Eaton powerwave 9315 Installation Manual
Eaton powerwave 9315 Installation Manual

Eaton powerwave 9315 Installation Manual

200–300 kva
Table of Contents

Advertisement

Quick Links

Powerware 9315 UPS
®
200–300 kVA
Installation Manual

Advertisement

Table of Contents
loading

Summary of Contents for Eaton powerwave 9315

  • Page 1 Powerware 9315 UPS ® 200–300 kVA Installation Manual...
  • Page 2: Save These Instructions

    Powerware and X−Slot are registered trademarks of Eaton Electrical Inc. ECopyright 2004-2007 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
  • Page 3: Table Of Contents

    ......... . . A−1 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com EATON Powerware ®...
  • Page 4 ..........11−4 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com EATON Powerware ®...
  • Page 5: Introduction

    You can enhance any of these system configurations by adding optional accessories such as a Remote Monitor Panel (RMP), Relay Interface Module (RIM), Supervisory Contact Module (SCM), or Remote Emergency Power−Off (EPO) control. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 1−1 EATON Powerware ®...
  • Page 6: Using This Manual

    In this manual, the term UPS refers only to the UPS cabinet and its internal elements. The term UPS system refers to the entire power protection system – the UPS cabinet, battery strings, and options or accessories installed. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 1−2 EATON Powerware ®...
  • Page 7: For More Information

    UPS system, and information about enabling, disabling, and customizing building alarms. Visit www.powerware.com or contact your Eaton service representative for information on how to obtain copies of this manual. 1.4 Getting Help...
  • Page 8 Introduction This page intentionally left blank. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 1−4 EATON Powerware ®...
  • Page 9: Getting Started

    NOTE Startup and operational checks should be performed only by authorized service personnel. This service is usually offered as part of the sales contract for your UPS system. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 2−1 EATON Powerware ®...
  • Page 10: Preparing Your Site

    Powerware 9315 UPS (200–300 kVA) Operation Manual. If you intend to operate the UPS at an altitude higher than 1500m (5000 ft), contact your Eaton service representative for important information about high altitude operation. The operating environment must meet the size and weight requirements shown in Table N on page A−13.
  • Page 11: Inspecting And Unpacking Each Cabinet

    1. Carefully inspect the outer packaging for evidence of damage during transit. C A U T I O N Do not install a damaged cabinet. Report any damage to the carrier and your Eaton service representative immediately. 2. Use a forklift or other material handling equipment to move the cabinet to a convenient unpacking area.
  • Page 12 Getting Started This page intentionally left blank. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 2−4 EATON Powerware ®...
  • Page 13: Installing The Ups

    The UPS cabinet is bolted to a sheet metal pallet consisting of four supports secured to foam cushions. The foam cushions act as shock absorbers for the cabinet during shipment and movement to the installed location. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 3−1 EATON Powerware ®...
  • Page 14: Figure 3-1. Removable I/O Section

    4. Insert the forklift jacks in the forklift slots and raise the UPS cabinet until the foam cushions clear the floor by approximately 3 mm (1/8″). 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 3−2 EATON Powerware ®...
  • Page 15: Figure 3-2. Removing Front And Rear Supports

    (labeled 2" in Figure 3-2). Discard or recycle the hardware and support brackets in a responsible manner. 8. Repeat Steps 1 through 7 for each cabinet you are preparing to install. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 3−3 EATON Powerware ®...
  • Page 16: Prepare For Installing Optional Cabinets Or Accessories

    NOTE A bypass neutral feeder must be supplied when the output neutral is used. If no bypass neutral is supplied, the output neutral is to be bonded to ground through a minimum 3/0 copper conductor. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 3−4 EATON Powerware ®...
  • Page 17: Figure 3-3. Preparing The Ups For Installation

