TRANSIENTS IN ELECTRICAL SYSTEMS
ANALYSIS, RECOGNITION, AND MITIGATION
J. C. Das
New York Chicago San Francisco Lisbon London Madrid
Mexico City Milan New Delhi San Juan Seoul
Singapore Sydney Toronto
Copyright © 2010 by The McGraw-Hill Companies, Inc. All rights reserved. Except as permitted under the United States Copyright Act of 1976, no part of
this publication may be reproduced or distributed in any form or by any means, or stored in a database or retrieval system, without the prior written permission of the publisher.
ISBN: 978-0-07-162603-3
MHID: 0-07-162603-4
The material in this eBook also appears in the print version of this title: ISBN: 978-0-07-162248-6,
MHID: 0-07-162248-9.
All trademarks are trademarks of their respective owners. Rather than put a trademark symbol after every occurrence of a trademarked name, we use names
in an editorial fashion only, and to the benefit of the trademark owner, with no intention of infringement of the trademark. Where such designations appear in
this book, they have been printed with initial caps.
McGraw-Hill eBooks are available at special quantity discounts to use as premiums and sales promotions, or for use in corporate training programs. To contact
a representative please e-mail us at bulksales@mcgraw-hill.com.
Information contained in this work has been obtained by The McGraw-Hill Companies, Inc. (“McGraw-Hill”) from sources believed to be reliable. However,
neither McGraw-Hill nor its authors guarantee the accuracy or completeness of any information published herein, and neither McGraw-Hill nor its authors
shall be responsible for any errors, omissions, or damages arising out of use of this information. This work is published with the understanding that McGrawHill and its authors are supplying information but are not attempting to render engineering or other professional services. If such services are required, the
assistance of an appropriate professional should be sought.
TERMS OF USE
This is a copyrighted work and The McGraw-Hill Companies, Inc. (“McGrawHill”) and its licensors reserve all rights in and to the work. Use of this work is
subject to these terms. Except as permitted under the Copyright Act of 1976 and the right to store and retrieve one copy of the work, you may not decompile,
disassemble, reverse engineer, reproduce, modify, create derivative works based upon, transmit, distribute, disseminate, sell, publish or sublicense the work or
any part of it without McGraw-Hill’s prior consent. You may use the work for your own noncommercial and personal use; any other use of the work is strictly
prohibited. Your right to use the work may be terminated if you fail to comply with these terms.
THE WORK IS PROVIDED “AS IS.” McGRAW-HILL AND ITS LICENSORS MAKE NO GUARANTEES OR WARRANTIES AS TO THE ACCURACY, ADEQUACY OR COMPLETENESS OF OR RESULTS TO BE OBTAINED FROM USING THE WORK, INCLUDING ANY INFORMATION THAT
CAN BE ACCESSED THROUGH THE WORK VIA HYPERLINK OR OTHERWISE, AND EXPRESSLY DISCLAIM ANY WARRANTY, EXPRESS OR
IMPLIED, INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
McGraw-Hill and its licensors do not warrant or guarantee that the functions contained in the work will meet your requirements or that its operation will be
uninterrupted or error free. Neither McGraw-Hill nor its licensors shall be liable to you or anyone else for any inaccuracy, error or omission, regardless of
cause, in the work or for any damages resulting therefrom. McGraw-Hill has no responsibility for the content of any information accessed through the work.
Under no circumstances shall McGraw-Hill and/or its licensors be liable for any indirect, incidental, special, punitive, consequential or similar damages that
result from the use of or inability to use the work, even if any of them has been advised of the possibility of such damages. This limitation of liability shall
apply to any claim or cause whatsoever whether such claim or cause arises in contract, tort or otherwise.
To My Parents
ABOUT THE AUTHOR
J. C. Das is currently Staff Consultant, Electrical Power Systems,
AMEC Inc., Tucker, Georgia, USA. He has varied experience in
the utility industry, industrial establishments, hydroelectric generation, and atomic energy. He is responsible for power system
studies, including short-circuit, load flow, harmonics, stability, arcflash hazard, grounding, switching transients, and also, protective
relaying. He conducts courses for continuing education in power
systems and has authored or coauthored about 60 technical publications. He is author of the book Power System Analysis, Short-Circuit,
Load Flow and Harmonics (New York, Marcel Dekker, 2002); its
second edition is forthcoming. His interests include power system
transients, EMTP simulations, harmonics, power quality, protection,
and relaying. He has published 185 electrical power systems study
reports for his clients.
He is a Life Fellow of the Institute of Electrical and Electronics
Engineers, IEEE (USA), a member of the IEEE Industry Applications
and IEEE Power Engineering societies, a Fellow of Institution of Engineering Technology (UK), a Life Fellow of the Institution of Engineers
(India), a member of the Federation of European Engineers (France),
and a member of CIGRE (France). He is a registered Professional
Engineer in the states of Georgia and Oklahoma, a Chartered Engineer
(C. Eng.) in the UK, and a European Engineer (Eur. Ing.).
He received a MSEE degree from Tulsa University, Tulsa, Oklahoma
in 1982 and BA (mathematics) and BEE degrees in India.
CONTENTS
Preface
xiii
CHAPTER 3 CONTROL SYSTEMS
CHAPTER 1 INTRODUCTION TO TRANSIENTS
1-1
Classification of Transients 1
1-2 Classification with Respect to Frequency
Groups 1
1-3
Frequency-Dependent Modeling 2
1-4
Other Sources of Transients 3
1-5
Study of Transients
1-6
TNAs—Analog Computers 3
3
1-7 Digital Simulations, EMTP/ATP, and Similar
Programs 3
References
4
Further Reading
3-1 Transfer Function
33
3-2 General Feedback Theory 35
3-3 Continuous System Frequency Response 38
3-4 Transfer Function of a Discrete-Time System 38
3-5 Stability 39
3-6 Block Diagrams 41
3-7 Signal-Flow Graphs 41
3-8 Block Diagrams of State Models 44
3-9 State Diagrams of Differential Equations
45
3-10 Steady-State Errors 47
3-11 Frequency-Domain Response Specifications 49
4
3-12 Time-Domain Response Specifications 49
3-13 Root-Locus Analysis 50
CHAPTER 2 TRANSIENTS IN LUMPED CIRCUITS
3-14 Bode Plot 55
2-1
Lumped and Distributed Parameters 5
3-15 Relative Stability 58
2-2
Time Invariance
3-16 The Nyquist Diagram 60
2-3
Linear and Nonlinear Systems 5
3-17 TACS in EMTP 61
2-4
Property of Decomposition 6
Problems 61
2-5
Time Domain Analysis of Linear Systems 6
References 63
2-6
Static and Dynamic Systems 6
Further Reading 63
2-7
Fundamental Concepts 6
2-8
First-Order Transients 11
CHAPTER 4 MODELING OF TRANSMISSION LINES AND CABLES
FOR TRANSIENT STUDIES
2-9
Second-Order Transients 15
4-1 ABCD Parameters
5
65
2-10
Parallel RLC Circuit 18
4-2 ABCD Parameters of Transmission Line Models
2-11
Second-Order Step Response 21
4-3 Long Transmission Line Model-Wave Equation
2-12 Resonance in Series and Parallel
RLC Circuits 21
2-13 Loop and Nodal Matrix Methods for Transient
Analysis 24
2-14
State Variable Representation 25
2-15
Discrete-Time Systems 28
2-16 State Variable Model of a Discrete
System 30
2-17
Linear Approximation 30
4-4 Reflection and Transmission at Transition Points
4-5 Lattice Diagrams
70
4-6 Behavior with Unit Step Functions at Transition
Points 72
4-7 Infinite Line 74
4-8 Tuned Power Line
74
4-9 Ferranti Effect 74
4-10 Symmetrical Line at No Load 75
31
4-11 Lossless Line 77
Reference
32
4-12 Generalized Wave Equations 77
32
67
71
Problems
Further Reading
67
4-13 Modal Analysis 77
v
vi CONTENTS
4-14
Damping and Attenuation 79
6-12 Interruptions of Capacitance Currents 144
4-15
Corona 79
6-13 Control of Switching Transients
4-16
Transmission Line Models for Transient Analysis
4-17
Cable Types
Problems
References
81
85
6-14 Shunt Capacitor Bank Arrangements
References 153
89
Further Reading 153
89
CHAPTER 5 LIGHTNING STROKES,
AND BACKFLASHOVERS
CHAPTER 7 SWITCHING TRANSIENTS AND
TEMPORARY OVERVOLTAGES
SHIELDING,
7-1 Classification of Voltage Stresses 155
7-2 Maximum System Voltage 155
5-1
Formation of Clouds
5-2
Lightning Discharge Types 92
7-3 Temporary Overvoltages 156
5-3
The Ground Flash
7-4 Switching Surges 157
5-4
Lightning Parameters
5-5
Ground Flash Density and Keraunic Level
5-6
Lightning Strikes on Overhead lines
5-7
BIL/CFO of Electrical Equipment 100
5-8
Frequency of Direct Strokes to Transmission Lines 102
5-9
Direct Lightning Strokes 104
91
92
7-5 Switching Surges and System Voltage 157
94
5-10
Lightning Strokes to Towers 104
5-11
Lightning Stroke to Ground Wire
7-6 Closing and Reclosing of Transmission Lines 158
98
7-7 Overvoltages Due to Resonance 164
99
7-8 Switching Overvoltages of Overhead Lines and
Underground Cables 165
7-9 Cable Models 166
7-10 Overvoltages Due to Load Rejection 168
7-11 Ferroresonance 169
107
7-12 Compensation of Transmission Lines
5-12 Strokes to Ground in Vicinity of Transmission
Lines 107
7-13 Out-of-Phase Closing
5-13
Shielding
7-14 Overvoltage Control 173
5-14
Shielding Designs
5-15
Backflashovers
Problems
References
108
7-15 Statistical Studies
110
169
173
175
Problems 179
113
References 180
117
Further Reading 180
121
Further Reading
150
Problems 152
89
Further Reading
147
121
CHAPTER 8 CURRENT INTERRUPTION IN AC CIRCUITS
CHAPTER 6 TRANSIENTS OF SHUNT CAPACITOR BANKS
8-1 Arc Interruption 181
8-2 Arc Interruption Theories 182
6-1
Origin of Switching Transients 123
6-2
Transients on Energizing a Single Capacitor Bank 123
8-3 Current-Zero Breaker
182
8-4 Transient Recovery Voltage
6-3 Application of Power Capacitors with Nonlinear
Loads 126
183
8-5 Single-Frequency TRV Terminal Fault 186
6-4
Back-to-Back Switching 133
8-6 Double-Frequency TRV 189
6-5
Switching Devices for Capacitor Banks 134
8-7 ANSI/IEEE Standards for TRV
6-6
Inrush Current Limiting Reactors 135
8-8 IEC TRV Profiles 193
6-7
Discharge Currents Through Parallel Banks 136
8-9 Short-Line Fault 195
6-8
Secondary Resonance 136
8-10 Interruption of Low Inductive Currents
6-9
Phase-to-Phase Overvoltages 139
8-11 Interruption of Capacitive Currents 200
6-10
Capacitor Switching Impact on Drive Systems
6-11
Switching of Capacitors with Motors 140
140
8-12 Prestrikes in Circuit Breakers
8-13 Breakdown in Gases 200
191
200
197
CONTENTS vii
8-14
Stresses in Circuit Breakers
Problems
References
204
CHAPTER 11 TRANSIENT BEHAVIOR OF INDUCTION AND
SYNCHRONOUS MOTORS
205
11-1 Transient and Steady-State Models of Induction
Machines 265
206
Further Reading
206
11-2 Induction Machine Model with Saturation 270
CHAPTER 9 SYMMETRICAL AND UNSYMMETRICAL
SHORT-CIRCUIT CURRENTS
11-3 Induction Generator 271
9-1
Symmetrical and Unsymmetrical Faults 207
11-5 Short-Circuit Transients of an Induction Motor 274
9-2
Symmetrical Components 208
11-6 Starting Methods 274
9-3 Sequence Impedance of Network
Components 210
11-7 Study of Starting Transients 278
11-8 Synchronous Motors
9-4 Fault Analysis Using Symmetrical
Components 211
9-6
Computer-Based Calculations 224
9-7
Overvoltages Due to Ground Faults 224
References
Problems
288
References 291
Further Reading 291
CHAPTER 12 POWER SYSTEM STABILITY
232
12-1 Classification of Power System Stability 293
233
Further Reading
280
11-9 Stability of Synchronous Motors 284
9-5 Matrix Methods of Short-Circuit Current
Calculations 221
Problems
11-4 Stability of Induction Motors on Voltage Dips 271
12-2 Equal Area Concept of Stability
233
295
12-3 Factors Affecting Stability 297
CHAPTER 10 TRANSIENT BEHAVIOR OF SYNCHRONOUS
GENERATORS
10-1
Three-Phase Terminal Fault 235
10-2
Reactances of a Synchronous Generator 237
10-3
Saturation of Reactances 238
10-4
Time Constants of Synchronous Generators 238
12-4 Swing Equation of a Generator 298
12-5 Classical Stability Model 299
12-6
Data Required to Run a Transient Stability Study 301
12-7 State Equations 302
12-8 Numerical Techniques 302
12-9 Synchronous Generator Models for Stability 304
10-5 Synchronous Generator Behavior on Terminal
Short-Circuit 239
12-10 Small-Signal Stability 317
10-6
Circuit Equations of Unit Machines
12-11 Eigenvalues and Stability 317
10-7
Park’s Transformation 246
12-12 Voltage Stability 321
10-8
Park’s Voltage Equation 247
12-13 Load Models 324
10-9
Circuit Model of Synchronous Generators 248
12-14 Direct Stability Methods 328
10-10
244
Calculation Procedure and Examples 249
References 331
10-11 Steady-State Model of Synchronous
Generator 252
Further Reading 332
10-12 Symmetrical Short Circuit of a Generator
at No Load 253
10-13
CHAPTER 13 EXCITATION SYSTEMS AND POWER
SYSTEM STABILIZERS
Manufacturer’s Data 255
13-1 Reactive Capability Curve (Operating Chart) of a
Synchronous Generator 333
10-14 Interruption of Currents with Delayed
Current Zeros 255
10-15
Synchronous Generator on Infinite Bus
Problems
References
257
13-2 Steady-State Stability Curves 336
13-3 Short-Circuit Ratio 336
263
13-4 Per Unit Systems 337
264
Further Reading
Problems 331
264
13-5 Nominal Response of the Excitation System 337
viii CONTENTS
13-6
Building Blocks of Excitation Systems 339
15-9 Static Series Synchronous Compensator 416
13-7
Saturation Characteristics of Exciter 340
15-10 Unified Power Flow Controller 419
13-8
Types of Excitation Systems 343
15-11 NGH-SSR Damper 422
13-9
Power System Stabilizers 352
15-12 Displacement Power Factor 423
13-10
Tuning a PSS
13-11
Models of Prime Movers 358
15-14 Active Filters 425
13-12
Automatic Generation Control 358
Problems 425
13-13
On-Line Security Assessments 361
References 426
Problems
References
355
15-13 Instantaneous Power Theory 424
362
Further Reading 426
362
Further Reading
CHAPTER 16 FLICKER, BUS TRANSFER, TORSIONAL
DYNAMICS, AND OTHER TRANSIENTS
363
CHAPTER 14 TRANSIENT BEHAVIOR OF TRANSFORMERS
16-1 Flicker 429
14-1
Frequency-Dependent Models 365
16-2 Autotransfer of Loads 432
14-2
Model of a Two-Winding Transformer 365
16-3 Static Transfer Switches and Solid-State Breakers 438
14-3
Equivalent Circuits for Tap Changing
16-4 Cogging and Crawling of Induction Motors 439
14-4
Inrush Current Transients
14-5
Transient Voltages Impacts on Transformers
14-6
Matrix Representations
14-7
Extended Models of Transformers 373
16-7 Out-of-Phase Synchronization 449
14-8
EMTP Model FDBIT 380
Problems 451
14-9
Sympathetic Inrush 382
References 451
367
368
368
16-6 Torsional Dynamics 446
371
Further Reading 452
14-10
High-Frequency Models 383
14-11
Surge Transference Through Transformers 384
14-12
Surge Voltage Distribution Across Windings 389
14-13
Duality Models
14-14
GIC Models
14-15
Ferroresonance 391
14-16
Transformer Reliability 394
Problems
References
16-5 Synchronous Motor-Driven Reciprocating
Compressors 441
CHAPTER 17 INSULATION COORDINATION
17-1 Insulating Materials 453
389
17-2 Atmospheric Effects and Pollution
391
453
17-3 Dielectrics 455
17-4 Insulation Breakdown 456
17-5 Insulation Characteristics—BIL and BSL
395
17-6 Volt-Time Characteristics 461
396
Further Reading
459
17-7 Nonstandard Wave Forms 461
396
17-8 Probabilistic Concepts 462
CHAPTER 15 POWER ELECTRONIC EQUIPMENT
AND FACTS
15-1
The Three-Phase Bridge Circuits
397
15-2
Voltage Source Three-Phase Bridge 401
15-3
Three-Level Converter 402
15-4
Static VAR Compensator (SVC)
15-5
Series Capacitors
15-6
FACTS
15-7
Synchronous Voltage Source
15-8
Static Synchronous Compensator 415
405
408
17-9 Minimum Time to Breakdown
465
17-10 Weibull Probability Distribution
465
17-11 Air Clearances 465
17-12 Insulation Coordination 466
17-13 Representation of Slow Front Overvoltages
(SFOV) 469
17-14 Risk of Failure 470
414
17-15 Coordination for Fast-Front Surges 472
414
17-16 Switching Surge Flashover Rate 473
17-17 Open Breaker Position
474
CONTENTS ix
17-18
Monte Carlo Method
474
CHAPTER 20 SURGE ARRESTERS
17-19
Simplified Approach 474
20-1 Ideal Surge Arrester 525
17-20
Summary of Steps in Insulation Coordination 475
20-2 Rod Gaps
Problems
References
475
20-3 Expulsion-Type Arresters 526
476
Further Reading
20-4 Valve-Type Silicon Carbide Arresters 526
476
20-5 Metal-Oxide Surge Arresters 529
CHAPTER 18 GAS-INSULATED SUBSTATIONS—VERY FAST
TRANSIENTS
18-1
Categorization of VFT 477
18-2
Disconnector-Induced Transients
18-3
Breakdown in GIS—Free Particles
18-4
External Transients 481
20-6 Response to Lightning Surges 534
20-7 Switching Surge Durability 537
20-8 Arrester Lead Length and Separation Distance 539
477
480
20-9 Application Considerations 541
20-10 Surge Arrester Models 544
20-11 Surge Protection of AC Motors 545
18-5 Effect of Lumped Capacitance at Entrance
to GIS 482
18-6
525
Transient Electromagnetic Fields
483
483
20-12 Surge Protection of Generators 547
20-13 Surge Protection of Capacitor Banks 548
20-14 Current-Limiting Fuses 551
18-7
Breakdown in SF6
18-8
Modeling of Transients in GIS 484
References 555
18-9
Insulation Coordination
487
Further Reading 555
Surge Arresters for GIS
488
18-10
Problems
References
Problems 554
CHAPTER 21 TRANSIENTS IN GROUNDING SYSTEMS
493
21-1 Solid Grounding 557
493
Further Reading
21-2 Resistance Grounding 560
494
21-3 Ungrounded Systems 563
CHAPTER 19 TRANSIENTS AND SURGE PROTECTION
IN LOW-VOLTAGE SYSTEMS
21-4 Reactance Grounding 564
19-1
Modes of Protection 495
21-6 Grounding for Electrical Safety 569
19-2
Multiple-Grounded Distribution Systems 495
21-7 Finite Element Methods 577
19-3
High-Frequency Cross Interference
21-8 Grounding and Bonding 579
19-4
Surge Voltages
19-5
Exposure Levels
19-6
Test Wave Shapes
19-7
Location Categories
19-8
Surge Protection Devices 505
References 585
19-9
SPD Components
Further Reading 586
498
499
21-5 Grounding of Variable-Speed Drive Systems 567
21-9 Fall of Potential Outside the Grid 581
499
21-10 Influence on Buried Pipelines 583
500
21-11 Behavior Under Lightning Impulse Current 583
502
Problems 585
508
19-10
Connection of SPD Devices 512
19-11
Power Quality Problems 516
19-12
Surge Protection of Computers
19-13
Power Quality for Computers 520
22-2 Types of Structures 587
19-14
Typical Application of SPDs 520
22-3 Risk Assessment According to IEC
Problems
References
523
517
22-1 Parameters of Lightning Current 587
588
22-4 Criteria for Protection 589
523
Further Reading
CHAPTER 22 LIGHTNING PROTECTION OF STRUCTURES
22-5 Protection Measures 592
524
22-6 Transient Behavior of Grounding System 594
x CONTENTS
22-7
Internal LPS Systems According to IEC 594
22-8 Lightning Protection According to NFPA
Standard 780 594
22-9 Lightning Risk Assessment According to
NFPA 780 595
22-10
Protection of Ordinary Structures 596
22-11
NFPA Rolling Sphere Model 597
22-12
Alternate Lightning Protection Technologies 598
22-13
Is EMF Harmful to Humans? 602
Problems
References
A-6 Complementary Function and Particular Integral 649
A-7 Forced and Free Response 649
A-8 Linear Differential Equations of the Second Order (With
Constant Coefficients) 650
A-9 Calculation of Complementary Function 650
A-10 Higher-Order Equations 651
A-11 Calculations of Particular Integrals 651
A-12
602
Solved Examples 653
A-13 Homogeneous Linear Differential Equations 654
603
Further Reading
A-5 Clairaut’s Equation 649
A-14 Simultaneous Differential Equations 655
603
A-15 Partial Differential Equations 655
CHAPTER 23 DC SYSTEMS, SHORT CIRCUITS,
DISTRIBUTIONS, AND HVDC
23-1
Short-Circuit Transients 605
23-2
Current Interruption in DC Circuits
Further Reading 658
APPENDIX B LAPLACE TRANSFORM
B-1 Method of Partial Fractions 659
615
B-2 Laplace Transform of a Derivative of f (t ) 661
23-3 DC Industrial and Commercial Distribution
Systems 617
B-3 Laplace Transform of an Integral
23-4
B-4 Laplace Transform of tf (t ) 662
HVDC Transmission 618
Problems
References
B-5 Laplace Transform of (1/t ) f (t ) 662
627
B-6 Initial-Value Theorem 662
628
Further Reading
661
B-7 Final-Value Theorem 662
629
B-8 Solution of Differential Equations 662
CHAPTER 24 SMART GRIDS AND WIND POWER GENERATION
B-9 Solution of Simultaneous Differential Equations 662
24-1
WAMS and Phasor Measurement Devices 631
B-10 Unit-Step Function 663
24-2
System Integrity Protection Schemes 632
B-11 Impulse Function 663
24-3
Adaptive Protection 633
B-12 Gate Function 663
24-4
Wind-Power Stations 634
B-13 Second Shifting Theorem 663
24-5
Wind-Energy Conversion 635
B-14 Periodic Functions 665
24-6
The Cube Law
B-15 Convolution Theorem 666
24-7
Operation
24-8
Wind Generators 639
B-17 Correspondence with Fourier Transform 667
24-9
Power Electronics
Further Reading 667
636
638
B-16 Inverse Laplace Transform by Residue Method
640
24-10
Computer Modeling 642
24-11
Floating Wind Turbines 645
References
C-1 Properties of z-Transform 670
645
Further Reading
APPENDIX C Z-TRANSFORM
C-2 Initial-Value Theorem 671
645
C-3 Final-Value Theorem
672
APPENDIX A DIFFERENTIAL EQUATIONS
C-4 Partial Sum 672
A-1
Homogeneous Differential Equations 647
C-5 Convolution
A-2
Linear Differential Equations 648
C-6 Inverse z-Transform 672
A-3
Bernoulli’s Equation
C-7 Inversion by Partial Fractions 674
A-4
Exact Differential Equations
648
648
672
C-8 Inversion by Residue Method 674
666
CONTENTS xi
C-9
C-10
Solution of Difference Equations 675
APPENDIX F STATISTICS AND PROBABILITY
State Variable Form 676
Further Reading
F-1 Mean, Mode, and Median 695
676
F-2 Mean and Standard Deviation 695
APPENDIX D SEQUENCE IMPEDANCES OF TRANSMISSION
LINES AND CABLES
F-3 Skewness and Kurtosis 696
D-1
AC Resistance of Conductors
F-5 Probability
D-2
Inductance of Transmission Lines 678
F-6 Binomial Distribution 699
D-3
Transposed Line
F-7 Poisson Distribution 699
D-4
Composite Conductors 679
F-8 Normal or Gaussian Distribution 699
D-5
Impedance Matrix
F-9 Weibull Distribution 701
D-6
Three-Phase Line with Ground Conductors 680
Reference 702
D-7
Bundle Conductors
Further Reading 702
D-8
Carson’s Formula
D-9
Capacitance of Lines 684
D-10
677
678
680
681
682
Cable Constants
F-4 Curve Fitting and Regression 696
698
APPENDIX G NUMERICAL TECHNIQUES
G-1 Network Equations 703
685
G-2 Compensation Methods 703
D-11 Frequency-Dependent Transmission
Line Models 688
G-3 Nonlinear Inductance 704
References
G-4 Piecewise Linear Inductance 704
688
G-5 Newton-Raphson Method 704
APPENDIX E ENERGY FUNCTIONS AND STABILITY
G-6 Numerical Solution of Linear Differential Equations 706
E-1
Dynamic Elements
G-7 Laplace Transform 706
E-2
Passivity
E-3
Equilibrium Points
E-4
State Equations
E-5
Stability of Equilibrium Points
E-6
Hartman-Grobman Linearization Theorem
E-7
Lyapunov Function
E-8
LaSalle’s Invariant Principle
E-9
Asymptotic Behavior 692
E-10
691
691
G-8 Taylor Series 706
691
G-9 Trapezoidal Rule of Integration 706
692
G-10 Runge-Kutta Methods 707
692
692
692
G-11 Predictor-Corrector Methods
692
G-12 Richardson Extrapolation and Romberg
Integration 708
References 709
Further Reading 709
Periodic Inputs 693
References
693
Further Reading
Index 711
693
708
This page intentionally left blank
PREFACE
The book aims to serve as a textbook for upper undergraduate and
graduate level students in the universities, a practical and analytical
guide for practicing engineers, and a standard reference book on transients. At the undergraduate level, the subject of transients is covered
under circuit theory, which does not go very far for understanding the
nature and impact of transients. The transient analyses must account for
special modeling and frequency-dependent behavior and are important
in the context of modern power systems of increasing complexity.
Often, it is difficult to predict intuitively that a transient problem
exists in a certain section of the system. Dynamic modeling in the
planning stage of the systems may not be fully investigated. The book
addresses analyses, recognition, and mitigation. Chapters on surge
protection, TVSS (transient voltage surge suppression), and insulation
coordination are included to meet this objective.
The book is a harmonious combination of theory and practice.
The theory must lead to solutions of practical importance and real
world situations.
A specialist or a beginner will find the book equally engrossing
and interesting because, starting from the fundamentals, gradually,
the subjects are developed to a higher level of understanding. In this
process, enough material is provided to sustain a reader’s interest
and motivate him to explore further and deeper into an aspect of
his/her liking.
The comprehensive nature of the book is its foremost asset. All
the transient frequencies, in the frequency range from 0.1 Hz to
50 MHz, which are classified into four groups: (1) low frequency
oscillations, (2) slow front surges, (3) fast front surges, and (4) very
fast front surges, are discussed. Transients that affect power system
stability and transients in transmission lines, transformers, rotating machines, electronic equipment, FACTs, bus transfer schemes,
grounding systems, gas insulated substations, and dc systems are
covered. A review of the contents will provide further details of the
subject matter covered and the organization of the book.
An aspect of importance is the practical and real world “feel” of
the transients. Computer and EMTP simulations provide a vivid
visual impact. Many illustrative examples at each stage of the development of a subject provide deeper understanding.
The author is thankful to Taisuke Soda of McGraw-Hill for his
help and suggestions in the preparation of the manuscript and
subsequent printing.
J. C. Das
xiii
This page intentionally left blank
CHAPTER 1
INTRODUCTION
TO TRANSIENTS
Electrical power systems are highly nonlinear and dynamic in nature:
circuit breakers are closing and opening, faults are being cleared,
generation is varying in response to load demand, and the power
systems are subjected to atmospheric disturbances, that is, lightning. Assuming a given steady state, the system must settle to a new
acceptable steady state in a short duration. Thus, the electromagnetic
and electromechanical energy is constantly being redistributed in
the power systems, among the system components. These energy
exchanges cannot take place instantaneously, but take some time
period which brings about the transient state. The energy statuses of
the sources can also undergo changes and may subject the system to
higher stresses resulting from increased currents and voltages.
The analysis of these excursions, for example, currents, voltages, speeds, frequency, torques, in the electrical systems is the
main objective of transient analysis and simulation of transients in
power systems.
1-1
CLASSIFICATION OF TRANSIENTS
Broadly, the transients are studied in two categories, based upon
their origin:
1. Of atmospheric origin, that is, lightning
2. Of switching origin, that is, all switching operations, load
rejection, and faults
Another classification can be done based upon the mode of generation of transients:
1. Electromagnetic transients. Generated predominantly by
the interaction between the electrical fields of capacitance
and magnetic fields of inductances in the power systems. The
electromagnetic phenomena may appear as traveling waves
on transmission lines, cables, bus sections, and oscillations
between inductance and capacitance.
2. Electromechanical transients. Interaction between the electrical energy stored in the system and the mechanical energy
stored in the inertia of the rotating machines, that is, generators and motors.
As an example, in transient stability analysis, both these effects
are present. The term transient, synonymous with surges, is used
loosely to describe a wide range of frequencies and magnitudes.
Table 1-1 shows the power system transients with respect to the
time duration of the phenomena.
1-2 CLASSIFICATION WITH RESPECT
TO FREQUENCY GROUPS
The study of transients in power systems involves frequency range
from dc to about 50 MHz and in specific cases even more. Table 1-2
gives the origin of transients and most common frequency ranges.
Usually, transients above power frequency involve electromagnetic
phenomena. Below power frequency, electromechanical transients
in rotating machines occur.
Table 1-3 shows the division into four groups, and also the phenomena giving rise to transients in a certain group is indicated. This
classification is more appropriate from system modeling considerations and is proposed by CIGRE Working Group 33.02.1
Transients in the frequency range of 100 kHz to 50 MHz are
termed very fast transients (VFT), also called very fast front transients.
These belong to the highest range of transients in power systems.
According to IEC 60071-1,2 the shape of a very fast transient is usually
unidirectional with time to peak less than 0.1 µs, total duration
less than 3 ms, and with superimposed oscillation at a frequency of
30 kHz < f < 100 MHz. Generally, the term is applied to transients
of frequencies above 1 MHz. These transients can originate in gasinsulated substations (GIS), by switching of motors and transformers
with short connections to the switchgear, by certain lightning conditions, as per IEC 60071-2.2
Lightning is the fastest disturbance, from nanoseconds to microseconds. The peak currents can approach 100 kA in the first stroke
and even higher in the subsequent strokes.
Nonpermanent departures form the normal line voltage, and
frequency can be classified as power system disturbances. These
deviations can be in wave shape, frequency, phase relationship,
voltage unbalance, outages and interruptions, surges and sags, and
impulses and noise. The phenomena shown in italics may loosely be
called transients.3 A stricter definition is that a transient is a subcycle
disturbance in the ac waveform that is evidenced by a sharp, brief
discontinuity in the waveform, which may be additive or subtractive
1
2
CHAPTER ONE
TA B L E 1 - 1
Time Duration of Transient
Phenomena in Electrical Systems
NATURE OF THE TRANSIENT PHENOMENA
TIME DURATION
The physical characteristics of a specific network element,
which affect a certain transient phenomena, must receive detailed
considerations. Specimen examples are:
■
Lightning
0.1 µs–1.0 ms
Switching
10 µs to less than a second
Subsynchronous resonance
0.1 ms–5 s
Transient stability
1 ms–10 s
The saturation characteristics of transformers and reactors
can be of importance in case of fault clearing, transformer
energization, and if significant temporary overvoltages are
expected. Temporary overvoltages originate from transformer
energization, fault overvoltages, and overvoltages due to load
rejection and resonance.
Dynamic stability, long-term dynamics
0.5–1000 s
■
Tie line regulation
10–1000 s
Daily load management, operator actions
Up to 24 h
TA B L E 1 - 2
Frequency Ranges of Transients
ORIGIN OF TRANSIENT
FREQUENCY RANGE
Restrikes on disconnectors and faults in GIS
100 kHz–50 MHz
Lightning surges
10 kHz–3 MHz
Multiple restrikes in circuit breakers
10 kHz–1 MHz
Transient recovery voltage:
Terminal faults
50/60 Hz–20 kHz
Short-line faults
50/60 kHz–100 kHz
Fault clearing
50/60 Hz–3 kHz
Fault initiation
50/60 Hz–20 kHz
Fault energization
50/60 Hz–3 kHz
Load rejection
0.1 Hz–3 kHz
Transformer energization
(dc) 0.1 Hz–1 kHz
Ferroresonance
(dc) 0.1 Hz–1 kHz
TA B L E 1 - 3
Classification of Frequency Ranges1
FREQUENCY RANGE
REPRESENTATION
SHAPE
DESIGNATION
REPRESENTATION
MAINLY FOR
GROUP
FOR
I
0.1 Hz–3 kHz
Low-frequency
oscillations
Temporary
overvoltages
II
50/60 Hz–20 kHz
Slow front surges
Switching overvoltages
III
10 kHz–3 MHz
Fast front surges
Lightning overvoltages
IV
100 kHz–50 MHz
Very fast front
surges
Restrike overvoltages,
GIS
On transmission line switching, not only the characteristics
of the line itself, but also of the feeding and terminating networks will be of interest. If details of initial rate of rise of overvoltages are of importance, the substation details, capacitances
of measuring transformers, and the number of outgoing lines
and their surge impedances also become equally important.
■
When studying phenomena above 1 MHz, for example, in
GIS caused by a disconnector strike, the small capacitances and
inductances of each section of GIS become important.
These are some representative statements. The system configuration under study and the component models of the system
are of major importance. Therefore, the importance of frequencydependent models cannot be overstated. Referring to Table 1-3,
note that the groups assigned are not hard and fast with respect to
the phenomena described, that is, faults of switching origin may
also create steep fronted surges in the local vicinity.
1-3
FREQUENCY-DEPENDENT MODELING
The power system components have frequency-dependent behavior, and the development of models that are accurate enough for
a wide range of frequencies is a difficult task. The mathematical
representation of each power system component can, generally,
be developed for a specific frequency range. This means that one
model cannot be applied to every type of transient study. This can
lead to considerable errors and results far removed from the realworld situations. This leads to the importance of correct modeling for each specific study type, which is not so straightforward in
every case.4
1-3-1
SoFT
TM
SoFT (Swiss Technology Award, 2006) is a new approach that
measures the true and full frequency-dependent behavior of the
electrical equipment. This reveals the interplay between the three
phases of an ac system, equipment interaction, and system resonances to achieve the most accurate frequency-dependent models
of electrical components. The three-step process is:
1. On-site measurements
2. Determining the frequency dependent models
3. Simulation and modeling
from the original waveform. Yet, in common use, the term transients embraces overvoltages of various origins, transients in the
control systems, transient and dynamic stability of power systems,
and dynamics of the power system on short circuits, starting of motors,
operation of current limiting fuses, grounding systems, and the like.
The switching and fault events give rise to overvoltages, up to
three times the rated voltage for phase-to-ground transients, and
up to four times for phase-to-phase transients. The rise time varies
from 50 µs to some thousands of microseconds. The simulation
time may be in several cycles, if system recovery from disturbance
is required to be investigated.
The modeling fits a state-space model to the measured data,
based upon vector fitting techniques. Five frequency-independent
matrices representing the state-space are generated, and in the frequency domain, the matrix techniques are used to eliminate the
state vector x.. An admittance matrix is then generated. The matrices
of state-space can be directly imported into programs like EMTP-RV.
Thus, a highly accurate simulation can be performed.
Apart from the reference here, this book does not discuss the
field measurement techniques for ascertaining system data for
modeling.
INTRODUCTION TO TRANSIENTS
1-4
OTHER SOURCES OF TRANSIENTS
Detonation of nuclear devices at high altitudes, 40 km and higher,
gives rise to transients called high-altitude electromagnetic pulse
(HEMP). These are not discussed in this book.
Strong geomagnetic storms are caused by sunspot activity every
11 years or so, and this can induce dc currents in the transmission
lines and magnetize the cores of the transformers connected to the
end of transmission lines. This can result in much saturation of
the iron core. In 1989 a large blackout was reported in the U.S. and
Canadian electrical utilities due to geomagnetic storms (Chap. 14).
Extremely low magnetic fields (ELF), with a frequency of 60 Hz
with higher harmonics up to 300 Hz and lower harmonics up to
5 Hz, are created by alternating current, and associations have
been made between various cancers and leukemia in some epidemiological studies (Chap. 22).
1-5
1-6
3
TNAs—ANALOG COMPUTERS
The term TNA stands for transient network analyzer. The power
system can be modeled by discrete scaled down components of
the power system and their interconnections. Low voltage and
current levels are used. The analog computer basically solves differential equations, with several units for specific functions, like
adders, integrators, multipliers, CRT displays, and the like. The
TNAs work in real time; many runs can be performed quickly and
the system data changed, though the setting up of the base system model may be fairly time-consuming. The behavior of actual
control hardware can be studied and validated before field applications. The advancement in digital computation and simulation
is somewhat overshadowing the TNA models, yet these remain a
powerful analog research tool. It is obvious that these simulators
could be relied upon to solve relatively simple problems. The digital computers provide more accurate and general solutions for large
complex systems.
STUDY OF TRANSIENTS
The transients can be studied from the following angles:
■
Recognition
■
Prediction
■
Mitigation
This study of transients is fairly involved, as it must consider the
behavior of the equipment and amplification or attenuation of the
transient in the equipment itself. The transient voltage excitation
can produce equipment responses that may not be easy to decipher
intuitively or at first glance.
Again coming back to the models of the power system equipment, these can be generated on two precepts: (1) based on lumped
parameters, that is, motors, capacitors, and reactors (though wave
propagation can be applied to transient studies in motor windings)
and (2) based on distributed system parameters, that is, overhead
lines and underground cables (though simplifying techniques and
lumped parameters can be used with certain assumptions). It is
important that transient simulations and models must reproduce
frequency variations, nonlinearity, magnetic saturation, surgearresters characteristics, circuit breaker, and power fuse operation.
The transient waveforms may contain one or more oscillatory
components and can be characterized by the natural frequencies
of these oscillations, which are dependent upon the nature of the
power system equipment.
Transients are generated due to phenomena internal to the
equipment, or of atmospheric origin. Therefore, the transients are
inherent in the electrical systems. Mitigation through surge arresters, transient voltage surge suppressors (TVSS), active and passive
filters, chokes, coils and capacitors, snubber and damping circuits
requires knowledge of the characteristics of these devices for appropriate analyses. Standards establish the surge performance of the
electrical equipment by application of a number of test wave shapes
and rigorous testing, yet to apply proper strategies and devices for
a certain design configuration of a large system, for example, highvoltage transmission networks, detailed modeling and analysis are
required. Thus, for mitigation of transients we get back to analysis
and recognition of the transient problem.
This shows that all the three aspects, analysis, recognition, and
mitigation, are interdependent, the share of analysis being more than
75 percent. After all, a mitigation strategy must again be analyzed
and its effectiveness be proven by modeling before implementation.
It should not, however, be construed that we need to start from
the very beginning every time. Much work has been done. Over the
past 100 years at least 1000 papers have been written on the subject
and ANSI/IEEE and IEC standards provide guidelines.
1-7 DIGITAL SIMULATIONS, EMTP/ATP,
AND SIMILAR PROGRAMS
The electrical power systems parameters and variables to be studied are
continuous functions, while digital simulation, by its nature, is discrete.
Therefore, the development of algorithms to solve digitally the differential and algebraic equations of the power system was the starting
point. H.W. Dommel of Bonneville Power Administration (BPA) published a paper in 1969,5 enumerating digital solution of power system
electromagnetic transients based on difference equations (App. C).
The method was called Electromagnetic Transients Program (EMTP).
It immediately became an industrial standard all over the world.
Many research projects and the Electrical Power Research Institute
(EPRI) contributed to it. EMTP was made available to the worldwide
community as the Alternate Transient Program (ATP), developed with
W. S. Meyer of BPA as the coordinator.6 A major contribution, Transient Analysis of Control Systems (TACS), was added by L. Dubé in
1976.
A mention of the state variable method seems appropriate here.
It is a popular technique for numerical integration of differential
equations that will not give rise to a numerical instability problem
inherent in numerical integration (App. G). This can be circumvented by proper modeling techniques.
The versatility of EMTP lies in the component models, which
can be freely assembled to represent a system under study. Nonlinear resistances, inductances, time-varying resistances, switches,
lumped elements (single or three-phase), two or three winding
transformers, transposed and untransposed transmission lines,
detailed generator models according to Park’s transformation, converter circuits, and surge arresters can be modeled. The insulation
coordination, transient stability, fault currents, overvoltages due to
switching surges, circuit breaker operations, transient behavior of
power system under electronic control subsynchronous resonance,
and ferroresonance phenomena can all be studied.
Electromagnetic Transients Program for DC (EMTDC) was
designed by D. A. Woodford of Manitoba Hydro and A. Gole and R.
Menzies in 1970. The original program ran on mainframe computers. The EMTDC version for PC use was released in the 1980s.
Manitoba HVDC Research Center developed a comprehensive
graphic user interface called Power System Computer Aided Design
(PSCAD), and PSCAD/EMTDC version 2 was released in the 1990s
for UNIX work stations, followed by a Windows/PC-based version
in 1998. EMTP-RV is the restructured version of EMTP.7,8
Other EMTP type programs are: MicroTran by Micro Tran Power
System Analysis Corporation, Transient Program Analyzer (TPA)
based upon MATLAB; NETOMAC by Siemens; SABER by Avant.8
It seems that in a large number of cases dynamic analyses are
carried out occasionally in the planning stage and in some situations
4
CHAPTER ONE
dynamic analysis is not carried at all.9 The reasons of lack of analysis were identified as:
■
A resource problem
■
Lack of data
■
Lack of experience
Further, the following problems were identified as the most crucial, in the order of priority:
■
Lack of models for wind farms
■
Lack of models for new network equipment
■
Lack of models for dispersed generation (equivalent
dynamic models for transmission studies)
■
Lack of verified models (specially dynamic models) and
data for loads
■
Lack of field verifications and manufacturer’s data to ensure
that generator parameters are correct
■
Lack of open cycle and combined cycle (CC) gas turbine
models in some cases
Thus, data gathering and verifications of the correct data is of
great importance for dynamic analysis.
EMTP/ATP is used to simulate illustrative examples of transient
phenomena discussed in this book. In all simulations it is necessary
that the system has a ground node. Consider, for example, the delta
winding of a transformer or a three-phase ungrounded capacitor
bank. These do have some capacitance to ground. This may not
have been shown in the circuit diagrams of configurations for simplicity, but the ground node is always implied in all simulations
using EMTP. This book also uses both SI and FPS units, the latter
being still in practical use in the United States.
REFERENCES
1. CIGRE joint WG 33.02, Guidelines for Representation of Networks
Elements when Calculating Transients, CIGRE Brochure, 1990.
2. IEC 60071-1, ed. 8, Insulation Coordination, Definitions, Principles,
and Rules, 2006; IEC 60071-2, 3rd ed., Application Guide, 1996.
3. ANSI/IEEE Std. 446, IEEE Recommended Practice for Emergency and Standby Power Systems for Industrial and Commercial Applications, 1987.
4. IEEE, Modeling and Analysis of System Transients Using
Digital Programs, Document TP-133-0, 1998. (This document
provides 985 further references).
5. H. W. Dommel, “Digital Computer Solution of Electromagnetic
Transients in Single and Multiphase Networks,” IEEE Trans.
Power Apparatus and Systems, vol. PAS-88, no. 4, pp. 388–399,
Apr. 1969.
6. ATP Rule Book, ATP User Group, Portland, OR, 1992.
7. J. Mahseredjian, S. Dennetiere, L. Dubé, B. Khodabakhehian,
and L. Gerin-Lajoie, “A New Approach for the Simulation
of Transients in Power Systems,” International Conference on
Power System Transients, Montreal, Canada, June 2005.
8. EMTP, www.emtp.org; NETOMAC, www.ev.siemens.de/en/pages;
EMTAP, www.edsa.com; TPA, www.mpr.com; PSCAD/EMTDC,
www.hvdc.ca; EMTP-RV, www.emtp.com.
9. CIGRE WG C1.04, “Application and Required Developments
of Dynamic Models to Support Practical Planning,” Electra,
no. 230, pp. 18–32, Feb. 2007.
FURTHER READING
A. Clerici, “Analogue and Digital Simulation for Transient Voltage
Determinations,” Electra, no. 22, pp. 111–138, 1972.
H. W. Dommel and W. S. Meyer, “Computation of Electromagnetic
Transients,” IEE Proc. no. 62, pp. 983–993, 1974.
L. Dube and H. W. Dommel, “Simulation of Control Systems in An
Electromagnetic Transients Program with TACS,” Proc. IEEE PICA,
pp. 266–271, 1977.
M. Erche, “Network Analyzer for Study of Electromagnetic Transients in High-Voltage Networks,” Siemens Power Engineering and
Automation, no. 7, pp. 285–290, 1985.
B. Gustavsen and A. Semlyen, “Rational Approximation of Frequency Domain Responses by Vector Fitting,” IEEE Trans. PD,
vol. 14, no. 3, pp. 1052–1061, July 1999.
B. Gustavsen and A. Semlyen, “Enforcing Passivity of Admittance
Matrices Approximated by Rational Functions,” IEEE Trans. PS, vol.
16, no. 1, pp. 97–104, Feb 2001.
M. Zitnik, “Numerical Modeling of Transients in Electrical Systems,”
Uppsal Dissertations from the Faculty of Science and Technology
(35), Elanders Gutab, Stockholm, 2001.
CHAPTER 2
TRANSIENTS IN LUMPED
CIRCUITS
In this chapter the transients in lumped, passive, linear circuits are
studied. Complex electrical systems can be modeled with certain
constraints and interconnections of passive system components,
which can be excited from a variety of sources. A familiarity with
basic circuit concepts, circuit theorems, and matrices is assumed.
A reader may like to pursue the synopsis of differential equations,
Laplace transform, and z-transform in Apps. A, B, and C, respectively, before proceeding with this chapter. Fourier transform can
also be used for transient analysis; while Laplace transform converts a time domain function into complex frequency (s =s+w),
the Fourier transform converts it into imaginary frequency of jw. We
will confine our discussion to Laplace transform in this chapter.
2-1
LUMPED AND DISTRIBUTED PARAMETERS
A lumped parameter system is that in which the disturbance originating at one point of the system is propagated instantaneously
to every other point in the system. The assumption is valid if the
largest physical dimension of the system is small compared to the
wavelength of the highest significant frequency. These systems can
be modeled by ordinary differential equations.
In a distributed parameter system, it takes a finite time for a disturbance at one point to be transmitted to the other point. Thus, we
deal with space variable in addition to independent time variable.
The equations describing distributed parameter systems are partial
differential equations.
All systems are in fact, to an extent, distributed parameter systems. The power transmission line models are an example. Each
elemental section of the line has resistance, inductance, shunt conductance, and shunt capacitance. For short lines we ignore shunt
capacitance and conductance all together, for medium long lines
we approximate with lumped T and P models, and for long lines
we use distributed parameter models (see Chap. 4).
Mathematically, if the state of the system at t = t0 is x(t) and for a
delayed input it is w(t) then the system changes its state in the stationary or time invariant manner if:
w(t + τ ) = x(t )
w(t ) = x(t − τ )
(2-1)
This is shown in Fig. 2-1. A shift in waveform by t will have no
effect on the waveform of the state variables except for a shift by t.
This suggests that in time invariant systems the time origin t0 is not
important. The reference time for a time invariant system can be
chosen as zero, Therefore:
x(t ) = φ[x(0), r(0, t )]
(2-2)
To some extent physical systems do vary with time, for example,
due to aging and tolerances in component values. A time invariant
system is, thus, an idealization of a practical system or, in other words,
we say that the changes are very slow with respect to the input.
