DPH Series 50 - 300/500 kVA (480 V)

The world's leading power density in a compact footprint provides the ultimate in UPS power protection

In this IT intensive world with heavy data traffic driven by the cloud, 4G/5G and media streaming applications, IT managers are facing the challenges of increasing rack power density and limited datacenter space. Delta’s innovative modularized UPS technologies provide the answer to customers’ demand for high power density, high power performance, and ultimate availability. The brand-new Delta Modulon DPH series UPS achieves the industry’s leading power density of 50 kVA / 50 kW per module, offering the smallest footprint and best space utilization. The Modulon DPH UPS is the ideal power protection for datacenters to achieve total cost of ownership (TCO) optimization.

DPH series 50-500kVA UPS - Applications
Product available regions:

North America Latin America
(50–300/500/600 kVA)


Downloads Request a Quote Subscribe Newsletter
 

Product Introduction

Features & Benefits

Excellent Power Performance

  • The industry‘s leading power density per module at 50 kVA in a 3U space, and the smallest footprint for 300 kVA in a single rack, achieves the best utilization compared with its peers
  • High AC-AC efficiency up to 97% and ECO mode to 99% results in marked energy cost savings with Energy Star 2.0 certification
  • Green mode features a load aggregation function that optimizes system efficiency

Ultimate Availability

  • Fully modularized design and easy-swappable key modules ensure the minimum Mean Time To Repair (MTTR)
  • Redundancy components and dual CAN bus deliver highest system availability and avoid single point of failure
  • Modularized UPS grows with your business by parallel expansion up to 4 units for 2 MVA of total power capacity
  • Key components preventive maintenance reduces the risk of drop load

High Manageability

  • User-friendly 10” color touch screen enables easy local UPS management
  • Inbuilt with remote access via SNMP, Modbus TCP/IP and Modbus RTU protocols
  • Environment information such as security, water, fire, and temperature can be integrated into the UPS for easy monitoring via the LCD of the UPS
  • Inbuilt waveform recorder captures failure symptoms of critical events for further diagnosis
Applications

UPS DPH Series applications

Specifications
  1. Model
  2. DPH-300K-HV / DPH-500K-HV

  3. Power Rating
  4. DPH-300K-HV
    50-300 kVA/kW
    50 kW Power Module Quantity: Up to 6 units
  5. DPH-500K-HV
    50-500 kVA/kW
    50 kW Power Module Quantity: Up to 10 units

  6. Input
  7. Nominal Voltage: 480 V (3-phase, 3-wire + G)
  8. Voltage Range: 408~552 Vac (full load)
  9. Current Harmonic Distortion: ≤ 2.5% *
  10. Power Factor: > 0.99
  11. Frequency Range: 40~70 Hz

  12. Output
  13. Voltage: 480 V (3-phase, 3-wire + G)
  14. Voltage Harmonic Distortion: ≤ 0.5% (linear load)
  15. Voltage Regulation: ± 1% (static)
  16. Frequency: 50/60 Hz ± 0.05 Hz
  17. Overload Capability:
    ≤ 105%: continuously
     > 105~110%: 60 minutes
    > 110~125%: 10 minutes
    > 125~≤ 150%: 1 minute

  18. Display: 10” color touch screen

  19. Interface
  20. Standard
    Parallel port x 4, USB Type A x 2, USB Type B x 1, Modbus port x 1, Ethernet x 1, RS232 x 1, REPO x 1, Input dry contact x 4, Output dry contact x 6, Battery temperature sensor x 4, External switch detection x 4, Smart card slot x 1
  21. Optional
    Relay I/O card, Battery cabinet temperature sensor cable

  22. Efficiency
  23. AC-AC Mode: Up to 97%
  24. ECO Mode: 99%

  25. Battery
  26. Nominal Voltage: 480 Vdc (Default, adjustable from 360 Vdc to 552 Vdc)
  27. Charge Voltage: 544 Vdc (Default, adjustable from 408 Vdc to 624 Vdc)
  28. Protection of Battery Deep Discharge: Yes

  29. Environment
  30. Operating Temperature: 0~40℃
  31. Relative Humidity: 0~95% (non-condensing)
  32. Audible Noise: < 75 dB **
  33. IP Protection: IP20

  34. Others
  35. Parallel Redundancy and Expansion: Module and system redundancy, Maximum 4 units
  36. Emergency Power Off: Remote (default)
  37. Battery Start: Yes

  38. Physical
  39. Dimensions (W x D x H)
    DPH-300K-HV: 23.62 x 33.46 x 78.74 in
    DPH-500K-HV: 55.12 x 33.46 x 78.74 in (default), 55.12 x 43.31 x 78.74 in (against the wall)
  40. Weight: UPS System (without power modules)
    DPH-300K-HV: 588.6 lbs
    DPH-500K-HV: 1162.3 lbs
  41. Weight: 50 kW Power Module (optional)
    78.26 lbs

  42. * When input vTHD is less than 1%.
    ** At a distance of 3.28 ft (1 meter) of the UPS

    All specifications are subject to change without prior notice.