    NOTE A bypass neutral feeder must be supplied when the output neutral is used. If no bypass neutral is supplied, the output neutral is to be bonded to ground through a minimum 3/0 copper conducter. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 3−5 EATON Powerware ®...
  • Page 18: Completing The Installation Checklist

    You should make a copy of the installation checklist before filling it out, and retain the original. After the installation is complete, your Eaton service representative will be able to verify the operation of the UPS system and commission it to support the critical load. The service representative cannot perform any installation tasks other than verifying software and operating setup parameters and installing an optional external modem or internal X−Slot...
  • Page 19: Installation Checklist

    - System Load Sync Control is mounted in its installation location and wired appropriately. (OPTIONAL) - Maintenance Bypass is mounted in place and wired appropriately. (OPTIONAL) - Circuit breakers with adjustable trip mechanisms are adjusted to match site requirements. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 3−7 EATON Powerware ®...
  • Page 20 Installing the UPS Notes _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 3−8 EATON Powerware ®...
  • Page 21: Installing Battery Cabinets

    When replacing batteries, use the same number of sealed, lead-acid batteries. Proper disposal of batteries is required. Refer to your local codes for disposal requirements. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 4−1 EATON Powerware ®...
  • Page 22 If you are installing battery cabinets not provided by Powerware, refer to the battery cabinet manufacturer’s operating manual for instructions on battery cabinet installation and maintenance. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 4−2 EATON Powerware ®...
  • Page 23: Recycling The Used Battery Or Ups

    C A U T I O N Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 4−3 EATON Powerware ®...
  • Page 24 Installing Battery Cabinets This page intentionally left blank. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 4−4 EATON Powerware ®...
  • Page 25: Installing Input And Output Transformers

    Front View Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Figure 5-1. Input Transformer Cabinet 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 5−1 EATON Powerware ®...
  • Page 26: Figure 5-2. Input Transformer Cabinet (208/480V)

    Installing Input and Output Transformers Customer Input Area Top View Front View Figure 5-2. Input Transformer Cabinet (208/480V) 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 5−2 EATON Powerware ®...
  • Page 27: Figure 5-3. Output Transformer Cabinet (480/208V)

    Installing Input and Output Transformers Customer Input Area (Top) Top View Front View Figure 5-3. Output Transformer Cabinet (480/208V) 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 5−3 EATON Powerware ®...
  • Page 28 Figure 5-5 for the location of connection points within the cabinets. 4. Close the rectifier input transformer cabinet doors and the bypass input transformer cabinet doors. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 5−4 EATON Powerware ®...
  • Page 29 Connection point in UPS Phase Input Output ∅ A ∅ B ∅ C Neutral 4. Close the UPS cabinet doors and the output transformer cabinet door. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 5−5 EATON Powerware ®...
  • Page 30: Figure 5-4. Installing An Input Transformer Cabinet

    Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Front Figure 5-4. Installing an Input Transformer Cabinet 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 5−6 EATON Powerware ®...
  • Page 31: Figure 5-5. Installing A 208/480 Vac Input Transformer Cabinet

    Installing Input and Output Transformers AC Output Output AC Input to UPS Input Neutral to Transformer Neutral Front Figure 5-5. Installing a 208/480 Vac Input Transformer Cabinet 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 5−7 EATON Powerware ®...
  • Page 32: Figure 5-6. Installing A 480/208 Vac Output Transformer Cabinet

    Installing Input and Output Transformers AC Input to Transformer AC Output to UPS Ground Neutral Front Figure 5-6. Installing a 480/208 Vac Output Transformer Cabinet 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 5−8 EATON Powerware ®...
  • Page 33: Installing A Power Distribution Module

    Distribution Module Installation and Operation Manual for PDM installation and operation. NOTE This option requires a UPS with a 208 Vac output. Figure 6-1. Typical PDM Cabinet 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 6−1 EATON Powerware ®...
  • Page 34 Installing a Power Distribution Module This page intentionally left blank. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 6−2 EATON Powerware ®...
  • Page 35: Installing A Remote Emergency Power−Off