2-3
LINEAR AND NONLINEAR SYSTEMS
Linearity implies two conditions:
1. Homogeneity
2. Superposition
Consider the state of a system defined by (see Sec. 2-14 on state
equations):
x = f[x(t ), r(t ), t]
(2-3)
If x (t) is the solution to this differential equation with initial conditions x(t0) at t =t0 and input r(t), t > t0:
x(t ) = φ[x(t 0 ), r(t )]
(2-4)
Then homogeneity implies that:
2-2
TIME INVARIANCE
When the characteristics of the system do not change with time it
is said to be a time invariant or stationary system.
φ[x(t 0 ), α r(t )] = α φ[x(t 0 ), r(t )]
(2-5)
where a is a scalar constant. This means that x(t) with input a r(t)
is equal to a times x(t) with input r(t) for any scalar a.
5
6
CHAPTER TWO
solutions are not available and each system must be studied specifically. Yet, we apply linear techniques of solution to nonlinear
systems over a certain time interval. Perhaps the system is not
changing so fast, and for a certain range of applications linearity
can be applied. Thus, the linear system analysis forms the very fundamental aspect of the study.
2-5 TIME DOMAIN ANALYSIS
OF LINEAR SYSTEMS
We can study the behavior of an electrical system in the time
domain. A linear system can be described by a set of linear differential or difference equations (App. C). The output of the system
for some given inputs can be studied. If the behavior of the system
at all points in the system is to be studied, then a mathematical
description of the system can be obtained in state variable form.
A transform of the time signals in another form can often express
the problem in a more simplified way. Examples of transform techniques are Laplace transform, Fourier transform, z-transform, and
integral transform, which are powerful analytical tools. There are
inherently three steps in applying a transform:
1. The original problem is transformed into a simpler form for
solution using a transform.
2. The problem is solved, and possibly the transformed form
is mathematically easy to manipulate and solve.
3. Inverse transform is applied to get to the original solution.
As we will see, all three steps may not be necessary, and sometimes a direct solution can be more easily obtained.
FIGURE 2-1
A time invariant system, effect of shifted input by t.
Superposition implies that:
φ[x(t 0 ), r1(t ) + r2 (t )] = φ[x(t 0 ), r1(t )]+ φ[x(t 0 ), r2 (t )]
(2-6)
That is, x(t) with inputs r1(t) + r2(t) is = sum of x(t) with input
r1(t) and x(t) with input r2(t). Thus linearity is superimposition
plus homogeneity.
2-4
PROPERTY OF DECOMPOSITION
A system is said to be linear if it satisfies the decomposition property and the decomposed components are linear.
If x′(t) is solution of Eq. (2-3) when system is in zero state for
all inputs r(t), that is:
x′(t ) = φ[0, r(t )]
(2-7)
And x″(t) is the solution when for all states x(t0), the input r(t) is
zero, that is:
x′′(t ) = φ[x(t 0 ), 0]
(2-8)
Then, the system is said to have the decomposition property if:
x(t ) = x′(t ) + x′′(t )
(2-9)
The zero input response and zero state response satisfy the
properties of homogeneity and superimposition with respect to initial states and initial inputs, respectively. If this is not true, then the
system is nonlinear.
Electrical power systems are perhaps the most nonlinear systems
in the physical world. For nonlinear systems, general methods of
2-6
STATIC AND DYNAMIC SYSTEMS
Consider a time-invariant, linear resistor element across a voltage
source. The output, that is, the voltage across the resistor, is solely
dependent upon the input voltage at that instant. We may say that
the resistor does not have a memory, and is a static system. On the
other hand the voltage across a capacitor depends not only upon
the input, but also upon its initial charge, that is, the past history
of current flow. We say that the capacitor has a memory and is a
dynamic system.
The state of the system with memory is determined by state variables that vary with time. The state transition from x(t1) at time t1 to
x(t2) at time t2 is a dynamic process that can be described by differential equations. For a capacitor connected to a voltage source, the
dynamics of the state variable x(t) =e(t) can be described by:
x =
1
r(t )
C
r(t ) = i(t )
(2-10)
We will revert to the state variable form in Sec. 2-14. By this
definition, practically all electrical systems are dynamic in nature.
2-7
FUNDAMENTAL CONCEPTS
Some basic concepts are outlined for the solution of transients,
which are discussed in many texts.
2-7-1
Representation of Sources
We will represent the independent and dependent current and voltage sources as shown in Fig. 2-2a, b, and c. Recall that in a dependent controlled source the controlling physical parameter may be
current, voltage, light intensity, temperature, and the like. An ideal
voltage source will have a Thévenin impedance of zero, that is, any
amount of current can be taken from the source without altering
the source voltage. An ideal current source (Norton equivalent)
TRANSIENTS IN LUMPED CIRCUITS
7
resistor and, the charging current assuming no source resistance
and ignoring resistance of connections, will be theoretically infinite.
Practically some resistance in the circuit, shown dotted as R1, will
limit the current. Note that the symbol t = 0+ signifies the time after
the switch is closed:
iC (0+ ) =
Vs
R1
As the current in the capacitor is given by:
iC = C
dv
dt
We can write:
dv Vs
=
dt R1C
When the capacitor is fully charged, dv/dt and iC are zero and the current through R2 is given by:
i2 =
Vs
R1 + R 2
And the voltage across the capacitor as well as the resistor R2 is:
FIGURE 2-2
(a) Independent voltage and current source. (b) Voltage
and current controlled voltage source. (c) Voltage and current controlled
current source.
will have an infinite admittance across it. In practice a large generator
approximates to an ideal current and voltage source. Sometimes utility systems are modeled as ideal sources, but this can lead to appreciable errors depending upon the problem under study.
2-7-2 Inductance and Capacitance Excited
by DC Source
Consider that an ideal dc voltage source is connected through a
switch, normally open (t = 0–) to a parallel combination of a capacitor and resistors shown in Fig. 2-3a. Further consider that there
is no prior charge on the capacitor. When the switch is suddenly
closed at t = 0+, the capacitor acts like a short circuit across the
vC (∞) = i2 R 2 =
Vs R 2
R1 + R 2
We have not calculated the time-charging current transient profile and have arrived at the initial and final value results by elementary circuit conditions.
Now consider that the capacitor is replaced by an inductor as
shown in Fig. 2-3b. Again consider that there is no stored energy in
the reactor prior to closing the switch. Inductance acts like an open
circuit on closing the switch, therefore all the current flows through
R2.
Thus, the voltage across resistor or inductor is:
vL =
Vs R 2
di
=L L
R1 + R 2
dt
Vs R 2
di L
=
dt L(R1 + R 2 )
In steady state diL /dt = 0, there is no voltage drop across the
inductor. It acts like a short circuit across R2, and the current will
be limited only by R1. It is equal to V/R1.
2-7-3
Coupled Coils
Two coupled coils are shown in Fig. 2-4. We can write the following
equations relating current and voltages:
v1 = L1
di
di1
+M 2
dt
dt
v2 = M
di1
di
+ L2 2
dt
dt
(2-11)
where M is given by the coefficient of coupling:
M = k L1L2
FIGURE 2-3
(a) Switching of a capacitor on a dc voltage source.
(b) Switching of a reactor on a dc voltage source.
(2-12)
In an ideal transformer, k =1. These equations can be treated as
two loop equations; the voltage generated in loop 1 is due to current in loop 2 and vice versa. This is the example of a bilateral
8
CHAPTER TWO
FIGURE 2-7
2-7-4
FIGURE 2-4
To illustrate mutually coupled coils.
Two-Port Networks
Two-port networks such as transformers, transistors, and transmission
lines may be three- or four-terminal devices. They are assumed to be
linear. A representation of such a network is shown in Fig. 2-8, with
four variables which are related with the following matrix equation:
v1
z
= 11
v2
z 21
FIGURE 2-5
Equivalent circuit model of coupled coils using
controlled sources.
circuit, which can be represented by an equivalent circuit of controlled sources (Fig. 2-5).
In a three-terminal device, with voltages measured to common
third terminal (Fig. 2-6), a matrix equation of the following form can
be written:
z
v1
= i
zf
v2
zr
z0
i1
i2
(2-13)
where zi is input impedance, zr is reverse impedance, zf is forward
impedance, and z0 is output impedance. The z parameters result in
current-controlled voltage sources in series with impedances. These
can be converted to voltage-controlled current sources in parallel
with admittances—y-parameter formation.
For example, consider a three-terminal device, with following y
parameters:
yi = 0 . 012
yr = − 0 . 001
y f = 0 . 0067
y0 = 0 . 002
All the above values are in mhos. Then the following equations can
be written:
i1 = 0 . 012v1 − 0 . 001v2
i2 = 0 . 0067 v1 + 0 . 002v2
Each of these equations describes connection to one node, and
the voltages are measured with respect to the reference node. These
can be represented by the equivalent circuit shown in Fig. 2-7.
FIGURE 2-6
Equivalent circuit, voltage of controlled sources.
Equivalent circuit of admittances, y-parameter representation.
z12
z 22
i1
i2
(2-14)
Note the convention used for the current flow and the voltage
polarity. The subscript 1 pertains to input port and the input terminals; the subscript 2 indicates output port and output terminals.
The four port variables can be dependent or independent, that is,
the independent variables may be currents and the dependent variables may be voltages.
By choosing voltage as the independent variable, y parameters
are obtained, and by choosing the input current and the output
voltage as independent variable h, parameters are obtained.
2-7-5
Network Reductions
Circuit reductions; loop and mesh equations; and Thévenin, Norton,
Miller, maximum power transfer, and superposition theorems,
which are fundamental to circuit concepts, are not discussed, and a
knowledge of these basic concepts is assumed. A network for study
of transients can be simplified using these theorems. The following
simple example illustrates this.
Example 2-1 Consider the circuit configuration shown in
Fig. 2-9a. It is required to write the differential equation for the
voltage across the capacitor.
We could write three loop equations and then solve these simultaneous equations for the current in the capacitor. However, this can be
much simplified, using a basic circuit transformation. It is seen from
Fig. 2-9a that the capacitor and inductor are neither in a series or a
parallel configuration. A step-wise reduction of the system is shown
in Figs. 2-9b, c, and d. In Fig. 2-9b the voltage source is converted to
a current source, and 20 Ω and 40 Ω resistances in parallel are combined. In Fig. 2-9c, the current source is converted back to the voltage source. Finally, we can write the following differential equation:
0 . 028vs =
dv
vc
+ C c + iL
23 . 33
dt
F I G U R E 2 - 8 Two-port network, showing defined directions of
currents and polarity of voltages.
TRANSIENTS IN LUMPED CIRCUITS
9
F I G U R E 2-9
(a), (b), (c), and (d) Progressive reduction of a network by source transformations/Dotted lines in Fig. 2-9a show wye-delta and
delta-wye impedance transformations.
A simpler reduction could be obtained by wye-delta transformation. Consider the impedances shown dotted in Fig. 2-9a, then:
Z12 =
Z1Z2 + Z1Z 3 + Z2 Z 3
Z3
Z Z + Z Z + Z2 Z 3
Z13 = 1 2 1 3
Z2
2-7-6
Impedance Forms
For transient and stability analysis, the following impedance forms
of simple combination of circuit elements are useful:
Inductance
v=L
(2-15)
di
= sLi
dt
z L = sL
Capacitance
Z Z + Z Z + Z2 Z 3
Z23 = 1 2 1 3
Z1
i=C
dv
= sCv
dt
zC =
1
sC
Conversely:
Series RL
Z12 Z13
Z1 =
Z12 + Z13 + Z23
Z2 =
Z12 Z23
Z12 + Z13 + Z23
Z3 =
Z13 Z23
Z12 + Z13 + Z23
sL
z = R 1 +
R
(2-16)
(2-17)
Series RC
z=
1 + sCR
sC
(2-18)
10
CHAPTER TWO
Response to the application of a voltage V and the resulting current flow can simply be found by the expression:
Parallel RL
z=
sL
1 + sL /R
(2-19)
Parallel RC
z=
R
1 + sCR
(2-20)
Parallel LC
z=
sL
1 + s2 LC
(2-21)
1 + s2 LC
SC
(2-22)
Series RLC
z=
1 + sCR + s2 LC
sC
(2-23)
sL
1 + (sL /R ) + s2 LC
FIGURE 2-10
(2-24)
(2-25)
Equation (2-25) is applicable if there is no initial charge on the
capacitors and there is no prior stored energy in the reactors. The
capacitance voltage does not change instantaneously, and therefore,
vC (0+ ) = vC (0) . The capacitance voltage and current are transformed according to the equations:
[vC (t )] = VC (s)
(2-26)
Figure 2-10a shows the equivalent capacitor circuit. Note that
the two-source current model is transformed into an impedance
and current source model.
In an inductance the transformation is:
[i L (t )] = I L (s)
di (t )
[v L (t )] = L L = sLI L (s) − Ii L (0)
dt
Parallel RLC
z=
V1
s z
dv (t )
[iC (t )] = C C = sCVC (s) − CVC (0)
dt
Series LC
z=
i(s) =
(2-27)
This two-source model and the equivalent impedance and source
model are shown in Fig. 2-10b.
(a) Transformed equivalent circuit for the initial conditions of voltage on a capacitor. (b) Transformed equivalent circuit for the current in
an inductor. (c) Circuit diagram for Example 2-2.
TRANSIENTS IN LUMPED CIRCUITS
Example 2-2 Consider a circuit of Fig. 2-10c. Initially the state variables are 50 V across the capacitor and a current of 500 mA flows in the
inductor. It is required to find the voltage across the capacitor for t > 0.
We can write two differential equations for the left-hand and
right-hand loops, using Kirchoff’s voltage laws:
dV
100 = 10 i L + 10−4 c + Vc
dt
Vc = 10i L + 1 . 0
di L
dt
The current in the capacitor is given by:
Vc (0) = 50 V
These values can be substituted and the equations solved for capacitor voltage (App. B).
The energy storage elements in electrical circuits are inductors and
capacitors. The first-order transients occur when the circuit contains only one energy storage element, that is, inductance or capacitance. This results in a first-order differential equation which can be
easily solved. The circuit may be excited by:
• DC source, giving rise to dc transients
When switching devices operate, they change the topology of the
circuit. Some parts of the system may be connected or disconnected.
Hence these may be called switching transients. On the other hand,
pulse transients do not change the topology of the circuit, as only the
current or voltage waveforms of a source are changed.
Example 2-3 Consider Fig. 2-11a, with the following values.
L = 0.15 H
V = 10 V
With the given parameters and the switch closed, we reduce the
circuit to an equivalent Thévenin voltage Vth = 9.09 V and series
Thévenin resistance Rth = 0.909 Ω (Fig. 2-11b). Therefore we can
write the following differential equation:
di
dt
FIGURE 2-11
dvC
dt
9 . 09 = 0 . 909 × 10−6
dvC
+ vc
dt
For steady state, dvC /dt = 0 and the capacitor is charged to 9.09 V.
When the switch is opened:
0 = 10−5
• AC source, giving rise to ac transients.
R2 = 10 Ω
iC = C
Thus, we can write:
FIRST-ORDER TRANSIENTS
9 . 09 = 0 . 909i + 0 . 15
di
dt
vc + iR th = vth
Vc = 10i L + si L − I L (0)
R1 =1 Ω
0 = 10i + 0 . 15
di/dt = 0 in steady state and therefore, current = 0.
In Example 2-3, we replace the inductor with a
capacitor of 1 µF and solve for the capacitor current, with resistances and voltage remaining unchanged. The Thévenin voltage
and impedance on closing the switch are the same as calculated
in Example 2-3. Therefore we can write the following differential
equation:
100
= 10i L + 10−3[s(Vc ) − Vc (0)]+ Vc
s
2-8
When steady-state condition is reached, di/dt = 0, and the steadystate current is 10 A, the reactor acts as an open circuit.
When the switch is opened, Vth = 0 V and Rth = 10 Ω. Therefore:
Example 2-4
Now apply Laplace transform:
I L (0) = 0 . 5 A
11
dvC
+ vC
dt
Again for steady state, dvC/dt is zero and the capacitor voltage
is zero. The above examples show the reduction of the system to a
simple RL or RC in series excited by a dc source. The differential
equation for series RL circuit is:
Ri + L
di
=V
dt
(2-28)
This is a first-order linear differential equation, and from App. A
its solution is:
R
t
ie L =
i=
V L RL t
e +A
L R
R
− t
V
+ Ae L
R
(a) Circuit with switch open, Example 2-3. (b) Circuit with switch closed, Example 2-3.
12
CHAPTER TWO
The coefficient A can be found from the initial conditions, at t = 0 i = 0.
Thus, A = –V/R:
i=
V
− R t
1− e L
R
(2-29)
The current increases with time and attains a maximum value of
V/R, as before. The voltage across the reactor is L di/dt:
VL = Ve
− Rt
(2-30)
L
That is, the inductor is an open circuit at the instant of switching
and is a short circuit ultimately.
We could also arrive at the same results by Laplace transform.
Taking Laplace transform of Eq. (2-28):
Ri(s) + Lsi(s) − LI(0) =
V
s
1
V
L s(s + R /L )
i(s) =
V − VC (0) −t /RC
e
R
(2-31)
VC(0) is the initial voltage on the capacitor.
di
+ Ri = V sin(ω t + θ )
dt
( R /L ) dt
t
ie L =
=
V
L
where Im is the peak value of the steady-state current (V is the peak
value of the applied sinusoidal voltage).
The same result can be obtained using Laplace transform though
more steps are required. Taking Lapalce transform:
ω cos θ s sin θ
+
=V 2
s + ω 2 s2 + ω 2
i(s) =
i(s) =
t
2
R
+ ω2
L2
ωL
sin ω t + θ − tan −1
+A
R
s
α
V sin θ 1
−
+
+
L(α 2 + ω 2 ) s + R /L s2 + ω 2 s2 + ω 2
R 2 + ω 2 L2
sin(ω t + θ − φ ) + Ae
(2-34)
The inverse Laplace transform of function in Eq. (2-33) is:
i=
−α t
α
1
1
= 2
e − cos ω t + sin ω t
2
2
2
ω
(s + α )(s + ω ) (α + ω )
s
1
=
[−αe −α t + ω sin ω t + cos ω t]
(s + α )(s2 + ω 2 ) (α 2 + ω 2 )
R
− t
L
α
V
ω cos θ e −α t − cos ω t + sin ω t
2
ω
L(α + ω )
2
+ sin θ (α cos ω t + ω sin ω t − αe −α t )
=
Thus:
V
Vω cos θ 1
s
α
−
+
L(α 2 + ω 2 ) s + R /L s2 + ω 2 s2 + ω 2
Substituting these results in Eq. (2-34):
∫ e L sin(ω t + θ )dt + A
V
L
ω cos θ s sin θ
1
V
+
L s + (R / L ) s2 + ω 2 s2 + ω 2
where a= R/L, therefore:
−1
R
t
eL
(2-32)
Therefore:
= e Rt /L
R
[sin(ω t + θ − φ ) − sin(θ − φ )e −Rt /L ]
= I m sin(ω t + θ − φ ) − I m sin(θ − φ )e −Rt / L
The solution is:
i=
R 2 + (ω L )2
−1
The integrating factor is:
R
V
i=
RL Series Circuit Excited by an AC Sinusoidal Source
Short circuit of a passive reactor and resistor in series excited by a
sinusoidal source is rather an important transient. This depicts the
basics of short circuit of a synchronous generator, except that the
reactances of a synchronous generator are not time-invariant:
e∫
The constant A can be found from the initial conditions at t = 0,
i = 0.
This gives:
α
s
1
1 1
= 2
− 2
+ 2
(2-33)
2
2
2 s + α
2
(s + α )(s + ω ) α + ω
s +ω
s + ω2
The solution of this equation gives:
L
ωL
R
This can be resolved into partial fractions:
V − VC (0)
di
i
+
=
dt RC
R
2-8-1
φ = tan −1
Ri(s) + Lsi(s) − LI(0) = V (sin ω t cos θ + cos ω t sin θ )
The inverse Laplace transform gives the same result as Eq. (2-29)
(see App. B). For solution of differential equations, it is not always
necessary to solve using Laplace transform. A direct solution can,
sometimes, be straightforward.
For the series RC circuit excited by a dc voltage, we can write the
following general equation:
i=
where:
V
[(ω cos θ − α sin θ )e −α t
L(α 2 + ω 2 )
− (ω cos θ − α sin θ )cos ω t + (α cos θ + ω sin θ )sin ω t]
(2-35)
TRANSIENTS IN LUMPED CIRCUITS
Remembering that:
tan φ = ω L /R = ωα sin φ = ω /(α + ω )
2
i=
2 1/ 2
cos φ = α /(α + ω )
V
[sin(ω t + θ − φ ) − sin(θ − φ )e −α t ]
(R 2 + ω 2 L2 )1/ 2
2
2 1/ 2
(2-36)
This is the same result as obtained in Eq. (2-32). Again, the derivation shows that direct solution of differential equation is simpler.
In power systems X/R ratio is high. A 100-MVA, 0.85 power factor generator may have an X/R of 110 and a transformer of the same
rating, an X/R = 45. The X/R ratios for low-voltage systems may be
of the order of 2–8. Consider that f ≈ 90°.
If the short circuit occurs when the switch is closed at an instant at
t = 0, q= 0, that is, when the voltage wave is crossing through zero
amplitude on x axis, the instantaneous value of the short circuit current from Eq. (2-36) is 2 Im. This is sometimes called the doubling
effect.
If the short circuit occurs when the switch is closed at an instant at
t = 0, q= p /2, that is, when the voltage wave peaks, the second term in
FIGURE 2-12
13
Eq. (2-36) is zero and there is no transient component. This is illustrated in Fig. 2-12a and b.
A physical explanation of the dc transient is that the inductance
component of the impedance is high. If the short circuit occurs at
the peak of the voltage, the current is zero. No dc component is
required to satisfy the physical law that the current in an inductance cannot change suddenly. When the fault occurs at an instant
when q– f= 0, there has to be a transient current whose value
is equal and opposite to the instantaneous value of the ac shortcircuit current. This transient current can be called a dc component and it decays at an exponential rate. Equation (2-36) can
be simply written as:
i = I m sin ω t + I dc e −Rt /L
(2-37)
This circuit transient is important in power systems from shortcircuit considerations. The following inferences are of interest.
There are two distinct components of the short-circuit current:
(1) an ac component and (2) a decaying dc component at an
(a) Short circuit of a passive RL circuit on ac source, switch closed at zero crossing of the voltage wave. (b) Short circuit of a passive RL
circuit on ac source, switch closed at the crest of the voltage wave.
14
CHAPTER TWO
FIGURE 2-13
To illustrate concept of time constant of an RL circuit.
exponential rate, the initial value of the dc component being equal
to the maximum value of the ac component.
Factor L/R can be termed as a time constant. The exponential then becomes Idc e–t/t′, where t′ = L/R. In this equation making
t = t′ will result in approximately 62.3 percent decay from its
original value, that is, the transient current is reduced to a value
of 0.368 per unit after a elapsed time equal to the time constant
(Fig. 2-13). The dc component always decays to zero in a short
time. Consider a modest X/R of 15; the dc component decays to
88 percent of its initial value in five cycles. This phenomenon is
important for the rating structure of circuit breakers. Higher is
the X/R ratio, slower is the decay.
The presence of the dc component makes the total short-circuit
current wave asymmetrical about zero line; Fig. 2-12a clearly shows
this. The total asymmetrical rms current is given by:
it (rms,asym ) = (ac component )2 + (dc component )2 (2-38)
FIGURE 2-14
phase a.
In a three-phase system, the phases are displaced from each
other by 120°. If a fault occurs when the dc component in phase a
is zero, the phase b component will be positive and the phase component will be equal in magnitude but negative. As the fault is symmetrical, the identity, Ia + Ib + Ic = 0, is approximately maintained.
Example 2-5 We will illustrate the transient in an RL circuit with
EMTP simulation. Consider R = 3.76 Ω and X = 37.6 Ω, the source
voltage is 13.8 kV, three phase, 60 Hz. The simulated transients in
the three phases are shown in Fig. 2-14. The switch is closed when
the voltage wave in phase a crests. The steady-state short-circuit current is 211A rms < 84.28°. This figure clearly shows the asymmetry
in phases b and c and in phase a there is no transient. In phases
b and c the current does not reach double the steady-state value,
here the angle φ = 84 . 28 ° . The lower is the resistance, higher is the
asymmetry.
The short circuit of synchronous machines is more complex and
is discussed in Chaps. 10 and 11.
2-8-2
First-Order Pulse Transients
Pulse transients are not caused by switching, but by the pulses generated in the sources. Pulses are represented by unit steps (App. B).
The unit step is defined as:
u(t − t1 ) = 0
t < t1
=1
t > t1
(2–39)
Any pulse train can be constructed from a series of unit steps
and the response determined by superimposition (Fig. 2-15). As
the network is linear, the step responses are all the same, only
shifted in time by the appropriate amount.
Consider the response of inductance and capacitance to a pulse
transient. The response to a unit step function is determined by
the state variable of the energy storage device. When the unit step
EMTP simulation of transients in passive RL circuit on three-phase, 13.8 kV, 60 Hz source, transient initiated at peak of the voltage in
TRANSIENTS IN LUMPED CIRCUITS
2-9-1
15
DC Excitation
We will first consider dc excitation. Consider resistance, inductance, and capacitance in series excited by a dc source. There is
no charge on the capacitor and no energy stored in the inductance
prior to closing the switch.
In App. A we studied the second-order differential equation of
the form:
f (t ) = a
d 2q
dq
+ b + cq
dt
dt 2
(2-41)
The solution of the complementary function (CF) depends upon
whether the roots are equal, imaginary or real, and different. In a
series RLC circuit, the current equation is written as:
L
di ∫ idt
+
+ Ri = f (t )
dt
C
(2-42)
Differentiating:
d 2i R di
i
+
+
= f ′(t )
dt 2 L dt LC
(2-43)
Case 1 (Overdamped)
If R > 4 L /C
FIGURE 2-15
(a) Unit step u (t ). (b) Unit step u (t – t1). (c) Pulse
u (t ) – u (t – t1).
(2-40)
1
i L (t ) =
u(t − t 1 )(1 − e −(t − t1 )/ τ )
R th
where τ = R thC for the capacitance and L/Rth for the inductance and
Rth is the Thévenin resistance.
Example 2-6 Consider a pulse source, which puts out two
pulses of 5 V, 5 ms in length spaced by 10 ms. Find the voltage on
a capacitor of 100 µF, Rth = 1000 Ω.
The voltage source can be written as:
v = 5u(t ) − 5u(t − 0 . 05) + 5u(t − 0 . 015) − 5u(t − 0 . 02)
τ = 103 × 100 × 10−6 = 10−1
) − 5u(t − 0.05)(1 − e
+ 5u(t − 0.015)(1 − e
2-9
−b − b2 − 4ac
s2 =
2a
−5(t − 0.015 )
(2-46)
The constants A and B can be found from the initial conditions.
Consider that the transient is initiated at t = 0+, the initial values of
q and q′ are found:
q(0+ ) = A + B + qss
q′(0+ ) = s1 A + s2 B + q′ss
b 2 = 4ac (R = 4 L /C )
Thus, the voltage on the capacitor is:
5u(t − e
−b + b2 − 4ac
2a
(2-47)
These equations give the values of A and B.
Case 2 (Critically Damped)
If both the roots are equal:
The time constant is given by:
−5(t − 0.05 )
(2-45)
where qss is the steady-state solution and s1 and s2 are given by:
s1 =
vC (t ) = u(t − t1 )(1 − e −(t − t1 )/ τ )
−5t
The system is overdamped. The solution can be written as:
q(t ) = Ae s1t + Be s2t + qss
function is zero, there is no voltage on the capacitor and no current
in the inductance. At t = t1:
(2-44)
(2-48)
the system is critically damped. The solution is given by:
)
) − 5u(t − 0.02)(1 − e
q(t ) = Ae st + Bte st + q ss
−5(t − 0.02 )
)
SECOND-ORDER TRANSIENTS
There are two energy storage elements, and a second-order differential equation describes these systems.
(2-49)
where s is given by:
s=
−b
2a
(2-50)
The constants A and B are found from the initial conditions.
16
CHAPTER TWO
A and B can be found from the initial conditions:
Case 3 (Underdamped)
If the roots are imaginary, that is,
b 2 < 4ac
(R < 4 L / C )
i(0+ ) = A + B + 2 . 5 = 0
(2-51)
The system is underdamped and the response will be oscillatory.
This is the most common situation in the electrical systems as the
resistance component of the impedance is small. The solution is
given by:
q(t ) = Ae −α t cos β t + Be −α t sin β t + q ss
(2-52)
where:
α=
b
2a
4ac − b 2
2a
β=
(2-53)
Again, the constants A and B are found from the initial conditions.
The role of resistance in the switching circuit is obvious; it will damp
the transients. This principle is employed in resistance switching as
we will examine further in the chapters to follow.
Example 2-7 A series RLC circuit with R = 1 Ω, L = 0.2 H, and
C = 1.25 F, excited by a 10 V dc source. The initial conditions are
that at t = 0, i = 0, and di/dt = 0. In the steady state, di/dt and d 2i /dt 2
must both be zero, irrespective of the initial conditions. These values are rather hypothetical for the purpose of the example and are
not representative of a practical power system. We can write the
differential equation:
2
d i
di
+ 5 + 4i = 10
dt
dt 2
Taking Laplace transform:
10
s i(s) − si(0) − I′(0) + 5[si(s) − I(0)]+ 4i(s) =
s
10
s2i(s) + 5si(s) + 4i(s) =
s
10
i(s) = 2
s(s + 5s + 4 )
2
Resolve into partial fractions:
i(s) =
2. 5
2
0.5
−
−
s (s + 1) (s + 4 )
i′(0+ ) = (− 1)A + (− 4 )B + 0 = 0
Given the initial conditions that i(0+ ) and i′(0+ ) are both zero,
A = –2, B = –1/2 and the complete solution is:
i = − 2e −t − 0 . 5e −4t + 2 . 5
It may not be obvious that the solution represents a damped
response. The equation can be evaluated at small time intervals and
the results plotted.
Example 2-8 Consider now the same circuit, but let us change
the inductance to 2.5 H. This gives the equation:
d 2i
di
+ 4 + 4 = 10
dt
dt 2
Here the roots are equal and the system is critically damped.
iss =
10
= 2. 5
4
i′ss = 0
s = −2
Therefore the solution is:
i = Ae −2t + Bte −2t + 2 . 5
From initial conditions:
i(0+ ) = A + 0 + 2 . 5 = 0
i′(0+ ) = (− 2)A + B + i′ss
Thus, A = –2.5, B = –5
The solution is:
i = 2 . 5(1 − e −2t ) − 5te −2t
Example 2-9 Next consider an underdamped circuit. R = 1 Ω,
L = 0.2 H, and C = 0.5 F, again excited by 10 V dc source; initial
conditions are the same. This gives the equation:
d 2i
di
+ 5 + 10i = 10
dt
dt 2
Therefore from Eq. (2-53):
Taking inverse transform, the solution is:
i = − 2e −t − 0 . 5e −4t + 2 . 5
This is an overdamped circuit. Alternatively, the solution can be
found as follows:
10
= 2.5
4
i′ss = 0
iss =
s1 =
− 5 + 25 − 16
= −1
2
s2 =
− 5 − 25 − 16
= −4
2
Therefore the solution is:
i = Ae −t + Be −4t + 2 . 5
α=
β=
b
= 2. 5
2a
4ac − b2
= 1 . 94
2a
Therefore the solution can be written as:
i = Ae −2.5t cos1 . 94t + Be −2.5t sin 1 . 94t + iss
iss = 1
i(0+ ) = A + iss = 0 A = − 1
i′(0+ ) = −α A + β B + i′ss = −(2 . 5)(− 1) + 1 . 94 B = 0 B = − 1 . 29
Therefore, from Eq. (2-52) the solution is:
i = −e −2.5t cos1 . 94t − 1 . 29e −2.5t sin 1 . 94t + 1
TRANSIENTS IN LUMPED CIRCUITS
Alternatively, the solution can be written as:
i = Ce
−α t
The PI can be calculated as 1.25 sin 2t (see App. A). The complete
solution is:
cos(β t − φ ) + iss
i = Be −2t + Cte −2t + 1 . 25 sin 2t
where:
Again the constants B and C are found from the initial conditions:
C = A 2 + B2
tan φ =
i(0+ ) = B = 0
B
A
i′(0+ ) = (− 2)B + C + 2 . 5 = 0
This gives:
Therefore the solution is:
i = 1 . 63e −2.5t cos(1 . 94t − 52 . 2 °) + 1
2-9-2
17
i = 1 . 25 sin 2t − 2 . 5te −2t
RLC Circuit on AC Sinusoidal Excitation
We studied the response with a dc forcing function. These examples
will be repeated with a sinusoidal function, 10 cos 2t.
Example 2-10: Overdamped Circuit The differential equation is:
d 2i
di
+ 5 + 4i = 10 cos 2t
dt
dt 2
1
1
cos 2t
10 cos 2t = 10
D 2 + 5D + 4
(− 22 ) + 5D + 4
= 10
D cos 2t
1
= sin 2t
cos 2t = 10
5D
5(− 22 )
CF = Be −t + C −4t
i = Be −t + Ce −4t + sin 2t
The constants B and C are found from the initial conditions:
i(0+ ) = B + C + 0 = 0
This gives B = 2/3 and C = –2/3. The solution is:
2
2
i = e −t − e −4t + sin 2t
3
3
Alternatively, we can arrive at the same result by using Laplace
transform:
20
s2 + 4
This gives:
20
i(s) = 2
(s + 4 )(s + 4)(s + 1)
2
2
2
−
+
s2 + 4 3(s + 4 ) 3(s + 1)
Taking the inverse Laplace transform, we get the same result.
Example 2-11: Critically Damped Circuit The differential
d 2i
di
+ 4 + 4 = 10 cos 2t
dt
dt 2
10(5D − 6)cos 2t
2 5(− 22 ) − 36
The complete solution is:
The constants A and B are found as before by differentiating and
substituting the initial values, A =–0.44, B =1.22. The solution is
therefore:
i = 1 . 22e −2.5t cos1 . 94t + 0 . 44e −2.5t sin 1 . 94t
+ 0 . 44 cos 2t + 0 . 74 sin 2t
i′(0+ ) = −B + 4C + 2
equation is:
=
1
10 cos 2t
cos 2t =
(5D + 6)
D 2 + 5D + 10
i = Ae −2.5t cos1 . 94t + Be −2.5t sin 1 . 94t
+ 0 . 44 cos 2t + 0 . 7 4 sin 2t
The complete solution is:
=
PI = 10
iss = 0 . 44 cos 2t + 0 . 74 sin 2t
We can write the CF of the equation as before in Example 2-7:
[s2i(s) − si(0) − I′(0)]+ 5[si(s) − I(0)]+ 4i(s) =
d 2i
di
+ 5 = 10i = 10 cos 2t
dt
dt 2
The PI, that is, the steady-state solution is:
Given the same initial conditions that i = 0, and di/dt = 0 at t = 0, as
before, we can write the Particular integral (PI) as:
PI =
Example 2-12 Lastly, we will consider the underdamped circuit,
excited by an ac source. As before the differential equation is:
In general, we can write the roots of the characteristic equation
of a series RLC circuit as:
s1, s2 = −α ± α 2 − ωd2
= α ± ωn2
(2-54)
where:
α = R / 2L
ωd = 1/ LC
(2-55)
We can term a as the exponential damping coefficient, wd as the
resonant frequency of the circuit and wn is the natural frequency.
Figure 2-16a, b, and c shows underdamped, critically damped, and
overdamped responses, respectively.
We can write the natural response of RLC circuit in the general
form:
i = I me −α t sin(ωnt + β )
(2-56)
The voltage across the capacitor is:
vC =
1
C
∫ idt = I m
L −α t
e sin[ωnt + β − (900 + δ )]
C
(2-57)
18
CHAPTER TWO
FIGURE 2-16
(a) Underdamped response. (b) Critically damped response. (c) Overdamped response patterns.
Then
where:
α
δ = tan −1
ωn
and
(α 2 + ωn2 ) = ωd2 +
1
LC
(2-58)
i′n (0) = i′(0) + i′f (0) = s1 A1 + s2 A2
The voltage across the inductor is:
vL = L
di
L −α t
=I
e sin[ωnt + β + (900 + δ )]
dt m C
(2-59)
Note that voltage across the capacitor is lagging more than 90°
with respect to the current. Also the voltage across the inductor
is leading slightly more than 90° with respect to current. In the
steady-state solution, these are exactly in phase quadrature. The
difference is expressed by angle d, due to exponential damping.
This angle denotes the displacement of the deviation of the displacement angle. As the resistance is generally small, we can write:
ωn ≈
1
LC
and
tan δ ≈
R
2 LC
(2-60)
In most power systems, d can be neglected.
In the preceding examples we have calculated the constants of
integration from the initial conditions. In general, to find n constants,
we need:
• The transient response f(0) and its (n – 1) derivatives
• The initial value of the forced response ff (0) and its n – 1
derivatives.
Consider for example a second-order system:
in (t ) = A1e s1t + A2e s2t
i′n (t ) = s1 A1e s1t + s2 A2e s2t
in (0) = i(0) + i f (0) = A1 + A2
(2-61)
From Eq. (2.61) the constants A1 and A2 can be calculated.
From the above examples we observe that the end results do not
immediately indicate what type of response can be expected. The
response can be calculated in small increments of time and plotted
to show a graphical representation.
Example 2-13 A 500-kvar capacitor bank is switched through an
impedance of 0.0069 +j0.067 Ω, representing the impedance of cable
circuit and bus work. The supply system voltage is 480 V, three phase,
60 Hz, and the supply source has an available three-phase shortcircuit current of 35 kA at < 80.5°. The switch is closed when the phase
a voltage peaks in the negative direction.
The result of EMTP simulated transients of inrush current and
voltage for 50 ms are shown in Fig. 2-17a. This shows that the
maximum switching current is 2866 A peak (=2027 A rms), and that
the voltage transient, shown in Fig. 2-17b results in approximately
twice the normal system voltage. The calculated steady-state current
is 507 A rms. This example is a practical case of capacitor switching
transients in low-voltage systems, and we will further revert to this
subject in greater detail in the following chapters.
To continue with this example, the resistance is changed to correspond to critical damping circuit. The response is shown in Fig. 2-17c;
the current transient is eliminated. The voltage transients also disappear,
which is not shown.
2-10
PARALLEL RLC CIRCUIT
The differential equation governing the parallel RLC circuit is similar to the series circuit. It can be written as:
d 2ϕ 1 dϕ ϕ
+
+
= f (t )
dt 2 RC dt LC
(2-62)
TRANSIENTS IN LUMPED CIRCUITS
FIGURE 2-17
19
EMTP simulation of switching of a 500 kvar capacitor on 480-V, three-phase, 60-Hz source of 35-kA short-circuit current, switch closed
at the crest of voltage in phase a, underdamped circuit. (a) Current transients. (b) Voltage transients. (c) Current transients, critically damped circuit.
20
CHAPTER TWO
FIGURE 2-17
where f(t) is the forcing function and j can be current or voltage.
Comparing with Eq. (2-43) for the series circuit we note that parallel circuit time constant RC is akin to the series circuit time constant
L/R. The product of these two time constants gives LC. If we define
a parameter:
η = R /Z0 = R / L /C
(2-63)
Then RC/(L/R), that is, ratio of the time constants or parallel and
series circuits is η 2 . This leads to duality in the analysis of the series and parallel
circuits. Note that Z0 = L /C is called the characteristic impedance
or surge impedance, which is of much significance in transmission
line analysis (Chap. 4).
Consider in a parallel RLC circuit, the capacitor is charged and
suddenly connected to the RL circuit in parallel, and there is no
external excitation. When the switch is closed, the current from the
charged capacitor divides between the resistance and inductance:
IC = I R + I L
(Continued )
The current in the inductor is given by:
s2 + s + 1 i L (s) = s + 1 I L (0) + I′L (0
0)
2
τp τ
τp
(2-66)
However, the initial current is zero and I′L (0) = VC (0)/L . Therefore:
i L (s) =
VC (0)
1
L
s
1
s2 + + 2
τ
τ
p
(2-67)
Again the form of solution will depend upon the values of the
roots of the quadratic equation:
s1, s2 = −
1
1 1
4
±
−
2τ p 2 τ p2 τ 2
(2-68)
If we want to find the capacitor voltage, then we can write the
equation:
dV
V
L dI L
−C C = I L + C = I L +
R dt
dt
R
d 2VC 1 dVC VC
+
+
=0
RC dt LC
dt 2
Eliminate VC from the above equations:
(2-69)
And in terms of Laplace transform, the voltage across the capacitor is:
d 2I L 1 dI L I L
+
+
=0
dt 2 RC dt LC
(2-64)
This equation can be solved like a series circuit differential equation,
as before. The equation can be written as:
d 2I L 1 dI L I L
+
+
=0
dt 2 τ p dt τ 2
(2-65)
vc (s) =
VC (0)
s2 + s + 1
2
τ p τ
(2-70)
Note the similarity between Eq. (2-62) and Eq. (2-43). These
differential equations can be solved as before and again the response
can be damped, critically damped, or oscillatory.
TRANSIENTS IN LUMPED CIRCUITS
2-11
And the response to the second step is:
SECOND-ORDER STEP RESPONSE
The step response of second-order systems for zero initial conditions is suitable in analysis of pulse transients. Consider zero initial
conditions. The final output with a step input is a constant:
q ss =
f (t )
c
(2-71)
Here c is same as in the general differential equation [Eq. (2-41)]. The
response will be overdamped, critically damped, or underdamped
depending upon the roots of the quadratic equation, as before.
Overdamped
b 2 > 4ac
q(t ) = −
b
1
1
b
1
1 +
e s1t − 1 −
e s2t +
2
2
2c
2c
c
b − 4ac
b − 4ac
(2-72)
1
i2 (t ) = [1 − e −0.25(t−0.1) cos 0 . 66(t − 0 . 1)
5
− 0 . 378e −0.25(t−0.1) sin 0 . 66(t − 0 . 1)] u(t )
The total current is:
i1(t ) + i2 (t )
2-12 RESONANCE IN SERIES AND PARALLEL RLC
CIRCUITS
Amplification of the voltage and currents can occur in RLC resonant
circuits. The natural frequency of a power distribution system is
much higher than any of the load-generated harmonics. However,
application of capacitors, in presence of harmonic producing loads,
can bring about a resonant condition (Chap. 6).
2-12-1
1
z = R + j ω L −
ω C
b2 = 4ac
(2-73)
At a certain frequency, say f0 , z is minimum when:
Underdamped
ωL −
b < 4ac
2
α
1 1
q(t ) = − e −α t cos β t − e −α t sin β t
βc
c c
Example 2-14
(2-74)
Consider a network given by the following
equation:
f (t ) = 10
d 2t
di
+ 5 = 5i
2
dt
dt
ωh =
α
1 1
i(t ) = − e −α t cos β t − e α t sin β t
c c
βc
β=
4ac − b
= 0 . 66
2a
Therefore:
1
i(t ) = (1 − e −0.25t cos 0 . 66t − 0 . 378e −0.25t sin 0 . 66t ) u(t )
5
Consider a pulse of:
2u(t ) − 2u(t − 0 . 1)
Response to first step is:
2
i1(t ) = (1 − e −0.25t cos 0 . 66t − 0 . 378e −0.25t sin 0 . 66t )u(t )
5
ω = ω0 =
1
LC
(2-75)
2
R
R
1
1
1
= ω0 1 + 2 +
+ +
2L
4Q0 2Q0
2 L LC
(2-76)
The bandwidth b shown in Fig. 2.18d is given by:
β=
2
c=5
or
2
R
R
1
1
1
ωl = − + +
= ω0 1 + 2 −
2L
4Q0 2Q0
2 L LC
Here
b
5
=
= 0 . 25
2a 20
1
=0
ωC
Figure 2-18b shows the frequency response. The capacitive reactance inversely proportional to frequency is higher at low frequencies, while the inductive reactance directly proportional to frequency
is higher at higher frequencies. Thus, the reactance is capacitive and
angle of z is negative below f0, and above f0 the circuit is inductive and angle z is positive (Fig. 2-18c). The voltage transfer function,
Hv = V2/V1 = R/Z, is shown in Fig. 2-18d. This curve is reciprocal of
Fig. 2-18b. The half-power frequencies are expressed as:
This represents an underdamped system. The solution is:
α=
Series RLC Circuit
The impedance of a series circuit (Fig. 2–18a) is:
Critically damped
1
b −st 1
te +
q(t ) = − e −st −
2ac
c
c
21
or
Q0 =
R ω0
=
L Q0
(2-77)
ω0 L
R
The quality factor Q is defined as:
maximum energy stored
Q0 = 2π
energy dissipated per cyclee
2-12-2
(2-78)
Parallel RLC Circuit
In a parallel RLC circuit (Fig. 2-19a), the impedance is high at resonance:
y=
1
1
+
+ jω C
R jω L
22
CHAPTER TWO
FIGURE 2-18
(a). Series RLC resonant circuit. (b) Impedance amplitude Z/R versus angular frequency. (c) Impedance angle versus angular
frequency. (d ) Voltage transfer function.
Thus, the resonant condition is:
−
1
+ωC = 0
ωL
or
ω = ωα =
1
LC
(2-79)
Compare Eq. (2-79) with Eq. (2-75) for the series circuit.
The magnitude Z/R is plotted in Fig. 2-19b. Half-power frequencies
are indicated in the plot. The bandwidth is given by:
β=
ωa
Qa
(2-80)
where the quality factor for the parallel circuit is given by:
Qa =
C
R
= ωa RC = R
L
ωa L
(2-81)
Example 2-15 This example is a simulation of the current in a
series resonant circuit excited by a three-phase, 480-V, and 60-Hz
source. The components in the series circuits are chosen so that
the resonant frequency is close to the source frequency of 60 Hz
(L =5 mH, C =0.00141 F) and the resistance in the circuit is
0.1 Ω. The transients are initiated by closing the switch at peak
of the phase a voltage in the negative direction and these will
reach their maximum after a period of three to five times the
time constant of the exponential term. As the resistance is low,
the maximums may be reached only after a number of cycles.
Figure 2-20a shows the current transient in phase a only.
A simulation of the transient in the same phase when the resonant frequency of the circuit is slightly different from the source
frequency is shown in Fig. 2-20b. As the natural and system
frequencies are different, we cannot combine the natural and
steady-state harmonic functions, and these will be displaced in
time on switching. The subtraction and addition of the two components occur periodically and beats of total current/voltage
appear. These beats will diminish gradually and will decay in three
to five time constants t. The circuit behavior after a short time of
switching can be represented by:
i = 2I m sin
2-12-3
ω − ωn
ω − ωn
t × cos
t
2
2
(2-82)
Normalized Damping Curves
Consider the parallel RLC circuit. The roots of the auxiliary equation can be written as:
s1, s2 =
1
1
±
1 − 4Qa2
2RC 2RC
(2-83)
The response to a step input of voltage and current can be expressed
as a family of damping curves for the series and parallel circuits. To
TRANSIENTS IN LUMPED CIRCUITS
FIGURE 2-19
FIGURE 2-20
23
(a) Parallel RLC resonant circuit. (b) Impedance amplitude Z/R versus angular frequency.
(a) EMTP simulation of RLC series resonance in 480-V, three-phase, 60-Hz system; the resonant frequency coincides with the supply
source frequency. Current transient in phase a, switch closed at the crest of the voltage wave in phase a. (b) Transient in phase a, the resonant frequency close
to the source frequency.
24
CHAPTER TWO
unitize the solutions, we use response of a parallel LC circuit. For
the voltage and current:
v(t ) =
1
sin(ωat )
ωaC
(2-84)
i(t ) =
1
sin(ωat )
ωa L
(2-85)
The maximum voltage or current occurs at an angular displacement
of ωat = π /2. If we set ωat = θ , then t/(2RC) can be replaced with
θ /2Qa .
Then the solution for underdamped circuit:
f (Qa ,θ ) =
θ 1 − 4Q 2
2Qa e −θ / 2Qa
a
sinh
2Qa
1 − 4Qa2
(2-86)
for critically damped:
f (Qa ,θ ) = θ e
−θ / 2Qa
2Qa e −θ / 2Qa θ 1 − 4Qa2
sin
1 − 4Qa2 2Qa
where I B is the vector of injection of bus currents. The usual convention for the flow of the current is that it is positive when flowing toward the bus and negative when flowing away from it. VB is
the vector of the bus or nodal voltages measured from the reference
node:
I1
I2
⋅
Y11
Y12
Y21
Y22
=
⋅
⋅
Yn−1,11 Yn−2,2
⋅ Y1,n−1
⋅ Y2,n−1
⋅
⋅
⋅ Yn−1,n−1
V1
V2
⋅
Vn
(2-90)
YB is nonsingular square matrix of order (n – 1)(n – 1). It has an
inverse:
(2-88)
2-13 LOOP AND NODAL MATRIX
METHODS FOR TRANSIENT ANALYSIS
This section provides an overview of matrix methods for transient
analysis, which are used extensively for the steady-state solutions
of networks. Network equations that can be formed in bus (nodal),
QP (75) = 1.00 pu.
