KNOCKOUTS TO BE DETERMINED AT 75 LBS (34 KG) TIME OF INSTALLATION. DESCRIPTION: BATTERY DISCONNECT SWITCH DRAWING NO: SHEET: 164201037−14 1 of 2 REVISION: A DATE: 010198 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−38 EATON Powerware ®...
Page 91
Customer Information TYPE K1200 BREAKER OUTLINE DESCRIPTION: BATTERY DISCONNECT SWITCH DRAWING NO: SHEET: 164201037−14 2 of 2 REVISION: A DATE: 010198 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−39 EATON Powerware ®...
Page 92
Customer Information This page intentionally left blank. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−40 EATON Powerware ®...