    Table 7-1. Remote EPO Wire Terminations From Remote EPO Station(s) To Communication Panel in UPS Remarks TB1−4 TB2−1 Twisted wires (2) 14−18 gauge TB1−5 TB2−2 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 7−1 EATON Powerware ®...
  • Page 36: Figure 7-2. Remote Epo

    Figure 7-2. Remote EPO switch wiring must be in accordance with UL Class II requirements. 6. Secure the UPS by reversing all steps taken to prepare it for Remote EPO installation. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 7−2 EATON Powerware ®...
  • Page 37: Installing A Remote Battery Disconnect

    3 (UV trip) must be connected to the DC source disconnect device(s). For battery switch dimensions, see Drawing 164201037−14 on page A−38. Side Front Figure 8-1. Remote Battery Disconnect Enclosure 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 8−1 EATON Powerware ®...
  • Page 38 UPS Model DC Voltage Circuit Breaker Rating 0.8 load pF 0.9 load pF Powerware 9315 200 Powerware 9315 225 Powerware 9315 250 Powerware 9315 300 1000 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 8−2 EATON Powerware ®...
  • Page 39: Installing A Remote Monitor Panel

    Table 9-1. Optional Monitoring Accessories Number and Type of Accessories Permitted Remote Monitor Panel Relay Interface Module Supervisory Contact Module 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 9−1 EATON Powerware ®...
  • Page 40: Figure 9-1. Remote Monitor Panel

    Installing a Remote Monitor Panel Flush Mount Surface Mount (for Hanging) Wires Must be Twisted Figure 9-1. Remote Monitor Panel 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 9−2 EATON Powerware ®...
  • Page 41: Figure 9-2. Terminal Block Bracket

    Communication Panel. Connect to Port 1 (DB−9) on Communication Panel Fuse Terminal Block (TB3) Figure 9-2. Terminal Block Bracket 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 9−3 EATON Powerware ®...
  • Page 42: Figure 9-3. Wiring An Rmp To The Ups

    RMP continues to self-test, replace the fuse with the spare included in the hardware kit. If this does not correct the problem, contact your Eaton service representative for verification that the RMP is working correctly.
  • Page 43 8. If you are installing an RIM or SCM in addition to an RMP, proceed to Chapter 10 or 11, respectively; otherwise, secure the UPS cabinet by reversing the steps on page 3−4. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 9−5 EATON Powerware ®...
  • Page 44 Installing a Remote Monitor Panel This page intentionally left blank. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 9−6 EATON Powerware ®...
  • Page 45: Installing A Relay Interface Module

    DB−9 connector on the Communication Panel of the UPS (see Figure 10-3). Use two screws from the spare parts kit to secure the terminal block bracket to the Communication Panel. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 10−1 EATON Powerware ®...
  • Page 46: Figure 10-2. Terminal Block Bracket

    Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó Figure 10-3. Wiring an RIM to the UPS 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 10−2 EATON Powerware ®...
  • Page 47 4. Connect RIM wiring to the terminal block using the terminations shown in Table 10-1. 5. Contact your Eaton service representative for verification and testing of the RIM and its connections prior to making connections with J1 through J4. You can order interface cables separately for connecting to the 15-Pin D-Sub Connectors.
  • Page 48 Installing a Relay Interface Module This page intentionally left blank. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 10−4 EATON Powerware ®...
  • Page 49: Installing A Supervisory Contact Module

    DB−9 connector on the Communication Panel of the UPS (see Figure 11-3). Use two screws from the spare parts kit to secure the terminal block bracket to the Communication Panel. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 11−1 EATON Powerware ®...
  • Page 50: Figure 11-2. Terminal Block Bracket