(2-89)
(2-87)
Figure 2-21 shows the normalized curves from which the response
can be ascertained. For the series RLC circuit, similar curves can be
drawn by replacing Qa with Q0. This is shown in Fig. 2-22. These
normalized curves are based upon the Figures in Reference 1.
FIGURE 2-21
IB = YBVB
I( n−1)
and for the overdamped circuit:
f (Qa ,θ ) =
loop (mesh), or branch frame of reference, that is, in the bus frame
the performance is described by n – 1 linear independent equations for n number of nodes. The reference node which is at ground
potential is always neglected. In the admittance form:
YB−1 = Z B
(2-91)
where Z B is the bus impedance matrix, also of order (n – 1)
(n – 1).
In this book we will denote a matrix Z by a top bar, that is, Z,
the transpose of the matrix by, Z t the inverse of the matrix by Z −1,
the conjugate of a matrix by Z * , the adjoint of a matrix by Zadj .
Yii (i =1, 2, 3, 4 …) is the self-admittance or driving point admittance of node i, given by the diagonal elements, and it is equal to the
algebraic sum of all admittances terminating in that node. Yik (i, k =
1, 2, 3, 4…) is the mutual admittance between nodes i and k, and it
is equal to negative of the sum of all admittances directly connected
between these nodes.
Normalized damping curves, parallel RLC circuit, 0.50 ≤ Qp ≤ 75.0, 0.50, 1.0, 2.0, 5.0, 10.0, 15.0, 30.0, and 75.0, with
TRANSIENTS IN LUMPED CIRCUITS
25
Normalized damping curves, series RLC circuit, 0.10 ≤ QS ≤ 100.0, 0.10, 0.30, 0.50, 0.75, 1.0, 1.5, 2.0, 5.0, 10.0, 15.0, 30.0, and
100.0, with QS (100) = 1.99.
FIGURE 2-22
In the loop frame of reference:
VL = Z L IL
(2-92)
where VL is the vector of loop voltages, IL is the vector of unknown
loop currents, and Z L is the loop impedance matrix of the order of l ×l.
The loop impedance matrix is derived from basic loop impedance
equations, and it is based upon Kirchoff’s voltage law. It can be
constructed without writing the loop equations, just like the admittance matrix in the bus frame of reference.
Consider the circuit of Fig. 2-23. By inspection, we can write the
following equations:
R1 + L1p +
1
C1p
−
1
C1p
1
−
C1p
1
R 2 + R 3 + L2 p +
C1p
0
−(R 3 + L2 p)
.
−(R 3 + L2 p)
L2 p + L 3 p + R 3 +
1
C1p
i1
V1
i2 = 0
V2
i3
(2-93)
where the operator p is defined as d/dt, and 1/p is written in place of
the integrator. Circuit theorems and reduction techniques applied
in steady state can be adapted to transient state.
2-14
STATE VARIABLE REPRESENTATION
The differential equations of a system can be written as first-order
differential equations. A state variable representation of nth order
can be arranged in n first-order differential equations:
x 1 = f1( x1, x 2 ,..., x n ; r1, r2 ,..., rn )
FIGURE 2-23
currents, i1, i2, and i3.
Circuit for loop matrix development with three loop
x n = f n ( x1, x 2 ,.. .., x n ; r1, r2 ,..., rn )
(2-94)
26
CHAPTER TWO
We write this in the following form:
x (t ) = f[x(t ), r(t ), t]
(2-95)
where x is n-dimensional vector of unknown variables, called the state
vector, r is m-dimensional input vector, f is the n-dimensional function vector, and t is the time variable. The output can be expressed in
terms of state x(t) and input r(t) and can be written as:
(2-96)
y(t ) = g[x(t ), r(t ), t]
The state and output equations constitute the state of the system.
In a model of a linear time-invariant system, the derivative of
each state is a linear combination of the system states and inputs:
x 1 = a x1 + a12 x 2 + ... + a1n x n + b11r1 + b12r2 + ... + b1mrm
at any time t0, the state is known, then the state equations
unequally determine the state at any time t > t0 for any given
input. Thus, given the state of the circuit at t =0, and all
inputs, the behavior of the circuit is completely determined
for t > t0.
• A state variable model is more amenable to simulation on a
digital computer.
• It permits compact description of complex systems.
• Thestate variable method lends itself easily to optimization
techniques.
• It is easy to apply the state variable method to time-varying
and nonlinear systems.
11
(2-97)
x n = a n1 x1 + a n 2 x 2 + ... + a nn x n + bn1r1 + bn 2r2 + ... + bnmrn
This can be written in the matrix form:
a11 a12
x 1
x 2 = a 21 a 22
⋅
⋅
⋅
a n1 a n 2
x n
⋅ a1n
⋅ a2n
⋅ ⋅
⋅ a nn
b11 b12
x1
x2
b21 b22
+
⋅
⋅
⋅
xn
bn1 bn 2
⋅ b1m
⋅ b2 m
⋅ ⋅
⋅ bnn
r1
r2
⋅
rn
In the abbreviated form we can write:
(2-99)
Similarly the output is a linear combination of system states and
inputs, and the output equations can be written as:
y1 = c11 x1 + c12 x 2 + + c1n x n + d11r1 + d12r2 + + d1mrm
(2-100)
or in the matrix form:
d1m
d2m
d pm
L
dvc
= i(t ) − i L
dt
di L
= −Ri L + vC
dt
(2-103)
We can write Eqs. (2-103) in the state variables x1 and x2:
yp = c p1 x1 + c p 2 x 2 + + c p1n x n + d p1r1 + d p 2r2 + + d pmrm
d11 d12
x1
d12 d 22
x2
+
d p1 d p 2
xn
ic = C
Ri L (t ) = v0
c1n
c2 n
c pn
is a vector of state variables.
And the output of the system is given by:
y2 = c21 x1 + c22 x 2 + + c2 n x n + d 21r1 + d 22r2 + + d 2 mrm
c11 c12
y1
y2
c21 c22
=
yp
c p1 c p2
Consider the circuit of Fig. 2-24. The system contains two energy storage elements. The state of the system can be
described in terms of set of state variables, which are somewhat arbitrary, say x1 and x2. Let x1 be the capacitor voltage and x2, the inductor
current. Then:
v (t )
x(t) = C
i L (t )
(2-98)
x = Ax + Br
Example 2-16
r1
r2
rm
(2-101)
dx1
1
1
= − x 2 + i(t )
dt
C
C
dx 2 1
R
= x1 − x 2
L
dt
L
The output equation is:
y1(t ) = v0 (t ) = Rx 2
Thus, we can write the two equations concisely as:
x = Ax + Br state equation
y = Cx + Dr output equation
(2-102)
where x is n-dimensional state vector, r is m-dimensional input
vector, y is p-dimensional output vector, A is n × n square matrix,
B is n × m matrix, C is p × n matrix, and D is p × m matrix.
In a linear time-varying system, the elements of matrices
A, B, C, D are functions of time.
The advantages of the state model are:
• The state variable model makes all the states visible for all
time, besides providing the output information. In an inputoutput relation only, the intermediate states are missed. If
FIGURE 2-24
An RLC circuit excited by a current source, Example 2-16.
TRANSIENTS IN LUMPED CIRCUITS
The zero input response is given by:
These equations can be further written as:
x =
0
1
L
dx(t )
= Ax(t )
dt
−1
1
C x+
i(t )
C
−R
0
L
= A x + B i(t )
(2-104)
Thus matrix A is constant 2 × 2 matrix and B is a constant vector.
And output equation is:
y= 0 R x
(2-105)
For solving Eq. (2-104) the initial conditions of the capacitor voltage and inductor current are required. Thus the pair vC(0) =V0 and
iL (0) = I0 is called the initial state:
V
x0 = 0
I 0
FIGURE 2-25
27
and is determined by the initial state equation x0. If we consider
the plot of iL(t), vC(t) as t increases from 0 to infinity. A curve is
traced called the state-space trajectory and the plane iL-vC is called
the state-space of the circuit. This trajectory will start at the initial
point V0, I0 and end at the origin (0, 0), when t = ∞ . The velocity
of the trajectory (di L /dt, dvC /dt ) can be obtained from Eq. (2-103).
Thus, the trajectory of a space vector in a two-dimensional space
characterizes the behavior of a second-order circuit.
Figures 2-25a and 2-25b are the overdamped and underdamped
responses, while Fig. 2.25c shows three kinds of trajectories for
(a) overdamped, (b) underdamped, and (c) loss-free circuits. In the
underdamped case the trajectory is a shrinking spiral and in the lossfree cases it is an ellipse, which shows continuous oscillations. In
overdamped case (a), segment starts at (0.7, 0.9). The semiaxes of the
ellipse depend upon L and C and the initial state iL(0) and vC (0).
For various initial states in the iL-vC plane, usually uniformly
spaced points, we obtain a family of trajectories called the phase
portrait, as shown in Fig. 2-26.
(a) Overdamped response of iL and Vc. (b) Underdamped response of iL and Vc. (c) State-space trajectory of the response. The dotted
ellipse shows response of a loss-less circuit.
28
CHAPTER TWO
FIGURE 2-26
A phase portrait of the trajectories.
A trajectory can be plotted by starting at the initial state:
x 0 vC (0), i L (0)
t
And finding an estimate of new state x at increased small time interval
by Euler’s method:
dx
x new = x old + Dt
dt old
(2-106)
where Dt is the step length. Essentially during this small interval,
it is assumed that dx/dt is approximately constant. Thus the straight
line segment is approximated by:
dx
Dx =
Dt
dt const
2-15
(2-107)
DISCRETE-TIME SYSTEMS
In discrete-time systems, the essential signals are discrete-time in
nature. Continuous-time signals can be analyzed numerically on
the digital computer by approximating the continuous-time model
by a discrete-time model.
FIGURE 2-27
In digital data-processing systems, the continuous-time signal is
converted into discrete-time signal, which is fed into the discretetime system. The discrete-time system operates on this signal to perform the required data processing. Figure 2-27 shows the interface
between the discrete- and continuous-time signals.
Consider the integral:
y(t ) =
t
∫ r(τ )dτ
0
or
(2-108)
kT
y(kT ) =
∫ r(τ )dτ
0
The value of y(t) is the area of curve under r(t) in the time interval
0 to tn, shown in Fig. 2-28. Divide the curve into n small strips, kT,
k =0, 1, 2, 3, … n. Above equation can be written as:
y(kT ) =
kT −T
∫
0
r(τ )dτ +
kT
∫
r(τ )dτ
kT −T
≈ y(kT − T ) + Tr(kT )
Interface between continuous-time and discrete-time systems with output in continuous time.
(2-109)
TRANSIENTS IN LUMPED CIRCUITS
2-15-2
29
Second-Order Difference Equation
Now consider second-order differential equation given by:
d 2 y(t )
dy(t )
+ a1
+ a 0 y(t ) = x(t )
dt
dt 2
(2-115)
Intial conditions:
y(0) = y0
dy(t )
dt
= y 0
t =0
The equation can be written as:
d 2 y(kT )
dy(kT )
+ a1
+ a 0 y(kT ) = x(kT )
2
dt
dt
k = 0, 1, 2,...
(2-116)
FIGURE 2-28
The second derivative can be approximated as:
Rectangular estimation of an integral.
dy
dy
−
dt
dt t=kT
d y(kT )
t =kT +T
=
2
T
dt
The area under the integral:
2
kT
∫
r( x )dx
kT −T
is equal to Tr(kT), shown shaded if T is sufficiently small. The
Eq. (2-109) can be written as difference equation:
y(k ) = y(k − 1) + Tr(k )
k = 1, 2, 3,...
(2-110)
or
y(k + 1) − y(k ) = Tr(k + 1)
2-15-1
First-Order Difference Equation
Consider a first-order differential equation given by:
dy(t )
+ ay(t ) = x(t ) y(0) = y0
dt
(2-111)
This can be written as:
dy(kT )
+ ay(kT ) = x(kT )
dt
y(kT + T ) − y(kT ) y(kT ) − y(kT − T )
−
T
T
T
=
y(kT + T ) − 2 y(kT ) + y(kT − T )
T2
(2-117)
Thus, the second-order equation can be approximated with the following difference equation:
k = 0, 1, 2,...
The integral of a continuous function can be converted into a difference equation, which can be solved numerically.
=
y(k + 1) +
a 0T 2 − a1T − 2
T2
1
x(k )
y(k ) +
y(k − 1) =
1 + a1T
1 + a1T
1 + a1T
y(k + 2) +
a 0T 2 − a1T − 2
1
y(k + 1) +
y(k )
1 + a1T
1 + a1T
or
=
T2
x(k + 1)
1 + a1T
k = 0, 1, 2,…
(2-118)
These concepts can be generalized. An nth-order differential
equation
k = 0, 1, 2, 3,...
(2-112)
The derivative of y(t) at t =kT is the slope of curve y(t) at t =kT and
can be approximated by the equation:
dy(kT ) y(kT + T ) − y(kT )
=
dt
T
(2-113)
By making T smaller and smaller, the accuracy of calculation
improves. Thus Eq. (2-113) becomes:
y(k + 1) + (aT − 1) y(k ) = Tx(k )
k = 0,1, 2,...
d n y(t )
d n−1 y(t )
dy(t )
+ a n−1
+ + a1
+ a 0 y(t )
n−1
n
dt
dt
dt
= bm
d m x(t )
+ + b0 x(t )
dt m
(2-119)
can be approximated with the following nth-order difference
equation,
y(k + n ) + α n−1 y(k + n − 1) + + α1 y(k + 1) + α0 y(k )
= βm x(k + m) + + β0 x(k )
k = 0, 1, 2,…
(2.120)
(2-114)
This is a first-order difference equation with the initial condition
that y(0) =y0
where a’s and b’s are appropriate constants.
As we stated in Chap. 1, the EMTP algorithms are based upon
difference equations.
30
CHAPTER TWO
2-17-1 Linearization of a Dynamic System
2-16 STATE VARIABLE MODEL
OF A DISCRETE SYSTEM
Similar to continuous-time case the state variable model of a discrete system is given by:
x(k + 1) = Ax(k ) + Br(k )
y(k ) = Cx(k ) + Dr(k )
state equation
(2-121)
o utput equation
where x(k) is n-dimensional state vector, r(k) is m-dimensional input
vector, y(k) is p-dimensional output vector, A =(n × n) matrix
of constants, B =(n × m) matrix of constants, C = (p × n) matrix of
constants, and D = (p × m) matrix of constants. The state equation is
a set of n (order of the system) first-order difference equations.
2-17
Electrical systems are highly nonlinear in nature. Even a linear
element is linear under constraints. Its characteristics undergo a
change with temperature and current. Linear systems can be analyzed easily and powerful analytical tools are available. The behavior
of many systems can be modeled with linear mathematical models
to a high accuracy provided the range of variables is limited.
First consider a static system, with input r(t) and output y(t), the
input-output relation shown in Fig. 2-29. Though the relationship
is nonlinear, it is continuous.
Consider the operating point given by r0, y0. A Taylor series
around the operating point gives:
x(k + 1) = f[x(k ), r(k )]
(2-126)
Equation (2-125) is for a continuous-time system, while (2-126)
is for a discrete-time system. It is desired to approximate the system
with a linear time-invariant model, given by:
x (t ) = Ax (t ) + Br(t )
x (k + 1) = Ax (k ) + Br(k )
(2-127)
x 1 = f1( x1,...., x n , r1,....., rm )
............
(2-128)
x n = f n ( x1,...., x n , r1,....., rm )
The Taylor theorem can be used to expand these equations about
the equilibrium point (x0, r0), retaining only the first-order terms:
∂f
∂f
∂f
∂ f
x 1 = x 1 = 1 x 1 + + 1 x n + 1 r1 + + 1 rm
∂ x1 0
∂ r1 0
∂ x n 0
∂ rm 0
∂ f
∂f
∂f
∂f
x n = x n = n x 1 + + n x n + n r1 + + n rm
∂ r1 0
∂ x n 0
∂ rm 0
∂ x1 0
(2-129)
(2-123)
where m is the slope of j(r) at the operating point. We can write:
y − y0 = m(r − r0 )
These equations can be written as:
x = Ax + Br
(2-130)
where:
(2-124)
or
(2-125)
...
(2-122)
For small variations of input around the operating point, only the first
term of the series may be considered, giving a linear approximation:
y = y0 + m(r − r0 )
x(t ) = f[x(t ), r(t )]
For a system with n state variables and m inputs, the state equation is written as:
LINEAR APPROXIMATION
dϕ r − r0 d 2ϕ (r − r0 )2
y = ϕ (r ) = ϕ (r0 ) +
+
+
dr 0 1! dr 2 0 2!
Consider a nonlinear time-invariant dynamic system, whose state
equations is given by:
y = mr
∂ f1
∂ x1
A= .
∂fn
∂ x1
∂ f1
∂ r1
B= .
∂fn
∂ r1
∂ f1
∂x n
.
.
∂fn
.
∂x n
.
∂fn
∂ rm
.
.
∂fn
.
∂ rm
(2-131)
0
.
(2-132)
0
The partial derivatives of f are evaluated at the equilibrium
points, which must be first found out. At the equilibrium points
the inputs reach steady-state values, which we may denote by:
r10 , r20 ,...., rm0 . Then for a linear or nonlinear system, x0 is an equilibrium point, if it does not change with constant input:
dx(t )
= f[x(t ), r0] = 0
dt
FIGURE 2-29
Linearization of a non-linear system.
x(k + 1) − x(k ) = f [x(k ), r0] = 0
(2-133)
TRANSIENTS IN LUMPED CIRCUITS
In this chapter we studied simple transients in lumped circuits.
We did not attach physical meaning to the various studies, except
the short circuit of an inductor with resistance connected to an ac
source and capacitor switching. However, many circuits studied
can be related to the practical phenomena, that is, switching of
capacitors, recovery voltages on current interruption in ac circuits,
harmonic resonance, lumped parameters of transmission lines,
damping of transients and the like. We also formed a conceptual
base of the space-state equations, difference equations, and numerical solutions of the differential equations, linearity, time-invariance,
and the like. These will be further discussed in appropriate chapters
in this book. We used Laplace method of analysis; however, this
has limited applications for modeling of large networks on digital
computers; also saturation and nonlinearity cannot be accounted
for. See App. G for continuing discussion.
31
5. Consider an ideal generator of 13.8 kV, with a series impedance of 0.01 +j0.10 Ω. Calculate the first peak of the shortcircuit current if a fault occurs at a time when the voltage (rms)
is decreasing and is at 5.0 kV.
6. Consider a series RLC circuit, R =4 Ω, L = 2.0 H, C =0.05 µF.
Find the charge and current at any time t > 0 in the capacitor, if the
switch is closed at t =0. Consider a source voltage of 100 V, and
repeat for a voltage of 100 sin 4t. Solve using differential equations.
7. Solve Problem 6 using Laplace transform.
8. In Fig. 2-P3, find the pulse response for a pulse duration of 2 ms.
PROBLEMS
1. A system is described by:
10 sin 3t =
d 2i
di
+ 4 sin = 4i = 0
dt
dt 2
FIGURE 2-P3
Given that:
i(0) = 1
Circuit for Prob. 8.
9. Find Laplace transform of a half-wave rectifier
di(0)
=4
dt
0 ≤ t ≤ 2π
find
f (t ) = sin t 0 ≤ t ≤ π
= 0 π ≤ t ≤ 2π
i(t ) for t > 0
10. Consider the circuit of Fig. 2-P4. Write a matrix equation
of the form:
2. In Fig. 2-10c, the initial voltage on capacitor =40 V, t =0,
initial current in inductor = 1A, t =0. Find the capacitor voltage
for t > 0.
ZI = V
and calculate the currents i1, i2 and i3.
3. Consider the circuit of Fig. 2-P1. Write the equations of the
system in state variable form.
FIGURE 2-P1
Circuit for Prob. 3.
4. Consider the circuit of Fig. 2-P2. Write a differential equation
relating e1(t) to e(t).
FIGURE 2-P2
Circuit for Prob. 4.
FIGURE 2-P4
Circuit for Prob. 10.
11. What is the value of RL for maximum power transfer from
the source in Fig. 2-P5? What is the value of the maximum
power transferred?
FIGURE 2-P5
Circuit for Probs. 11 and 14.
32
CHAPTER TWO
12. Design a parallel tuned circuit for resonance, consisting
of an inductor and capacitor in parallel, at 660 Hz, with bandwidth of 60 Hz. If the resistance of the coil is 10 Ω, what is the
impedance of the circuit at resonance?
13. A capacitor C1 of 1 µF is charged to 100 V. It is suddenly
connected to another discharged capacitor C2 of 2µF with a
series resistor of R Ω. Find the energy stored in each capacitor
when the switch is closed, energy stored after a long time, and
the energy dissipated in the resistance R.
14. In Fig. 2-P5, the switch is closed at t =0, after it has been open
for a long time. Obtain the Laplace transform of the current, t > 0.
15. Select the correct option for the arrangement of resistor,
inductor, and capacitor: (1) all are linear, (2) all are nonlinear,
(3) resistance is linear, while the capacitor and inductor can be
nonlinear because the reactance varies with the frequency, (4)
all can be linear or nonlinear.
16. Write a difference equation for the second-order differential
equation:
d2 y
dy
+ 5 = 10 y = 100
dt
dt 2
y(0) = 10
dy
= −2
dt t=0
17. Compare a space-state model of a system with a model
derived through differential equations and Laplace transform.
18. Solve the following simultaneous differential equations
relating to a transmission line:
−
dV
= Ri
dx
−
di
= GV
dx
Given the conditions that V =0, at x =l, and V =V0 at x =0
19. Write a step-by-step proof of Eqs. (2-85), (2-86), and
(2-87) in the text of this chapter.
REFERENCE
1. IEEE Std. 399, Brown Book, Power Systems Analysis, Chapter 11,
1997.
FURTHER READING
D. L. Beeman, ed., Industrial Power System Handbook, McGraw-Hill,
New York, 1955.
J. O. Bird, Electrical Circuit Theory and Technology, Butterworth,
Heinemann, Oxford, UK, 1997.
J. A. Cadzow, Discrete Time Systems, Prentice Hall, Englewood Cliffs,
NJ, 1973.
D. K. Cheng, Analysis of Linear Systems, Addison-Wesley Publishing Co.,
New York, 1959.
J. C. Das, Power System Analysis, Marcel and Dekker, New York,
2002.
J. A. Edminster, Theory and Problems of Electrical Circuits, 2d ed.,
Schaum’s Outline Series, McGraw-Hill, New York, 1983.
O. I. Elgord, Electrical Energy System Theory—An Introduction,
McGraw-Hill, New York, 1971.
S. Fisch, Transient Analysis in Electrical Engineering, Prentice Hall,
New York, 1971.
A. Greenwood, Electrical Transients in Power Systems, 2d ed., John
Wiley, New York, 1991.
W. R. LePage and S. Scely, General Network Analysis, McGraw-Hill,
New York, 1952.
W. E. Lewis and D. G. Pryce, The Application of Matrix Theory to
Electrical Engineering, E and FN Spon, London, 1965.
A. H. Peterson, Transients in Power Systems, John Wiley, New York,
1951.
M. B. Reed, Alternating Current Theory, 2d ed., Harper and Row,
New York, 1956.
L. A. Zedeh and C. A. Desoer, Linear System Theory, McGraw-Hill,
New York, 1963.
CHAPTER 3
CONTROL SYSTEMS
The control systems interface with electrical power systems and may
have a profound effect on the transient behavior of power systems.
One example is the excitation systems of synchronous generators
and their impact on transient stability. A badly tuned and applied
control system interface with a power system can result in oscillations and instability. Control engineering is based upon feedback
theory, linear system analysis, and network theory. It is not exclusive to electrical engineering and has far-reaching applications into
automation, robotics, artificial intelligence, man-machine interface
(MMI), and intelligent systems. We will form a basic understanding
of the transfer functions, damping and stability, feedback control
systems, root locus, Bode plots, block diagrams, and frequency
response methods.
We studied the overdamped, critically damped, and underdamped response of an RLC circuit in Chap. 2. Consider a secondorder, linear, constant coefficient differential equation of the form:
d2 y
dy
+ 2ξωn + ωn2 y = ωn2 u
dt
dt 2
(s + 2ξωn ) y0
p(s)
=
s2 + 2ξωn s + ωn2 q(s)
(3-1)
(3-2)
The denominator polynomial q(s) when set to zero is called the
characteristic equation, because the roots of this equation determine
the character of the time response. The roots of this equation are
also called the poles of the system.
The roots of the numerator polynomial p(s) are called the zeros
of the system. Poles and zeros are critical frequencies. At the poles
the function y(s) becomes infinite, whereas at zeros it becomes zero.
The complex frequency s-plane plot of poles and zeros graphically
portrays the character of the transient response. The poles and
zeros are the complex numbers determined by two real variables,
one representing the real part and the other representing the imaginary part. In the s plane, the abscissa is called the s axis, and the
ordinate is called the jw axis. In the z plane, the abscissa is called
the µ axis, and the ordinate is called the ju axis. From Eq. (3.2), the
characteristic equation is:
s2 + 2ξωn s + ωn2 = 0
s1, s2 = −ξωn ± jωn 1 − ξ 2
= −α ± jωd
(3-3)
(3-4)
where a = xwn is called the damping coefficient, wd is called the
damped natural frequency, and a is the inverse of the time constant of
the system, that is, a = 1/t. The weighting function of Eq. (3.1) is:
w(t ) =
1 −α t
e sin ωdt
ωd
(3-5)
The unit step response is given by:
t
y1(t ) =
∫ w(t − τ )ωn2 dτ = 1 −
0
We can write y(s) as:
y(s) =
In Eq. (3.1), x is called the damping ratio, and wn is called the
undamped natural frequency. The roots of the denominator are:
ωne −α t
sin(ωdt + φ )
ωd
(3-6)
where φ = tan −1(ωd /α ) and w = weighting function
The response in Fig. 3-1 is a parametric representation of the
unit step function, normalized with respect to ωnt. This can be
compared with Fig. 2-21.
From Chap. 2 we know that if x > 1, the roots are real, when
x < 1, the roots are complex and conjugate, and when x = 1, the
roots are repeated and real, corresponding to critical damping.
The s-plane plot of poles and zeros is shown in Fig. 3-2a. As
x varies with wn constant, the complex conjugate roots follow a circular locus (Fig. 3-2b). The transient response is increasingly oscillatory
as the roots approach the imaginary axis and x approaches zero.
3-1
TRANSFER FUNCTION
A transfer function is the Laplace transform of the ratio of variables, which can be current ratio, voltage ratio, admittance, or
impedance. Transfer functions assume that the initial conditions
are zero.
Example 3-1 Consider a simple RC network as shown in Fig. 3-3.
The transfer function is:
v (s)
Output
(1/τ )
1
= G(s) = 2 =
=
Input
v1(s) RC s + 1 s + 1/τ
(3-7)
where τ is the time constant of the network.
33
34
CHAPTER THREE
FIGURE 3-1
Normalized damping curves, second-order systems, unit step response.
A multiloop electrical circuit will result in a number of simultaneous equations in Laplace variable. It is convenient to solve
the simultaneous equations using matrix techniques. Consider a
dynamic system represented by the differential equation:
dn y
d n−2r
d n−1 y
d n−1r
+
+
+
=
+
+ + p 0r
q
q
y
p
p
n
n
n
−
−
1
−
0
1
2
dt n
dt n−2
dt n−1
dt n−1
(3-8)
If the initial conditions are all zero, that is, the system is at rest,
the transfer function is:
y(s) = G(s)R(s) =
=
p(s)
R(s)
q(s)
p n−1s n−1 + p n−2 s n−2 + + p0
R( s )
(s n + q n−1s n−1 + + q0 )
(3-9)
CONTROL SYSTEMS
35
where q(s) = 0 is the characteristic equation, Y1(s) is the partial fraction expansion of the natural response, Y2(s) is the term involving
factors of q(s), and Y3(s) is the term involving partial fraction expansion of the terms involving d(s). Taking inverse Laplace transform:
y(t ) = y1(t ) + y2 (t ) + y3 (t )
(3-12)
y1(t) + y2(t) is the transient response and y3(t) is the steady-state
response.
Not all transfer functions are rational algebraic expressions. The
transfer function of a system having time delays contains terms of
the form e–st (Chap. 2).
3-2
GENERAL FEEDBACK THEORY
Linear control systems are represented in block diagram forms, and
Fig. 3-4 shows such a block representation. C is the controlled variable, R is the reference (input variable), E is the error. The forward
transfer function, expressed as GcGp, consists of a controlled plant
and a compensator to improve stability or reduce the steady-state
error. It is also called the direct transfer function. H is the feedback
transfer function, and the primary feedback signal B is a function
of the output. GcGp H is called the loop transfer function. This is
equivalent to open-loop transfer function. The negative feedback
means that summing point is a subtractor. The closed-loop transfer
function can be written as:
GcGp
C
=
R 1 ± H(GcGp )
(3-13)
The ratio E/R is called the actuating signal ratio or the error
ratio, and B/R is the primary feedback ratio. Ratio C/R is also called
control ratio.
FIGURE 3-2
Second-order system, location of poles in the s-plane.
The output response consists of a natural response and a forced
response, determined by the initial conditions and the input. If the
input has the rational form:
R(s) =
n(s)
d(s)
(3-14)
GcGp H
B
=
R 1 ± GcGp H
(3-10)
We can write:
y(s) =
1
E
=
R 1 ± GcGp H
m(s) p(s) n(s)
+
q(s) q(s) d(s)
= Y1(s) + Y2 (s) + Y3 (s)
(3-11)
The negative feedback means that the summing junction is a subtractor, that is, E = R – B. Conversely for the positive feedback, it is
an adder, that is, E = R + B.
The term controller in a feedback system is associated with the
elements of the forward path, between error signal E and the control variable U. Sometimes it may include the summing point, the
feedback elements, or both. The terms controller and compensator
are sometimes used synonymously.
A proportional controller (P) gives an output U proportional to
its input, that is, U = KpE; a derivative controller (D) provides an
output E that is derivative of its input; an integrator (I) provides an
output which is integral of its input E. Thus, a PID has an output
of the form:
U PID = K p E + K D
dE
+ K I ∫ E(t )dt
dt
(3-15)
The transfer function of a PID controller is:
PPID (s) = K P + K D s +
FIGURE 3-3
Example 3-1, transfer function of a RC circuit.
=
KI
s
K D s2 + K P s + K I
s
(3-16)
36
CHAPTER THREE
FIGURE 3-4
3-2-1
To illustrate elements of a closed-loop control system.
Compensators
Compensation networks are introduced to improve the performance of a control system. These can be introduced in the forward
path or the feedback path and the compensation can be passive
or active.
The three compensators using passive RC networks are illustrated in Fig. 3-5a, b, and c.
Lead Compensator (Fig. 3-5a)
PLead (s) =
s+a
s+b
1
Zero = −a = −
R1C
1
1
Pole = −b = −
+
R
C
R
C
1
2
(3-17)
b>a
Lag Compensator (Fig. 3-5b)
PLag (s) =
a(s + b)
b(s + a )
1
Zero = −b = −
R 2C
1
Pole = −a = −
(R1 + R 2 )C
(3-18)
b>a
Lag-Lead Compensator (Fig. 3-5c)
The transfer function is:
PLL (s) =
(s + a1 )(s + b2 )
(s + b1 )(s + a 2 )
(3-19)
FIGURE 3-5
(a) Passive lead compensator. (b) Lag compensator.
(c) Lead-lag compensator.
CONTROL SYSTEMS
Equation (3.19) can be derived using techniques discussed in
Chap. 2. In Fig. 3-5c, the current i in the loop is:
1
C2
t
Comparing this with Eq. (3-2), the natural frequency should be 4.
Thus:
∫ idt + iR2
0
Taking Laplace transform with zero initial conditions and
eliminating i(s),
1
V0 (s)
+ C1s [Vi (s) − V0 (s)] =
(1/sC2 ) + R 2
R1
ξ = 0 . 4 / 2ωn = 0 . 05
We need to change it to 0.7. Modify the control system by adding a
compensator, as shown in Fig. 3-6b. The transfer function is:
(0 . 4 K ) (s + ω1 )
s(s + 0 . 4 ) (s + ω2 )
0 . 4 K(s + ω1 )
=
s(s + 0 . 4 ) (s + ω2 ) + 0 . 4 K(s + ω1 )
(0 . 4 K ) (s + ω1 )
1+
s(s + 0 . 4 ) (s + ω2 )
(s + a1 )(s + b2 )
(s + b1 )(s + a 2 )
Simplifying, it can be shown that:
b1a 2 = a1b2
K = 40
2ξωn = 0 . 4 s
1
1
s +
s +
V0 (s)
R1C1 R 2C2
=
PLL =
Vi (s)
1
1
1
1
s2 +
+
+
s+
R 2C2 R 2C1 R1C1 R1C1R 2C2
1
a1 =
R1C1
ωn = 4 = 0. 4K
The damping ratio is:
The transfer function is:
=
damping ratio ξ of 0.707 and an undamped natural frequency of 4.
The transfer function is:
0 . 4 K /[s(s + 0 . 4 )]
0. 4K
=
1 + 0 . 4 K /[s(s + 0 . 4 )] s2 + 0 . 4 s + 0 . 4 K
Vi − Vo
d
+ C1 (Vi − Vo ) = i
dt
R1
V0 =
37
We can cancel out (s + ω1 ) and (s + 0 . 4 ) by making ω1 = 0 . 4 . Then
the transfer function reduces to:
1
b2 =
R 2C2
b1 + a 2 = a1 + b2 +
(3-20)
1
R 2C1
To get the required damping ratio:
Example 3-2 Consider a control system given by the block diagram in Fig. 3-6a. It is desired to modify the system so that it has a
FIGURE 3-6
0. 4K
0. 4K
=
s(s + ω2 ) + 0 . 4 K s2 + ω2 s + 0 . 4 K
ξ = 0.7 =
ω2
2ωn
ω2 = 5 . 6 rad/ sec
Example 3-2, altering the response of a control system by adding a compensator.
38
CHAPTER THREE
The control system is now drawn as shown in Fig. 3-6c. The
gain of the compensated system is given by:
G(s) =
s + 0.4
1
16
× 16 ×
=
= 2 . 86
s + 5.6
s(s + 0 . 4 ) s(s + 5 . 6)
3-3 CONTINUOUS SYSTEM FREQUENCY
RESPONSE
The steady-state response of a stable system to an input u = A sin w t
is given by:
yss = A P( jω ) sin(ω t + φ )
(3-21)
where φ is arg P( jw). The complex number P( jw) is obtained by
replacing s with jw in P(s). The magnitude and the angle for all w’s
define the system frequency response. It is generally represented
by two graphs: one for the magnitude of P( jw), called the gain of
the system, and the other for the arg P( jw). It can be determined
graphically in the s plane from a pole-zero map of P(s).
For a step-function input of magnitude A, often called dc input,
the Laplace transform of the output is:
Y (s) = P(s)
A
s
(3-22)
If system is stable then the steady-state response is a step function
of AP(0), that is, the amplitude of the input signal is multiplied by
P(0) to determine amplitude of output. P(0) is, therefore, called the
dc gain of the system.
Example 3-3 Consider a system with transfer function:
P(s) =
1
(s + 1)(s + 3)
We will compute the magnitude and angles for jw = 1. Then from
Fig. 3-7a:
P( j1) =
1
10 2
= 0 . 223
arg P( j1) = − 18 . 4 ° − 45 ° = 63 . 43 °
The values of |P( jω )| and arg |P(jw)| at various values of jw can
be calculated and a graph plotted, as shown in Fig. 3-7b and c.
3-4 TRANSFER FUNCTION OF A DISCRETE-TIME
SYSTEM
If all terms due to initial condition are zero, then for an input U(z):
P(z ) =
Y (z ) K(z + z1 )(z + z 2 ) + + (z + z m )
=
U (z ) (z + p1 )(z + p2 ) + + (z + p n )
(3-23)
that is, P(z) is specified by system poles and zeros and a gain
factor K.
The system poles and zeros can be represented in a pole-zero
map in the z plane. The pole-zero map of the output y(z) can be
constructed from pole-zero map of P(z) by including poles and
zeros of the input U(z).
FIGURE 3-7
Example 3-3, computation of the magnitude and angle
of a transfer function.
The order of the denominator polynomial of a transfer function
of a casual discrete-time system must be greater than or equal to the
order of the numerator polynomial. The steady-state response to a
unit-step input is called the dc gain and is given by the final value
theorem (Chap. 2).
Example 3-4 The transfer functions of a discrete-time system
described by the equation:
y (k + 2) + 1 . 1 y(k + 1) + 0 . 3 y(k ) = u(k + 2) + 0 . 2u(k + 1)
can be found by taking z-transform:
(z 2 + 1 . 1z + 0 . 3)Y (z ) = (z 2 + 0 . 2z )U (z )
CONTROL SYSTEMS
Therefore:
P(z ) =
can be determined by constructing a Routh table as follows:
z( z + 0 . 2 )
z( z + 0 . 2 )
=
z 2 + 1 . 1z + 0 . 3 (z + 0 . 5)(z + 0 . 6)
sn
The system has zeros at –0.2 and two poles at –0.5 and –0.6. The
system is stable as the poles are within the unit circle and the dc
gain is:
P(1) =
3-4-1
1.2
= 0. 5
1.5 × 1.6
Discrete-Time System Frequency Response
The frequency response of a stable discrete system to an input
sequence u( k) = A sin w kT, where k = 0, 1, 2,…, which has a transfer function P(z) given by:
yss = A Pe jω t sin(ω kT + φ )
k = 0, 1, 2, ...
(3-24)
The complex function P(e jωT ) is determined from P(z ) by
replacing z with e jωT . The system response is a sequence of samples
of the sinusoidal with the same frequency as the input sinusoidal.
The output sequence is obtained by multiplying A of input with
Pe jωT , and shifting the phase angle of the input by arg Pe jωT . The
magnitude Pe jωT , gain, and arg Pe jωT for all w’ s define discretesystem frequency function.
The discrete-time system frequency response function can be
determined in the z plane from a pole-zero map of P(z) in the same
manner as calculation of residues (App. C).
3-5
STABILITY
We may characterize a continuous or discrete system as stable, if
every bounded input produced a bounded output. A necessary and
sufficient condition for the system to be stable is that real parts
of the roots of the characteristic equation have negative real parts.
The impulse response will then decay exponentially with time. If the
roots have real parts equal to zero, the system is marginally stable,
the impulse response does not decay to zero, and some other inputs
may produce unbounded outputs. Thus, marginally stable systems are
unstable. For example, a system with roots, –4, –2, and 0 is marginally stable. The system with roots –1 + j and –1 – j is stable as the real
part is negative. A system which has poles at –1, –4, and zeros at –2
and 1 is stable, though the system has a zero with positive real part.
3-5-1
39
Routh Stability Criteria
The stability of a system with nth-order characteristic equation of
the form:
a n s n + a n−1s n−1 + + a1s + a 0 = 0
FIGURE 3-8
(3-25)
an
a n−2
a n− 4
...
s n−1
a n−1
a n −3
a n−5
...
s n−2
b1
b2
b3
. ..
.
c1
c2
c3
...
.
.
.
.
.
(3-26)
where:
b1 =
a n−1a n−2 − a na n−3
a n−1
b2 =
a n−1a n−4 − a na n−5
a n−1
...
(3-27)
b a −a b
c1 = 1 n−3 n−1 2
b1
c2 =
b1a n−5 − a n−1b2
b1
...
The table is continued horizontally and vertically till only zeros are
obtained. All the roots of the characteristic equation have negative
real parts if and only if the elements of the first column of the table
have the same sign. If not, then the number of roots with the positive real parts is equal to the number of changes of sign.
Example 3-5 Consider a system as shown in the block diagram
of Fig. 3-8 and find the value of K for stability:
GH =
K
s(s + 3)(s2 + 7 s + 12)
The characteristic equation is:
s 4 + 10s 3 + 33s2 + 36s + K = 0
The Routh table is:
s4
s3
s2
s1
s0
1
33 K
10
36 0
K 0
29 . 4
36 − 0 . 34 K 0 0
K
Example 3-5, block circuit diagram of a control system, value of K for stability.
40
CHAPTER THREE
Therefore:
is a stable or unstable system. Calculate the determinants as follows:
K >0
36 − 0 . 34 K > 0
D3 =
a n−1 a n−3 a n−5
6
a n a n−2 a n−4 = 1
0
0 a n−1 a n−3
D2 =
a n−1 a n−3
6
=
a n a n−2
1
K = 105 . 9
For stability:
0 < K < 105 . 9
If rows are zero for s row of the table, they form an auxiliary
equation:
As2 + B = 0
20
10
where A and B are the first and second elements of the row s .
Replace the zeros of row s1 with the differential of the auxiliary
equation, that is, 2A and zero in this case.
Hurwitz Stability Criteria
The criteria are applied using the determinants formed from the
coefficients of the characteristic equation in the matrix:
a (n odd )
0 .
0
a (n even )
1
a (n odd )
1
0 .
a (n even )
0
a n−1
a n −3
.
an
a n −2
.
0
a n−1
a n −3
.
.
.
0
0
an
a n−2
.
.
.
0
.
.
.
.
.
.
.
0
.
.
.
.
. a0
0
(3-29)
D1 = a n−1
D3 =
a n−1 a n−3 a n−5
a n a n−2 a n−−4
0 a n−1 a n−3
(3-30)
All the roots have negative real parts if and only if
i = 1, 2, . . . , n
(3-31)
Note that the coefficient an is positive.
Example 3-6 Apply Hurwitz criteria to ascertain whether the
system represented by:
s 3 + 6s2 + 10s + 20 = 0
Routh criteria can also be applied to discrete systems. The stability
is determined from the characteristic equation:
Q(z ) = a n z n + a n−1z n−1 + ... + a1z + a 0 = 0
(3-32)
The stability region is defined by a unit circle |z| = 1 in the z
plane. The necessary and sufficient condition of the stability is that
all the roots of the characteristic equation have a magnitude less
than 1, that is, these are within the unit circle. The stability criteria
similar to discrete systems are called the jury tests. The coefficients
are first arranged in a jury array:
1
2
3
4
5
6
.
2n − 5
2n − 4
2n − 3
.
.
.
.
.
.
.
r3
r0
a0
a1
a2
an
a n−1 a n−2
b0
b1
b2
bn−1 bn−2 bn−3
c0
c1
c2
cn−2 cn−3 cn−4
.
.
.
r0
r1
r2
r3
r2
r1
s0
s1
s3
a n−1 a n
a1
a0
bn−1
b0
cn−2
c0
.
(3-33)
where:
The determinants are formed as follows:
a n−1 a n−3
a n a n−2
Stability of Discrete-Time Systems
0
Dn =
D2 =
As all the determinants are positive, the system is stable.
3-5-3
(3-28)
2
Di > 0
0
0
20
D1 = a n−1 = 6
1
3-5-2
20
10
6
bk =
a0
an
a n−k
ak
ck =
b0 bn−1−k
bn−1
bk
s0 =
r0
r3
r3
r0
(3-34)
s1 =
r0
r3
r2
r1
s3 =
r0 r1
r3 r2
The first two rows are constructed using coefficients of the characteristic equation; next two rows are computed using determinant
relations shown above. This is continued with each succeeding pair
of rows having one less column than the previous pair, until row
2n – 3 is computed, which has only three entries. The array is then
terminated.
The necessary and sufficient conditions of stability are:
Q(1) > 0
Q(− 1) > 0
(n even)
Q(− 1) < 0
(n odd)
CONTROL SYSTEMS
Multiplication Rule (Fig. 3-10c)
a0 < a n
X n = A21 ⋅ A 32 ...A n( n−1) X1
b0 > bn−1
c0 > cn−2
r0 > r3
The array may not be constructed if some of the initial conditions of stability, that is Q(1), Q(–1), a0, and an are not met, and then
the system will be unstable.
Example 3-7 A continuous system is given by:
Q(z ) = 3z 4 + 2z 3 + z 2 + 2z + 1 = 0
Q(− 1) = 3 − 2 + 1 − 2 + 1 = 1 > 0
(3-39)
X m = A m1 X1 + A m2 X 2 + + A mn X n
Thus, the jury array can be constructed:
1 2
1 2 3
3
2
1 2 1
−8 −4 −2 −4
−4 −2 −4 −8
80 24
0
■
An equation in X1 is not required if X1 is an input node.
■
Arrange larger nodes from left to right.
■
Connect the nodes by appropriate branches A11, A12 . . .
■
If desired output node has outgoing branches, add a dummy
node and unity gain branch.
Examine the remaining conditions:
a0 = 1 < 3 = a n
Example 3-9 Consider the circuit shown in Fig. 3-11a. The following equations can be written:
b0 = − 8 > − 4 = bn−1
c0 = 80 > 0 = cn−2
i1 =
Thus, the system is stable.
1
1
v − v
R1 1 R1 2
v2 = R 3i1 − R 3i2
BLOCK DIAGRAMS
A block diagram is a convenient way of representing a physical
system. We used block diagrams in the examples above to calculate transfer functions and simple combinations of forward blocks.
Block diagram transformations are shown in Fig. 3-9a. A given control system can be simplified by using these transformations.
Example 3-8 Consider the block diagram of control system in
Fig. 3-9b. This can be simplified using the transformations shown
in Fig. 3-9a, and the simplified control system is progressively
shown in Fig. 3-9c and 3-9d.
SIGNAL-FLOW GRAPHS
Though block diagrams are used extensively for the representation
of control systems, signal-flow graphs are yet another representation. A signal-flow graph is a pictorial representation of the simultaneous equations describing a system. As a simple example Fig. 3-10a
is a representation of Ohm’s law, E = R1. Note the designations of
nodes and branches.
Addition Rule (Fig. 3-10b)
i2 =
(3-36)
1
1
v −
v
R2 2 R2 3
v 3 = R 4 i2
The signal-flow graph is shown in Fig. 3-11b.
3-7-1
Mason’s Signal-Flow Gain Formula
The relationship between an input variable and output variable of
a signal-flow graph is given by the net gain between input and output nodes and is called the overall gain of the system. Mason’s gain
formula is:1
Tij =
where:
n
j=1
A loop is a closed path that originates and terminates on the
same node, and along the path no node is met twice. Two loops are
said to be nontouching if they do not have a common node. Two
touching loops share one or more common nodes.
To construct a signal-flow graph write the equations in the
form:
X 2 = A21 X1 + A22 X 2 + + A2 n X n
Q(1) = 3 + 2 + 1 + 2 + 1 = 9 > 0
X i = ∑ Aij X j
(3-38)
X1 = A11 X1 + A12 X 2 + + A1n X n
Ascertain whether the system is stable:
3-7
X i = Aik X k
i = 1, 2, . . . n, k
s0 > s2
3-6
(3-37)
Transmission Rule (Fig. 3-10d)
(3-35)
1
2
3
4
5
41
∑ k Pijk Dijk
D
Pijk = k th path from variable xi to variable xj
D = determinant of the path
Dijk = cofactor of the path Pijk
(3-40)
F I G U R E 3 - 9 (a) Transformation of control circuit diagrams. (b) Original block diagram of a control system. (c) and (d ) Progressive simplification of the
control system block diagram. (Continued )
42
CONTROL SYSTEMS
FIGURE 3-9
The summation is taken for all possible paths from xi to xj. The
cofactor Dijk is the determinant with the loops touching the removed
kth path. The determinant D is
N
M, Q
n=1
m=1,q=1
D = 1 − ∑ Ln +
∑
L m L q − ∑ L r L s Lt +
(3-41)
(Continued)
Path 1 : P1 = G1G2G3G4
Path 2 : P2 = G5G6G7
Loop 1 : L1 = G2 H 2
Lo o p 2 : L2 = G3H 3
where Lq equals the qth loop transmittance. Therefore, the rule of
evaluating D is:
D = 1– (Sum of all different loop gains)
Loop 3 : L 3 = G6 H 4
Loops L1 and L2 do not touch L3. Therefore the determinant is:
+ Sum of gain products of all combinations
of two nontouching loops)
D = 1 − ( L1 + L2 + L 3 ) + ( L1L 3 + L2 L 3 )
– (Sum of gains products of all combinations of
three nontouching loops)
Cofactor of the determinant along path 1 is evaluated by removing
the loops that touch path 1 from D. Therefore:
+...
(3-42)
L1 = L2 = 0
D1 = 1 − L 3
The cofactor for path 2 is:
Example 3-10 Consider the signal-flow graph shown in Fig. 3-12.
The paths connecting input to output are:
43
D2 = 1 − L1 − L2
44
CHAPTER THREE
FIGURE 3-11
Example 3-9, (a) Original circuit diagram. (b) Signal-
flow graph.
There are three loops:
L1 = G1G4 H1
L2 = − G1G2G4 H 2
L 3 = − G1G3G4 H 2
FIGURE 3-10
(a) Signal-flow graph of ohms law. (b) Rule of addition. (c) Rule of multiplication. (d ) Rule of transmission.
There are no nontouching loops. Thus:
D = 1 − ( L1 + L2 + L 3 )
Then:
D1 = D2 = 1
PD +P D
Y (s)
= T (s) = 1 1 2 2
D
R(s)
=
Thus:
G1G2G3G4 (1 − L 3 ) + G5G6G7 (1 − L1 − L2 )
1 − L1 − L2 − L 3 + L1L 3 + L2 L 3
Example 3-11
T (s) =
Draw the signal graph of the control system
shown in Fig. 3-13a and find overall gain. Using the procedure
outlined above, the signal-flow graph is constructed and is shown
in Fig. 3-13b. There are two forward paths:
Path 1 : P1 = G1G2G4
Path 2 : P2 = G1G3G4
FIGURE 3-12
3-8
P1 + P2
D
BLOCK DIAGRAMS OF STATE MODELS
In Chap. 2 we observed that in the state model the dynamics of the
system can be represented by first-order differential equations or by
the state differential equations. It is useful to develop a state flow
graph model and use this model to relate state variable concept
with the transfer function representation.
Example 3-10, signal-flow graph.
CONTROL SYSTEMS
FIGURE 3-13
Example 3-11, (a) Block circuit diagram of a control system. (b) Signal-flow graph of the control system in (a).
The state diagram using two integrators is shown in Fig. 3-16.
This can be generalized for n integrators.
From Example 2-16, we had following equations:
x 1 = −
1
1
x + u(t )
C 2 C
1
R
x 2 = x1 − x 2
L
L
(3-43)
v0 = Rx 2
The flow graph is shown in Fig. 13-14. Consider a first-order differential equation:
x (t ) = ax(t ) + br(t )
x(0) = x 0
(3-44)
The state diagram for this differential equation is shown in Fig. 3-15.
Start with the signals x(t) and r(t) and form the right-hand side to give
x (t ). The initial condition x(0) = x0 is added to the integrator.
Now consider a system with single input r(t) and output y(t)
given by two state variables:
x 1 = a11 x1 + a12 x 2 + b1r
x1(0) = x10
x 2 = a 21 x1 + a 22 x 2 + b2r
x 2 (0) = x 20
3-9 STATE DIAGRAMS OF DIFFERENTIAL
EQUATIONS
The state diagram for a differential equation is not unique and a
number of state models are possible for a given differential equation.
Consider a differential equation:
dn y
d n−1 y
dy
+ a n−1 n−1 + + a1 + a 0 y(t ) = r(t )
n
dt
dt
dt
y(0), y (0), … ,
d n−1 y(0)
dt n−1
(3-45)
(3-46)
initial conditions
To arrive at a state model define:
x1 = y
x 2 = y
(3-47)
y = c1 x1 + c2 x 2 + dr
xn =
d n−1 y
dt n−1
Then the given equation of nth order is reduced to n first-order
differential equations:
x 1 = x 2
x 2 = x 3
x n−1 = x n
FIGURE 3-14
45
Example 2-16, flow graph of the state space model.
x n = −a 0 x1 − a1 x 2 − − a n−1 x n + r
(3-48)
46
CHAPTER THREE
FIGURE 3-15
State diagram for first-order differential equation, one integrator.
FIGURE 3-16
State diagram with two state variables and two integrators.
These form the state model:
0
x 1
x 2
0
. = .
x n−1
0
x n
−a 0
1
0
0
1
.
.
0
0
−a1 −a 2
y= 1 0 0 . 0
x1
x2
.
x n−1
xn
.
0
.
0
.
.
.
1
. −aa n−1
0
x1
0
x2
. + .
x n−1
0
xn
1
The state diagram of the nth-order differential equation is shown
in Fig. 3-17. Now consider a transfer function defined by:
C b2 s2 + b1s + b0
=
R s 3 + a 2 s + a1s
r
(3-49)
(3-50)
We can write
r(t ) =
x1 + a 2
x1 + a1 x 1
y(t ) = c(t ) = b2
x1 + b1 x 1 + b0 x1
or in the matrix form:
(3-51)
CONTROL SYSTEMS
FIGURE 3-17
x 1
0
x 2 = 0
x 3
0
y(t ) = b0
1
0
0
1
−a1 −a 2
b1 b2
x1
0
x2 + 0
x3
1
State diagram for n-th order differential equation.
Using Laplace final value theorem:
r(t )
x1
x2
x3
e ss (t ) = lim s→0
(3-52)
Figure 13-18 shows the development of the block diagram.
Example 3-12 Consider the state variable block diagram given
in Fig. 13-19. What is the transfer function?
By reversing the process, we can find the required transfer function, which is:
Y (s)
3s + 1
=
R(s) (s 3 + s2 + 3s + 7 )
3-10
(3-53)
Three types of inputs for which the errors are well defined are:
■
Step input: position error
■
Ramp or velocity input: error in velocity
■
Parabolic input: error in acceleration
Therefore:
lim s→0GH(s) = lim s→0
K
sn
(3-56)
Rs n
s +K
(3-57)
n
It is R/(1 + K) for type-zero system and 0 for type-one and type-two
systems.
3-10-2
Velocity Error
The velocity is the term used for a ramp input, r(t) = R′(t). The
Laplace transform is R′/s2. R′ is the slope of the ramp.
R′
s [1 + GH(s)]
2
e ss (t ) = lim s→0 s
= lim s→0
R′
= lim s→0
s2[1 + GH(s)]
R′
s
K
1+ n
s
(3-58)
R ′s n−1
R′s n−1
= lim s→0
n
K
s +K
For a type-zero system, the error is infinite; for type-one system, it
is R′/K; and for type-two system, it is zero.
Position Error
Laplace transform of unit step is 1/s, so the error for unit step is:
E(s) =
s
s
s
K 1 + 1 + 1 +
z
z
z
k
1
2
GH(s) =
s
s
s
s n 1 + 1 + 1 +
p1 p2 p m
E(s) =
The response is determined by the number of integrators in
denominator term of GH of the form sn, where n is the number of
integrators. A type-one system has one integrator, a type-two system has two integrators, and a type-zero system has no integrators
in the open-loop transfer function.
3-10-1
(3-55)
The term GH(s) can be expressed as:
e ss (t ) = lim s→0
If open-loop transfer function and input r are expressed as a function of s, then error as a function of s is:
1
1 + GH(s)
R
1 + GH(s)
The steady-state error is:
STEADY-STATE ERRORS
E(s) = R(s)
47
R
1
s 1 + GH(s)
(3-54)
3-10-3
Acceleration Error
It can be similarly proved that for type-zero and type-one systems
the steady-state error will be infinite and for type-two system it will
be finite, 2R″/K.
48
CHAPTER THREE
FIGURE 3-18
FIGURE 3-19
Development of the block diagram of a second-order differential equation.
Example 3-12, calculation of transfer function from the block circuit diagram.
CONTROL SYSTEMS
We can summarize that the system with zero integrator in the
open loop has a finite position error and infinite velocity and acceleration errors. An infinite steady-state error indicates that the system
cannot track the particular type of function which causes the error.
Given enough time, a system with one integrator in the open
loop will track position perfectly and will follow a ramp function
with finite error but cannot track an acceleration input at all.
A system with two integrators in the open-loop function can
track both position and velocity with no long-run errors, but will
have constant error with respect to acceleration input. Systems with
more than two integrators in the open loop will have closed-loop
performance able to track all derivates equal to one less than the
number of integrators. However, systems with even two integrators
have difficulty in damping transients. Systems with more than two
integrators are very difficult to stabilize.
that is, it is 180° plus the phase angle of open-loop transfer function at
unity gain. ω1 is called the gain crossover frequency. Figure 3-20 shows
phase and gain margins of typical continuous-time control system.
Delay Time Delay time, as a frequency-domain specification, is
interpreted as a measure of the speed of response:
Td (ω ) = −
dγ
dω
The frequency-domain specifications form a design criteria and are
stated in the following parameters:
Gain margin Gain margin is a measure of relative stability and
defined as reciprocal of open-loop transfer function at a frequency
at which phase angle is –180°.
Bandwidth, Cutoff Frequencies
It is generally defined as
range of frequencies over which the values do not differ by more
than –3 dB, (Fig. 3-21). Decibel, abbreviated as dB, is defined as:
(3-59)
where arg GH(ωπ ) = –180°, and ωπ is called the phase crossover
frequency
Phase Margin Phase margin is given by:
φPM = [180 ° + arg GH(ω1 )]
(3-60)
where GH(ω1 ) = 1.
FIGURE 3-20
(3-62)
The magnitude ratio is 0.707, approximately –3dB at the cutoff frequencies shown in Fig. 3-21
Resonant Peak and Resonant Frequency The resonant
peak is maximum value of the magnitude of closed-loop frequency
response:
M p ≡ max
1
Gain margin ≡
GH(ωπ )
(3-61)
where γ = arg(C /R ).
Average value of Td (ω ) over frequencies of interest is specified.
dB = 20 log10 (any magnitude ratio)
3-11 FREQUENCY-DOMAIN RESPONSE
SPECIFICATIONS
49
C
R
(3-63)
and the frequency at which it occurs is called the resonant frequency.
It is a measure of the stability. The resonant peak Mp and the resonant frequency wp for an underdamped second-order system are
illustrated in Fig. 3-22.
3-12
TIME-DOMAIN RESPONSE SPECIFICATIONS
Similar specifications for the time-domain response can be written from the response characteristics shown in Fig. 3-23. Transient
response is described in terms of unit-step function response.
Phase and gain margins for stability—continuous control system.
50
CHAPTER THREE
FIGURE 3-21
FIGURE 3-22
Cut-off frequencies, continuous control system.
The resonant peak and bandwidth of a continuous control system.
Overshoot The maximum difference between the transient and
steady-state solution for a unit-step input.
Time Delay Td The time required for the response to a unit-step
function to reach 50 percent of its initial value.
Rise Time Tr The time required for the unit-step input to rise
from 10 to 90 percent of the final value.
Settling Time Ts The time required to reach and remain within
a specified value, generally 2 to 5 percent of its final value.
Time Constant T The time when the exponential reaches
63 percent of its initial value as shown in the exponential envelope
of Fig. 3-23. For continuous feedback control systems of the order
higher than two, the exponential is given by:
τ≤
1
ξωn
(3-64)
examined as the system parameters vary. This graphical method can
be used to evaluate the initial design and subsequent modifications.
A computer simulation is generally used.
In order to evaluate the relative stability and transient performance of a closed-loop system, the roots of the denominator of
the closed-loop transfer function are determined. The open-loop
transfer function GH can be represented by:
GH ≡
KN
D
(3-65)
where N and D are polynomials in complex variables s or z, and K is the
open-loop gain. The closed-loop transfer function can be written as:
C
G
GD
=
=
R 1 + GH D + KN
(3-66)
The closed-loop poles are the roots of the characteristic equation:
3-13
ROOT-LOCUS ANALYSIS
The root locus is helpful in determining the relative stability and
transient response of a closed-loop system, as these are directly
related to the location of the closed-loop roots of the characteristic
equation. The movement of these roots in the complex plane can be
D + KN = 0
(3-67)
Thus, the location of the roots in s or z plane changes as the open
loop-gain factor K changes. A locus of these roots plotted in s or
z plane as a function of K is called a root locus.
CONTROL SYSTEMS
FIGURE 3-23
Time-domain transient response, step input function.
Consider K = 0. Then the roots of Eq. (3-67) are roots of the
polynomial D, which are the same as the poles of the open-loop
transfer function GH. Consider K very large; the roots approach
those of polynomial N, that is, the open-loop zeros. Thus as K is
increased from zero to infinity, the close-loop poles originate from
open-loop poles and terminate at open-loop zeros. The closed-loop
transfer function C/R is determined from the root-locus plot, for a
specified value of K. For a unity feedback (H = 1), we can write:
G=
KN K(s + z1 )(s + z 2 )(s + z m )
=
(s + p1 )(s + p2 )(s + p n )
D
(3-68)
Example 3-13 A system with one integrator and variable gain has
an open-loop transfer function GH = K/s. It is required to place the
closed-loop pole at s = –4. There are no poles or zeros to the right of
the origin in s plane. Thus, the positive axis is not part of the root locus,
and the entire negative axis is the root locus. GH = 0, at s = infinity. To
find the value of K for closed-loop pole at s = –4, we write GH = –1,
and insert desired value of s to solve for K, which gives K = 4.
3-13-1
Angle and Magnitude
For root locus to pass through a point p1 in complex plane, it should
be a root of the characteristic equation (3-67) for some real value of K.
Therefore:
C
KN
KN
=
=
R D + KN (s + α1 )(s + α2 )(s + α n )
51
D( p1 ) + KN( p1 ) = 0
(3-69)
Thus, C/R and G have the same zeros, but not the same poles,
except when K = 0.
or
GH =
KN( p1 )
= −1
D( p1 )
52
CHAPTER THREE
Complex number GH(p1) must have phase angles of 180 ° + 360n°,
therefore:
arg GH( p1 ) = 180 ° + 360n°
3-13-5
Departure and Arrival Angles
The departure and arrival angles, θ D ,θ A, of the root locus from complex poles are given by:
θ D = 180 ° + arg GH′
= (2n + 1)π radians
(3-75)
θ A = 180 ° − arg GH′′
or
(3-70)
N( p )
1
arg
= (2n + 1)π
D( p1 )
= 2 nπ
K >0
K <0
where GH′ is the phase angle of GH computed at complex pole,
ignoring the contribution of that particular pole, and GH″ is the
phase angle of GH at complex zero, ignoring the effect of that zero.
3-13-6
where
Procedure for Constructing Root Locus
The procedure for constructing root locus can be summarized as
follows:
n = 0, ± 1, ± 2,...
■
Write characteristic equation
■
Factor polynomial if required in the form of poles and zeros
■
Locate poles and zeros on s plane
■
Locate segments on real axis that are root loci
3-13-2 The Number of Loci
■
Determine number of separate loci
The number of loci, that is, the branches of the root locus are equal
to the number of poles of the open-loop transfer function GH.
■
Root locus must be symmetrical with respect to real axis
■
Calculate asymptotes and departure angles
■
Calculate breakaway points
Also the magnitude criteria should be satisfied. Thus K must have
the particular value that satisfies:
K =
D( p1 )
N( p1 )
(3-71)
For K > 0. Points of the root locus on the real axis lie to the left
of the odd number of finite poles and zeros.
For K < 0. Points of the root locus on the real axis lie to the left
of an even number of finite poles and zeros.
If no points on the real axis lie to the left of an odd number of
finite poles and zeros, then no portion of the root locus for K > 0
lies on the real axis. A similar statement is true for K < 0
3-13-3
Asymptotes
The asymptotes originate from a point on the real axis called the
center of asymptotes, which is given by:
i=n
i=m
σ c = − i=1
i=1
∑ pi − ∑ z i
(3-72)
n−m
(2l + 1)180
n−m
deg rees
(2l)180
n−m
deg rees
n
i=1
Determine the angle of locus departure from complex poles
and angle of arrival at complex zeros, using phase criteria:
< P(s) = 180 ° ± q360 ° at s = p j
■
or z i
Determine the root locations that satisfy the criteria:
< P(s) = 180 ° ± q360 ° at root s x
■
(3-76)
(3-77)
Determine the parameter Kx at root location sx:
K <0
(3-73)
Kx =
j=1
nz
∏ s + zi
(3-78)
We will illustrate the root-locus analysis and procedure through
some solved examples.
Example 3-14 Consider an open-loop transfer function:
GH =
Breakaway Points
m
1
1
=∑
+ zi )
σ
(
+
p
)
b
b
i
i=1
∏ s+ pj
i=1
A breakaway point is defined where two or more branches of the
root locus arrive or depart at the real axis. The location is given by:
∑ (σ
■
K >0
where l is an arbitrary integer.
3-13-4
Determine the points at which the locus crosses the imaginary axis
np
where n is the number of poles and m is the number of zeros, and
–pi are the poles and –zi are the zeros of GH.
The angles between the asymptotes and the real axis are given by:
β=
■
(3-74)
where pi and zi are the poles and zeros of GH, and sb is the breakaway point.
K(s + 1)
s2 (s + 4 )
Find the center of the asymptotes and their angles. At the real axis, there
are three poles and one zero; therefore n – m = 2. From Eq. (3-72):
σc = −
4 −1
= −1.5
2
There are two asymptotes. Their angles with the real axis are given
by Eq. (3-73). These are 90° and 270°, respectively.
CONTROL SYSTEMS
FIGURE 3-24
Example 3-16, root-locus diagram.
Find K for damping ratio ξ = 0 . 707 . Also find closed-loop response
to a unit-step function. Here, we have two adjacent poles and a
zero. Thus, the root locus is a circle, and the radius is given by:
Example 3-15 Determine the breakaway points of:
GH =
K
s(s + 1)(s + 3)
From Eq. (3-74), the following equations must be solved:
r = (z − p1 )(z − p2 ) = − 9 × − 6 = 7 . 35
ξ = 0 . 707
1
1
1
+
+
=0
σ b σ b +1 σ b + 3
cos −1 ξ = 45 °
From Fig. 3-25, the closed loop-poles can be calculated graphically.
Alternatively, the equation of the circle for ξ = 0 . 707 and ω = −σ
(σ b + 1)(σ b + 3) + σ b (σ b + 3) + σ b (σ b + 1) = 0
3σ b2 + 8σ b + 3 = 0
(σ + 9)2 + ω 2 = 54
The roots are –0.45 and –2.22. Thus for K > 0, there are
branches between 0 and –1, and the breakaway point is at –0.45.
For K < 0, the breakaway point is –2.22, since the portion of the
real axis between –1 and –3 is on the root locus for K < 0.
Example 3-16 Consider a continuous-system, open-loop function defined by:
G=
σ 2 + 18σ + 81 + σ 2 = 54
This gives:
σ = − 1 . 902, − 7 . 098
K( s + 2 )
(s + 1)2
It is required to construct the root locus and find a closed-loop pole at
K =2. When we have two adjacent poles with a zero, the root locus is
a circle, centered at zero and having a radius which is a geometric mean
of the distances from zeros to the poles. The radius of the circle is:
[(z − p1 )(z − p2 )]1/ 2
(3-79)
The root locus is as shown in Fig. 3-24. We know that C/R and G
have the same zeros, but not the same poles unless K = 0. Closedloop poles may be determined from the root locus for a given K,
but closed-loop zeros are not equal to the open-loop zeros. Several
values of K are shown in Fig. 3-24 by small triangles. These are the
closed-loop poles corresponding to the specified values of K. As an
example for K = 2, the closed-loop poles are:
2(s + 2)
(s + 2 + j)(s + 2 − j)
Example 3-17 A system with unity feedback has an open-loop
transfer function given by:
K( s + 9 )
s(s + 3)
53
FIGURE 3-25
Example 3-17, root-locus diagram.
54
CHAPTER THREE
For the first set of poles:
σ = − 1 . 902 ± j1 . 902
Characteristic equation is:
1 + GH = 0
1+
K( s + 9 )
=0
s(s + 3)
s2 + (3 + K )s + 9K = 0
Also:
(s + 1 . 902 + j1 . 902)(s + 1 . 902 − j1 . 902) = 0
s2 + 2 × 1 . 902s + 2 × 1 . 9022 = 0
Comparing:
3 + K = 2 × 1 . 902
9K = 2 × 1 . 9022
Both of these relations give K = 0.8038. Thus, the closed-loop
transfer function is:
(0 . 8038)(s + 9)
s2 + 3 . 8038s + 7 . 235
Step response is given by:
1 G 1 (0 . 8038)(s + 9)
c(s) =
=
s 1 + GH s s2 + 3 . 8038s + 7 . 2 35
Resolve into partial fractions:
s + 1 . 902
1
0 . 577(1 . 902)
c(s) = −
−
s (s + 1 . 902)2 + (1 . 902)2 (s + 1 . 902)2 + (1 . 902)2
FIGURE 3-26
Thus:
Example 3-18, root locus diagram.
C(t ) = 1 − e −1.902t[cos1 . 902t + 0 . 577 sin 1 . 902t]
This can be repeated for the second set of poles at − 7 . 098 ± j7 . 098
Example 3-18 Construct the root locus for closed-loop continuous system for K > 0, given the open-loop transfer function:
K
GH =
s(s + 2)(s + 4 )
Mark the poles 0, 2, and 4 on the real axis, as shown in Fig. 3-26. The
root locus on the real axis is straightforward. Next, find asymptotes:
(2 + 4 ) − 0
σ c = −
= −2
3−0
This gives the center of the asymptotes; there are three asymptotes. These angles are calculated from Eq. (3-73) and are
β = 60 °, 180 °, and 300 ° . There is a breakaway point between 0
and –2 on the real axis. Using Eq. (3-74) this breakaway point is at
–0.845. The value of K at crossing of the root locus on imaginary
axis can be found from the characteristic equation:
s(s + 2)(s + 4 ) + K = 0
s = jω = 0 at the imaginary axis. This gives K = 48 and ω = 2 . 82 .
The values of K can be calculated similarly for other points on the
axis. The gain factor K required to give a specific damping ratio ξ
is determined from:
θ = cos −1 ξ
(3-80)
The procedure can be applied to any pair of complex conjugate
poles for systems of second order or higher.
Let us find the gain which gives a damping ratio of 0.55. Here,
cos −1 0 . 55 = 56 . 6 ° . This intersects the root locus at K = 7.
Example 3-19 Consider the characteristic equation of a fourthorder system as K varies, K > 0:
1+
K
=0
s 4 + 9s 3 + 36s2 + 54 s
This can be written as:
1+
K
s(s + 3)(s + 3 + 3 j)(s + 3 − 3 j)
Thus, as K varies from zero to infinity, the system has no finite
zeros. Locate the poles in the s plane as shown in Fig. 3-27a.
Root locus between s = 0 and s = –3 can be easily drawn. For
the fourth-order system, we should have four separate loci and the
CONTROL SYSTEMS
FIGURE 3-27
Example 3-19, root locus diagram.
root locus is symmetrical with respect to real axis. The angles of the
asymptotes are found from Eq. (3-73) and are:
β=
(2l + 1)180 °
= 45 °, 135 °, 225 °, 315 °
4
The center of the asymptotes is calculated from Eq. (3-72), which
gives:
σc =
−3 − 3 − 3
= 2 . 25
4
The asymptotes can be drawn, as shown in Fig. 3-27a. The characteristic equation is:
s(s + 3)(s2 + 6s + 18) + K = s 4 + 9s 3 + 36s2 + 54 s + K = 0
Apply Routh’s criteria of stability:
s4
1
36
s3
9
54
s2
30
s1
54 − 0 . 3K
s0
K
The points where the root locus crosses the imaginary axis are
shown in Fig. 3-27a. Estimate the breakaway point between s = 0
and s = –3.
1
1
1
1
+
+
+
=0
σb σb + 3 σb + 3+ 3 j σb + 3− 3 j
The solution can be found by hit and trial between 0 and –3. An
estimated value of –s = –0.5 satisfies this equation. We can also find
the break point by maximizing the polynomial for s:
−s(s + 3)(s + 3 + j3)(s + 3 − j3)
The angle of departure at the complex pole p1 can be found by
utilizing the angle criteria:
θ1 + 90 ° + 90 ° + θ 3 = 180 °
θ 3 = 135 °
Therefore:
θ1 = − 135 ° = + 225 °
Note that θ 3 is the angle of the vector from the pole at p3.
The completed root locus plot is shown in Fig. 3-27b. Consider
a damping ratio, ξ = 0 . 707 . Then we can graphically find the gain
K to the root location at s1 as follows:
K
K = s1 s1 + 3 s1 − p1 s1 − p2 ≈ 100
K
The limiting value of K for stability is:
54 − 0 . 3K = 0
55
K = 180
The auxiliary equation is:
approximately
Roots s3 and s4 occur when K = 100. The effect of these roots on
transient response will be negligible compared to roots s1 and s2.
The complex conjugate roots near the origin of the s plane relative
to other roots are labeled dominant roots of the system because
they represent dominant transient response.
30s2 + 180 = 0
3-14
30(s2 + 6) = 0
The Bode plot or Bode diagram is a frequency plot of the system,
where the amplitude in decibels and the phase angle in degrees
are plotted against the logarithm of the frequency. Thus, the Bode
30(s + j2 . 44 )(s − j2 . 44 )
BODE PLOT
56
CHAPTER THREE
plot consists of two graphs. The representation of the open-loop
frequency response function GH(w) may refer to a discrete-time or
continuous-time system. Bode plot clearly illustrates the stability
of the system, and often the gain and phase margins are defined in
terms of Bode plots (Chap. 13).
The Bode form of the function can be written by replacing
s with jw, that is
GH( jω ) =
=
K( jω + z1 )( jω + z 2 )( jω + z m )
( jω )l ( jω + p1 )( jω + p2 )( jω + p n )
K B (1 + jω / z1 )(1 + jω / z 2 )(1 + jω / z m )
( jω )l (1 + jω / p1 )(1 + jω / p2 )(1 + jω / p n )
(3-81)
where l is any nonnegative integer, and KB is defined as the Bode
gain given by:
m
KB =
K∏ z i
i=1
n
(3-82)
∏ pi
FIGURE 3-28
(a) Bode plot magnitude. (b) Phase angle for KB.
i=1
Taking logs:
20 log GH( jω ) = 20 log K B + 20 log 1 +
− 2 0 log ( jω )l − 20 log 1 +
jω
jω
+ + 20 log 1 +
z1
zm
jω
jω
− − 20 log 1 +
p1
pn
(3-83)
and:
jω
jω
arg GH( jω ) = arg K B + arg 1 + + + arg 1 +
z
zm
1
1
1
1
+ arg
+ + arg
+ arg
l
ω
j
p
j
ω
/
p
1
1
+
/
+
( jω )
n
1
(3-84)
Here, we denote log as the log to the base 10
Each part of GH in the factored form can be plotted separately
and the results added. The Bode plots are drawn on semilog paper.
3-14-1
Bode Plots of Simple Functions
The magnitude plot of 20 log10 K B is a straight line and can be easily plotted. KB has a phase angle of zero if positive, and –180° if negative.
The magnitude and phase angle plots are shown in Fig. 3–28a and b.
The frequency response functions of the pole at origin, that is,
1/(jw)l , 20log s–l are straight lines, and have a slope of 20 dB per
unit of log w (Fig. 3-29a). Args of 1/(jw)l are straight lines, as shown
in Fig. 3-29b. Since a unit for a logarithmic scale is a change by a
factor of 10 (log 1000 – log 100 = 3 – 2 = 1), the logarithmic unit
is a decade of frequency, 20 dB per decade for l = 1. For l = 2, it will
be 40 dB per decade (Fig. 3-29a).
Similarly, the frequency response and args of 20 log (jw)l are shown
in Fig. 3-30a and b. The slope is positive for zero and negative for a pole. The
plots for the single-pole transfer functions 1/ (1 + jw /p) are shown in
Fig. 3-31a and b. The asymptotic approximations are arrived as follows:
For w /p << 1 or w << p
20 log
1
≅ 20 log 1 = 0 dB
1 + jω /p
(3-85)
FIGURE 3-29
order l at the origin.
(a) Bode plot, magnitude. (b) Phase angle for pole of
CONTROL SYSTEMS
FIGURE 3-30
(a) Bode plot, magnitude. (b) Phase angle for zero of
FIGURE 3-31
57
(a) Bode plot, phase angle. (b) Magnitude for single-
order l at the origin.
pole.
For w /p >> 1 or w >> p
is +11.3° and –11.3°, respectively, and the magnitude error is
–0.17dB.
Similarly, the Bode plots and their asymptotic approximations
for single zero frequency response function, 1 + jw /z, are shown in
Figs. 3-32a and b.
20 log10
1
≅ − 20 log(ω /p )
1 + jω /p
(3-86)
The Bode magnitude plot asymptotically approaches a straight
line horizontally at 0 dB as w /p approaches zero and −20 log10 (ω /p)
as w /p approaches infinity. Note that the horizontal axis is normalized to w /p. The high-frequency asymptote is a straight line with
a slope of –20 dB/decade or –6 dB/octave, when plotted on a logarithmic frequency scale as shown. The two asymptotes intersect at
the corner frequency, where w = p rad/s.
For w /p << 1 or w << p
1
arg
= − tan −1(ω /p) ω p ≅ 0 °
1 + jω /p
(3-87)
For w /p >> 1 or w >>p
1
arg
= − tan −1(ω /p) ω p ≅ − 90 °
1 + jω /p
(3-88)
Bode plot angle asymptotically approaches 0° as w /p approaches
zero and –90° when w /p approaches infinity. Note the straight line
portion (asymptote) between w = p/5 and w = 5p. It is tangent to
the exact curve at w = p.
The magnitude error when w = p is –3 dB maximum and the
phase angle error is zero. At w = 5p and 5/p, the phase angle error
3-14-2
Bode Plot for Second-Order Frequency Response
The Bode plot and their asymptotic approximations for the secondorder frequency response function with complex poles:
1
1 + j2ξω /ωn − (ω /ωn )2
0 ≤ ξ ≤1
(3-89)
are constructed as shown in Fig. 3-33a and b. The magnitude asymptote has a corner frequency at w = wn and a high-frequency asymptote twice that of single-pole case, that is, 40 dB. The phase angle
asymptote is similar to that of a single pole, except that the highfrequency portion is at –180°, instead of –90° for the single-pole
case. The point of inflection is at –90°. Note the effect of damping
ratio ξ.
The Bode plots for a complex pair of zeros will be the reflections
about 0 dB and 0° lines of those for the complex poles.
3-14-3
Construction of Bode Plots
The Bode plots can be constructed based upon the concepts outlined above. This will be illustrated by an example.
58
CHAPTER THREE
FIGURE 3-32
(a) Bode plot, phase angle. (b) Magnitude for
single-zero.
Example 3-20 Construct the asymptotic Bode plots for the
frequency response function:
GH( jω ) =
10(1 + jω )
( jω )2[1 + jω / 3 − (ω / 3)2]
The asymptotes are constructed using the equations already derived
above. Taking logs,
20 log10 GH(ω ) = 20 log 10 + 20 log 1 + jω
+ 20 log
1
1
+ 20 lo g
1 + jω / 3 − (ω / 3)2
( jω )2
The construction is shown in Fig. 3-34a and b. Note the construction of asymptote for each component using the techniques as
graphically illustrated before. The complex poles are constructed
as follows:
Magnitude asymptote is ω = ωn = 3, which gives the corner
frequency. Draw a –40 dB slope between 3 and 30 rad/s.
Phase angle asymptote 5p = 15 and 0.2p = 0.6. Draw an
asymptote spanning 180°.
The asymptotic Bode plot is obtained by summation of all
the asymptotes, shown in bold. The Bode plots can be
FIGURE 3-33
(a) Bode plot, phase angle. (b) Magnitude for secondorder frequency function with complex poles.
constructed around these asymptotes. A computer simulation
is commonly used.
3-15
RELATIVE STABILITY
The criteria of relative stability in terms of system open-loop frequency response are phase and gain margins, for both discrete-time
and continuous-time systems. These are easily determined from
Bode plots (Fig. 3-35).
0 dB corresponds to a magnitude of 1. The gain margin is the
number of decibels the magnitude of GH is below 0 dB, at the
phase crossover frequency:
[arg GH(ω )] = − 180 ° = ωπ
(3-90)
The phase margin is the number of degrees arg (GH) is above –180°
at the gain crossover frequency ω1
GH(ω ) = 1
(3-91)
CONTROL SYSTEMS
59
response from the Bode plots. The closed-loop frequency response
can be approximated as follows:
GH(ω ) >> 1
C
(ω )
R
≈
GH(ω ) >>1
1
G(ω )
=
GH(ω ) H(ω )
(3-92)
and
GH(ω ) << 1
C
(ω )
R
(3-93)
≈ G(ω )
GH(ω ) <<1
The open-loop frequency response for most systems shows high
gain, which decreases as the frequency is increased, because the
poles predominate over zeros. The closed-loop frequency response
for unity feedback systems is approximated by magnitude of 1 (0 dB)
and phase angle of 0° for frequency below gain crossover frequency
of ω1. For higher frequencies, above ω1, the close-loop frequency
response may be approximated by magnitude and phase angle of
G(w).
Example 3-21 Consider the given Bode plot of the open-loop
frequency response function of the form in Fig. 3-36:
GH(s) =
K
s(s + ω1 )(s + ω2 )
Both magnitude and phase angle are given. Find ω1, ω2, K and
phase margin. Adjust K to give a phase margin of 45°. ω1 and ω2
can be easily found from the Bode plot by observing the two break
points at 10 and 100 rad/s. Therefore:
T1 = 1/ω1 = 0 . 1s
FIGURE 3-34
3-15-1
Example 3-20, asymptotic Bode plots.
Closed-Loop Frequency Response
In most cases the phase margin and the gain margin, shown in
Eqs. (3-90) and (3-91) will ensure relative stability. The absolute
stability can be ascertained by Routh’s array or Nyquist stability
plots. There is no straightforward method of plotting the closed-loop
GH(s) =
T2 = 1/ω2 = 0 . 01s
K
K′
=
s(0 . 1s + 1)(0 . 01s + 1) s(s + 10)(s + 100)
GH( j ω ) =
K
jω ( jω + 10)( jω + 100)
At 0.1 rad/s, the gain in dB = 60. Substituting:
GH( jω ) = 60 dB = 1000 =
K
(0 . 1 j)(0 . 1 j + 10)(0 . 1 j + 100)
K = 10,0000
From Fig. 3-36 at 0 dB, the phase angle is –175°. Thus, the phase
margin is 5°, and the system is unstable.
For a phase margin of 45°, the phase plot should cross at an
angle of –135° at 0 dB. Again referring to Fig. 3-36, at –135°, our
gain is 20 dB at a frequency of 10 rad/s. Thus, we can reduce our K
by 20 dB, that is, by a factor of 10 (K = 104).
Example 3-22 Consider two open-loop functions in cascade
represented by the Bode magnitude plot in Fig. 3-37. Find the
open-loop transfer function. If the two functions are in a forward
loop with unity feedback, is the system stable?
Consider the plot of the function G1(s). The break point is
clearly at 50 rad/s, and if we examine the plot from 0.5 through
50 rad/s, it has a roll of 20 dB and 40 dB past 50 rad/s. Therefore,
the function is:
FIGURE 3-35
Relative stability, phase and gain margins, system
open-loop frequency response.
G1(s) =
K1
s(0 . 2s + 1)
60
CHAPTER THREE
FIGURE 3-36
FIGURE 3-37
Example 3-21, Bode plot, magnitude and phase angle.
Example 3-22, Bode plot, gain magnitude of two functions.
At j(0.5), the gain is 50 dB. Pick up a point as far away from the
break point as possible. By substitution K1 = 158. The function G2 (s)
has a single pole given by:
K2
G2 (s) =
0 . 5s + 1
K2 is obviously the dc gain when s = 0 and is 20 dB, K = 10. The
open-loop transfer function is:
G(s) =
1580
s(0 . 02s + 1)(0 . 5s + 1)
By examining Fig. 3-37, the Bode plot of the overall function
will cross over 0 dB at 50 rad/s. Substituting the values:
G( j50) = 0 . 89 < − 223 °
It has negative phase margin at a gain of 0.893, and the system is
definitely unstable.
3-16
THE NYQUIST DIAGRAM
In the Nyquist diagram, the amplitude of GH is plotted against
phase angle in a polar form. The points are found by ascertaining
the magnitude as well as the phase angles at each frequency.
CONTROL SYSTEMS
FIGURE 3-39
FIGURE 3-38
Data flow between power system and TACS in EMTP.
Nyquist diagram to illustrate stability concepts.
The absolute stability of a closed-loop system can be determined
from the behavior of the curve near the –1 point. Figure 3-38 shows
the curves plotted with unit circle which is the magnitude of GH.
The system will be absolutely stable if the curve of GH versus < GH
does not encircle the –1 point on the Nyquist diagram.
The behavior of the closed-loop system will be determined
mainly by the closeness of the curve to the –1 point. The gain and
phase margins are available on the curve. The stable and unstable
curves shown in the figure are for a single integrator. As the gain is
increased the system becomes unstable.
The Nyquist diagram is more difficult to construct as compared
to the Bode plot. While Bode plots and root-locus methods are
common, the Nyquist diagram is occasionally used. This book does
not provide a detailed analysis of the Nyquist diagram.
3-17
61
TACS IN EMTP
Transient analysis of control systems (TACS) was added to EMTP by
L. Dubé. In 1983–1984 Ma Ren Ming made major revisions to it.2
It was originally written to simulate operation of high-voltage DC
(HVDC) converters, but soon had wider applications, for example,
excitation systems of synchronous machines, arcing phenomena in
circuit breakers, and surge arrester modeling.
The control system in TACS has been solved separately. Output quantities from network are used as input quantities in TACS
over the same time step. Output quantities from TACS become the
input quantities to the network solution only over the next time step.
TACS accepts as input network voltages, currents, switch currents,
status of switches, and internal variables, and the network solution
accepts output signals from TACS (Fig. 3-39). In many cases the
error is due to time delay; Dt may not be of significance, but not
always. With continuous voltage and current source functions and
fast varying data coming out of TACS, the time delay can become
critical and can cause numerical instability.
The solution can be straightforward, if all devices in the control
system are linear. Consider a transfer function of the form:
K ( N 0 + N1 s + + N m s m )
;m<n
D0 + D1s + D n s n
The differential equations can be converted into difference equations with trapezoidal rule of integration (see App. G):
x i (t ) =
2
2
x i−1(t ) − x i (t − D t ) +
x i−1(t − D t ) i = 1, . . . , n
Dt
Dt
(3-96)
u j (t ) =
2
2
u j−1(t ) − u j (t − D t ) + u j−1(t − D t )
Dt
Dt
j = 1, . . . , n
(3-97)
Expressing xn as a function of xn–1 and then expressing xn–1 as a function of xn–2 and so on, and then using the same procedure for u, we
have a single output-input relation:
cx(t ) = Kdu(t ) + hist(t − D t )
(3-98)
where “hist” is the history term after the solution at each time step,
n history terms must be updated to obtain single term “hist” for the
next time step. If recursive formulas are used:
hist n (t ) = Kd n u(t ) − cn x(t )
(3-99)
Equation (3-98) is used in the transient solution of the control
system. Fast varying components may create instabilities and end
up in wrong operating region. More discussion on improvements of
TACS is available in Refs. 3 to 6.
A new approach for eliminating delays in the solution of control
systems is presented in Ref. 7. The complete system is formulated
using a jacobian matrix and solved through an iterative process.
The iterative methods, noniterative method, and ordering issues are
discussed with some test results.
PROBLEMS
(3-94)
Input is u(s) and output x(s). In changing nth-order differential
equation to n differential equations of first order, we have an algebraic equation:
D0 x + D1 x1 + + D n x n = K(N o u + N1u1 + + N m u m ) (3-95)
1. A unity feedback control system has a forward transfer
function:
G=
20
s(s + 10)
A tachometer feedback is applied, with a transfer function ks.
Determine k for a damping ratio of 0.707.
62
CHAPTER THREE
2. A control system has the following open-loop transfer function:
GH =
106
(s + 10s + 100)(s + 100)
9. Reduce the block diagram of Fig. 3-P2, and eliminate feedback loop H2 and the summing junction 1.
2
Is the system stable? Add a lag compensator of the form
1/(1+Cs), and select C to provide 45° phase margin.
3. A closed-loop control transfer function is given by:
K
s 3 + 2s 2 + 4 s + K
For positive values of K, sketch the root locus and find (a)
breakaway points on real axis, (b) frequency and gain at any
point where instability begins, and (c) complex frequency
and gain for a damping ratio of 0.707.
4. The characteristic equation of system is given by:
s 4 + 5s 3 + 10s2 + 6s + K = 0
FIGURE 3-P2
Block diagram of a control system, Prob. 9.
10. Consider the signal-flow graph as shown in Fig. 3-P3.
Find forward paths, feedback paths, nontouching loops,
touching loops, loop gain of feedback loops, and path gains of
the forward loops.
Find the value of K so that the system is stable.
5. Use Hurwitz stability criteria to find out if the control system given by the following equation is stable or unstable:
s 3 + 10s2 + 13s + 20 = 0
6. Find if the discrete system given by the following equation
is stable:
FIGURE 3-P3
Signal-flow graph, Prob. 10.
z 4 + 2z 3 + 4 z 2 + z + 1 = 0
7. Find the transfer function of the differential equation represented by the following equation:
11. Draw a signal-flow graph for the electrical network shown
in Fig. 3-P4.
du
d2 y
dy
+ 6 + 5 y = 2u +
dt
dt
dt 2
8. Find the transfer function of the electrical network shown
in Fig. 3-P1a and b
FIGURE 3-P4
Circuit for drawing signal-flow graph, Prob. 11.
12. The system defined by the Fig. 3-P5 is a (1) type-one
system, (2) type-two system (3) type-zero system? Describe the
position, velocity, and acceleration errors of type-zero, typeone and type-two systems. What is the major problem of typethree systems?
FIGURE 3-P1
(a) and (b). Calculation of transfer functions, Prob. 8.
FIGURE 3-P5
Block diagram of a control system, Prob. 12.
CONTROL SYSTEMS
13. Find the breakaway point for:
GH =
K(s + 1)
(s + 1 + j 2 )(s + 1 − j 2 )
14. Construct the root locus for:
K >0
15. Construct the Bode plot for the open-loop frequency
response function:
GH( jω ) =
1 + 0 . 33 jω − (0 . 33ω )
jω (1 + 0 . 25 jω )(1 + 0 . 5 jω )
2
16. Obtain the state diagram for the following equations:
y(t ) + 3 y (t ) + 5 y(t ) = r(t )
y(k + 2) + ay(k + 1) + by(k ) = r(k )
17. Consider the system shown in Fig. 3-P6. Find a compensator so that closed-loop transfer function has damping ratio
of 0.707 and natural frequency of 0.15.
FIGURE 3-P6
Control circuit for designing a compensator,
Prob. 17.
18. Draw the state diagram of a system represented by the following differential equation:
a
3. R. H. Lasseter and J. Zhou, “TACS Enhacements for the Electromagnetic Transient Program,” IEEE Trans. PS, vol. 9, no. 2,
pp. 736–742, May 1994.
4. S. Lefebvre and J. Mahseredjian, “Improved Control System
Simulation in the EMTP Through Compensation,” IEEE Trans.
PS, vol. 9, no. 3, pp. 1654–1662, July 1994.
and draw the root locus.
K
(s + 2)(s + 2 − j)(s + 2 + j)
63
d2 y
dy
+ b + cy = u(t )
dt
dt 2
REFERENCES
1. G. Newton, L. Gould, and J. Kaiser, Analytical Design of Feedback Control, John Wiley, New York, 1957.
2. M. Ren Ming, “The Challenge of Better EMTP-TACS Variable
Ordering,” EMTP Newsletter, vol. 4, no. 4, pp.1–6, Aug. 1984.
5. X. Cao, A. Kurita, T. Yamanaka, Y. Tada, and H. Mitsuma,
“Supression of Numerical Oscillation Caused by the EMTP-TACS
Interface using Filter Incorporation,” IEEE Trans. PD, vol. 11, no. 4,
pp. 2049–2055, Oct. 1996.
6. A. E. A. Araujo, H. W. Dommel, and J. R. Marti, “Simultaneous
Solution of Power and Control System Equations,” IEEE Trans.
PS, vol. 8, no. 4, pp. 1483–1489, Nov. 1993.
7. J. Mahseredjian, L. Dube, M. Zou, S. Dennetiere, and G. Joos,
“Simultaneous Solution of Control System Equations in EMTP,”
International Conference on Power System Transients, Montreal,
June 2005.
FURTHER READING
B. K. Bose, Power Electronics and Variable Frequency Drives, IEEE
Press, Piscataway, NJ, 1997.
J. A. Cadzow, Discrete Time Systems, Prentice Hall, Englewood Cliffs,
NJ, 1973.
C., Chi-Tsing, Linear System Theory and Design, Holt, Rinehart, and
Winston, New York, 1984.
R. C. Dorf, Electrical Engineering Handbook, 2d ed., CRC Press, Boca
Raton, FL, 1998.
R. C. Dorf and R. H. Bishop, Modern Control Systems, 8th ed., AddisonWesley, Berkeley, CA, 1999.
W. R. Evans, Control System Dynamics, McGraw Hill, New York,
1954.
M. M. Gupta, Intelligent Control, IEEE Press, Piscataway, NJ, 1995.
R. R. Kadiyala, “A Tool Box for Approximate Linearization of NonLinear Systems,” IEEE Control Systems, pp. 47–56, April 1993.
E. W. Kamen and B. S. Heck, Fundamentals of Signals and Systems
Using MALAB, Prentice Hall, Englewood Cliffs, NJ, 1997.
B. C. Kuo. Automatic Control Systems, 5th ed., Prentice Hall, Englewood
Cliffs, NJ, 1996.
W. S. Levine. The Control Handbook, CRC Press, Boca Raton, FL,
1996.
G. Norris, “Boeing Seventh Wonder,” IEEE Spectrum, pp. 20–23,
October 1995.
This page intentionally left blank
CHAPTER 4
MODELING OF TRANSMISSION
LINES AND CABLES FOR
TRANSIENT STUDIES
Electrical power systems can be classified into generation, transmission,
sub-transmission, and distribution systems. Individual power systems
are organized in the form of electrically connected areas of regional grids,
which are interconnected through transmission lines to form national
grids and also international grids. Each area is interconnected to another
area in terms of some contracted parameters like generation and scheduling and tie line power flow, contingency operations. The irreplaceable
sources of power generation are petroleum, natural gas, oil and nuclear
fuels. The fission of heavy atomic weight elements like uranium and thorium and fusion of lightweight elements, such as deuterium, offer almost
limitless reserves. Replaceable sources are elevated water, pumped storage systems, solar, geothermal, wind and fuel cells, which in recent times
have received much attention. Single shaft steam units of 1500 MW are
in operation, and superconducting single units of 5000 MW or more are
a possibility. On the other hand, dispersed generating units integrated
with grid may produce only a few kilowatts of power.
The generation voltage is a low 13.8–25 kV, the transmission voltages have risen to 765 kV or higher, and many HVDC links around
the world are in operation. While, maintaining acceptable voltage
profile and load frequency control is one issue, the transient phenomena on transmission lines due to lightning and switching and
mitigation of these transients through shielding, surge arresters, and
control of switching overvoltages are equally important and covered
in this book. Synchronous condensers, shunt capacitors, static var
compensators, and FACTS devices are employed to improve power
system stability and enhance power handling capability of transmission
lines and also impact the transient behavior. The sub-transmission
voltage levels are 23 kV to approximately 69 kV, though for large
industrial consumers voltages of 230 kV and 138 kV are also used.
Sub-transmission systems connect high voltage substations to local
distribution substations. The voltage is further educed to 12.47 kV,
and several distribution lines and cables emanate from distribution
stations. The refinements in modeling and analytical techniques
continue, as we will discuss in this chapter.
The modeling of transmission lines for transient analysis should
be based on the frequency. For load flow and power transmission,
the models are based on the length of the line, though the same
load flow models (in modified form) are used for the transient studies. Conventionally, lines exceeding approximately 150 mi are considered long lines and we consider wave propagation, that is, the
voltage and currents propagate on a conductor with finite velocity,
which are reflected or refracted at the impedance discontinuities. As
discussed in Chap. 2, partial differential equations are used to derive
the wave equations, the capacitance of the transmission lines playing an important role. For short lines of less than 50 mi, the line is
modeled based on conductor series resistance and inductance only.
For the transmission lines in the range of 50 to 150 mi, there are two
models in use, the nominal P and nominal T-circuit models. In the
T-circuit model, the shunt admittance is connected at the midpoint
of the line, while in the nominal P model, it is equally divided at the
sending end and the receiving end.
Table 4-1 shows the models with respect to frequency and transmission line parameters. This table is based on CIGRE guidelines.1
Depending on the nature of specific transient study, additional
details of shielding, tower footing resistance, towers themselves, and
soil resistivity data will be required to derive an appropriate model.
The length of the line modeled depends on the frequency involved.
For high-frequency studies, it will be appropriate to model a couple
of spans of the transmission line, and for low-frequency transients,
the whole line length may be included in the studies. For VFT, even
for short lines the load flow model is not proper, and distributed
parameter model should be used (Table 4-1).