    4. Connect the SCM wiring to the terminal block using the terminations shown in Table 11-1. 5. Contact your Eaton service representative for verification and testing of the SCM and its connections prior to making connections to terminal strip shown in Figure 11-4.
  • Page 51 TB1−7 TB3−4 From SCM B (if used) To UPS Remarks TB1−4 TB3−5 TB1−5 TB3−6 Twisted wires (4) 1−2 turns per 3″ TB1−6 TB3−7 TB1−7 TB3−8 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 11−3 EATON Powerware ®...
  • Page 52: Figure 11-4. Supervisory Contact Module Tb2

    NOTE Supervisory contacts are rated at 2.0A at 28 Vdc or 120 Vac and 0.15A at 115 Vdc. NOTE Supervisory contacts require external an power supply. Internal 24 Vdc is not capable of supplying contact current. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com 11−4 EATON Powerware ®...
  • Page 53: Appendix A Customer Information

    164201037−9 Maintenance Bypass Module 164201037−10 Remote Emergency Power Off 164201037−11 Remote Monitor Panel 164201037−12 Relay Interface Module 164201037−13 Supervisory Contact Module 164201037−14 Battery Disconnect Switch 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−1 EATON Powerware ®...
  • Page 54 DESCRIPTION: INSTALLATION NOTES NOTE: Callout letters DRAWING NO: SHEET: map to drawing #164201037−3 164201037−1 1 of 17 400V = 380/400/415 Volt REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−2 EATON Powerware ®...
  • Page 55 AWG or kcmil(ea) 350(3) 3/0(2) DESCRIPTION: INSTALLATION NOTES NOTE: Callout letters DRAWING NO: SHEET: map to drawing #164201037−3 164201037−1 2 of 17 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−3 EATON Powerware ®...
  • Page 56 Minimum conductor size (number per O) DESCRIPTION: INSTALLATION NOTES NOTE: Callout letters DRAWING NO: SHEET: 164201037−1 3 of 17 map to drawing #164201037−3 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−4 EATON Powerware ®...
  • Page 57 250(2) DESCRIPTION: INSTALLATION NOTES NOTE: Callout letters DRAWING NO: SHEET: map to drawing #164201037−3 164201037−1 4 of 17 400V = 380/400/415 Volt REVISION: DATE: 051506 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−5 EATON Powerware ®...
  • Page 58 AWG or kcmil(ea) 350(3) 3/0(2) DESCRIPTION: INSTALLATION NOTES NOTE: Callout letters DRAWING NO: SHEET: 164201037−1 5 of 17 map to drawing #164201037−3 REVISION: DATE: 051506 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−6 EATON Powerware ®...
  • Page 59 Minimum conductor size (number per O) DESCRIPTION: INSTALLATION NOTES NOTE: Callout letters DRAWING NO: SHEET: 164201037−1 6 of 17 map to drawing #164201037−3 REVISION: DATE: 051506 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−7 EATON Powerware ®...
  • Page 60 NOTE: Customer ground, size 2/0, can be run in any conduit listed in Table G DRAWING NO: SHEET: 164201037−1 7 of 17 and Table H. REVISION: C DATE: 121598 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−8 EATON Powerware ®...
  • Page 61 NOTE: Customer ground, size 2/0, can be run in any conduit listed in Table G. DRAWING NO: SHEET: 164201037−1 8 of 17 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−9 EATON Powerware ®...
  • Page 62 DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 164201037−1 9 of 17 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−10 EATON Powerware ®...
  • Page 63 AC output to critical load shown in Table B through Table F. The recommended line-to-line load unbalance is 50% or less. DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 164201037−1 10 of 17 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−11 EATON Powerware ®...
  • Page 64 0.9 load pF Model 200 Model 225 Model 250 Model 300 1000 DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 164201037−1 11 of 17 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−12 EATON Powerware ®...