While deriving appropriate line models in EMTP-like programs,
more data of the lines will be required than are available in the line
constant tabulations in most handbooks. Appendix D is devoted to
the estimation of line constants, and the reader may like to study it
before proceeding with this chapter.
We will revert to the models for the transient studies in a later
section of this chapter.
4-1 ABCD PARAMETERS
A transmission line of any length can be represented by a four-terminal
network, Fig. 4-1a. In terms of A, B, C, and D parameters, the relation
65
66
CHAPTER FOUR
TA B L E 4 - 1
TOPIC
LOW FREQUENCY TRANSIENTS
GROUP I
Modeling of Transmission Lines
SLOW FRONT TRANSIENTS
GROUP II
FAST FRONT TRANSIENTS
GROUP III
Representation of Lumped parameters;
transposed lines multiphase P circuits
Distributed parameter; multiphase
model; multiphase P circuits
possible
Line asymmetry
Important
Capacitive and inductive asymmetry Negligible for single-phase
important; for statistical study
simulations, otherwise
inductive asymmetry not important important
Negligible
Frequencydependent
parameters
Important
Important
Important
Important
Corona effect
Important if phase
conductor voltage can
exceed the corona
inception voltage
Negligible
Very important
Important
FIGURE 4-1
Distributed parameter; single-phase
model
(a) Schematic representation of a two-terminal network using ABCD constants; (b) two networks in series; (c) two networks in parallel.
between sending- and receiving-end voltages and currents can be
expressed as:
Vs
= A B
C D
Is
Distributed parameter;
multiphase model
VERY FAST FRONT TRANSIENTS
GROUP IV
Vr
Ir
(4-1)
where Vs and Is are the sending-end voltage and current and Vr and Ir
are the receiving-end voltage and current, respectively.
In case sending-end voltages and currents are known, the
receiving-end voltage and current can be found by:
Vr
= D −B
−C A
Ir
Vs
Is
(4-2)
The significance of A, B, C, and D parameters can be stated as
follows:
MODELING OF TRANSMISSION LINES AND CABLES FOR TRANSIENT STUDIES
A = Vs/Vr , when Ir is 0, that is, the receiving end is open-circuited.
It is the ratio of two voltages and is, thus, dimensionless.
B = Vr /Ir, when Vr is 0, that is, the receiving end is short-circuited.
It has the dimensions of impedance and is specified in ohms.
C = Is/Vr, when the receiving end is open-circuited and Ir is 0. It
has the dimensions of admittance.
reactance of the elemental section. The impedance for the elemental
section of length dx is z dx and the admittance is y dx, Z = zl, where
l is the length of the line and Y = yl. Referring to Fig. 4-3, by
Kirchoff’s voltage law, the voltage drop in the elemental length dx
due to resistance and inductance is:
dV =
Vs
A B A2 B2 Vr
A A +B C A B +B D V
= 1 1
= 1 2 1 2 1 2 1 2 r
Is
C1 D1 C2 D2 I r
C1 A2 + D1C2 C1B2 + D1D2 I r
(4-3)
For parallel ABCD networks (Fig. 4-1c) the combined ABCD
parameters are:
A = ( A1B2 + A2 B1 )/(B1 + B2 )
B = (B1B2 )/(B1 + B2 )
C = (C1 + C2 )
D = (B2 D1 + B1D2 )/(B1 + B2 )
∂V
∂i
=L
∂x
∂t
∂
∂I
dx = Vg sh dx + (D ϕ )
∂t
∂x
∂
= Vg sh dx + (VCdx )
∂t
∂
= g sh + C Vdx
∂
t
∂I =
4-3 LONG TRANSMISSION LINE MODEL-WAVE
EQUATION
Lumping together the shunt admittance of the lines at sending
and receiving ends is an approximation, and for line lengths over
150 mi (240 km), distributed parameter representation of a line
is used. Each elemental section of line has series impedance and
shunt admittance associated with it. The operation of a long line
can be examined by considering an elemental section of impedance
z per unit length, z = rsc + jxsc = rsc + jwL and admittance y per unit
length. Here, we have denoted rsc and xsc as the series resistance and
TA B L E 4 - 2
EQUIVALENT CIRCUIT
Series impedance only
(4-6)
The change in the flux with respect to time produces a voltage
along the line given by the above expression. The term L ∂i/∂t by
definition is equal to the rate of change in the flux.
Define the following elements, to distinguish from line series
elements:
g sh = shunt conductance, bsh = shunt susceptance, xsh = shunt
capacitive reactance, and C = capacitance per unit length. Shunt
conductance is small and ignoring it gives y = j/xsh.
The shunt current through the conductance and capacitance is:
(4-4)
Table 4-2 gives the ABCD parameters of transmission line models—
T or P representation parameters and distributed parameters
model. For the medium long lines, the P representation is more
commonly used, compared to the T representation. A reader can
derive T and P models by considering the terminal current and
voltage conditions, as shown in Fig. 4-2a, b, c, and d.
Short
(4-5)
If we ignore the series resistance, the equation can be written as:
4-2 ABCD PARAMETERS OF TRANSMISSION LINE
MODELS
LINE LENGTH
∂V
∂
dx = irsc dx + L (idx )
∂x
∂t
∂
= rsc + L idx
∂t
D = Is /Ir, when Vr is 0, that is, the receiving end is shortcircuited. It is the ratio of two currents and is, thus,
dimensionless.
Two ABCD networks in series (Fig. 4-1b) can be reduced to a
single equivalent network as follows:
67
where D ϕ is the change in the electrostatic flux between the conductors. Ignoring shunt conductance, this equation can be written as:
∂V
∂i
=C
∂t
∂t
(4-8)
A change of current with time produces a change of voltage with
position along the line, and a change of voltage with time produces
a change of current with position along the line.
Taking Laplace transform with respect to time variable t, the
equations can be written as:
∂V
= (rsc + Ls) i = zi
∂x
(4-9)
∂i
= ( g sh + Cs) i = yi
∂x
ABCD Parameters
A
1
(4-7)
B
C
D
Z
0
1
1
1+ YZ
2
1
1+ YZ
2
Medium
Nominal P
1
1+ YZ
2
Z
1
Z 1+ YZ
4
Medium
Nominal T
1
1+ YZ
2
1
Z 1+ YZ
4
Y
Long
Distributed parameters
Coshγl
Z 0 sinhγl
sinhγl
Z0
Coshγl
68
CHAPTER FOUR
FIGURE 4-2
(a) P representation of a transmission line; (b) phasor diagram of the P circuit; (c) T-representation of a transmission line; (d ) phasor
diagram of T-circuit.
FIGURE 4-3
Modal of a small section of a long transmission line.
MODELING OF TRANSMISSION LINES AND CABLES FOR TRANSIENT STUDIES
Differentiating these equations gives:
∂2V
= yzV
∂x 2
∂2I
= yzI
∂x 2
Again neglecting gsh:
(4-10)
< Z0 =
These differential equations have solutions of the form:
(4-11)
Or in a more general form:
f1(t )e + f2 (t )e
γx
− γx
(4-12)
γ = yz
= [rsc g sh + (rscC + Lg sh )s + LCs2]1/ 2
1/ 2
1/ 2
(4-13)
If we ignore the shunt conductance:
y = jbsh
yz = −bsh x sc + jrsc bsh
(4-14)
γ = bsh (rsc2 + x 2sc )1/ 4
The complex propagation constant can be written as:
γ = α + jβ
g 1 r
g
1 r
= sc + sh + j sc − sh
C 2 L
2 L
C
(4-15)
where a is defined as attenuation constant. Common units are nepers per mile or per kilometer. b is the phase constant. Common units
are radians per mile. Again ignoring shunt conductance, the equations are simplified to the following form:
1
−r
α = γ cos tan −1 sc
2
x sc
1
−r
β = γ sin tan −1 sc
2
x sc
(4-16)
β=
rsc g sh − ω 2 LC + (rsc g sh − ω 2 LC)2 + ω 2 ( Lg sh + Crsc )2
2
−rsc g sh + ω 2 LC + (rsc g sh − ω 2 LC)2 + ω 2 ( Lg sh + Crsc )2
2
(4-17)
The characteristic impedance, also called surge impedance, is:
Z0 =
(4-20)
Vr + Z0I r α x+ jβ x Vr + Z0I r −α x − jβ x
e
e
+
2
2
1/ 2
(4-18)
(4-21)
These equations represent traveling waves. The solution consists of
two terms, each of which is a function of two variables, time and
distance. At any instant of time the first term, the incident wave, is
distributed sinusoidally along the line, with amplitude increasing
exponentially from the receiving end. After a time interval Dt, the
distribution advances in phase by ω Dt/β, and the wave is traveling
toward the receiving end. The second term is the reflected wave,
and after time interval Dt, the distribution retards in distance phase
by ω Dt/β, the wave traveling from the receiving end to the sending end.
Similar explanation holds true for the current. It is given by:
Ix =
Vr /Z0 + I r α x+ jβ x Vr /Z0 − I r −α x − jβ x
e
e
−
2
2
(4-22)
These equations can be written as:
e γx + e − γx
e γx − e − γx
Vx = Vr
+ I r Z0
2
2
e γx + e − γx
Vr e γx − e − γx
Ix =
+ Ir
Z0
2
2
(4-23)
Or in matrix form as:
Z0 sinh γ l
cosh γ l
1
sinh γ l cosh γ l
Z0
(4-24)
This result is also shown in Table 4-2 for the ABCD constants of the
distributed parameter lines.
Wavelength A complete voltage or current cycle along the line,
corresponding to a change of 2 π radians in angular argument of b
is defined as the wavelength l. If b is expressed in radians per mile
or radians per meter:
λ=
z
y
L s + α + β
=
C s + α − β
L
C
Z0 =
Vs
=
Is
The expressions for a and b can be written as:
α=
−r
1
tan − 1 sc
2
x sc
If we neglect the line series resistance also:
Vx =
= [(rsc + Ls)( g sh + Cs)]1/ 2
1 rsc g sh
s + s +
C
LC L
(4-19)
Equation (4-20) is of much practical importance in the transient
behavior of the transmission lines.
The voltage at any distance x can be written as:
where γ is the propagation constant and is defined as:
=
z rsc + jx sc
=
y
jbsh
Z0 = x sh (rsc2 + x 2sc )1/ 4
V = V1e γx + V2e − γx
69
2π
β
(4-25)
For a lossless line, that is, a line with zero series resistance and
shunt conductance:
β = ω LC
(4-26)
70
CHAPTER FOUR
Therefore:
1
λ=
f LC
(4-27)
and the velocity of propagation of the wave:
v = fλ =
1
(4-28)
LC
Substituting the values of L and C for a two-conductor line from
App. D:
v=
≈
connected to the junction point. An example of ground impedance
is a capacitor bank. The n lines have surge impedances Z1 … Zn,
and impedances Z1(s), Z2(s), … are lumped impedances expressed
in Laplace transform. Let V1, I1 be the voltage and current related to
incident wave, V1′, I1′ related to reflected wave, and Vk″, Ik″ related
to transmitted wave. The total impedance of the line is:
Zt(s) = Z1(s) +
1
k=n
1
1
+∑
Z g(s) k=2 (Zk (s) + Zk)
(4-30)
1
We can write the following relations from Kirchoff’s laws:
1
+ 1
µ0k0
4 ln(d /a )
V1 = Z1I1
1
(4-29)
µ0k0
where µ0 is 4 π × 10 and k0 is 8.854 × 10 . Therefore, 1/( µ0k0 )
= 3 × 1010 cm/s or 186,000 mi/s is velocity of light.
The actual velocity of the propagation of wave along the line is
somewhat less than the speed of light because of reactance, resistance, and leakage of the line. The value of attenuation constant
is determined from Eq. (4-16) and is a function of the frequency.
Thus, all the frequencies will not be attenuated equally. Also, phase
constant is a function of frequency, and as the velocity of propagation is inversely proportional to phase constant and directly to w,
which also involves frequency, the velocity will be some function
of frequency. All frequencies applied to the transmission line will
not have the same time of transmission, some frequencies being
delayed more than the others, giving rise to phase distortion. This
is an important concept.
–7
V1′ = −Z1I1′
(4-31)
Vk′′ = ZkI′′k
–12
4-4 REFLECTION AND TRANSMISSION
AT TRANSITION POINTS
When there is a change in the parameters of a transmission line, that is,
open circuit, short circuit, terminations through a cable, or other impedances, the traveling wave goes through a transition—part of the wave is
reflected and sent back and only part of the wave is transmitted.
Consider a general junction point, as shown in Fig. 4-4, with n
lines originating from the junction point and also ground impedance
FIGURE 4-4
The total voltage and current at the transition point t are:
Vt = V1 + V1′ = Zt (s)It = Zt(s)(I1 + I 2 )
(4-32)
Thus, the following relations can be written:
V1′ =
Zt(s) − Z1
V
Zt(s) + Z1 1
Vt =
2 Zt(s)
V
Zt(s) + Z1 1
I1′ =
Zt(s) − Z1
I
Zt(s) + Z1 1
It =
2 Zt(s)
I
Zt(s) + Z1 1
(4-33)
The ground current is:
Ig =
V1
2 Z(s)
=
V
Z g(s) Z g(s)[Zt(s) + Z1] 1
Multiple line terminations on a junction T, propagation of waves.
(4-34)
MODELING OF TRANSMISSION LINES AND CABLES FOR TRANSIENT STUDIES
The transmitted voltage and current are:
I′′k =
Vg
Zk(s) + Zk
Vk′′ = ZkIk′′ =
=
2 Z(s)
V
[Zt(s) + Z1][Zk(s) + Zk ] 1
2 Z(s)Zk
V
[Zt(s) + Z1][Zk(s) + Zk ] 1
source reflection coefficient akin to the load reflection coefficient
can be defined as:
(4-35)
2 Z(s)Zk(s)
V
[Zt(s) + Z1][Zk(s) + Zk ] 1
(4-36)
These are functions of s. The inverse transform gives the desired
time functions.
When the junction consists of two impedances only, the reflection and transmission coefficients are simpler. The reflection coefficient is defined at the load as the ratio of the amplitudes of the
backward and forward traveling waves. For a line terminated in a
load impedance Z2:
Z − Z
V1′ = 2 1 V1
Z2 + Z1
(4-37)
Therefore, the reflection coefficient at the load end is:
Z − Z
ρL = 2 1
Z2 + Z1
Z − Z
ρs = s 1
Z s + Z1
(4-39)
The transmission coefficient is:
The voltage drop across the lumped series impedances is:
Vk = Zk(s)Ik′′ =
71
(4-38)
The current reflection coefficient is negative of the voltage reflection coefficient. The reflected wave at an impedance discontinuity
is a mirror image of the incident wave moving in the opposite direction. Every point on the wave is the corresponding point on the
incident wave multiplied by the reflection coefficient, but a mirror
image. Figure 4-5a, b, and c clearly shows these phenomena. The
F I G U R E 4 - 5 (a) Incident and reflected waves at an impedance
discontinuity; (b) reinforcement of incident and reflected waves; (c) incident
and reflected waves crossing each other.
V1′′= (1 + ρ )V1 =
2 Z2
Z2 + Z1
I1′ = (1 − ρ )I1 =
2 Z1
Z2 + Z1
4-5
(4-40)
LATTICE DIAGRAMS
The forward and backward traveling waves can be shown on a lattice diagram. The horizontal axis is the distance of the line from
the source and the vertical axis is labeled in time increments, each
increment being the time required for the wave to travel the line in
one direction, that is, from the source to the load. Consider a point
P on the pulse shape of Fig. 4-6a at time t′. The time to travel in one
direction is l/u, where u is close to the velocity of light. The point P
then reaches the load end at t′ + l/u seconds, and is reflected back.
The corresponding point on the reflected wave is PrL. At the sending end, it is reflected as PrLrs. This is shown in Fig. 4-6b.
Example 4-1 A lossless line has a surge impedance of 300 Ω. It
is terminated in a resistance of 600 Ω. A 120-V dc source is applied
to the line at t = 0 at the sending end. The voltage profile along the
line for several time periods is drawn considering that the transient
time in one direction is t seconds.
The reflection coefficient of voltage at the receiving end (load
end) is 1/3 and at the source end is –1. (The source impedance is
zero.) The lattice diagram is in Fig. 4-7a and the receiving end voltage
is shown in Fig. 4-7b.
(a) A point P at time t ′ on a pulse signal applied to the
sending end of a line; (b) lattice diagram.
FIGURE 4-6
72
CHAPTER FOUR
FIGURE 4-7
(a) Lattice diagram of Example 4-1; (b) voltage at receiving end of the line.
4-6 BEHAVIOR WITH UNIT STEP FUNCTIONS
AT TRANSITION POINTS
Some typical cases can be studied as follows:
Line Open at Far End As the line is open, Z2 = ∝. Therefore, the
reflection coefficient is:
Z − Z
ρL = 2 1
Z2 + Z1
1 − Z /Z
L
1
=
=1
1 + Z1 /Z L
(4-41)
The reflected wave is equal to the incident wave and the transmitted wave is:
V ′′ = (1 + ρ L )V = 2V
(4-42)
The voltage will be doubled and the current is zero. If the line
is terminated in impedance, which is much higher than its surge
impedance, the voltage will be almost doubled. The highest overvoltages result when a circuit consists of overhead lines and cables,
particularly if the length of one is smaller than the other.
Line Short-Circuited at the Far End As the line is short-circuited,
Z2 = 0; therefore, from Eq. (4-38) the reflection coefficient = –1. The
reflected voltage wave is, therefore, reverse of the incident voltage
wave and the transmitted voltage wave = 0, the current will be
MODELING OF TRANSMISSION LINES AND CABLES FOR TRANSIENT STUDIES
73
doubled. A negative reflected voltage wave starts traveling the line
canceling the incident wave, while a positive current wave travels
the line increasing the current.
Line Terminated in a Reactor Consider that the line is terminated with a reactor, and a step voltage is applied. We can calculate
the expressions for transmitted and reflected voltages as follows:
We can write Z2 = Ls in Laplace transform and let Z1 = Z. Then
the reflection coefficient is:
ρL =
(s − Z / L )
(s + Z / L )
(4-43)
The reflected wave is:
V ′(s) =
(s − Z / L ) V
(s + Z / L ) s
1
2
= − +
s s + Z /L
(4-44)
Taking inverse transform:
V ′ = [− 1 + 2e −( Z /L )t ]Vu(t ), where u(t) is a step function. (4-45)
The voltage of the transmitted wave is:
V ′′(s) = (1 + ρ L ) V (s)
=
2V
(s + Z /L)
(4-46)
Thus:
V ′′ = 2Ve −( Z / L )t
(4-47)
The voltage across the inductor rises initially to double the incident voltage and decays exponentially.
Line Terminated in a Capacitor Here we write Z2 = 1/Cs
The reflection coefficient is:
1
−Z
Cs
1 − CZs
ρL =
=
1 + CZs
1
+ Z
Cs
(4-48)
1 − CZs V 1 2CZs
= −
V
1 + CZs s s 1 + CZs
V ′ = [1 − 2e
−t /cz
(4-49)
Z
I 2 = Vb
Z11 1
Z12 1
Z
(4-52)
Now consider that one of the conductors is grounded, for example, a shield wire or sky wire on a transmission line. Then, the voltage
on the grounded conductor is zero.
Z12
I
V f 1 = Z11I f 1 + Z12I f 2
Z22 f 1
Z2
= I f 1 Z11 − 12
Z22
(4-53)
situation is shown in Fig. 4-8b. We know that the following relations are applicable:
And the transmitted voltage wave is:
(4-50)
From the expression of V″ in Eq. (4-50), the steepness of the front is
reduced and the voltage rises slowly in an exponential manner. The
capacitor behaves like a short circuit at t = 0, and will be charged
through line impedance Z. The voltage at junction will finally rise
to two times the incident voltage.
Two Parallel Conductors Connected to a Bus The voltage at
the bus will be the same, though the currents in the conductors will
differ. In the matrix form:
V = ZI
I1 = Vb
1 Z12
1 Z22
One Conductor Shorter Than the Other and Grounded This
]Vu(t )
V ′′ = 2[1 − e −t / cz ]Vu(t )
Therefore, with reference to Fig. 4-8a, if Vb is the bus voltage:
Vf 2 = 0 I f 2 = −
The reflected voltage wave is:
V ′(s) =
F I G U R E 4 - 8 (a) Two parallel conductors connected to a bus, propagation of waves; (b) two parallel conductors, one shorted to ground, other
continuous; propagation of waves.
(4-51)
Vt1 = V f 1 + Vr1 = Z11It1
Vt 2 = V f 2 + Vr 2 = 0
(4-54)
It1 = I f 1 + I r1
Then, it can be shown that:
Vr1 =
2
2
Z12
Z12
Vf1 −
Vf 2
2
2
2 Z11Z22 − Z12
2 Z11Z22 − Z12
Vt1 =
2 Z11Z22
2 Z11Z12
Vf1 −
Vf 2
2
2
2 Z11Z22 − Z12
2 Z11Z22 − Z12
(4-55)
(4-56)
74
CHAPTER FOUR
and
Ir 2 =
4-7
Z11 −Vr1
Z12 −Vr 2
(4-57)
Z
INFINITE LINE
When the line is terminated in its characteristic load impedance,
that is, R = Z0, the reflected wave is zero and the transmitted wave
is equal to the incident wave. Such a line is called an infinite line,
and the incident wave cannot distinguish between the termination
and the continuation of the line.
The characteristic impedance, also called surge impedance, is
approximately 400 Ω for overhead transmission lines, and its phase
angle may vary from 0° to 15°. For underground cables, the surge
impedance is much lower, approximately 1/10 of the overhead
lines.
4-7-1 Surge Impedance Loading
The surge impedance loading (SIL) of the line is defined as the power
delivered to a purely resistive load equal in value to the surge
impedance of the line.
SIL =
Vr2
(4-58)
Z0
For a 400-Ω surge impedance, the SIL in kW is 2.5 multiplied by
the square of the receiving-end voltage in kV. The surge impedance is a real number, and therefore the power factor along the line
is unity, that is, no reactive power compensation is required. The
SIL loading is also called the natural loading of the transmission line.
Practically, this loading is not achieved.
4-8
TUNED POWER LINE
In the long transmission line model, if the shunt conductance and
series resistance are neglected, then:
(4-59)
where l is the length of the line. This simplifies ABCD parameters
and the following relation results:
jZ0ω l LC
cos ω l LC
Vr
Ir
(4-60)
If:
(n = 1, 2, 3, ....)
(4-61)
and
I s = Ir
(4-62)
This will be an ideal situation to operate a transmission line; the
receiving-end voltage and currents are equal to the sending-end
voltage and current. The line has a flat voltage profile.
β=
2π f 2π
=
λ
v
Vr αl+ jβl Vr −αl− jβl
+ e
e
2
2
(4-64)
At l = 0, both incident and reflected waves are equal to VR /2.
As l increases, the incident wave increases exponentially, while the
reflected wave decreases. Thus, the receiving-end voltage rises.
Another explanation of this phenomenon is provided by considering the line capacitance lumped at the receiving end. On open
circuit, the sending-end current is:
Is =
Vs
1
jω Ll −
jω Cl
(4-65)
In Eq. (4-65) C is small in comparison with L. Thus, w Ll can be
neglected. We can write the receiving-end voltage considering only
the voltage drop in the series inductance of the transmission line:
= Vs (1 + ω 2CLl2 )
(4-66)
Vs ω 2CLl2 = Vs ω 2l2 /v2
(4-67)
where v is the velocity of propagation. Considering that the velocity
of propagation is constant, the receiving-end voltage rises as the
line length is increased.
Also from Eq. (4-60) the voltage at any distance x in terms of
sending-end voltage, with the line open circuited and resistance
neglected is:
Vx = Vs
cos β(l − x )
cos βl
(4-68)
and the current is:
Then:
Vs = Vr
Vs =
This gives a voltage rise at receiving end of:
Sinhγ l = sinh jω l LC = j sin ω l LC
ω l LC = nπ
FERRANTI EFFECT
As the transmission line length increases, the receiving-end voltage
rises above the sending-end voltage due to line capacitance. This is
called Ferranti effect. In a long line model, at no load (IR = 0), the
sending-end voltage is:
= Vs + Vsω 2CLl2
Coshγ l = cosh jω l LC = cos ω l LC
cos ω l LC
j
sin ω l LC
Z0
4-9
Vr = Vs − I s ( jω Ll)
γ = YZ = jω LC
Vs
=
Is
As 1/ LC is equal to the velocity of light, the line length l
is 3100, 6200, . . . mi or b = 0.116° per mile. The quantity bl =
electrical length of the line. The line length calculated earlier is too
long to avail this ideal property. This suggests that power lines can
be tuned with series capacitors to cancel the effect of inductance
and shunt inductors to neutralize the effect of line capacitance. This
compensation may be done by sectionalizing the line. For power
lines, series and shunt capacitors for heavy load conditions and
shunt reactors under light load conditions are used to improve
power transfer and line regulation.
Also, see Chap. 15 for flexible ac transmission system (FACTS)
controllers, which improve the performance of transmission lines
based on the concepts outlined here.
(4-63)
Ix = j
Vs sin β(l − x )
Z0 cos βl
Example 4-2
(4-69)
A 230-kV three-phase transmission line has
795 kcmil aluminum conductor steel reinforced (ACSR) conductors, one per phase, neglecting resistance, z = j0.8 Ω/mi, and y =
j5.4 × 10–6 siemens per mile. Calculate the voltage rise at the receiving end for a 400-mi long line.
MODELING OF TRANSMISSION LINES AND CABLES FOR TRANSIENT STUDIES
Using these expressions, Z0 = 385 Ω, b = 2.078 × 10–3 rad/mi =
0.119° per mile. bl = 0.119 × 400 = 47.6°, the receiving-end voltage rise from Eq. (4-68) is 48.3 percent and at 756 mi, one-quarter
wavelength it will be infinite.
Even a voltage rise of 10 percent at the receiving end is not acceptable as it may give rise to insulation stresses and affect the consumer
apparatus. Practically, the voltage rise will be more than calculated here.
As the load is thrown off, the sending-end voltage will rise before the
generator voltage regulators and excitation systems act to reduce the
voltage, further increasing the voltage on the line. It is imperative that
the transmission lines are compensated to control voltage excursions.
In the above example, the sending-end charging current is
1.18 per unit and falls to zero at the receiving end. This means that
the capacitive charging current flowing in the line is 118 percent of
the line natural load current.
4-10
SYMMETRICAL LINE AT NO LOAD
If we consider a symmetrical line at no load, with the sending-end
and receiving-end voltages maintained at the same level, these voltages have to be in phase as no power is transferred. Half the charging current is supplied from each end, and the line is equivalent
to two equal half-sections connected back-to-back. The voltage
rises at the midpoint, where the charging current falls to zero and
reverses direction. The synchronous machines at the sending end
absorb leading reactive power, while the synchronous machines at
the receiving end generate lagging reactive power (Fig. 4-9a, b, and c).
75
The midpoint voltage is therefore equal to the voltage as if the line
was half the length.
On loading, the vector diagram shown in Fig. 4-9d is applicable.
By symmetry, the midpoint voltage vector exactly bisects the sendingand receiving-end voltage vectors. The power factor angle at both
ends are equal but of the opposite sign. Therefore, receiving-end
voltage on a symmetric line of length 2l is the same as that of line of
length l at unity power factor load. From Eq. (4-60), the equations
for sending-end voltage and current for a symmetrical line can be
written with b l replaced with b l/2 = θ /2.
θ
θ
Vs = Vm cos + jZ0I m sin
2
2
θ
θ
V
I s = j m sin + I m cos
Z0
2
2
(4-70)
At the midpoint:
Pm + jQm = VmI*m = P
Qs = Img VsI*s = j
sin θ 2 Vm2
Z I −
2 0 m Z0
(4-71)
where P is the transmitted power. No reactive power flows past the
midpoint and it is supplied by the sending end.
Example 4-3 Consider a line of medium length represented by
a nominal P circuit. The impedances and shunt susceptances are
shown in Fig. 4-10 in per unit on a 100-MVA base. Based on the
given data, calculate ABCD parameters. Consider that 1 per unit
current at 0.9 power factor lagging is required to be supplied to
the receiving end. Calculate sending-end voltage, currents, power,
and losses.
1
D = A = 1 + YZ
2
= 1 + 0 . 5 [ j0 . 0538][0 . 0746 + j0 . 394]
= 0 . 989 + j0 . 002
1
C = Y 1 + YZ
4
= ( j0 . 0538)[1 + (− 0 . 0053 + j0 . 9 947 )]
= − 0 . 000054 + j0 . 0535
B = Z = 0 . 0746 + j0 . 394
Voltage at receiving bus is 1 < 0°. The receiving-end power is:
V2I*2 = (1 < 0 °)(I 2 < 25 . 8 °) = 0 . 9 + j0 . 436
The sending-end voltage is:
V1 = AV2 + BI 2
= (0 . 989 + j0 . 002)(1 < 0 °) + (0 . 0746
+ j0 . 394 )((1 < 25 . 8 °)
= 1 . 227 + j0 . 234
V1 = 1 . 269 < 14 . 79 °
The sending-end current is given by:
FIGURE 4-9
(a) Phasor diagram of a symmetrical line at no load; (b)
the voltage profile of a symmetrical line at no load; (c) charging current profile; (d) phasor diagram of the symmetrical line with reference to midpoint,
at no load.
I1 = CV2 + DI 2
= (− 0 . 000054 + j0 . 0535) + (0 . 989 + j0 . 0021)(1
1 < 25 . 8 °)
= 0 . 8903 − j0 . 3769
= 0 . 9668 < − 22 . 944 °
76
CHAPTER FOUR
FIGURE 4-10
Transmission line and load parameters for Examples 4-3 and 4-4.
The sending-end power is, therefore:
We can write:
V1I1* = (1 . 269 < 14 . 79 °)(0 . 9668 < 22 . 944 °)
Z = 0 . 0746 + j0 . 394
Y = 0 . 0538
= 0 . 971 + j0 . 7 5
The active power loss is 0.071 per unit and the reactive power
loss is 0.314 per unit. The reactive power loss increases as the load
power factor becomes more lagging.
The power supplied, based on known sending-end and receivingend voltages, can also be calculated from the equations:
[V12 − V1V2 cos(θ1 − θ 2 )g12 −[V1V2 sin(θ1 − θ 2]b12
a = 0.0136687 Np
b = 0.146235 rad
cosh γ = cosh α cos β + j sinh α sin β
−[1 . 269 sin (14.79°)]( − 2 . 450)
(4-72)
This gives the same result as calculated before. A dilemma of the
calculation is that for a given load, neither the sending-end voltage
nor the receiving-end current is known.
The sending-end reactive power is:
Y 2
V
2 1
= [11 . 269 sin 14 . 79 °] 0 . 464 −[1 . 2692 − 1 . 269 cos1
1 4 . 79 °]
Q12 = [−V1V2 sin(θ1 − θ 2 )]g12 −[V12 − V1V2 cos(θ1 − θ 2]b12 −
= (1 . 00009)(0 . 987362) + j(0 . 013668)(0 . 14571)
= 0 . 990519 < 0 . 1152 °
Sinh γ = sinh α cos β + j cosh α sin β
= (0 . 013668)(0 . 989326) + j(1 . 000
0 09)(0 . 14571)
= 0 . 146349 < 84 . 698 °
The sending-end voltage is:
V1 = cosh γ V2 + Z 0 sinh γ I 2
= (0 . 990519 < 0 . 1152 °)(1 < 0) + (2 . 73 < − 5 . 361 °)
× (− 2 . 450) − (0 . 0269)(1 . 269 )
2
= 0 . 75
From Eq. (4.17):
The hyperbolic functions cosh γ and sinh γ are given by:
= [1 . 26 92 − 1 . 269 cos(14 . 79 °)0 . 464
= 0 . 971
ZY = 0 . 021571 < 169 . 32 °
(4-73)
× (0 . 1463449 < 84 . 698 °)(1 < − 25 . 842 °)
= 1 . 269 < 14 . 73 °
The receiving-end active power is:
P21 = [−V2V1 sin(θ 2 − θ1 )] b12 +[V22 − V2V1 cos(θ 2 − θ1 )] g12
= 0.9
(4-74)
Also, receiving-end reactive power is:
1
I 2 = (sinh γ)V2 + (cosh γ)I 2
Z0
= (0 . 3663 < 5 . 361 °)(0 . 146349 < 84 . 698 °)
Y
Q21 = [−V2V1 sin(θ 2 − θ1 )] g12 −[V22 − V2V1 cos(θ 2 − θ1 )] b12 − V22
2
= [− 1 . 269 sin(− 14 . 79 °)] 0 . 464 −[1 − 1 . 269 cos(−
− 14 . 79 °)]
× (− 2 . 450) − (0 . 0269)(1)
= 0 . 436
The result is fairly close to the one calculated with P model.
The sending-end current is:
(4-75)
Example 4-4 Example 4-3 is repeated with long line model and
the results are compared.
+ (0 . 990519 < 0 . 1152 °)(1 < − 25 . 84 °)
= 0 . 968 < − 22 . 865 °
Again this result is close to the one calculated with P model. The
parameters of the transmission line shown in this example are for a
138-kV line, length of approximately 120 mi. For longer lines, the
difference between the calculations using two models will diverge.
These two examples, though on power transmission, do underline some voltage problems, reactive power supply, and loss, which
play a role in the transient analysis.
MODELING OF TRANSMISSION LINES AND CABLES FOR TRANSIENT STUDIES
4-11
Similarly, we can write the current equation in the matrix form:
LOSSLESS LINE
To eliminate frequency and delay distortion in a line, a and velocity
of propagation should be independent of frequency. As the velocity
of propagation is given by:
ω
v=
β
(4-76)
(4-77)
then, from Eq. (4-17)
β = ω LC
(4-78)
and the velocity of propagation is:
v=
1
(4-79)
LC
This will be the same for all frequencies. Also, from Eq. (4-17):
α = rsc g sh
(4-80)
which is also independent of frequency.
Such a hypothetical line is not practical. From Eq. (4-77), it
requires a very large value of inductance L as shunt conductance gsh
is small. If gsh is intentionally increased, then a increases, that is, the
attenuation increases. To reduce rsc, the size and cost of conductors
increase beyond economical limits, so the hypothetical results cannot be achieved in practice.
4-12
GENERALIZED WAVE EQUATIONS
It is recommended that the reader studies App. D on transmission
line constants before continuing with the rest of this chapter.
A lossless line can be represented by its self-inductance, mutual
inductance, capacitance to ground, and mutual capacitances. We
had arrived at the inductance and capacitance matrices of threephase transmission lines in App. D. The following is the alternative
approach.
The voltage drop across a section of the line can be written as:
∂I
∂I
∂I
D V1 = D x L11 1 + L12 2 + + L1n n a
∂t
∂t
∂t
∂I
∂I
∂I
D Vn = D x L n1 1 + L n 2 2 + + L nn n
∂
∂
∂t
t
t
L12
L 22
.
Ln2
(4-82)
. L1n
. L2 n
. .
. L nn
∂I
∂V
= −C
∂x
∂t
(4-85)
The capacitance matrix for a three-phase line can be written as
(App. D):
C11 −C12
C123 = −C21 C22
−C31 −C32
−C13
−C23
C33
(4-86)
From Eqs. (4-85) and (4-86):
∂2V
∂2V
= LC 2
2
∂x
∂t
(4-87)
For a perfect earth, we can write:
LC =
I
=M
v2
(4-88)
For kth conductor:
∂2Vk 1 ∂2Vk
=
∂ x 2 v2 ∂ t 2
(4-89)
This shows that the wave equation of each conductor is independent of the mutual influence of other conductors in the system—
a result which is only partially true. However, for lightning surges
and high frequencies, the depth of the current image almost coincides with the perfect earth. This may not be true for switching
surges. The M matrix in Eq. (4-88) is not a diagonal matrix. We will
use decoupling to diagonalize the matrix (App. D). With respect to
transmission lines, this is called modal analysis as it gives different
modes of propagation.
4-13
MODAL ANALYSIS
V = TVm
(4-81)
The matrix L for n-phase line is:
L11
L21
L=
.
L n1
(4-84)
Consider a matrix of modal voltages Vm and a transformation matrix T,
transforming conductor voltage matrix V:
or in the matrix form as:
∂I
∂V
= −L
∂t
∂x
∂V
∂ I1 ∂ V1
∂V
= C
+ C12 2 + + C1n n
∂ x 11 ∂ t
∂t
∂t
∂V
∂ I n ∂ V1
∂V
+ Cn 2 2 + + Cnn n
= Cn1
∂t
∂t
∂t
∂x
or in the matrix form:
b should be made a direct function of frequency.
If we make:
Lg sh = Crsc
77
(4-83)
(4-90)
Then, the wave equation can be decoupled and written as:
∂2Vm
∂2Vm
−1
=
T
LC
T
[
]
∂t2
∂x 2
2
∂V
= T −1M −1T 2m
∂t
∂2Vm
=λ
∂t2
(4-91)
For decoupling matrix, λ = T −1M −1T must be diagonal. This is
done by finding the eigenvalues of M from the solution of its characteristic equation. The significance of this analysis is that for n
conductor system, the matrices are of order n, and n number of
78
CHAPTER FOUR
FIGURE 4-11
Modes of propagation for three-conductor and two-conductor lines.
modal voltages are generated which are independent of each other.
Each wave travels with a velocity:
vn =
1
λk
k = 1, 2, ..., n
(4-92)
and the actual voltage on the conductors is given by Eq. (4-90).
For a three-phase line:
1 1 1
T = −1 0 1
0 −1 1
(4-93)
Figure 4-11 shows modes for two-conductor and three-conductor lines. For a two-conductor line, there are two modes. In the line
mode, the voltage and current travel over one conductor returning
through the other, none flowing through the ground. In the ground
mode, modal quantities travel over both the conductors and return
through the ground. For a three-conductor line, there are two line
modes and one ground mode.
The line-to-line modes of propagation are close to the speed of
light and encounter less attenuation and distortion compared to
ground modes. The ground mode has more resistance, and hence
more attenuation and distortion. The resistance of the conductors
and earth resistivity plays an important role.
The ground component Vg of a three-phase line carrying surge
voltages to ground of V1, V2, V3 is defined as:
1
Vg = (V1 + V2 + V3 )
3
(4-95)
Thus, all three components of the model voltages are present on
the struck conductor, and one-line mode voltage is missing on conductors 2 and 3. This shows that the charge on phase a is balanced
by the charges on phases b and c. Figure 4-12 shows the resolution
into components and the distortion produced after the components
have traveled some distance.
The calculation of the transmission line parameters for mode
propagation becomes important, based on the collected transmission line data. We will illustrate these calculations in Example 4-6.
Further analysis of the transition points in multiconductor systems
can be made using modal analysis.
4-13-1 Distortion Caused by Mode Propagation
Mode propagation gives rise to further distortion of multiconductor
lines. For voltages below corona inception voltage (Sec. 4-15), the
velocity of propagation of the line components is close to the velocity of light and the distortion is negligible. For ground currents, the
charges induced are near the surface, while the return current is well
below the surface, at a depth depending on the frequency and earth’s
resistivity. For a perfectly conducting earth, the current will flow at
the earth’s surface at a velocity equal to the velocity of light.
V1 = Vm1 + Vm2 + Vg
V2 = −Vm1 + 0 + Vg
V3 = 0 − Vm2 + Vg
(4-94)
FIGURE 4-12
Mode propagation and distortion on a balanced
three-phase line: 1. Line components; 2. ground components; 3. total
voltage wave.
MODELING OF TRANSMISSION LINES AND CABLES FOR TRANSIENT STUDIES
4-13-2
Integration gives the change of current along the line:
Approximate Long-Line Parameters
Regardless of voltage, conductor size, or spacing of a line, the series
reactance is approximately 0.8 Ω/mi and the shunt-capacitive reactance is 0.2 MΩ/mi. This gives b of 1.998 × 10–3 per mile or 0.1145°
per mile. These may be considered for the line mode and will vary
over large values with respect to the mode of propagation. It is necessary to calculate parameters accurately for the study of transients
with respect to each mode of propagation. The numbers stated here
provide “ball-park” figures.
4-14
DAMPING AND ATTENUATION
We alluded to the phase and frequency distortion and that an ideal
lossless line with LG = CR is not practical. The decrease in the magnitude of the wave as it propagates is called attenuation. The current and
voltage wave shapes become dissimilar, though these may be the same
initially. Attenuation is caused by the energy loss in the line and the
distortion is caused by change in the inductance and capacitance of
the line. The constant surge impedance assumes that the wave shapes
are not altered. The conductor resistance is modified by skin effect and
the changes in the ground resistance. The changes in the inductance
occur because of nonuniform distribution of currents and proximity
to steel structures, that is, line supports. The capacitance can change
due to change in the insulation nearest to the line supports.
The energy stored in the traveling wave is the sum of the electrostatic and electromagnetic energies:
1
1
E = CV 2 + LI 2
2
2
(4-96)
As the two components of the energy are equal:
1
1
CV 2 = LI 2
2
2
(4-97)
L
V
=
= Z0
I
C
∫ Edx = C ∫ V
2
dx = L ∫ I dx
2
(4-98)
The power of the pulses that pass through a given section is given
by the product of energy content and the velocity of propagation:
W = Etotal v = I 2 L ×
1 R
I = I 0 exp − + Z0G x
Z
2
0
(4-102)
where I0 is the amplitude of the current pulse at any selected arbitrary origin or starting point. For the voltage pulse, the required
change along the line is:
1 R
V = V0 exp − + Z0G x
Z
2
0
(4-103)
The G of the overhead lines is small, that is, the transmission
lines have high insulation resistance, and if we ignore G:
V
I
= = e −Rx / 2 Z0
V0 I 0
(4-104)
V0 and I0 are the voltage and current pulses at an arbitrary selected
origin. Equation (4-103) shows that damping is directly proportional
to the resistance and inversely proportional to the surge impedance.
Therefore, it is much higher in cables than in overhead lines.
For the rapidly propagating pulses, the resistance of the conductors is increased above dc resistance values due to skin effect
(App. D).
Example 4-5 Calculate the attenuation in an overhead line with
a resistance of 0.5 Ω/km, and also in cables of the same cross section, length in each case being 200 km. The surge impedance of the
overhead line is 400 Ω and that of the cable is 50 Ω.
For the overhead line, the attenuation is:
e −0.5 × 200 / 400 = 0 . 778
For the cable, it is:
where Z0 is the surge impedance. The total energy content is then
estimated by integration over the length of the line:
Etotal =
79
1
LC
= I 2 Z0 =
V2
Z0
(4-99)
For the same voltage, the power is much higher in cables than
in overhead lines, as the cables have a much lower surge impedance (50 Ω approximately) compared to overheads lines (400 Ω
approximately). The surge impedance of paper-insulated high-voltage (HV) cables is higher than 50 Ω, as indicated earlier.
These equations have not considered the resistance and insulation resistance (G), and thus the waves are propagated without loss.
If we consider R = series resistance of the line and G = the conductance of the line, then the heat loss (energy loss) is given by:
dW = I 2 Rdx + V 2Gdx
= I 2 (R + Z 20G)dx
(4-100)
From Eqs. (4-100) and (4-101):
di 1 R
= + Z0G dx
i 2 Z0
(4-101)
e −0.5 × 200 / 50 = 0 . 135
4-15
CORONA
Corona discharges follow an avalanche process and an ionization
process is set in. As the voltage increases, and the surrounding air
is ionized, the energy is supplied until the critical field intensity
for the air is reached. Once this level is reached, the field intensity
cannot increase anymore with the rise in voltage. After the crest of
the voltage is reached and the wave starts trailing, the space charge
does not diminish or vanish. It is not the intention to go into the
streamer theory, corona modes, except to consider some aspects
of corona with reference to HV transmission lines. The impact of
corona discharges has been recognized since the early days of the
electric power transmissions. These effects can be summarized as:
Corona Noise A pulsating sine wave is generated from the discharge
due to increase in pressure of the air and is audible in the immediate
vicinity of the HV lines. Analyses to predict levels of audible noise
consider A-weighted sound level during rain, L50, which means that
the level is exceeded 50 percent of the time during rain; and L5, which
is the level exceeded 5 percent of the time during rain. A comparison
of the audible noise formulas that have been developed in various
countries is included in the IEEE Task Force Report of 1982.2
Modal analysis provides a convenient approach to evaluate noise
currents on line conductors. First, the noise currents are transposed
into their modal components, which propagate without distortion
along the line conductors at their own velocity.
Im =
1
α
M −1 IL
(4-105)
80
CHAPTER FOUR
where a is the real part of the propagation constant, as defined in
Eq. (4-15). From the model currents, the line currents are obtained by
reverse transformation. The magnetic and electrical fields produced
by noise currents in the conductors can then be calculated. Moreau and
Gary obtained good correlation between the calculated and experimental results.3 They used Clarke’s transformation for the model
matrix M. (Clarke’s transformation is discussed in (Sec. 4-16-2.)
Radio and Television Noise The noise is caused by complete
electrical discharges across small gaps (insulators, line hardware,
which should be corona-free), and by partial discharges. Gap discharges may generate sharp pulses with nanosecond rise time and
may interfere with TV reception.
Ground-Level Electric Fields The electric fields in the vicinity
of a transmission line are the superimposition of three-phase conductors and the conducting earth, represented by the image charges
below the earth equal to the height of the conductors. The effects
on humans is due to discharges from the objects typically insulated
from ground, like vehicles, buildings, and fences, which become
electrically charged due to induction from the line.
Ground-Level Magnetic Fields Magnetic field couplings affect
objects which parallel the line for a distance. The parallelism of pipelines is a major concern, which is discussed in Chapter 21.
4-15-1 Corona Loss
Corona loss is described in terms of energy loss per unit length of
the line. These may be negligible under fair-weather conditions, but
may reach values of several hundred kW/km of line length during
foul-weather conditions. The foul-weather losses are evaluated in
test cages under artificial rain conditions. Peek’s formula for corona
loss per unit length of the line is:
Ploss
K
= (V − Vc )2
n
(4-106)
where K is a constant, which relates crest voltage in volts to energy
loss in Joules per foot per half cycle. For HV transmission lines, it is
of the order of 4 × 10–12. The factor n may be considered = 2.4 for
the positive waves and n = 4 for the negative waves.
Corona will reduce the crest of the voltage wave limiting it to the
critical corona voltage. The voltage above the corona voltage will
cause power loss by ionizing the surrounding air. This increases
the effective diameter of the conductor, which in turn increases the
capacitance of the conductor and velocity of propagation.
The corona inception voltage is given by:
Vc =
2π rε 0 Ec
C × 106
(4-107)
where r is the radius of conductor in m, ε 0 is the permittivity of
free space, Ec is the corona inception electric field in kV/m on the
conductor surface, and C is the capacitance of the overhead line
in µF/m. The corona onset voltage is, generally, 30 to 40 percent
above the rated operating voltage.
Using Peek’s equation, Vc can be expressed as:
0. 3
1 . 66 × 10−3 nmkd2 / 3r 1 +
r
Vc =
kh C
(4-108)
where n is number of subconductors in a bundle, m is conductor
surface factor which varies from 0.7 to 0.8, kd is relative air density,
r is conductor radius in cm, C is capacitance as above in µF/m,
and kb is ratio of maximum-to-average surface gradient for bundle
conductors. This is given by the expression:
π r
kb = 1 + 2(n − 1)sin
n A
(4-109)
where A is the distance between adjacent subconductors in cm.
FIGURE 4-13
(a) Voltage waveshapes on the surged conductor at
various distances from the origin; (b) voltage waveshape on parallel unsurged
conductor. Positive polarity wave applied to a 2.0-in diameter ACSR.
As the surge voltage is much higher than the corona inception
voltage, the corona discharge adds to the energy losses and retards
the portion of the voltage wave front above Vc. A sort of shearing
back of the voltage wave occurs, as shown in Fig. 4-13.
A voltage wave can be divided into sections of voltage levels
of increasing magnitude, each section corresponding to a different
velocity of propagation. Prior to ionization, the velocity of propagation is given by, say, Cn, and above inception of corona voltage by Cd,
a variable capacitance depending on the voltage and corona inception level. As Cd increases with voltage, the voltage elements above
the corona voltage will be retarded behind the voltage elements of
lower voltage level. This will flatten the wave. Figure 4-13a shows
the voltages on the surged conductor and Fig. 4-13b shows the
voltages on parallel unsurged conductors. A point above the corona
inception voltage will be retarded by:
1 1
td = l −
vd vc
(4-110)
where vc is the velocity of propagation with capacitance Cn and vd is
the velocity of propagation with Cd.4 While Cn is calculated by conventional expressions, Cd is much dependent on the polarity of the
wave, the effect of positive polarity wave being significantly higher
than that of negative polarity.
Skilling and Dykes5 give the following expression for retardation
and the distance traveled:
Dt
k Vc
=
1 −
D vcCn Vd
(4-111)
MODELING OF TRANSMISSION LINES AND CABLES FOR TRANSIENT STUDIES
81
in the ground mode of overhead lines (0.2 to 0.25 km/µs) is lower
than the propagation speed of approximately 0.3 km/µs in the line
mode. Except for lightning overvoltages, the earth wires can be
removed and the impedance matrix is reduced to a 3 × 3 matrix.
For group III, lightning surge studies, earth wires must be
included and the transformations to decouple n-conductors to
n-equivalent single-conductor system are necessary; see App. D.
For group IV transients, it is adequate to represent an overhead line
connected to gas-insulated substations (GIS) through its surge impedances. Within GIS, each small section is modeled; see Chap. 18.
Length of Line A line can be modeled with n P sections, n
depending on the frequency of transient oscillation. The highest
frequency that can be attained by a P section is the natural frequency of one individual element representing the total length:
lsection = ltotal/n. With L = nL′ and C = nC′, this gives:
f max =
1
2π n L′C′ / 2
v
4 . 44 n
=
(4-113)
Or, in other words, if a maximum frequency fmax is to be represented, the maximum length of the section should be:
n≤
F I G U R E 4 - 1 4 Slope reduction of traveling waves. 1, 2: 2-in diameter SCA (steel-cored aluminum conductor). 3, 4: 0.927 SCA. 1, 3: negative
polarity surges. 2, 4: positive polarity surges.
where Dt is the retardation, D is distance traveled, Vd is voltage
above corona voltage Vc, vc is propagation velocity below Vc in m/s,
Cn is capacitance of conductor in µF/m, below corona voltage Vc,
and k is empirical constant determined by field tests.
Figure 4-14 gives the function Dt /D versus conductor voltage
without calculating the rest of Eq. (4-111). The following approximations can be applied with respect to front time prolongation and
crest attenuation.
Front Time Prolongation Below Vc: 3 percent per km for first
5 km; 1.2 to 2 percent per km for the next 30 km.
Above Vc: 0.6 µs/km for negative surges and 1.2 µs/km for positive surges.
Crest Attenuation Below Vc: 3 percent per km for the first
5 km; 1.2 to 2 percent per km for the next 30 km.
Above Vc: Foust and Menger formula6 can be used:
Vdcrest =
V0crest
(k′DV0crest + 1)
v
4 . 44 f max
(4-114)
The considerations of rise time, attenuation, and phase shift also
apply. In case the first capacitance of the P section is switched in parallel with system capacitance, spurious oscillations may arise and a
series resistance equal to the surge impedance is connected in series.
4-16-1
EMTP Models
EMTP permits a number of transmission line models for the transient studies. The P model can be used for steady-state or frequency scan solutions and is not valid for time-domain solutions.
The model data produced is in terms of a Y-matrix representation
that includes series and shunt branches.
The constant parameter (CP) model is a frequency-independent
transmission line model for the wave equation of the distributed
parameter line. It is not accurate for zero sequence currents or
high-frequency phenomena. It can be successfully used for problem analysis with limited frequency dispersion.
J. Marti’s frequency-dependent model7 is more accurate than the
CP model, though computationally slower. It takes into account the frequency dependence of series resistance and inductance of the line. This
model is also based on modal decomposition techniques.
4-16-2
Clarke’s Transformations
EMTP uses the following transformation matrices. The Clarke’s ab0
transformation matrix for m-phase balanced line is:
(4-112)
1
where Vdcrest and V0crest are the crest voltages at the origin and after
travel of distance D in km, respectively. k′ is a constant which
increases from 0.0001 for waves of approximately 20 µs half-time
to 0.0002 for waves of about 5 µs half-time. For chopped waves, it
can be higher up to 0.00045.
4-16 TRANSMISSION LINE MODELS FOR
TRANSIENT ANALYSIS
With the earlier background, we return to Table 4-1. CIGRE
guidelines describe models for TNA analysis and digital computer
simulations; the TNA models are not discussed here. TNA models,
however, cannot be used for group III and group IV surges (fast
front and very fast front surges). For digital computer simulation,
mathematical transformations that allow different modes of propagation in the low-frequency range (groups I and II) are required.
This is so because the propagation speed of electromagnetic waves
m
1
m
1
Ti =
m
1
−
1
2
1
6
1
2
0
−
6
2
6
.
.
.
.
.
0
.
.
.
1
.
.
.
.
.
.
0
0
.
m
1
j( j − 1)
1
j( j − 1)
.
−( j − 1)
j( j − 1)
0
.
0
.
.
1
m(m − 1)
1
m(m − 1)
.
.
.
.
.
.
.
.
−(m − 1)
.
m(m − 1)
(4-115)
82
CHAPTER FOUR
Applying this m-phase transformation to the matrices of m-phase
balanced lines will produce a diagonal matrix of the form:
Z g −m
Z L −m
(4-116)
.
Z L −m
Zg–m is the ground mode matrix and Zl–m is the line mode matrix.
The solution becomes simpler if m-phase transmission line equations (M-coupled equations) can be transformed into M-decoupled
equations. Many transposed and even untransposed lines can be
diagonalized with transformations to modal parameters based on
eigenvalue/eigenvector theory. The phase differential equation:
d 2Vph
= Z ph Yph Vph
dx 2
(4-117)
becomes:
d 2Vmode
= ΛVmode
dx 2
(4-118)
where:
Λ = Tv−1Z ph YphTv
(4-119)
The diagonal elements of Λ are eigenvalues of matrix product
Z ph Yph and Tv is the matrix of eignvectors or modal matrix of that
matrix product. Some methods of finding eigenvectors and eigenvalues are QR transformation and iteration schemes8; see App. G.
Similarly, for current:
Imode = Ti Iph
(4-120)
2
d Vmode
= ΛVmode
dx 2
(4-121)
Ti = [Tvt ]−1
(4-122)
For a three-phase line:
1
1
3
1
Ti =
−
3
1
−
0
3
(4-123)
6
2
6
We can write:
Z012 = Ti−1ZabcTi
(4-124)
Then:
1
Z123 =
3
1
3
1
3
=
1
2
1
−
−
Z s + 2M u
0
0
6
1
2
0
1
−
6
2
−1
1
1
Zs
Mu
Mu
Mu
Zs
Mu
Mu
Mu
Zs
3
1
3
1
3
6
0
Zs − Mu
0
(4-126)
Table 4-1 qualifies the representation of transposed lines. For
this case, modal decoupling is still possible; however, transition
matrices Ti and Tv are different for each line configuration and are a
function of frequency.
Example 4-6 Consider the following parameters of a 400-kV
transmission line:
Phase conductors: ACSR, 30 strands, 500 kcmil, resistance at
25°C = 0.187 Ω/mi, resistance at 50°C = 0.206 Ω/mi, Xa =
0.421 Ω/mi, outside diameter = 0.904 in, GMR = 0.0311 ft.
Ground wires: 7#8, 115.6 kcmil, 7 strands, resistance at 25°C =
2.44 Ω/mi, resistance at 50°C = 3.06 Ω/mi, Xa = 0.749 Ω/mi,
outside diameter = 0.385 in, GMR = 0.00209 ft.
Line configuration: Phase conductors, flat formation, height
above ground = 108 ft. Two ground wires, height above ground =
143 ft. Spacing between the ground wires = 50 ft.
Other data: Soil resistivity = 100 Ω/m, tower footing resistance =
20 Ω, span = 800 ft.
The calculated modal parameters for a CP, balanced line using
EMTP routine are shown in Fig. 4-15. Note that this table shows
two sets of parameters, one at 3543 Hz and the other at 60 Hz. The
CP model will be fairly accurate up to 3543 Hz.
4-16-3
Frequency-Dependent Model, FD
The propagation constant can be defined as the ratio of the receivingend voltage to the source voltage for an open-ended line if the line
is fed through its characteristic impedance (Fig. 4-16a). Then there
will be no reflection from the far end. In this case, Vm + ZcImk = Vs .
We can write the receiving-end voltage at k as:
(4-127)
ω = exp(−γ l)
6
1
2
ˆ
Y = Tv−1Y Tv
Vk = Vs A(ω )
1
2
1
In equation 4-125, Zs is self impedance and Mu is neutral impedance. In App. D, we had the same result using symmetrical components. Similarly for the shunt elements:
0
0
Zs − Mu
−
1
2
1
6
1
2
0
−
6
2
6
(4-125)
If a unit voltage from dc to all frequencies is applied at the
source end, then its time response will be unit impulse, infinitely
narrow (area = 1.0), and integral of voltage = unit step (Chap. 2).
We can write time response, a(t), to a unit impulse as inverse Fourier transform of A(w)[ A(ω ) = e −γ l]. This will not be attenuated and
no longer infinitely narrow. The impulse response for a lossless line
is unit impulse at t = t, with area 1.0. Setting V source = 1.0 in
Eq. (4-127) means that A(w) transformed into time domain must
be an impulse, which arrives at the other end k if the source is a
unit impulse.
The history term Vm /Zc + Imk at t – τ is picked up and weighted
with a(t) (App. G.) This weighting at the other end of line is done
with convolution integral:
τ =max
hist propagation =
∫
τ =min
im−total (t − u )a(u )dt
(4-128)
which can be evaluated with recursive convolution. Im-total is the sum
of the line current Imk and a current which will flow through characteristic impedance if a voltage Vm is applied to it. The approximation of Zc, a frequency-dependent impedance, is done with a
Foster-I-R-C network, Fig. 4-16b. Applying trapezoidal rule of integration, App. G, each RC block is a current source in parallel with
MODELING OF TRANSMISSION LINES AND CABLES FOR TRANSIENT STUDIES
FIGURE 4-15
Calculated modal parameters of the transmission line described in Example 4-6, EMTP calculation routine.
an equivalent resistance. Summing these up, a frequency dependent line is represented as shown in Fig. 4-16c. J. Marti9 shows that
it is best to sum up A(w) and Z(w) in the frequency domain.
A(s) = e −sτ min k
(s + z1 )(s + z 2 )(s + z n )
(s + p1 )(s + p2 )(s + p n )
(4-129)
From Chap. 3, partial fractions can be used and the time response is:
a(t ) = [k1e − p1 (t−τ min ) + k2e − p2 (t−τ min ) + + kme − pm (t−τ min )] for t ≥ τ min
= 0 for t < τ min
83
(4-130)
The weighting factor is used to calculate the history term in each
time step. Similar expression of a transfer function of poles and
zeros for Zc is applicable.
Z c (s) = k
(s + z1 )(s + z 2 )(s + z n )
(s + p1 )(s + p2 )(s + p n )
(4-131)
The success depends on the quality of approximation for
A(w) and Zc(w). J. Marti used Bode’s procedure for approximating the magnitudes of the functions. The M-phase lines, any of the
M-modes can be specified as frequency dependent or with lumped
resistances or distortionless. Field tests have verified the accuracy
of calculations.10
Figure 4-17 shows the comparative simulation results of a
320-mi line, a dc voltage of 10 V connected to the sending end
of the line, receiving end terminated with a shunt inductance of
100 mH, R = 0.0376 Ω/mi, L = 1.52 Ω/mi, and C = 14.3 nF/mi.
The simulation results with P sections (8 and 32) and distributed parameters are shown. Note the spurious oscillations due to
lumpiness.
84
CHAPTER FOUR
FIGURE 4-16
To explain J. Marti’s frequency-dependent line model (FD) in EMTP: (a) a voltage source connected through matching impedance to
node m; (b) RC network; (c) circuit with equivalent resistance after applying implicit integration.
FIGURE 4-17
Comparative response of a transmission line with P sections (8 and 32) and CP model. See text.
MODELING OF TRANSMISSION LINES AND CABLES FOR TRANSIENT STUDIES
Example 4-7 Consider a three-phase 400-kV, 200-mi long line
model, as arrived in Example 4-6, energized from a three-phase
source ( Z + = 0 . 3856 + j5 . 776 Ω, Z0 = 0 . 5245 + j6 . 805 Ω), by
closing an ideal switch at t = 0, at the peak of phase a voltage. The
receiving end is open-circuited. The EMTP simulation of voltage
profile at the sending and receiving end is shown in Fig. 4-18a and
b, respectively. The receiving-end voltage approximately doubles.
Example 4-8 This example models a lightning surge of 1.2/50 µs,
500 kV, which impacts phase a of a 400-kV transmission line at
1000’ away from the receiving-end substation and the receiving end
is open. The 400-kV line has two ground wires and a CP model is
used. A description of 1.2/50 µs waveshape is provided in Chap. 5.
Figure 4-19a shows the surge voltages at the receiving end of the
line. The phase a voltage rises to approximately 920 kV peak. Voltages on coupled phases b and c are also shown. Figure 4-19b shows
the surge voltages on the ground wires at the receiving end.
FIGURE 4-18
4-17
85
CABLE TYPES
Extruded dielectric (XD), also called solid dielectric—principally
cross-linked polyethylene (XLPE) cables—have been used up to 500 kV.
These are replacing pipe insulated cables and oil-filled paperinsulated cables because of lower costs and less maintenance.
Extruded cables include ethylene-propylene rubber (EPR) and lowdensity polyethylene (LLDPE), though XLPE is the most common
insulation system used for transmission cables. The XD cables also
have a lower capacitance compared to the paper-insulted cables.
In the United States, though XD cables are popular for the new
installations, approximately 70 percent of circuit miles in service
are pipe-type cables. Triple extrusion (inner shield, insulation,
and outer conducting shield) processed in one sealed operation is
responsible for the development of XLPE cables for higher voltages.
Also, a dry vulcanization process with no steam or water is used in
the modern manufacturing technology.
(a) Simulated three-phase receiving-end voltage transients, Example 4-7; (b) three-phase sending-end voltage transients, Example 4-7.
86
CHAPTER FOUR
× 105
Receiving end phases a, b, and c
10
5
0
–5
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
t (ms)
FIGURE 4-19
2
(a)
(a) Simulated surge voltage transients at the receiving end, Example 4-8; (b) voltage transients on the ground wires.
An EHV XLPE construction from inside to outside follows:
■
Semiconducting tapes
■
■
Laminated aluminum tape (water vapor diffusion barrier)
■
Outer polyethylene sheath
Copper or aluminum conductor which may be sector
shaped
■
Carbon paper, and inner extruded semiconducting shield
■
XLPE insulation
■
Outer semiconducting extruded screen
■
Semiconducting tapes
■
Copper screen with counter helix
■
Layer of swelling material, longitudinal water barrier; the
XD cables are proven to be sensitive to moisture, so moisture
barriers are used
Over the course of years, the reliability of XLPE cables has
increased, costs have decreased, and electrical stresses have increased,
allowing construction of XLPE cables to be applied to high voltages.
Low-pressure oil-filled cables, also called self-contained liquidfilled systems (SCLF), were developed in 1920 and were extensively
used worldwide until 1980, while in the United States, pipe-type
cables (described next) were popular. There are many miles in
operation at 525 kV, both land and submarine cables. The stranded
conductors are formed to form a hollow duct in the center of the
conductor. These may be wrapped with carbon paper, nonmagnetic
MODELING OF TRANSMISSION LINES AND CABLES FOR TRANSIENT STUDIES
steel tape, and conductor screen followed by many layers of oil-filled
paper insulation. Insulation screen, lead sheath, bedding, reinforcement tapes, and outer polymeric sheath follow next. When the cable
heats up during operation, the oil flows through the hollow duct in
an axial direction into oil reservoirs connected with the sealing ends.
The oil reservoirs are equipped with gas-filled flexible-wall metal
cells. The oil flow causes the cells to compress, thus increasing the
pressure. This pressure forces the oil back into the cable.
High-pressure fluid-filled (HPFF) cables have been a U.S. standard. The system is fairly rugged. A welded cathodically protected
steel pipe, typically 8.625 or 10.75 in optical density, is pressure
and vacuum tested, and three mass-impregnated cables are pulled
into the pipe. The cable consists of copper or aluminum conductors, conductor shield, paper insulation, insulation shield, outer
shielding, and skid wire for pulling cables into the pipe. The pipe
is pressurized to approximately 200 psig with dielectric liquid to
suppress ionization. The expansion and contraction of the liquid
requires large reservoir tanks and sophisticated pressurizing systems. Nitrogen gas at 200 psi may be used to pressurize the cable
at voltages up to 138 kV.
To state other constructions, mass-impregnated nondraining
cables (MIND) are used for HVDC circuits. Superconductivity
using liquid helium at 4 K has been known and, in the last couple
of years, has produced high-temperature superconductors (HTS).
These use liquid nitrogen temperatures (80 K).
Comparing with power lines, some advantages are:
■
Environmentally little or no visual impact, no electric
fields or low magnetic fields, high safety, no external corona
discharges
■
Not effected by weather conditions, like storm, snow, fog,
or dust
■
Low maintenance, lower power losses, less right of the way
compared to power lines
■
Fewer faults, higher short-term overload capability, and
reliability
Conversely, a variety of problems are associated with long
underground cables. The charging current of the cables is high due
to higher capacitance. At high voltages, this becomes important,
and reactive power compensation should be carefully considered.
The charging current is given by 2π fCVlg , where Vlg is the lineto-ground voltage. A relatively high voltage can occur at the open
end when a cable is connected to a relatively weak electrical system.
TA B L E 4 - 3
Another potential problem can be self-excitation of a synchronous
machine connected to the far end.
Temporary overvoltages can occur when a cable is switched with
a transformer. These are all related to large cable capacitance. Shunt
reactors are commonly used to compensate for cable capacitance.
These need to be properly sized to prevent steady-state and transient
overvoltages. The risk of overvoltages will be more under light load
conditions. Table 4-3 compares the electrical characteristics of cables
versus that of 230-kV overhead lines.11
4-17-1
Cable Models
Appendix D contains calculation routines for cable constants. The
cable models for transient analysis depend on the cable construction and also on the geometry of installation, which become all
the more important for submarine and pipe-type cables. A cable
can be represented in a transient analysis by its resistance, characteristic impedance, attenuation, or velocity of propagation, much
like a transmission line. A cable length can be considered short if
the surge traveling time is lower than about 30 percent of the time
constant of the main voltage rise time in the system. If a rectangular
pulse travels on an overhead line and then a short length of cable,
then the cable termination is seen more like a lumped capacitance.
If the cable is modeled accurately as a lossless distributed parameter
line, the buildup of the voltage has a staircase shape.
The P model can be used for steady-state or frequency scans
and is not valid for time-domain simulations. Spurious oscillations
may occur due to lumped models, though a number of sections
may be used (Fig. 4-2a).
The CP model assumes that R, L, C are constants, and they are
calculated at a certain frequency. The model considers R and L to
be distributed, while R is lumped at three places, at cable ends
and cable middle. The conductance is neglected. The model is a
lumped-impedance representation of the cable. The cross bonding
of sheaths of the cables presents yet other considerations, and each
subsection of the cable model has sheath bonding and grounding
connections. To model a cross-bonded cable accurately, it is divided
into sections, analogous to modeling a transposed transmission
line. Sheath bonding and sheath connections are made using EMTP
nodes. This modeling of short sections of 400 m or so requires a
very small time step, and a number of these major sections must
be connected to represent the entire cable length. This becomes
computationally intensive.
Similar to transmission lines, the models for cable systems can be
type FDQ, frequency-dependent, which provide an accurate representation of the distributed nature of all cable parameters, series and shunt
elements, and their frequency dependence of transition matrices Ti and
Typical Electrical Characteristics, 230-kV OH Lines versus
Underground Cables
PARAMETER
OVERHEAD LINE
UNDERGROUND XLPE
UNDERGROUND HPFF
Shunt capacitance, µF/mi
0.015
0.30
0.61
Series inductance, mH/mi
2.0
0.95
0.59
Series reactance, Ω/mi
0.77
0.36
0.22
Charging current, A/mi
1.4
15.2
Dielectric loss, kW/mi
0+
0.2
2.9
Reactive charging power, MVA/mi
0.3
6.1
12.1
Capacitive energy, kJ/mi
0.26
2.3
7.6
26.8
14.6
Surge impedance, Ω
375
Surge impedance loading limit, MW
141
87
1975
30.3
3623
88
CHAPTER FOUR
The self-impedance of loop 1 consists of three parts:
′ = Z′core-out + Z′core/sheath-insulation + Z′sheatth-in
Z11
(4-133)
With
Z′ core-out
= internal impedance of tubular core
conductor with return path
outside tube, through sheath
Z′ core/sheath-insulation = impedance of insulation between
core and sheath
Z′ sheath-in
= internal impedance of the tubular
sheath with return path inside the
tube
Z′22 = Z′sheath-out + Z′sheath/armor-insulation + Z′arrmor-in
Z′33 = Z′armor-out + Z′armor/earthinsulation + Z′earth
(4-134)
Analogous definitions apply. For shunt admittances:
FIGURE 4-20
Cross section of a single core self-contained cable,
with current loops. (Conductive layers are not shown.)
Tv in modal quantities. To create data for this model, it is necessary
to approximate with rational functions the characteristic admittance
Yc and the propagation function A = e −γ l for each mode of the cable
and the modal transformation matrix Q in the frequency domain.12
Chapter 7 has an example of FDQ model for a 400-kV cable.
The cable parameters of coaxial arrangements, as shown in
Fig. 4-20, are derived from coaxial loops.13 Loop 1 is formed by
core conductor and sheath as return, loop 2 by metallic sheath
and armor, and loop 3 by armor and earth or sea water. The series
impedance can be written as:
dV1
dx
′
Z11
dV2
−
= Z′21
dx
0
dV3
dx
FIGURE 4-21
′
Z12
Z′22
Z′32
0
Z′23
Z′33
I1
I2
I3
(4-132)
dI1
= (G1′ + jω C1′ )V1
dx
dI
− 2 = (G′2 + jω C′2 )V2
dx
dI 3
−
= (G′3 + jω C′3 )V3
dx
−
(4-135)
The calculation of all the parameters becomes involved.
Equation (4-132) is not yet supported in EMTP routine.
Example 4-9 A cable 5-km long, with a characteristic impedance of 50 Ω, propagation velocity 1E05 km/s is connected to a
1-km long line, with characteristic impedance 400 Ω, propagation
velocity 3E05 km/s, and open at the receiving end. The sending
end is impacted with a step of 10 kV, duration 10 µs. Figure 4-21
shows the voltages at the junction of the cable and transmission
line and also at the open end of the transmission line. Due to different speeds of propagation on cables and lines, multiple reflections
occur at the junction point; voltage escalation of 3.7 times occurs at
the open end of the transmission line.
Transients at the open end of a transmission line connected to a cable and also at the junction of cable and transmission line, Example 4-9.
MODELING OF TRANSMISSION LINES AND CABLES FOR TRANSIENT STUDIES
PROBLEMS
1. Write an equation relating R, L, G, and C for a lossless line.
Why can such a line not be constructed? What is an infinite
line? Why line compensation in the form of capacitors or
reactors is required?
2. A rectangular voltage pulse of 50 V, 6 µs duration is applied
to the sending end of a cable having a source impedance of
100 Ω, short-circuited at the far end. The cable parameters are:
C = 100 pF/m, L = 0.16 µH/m. The cable is 400 m long. Draw
a lattice diagram and plot the sending-end voltage for 15 µs.
3. Derive the ABCD constants for a line having resistance of
0.1 Ω/mi, reactance 0.86 Ω/mi, and capacitance 0.04 Ω/mi
using long line model. What is the electrical length of the line?
4. In Problem 3, calculate the rise in voltage at the receiving
end. Use a long line model and consider 400 mi of line length,
the sending-end voltage being 230 kV.
5. In Problem 3, what is the SIL loading of the line?
6. Consider the parameters of Example 4-9. A voltage of 10 kV
(continuous ramp) is applied to the sending end of the cable at
t = 0. Draw a lattice diagram and plot the voltage profiles: (1)
at the junction point, (2) at the open end of the transmission
line, and (3) at the sending end.
89
4. P. Chowdhri, Electromagnetic Transients in Power Systems,
Research Study Press, Somerset, England, 1996.
5. H. H. Skilling and P. Dykes, “Distortion of Traveling Waves by
Corona,” AIEEE Trans, vol. 56, pp. 850–875, 1937.
6. Transmission and Distribution Handbook, Westinghouse
Electric Corporation, Pittsburgh, PA, 1964.
7. J. Marti, “Accurate Modeling of Frequency Dependent Transmission Lines in Electromagnetic Transient Simulations,” IEEE
Trans. Power Apparatus and Systems, vol. PAS101, pp. 147–157,
1982.
8. J. H. Wilkinson, The Algebraic Evaluation Problem, Oxford University Press, London, 1965.
9. J. R. Marti, “The Problem of Frequency Dependence in Transmission Line Modeling,” PhD thesis, The University of British
Columbia, Vancouver, Canada, April 1981.
10. W. S. Meyer and H. W. Dommel, “Numerical Modeling of Frequency Dependent Transmission Line Parameters in EMTP,” IEEE
Trans. Power Apparatus and Systems, vol. PAS93, pp. 1401–1409,
Sept./Oct. 1974.
11. H. W. Beaty and D. G. Fink (eds.), Standard Handbook for
Electrical Engineers, 15th ed., McGraw-Hill, New York, 2007.
7. A line of surge impedance 400 Ω is terminated in a resistor
in parallel with a capacitor. Write an expression for the voltage
across the resistor.
12. L. Marti, “Simulation of Transients in Underground Cables
with Frequency-Dependent Modal Transformation Matrices,”
IEEE Trans. Power Delivery, vol. 3, no. 3, pp. 1099–1110,
1988.
8. Draw the current and voltage profile of a symmetrical
230-kV, 300-mi long line, at no load and when supplying
150 MW of power at 0.8 power factor. Consider L = 2 mH/mi,
C = 0.12 µF/mi.
13. L. M. Wedepohl and D. J. Wilcox, “Transient Analysis of Underground Power Transmission Systems: System Model and Wave
Propagation Characteristics,” Proc. IEE, vol. 120, pp. 252–259,
Feb. 1973.
9. An infinite rectangular wave on a line having a surge
impedance of 400 Ω strikes a transmission line terminated in a
capacitor of 0.004 µF. How much is the wave front retarded?
FURTHER READING
10. A long transmission line is energized by a unit step function at the sending end and is open-circuited at the receiving
end. Construct Bewely lattice diagram and obtain the value of
the voltage at the receiving end after a long time. Consider an
attenuation factor of 0.8.
11. Derive the relations shown in Eq. (4-17).
12. To study transient behavior up to a maximum frequency
of 3000 Hz, how many P sections should be modeled for a
line length of 150 mi?
REFERENCES
1. CIGRE WG 33.02, “Guidelines for Representation of Network
Elements when Calculating Transients,” CIGRE Brochure 39,
1990.
2. IEEE Task Force Report, “A Comparison of Methods for Calculating Audible Noise of High Voltage Transmission Lines,” IEEE
Trans. Power Apparatus and Systems, vol. PAS101, no. 10,
p. 4290, Oct. 1982.
3. M. R. Moreau and C. H. Gary, “Predetermination of RadioInterference Level of High-Voltage Transmission Lines-1:
Predetermination of Excitation Function,” IEEE Trans. Power
Apparatus and Systems, vol. PAS91, p. 284, 1972.
G. W. Alexander and H. R. Armstrong, “Electrical Design of a
Double Circuit Transmission Line, Including the Effects of Contamination,” IEEE Trans. Power Apparatus and Systems, vol. 85,
pp. 656–665, 1966.
J. G. Anderson, Transmission Reference Book, Edison Electric Company, New York, 1968.
J. Aubin, D. T. McGillis, and J. Parent, “Composite Insulation
Strength of Hydro-Quebec 735 kV Towers,” IEEE Trans. Power
Apparatus and Systems, vol. 85, pp. 633–648, 1966.
L. V. Beweley, Traveling Waves on Transmission Systems, 2d ed., John
Wiley & Sons, New York, 1951.
C. Gary, D. Cristescu, and G. Dragon, “Distortion and Attenuation
of Traveling Waves Caused by Transient Corona,” CIGRE Study
Committee 33 Report, 1989.
IEEE Task Force Report, “Review of Technical Considerations on
Limits of Interference from Power Lines and Stations,” IEEE Trans.
Power Apparatus and Systems, vol. PAS99, no. 1, p. 365, Jan./Feb.
1980.
L. B. Loeb, Electrical Coronas: Their Basic Physical Mechanisms, University of California Press, USA, 1965.
M. R. Moreau, and C. H. Gary, “Predetermination of Radio-Interference
Level of High-Voltage Transmission Lines-II: Field Calculating
Method,” IEEE Trans. Power Apparatus and Systems, vol. PAS91,
p. 292, 1972.
90
CHAPTER FOUR
M. S. Naidu and V. Kamaraju, High Voltage Engineering, 2d ed.,
McGraw-Hill, New York, 1999.
R. Rudenberg, Transient Performance of Electrical Systems, McGrawHill, New York, 1950.
Transmission Line Reference Book, 345 kV and Above, EPR1, Palo Alto,
CA, 1975.
C. F. Wagner, “A New Approach to the Calculation of Lightning
Performance of Transmission Lines, Part I,” AIEE Trans. vol. 75 Pt. III,
pp. 1233–1256, 1956.
C. F. Wagner and A. R. Hileman, “A New Approach to the Calculation of Lightning Performance of Transmission Lines, Part II,” AIEE
Trans. vol. 78 Pt. III, pp. 996–1081, 1959.
C. F. Wagner and A. R. Hileman, “A New Approach to the Calculation of Lightning Performance of Transmission Lines, Part III,” AIEE
Trans. vol. 79 Pt. III, pp. 588–603, 1960.
C. F. Wagner and B. L. Lloyd, “Effects of Corona on Traveling
Waves,” AIEE Trans., vol. 74, Pt. III, pp. 858–872, 1955.
CHAPTER 5
LIGHTNING STROKES,
SHIELDING, AND
BACKFLASHOVERS
The scientific study of lightning started in the summer of 1752,
when Benjamin Franklin attached a metal key to a kite string
and then flew the kite during a thunderstorm. Thus, more than
250 years ago he proved that lightning was an electrical discharge.
Modern research began in the twentieth century with the work of
C.T.R. Wilson, who was the first to infer the charge structure of the
thunderclouds and the magnitude of charge involved in lightning.
In 1930, the research was motivated primarily to protect power
systems and understand lightning phenomena. In 1960, there was
a renewed interest because of vulnerability of solid-state electronic
devices to surges. The research was further accelerated in 1969 when
the Apollo/Saturn crew survived two lightning flashes after takeoff.
Research continues in this field, for example, rocket-triggered lightning tests (RTL) and linear finite difference time-domain (FDTD)
electromagnetic solvers. On transmission lines, lightning is the
main cause of unscheduled interruptions. In recent years much
knowledge has been gained on very widely varying phenomena of
statistical and nonlinear nature as evidenced by a spate of publications on the subject.
5-1
FORMATION OF CLOUDS
The clouds are composed of water droplets and ice crystals. The
altitude at which supersaturation occurs in the rising air streams
and clouds begin to form is called the lifted condensation level
(LCL), which is within 1000 m of the earth’s surface. A great
majority of clouds form at temperatures above freezing and consist
entirely of liquid droplets. Many observations disclose that a cloud
must extend 2 to 3 km in the subfreezing portion of atmosphere
before the first lighting is observed. A large variety of meteorological conditions are favorable for lightning to occur.
Figure 5-1 describes the tripole structure of the thundercloud,
and Fig. 5-2, which shows three regions, is the classic Simpson’s
model. Below region A, the air currents travel above 800 cm/s and
no raindrops fall through. In region A, the velocity of air currents
is high enough to break falling raindrops, causing positive charge
spray in the cloud and negative charges in the air. The spray is
blown upward, but as the velocity decreases, the positively charged
water drops combine with larger drops and fall again. Region A
becomes positively charged, while region B becomes negatively
charged due to air currents. In the upper regions, the temperature
is below the freezing point and only ice crystals exist.
Though the theory has been modified, the three charge regions
are confirmed by modern measurements. The main negative charge
in the central portion is in the temperature zone between –10° and
–20° C, often less than 1 km in vertical extent. The upper and lower
regions in the cloud are separated by a quasi-neutral zone. The main
charge regions in the cloud are confined vertically rather than horizontally. The lower positive charge is typically smaller in magnitude
than the main negative charge. The top positive charge is more diffused. As the freezing of droplets progresses from outside to inside,
the outer negatively charged shells fall off, and the remaining positively charged fragments are swept upward in the convection current. The exact mechanism of thundercloud electrification is still
not clearly understood, although a number of theories attempt to
account for the electrification mechanism. Some examples are
■
Inductive mechanism and convective mechanism
■
Selective ion capture theory
■
Drop breakup theory
■
Thermoelectric effects
■
Surface potential theories
We will not go into these theories and Ref. 1 provides further
reading. For lightning to occur, some conditions to be met are:
1. Cloud depth must be greater than 3 to 4 km.
2. Strong electrifications are not observed unless the cloud
extends above freezing level.
3. Highly charged regions almost always coincide with coexistence of ice and supercooled water.
91
92
CHAPTER FIVE
FIGURE 5-1
FIGURE 5-2
The tripole structure of thunderclouds.
The classic charge structure of a thundercloud.
4. Strong electrification occurs when the cloud exhibits strong
convective activity with rapid vertical development. The initial
rate of electrification has a time constant of about 2 min. In
the mature stage, electrical fields as high as 400 kV/m may be
produced.
5-2
LIGHTNING DISCHARGE TYPES
The main lightning discharge types are (Fig. 5-3):
■
Intercloud flash. The most common lightning discharge type
is intercloud flash. This is a discharge between upper
positive and main negative charge region of the cloud.
■
Cloud to ground flash. The ground flash transfers negative
charge (generally) from the main negative region of the cloud
to ground; however, an initial discharge between the upper
negative and the lower positive charge is an essential process.
Also positive-charge transfers to ground can occur, though not
so common.
■
Air discharge. An air discharge is a discharge in the air; it
does not touch the ground.
5-3
THE GROUND FLASH
The ground flash occurs between charge centers of the cloud and
ground. A negative ground flash brings negative charge to ground
and is most common, and a positive ground flash brings positive
charge to ground. From the power systems point of view, this is of
much concern and we will study its mechanism in the following
sections.
5-3-1
Stepped Leader
The ground flash is initiated by electrical breakdown in the cloud,
called the primary breakdown. This creates a column of charge
called a stepped leader that travels from the cloud to ground in a
stepped manner. On its way to ground, it may give rise to several branches. Periodically, the streamer reaches too far from the
charge in the cloud, and the electrical field at the tip is too weak
to propagate it further toward the ground. This slight time delay
allows more charge to be transferred from the cloud to the tip of
the streamer, and it moves further toward the ground, hence the
name stepped leader. The propagation of each step is random, as
the charge density at the tip of the streamer is dependent on local
LIGHTNING STROKES, SHIELDING, AND BACKFLASHOVERS
FIGURE 5-3
Predominant lightning types: (a) Intercloud flash; (b) cloud to ground flash; (c) air discharge.
conditions. Thus, most stepped leaders follow a rather twisted path
to the ground. Figure 5-4 shows that several streamers can originate
from the same charge cluster, and these become secondary leaders.
5-3-2
93
Return stroke
As the leader approaches the ground, the electrical field at ground
level increases. Elevated objects, such as trees, power lines, structures, and buildings, are more vulnerable. Around an induced electrical field level of about 3 MV/m, a corona streamer of opposite
polarity rises from the object to meet the downward leader. These
discharges from the grounded buildings and structures are called
connecting leaders and they travel toward the stepped leader. One of
the connecting leaders may successfully bridge the gap between the
ground and the stepped leader. This separation between the object
struck and the tip of the stepped leader at the inception of the connecting leader is called the striking distance, which is of importance
in shielding and lightning protection, as discussed in Sec. 5-6. This
completes the current path between the cloud and the ground, and
high discharge current flows to neutralize the charge, positive from
ground to negative in the cloud. This is called the return stroke; it
FIGURE 5-4
is highly luminous and strongly branched. Currents of the order of
100 kA and more are possible.
In most cases, the return stroke prevents any further propagation of the leader, as the current path is neutralized. However, two
branches of the leader can reach the ground simultaneously, resulting in two return strokes.
An upward moving stroke may encounter a branch end and
there is an immediate luminosity of the channel; such events are
called branch components. In certain cases, the return stroke current may not go to zero quickly and continue to flow for tens to
a few hundreds of milliseconds. Such long-duration currents are
called continuing currents.
5-3-3
Dart leader and multiple flashes
The lightning flash may not end in the first flash. The depletion
of charge in the original cloud cluster creates cloud to cloud (CC)
discharges and connects the adjacent charge clusters to the original
charge cluster, which may get sufficiently charged to create subsequent flashes. Because the discharge path from the original flash
is still ionized, it takes less charge to start a flash. The preionized
Typical parameters of lightning flash, U.S. Nuclear Regulatory Commission.2
94
CHAPTER FIVE
channel results in subsequent strokes with about one-third the current and shorter rise time in comparison with the original stroke.
Sometimes discharges originate several kilometers away from the end
of the return stroke channel and travel toward it. These may die out
before reaching the end of the return stroke point and are called the
“K” changes. If these discharges do make contact with the returnstroke channel and the channel is carrying continuous current, it
results in a discharge that travels toward the ground and is called the
“M” component. If the return stroke channel is in partially conducting stage, it may initiate a dart leader that travels toward the ground.
Where ionization has decayed, it will prevent continuous propagation of the dart leader, and it may start propagating to ground as a
stepped leader, called dart-stepped leader. If these leaders are successful in traveling all the way to ground, then subsequent return strokes
occur. It is not uncommon for the dart leader to take a different path
than the first stroke. A ground flash may last up to 0.5 s with a mean
number of strokes ranging from 4 to 5. The separation between subsequent channels was observed to be a few kilometers on average.
The positive leaders propagate approximately in a similar manner as described for the negative strokes.
5-4
LIGHTNING PARAMETERS
Figure 5-53,4,5 shows cumulative distribution of lightning peak
currents; Fig. 5-64,6 shows time to peak of lightning stroke currents; Fig. 5-77 shows rate of rise of lightning stroke current; and
it also shows the front of a negative return stroke from Ref. 8. It is
characterized by:
■
Steep front rise
■
Broad peak area with several minor peaks
■
Slow decay to a low current.
[6]
[4]
FIGURE 5-6
FIGURE 5-7
Time to peak of lightning stroke currents.4,6
Rate of rise of lightning stroke current.
The critical part of the curve (Fig. 5-8) is the initial rise and the
various parameters, which are used to define the range of lightning
stroke waveshape. Table 5-1 provides typical values of these parameters. Actual parameters are spread randomly and their probability
distribution is described mathematically as a “log-normal” function, when lnIp has a normal distribution. The probability density
function P(Ip) of Ip can then be expressed as:
2
ln I − ln I
1
pm
p
P(I p ) =
exp − 0 . 5
2π I pσ ln I
σ ln I
p
p
FIGURE 5-5
3,4,5
distributions.
Cumulative distribution of lightning peak current
(5-1)
where σ ln I is standard deviation of ln Ip, and Ipm is maximum value
p
of return stroke current.
LIGHTNING STROKES, SHIELDING, AND BACKFLASHOVERS
FIGURE 5-8
TA B L E 5 - 1
Parameters of the front of return stroke current wave.8
Median Values of Stroke Parameters
PARAMETER
DESCRIPTION
Peak (kA)
Peak value
Tan-10 (kA/µs)
Tangent at 10%
FIRST STROKE
FOLLOWING
STROKES
31.1
12.3
2.6
18.9
S-30 (kA/µs)
Slope from 30 to 90%
7.2
20.1
T-90 (µs)
Time from 10 to 90%
4.5
0.6
T2 (µs)
Time to 50% on tail
80
32
The cumulative probability is given by:
Pc (I p ) =
1
π
∞
∫ e −u
2
du
(5-2)
0
where:
u=
ln I p − ln I pm
2σ ln I
(5-3)
p
The median value represents the 50 percent mark on the cumulative
distribution curve, that is, 50 percent of the observed parameters are
above and 50 percent below the mark. The cumulative distributions in
Table 5-1 are shown in Figs. 5-9, 5-10, 5-11, and 5-12.8, 9
The parameter S30/90 is the steepness of the front measured
by a line drawn through 30 percent and 90 percent points. The
parameter T30 is time to crest. For a wide range of peak current values, the field data distribution can be expressed by a much simpler
equation by Anderson:10
100
Pc =
1 + (I p / 31)2.6
(5-4)
where Pc is the probability of peak current exceeding Ip, the peak
first stroke current. Consider a lightning voltage of 100 kV that
includes all but 20 percent of the strokes:
■
Peak current from Fig. 5-9 gives the first stroke current = 48 kA,
and subsequent stroke current = 19 kA.
■
95
Rise time from Fig. 5-10 gives first stroke current T90 = 7.5 µs,
and rise time = 1.25 × 7.5 = 9.4 µs; following stroke current,
T90 = 1.5 µs and rise time = 1.25 × 1.5 = 1.9 µs.
■ Steepness from Fig. 5-11 gives first stroke current Tan-10 =
5.8 kA/µs, S-30 = 13 kA/µs; following stroke
Tan-10 = 59 kA/µs, S-30 = 45 kA/µs.
Figure 5-13 is CIGRE/IEEE standard probability curves of first
stroke, negative downward flash.11
The lightning flash includes several individual strokes and the
total transfer of electric charge can only be determined by considering the entire succession of waveforms. Research shows that
lightning stroke produces more energy than has been considered
previously possible. A typical lightning stroke carries approximately
30 × 108 KW at approximately 125 MV and an average current of
more than 20 kA.
To summarize, lightning currents can be very high, of the order
of 200 kA. These currents rise at a very fast rate which varies from
less than a microsecond to 10 to 20 ms and then decay to small
values, a low-current component persisting even for a few seconds.
A lightning stroke is a random phenomenon, and statistical data
has been accumulated over the years. As the lightning current is
so high the voltage developed depends upon the impedance of the
system, and it can be of the order of several megavolts. Table 5-2
gives variations of lighting stroke parameters.
In power systems, most severe voltage surges are caused by lightning. As the system operating voltages increase, the switching surge
transference becomes as important as lightning surges (Chap. 7).
For application of surge arresters, the important parameters are
overvoltages at the equipment terminals and the energy dissipation
through the surge arrester. The effects of the lightening stroke currents can be summarized as:
■
The crest current is responsible for ohmic voltage drops,
especially in the ground resistance.
■
The steepness of lightning current determines the inductive
voltage drop, induced voltage, and magnetic couplings.
■
The electric charge of the lightning current is a measure of
the energy transferred by the lightning arc to metallic objects,
causing melting and diffusion of the transient electromagnetic
field through metallic screens.
■
The integral of current squared multiplied by time is fundamental to mechanical effects and impulse heating.
■
The lightning parameters vary over large values. The current
and wave shape data are defined statistically. The frequency of
lightning strokes is an important issue in determining the surge
arrester duty.
FIGURE 5-9
Cumulative distributions of peak stroke current, showing negative polarity.
FIGURE 5-10
96
Cumulative distribution of T90 data for return stroke currents.8
FIGURE 5-11
Cumulative distribution of Tan-10 and S-30 data for return stroke currents.8
FIGURE 5-12
Cumulative distribution of stroke distribution T2, data.9
97
98
CHAPTER FIVE
TA B L E 5 - 2
Variations of Lightning Stroke
Parameters
PARAMETER
RANGE
Total charge transferred
2–300 C
Peak currents achieved
200–40 kA
Time duration to half value
10–250 µs/stroke
Current rise at 90% of its peak value
A few ns to 30 µs
Velocity of propagation
1–21 m/s
Time between strokes in one flash
3–100 ms
Number of strokes per flash
1–26
Energy per strike
> 1010 J
RFI range
1 kHz–100 MHz
is rather a coarse measurement and its calculation requires simple
observations. The keraunic-level data is available for a number of
years all over the world. Figures 5-14 and 5-1512 show the isokeraunic levels of the world and the United States, respectively.
An equation representing the relation between keraunic level
and ground flash density is:
N g = 0 . 14TD1.03
where Ng is the ground flash density in flashes per square kilometer
per year and TD is the keraunic level. Another relation used in a
Canadian research is:
FIGURE 5-13
IEEE and CIGRE probability distributions of first
stroke, negative downward flash.
5-5 GROUND FLASH DENSITY AND KERAUNIC LEVEL
The ground flash density is the number of lightning flashes to a
specific area in a given time. It is measured in terms of flashes per
square kilometer per year. This data may not be readily available.
However, meteorological available data is in the form of counters
depicting number of days (24 hour period) per year on which thunder is heard. This is also known as keraunic level. Keraunic level
FIGURE 5-14
(5-5)
N g = 0 . 054TH1.1
(5-6)
where TH is the number of hours per year during which thunder
is heard at a certain location. Figure 5-16 shows the variation of
ground flash density with TD. The following equation has been
accepted by CIGRE and IEEE:
N g = 0 . 04TD1.25
Isokeraunic map of the world.
(5-7)
LIGHTNING STROKES, SHIELDING, AND BACKFLASHOVERS
FIGURE 5-15
99
Isokeraunic map of the United States.
As a first step it is necessary to estimate the area and the number
of lightning surges on a power system. The fundamentals of lightning mechanism described above are of help in this analysis.
5-6-1
Striking Distance
As the stepped leader descends downward and approaches an
object, the intensity of the electric field is determined by the geometry of the object (for tall slender objects like transmission line
towers and chimneys, the height above ground is the predominant
factor). A corona steamer is initiated from the structure when the
electric field intensity reaches a certain level (3 MV/m), and this
ascending corona steamer creates a highly ionized channel. The
distance between the tip of the leader and the structure at which
it happens is called the striking distance. (Another definition of the
striking distance is provided in Sec. 5-3-2) For transmission lines, it
is the semicylindrical envelope around the conductor8 given by:
rs = (0 . 4 + 0 . 01hs )I(s1.4−0.001hs )
FIGURE 5-16
5-6
Ground flash density versus thunder days per year.
LIGHTNING STRIKES ON OVERHEAD LINES
The effect of lightning on the transmission lines is important in
power system engineering. It gives rise to a number of related
phenomena—surge protection, insulation coordination, shielding,
safety of equipment and personnel, and concerns about continuity
of power supply.
(5-8)
where rs is the striking distance in meters, Is is the peak lightning
stroke current, hs is the height of the structure above ground in
meters. For a lightning current of 40 kA and a tower of 10 m, the
striking distance is 84.6 m
A number of formulas for calculating the striking distance by
various authors/researches are shown in Table 5-3. The most commonly used expression, which is in current use based upon IEEE
committee report, is:13
rs = 8I 0p .65
(5-9)
where Ip, the return stroke current, varies from 1 to 200 kA.
100
CHAPTER FIVE
TA B L E 5 - 3
Expressions for the Striking
Distance in Meters
AUTHOR/RESEARCHER
Darveniza, 1979
STRIKING DISTANCE
EXPRESSION, rs TO
PHASE GONDUCTORS
AND GROUND WIRE
(IN METERS)
STRIKING DISTANCE
EXPRESSION, rg TO
EARTH OR GROUND
WIRES (IN METERS)
2Is + 30(1 – e–0.147l)
—
0.65
s
Love, 1973
10I
10Is0.65
Brown-Whitehead, 1977
7.1Is0.75
6.4Is0.75
Suzuki, 1981
3.3Is0.78
—
0.6 0.74
s
Erickson, 1982
0.67h I
0.67h 0.6Is0.74
IEEE-1995 Subcommittee
8h 0.6Is0.65
8h 0.6Is0.65
Is, the first return stroke current.
The upward leader from the structure may not contact the
stepped leader; this may happen if the stepped leader crosses the
striking distance envelope far away from the vertical axis. In this
case the leader may proceed directly to the ground, without hitting
the object. The loci of the stepped leader and the upward leader
form a parabola above the structure, as shown in Fig. 5-17.