  • Page 65 8 at 214 (471) Series 1085−J47 2178 (4800) 8 at 272 (600) DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 164201037−1 12 of 17 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−13 EATON Powerware ®...
  • Page 66 Regardless of assignment, alarms display as Building Alarm 1, Building Alarm 2, etc., on the Monitor Panel. Use twisted-pair wires for each alarm input and common. DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 164201037−1 13 of 17 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−14 EATON Powerware ®...
  • Page 67 RELAY 2 NC General purpose NO and NC relay contacts. NOTICE RTN DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 164201037−1 14 of 17 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−15 EATON Powerware ®...
  • Page 68 CONTACT RATING: Maximum Switched Voltage 32 VAC 42 VDC Maximum Carrying Current DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 164201037−1 15 of 17 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−16 EATON Powerware ®...
  • Page 69 NOTE: This switch must be a dedicated switch, and not tied into any other circuits. DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 164201037−1 16 of 17 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−17 EATON Powerware ®...
  • Page 70 NOTE: For other than Powerware battery cabinets that use UV trip coils, connect to TB4 Pin 3 instead of TB4 Pin 2. DESCRIPTION: INSTALLATION NOTES DRAWING NO: SHEET: 164201037−1 17 of 17 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−18 EATON Powerware ®...
  • Page 71 UPS cabinet. DESCRIPTION: TYPICAL UPS SYSTEM DRAWING NO: SHEET: 164201037−2 1 of 1 REVISION: DATE: 020497 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−19 EATON Powerware ®...
  • Page 72 Sheet 4 208/208 Auto (Dual Feed) (Wye in, Wye out) DESCRIPTION: UPS SYSTEM ONELINE CONFIGURATIONS DRAWING NO: SHEET: 164201037−3 1 of 1 REVISION: DATE: 041500 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−20 EATON Powerware ®...
  • Page 73 NOTE 2: See Table U to determine when an input DESCRIPTION: ONELINE DRAWINGS OF UPS SYSTEM transformer is required. DRAWING NO: SHEET: 164201037−4 1 of 4 REVISION: DATE: 082806 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−21 EATON Powerware ®...
  • Page 74 NOTE 2: See Table U to determine when an input DESCRIPTION: ONELINE DRAWINGS OF UPS SYSTEM transformer is required. DRAWING NO: SHEET: 164201037−4 2 of 4 REVISION: DATE: 082806 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−22 EATON Powerware ®...
  • Page 75 ONELINE DRAWINGS OF UPS SYSTEM conductor. DRAWING NO: SHEET: 164201037−4 3 of 4 NOTE 2: See Table U to determine when an input REVISION: DATE: transformer is required. 082806 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−23 EATON Powerware ®...
  • Page 76 ONELINE DRAWINGS OF UPS SYSTEM conductor. DRAWING NO: SHEET: 164201037−4 4 of 4 NOTE 2: See Table U to determine when an input REVISION: DATE: transformer is required. 082806 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−24 EATON Powerware ®...
  • Page 77 AC OUTPUT RS−232 (E9, E10, E11) COMMUNICATION CONNECTION PANEL DESCRIPTION: LOCATION OF UPS POWER TERMINALS DRAWING NO: SHEET: 164201037−5 1 of 1 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−25 EATON Powerware ®...
  • Page 78 (65.1) 1866.1 (73.5) (13.1) 484.4 (19.1) (28.9) Dimensions are in millimeters (inches) DESCRIPTION: UPS CABINET DRAWING NO: SHEET: 164201037−6 1 of 2 REVISION: DATE: 020497 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−26 EATON Powerware ®...
  • Page 79 (9.0) (16.17) (23.15) Dimensions are in millimeters (inches) UPS CABINET DESCRIPTION: BOTTOM UPS CABINET DRAWING NO: SHEET: VIEW 164201037−6 2 of 2 REVISION: DATE: 020497 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−27 EATON Powerware ®...
  • Page 80: Front View