5-6-2
The Attractive Radius
Figure 5-17 shows the attractive radius, as the horizontal coordinate of the interception of the upward leader and the downward
stepped leader. This means that all lightning strokes of current Is
will strike it, according to Eq. (5-10):
ra = 0 . 84I s0.74hs0.6
(5-10)
where ra is in meters. For a 10 m tower and a lightning current of
40 kA, the attractive radius is 51.26 m. A relation independent of
the stroke current gives the average attractive radius, solely dependent upon the height of the object:14
rav = 14hs0.6
(5-11)
5-7
BIL/CFO OF ELECTRICAL EQUIPMENT
For electrical equipment to withstand surges of atmospheric origin
(lightning) and switching, test standards and test waveshapes have
been established. Basic insulation level (BIL) shows the rating of
the equipment to which it is impulse tested. Most electrical equipment, that is, line insulators, transformers, reactors, circuit breakers, switches, surge arresters, and the like have a BIL rating, which
is an important parameter in insulation coordination and lightning
protection of the equipment. The BIL may be statistical or conventional. The statistical BIL applies to self-restoring insulation, that
is, insulation which completely recovers insulating properties after
a flashover, for example, external insulators. The conventional BIL
applies to non-self-restoring insulation, that is, insulation that does
not recover after a disruptive discharge, for example, transformer
windings. IEC terminology is “lightning impulse withstands voltage.” We will often return to BIL in the chapters to follow.
Statistical and conventional BSL are similarly defined for switching test impulse. For every application of an impulse having standard waveshape, whose crest is equal to BIL or BSL, the probability
of flashover or failure is 10 percent. The insulation strength can be
represented by gaussian distribution (see App. F).
For self-restoring external insulation, for example, insulators
and CFO, the critical flashover voltage is used. The CFO is defined
as the impulse voltage level at which the probability of flashover is
50 percent, that is, half the impulse flashover. Considering the BIL
and BSL at 10 percent point results in the definition that these are
1.28 standard deviation, σ f , below CFO:
σ
BIL = CFO 1 − 1 . 28 f
CFO
σf
BSL = CFO 1 − 1 . 28
CFO
(5-12)
σ f in per unit of CFO is called the coefficient of variation. Thus, s of
5 percent is a standard deviation of 5 percent of the CFO. For lightning the standard deviation is 2 to 3 percent, while for switching
impulse it varies say 5 percent for tower insulation to 7 percent for
station-type insulators. We will revert to these probability concepts
in greater detail in Chap. 17 on insulation coordination.
5-7-1 1.2/50-µs Test Wave
Figure 5-18 shows the waveshape of the lightning current for laboratory BIL testing. The BIL tests are type tests to establish the integrity of the equipment to withstand steep-fronted lightning surges.
The waveshape shown in Fig. 5-18 is according to ANSI/IEEE standards. It is called a 1.2/50-µs wave and the important parameters
are as shown. The front time for the voltage wave is defined as:
1 . 67(t 90 − t 30 ) = 1 . 2 µ s ± 0 . 36 µ s
(5-13)
The duration is defined as the time between virtual origin and
the time of 50 percent point on the tail. The virtual origin is a point
where a straight line between 30 percent and 90 percent points on
the leading edge of the waveform intersects V = 0 line.
Duration = 50 µ s ± 10 µ s
(5-14)
The lightning impulse waveshape can be described by two
exponentials:
FIGURE 5-17
Loci of the interception of stepped leader by the
upward leader from power line structure.22
v = Vp (e −αt − e βt )
(5-15)
LIGHTNING STROKES, SHIELDING, AND BACKFLASHOVERS
FIGURE 5-18
Selection of a = 1.4E4 and b = 4.5E6 gives the 1.2/50-µs wave. The
waveshape can also be represented by the equation:
−t
−t
V (t ) = AVp 1 − exp exp
τ1
τ 2
(5-16)
where τ 1 = 0 . 4074 µ s, τ 2 = 68 . 22 µ s and A = 1.037. Figure 5-18
shows a full impulse wave. This is the shape seen at some distance
from the lightning impulse. The wave can get chopped on the tail or
front. These waveshapes and volt-time characteristics of the insulation are described in Chap. 17.
FIGURE 5-19
101
1.2/50-µs voltage test wave.
5-7-2
8/20-µs Test Wave
Another test wave of interest is 8/20-µs current wave shape shown
in Fig. 5-19. Here the front time is defined as:
1 . 25(t 90 − t10 )
(5-17)
where t90 and t10 are the times for 90 percent and 10 percent amplitude
points on the leading edge of the waveform. The duration is defined as
the time between virtual origin and the time of the 50 percent amplitude point on the tail. Here the virtual origin is obtained by a straight
line between 10 percent and 90 percent amplitude points on the leading edge of the waveform where it intersects I = 0 line (Fig. 5-19).
8/20-µs current test wave.
102
CHAPTER FIVE
The wave can also be represented by double exponential
equation [Eq. (5-15)] with appropriate choice of a and b. Another
equation is:
−t
I(t ) = AI pt exp
τ
3
(5-18)
where τ = 3 . 911 µ s and A = 0 . 01234 (µ s)−3
These waveshapes are described as “impulse” in IEC. Both
waves together are described as “combination waves” because these
can be delivered by a generator, on open circuit, 1.2/50-µs wave
and an 8/20-µs wave on short circuit. These can be readily generated
in many laboratories and are commonly used for the study of lightning strikes. The earlier IEEE standard for the voltage wave was
1.5/40 µs. The other test waves are discussed in Chap. 19.
A direct stroke can occur on phase conductors, towers, or ground
wires. This will give rise to overvoltages which may exceed CFO.
Thus, direct strokes are important concerns for protection of the
transmission lines. Indirect strokes may not induce high enough
voltage to exceed CFO on high-voltage lines. Indirect lightning
strokes can induce 50 to 60 kV or even higher overvoltages for a
lightning stroke in the vicinity, with a relatively low-peak discharge
current. This may exceed the insulation strength of distribution
networks.
Once Ng is known, the frequency can be directly calculated from:
(5-19)
where Ng is the ground flash density in flashes per square kilometer
per year, and Nd is the number of direct strikes to the line. The
problem is to calculate the area of exposure and various models
have been in use. Some of these are described below:
(a) Based upon attractive radius and height. Referring to
Fig. 5-20a, the area exposed to lightning is given by:
Ae = 0 . 001(2rav + w)l
(5-20)
where l is the length of the line in kilometers, Ae is the exposed
area in square kilometers and w is horizontal line width. It is
zero for conductors placed vertically on the structure, that is,
when there are no cross-arms, r av is the average striking
distance. This may be calculated from the conductor height
less half the conductor sag. This equation applies to all lines
that have shield wires. Tall objects in the vicinity of the line
may divert lightning flashes. This shielding effect can be
calculated in the flash frequency calculations.15
(b) Protective shadow of a structure. A vertical structure attracts
lightning from a distance twice its height. If b is the spacing
between the shield wires and H is the height, then the width of
shadow W is:
W = b + 4h meters
(5-21)
where h should be adjusted for the sag in the shield wires.
(c) Strokes to shield wire, one shield wire. The geometric
construction is shown in Fig. 5-20b. This shows two striking
distances, rs and rg. The breakdown gradient on top of tower
differs from the gradient to cause flashover to ground. The
numbers of strokes terminating on ground wire are:
N(G) = Ae N g = (2 D gl)N g
dN(G) = Ae N g f (I )dI
(5-23)
and total number of strokes is:
∞
N(G) = 2N gl ∫ D g f (I )dI
(5-24)
3
(d) Two overhead wires. The geometric construction is shown
in Fig. 5-20c. Here:
∞
N(G) = 2N gl ∫ D g f (I )dI + N glS g
(5-25)
3
5-8 FREQUENCY OF DIRECT STROKES TO
TRANSMISSION LINES
N d = N g Ae
Area Ae that collects the strokes is 2Dg l. The probability that
this stroke current will occur is:
(5-22)
(e) Eriksson’s model. There exists no striking distance to
ground or earth (Fig. 5-20d):
D g = rs = 0 . 67h 0.6I 0.74
(5-26)
( f) Electrogeometric model. This is shown in Fig. 5-20e. Curve
a enclosing line conductor is locus of stroke tip positions,
which decide whether the leader will strike the conductor or
the earth. However, even if the stroke tip is within the curved
boundary, it will strike the earth if its distance from the conductor is greater than rs.
rg = βrs
(5-27)
for b more than or equal to 1, the curve is a parabola. The
width a1b1 is:
a1b1 = 2 h(2rs1 − h )
(5-28)
and for rs1 ≤ h
a1b1 = 2rs1
(5-29)
If the probability of return stroke current exceeding I is P, then
the number of strokes exceeding I and striking the line is:
N = Ae N g P
(5-30)
where P can be calculated from (5-4).
Example 5-1 A transmission line runs through an area with
thunderstorm activity TD = 10 thunderstorm hours per year. The
height of the top conductor = 11 m, the sag = 2 m, the horizontal
line width = 3 m, and the line length = 20 km.
Calculate Ng using Eq. (5-5). This gives 1.5 flashes per square
kilometer per year. Calculate attractive radius based upon a height
of 10 m (11 m less 50 percent sag):
rav = 14hs0.6 = 14(10)0.6 = 56 m
The area Ae from Eq. (5-20) is:
Ae = (0 . 001)(20)(2 × 56 + 3) = 2 . 3 km 2
Therefore from Eq. (5-19), Nd = 3.45 direct strikes per year. To
use Eq. (5-21), assume b = 1.5 m. Then width of shadow is 40.18 m.
This is calculated by adjusting h from the sag, that is, h = height of
structure –0.667. The result is 1.2 strokes per year for 20 km of
line length.
LIGHTNING STROKES, SHIELDING, AND BACKFLASHOVERS
103
F I G U R E 5 - 2 0 Models for calculating incident of lightning strokes: (a) model based upon average attractive radius; (b) and (c) geometric models for
single and double ground wires, respectively; (d) Eriksson’s geometric model; and (e) electro-geometric model.
To calculate rs, assume a peak current Ip = 40 kA. Then from
Eq. (5-26), rs = 43.2 m. Then from Eriksson’s model equation,
number of strokes = 2.6 for 20 km of line per year. The electrogeometric model gives the same results as rs1 ≤ h and a1b1 = 2rs =
86.4 m and number of strokes = 2.6 for 20 km per year. The
probability from Eq. (5-4) for 40-kA current = 0.3401. Then
from Eq. (5-30), the number of strokes exceeding Ip = 0.88.
There are variations in the results calculated based upon the
model used. Also various models do not correlate so well with
the field measurements.
104
CHAPTER FIVE
To relate long-range data with short-range statistics, a probability distribution function (Poisson distribution) as follows can
be used:
Pn =
100(N dt )e n−N dt
n!
(5-31)
where Pn is the probability of occurrence of exactly n flashes, n is
the number of flashes striking the system, t is the time duration of
interest in years.
Example 5-2 Find the probability of having more than five strikes
per year in Example 5-1. Substituting the values in Eq. (5-31):
Pn =
100(3 . 45)(1)e n−( 3.45)(1)
n!
5-10
LIGHTNING STROKES TO TOWERS
If a lightning stroke occurs to a transmission line tower, the lightning
currents in the phase conductors, ground wires, and towers are at
right angles. The mutual effects of these currents do not obey conventional traveling wave theory which applies to parallel conductors.
For steep-front lightning currents, a 30-m high tower behaves like a
surge impedance of approximately 50 to 100 Ω for a 0.2-µs return
traveling time. For lightning currents with wave fronts exceeding
0.5 µs, the tower behaves like an inductance of about 0.2 to 0.4 µH/m.
The tower surge impedance has been computed and measured
in the field and on scale models.16,17 It varies along the tower and
considerable attenuation exists. A constant value can, however, be
derived for practical purposes. For conventional double circuit towers, the surge impedance is given by Refs. 16 and 17.
h2
Zt = 30 ln 2 1 + 2
r
Probability for
0 strike = 3.17 percent
1 strike = 10.90 percent
2 strikes = 18.86 percent
3 strikes = 21.60 percent
4 strikes = 18.71 percent
5 strikes = 12.90 percent
Total = 86.14 percent.
(5-35)
where h is the height of a cone of the same height as the tower and
r is its base radius (mean periphery divided by 2π). For cylindrical
towers the following expression can be used:
r
h
Zt = 60 ln + 90 − 60
h
r
(5-36)
Thus, probability of having more than five direct strikes is
13.86 percent
This equation can also be used for down leads with r representing the wire radius. For towers which cannot be approximated with
cones or cylinders, scale models and testing are required to determine the effective surge impedance.
5-9
5-10-1
DIRECT LIGHTNING STROKES
Direct lightning strokes to conductors, towers, and even shield or
ground wires produce high voltages. The strokes to ground in the
vicinity of a transmission line produce the lowest overvoltages. Consider a direct stroke to a conductor. As the stroke current will flow in
either direction, the voltage induced V is approximately given by:
V = 0 . 5IZ0
(5-32)
where Z0 is the surge impedance of the line. Thus, even a stroke
current of 20 kA and a surge impedance of 400 Ω will give a voltage of 4000 kV. Thus, most strokes to phase conductors will result
in a flashover. The voltage induced on other phases will be given
by KV, where K is the coupling factor, and the voltage between two
phase conductors will be (1 – K)V. A flashover between two conductors can occur, depending upon the separation between them.
The voltages on the conductors will travel in either direction and a
flashover will occur if CFO is exceeded. For a midspan stroke, the
critical stroke current magnitude that will cause flashover is given
by:
I c = 2CFO/Z0
(5-33)
This follows from the definition of CFO. It is a standard practice
to prevent direct strokes to conductors by arranging one or more
shield (ground) wires, which are discussed in Sec. 5-13.
If Z is the impedance of the power system at the point of lightning strike, and Zs the surge impedance of the stroke channel, then
the stroke current I0 (to zero earth resistance, infinite conductivity)
will divide into Zs and Z in parallel, and the voltage across Z, the
stricken object, is given by:
V=
I 0 ZZ s
(Z + Zs )
(5-34)
The problem lies in accurately calculating the surge channel
impedance Zs.
Tower Footing Resistance
Another parameter to be considered is the tower footing resistance, which will be much different from the resistance at power
frequency currents. At the power frequency level the resistance is
mainly a function of soil resistivity. Under currents of high intensity, the soil becomes ionized and may partially breakdown. The
impulse value of the resistance is, therefore, lower than the power
frequency resistance (Chap. 21).
The footing resistance at high impulse current can be determined from the following equation:
Ri =
R0
1+
IR
Ig
(5-37)
where Ri is the footing resistance at impulse current, R0 is the resistance measured at low current, and IR is the lightning current through
the footing resistance. Ig is the current required to produce a soil gradient, E0, at which soil breakdown occurs. This current is given by:
Ig =
1 ρ E0
2π R 02
(5-38)
where ρ is the soil resistivity in ohms-meter, E0 is the breakdown
gradient, which is assumed = 400 kV/m. As the current increases,
streamers are generated that evaporate the soil moisture, and arcs
are produced. Within arcing and streamer zones, the resistivity
decreases; we can imagine that the grounding rod becomes a hemisphere at high currents.
A single counterpoise behaves first with its surge impedance,
which then falls to power frequency resistance. Consider a counterpoise of 100-m length; the counterpoise will have the surge
impedance of buried wire, say equal to 150 Ω. A counterpoise may
be represented by a series of leakage resistance (to duplicate distributed leakage current to ground) in parallel with Ri. Voltage and
current waves travel down the tower impinge on this combination,
LIGHTNING STROKES, SHIELDING, AND BACKFLASHOVERS
and the waves travel at about one-third the speed of light. At a time
equal to twice the travel time, the impedance is reduced to power
frequency resistance, which is equal to total leakage impedance of
the counterpoise.
For towers without shield wires, the voltage drop from the top
of the tower to earth is:
DV = L
di
+ Rfi
dt
(5-39)
where Rf is the footing resistance of the tower and i is the surge
current. For each frequency and current, the footing resistance varies. Neglecting induced voltages on phase conductors, DV appears
across line insulators of the struck tower; the total voltage is, thus,
the service voltage of the conductors plus DV. If this total voltage
exceeds the insulator flashover voltage, a flash will occur. This is
called backflashover. When this occurs, half of the surge impedance
of the phase conductors acts in each direction, and the primary
traveling waves on the struck conductor in each direction give rise
to induced (coupled) traveling waves on the other two phases. This
may reduce the induced voltage by 30 to 40 percent on the insulators of phases which were not struck by lightning and prevent
further flashovers. Thus, the backflashovers remain on the phase
originally struck by the lightning.
This is rather a simplified description of complex phenomena.
The lightning current in the stroke channel and towers flows at right
angles and does not observe the conventional traveling wave theory.
The field theory concepts can be used, which get fairly involved.
For practical use Wagner and Hileman17 derived the voltage across
the insulation by superimposing two voltage components: (1) the
current injected into the tower and ground wire system and (2) the
charge over the tower. The effect of (1) predominates for shortwave fronts up to 1 µs, while the effect of (2) increases for longer
wave fronts above 2 µs.
To further complicate this picture, the voltage stresses on tower
insulation can be reduced by the streamer projecting from the tower
to meet the opposite polarity leader head. However, streamer length
cannot be so precisely calculated. Most practical methods ignore
this effect and consider only the injected current component.
For a tower with ground wires, the terminating impedance can
be written as:
Z=
Zt Z g
Z g + 2 Zt
(5-40)
This expression shows that the total impedance is the tower surge
impedance Zt in parallel with the ground wire surge impedance Zg.
Considering ground wire extension in both directions, the effective
surge impedance is 0.5 Zg.
The tower top potential can now be calculated from (5-40),
that is:
Vt =
I 0 ( Zt Z g )Z s
Zt Z g + Z s ( Z g + 2 Zt )
(5-41)
The ground wire potential couples with the phase conductors
and the voltage stressing the tower insulation is the difference in the
potential between tower top potential and the voltage induced in
the phase conductor. The induced voltage is given by:
Vi = (1 − K )Vt
(5-42)
where, the coupling coefficient K varies from 0.15 to 0.30. The
coupling coefficient is:
K = Z gp / Z g
(5-43)
where Zgp is the mutual surge impedance between the shield wire
and the phase conductor.
105
Greater the distance between the conductors, lower is the value
of K. Two ground wires have greater coupling to the phase conductors than a single ground wire. A continuous counterpoise also
increases the coupling factor. Vi is also the voltage developed across
the insulator string. If the cross arm is not near the top of the tower,
its voltage can be determined from the lattice diagram.
The corona increases the conductor’s effective radius, which
increases the coupling factor and reduces the insulation stress (see
Chap. 4). The corona streamers carry significant quantities of charge
away from the conductors and tower members. This effect creates nonlinear changes in the capacitance of conductors to ground
and between phases (Chap. 4) and distorts the voltage waveshape
appearing across the insulators. Corona moving outward is equivalent to a uniform extension of conductor diameter, until the gradient
at the conductor drops to some critical extinction voltage, E0—its
value has been accepted to be 1500 kV/m. Corona diameters are
plotted against V/E0. For backflashovers, the voltage of the shield
wire is taken as 1.8 times the CFO of insulators for 2 µs to crest.
The corona does not change the inductance and this increases the
no-corona surge impedance of the conductor.
The tower footing resistance is much less than the tower surge
impedance. The incident wave traveling down the tower is reflected
at the foot of the tower in an upward direction, up the tower, with
opposite sign (Chap. 4). This may occur in a fraction of a microsecond, and this reflected wave is superimposed on the existing
tower potential. Generally the wave front of the current surge will
be much longer than the time taken by the reflected wave to move
up the tower. This will reduce the rate of rise because the tower top
potential has not yet reached its peak. A lower tower footing resistance will be effective in reducing the tower top potential. Considering a zero footing resistance, the incident wave will be reflected
with the sign reversed multiplied by coupling factor K. The longer
the surge front, the more effective will be the slope reduction.
The effect of the adjacent tower will be that the voltage waves
traveling away from the struck tower on the ground conductors in
both directions will be reflected back from the adjacent towers with
opposite signs. If the time to crest is longer than the return time of
the reflected wave, they will act like reflected waves from the base
of the tower, further reducing the tower top voltage. If these arrive on
the voltage tail, they will still have some effect on shortening the tail
and reducing the stresses.
During the front of the wave, the impulse voltage induced
across line insulation consists of two components: (1) due to surge
response of tower and (2) resistive voltage rise of footing. During
wave tail, the voltage across the tower reduces. If the flashovers
do not occur during rise time or before return reflections from the
adjacent towers, these are unlikely to occur subsequently.
Example 5-3 Consider a lightning stroke ramp rising at 40 kA/µs,
with a wave front of 0.5 µs, and infinite tail. Tower surge impedance Zt =
100 Ω. The ground wire impedance Zg = 300 Ω. Tower height = 30 m.
Velocity down the tower = 240 m/µs, velocity along the ground (shield)
wire = 300 m/µs. The tower footing resistance = 10 Ω. Coupling factor K = 0.3, span = 300 m. Calculate the tower top voltage, insulation
stress, voltage at base of the tower for the duration of the lightning wave
front, that is, 0.5 µs. Consider a surge channel impedance of 1500 Ω.
The equivalent impedance of half the ground wire and tower
surge impedance is:
Z=
150 × 100
= 60 Ω
150 + 100
The rate of rise of the lightning current = 40 kA/µs.
Therefore after 0.25 µs, the tower top potential is:
Vt =
60
× 40 × 0 . 25 = 576 kV
(1 + 60 / 1500)
Ignoring the lightning channel impedance, it will be 600 kV.
106
CHAPTER FIVE
After 0.25 µs, the voltage buildup on the tower top is reduced by:
The voltage stressing the insulation is:
(− 0 . 818)(1 . 2)( 40) = − 39 . 2 kA/µ s
Vi = (1 − K )600 = 0 . 7 × 600 = 430 kV
Considering reflections from the tower base, the reflection coefficient at the tower base is:
ρ gr =
Rtf − Zt
=
R tf + Zt
10 − 100
= − 0 . 818
110
With the given speed, the travel time of the wave to the base of
the tower is 30/240 = 0.125 µs. Thus, the wave reflected from the
base at ground level will reach the tower top in 0.25 µs. The reflection coefficient at the tower top is:
ρtr =
Z g − 2 Zt
Z g + 2 Zt
=
300 − 200
= 0.2
300 + 200
as
ρtt = 1 + ρtr =
Zg
(0 . 5Z g ) + Zt
=
300
= 1.2
150 + 100
FIGURE 5-21
This reverses the voltage buildup. As per original ramp of 40 kA/µs,
the voltage after 0.5 µs would have been 1200 KV. Considering the
negative ramp of –39.2 kV/µs starting at 0.25 µs, the voltage at 0.5 µs
will be 600 + (600 – 588) = 612 kV. The next reflected wave from
the bottom of the tower will arrive in 0.5 µs. The reflection coefficient of the wave returning to top is 0.2, as calculated above. Thus
the tower-top voltage under goes a change at 0.5 µs:
(0 . 2)(− 0 . 818) = − 0 . 1636 times the first
= − 6 . 413 kA / µ s
Thus, at 0.75 µs, the tower-top potential = 612 + (40 – 6.413 ×
0.98) 60 × 0.25 = 1121 kV. The ladder diagram and the voltage
buildup are as shown in Fig. 5-21. A curve can be drawn through
the tower-top stepped potential profile.
Consider the reflections from the adjacent towers. The surge
impedance of the towers will be:
Zta =
Zt Z g
Zt + Z g
= 75 Ω
Calculation of tower-top potential, ladder diagram.
LIGHTNING STROKES, SHIELDING, AND BACKFLASHOVERS
length, as negative reflections will take place from the adjacent
towers. In Fig. 5-22, apart from stroke impulse current, no power
frequency voltage is present.
The reflection coefficient is:
Zta − Z g
Zta + Z g
= −0 . 6
Therefore, the coefficient of the surge transmitted back to the struck
tower = 1 – 0.6 = 0.4. Waves will arrive simultaneously from both the
directions in 2 µs (as the span is 300 m). The associated reduction
ramp is:
The lighting surge may be at its tail by this time, and a backflashover might have already occurred. Thus, the reflections from
the adjacent towers are not so significant and the reflections from
the base of the tower dictate the reduction in the rate of rise. This
shows the importance of having a lower tower footing resistance.
The voltage at the base of the tower can be calculated similarly.
The stroke current passing down the tower is:
0 . 5Z g
= 0. 6
Therefore, after the first travel time, the voltage at the base of the
tower is:
0 . 6 × 40 × R f = 240 kV / µ s
Subsequently, the current transmitted to ground is:
ρtt = 1 + ρtr =
2R f
Zt + R f
5-11
(5-44)
Backflashover is an important parameter for insulation coordination, and two parameters to control it are: (1) increase the
insulation strength, and (2) reduce the tower footing resistance,
especially some distance from the substation. Figure 5-22 shows
that the pattern of insulator strings voltage for a surge on a tower
top, shielded line. Note the effect of impulse wave risk time on the
insulator voltage. Other factors are tower height, footing resistance,
tower surge impedance, surge channel impedance, width of cross
arms, length of suspension strings, operating voltage, and span
LIGHTNING STROKE TO GROUND WIRE
If a stroke occurs to a ground wire somewhere away from the tower, say
at midspan, then the terminating impedance is half of the surge impedance of the ground wire, and the voltage on the ground wire will be:
Vg =
(− 0 . 6)(0 . 4 )40 = − 9 . 6 kA / µ s
0 . 5Z g + Zt
107
I0 Z g Zs
(2 Z s + Z g )
(5-45)
Voltage on the nearest phase conductor will be KVg. The air clearances must withstand the difference (1 – K)Vg. This voltage is much
higher than any voltage across the insulator strings caused by a
stroke of equal intensity to either the tower or the ground wire. Also
the return time of the negative reflected wave from the adjacent
towers is much longer because of higher effective terminating surge
impedance at the midspan. For this reason, sometimes the midspan
clearances between phase and ground conductors are increased.
However, there is a voltage stress reduction due to predischarge
current that flows between the ground wire and the phase conductor—a phenomena described by Wagner and Hileman.18 This
may delay the breakdown sufficiently to allow the negative reflected
waves from the adjacent towers to prevent a breakdown. Generally,
midspan flashes are rare. Assuming that no flashover occurs at the
midspan, the voltage waves on the ground wires and phase conductors travel to the adjacent towers where these will be modified by
reflections. The tower top voltage in this case is:
Vt′ = Vg Zt /( Zt + 0 . 5Z g )
(5-46)
The voltage stressing the insulation is:
Vi′ =
(1 − K )Vg
(1 + Z g / 2 Zt )
(5-47)
Assuming that there are no midspan flashes, the traveling waves
on ground and phase wires arrive at the adjacent towers, where
they are modified by reflections, and tower flashovers can occur
due to strokes on midspan, yet midspan flashovers are rare.
5-12 STROKES TO GROUND IN VICINITY
OF TRANSMISSION LINES
FIGURE 5-22
Effect of surge front on tower-top potential.
The charges in the lower part of the clouds induce charges of opposite polarity on the ground. The classic picture is that an induced
charge slowly builds up on the phase conductors of a transmission
line, which are grounded through transformers, potential transformers, or neutral resistors. This induced voltage is given by V =
Q/C. A flash to ground in the vicinity of the transmission line discharges the cloud and the charge on the transmission line is simultaneously released, initiating traveling waves in both direction of
half the amplitude.
The theory was significantly advanced by Wagner in 1942.19 He
emphasized the predominating effect of the field of the lightning
channel in comparison to the field of the thundercloud. The problem was further studied by many authors, and a mathematical solution was given by Rusck in 1958.20
These studies basically considered (1) the electric charge Q
which is deposited in the leader channel and (2) the evacuation
of this charge in the return stroke. It was concluded that the magnetic effect of the return-stroke current is much less and the electrostatic effects predominate, and that the voltage on the line will
be a traveling wave in character, unipolar in nature because of
electrostatic effect, and of a polarity opposite to that of the return
stroke current. Chowdhuri and Gross21 based on much observed
108
CHAPTER FIVE
data have drawn attention to the fact that there is also an electromagnetic induction from the return stroke current and magnetic
effects cannot be ignored. The induced voltage can be bipolar in
character depending upon the wave shape of the return stroke
current, and the induced voltage is not entirely a traveling wave
phenomena.
As the induced current is almost at right angles to the conductors, basic field theory is applied for the calculations. The induced
voltage can be much higher then that will occur due to electrostatic
effect only. These voltages can be sufficiently high to cause flashover
of the insulation of lines in higher voltage range.
The mechanism of induction can be summarized as:
■
Charged cloud induces charges on the line.
When cloud discharges, the voltage and current traveling
waves occur.
■
The stepped leader further induces charges on the
conductors.
■
When stepped leader is neutralized by return stroke, the
charges on conductors are released, producing traveling waves
similar to cloud discharge.
■
The residual charges in return stroke induce an electrostatic
field in vicinity of line and hence induce a voltage.
■
The di/dt of the return stroke produces a magnetically
induced voltage on the line.
The parameters affecting these phenomena are many: height of
the line, peak magnitude of the return-stroke current, cloud height,
wave shape of return-stroke current, perpendicular distance of the
struck point from line, horizontal distance along ground, return
stroke velocity, and presence of shield wires (the induced voltages
may be reduced from 10 to 30 percent). A lossless line and perfectly
conducting ground is assumed.
Whether the line or the ground will be struck can be ascertained
from the simple geometric relations in Fig. 5-23. If the perpendicular distance of the leader stroke is greater than a critical distance, the
leader will strike the ground, otherwise the line. The least distance
of ground strike can be calculated from the following expression:
= rs
rs > h
rs ≤ h
5-13
SHIELDING
A shielding angle of 30° was popular for many years, until in the
1950s the failure rate on double circuit lines on towers up to 45-m
high increased. This led to further study of shielding practices. It
is well known that taller structures attract more lightning strokes.
We defined attractive radius, the effect of return stroke current, and
height of the structure in Eq. (5-10). Eriksson’s equation for phase
conductors and shield wires is:
ra = 0 . 67h 0.6 (I p )0.74
■
y = rs2 − (rs − h )2
Referring to Fig. 5-23, rs is the striking distance, h is the height of
the conductor above ground, and y = horizontal distance to the
strike point.
(5-48)
(5-49)
Comparing with Eq. (5-10), Eriksson assumed that the attractive
radius for shield wires and phase conductors will be reduced by
80 percent.22
It is realized that several other parameters should also influence striking distance, that is, the charge distribution along leader
stroke, return stroke velocity, presence of other conductors, and
polarity of the leader stroke.
For each value of stroke current, the striking distance rs and rg
define a surface ABCD, of which, the portion BC is the exposed
boundary (Fig. 5-24). All strokes crossing BC are assumed to land
on the phase conductors. The arc BC shrinks with increasing stroke
currents, that is, increasing rs until it becomes zero for a certain
rs2. For smaller currents the exposure increases, but we need to
consider rs1 for the critical stroke current (I = 2V/Z). A flashover
cannot occur if:
rs1 ≥ rs2
(5-50)
This clearly shows that the shielding angle should be reduced
as the height increases. For partially shielded lines, the average
number of strokes crossing the arc BC can be determined from
geometric considerations. The breakdown gradient to the ground
plane may differ from that of the shielding and the conductors.
This is accounted for in a factor Ksg, Rsg in Fig. 5-24, Rsg = rs Ksg. In
Fig. 5-24, the number of strokes that terminate on phase conductor, shielding failure rate (SFR), is given by the area formed by Dc,
length of line and ground flash density:
SFR = 2N g Dcl
(5-51)
where l is the length of the line.
The probability of occurrence of this current is f(I) dI, so that SFR
for all currents is:
Im
SFR = 2N gl ∫ Dc f (I )dI
(5-52)
3
The minimum value of current = 3 kA is from CIGRE, and at the
maximum current Im, the three arcs coincide and Dc = 0. All strokes that
terminate on phase conductors will not result in flashover, therefore
the equation for shielding failure flashover rate (SFFOR) becomes:
Im
SFFOR = 2N gl ∫ Dc f (I )dI
(5-53)
Ic
Ic is defined in Eq. 5-33. Anderson suggested that the average value
of Dc over the interval from Ic to Im is half of the value of Dc at I = Ic,
and is a constant. Thus:
FIGURE 5-23
Direct and indirect lightning strokes.
SSFOR = N glDc P(I m ≥ I ≥ I c )
(5-54)
LIGHTNING STROKES, SHIELDING, AND BACKFLASHOVERS
FIGURE 5-24
109
The geometric model for shielding of transmission lines.
We use log normal distribution to solve this equation, which can
be written as:
N glDc[Q(I c ) − Q(I m )]
(5-55)
where: Q(I ) = 1 − F(I )
To illustrate the geometric relations, a section of Fig. 5-24 is
enlarged as shown in Fig. 5-25a. Figure 5-25b is the Eriksson model.
From this geometric construction:
Dc = rs[cos θ − cos(α + β )]
(5-56)
D g = rs cos(α − β )
where:
β=
(h − y) 1 + tan 2 α
1
sin −1
2
2rs
θ = sin −1
rg − y
rs
α = tan −1
(5-57)
a
h− y
For Im, where all striking distances coincide at a single point:
a = rs2 − (rg − h )2 − rs2 − (rg − y)2
rgm =
(h + y)/ 2
1 − (rs /rg )sin α
r
I m = gm
A
(5-58)
1/ b
(rg = AI sb ) (Table 5 - 3)
FIGURE 5-25
(a) Details of Fig. 5-24. (b) Eriksson’s modifications.
110
CHAPTER FIVE
TA B L E 5 - 4
The Pathfinder Project reports results of 640 km of 110 to 220 and
345-kV lines, statistical survey covering 84,000 km/year.
Table 5-4 indicates the importance of backflashes and shielding
failures. The majority of shielding failures are top single-conductor
trip outs (39 out of 45). The backflashovers involving both circuits
of double circuit lines are 20 out of 46 trip outs.
Another similar study is the CIGRE study, results of which are
summarized in Table 5-5 and Fig. 5-26.24,27 These clearly indicate
that shielding angle and the height of the tower are two major factors in reducing the standard trip out rates (STR). The STR is defined
as the number of outages caused by lightning per 100 km/year.
Summary of Pathfinder Operations
Edison Electric Institute Research
Project No. RP-50
DESCRIPTION OF DATA
NO.
Total Pathfinder instrument operations
167
Number of separate lightning strokes
111
Number of strokes causing tripouts
94
Number of strokes causing shielding failure
51
TYPE OF FAULT FROM SHIELDING FAILURES
5-14
Top single conductor tripouts
39
Middle single conductor tripouts
2
Multiple conductor tripouts
3
Double circuit tripouts
1
No tripout
6
Number of strokes causing backflashovers
52
TYPE OF FAULT FROM BACKFLASHOVERS
Top single conductor tripouts
21
Multiple conductor tripouts
5
Double circuit tripouts
20
No tripout
6
Indicated number of negative polarity strokes
103
Indicated percentage negative polarity strokes
93
Instrument failures
x c = −d p + rs2 − (rsg − h p )2
8
rg − (h + y)/ 2
rs
≈
rg
rs
−
1 h + y
rs 2
(5-60)
hs = rsg − rs2 − x c2
(5-59)
An extensive study for HV and EHV lines is “Pathfinder Project”
conducted by Edison Electric Institute and reported in Refs. 23 and 24.
TA B L E 5 - 5
rsg ≥ h p
Note that for factor Ksg = 1, Rsg = rs. Draw an arc with center C
and radius rs passing through the outermost conductor. It may cut
the vertical line through the middle conductor at some point S. A
ground (shield) wire placed at this point will protect all three-phase
conductors. Analytically the height of the shield wire is:
For perfect shielding the angle is given by:
α p = sin −1
SHIELDING DESIGNS
We will discuss two methods of shielding designs. One method is
based upon the work of Whitehead (Fig. 5-27) and the concepts
discussed above. This figure gives the critical mean shielding angle
based upon the conductor height hp, (hp = y in Fig. 5-27) and conductor to ground wire spacing c. These quantities are normalized
in per unit of striking distance rs. The field results of Pathfinder
Project correlate well with this method.
The second method is a simple geometric construction for
placing the shield wires based upon the electromagnetic model
of shielding.25 The procedure can be discussed with reference to
Fig. 5-28a. First find the critical shielding current. It is generally
increased by 10 percent. Based upon this critical current, the striking distance rs is known.
To locate the center C for describing an arc with radius equal
to the striking distance rs, the ordinate is given by rsg and the
abscissa is:
(5-61)
A qualification applies that the minimum clearance required
between the phase conductor and shield wire should be observed.
If this clearance is Sps and hs is less than Sps, then make Sps = hs.
Lightning Outages for 100 km-yr and 40 Thunder Days per year (STR = 40) for Five HV and EHV
Lines Operating in Comparable Environments except for the Heights and the Shielding Angles.
CIGRE
LINE NO.
KM-YR
U (KV)
U (50%)
(KV)
TD (YR–1)
Rg (Ω)
H (M)
Y (M)
p (DEG)
SC (M)
STR-40
32*
1760
345
1600
40
5
43
34
31
23.4§
5.70
†
1570
345
1600
43
5
43
25
22
12.6
3.44
30
‡
5900
230
1500
40
5
28
16
15
–4.8
0.24
39
‡
3140
345
1600
40
5
29
16
–15
–27.7
0.19
40‡
4460
220
1580
32
12
27
19
14
–4.6
0.09
31
*
Double-circuit vertical conductor configuration, one shield wire.
Double-circuit vertical conductor configuration with two shield wires. Middle conductor data given; 67 percent of outages on this phase.
‡
Single-circuit horizontal conductor configuration with two shield wires.
§
Positive values of exposure arc Sc are an index of the shielding wire inefficiency.
†
LIGHTNING STROKES, SHIELDING, AND BACKFLASHOVERS
FIGURE 5-26
111
Standard trip out rates (STR) for different types of tower construction.4,24
The arc thus drawn in Fig. 5-28a may not cross the vertical through the middle conductor. Two shield wires are then
required. Draw another arc with P3 as center and Sps as the radius
(Fig. 5-28b). The intersection of these two arcs gives the location of the shield wire. The second shield wire is symmetrically
placed.
Example 5-4 Calculate the SFFOR for a transmission line with
two shield wires, located at 30 m, conductor height = 25 m, shielding angle = 30°, Ic = 15 kA, Ng = 4.
FIGURE 5-27
Let us use IEEE equations for rs and rg, from Table 5-3. These
give rs = rg = 46.5 m, rc/rg = 1
rgm =
(30 + 25)/ 2
= 55 m
1 − sin 30 °
I m = (55 / 8)1/ 0.65 = 19 . 4 kA
This gives Dc = 2.51 m.
Critical shielding angle in terms of normalized geometry.24
β = 3 . 56°
θ = 27 . 5 °
112
CHAPTER FIVE
TA B L E 5 - 7
Median and Log Standard Deviations
for CIGRE Distribution
MEDIAN MI
BETA aI
3–20
61.1
1.33
>20
33.3
0.605
CURRENT RANGE (KA)
and then the values of Q:
zc =
ln(15 / 61 . 1)
= − 1 . 05
1 . 33
Qc = 1 − 0 . 31e −1.1025/1.6 = 0 . 844
zm =
ln(19 . 4 / 61 . 1)
= − 0 . 863
1 . 33
Qm = 1 − 0 . 31e −0.863/1.6 = 0 . 819
Therefore:
SFFOR = 4 × 100 × 2 . 51 × 0 . 025 × 10−3 = 0 . 0251/100 km − years.
Table 5-8 shows required shielding angle for SFFOR of
0.05/100 km yr.26
Example 5-5 Consider an overhead line with the configuration
as shown in Fig. 5-29. The spacing between conductors = 5 m, the
minimum separation of shield wire as shown = 5 m, tower height =
27 m. TD (keraunic level) = 27. The insulator strings have a CFO =
1500 kV, the surge impedance = 500 Ω. Estimate the shielding
flashover rate. Redesign the shielding for better protection, using
the two methods of calculations as described above. Is one shield
wire adequate?
The shielding design is calculated based upon Figs. 5-27 and 5-28.
F I G U R E S 5 - 2 8 Geometric constructions for placement of shield wires:
(a) one shield wire adequate; (b) two shield wires required.
An approximation to CIGRE cumulative distribution is shown
in Table 5-6, and median and log standard deviations are shown in
Table 5-7. Using the values from these tables first calculate:
z=
ln I − ln M1
β1
TA B L E 5 - 6
RANGE OF CURRENT I (KA)
3–20
20–60
60–200
(a) Based upon Fig. 5-27. Multiply the critical current by 1.1,
which gives 6.6 kA. Then rs = 30.3 m. Let Ksg = 1.
Let height of the conductor hp = 22 m. Normalize with
respect to rs: hp = 22/30.3 = 0.726
In Fig. 5-27, we may consider c approximately equal to 5 m.
Thus c/rs = 5/30.3 = 0.166.
As a first approximation, we can use the curve marked
c/rs = 0.2. A shielding angle of 12° can be read. Check back to
c/rs estimate used in the calculation. From the geometry
shown in Fig. 5-27,
c = sps / cos θ s = 5 . 1 m
TA B L E 5 - 8
Required Shielding Angle for SFFOR
of 0.05/100 km-yr.26
GROUND FLASH
PHASE
SHIELDING
SHIELDING
DENSITY (FLASHES GROUND WIRE CONDUCTOR
ANGLE
ANGLE
km2 YEAR)
HEIGHT (m) HEIGHT (m) IEEE (DEG.) CIGRE, (DEG.)
CIGRE Cumulative Distribution
Approximations
APPROXIMATE EQUATION OF Q
0.5
3.0
–z2/1.6
1 – 0.31e
0.50–0.35Z
0.278e
–z2/1.7
5.0
30
22
38
42
45
37
12
28
30
22
33.5
36
45
37
30
33
32
35
45
37
4
17
19
LIGHTNING STROKES, SHIELDING, AND BACKFLASHOVERS
113
And the ordinate is 30.3 m. A graphical construction gives
approximately the same spacing as calculated before.
5-15
BACKFLASHOVERS
An outage can occur from backflash, which occurs if lightning strikes
a shield wire or tower. The potential rise of the tower top due to flow
of lightning current may exceed the insulation strength of the insulators. An arc between the ground wire and phase conductor will
inject some portion of the lightning current into the phase conductors. Figure 5-30 shows a backflash. It is an important mechanism
for surge transfer and breakdown and is discussed further.
There are two methods in use: CIGRE method and IEEE
method. The calculations are performed using computer programs
because of the iterative nature of the calculations. Anderson estimating method using a constant 2-µs front with minor modifications is adopted by IEEE working group.27 The basic concepts of a
backflashover are explained in Sec. 5-10, for example, the voltage
across the insulation has to be greater than the CFO, for a certain
critical current Ic. Thus, for a certain stroke current, the probability
of flashover can be expressed as:
∞
FIGURE 5-29
Placement of shield wires.
P(I ≥ I c ) =
∫ f (I )dI
(5-62)
Ic
Thus, the initial estimate of c/rs is acceptable. The horizontal
spacing between the phase conductor and ground wire is:
hs tan 12 = 5 × 0 . 212 = 1 . 06 m
°
Two ground wires with spacing between them = 7.88 m
are required. See Fig. 5-29.
(b) Based upon Fig. 5-28. The center of the circle is located
at C. The abscissa from Eq. (5-60) is:
xc = −5 +
30 . 32 − (30 . 3 − 22)2 = 29 . 14 m
FIGURE 5-30
The BFR is then:
BFR = 0 . 6N L P(I c )
(5-63)
where NL are the number of strokes to transmission line, estimated
from:
NL = Ng
(28h 0.6 + S g )
10
(5-64)
The Sg is shown in Fig. 5-20c.
Note the factor 0.6. As stated before, the flashovers within the
span can be neglected, and the voltages at the tower for strokes
Illustration of a backflashover.
114
CHAPTER FIVE
within the span are much lower compared to voltages for strokes on
the tower itself. To account for the strokes terminating on the tower,
adjustments are made to the BFR.
The voltage across insulation increases as the time to crest decreases.
Thus, Eq. (5-63) should be modified to consider various fronts:
∞
BFR = ∫ (BFR ) f (t f )dt f
(5-65)
0
Above the corona inception voltage, the ground wire surge
impedance decreases and the coupling factor K increases. The critical current increases as (1 – K) decreases. Corona does not significantly alter BFR.
The CIGRE method basically starts with selection of crest time.
For 115 to 230 kV lines, a front of 2.5 µs is appropriate, and for
345 kV and above, a front of 4.0 µs is appropriate. Assume a value
of Ri equal to 50 percent of R0, and solve for Ic:
Ic =
Ri Zg
CFONS − VPF
, Re =
R e (1 − K )
Z g + 2R i
(5-66)
where CFONS is the nonstandard surge critical flashover, given by:
V
2 . 82
CFONS = 0 . 977 +
1 − 0 . 2 PF CFO
CFO
τ
(5-67)
VPF = K PFVLN
τ=
Zg
Ri
(5-68)
Ts
where KPF is a factor which depends upon the phase configuration,
VLN is the peak line to neutral voltage, Zg is the surge impedance of
the ground wire, t is time constant of the tail, much akin to R/L,
L = Zg /v (span length) = ZgTs, and v is velocity of light.
FIGURE 5-31
Calculate IR, iterate on Ri, and when it is satisfactory, calculate
median front for Ic; if this does not match assumed front, start over.
CIGRE computer program BFR simplifies the calculation. It is obvious that BFR will vary with CFO and line construction.
Here we will use EMTP simulation and appropriate modeling,
taking into account all the variable factors. The results of the simulation should be more accurate than hand calculations and other
iterative methods, though no test verification is provided.
Example 5-6 This example is an EMTP simulation of a lightning
stroke to the top of a transmission line tower. The following system
data applies:
(i) Towers. Framed steel structure for 345-kV, three-phase,
60-Hz transmission line, the configuration of the phase conductors, shield wires, height of the tower, and other dimensions are shown in Fig. 5-31. There are two shield wires, and
each phase consists of two bundle conductors spaced 18 in
apart, 95400 circular mils (equivalent copper = 600000
circular mils), Aluminium Cable Steel Reinforced (ACSR).
The span is 250 m (820 ft) and the sag = 4 m.
(ii) System configuration. Figure 5-32 shows the system configuration. 250-m spans between the last three transmission
line towers T1, T2, and T3 are modeled with a FD model as
discussed in Chap. 4. Similarly the FD model for the 40-km
long line is derived. The line is terminated in a 200-MVA,
wye-delta connected, 345 to 138 kV transformer at no-load.
The transformer is modeled with bushing, winding, and
interwinding capacitances (see Chap. 14).
(iii) Tower surge impedance and footing resistance. Each tower has a
surge impedance of 50 Ω and a footing resistance of 15 Ω,
controlled by an equivalent Norton current source to account
for change in the resistance with surge current. There are no
counterpoises.
Tower configuration for Example 5-6.
LIGHTNING STROKES, SHIELDING, AND BACKFLASHOVERS
FIGURE 5-32
System configuration for study of backflashover.
(iv) Insulators—CFO. A CFO of 1210 kV is considered. These
can be represented by voltage-dependent switches in parallel with capacitors connected between phases and tower. The
capacitors simulate the coupling effect of conductors to the
tower structure. Typical capacitance values for suspension
insulators are 80 pF/unit. Ten insulators in a string will have a
capacitance of 10 pF/string. An expression for the backflashover of insulators28 considers a simplified model with an ideal
short-circuit representation:
Vvt = K1 +
where:
K2
t 0.75
(5-69)
K1 = 400L
K2 = 710L
Vvt = Flashover voltage, kV
L = length of insulator, m
t = Elapsed tie after lightning stroke, µs
FIGURES 5-33
115
(v) Lightning surge. A surge of 60 kA, 3/100 µs impacts the
tower T2, as shown in Fig. 5-32.
(vi) Surge arrester. The simulation is repeated with a 258-kV,
metal-oxide, gapless surge arrester at 200-MVA transformer
terminals which will be invariably provided. Also a surge
arrester on the transformer secondary (low-voltage side)
terminals is required (Chaps. 14 and 20).
The results of the simulation are shown in Figs. 5-33
through 5-37, without 258-kV surge arrester.
Figure 5-33a, b, and c shows that the insulators in phases b
and c of towers T2 and T3 flash over. None of the insulators in
phase a on any three towers flash over. The insulators on phase b
on T1 also do not flash over.
Figure 5-34 shows the current in the tower footing resistance.
Note that the maximum flashover current occurs in T3, a tower
ahead of the one that is struck. The reflection coefficient will
be different because of termination of the line in a transformer.
Insulator flashover currents of towers T1, T2, and T3. (Continued)
116
CHAPTER FIVE
FIGURES 5-33
Figure 5-35 shows tower-top potential of the struck tower, T2.
Figure 5-36a shows the gap voltages (voltages across the insulator
strings) in phases a, b, and c of tower T2. Figure 5-36b is the picture
of insulator flashovers towers T1, T2, and T3. Figure 5-37a shows
the voltages across the 200-MVA transformer windings.
When a surge arrester is applied to the transformer primary
windings, Fig. 5-37b depicts the voltage on the transformer primary
windings. Figure 5-37c shows current through the surge arrester.
Figure 5-38 illustrates that no flashover of insulators occurs on
towers T1 and T2, and only insulator strings of phases b and c of
Tower T3 flashover.