    Ó Ó Ó Ó Ó Ó Ó Ó Ó Ó FRONT VIEW Dimensions are in millimeters (inches) DESCRIPTION: TRANSFORMER CABINETS DRAWING NO: SHEET: 164201037−7 1 of 3 REVISION: DATE: 113004 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−28 EATON Powerware ®...
  • Page 81 (47.2) INPUT ISOLATION TRANSFORMER CABINET (208/480) DESCRIPTION: TRANSFORMER CABINETS DRAWING NO: SHEET: 164201037−7 2 of 3 REVISION: C DATE: Dimensions are in millimeters (inches) 121598 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−29 EATON Powerware ®...
  • Page 82 (47.2) OUTPUT AUTO TRANSFORMER CABINET (480/208) DESCRIPTION: TRANSFORMER CABINETS DRAWING NO: SHEET: 164201037−7 3 of 3 REVISION: C DATE: Dimensions are in millimeters (inches) 121598 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−30 EATON Powerware ®...
  • Page 83 POWER DISTRIBUTION MODULE Distribution Module Installation and DRAWING NO: SHEET: Operation Manual 164201061 for 164201037−8 1 of 1 PDM installation and operation. REVISION: D DATE: 041500 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−31 EATON Powerware ®...
  • Page 84 Module (MBM) Installation and Operation Manual 164201233 for MBM installation and operation. DESCRIPTION: MAINTENANCE BYPASS MODULE DRAWING NO: SHEET: 164201037−9 1 of 1 REVISION: D DATE: 041500 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−32 EATON Powerware ®...
  • Page 85 TO OTHER TO UPS Dimensions are in millimeters (inches) EQUIPMENT DESCRIPTION: REMOTE EMERGENCY POWER OFF DRAWING NO: SHEET: 164201037−10 1 of 1 REVISION: D DATE: 041500 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−33 EATON Powerware ®...
  • Page 86 (14−18 gauge) EXCEED 500 FEET. Dimensions are in millimeters (inches) DESCRIPTION: REMOTE MONITOR PANEL DRAWING NO: SHEET: 164201037−11 1 of 1 REVISION: D DATE: 041500 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−34 EATON Powerware ®...
  • Page 87 MIN WIRE SIZE NO. 18 AWG. Dimensions are in millimeters (inches) DESCRIPTION: RELAY INTERFACE MODULE DRAWING NO: SHEET: 164201037−12 1 of 2 REVISION: D DATE: 041500 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−35 EATON Powerware ®...
  • Page 88 KNOCKOUTS PROVIDED ON FIVE SURFACES Dimensions are in millimeters (inches) DESCRIPTION: RELAY INTERFACE MODULE DRAWING NO: SHEET: 164201037−12 2 of 2 REVISION: D DATE: 041500 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−36 EATON Powerware ®...
  • Page 89 REMOTE MONITOR AND UPS NOT TO EXCEED 500 FEET. Dimensions are in millimeters (inches) DESCRIPTION: SUPERVISORY CONTACT MODULE DRAWING NO: SHEET: 164201037−13 1 of 1 REVISION: D DATE: 041500 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−37 EATON Powerware ®...
  • Page 90 KNOCKOUTS TO BE DETERMINED AT 75 LBS (34 KG) TIME OF INSTALLATION. DESCRIPTION: BATTERY DISCONNECT SWITCH DRAWING NO: SHEET: 164201037−14 1 of 2 REVISION: A DATE: 010198 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−38 EATON Powerware ®...
  • Page 91 Customer Information TYPE K1200 BREAKER OUTLINE DESCRIPTION: BATTERY DISCONNECT SWITCH DRAWING NO: SHEET: 164201037−14 2 of 2 REVISION: A DATE: 010198 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−39 EATON Powerware ®...
  • Page 92 Customer Information This page intentionally left blank. 9315 UPS (200–300 kVA) Installation Manual S 164201037 Rev G www.powerware.com A−40 EATON Powerware ®...
  • Page 94 *164201037G* 164201037 G...