The effect of tower footing resistance may not be so obvious in
this example, but it impacts the tower top potential and overvoltage
for backflashover, as stated before. Figure 5-39 illustrates the effect
of tower grounding on the tower top potential. For the first 0.2 µs, the
(Continued )
tower top potential is not affected by the tower grounding. CIGRE
has accepted the following volt–time curve for line-insulator flashover based upon the work in Ref. 29.
V f = 0 . 4W +
where:
0 . 71W
t 0.75
(5-70)
W = line insulator length, m
t = time to breakdown, s
Vf = flashover voltage for negative surges, MV
Counterpoise is used in the areas of high resistivity. If this is
not sufficient to achieve the required backflash performance, the
insulator string length can be increased, in other words, CFO can be
increased as demonstrated in this example.
LIGHTNING STROKES, SHIELDING, AND BACKFLASHOVERS
FIGURE 5-34
FIGURE 5-35
117
Tower footing currents.
Tower top potential for tower T 2.
It will be prohibitively expensive to design a system to cater to
the worst lightning conditions, and a statistical approach is taken in
the chapter on insulation coordination (Chap. 17).
PROBLEMS
1. What are K changes and M discharges? What is the typical
stepped leader duration before a connection with the ground
is made? Describe the significance of striking distance. Write
three different expressions given in this chapter, explaining the
difference between these.
2. Given TD = 30, h = 30 m, b = 6 m, calculate the number
of lightning strokes 100 km/year with the various analytical
expressions given in this chapter. Is it necessary to calculate
the attractive radius?
3. Which state in the United States experiences the highest
lightning activity?
4. What is 98 percent probability of a peak current in a lightning stroke? What can be the maximum peak?
5. Calculate the tower-top and tower-base potential for a
period of a lighting strike, impulse 60 kA/µs occurs at top of a
118
CHAPTER FIVE
FIGURE 5-36
(a) Voltage across insulator strings of tower T 2. (b) Tower insulator flashovers without surge arresters.
FIGURE 5-37
200-MVA transformer primary voltage (a) without and (b) with surge arrester, and (c) current through the surge arrester.
119
120
CHAPTER FIVE
FIGURE 5-38
Tower insulator flashovers with a 258-kV metal-oxide surge arrester applied at 200-MVA transformer primary windings.
7. In Prob. 5, consider a coupling factor K = 30 percent, what
is the voltage stress on the insulation? If the insulators have a
CFO of 1600 and 1000 kV, will a back flashover occur?
8. The line in Prob. 5 is located in an area with keraunic
level of 60. Calculate shielding flashover rate (SFO) in flashovers/
100 km years, using the expressions in this chapter.
9. Calculate the critical stroke current and the striking distance. Consider a surge impedance of 400 Ω.
10. Consider that the configuration of the transmission line in
Example 5-6, as shown in Fig. 5-31. Ignoring the shield wire
system shown in this figure, redesign using expressions in this
chapter.
FIGURE 5-39
Effect of counterpoises on tower-top potential.
transmission tower for one µs. Consider tower footing resistance of 30 Ω, tower surge impedance of 150 Ω, neglect lightning channel impedance. The tower has one ground wire of
surge impedance of 400 Ω. Consider a speed of 240 m/µs for
the surge to travel down the tower, and a tower-height of 36 m.
What is the maximum tower-top potential reached in one µs?
6. In Prob. 5, if the adjacent towers are 300 m apart, calculate
the reflection from the adjacent towers and its travel time to reach
the struck tower. How does it affect the tower-top potential?
11. In Prob. 5, the lightning strike occurs at the ground wire
100 m away from a tower. Consider the same stroke current as
specified in Prob. 5. Determine the voltage of the closet tower
top after µs of the strike.
12. Repeat Prob. 5 with a tower footing resistance of 0 and 5 Ω.
What is the maximum tower-top voltage in each case?
13. Describe CIGRE iterative method of BFR calculations.
Why is CFONS different from conventional CFO? Relate it to a
BIL of 1000 kV.
14. How does shielding of substations differ from that of
transmission lines? Substation shielding is also provided
by high masts. Comment on their efficacy and shielding
angle.
LIGHTNING STROKES, SHIELDING, AND BACKFLASHOVERS
REFERENCES
1. E. R. Williams, “Triple Pole Structure of Thunderstorms,”
J. Geophysics Research, vol. 94, pp. 13151–13167, 1989.
2. M. W. Maier, A. G. Boulangie, and R. I. Sax, “An Initial Assessment of Flash Density and Peak Current Characteristics of
Lightning Flashes to Ground in South Florida,” U.S. Nuclear Regulatory Commission, Washington, DC, NUREG/CR-102, 1979.
3. AIEE Committee Report, “A Method of Estimating Lightning
Performance of Transmission Lines,” AIEEE Trans. Part III,
vol. 69, pp. 1187–1196, 1950.
4. J. G. Anderson, EHV Transmission Reference Book, Edison
Electric Company, New York, 1968.
5. CIGRE Report, Electra, no. 22, pp. 139–147, 1972.
6. K. B. McEachron, “Lightning Stroke on Empire State Building,”
AIEEE Trans. vol. 60, pp. 885–962, 1941.
7. Westinghouse Transmission and Distribution Reference Book, East
Pittsburg, PA, 1964.
8. R. B. Anderson and A. J. Eriksson, “A Summary of Lightning
Parameters for Engineering Applications,” CIGRE Electra,
no. 69, pp. 65–102, March 1980.
9. K. Berger, R. B. Anderson, and H. Kroninger, “Parameters of
Lightning Flashes,” CIGRE Electra, no. 41, pp. 919–932, July
1975.
10. J. G. Anderson, “Lightning Performance of Transmission Lines,”
Chapter 12 of Transmission Line Reference Book, 345 kV and
Above, 2d ed., EPRI, Palo Alto, CA, 1987.
11. CIGRE Working Group 33.01, “Guide to Procedures for
Estimating the Lightning Performance of Transmission Lines,”
Brochure no. 63, Oct. 1991.
12. ANSI/IEEE Std. C62.42 IEEE Guide for the Application of Gas
Tube Arresters-Low-Voltage Surge Protective Devices, 1987.
13. IEEE Working Group Report, “Estimating Lightning Performance of Transmission Lines II-Updates to Analytical Models,”
IEEE Trans. PD, vol. 8, pp. 1257–1267, 1993.
14. A. J. Eriksson, “The Incident of Lightning Strikes to Power
Lines,” PWRD-2, vol. 3, pp. 859–870, July 1987.
15. A. K. Mousa and K. D. Srivastva, “Effect of Shielding by Trees
on Frequency of Lightning Strokes to Power Lines,” IEEE Trans.
PWRD, vol. 3, pp. 724–732, 1988.
16. M. Kawai, “Studies of Surge Response on a Transmission
Tower,” IEEE Trans. PAS, vol. 83, pp. 30–34, 1964.
17 C. F. Wagner and A. R. Hileman, “A New Approach to the
Calculation of Lightning Performance of Transmission Lines,
Part III,” AIEEE Trans. Part III, pp. 589–603, 1960.
18. C. F. Wagner and A. R. Hileman, “Effect of Pre-Discharge
Currents on Line Performance,” IEEE Trans. PAS, vol. 82,
pp. 117–131, 1963.
19. C. F. Wagner and G. D. McCain, “Induced Voltages on Transmission Lines,” AIEEE Trans. no. 61, pp. 916–930, 1942.
20. R. Rusck, “Induced Lightning Overvoltages on Power Transmission Lines with Special Reference to Overvoltage Protection
of Low-Voltage Networks,” Trans. Royal Institute of Tech.,
Stockholm, Sweden, no. 120, 1958.
121
21. P. Chowdhuri and E. T. B. Gross, “Voltages Induced on Overhead Multi-conductor Lines by Lightning Strokes,” Proc. IEE,
vol. 116, pp. 561–565, 1969.
22. A. J. Eriksson, “An Improved Electromagnetic Model for Transmission Line Shielding Analysis,” PWRD-2, vol. 3, pp. 871–886,
July 1987.
23. D. W. Gilman and E. R. Whitehead, “The Mechanism of Lightning Flashover on HV and EHV Lines,” Electra, 27, pp. 69–89,
1973.
24. E. R. Whitehead, “CIGRE Survey of the Lightning Performance
of Extra High Voltage Transmission Lines,” Electra, vol. 33,
pp. 63–89, 1974.
25. P. Chowdhuri, Electromagnetic Transients in Power Systems,
Research Studies Press Ltd., Somerset, England, 1996.
26. ANSI/IEEE Standard 1313.2. IEEE Guide for Application of
Insulation Coordination, 1999.
27. IEEE Working Group on Lightning Performance of Transmission Lines, “A Simplified Method of Estimating Lightning
Performance of Transmission Lines,” IEEE Trans. PAS,
vol. 104, pp. 919–932, April 1985.
28. IEEE Report, “Modeling Guidelines for Fast Front Transients,”
IEEE Trans. PD, vol. 11, pp. 493–506, Jan. 1996.
29. E. R. Whitehead, “Protection of Transmission Lines,” in
Lightning, vol. 2, R. H. Golde, ed. Academic Press,
New York, pp. 697–745, 1981.
FURTHER READING
H. R. Armstrong and E. R. Whitehead, “Field and Analytical Studies of Transmission Line Shielding,” IEEE Trans. PAS, vol. 87,
pp. 270–271, 1968.
K. Berger, “Observations on Lightning Discharges,” J. Franklin Institute, No. 283, pp. 478–482, 1967.
G. W. Brown, and E. R. Whitehead, “Field and Analytical Studies
of Transmission Line Shielding-II,” IEEE Trans. PAS, vol. 88.
pp. 617–626, 1968.
V. V. Burgsdrof, “Lightning Protection of Overhead Lines and
Operating Experience in USSR,” Proc. CIGRE, Report 326, 1958.
P. Chowdhuri, “Lightning Induced Overvoltages on MultiConductor Overhead Lines,” IEEE Trans. PWRD, vol. 5, pp. 658–667,
1990.
M. Darveniza, F. Popolansky and E. R. Whitehead, “Lightning Protection
of EHV Transmission Lines,” Electra, vol. 41, pp. 36–39, July 1975.
EPRI, Transmission Line Reference Book 345 kV and Above, 2d ed.,
Chapter 12, Palo Alto, CA, 1987.
R. H. Golde, “Lightning Surges on Overhead Distribution Lines
Caused by Indirect and Direct Lightning Strokes,” AIEE Trans.,
vol. 73, Part III, pp. 437–446, 1954.
R. H. Golde, Lightning Protection, Edward Arnold Publishers,
London, 1973.
P. R. Krehbiel, M. Brook, and R. A NcRory, “An Analysis of the
Charge Structure of Lightning Discharges to Ground,” J. Geophysics
Research, vol. 84, pp. 2432–2451, 1979.
A. C. Lewis and S. C. Mar, “Extension of the Chowdhari-Gross
Model for Lightning Induced Voltage on Overhead Lines,” IEEE
Trans. PWRD, vol. 1, pp. 240–247, 1986.
122
CHAPTER FIVE
D. R. MacGorman, M. W. Maier, and W. D. Rust, “Lightning Strike
Density for the Contiguous United States from Thunderstorm
Duration Records,” U.S. Nuclear Regulatory Commission, NUREG/
CR-3579, 1984.
NASA, Technical Memorandum 82473, Section 11, Atmospheric
Electricity.
NASA Technical Memorandum 473, Section II, Atmospheric Electricity, 1982.
M. A. Sargent and M. Darvenzia, “Tower Surge Impedance,” IEEE
Trans. PAS, vol. 88, no. 5, pp. 680–687, 1969.
S. Yokoyama, “Advanced Observations of Lightning Induced
Voltages on Power Distribution Lines-I,” IEEE Trans. PWRD, vol. 1,
pp. 129–139, 1986.
S. Yokoyama, “Advanced Observations of Lightning Induced
Voltages on Power Distribution Lines-II,” IEEE Trans. PWRD, vol. 4,
pp. 2196–2203, 1989.
CHAPTER 6
TRANSIENTS OF SHUNT
CAPACITOR BANKS
In Chap. 2, capacitor switching transients in lumped circuits were
studied. These transients are of importance, as large capacitor
banks are finding applications and acceptability in industrial distribution and utility systems. Shunt power capacitors have practically replaced rotating synchronous condensers, and are used on
power transmission systems at voltage levels up to 500 kV, bank
sizes ranging from a few Mvar to 300 Mvar. The size and location
is based on the load flow and stability studies of the transmission
network. These give rise to current and voltage transients, stress
the switching devices and insulation systems, and can be detrimental to the sensitive loads. The switching transients of capacitor
banks are at a frequency higher than that of the power frequency
(Chap. 2). Historically, capacitor-switching transients have caused
problems that have been studied in the existing literature. During
the period from the late 1970s to 1980s, switching of capacitor
banks in transmission systems caused high phase-to-phase voltages
on transformers and magnification of transients at consumer-end
distribution capacitors. Problems with switchgear restrikes caused
even higher transients. Problems were common in industrial distributions with capacitors and dc drive systems, and the advent
of pulse width modulation (PWM) inverters created a whole new
concern of capacitor switching. These concerns and also the phenomena of secondary resonance, when a large utility capacitor
bank is switched, while a capacitor bank at the downstream lowvoltage distribution system remains energized, are investigated in this
chapter; discussions are confined to shunt capacitor banks. The series
capacitors and static var compensators (SVCs) used to enhance the
power system stability limits are discussed in Chap. 15.
6-1
ORIGIN OF SWITCHING TRANSIENTS
The switching transients originate from:
4. Possible secondary resonance when the capacitors are applied
at multivoltage level (i.e., at 13.8-kV level as well as at 480-V
level) in a distribution system
5. Restrikes and prestrikes in the switching devices
6. Autoclosing with precharge on the capacitors
A transient, from its point of origin, will be propagated in either
direction in the distribution system and will be transferred through
the transformer inductive/capacitive couplings to other voltage levels.
Transformer part-winding resonance can occur.1
The application of shunt capacitors can lead to the following
additional side effects:
■
Bring about severe harmonic distortion and resonance with
load-generated harmonics
■
Increase the transient inrush current of power transformers
in the system, create overvoltages, and prolong its decay rate1
■
Stress the capacitors themselves due to switching transients
■
Increase the duty on switching devices, which may be
stressed beyond the specified ratings in ANSI/IEEE standards2,3
■
Discharge into an external fault, and produce damaging
overvoltages across current transformer (CT) secondary
terminals
■
Impact the sensitive loads, that is, drive systems and bring
about a shutdown
1. Switching of a shunt capacitor bank, which may include
switching on to a fault
6-2 TRANSIENTS ON ENERGIZING A SINGLE
CAPACITOR BANK
2. Back-to-back switching, that is, switching of a second
capacitor bank on the same bus in the presence of an already
energized bank
Consider the transients on energizing a single shunt capacitor
bank. This assumes that there are no other capacitor banks in the
immediate vicinity that will impact the transient behavior, though
practically this will not be the case. On connecting to a power
source, a capacitor is a sudden short circuit because the voltage
across the capacitor cannot change suddenly (Chap. 2). The voltage
3. Tripping or de-energizing a bank under normal operation
and under fault conditions
123
124
CHAPTER SIX
of the bus to which the capacitor is connected will dip severely.
This voltage dip and the transient step change is a function of the
source impedance behind the bus. The voltage will then recover
through a high-frequency oscillation. In the initial oscillation, the
transient voltage can approach 2 per unit of the bus voltage. The
initial step change and the subsequent oscillations are important.
As these are propagated in the distribution system, they can couple across transformers and can be magnified. Transformer failures
have been documented.4,5 Surge arresters and surge capacitors
can limit these transferred overvoltages and also reduce their
frequency.6 In a part-winding resonance, the predominant frequency of the transient can coincide with a natural frequency of the
transformer. Secondary resonance, described further in this chapter,
is a potential problem, and the sensitive loads connected in the
distribution system may trip.
Example 6-1 In Chap. 2, switching transient of a series RLC circuit with sinusoidal excitation was discussed. A practical application is illustrated in Fig. 6-1. To improve the load power factor, a
6-Mvar capacitor bank is switched on 13.8-kV bus by closing its circuit breaker CB1. The term “bank” by definition means an assembly
with all switching accessories, protective equipment, and controls
required for a complete operating installation. The distribution can
be reduced to Thévenin impedance, as seen from 13.8-kV bus. For
switching transient studies, this is not permissible and complete
distribution system should be modeled in all its details. This is so
because much like lightning transients, the switching transients
will be transmitted and reflected from the impedance discontinuities and will be transferred through the transformers windings too,
altering the time-domain profile of the calculated transient. With
this explicit qualification, this example illustrates the nature
of capacitor switching transients. With this simplification, the
FIGURE 6-2
FIGURE 6-1
Circuit diagram for the study of switching transients of
a 6-Mvar capacitor bank.
equivalent impedance, as seen from the 13.8-kV bus, is Z = (0.0115 +
j0.1056, per unit 100-MVA base). Thus, the transient analysis is
reduced to excitation of a series RLC circuit. The reacrance in series
with capacitor bank shown in this figure is not considered.
Figures 6-2 and 6-3 show EMTP simulation of current and voltage transients in phase a. With the given parameters and looking
Switching current transient of 6-Mvar capacitor bank, Fig. 6-1.
TRANSIENTS OF SHUNT CAPACITOR BANKS
FIGURE 6-3
Voltage transient, 13.8-kV bus 1, on switching of 6-Mvar capacitor bank, Fig. 6-1.
at Thévenin impedance of 13.8-kV bus, the following differential
equation for the inrush current can be written as:
5 . 08 × 10−4
(6-1)
If damping in a series LC circuit is neglected and the circuit is
excited through a step function V, the following equation can be
written:
di ∫ idt
+
=V
dt
C
(6-2)
Taking Laplace transform:
s2i(s) − sI(0) − I '(0) +
i(s)
=0
T2
(6-3)
The initial current is zero, and from Eq. (6-2):
di V
= = I '(0)
dt L
(6-4)
V
1
L ( s 2 + 1/ T 2 )
(6-5)
V 1
V
sin(1/T )t =
L 1/ T
L
=V
LC sin
1
LC
t
1
C
sin
t
L
LC
(6-6)
Thus, the peak inrush current can be written as:
imax,peak =
2 ELL
Ceq
3
Leq
(6-7)
where imax,peak is the peak inrush current in amperes without damping, ELL is the line-to-line voltage in volts, Ceq is the equivalent
capacitance in farads, Leq is the equivalent inductance in henries.
(All inductances in the switching circuit, including that of cables
and buses, must be considered.) The frequency of the inrush
switching current f is given by:
f=
Therefore:
i(s) =
Taking inverse transform:
i=
di
∫ idt
+ 2 . 19 × 10−2 i +
dt
83 . 6 × 10−6
= 11 . 26 × 103 sin ω t
L
125
1
2π LeqCeq
(6-8)
The voltage across the capacitor, which will also be the bus
voltage, is given by:
Vc (s) =
i(s) V
1
=
sC LC s(s2 + 1/T 2 )
(6-9)
126
CHAPTER SIX
Resolving into partial fractions:
Vc (s) =
V
LC(1/T 2 )
1
s
s − ( s 2 + 1/ T 2 )
(6-10)
Taking inverse transform:
1
Vc = V 1 − cos
t = V (1 − cos ω0t )
LC
Thus, the maximum voltage occurs at:
ω0t = π
(6-11)
(6-12)
These equations give a peak current of 4.58 kA and a frequency of
770 Hz, which corresponds well with the simulation results shown
in Fig. 6-2 and 6-3. The high-frequency oscillation is clearly visible in these figures. It takes about six cycles before the oscillations
appreciably damp out. The damping is a function of the resistance
and losses in the system (rigorously some resistance of the capacitors themselves should also be modeled). Figure 6-3 shows a peak
voltage excursion of approximately 22 kV, that is, two times the
bus-rated voltage of 13.8 kV rms. The inrush current, as read from
Fig. 6-2, is 4.6 kA, and its frequency can be approximately determined around 700 Hz.
The damping due to the presence of the resistor has not been
accounted for, yet the calculated results are close to the simulation.
These can be further examined. Calculate Q0:
Q0 =
X
10
R
(6-13)
Thus, it does not have appreciable effect on damping. From Eq. (6-8)
f0 =
1
2π LC
= 770 Hz
Thus, inrush current frequency is 770 Hz.
(6-14)
(6-15)
6-2-1 Prior Charge on the Capacitors
A prior trapped charge on the capacitors will prolong the transients.
As per ANSI/IEEE specifications,7 the capacitors are provided with
an internal discharge device that will reduce the residual charge to
50 V or less within 1 min for capacitors of 600 V or less and 5 min
for capacitors over 600 V.
Thus, rapid switching in and switching out of the capacitors
should be avoided to limit inrush current transients. Any switching
arrangement should block reconnecting the capacitor banks to the
power supply system without the required time delay. Up to twice
the normal inrush currents are possible when a circuit breaker is
employed to reswitch capacitive loads. When the bank is interrupted at or near current zero, the voltage trapped on the bank
may be near the peak value. Reclosing will produce high inrush
currents. When a capacitor bank is connected on the load side of
a feeder, the high inrush currents can be avoided by isolating the
capacitor bank before reclosing takes place or reclosing must be
sufficiently time-delayed.
6-3 APPLICATION OF POWER CAPACITORS
WITH NONLINEAR LOADS
Nonlinear loads like variable speed drives, wind power generation,
switched mode power supplies, arc furnaces, and so on can give
rise to a variety of line harmonic spectrums. It is not the intention
to go into the much-involved subject of harmonics, except to relate
it to switching transients and distortions that can be caused by the
application of power capacitors with nonlinear loads. For the purpose of this analysis, we will confine the discussion to six-pulse
current source converters, which produce characteristic harmonics
of the order of 5th, 7th, 11th, 13th, . . . (Chap. 15).
Harmonics generated by nonlinear loads may be described as
(1) having a Fourier series with fundamental frequency equal to the
power system frequency, and a periodic steady state exists—this
is the most common case; (2) a distorted waveform having submultiples of power system frequency, and a periodic steady state
exists—certain types of pulsed loads and cycloconverters produce
these types of waveforms; (3) the waveform is aperiodic, but perhaps almost periodic, and a trigonometric series expansion may
still exist, examples being arcing devices, arc furnaces, and sodium
vapor lighting; (4) the components in a Fourier series that are not
a multiple of power frequency are called noninteger harmonics.
Harmonics generating loads in the power systems are always on an
increase due to the proliferation of power electronics. The effects
of harmonics on power system operation are manifold. The presence of capacitors in a system does not generate harmonics in itself,
but can accentuate these, create more distortion, and bring about
resonant conditions.8
6-3-1 Harmonic Resonance
Series and parallel resonant circuit concepts of Chap. 2 are applied
to harmonic resonance that occurs when power capacitors are
applied in distribution systems which have nonlinear loads.
The shunt power capacitors act in parallel with the power system. Thévenin impedance, as seen from the point of application of
the capacitor, ignoring resistance, is the impedance of the parallel
combination:
jω L(1/jω C)
( jω L + 1/jω C)
(6-16)
Assuming that L and C remain invariant with frequency, resonance
will occur when the inductive and capacitive inductance of the
denominator in Eq. (6-16) is equal and the denominator is zero.
This means that the impedance of the combination is infinite for a
lossless system. The impedance angle will change abruptly as the
resonant frequency is crossed. Thus, at the resonant frequency fn:
j2π f n L =
1
j2π f nC
(6-17)
Without the presence of power capacitors, the natural resonant
frequency of the power system is fairly high, much above any loadgenerated harmonic. As the frequency is increased, the capacitive
reactance decreases and the inductive reactance increases. It may so
happen that at a load-generated harmonic, say 5th, (fn = 300 Hz),
Eq. (6-17) is satisfied. The power capacitor acts like one branch of
a parallel-tuned circuit while the rest of the system acts likes the
other parallel branch. Such a circuit, when excited at the resonant
frequency (5th harmonic, in this case), will result in the magnification of the harmonic current, which may even exceed the fundamental frequency current. This will overload the capacitors and all
the system components with deleterious results. Resonance with
one of the load-generated harmonics is a major concern in power
systems, and this condition must be avoided in any application of
the power capacitors. Equation (6-17) can be simply written as:
h=
fn
=
f
kVA sc
kvarc
(6-18)
where h is the order of the harmonic, fn is the resonant frequency,
f is the supply system frequency, kVAsc is the short-circuit kVA at
the point of application of the capacitor, and kvarc is the shunt
capacitor rating. For a short-circuit level of 500 MVA, resonance at
5th, 7th, 11th, and 13th harmonics will occur for a capacitor bank
TRANSIENTS OF SHUNT CAPACITOR BANKS
127
size of 20, 10.20, 4.13, and 2.95 Mvar, respectively. The smaller the
size of the power capacitor, the higher is the resonant frequency.
Sometimes, this simple artifice is used to size capacitor banks
for a given distribution system to avoid resonance. A capacitor bank
size is selected so that the resonant frequency does not coincide
with any load-generated harmonics. However, the short-circuit
level in a power system is not a constant parameter. It will vary
with the switching conditions; for example, a generator or a tie-line
circuit may be out of service or part of the motor loads may have
been shut down, which will lower the short-circuit level. Thus, it
can be concluded that:
■
The resonant frequency will float around in the system,
depending on the switching conditions.
■
An expansion or reorganization of the system may bring
about a resonant condition where none exited before.
6-3-2
Frequency Scan
An elementary tool to accurately ascertain the resonant frequency
of the system in the presence of capacitors is to run a frequency
scan on a digital computer. The frequency is applied in incremental steps, say 2 Hz, for the range of harmonics to be studied, say
from the fundamental frequency to 2400 Hz. (This means 1200
calculations for the entire range.) The procedure is equally valid,
whether there are one or more than one harmonic-producing loads
in the system, so long as the principle of superimposition is held
valid. Then, for the unit current injection, the calculated voltages
give the driving point and transfer impedances, both modulus and
phase angle. The Ybus matrix contains only linear elements for each
incremental frequency. Thus, an impedance plot can be made with
varying frequency, which gives resonant frequencies. System component models used for power frequency applications, for example,
transformers, generators, reactors, and motors, are modified for the
higher frequencies, which are not discussed in this book.
Example 6-2 For this example, the circuit of Fig. 6-1 is modified and a 5-MVA transformer, which supplies a six-pulse drive
system (three-phase fully controlled bridge circuit, Chap. 15)
load of 5 MVA, is added; see Fig. 6-4. The harmonic spectrum is
shown in Table 6-1, which is also a function of the source impedance (Chap. 15). A frequency scan of bus 2, both impedance
modulus and angle, is shown in Figs. 6-5 and 6-6, respectively. A
resonance occurs close to the 11th harmonic, and Fig. 6-6 shows
that the angle abruptly changes at the resonant frequency. The calculated resonant frequency is 672 Hz. The calculation is made in an
incremental step of 2 Hz. To capture the resonant frequency close
to the actual, the incremental step should be small. Suppose an
incremental step of 10 Hz is selected, the actual resonant frequency
may be at a variation of ± 5 Hz.
Figure 6-7 shows the voltage spectrum of 13.8-kV bus 1 and
4.16-kV bus 2. This shows that the 11th harmonic voltage at
4.16-kV bus 2 is 17.2 percent, while at 13.8-kV bus 1, it is 11.8
percent. Figure 6-8 shows distorted waveform of the voltage at
these two buses for one cycle. Figure 6-9 depicts the spectrum of
current flow through the capacitor; the 11th harmonic current
is 130 percent of the fundamental current = 326 A at 13.8 kV
(the fundamental frequency current is not shown). Note that the
injected 11th harmonic current, a current at 4.16-kV bus 1B, is
63 A based on the harmonic spectrum shown in Table 6-1. Thus,
there is a magnification of approximately 17 times. This is the characteristic of a parallel-tuned circuit, that while the exciting current
can be small, the capacitor forms a resonant tank circuit with the
source impedance, resulting in much magnification of the injected
current.
A harmonic source can be considered as a harmonic generator. The
harmonic current injected at the source will flow to the 13.8-kV
FIGURE 6-4
TA B L E 6 - 1
Circuit diagram to illustrate harmonic resonance.
Harmonic Spectrum of Six-Pulse Load
h
5
7
11
13
17
19
23
25
29
31
%
18
13
6.5
4.8
2.8
1.5
0.5
0.4
0.3
0.2
bus through 5 MVA coupling transformer and divide into other
system components connected to this bus, depending upon
their harmonic impedances. Harmonic load flow is akin to the
fundamental frequency load flow in this respect. Apart from
overloading of the capacitors, the harmonic currents in the distribution systems seriously derate the transformers, produce
additional losses, result in negative sequence overloading of the
generators, give rise to transient torques and torsional oscillations in rotating machinery, and impact the protective relaying,
to name a few effects.
Generators have a limited I 22t rating, where I2 is the negative sequence current (Chap. 10). Harmonics of the order of
h = 6m + 1, where m is any integer, are forward going, that is,
harmonics of the order of 7th, 13th, 19th, . . ., and these rotate
at 1/h of the speed. Harmonics of the order h = 6m − 1 are reverse
going, that is, harmonics of the order of 5th, 11th, 17th, . . .
In a synchronous machine, the frequency induced in the rotor
is the net rotational difference between fundamental frequency
and harmonic frequency. The 5th harmonic rotates reverse with
respect to stator, and with respect to rotor, the induced frequency is that of 6th harmonic. Similarly, the forward-going 7th
harmonic produces a frequency of 6th harmonic in the rotor.
The harmonic pairs 11th and 13th will produce a frequency of
12th harmonic in the rotor. If the frequency of mechanical resonance happens to be close to these harmonics during starting,
large mechanical forces can occur.
A similar phenomenon occurs in induction motors. Here, positivesequence harmonics of the order of h = 1, 4, 7, 10, 13, . . . produce
a torque of (h − 1 + s)ω in the direction of rotation, and negativesequence harmonics, h = 2, 5, 8, 11, 14, . . ., produce a torque
of −(h + 1 − s)ω opposite to the direction of rotation. Again,
torque amplifications can occur.
128
CHAPTER SIX
FIGURE 6-5
FIGURE 6-6
Impedance modulus, 4.16-kV bus 2, Fig. 6-4.
Impedance angle, 4.16-kV bus 2, Fig. 6-4
FIGURE 6-7
FIGURE 6-8
Voltage spectrum, 13.8-kV bus 1 and 4.16-kV bus 2, Fig. 6-4.
Distorted voltage waveforms, 13.8-kV bus 1 and 4.16-kV bus 2, due to harmonic resonance, Fig. 6-4.
129
130
CHAPTER SIX
FIGURE 6-9
6-3-3
Harmonic current spectrum through 6-Mvar capacitor bank, Fig. 6-4.
The limits on rms voltage are given by:
Harmonic Propagation and Mitigation
Example 6-2 depicts a rather simple distribution system with respect
to harmonic amplification. When capacitors are located close to a
plant with significant harmonic-producing loads, harmonic resonance becomes a potential possibility, and a nearby distribution
system, which does not have any nonlinear loads of its own, may
be subjected to harmonic pollution. This means that the impact
can be propagated through interconnections and impact remotely.
There have been two approaches:
1. Consider capacitor placement from reactive power compensation point of view and then study harmonic effects.
2. Study fundamental frequency, voltage, and harmonic effects
simultaneously.
For the power capacitors, the limitations due to harmonic loading
are well defined.7 Per unit kvar should not exceed 1.35:
kvar( pu ) ≤ 1 . 35 =
h = hmax
∑
h =1
(Vh Ih )
(6-19)
The rms current should not exceed 135% of nominal current
based upon rated kvar and rated voltage, including fundamental and
harmonic currents.
I rms
h = hmax
≤ 1 . 35 = ∑ Ih2
h =1
1/ 2
(6-20)
1/ 2
h = hmax
Vrms ≤ 1 . 1 = ∑ Vh2
h =1
(6-21)
The crest shall not exceed 1 . 2 × 2 times rated rms voltage,
including harmonics but excluding transients.
V( rest ) ≤ 1 . 2 2 =
h = hmax
∑
h =1
Vh
(6-22)
Unbalances within a capacitor bank, due to capacitor element
failures and/or individual fuse operations result in overvoltages on
other capacitor units. In a filter bank, failure of a capacitor unit
will cause detuning. The limitations of the capacitor bank loadings
become of importance in the design of capacitor filters. A capacitor tested according to IEEE Std 1820 will withstand a combined
total of 300 applications of power frequency terminal-to-terminal
overvoltages without superimposed transients or harmonic content. The capacitor unit is also expected to withstand transient currents inherent in the operation of power systems, which include
infrequent high lightning currents and discharge currents due to
nearby faults. Ref. 21 provides curves of voltage and transient currents withstand for shunt capacitors.
The impact of capacitor applications at transmission and subtransmission systems becomes fairly involved and is not the main
subject of discussion in this book. Figure 6-10 shows the frequency
scan of a 400-kV line with bundle conductors. IEEE Std. 519
defines the limits of harmonic indices, current, and voltage at the
point of common coupling (PCC).9 This can be the point of metering
TRANSIENTS OF SHUNT CAPACITOR BANKS
FIGURE 6-10
Impedance modulus of a 400-kV line.
or the point of connection of consumer apparatus with the utility
supply company. Within a plant, PCC is the point between the
nonlinear load and the other loads. The recommended current
distortion limits in IEEE Standard 519 are concerned about total
demand distortion,9 which is defined as:
h=hmax
TDD =
∑
h=2
IL
Ih2
(6-23)
where IL is the load current demand for 15 or 30 min. The limits of
the TDD are specified at each harmonic, and also total permissible
TDD, as a function of Isc/IL, where Isc is the short-circuit current.
The harmonics may be limited by (1) phase multiplication
(Chap. 15), (2) use of passive or active harmonic filters, and (3) modern
power electronics technology that limits the harmonics at the source.
The application of a single-tuned harmonic filter, also called a
band pass filter, is briefly discussed, with reference to Fig. 6-11. A
band pass filter consists of merely a reactor in series with a capacitor,
and referring to Chap. 2, at its resonant frequency it offers a low
impedance path to the harmonic of interest that is required to be
shunted through the filter to minimize its propagation through
the system. Two or three ST filters can be used, each appropriately tuned to a different harmonic that needs to be controlled and
bypassed. Referring to the equivalent circuit, the injected harmonic
current divides between the harmonic filter and the source impedance, as seen from the point of application of the capacitor bank.
The harmonic injected current flows partly into the capacitor and
partly into the source.
Ih = I f + I s
Equivalent harmonic injection circuit, distribution
system represented by single impedance, Zs.
(6-24)
Also, voltage across the combination of reactor and capacitor
should be equal to the voltage across Zs.
I f Z f = Is Zs
(6-25)
Then:
Zs
If =
I h = ρf I h
Z f + Z s
Zf
Is =
I h = ρs I h
Z f + Z s
FIGURE 6-11
131
(6-26)
In harmonic flow analysis and harmonic filter design, the complex quantities rs and rf are of interest. To control the current injection into the utility system, these factors should be controlled, the
system impedance playing an important role. As the utility source
impedance may be considered fixed for a certain electrical distribution system, more current can be made to flow through the filter,
by increasing the size of the capacitor bank. The effectiveness of
harmonic filtering vis-à-vis source impedance is apparent from
Eq. (6-26). The lower the source impedance, the greater is the
harmonic current flowing into it, for the same filter size.
Generally, in the presence of load-generated harmonics, the
capacitors are applied as harmonic filters, and the series tuning
reactor serves the dual purpose of forming a low-impedance tuned
circuit as well as limiting the inrush current and its frequency on
switching a capacitor bank.
132
CHAPTER SIX
Example 6-3
The capacitor bank C1 shown in Fig. 6-4 is turned
into a ST filter, the tuned frequency being 4.67 times the fundamental. The new frequency scan, impedance modulus, and angle
are now depicted in Figs. 6-12(a) and 6-12(b), respectively. The
FIGURE 6-12
application of a band pass filter has not eliminated the resonance,
but now it occurs at a frequency below the tuned frequency that
can be placed at a point so that the load-generated harmonics, and
transformer inrush current harmonics are away from it. There will
(a) Impedance modulus with 6-Mvar capacitor bank turned into a single tuned band-pass filter, tuning frequency 4.67th of fundamental,
Fig. 6-4 (b) Impedance angle.
TRANSIENTS OF SHUNT CAPACITOR BANKS
FIGURE 6-13
133
Voltage waveform, 13.8-kV bus 1, with 6-Mvar capacitor bank turned into a single-tuned band-pass filter, tuning frequency 4.67th of
fundamental, Fig. 6-4.
be some swings in the tuned and resonant frequency with varied
system switching conditions, and in a practical filter design, these
must be considered with filter loading in each case.8 Figure 6-13
shows 13.8-kV bus voltage with the applied filter; this can be compared with Fig. 6-8.
6-4
BACK-TO-BACK SWITCHING
The back-to-back switching involves energizing a capacitor bank
on the same bus when another energized bank is present. The
inrush transient in this case mainly consists of interchange of currents between the two banks, and the current supplied from the
supply system can be ignored. This will not be true if the supply
system impedance is comparable to the impedance between the
banks being switched back to back.
The switching inrush current and frequency can be calculated
from:
imax, peak =
2 ELL
3
C1C2
(C1 + C2 )L m
Example 6-4
The circuit of Fig. 6-1 is modified with the addition of another capacitor bank C2, similar to bank C1 of 6 Mvar, as
shown in Fig. 6-14. C1 is already energized and its circuit breaker
CB1 is closed. Bank C2 is switched on the same bus by closing its
circuit breaker CB2. The equivalent switching circuit is shown in
Fig. 6-15. To calculate the switching transients, it is necessary to
calculate the inductance between the banks accurately.
■
Inductance of cables C1 and C2 between the banks = 2-3/C
500 KCMIL, 11 m, Lc1 + Lc2 = 4.6 µH
(6-27)
And the frequency of the inrush current is:
f=
1
C1C2
2π L m
(C1 + C2 )
(6-28)
where C1 and C2 are the sizes of the capacitors in farad and Lm is
the inductance between them in henries. Apart from stresses on the
circuit breaker, the high-frequency transient can stress the other
equipment too.
FIGURE 6-14
A circuit diagram for the study of back-to-back
switching of capacitor banks.
134
CHAPTER SIX
FIGURE 6-15
Calculation of inductance for back-to-back switching of capacitor banks.
■
Inductance of bus duct between the circuit breakers,
13.8 kV, 1200 A, 2 m = 1.4 µH
■
Inductance of each bank itself = 5 µH
■
Total inductance = 16 µH
The source inductance of our example, as calculated earlier, is
588 µH. Thus, the inrush current can be calculated by ignoring
the source inductance. Using these equations, the inrush current is
435 kA and its frequency is 6144 Hz, which are very high.
6-5 SWITCHING DEVICES FOR CAPACITOR BANKS
The derating of switching devices is required for capacitor switching
duties, whether these are contactors, circuit breakers, or load break
switches. The current requirement for rating the switching device
should consider the effect of overvoltages (generally 10 percent),
capacitor tolerances (105 to 115 percent), and harmonic components. For example, review the application of an indoor oil-less
metal-clad 15-kV circuit breaker. The rated current of a 6-Mvar
bank at 13.8 kV is 251 A. IEEE Standard C37.06-1987 specifies that
a “general-purpose” 1200-A circuit breaker has a capacitor switching current rating of 250 A only.2 A definite-purpose circuit breaker
for capacitor switching, rated 1200 A, and 40-kA rms short-circuit
rating, has a rated capacitance switching current of 630 A for isolated capacitor bank or for back-to-back switching. Furthermore,
the inrush current and its frequency should not exceed 15 kA and
2000 Hz, respectively. This means that for the proper application
of even a definite-purpose breaker, the inrush current and its frequency should be reduced for back-to-back switching applications.
For high-voltage outdoor circuit breakers, similar derating applies.
For example, a general-purpose 362-kV breaker, rated for 2000 or
3000 A and short-circuit rating of 65-kA rms symmetrical has an
overhead line or isolated capacitor bank switching current of 250 A,
and a definite-purpose circuit breaker must limit the inrush current to 25 kA, frequency 4250 Hz, on back-to-back switching. Gas
circuit breakers, SF6 or air-blast type, have a much better capability
of capacitor switching and are now used exclusively for high-voltage
networks. These can cope with high recovery voltages without
restrikes. Installing closing resistors is one way to reduce switching
transients; see Sec. 6-13-1. The vacuum switchgear, which is commonly used at medium voltage, cannot be provided with resistor
switching, though two breakers with a separately mounted resistor
can be used. The interruption of capacitor currents and effects on
recovery voltages are covered in Chap. 8.
A bank is considered “isolated” if the rate of change of the transient inrush current does not exceed the maximum rate of change
of symmetrical interrupting capability of the circuit breaker at the
applied voltage.
Again, for a 15-kV indoor oil-less breaker, rated short-circuit
current of 40 kA, K factor is 1.0. Then maximum rate of change is
given by:
di
= 2ω( 40 . 0 × 103 ) × 10−6
dt max
(6-29)
= 21 . 32 A/µ s
An inrush current of 4.58 kA (peak) and a frequency of 770 Hz
was calculated when switching 6-Mvar bank in Example 6-1. This
gives a rate of change of:
2π (770)( 4580) × 10−6 = 22 . 16 A/µ s
(6-30)
Therefore, switching of even a single 6-Mvar capacitor bank in
Fig. 6-1 cannot be considered isolated bank switching. It requires
a breaker of higher interrupting rating or, alternatively, the size of
the capacitor bank should be reduced. Another option will be to
provide an inrush current limiting reactor.
The year 2000 revision of ANSI/IEEE Standard C37.06-1987
has made K factor of oil-less indoor circuit breakers = 1. (This is
an attempt to harmonize ANSI standards with IEC standards.) This
reference may be seen for new rating tables of oil-less indoor circuit
breakers.2
TRANSIENTS OF SHUNT CAPACITOR BANKS
6-6
INRUSH CURRENT LIMITING REACTORS
When applying an inrush current limiting reactor, the following
considerations apply:
1. An inrush current-limiting series reactor will tune the
capacitor to a certain frequency. When load-generated harmonics are present, caution is required that the series reactor does
not tune the capacitor close to a load-generated harmonic,
unless the intention is to turn the capacitors into single-tuned
filters, which requires detailed considerations. This is to avoid
overloading of the capacitors, which will act as filters and
create a low-impedance path to a load-generated harmonic.
2. A series reactor does reduce the capacitive reactance, yet,
the net leading kvar output from the combination increases
rather than decreases. This is so because the voltage drop
across the reactor is additive to the capacitor voltage and the
terminal voltage of the capacitor rises. As the reactive output
of a capacitor changes in proportion to the square of the voltage,
there is a net increase in the leading reactive kvar from the combination. This brings another consideration that the capacitorrated voltage may have to be increased. Voltage at the junction
of the capacitor and reactor will be:
n2
(6-31)
n −1
where n = fn /f, fn is the frequency in presence of the reactor. Also,
the reactive power of the capacitor bank will be:
Vc =
Sf =
2
n2
× reactive power without reactor
n −1
2
FIGURE 6-16
(6-32)
135
Example 6-5 The limitation of switching inrush current and its
frequency for isolated bank switching is demonstrated in this example by providing an inrush current-limiting reactor. A series reactor
of 3.8 mH, with an X/R = 50 is provided in the switching circuit of
6-Mvar capacitor bank in Fig. 6-1. Then from Eqs. (6-7) and (6-8),
the inrush current is reduced to 1633 A, and its frequency to 264 Hz.
An EMTP simulation is shown in Fig. 6-16, which shows that in
the first positive 1/ 2 cycle, the simulated value is close to the calculated value. The current increases in the negative 1/ 2 cycle, and
this can be attributed to the exchange of energy between two energy
storage elements, that is, the inductance and the capacitance. Also,
it is noted that the decay of the current is prolonged due to added
reactor. The transients are much reduced.
To reduce the inrush current on the back-to-back switching to
be within the circuit breaker capability, its magnitude should be
no more than 15 kA and frequency should be equal to or less than
2000 Hz.
Equation (6-7) can be used to calculate the minimum inductance
between the banks to limit the transients. Both, inrush current limitation as well its frequency limitation should be considered. This
calculation shows that minimum inductance should be 14.32 mH to
reduce the frequency to 2000 Hz, and the inrush current will fall
to 5.089 kA.
The ohmic losses in reactors can be substantial. A reactor of
4.3 mH, as calculated earlier and a Q factor of 40, has resistance of
0.04 Ω. The full-load current of 6-Mvar bank is 251 A. This gives
an energy loss of 7.56 kWh, which, on a yearly basis, translates into
66 MWh of energy loss. For indoor reactors, the heat dissipation
and ventilation for large reactors becomes a major consideration,
and proper ventilation and heat dissipation measures should be
considered.
Reduction in current transient of 6-Mvar capacitor bank, Fig. 6-1, with a series inductor of 3.8 mH introduced in the capacitor bank.
136
CHAPTER SIX
FIGURE 6-17
Surge suppressors across CT secondary windings to
limit the voltages on discharge of capacitor currents on a fault.
6-7 DISCHARGE CURRENTS THROUGH
PARALLEL BANKS
In Fig. 6-4, assume a fault occurs at F. The charged capacitors
in the system will discharge into the fault. If the capacitors are
ungrounded (the usual case for the industrial distributions), the
maximum discharge current will occur for a three-phase fault. If
the capacitors are grounded, the maximum discharge current will
occur for a three-phase to ground or single-phase to ground fault.
The total discharge current will be the sum of the discharge currents from individual banks given by Eq. (6-7). Again the capability
of the breaker to withstand this discharge current should not be
exceeded. The effect on bushing CTs and linear couplers should
be calculated.
Vcts =
I transient
f
× VAohms × t
f
CT ratio
(6-33)
where Vcts is secondary voltage developed across BCT, VA ohms is CT
burden in ohms, ft is transient frequency, and f is supply system
frequency.
The voltage should be limited to safe levels. Sometimes, the provision of surge suppressors across CT terminals becomes necessary
(Fig. 6-17).
For example, for a total discharge current of 20 kA, frequency
of 2000 Hz, relay burden of 0.5 Ω and CT ratio of 1000/5, the
secondary voltage across CT from Eq. (6-33) is 1.67 kV, which will
impact all the relays and instruments connected across the secondary of the CT.
6-8
FIGURE 6-18
A circuit diagram for the study of secondary resonance.
where fc is coupled frequency, fm is the main switching frequency,
Ls and Cs are inductance and capacitance in the secondary circuit, and Lm and Cm are the inductance and capacitance in the
main circuit. The lower the ratio fc/fm, the greater is the magnitude of the coupled transient. High-transient voltages of the
order of five times the rated voltage are possible, as shown in
Fig. 6-19.10
These transient voltages can result in failures and fuse operations in low-voltage power factor correcting capacitors and nuisance trips of power electronic-based devices, such as adjustable
speed drives.
SECONDARY RESONANCE
Figure 6-1 is now redrawn as shown in Fig. 6-18, and a 2-MVA
transformer with secondary load and a 200-kvar capacitor bank
are added. Such a circuit gives rise to the possibility of secondary resonance. The switching of a large high-voltage capacitor can
cause a much higher per unit transient voltage at the location of a
smaller low-voltage capacitor bank. This occurs in the secondary
circuits, which have their resonant frequencies close to the natural
frequency of the switched capacitor bank. The initial surge can trigger oscillations in the secondary circuits, which are much greater
than in the switched circuit:
fc
=
fm
L mCm
L sCs
(6-34)
FIGURE 6-19
Overvoltages due to secondary resonance.
TRANSIENTS OF SHUNT CAPACITOR BANKS
The studies show that:
1. Transients will predominate when the size of the switched
capacitor bank is much larger than the capacitance of the lowvoltage capacitor and cable, which is generally the case.
2. Highest transients will occur when the energizing frequency
is close to the series-resonant frequency formed by the stepdown transformer and low-voltage capacitance.
3. Problems predominate when there is little damping, which is
very common in industrial distributions as the resistance is low.
Example 6-6 The 200-kvar capacitor connected to the 2-MVA,
13.8 to 0.48-kV transformer in Fig. 6-18 remains in service, while
6-Mvar capacitor at 13.8-kV bus is switched. The simulation in
Fig. 6-20 shows that a peak voltage of 1220 V line-to-neutral is
developed across the secondary of 480-V transformer. This overvoltage is 3.1 times the rated system voltage. The calculations show
that fc / fm ≈ 3.8. Figure 6-21 shows the transient current that flows
through the 200-kvar capacitor; its peak value is 2200 A, approximately 6.5 times the full-load current of 200-kvar capacitor.
When capacitors are applied at multivoltage level in a distribution system, apart from the overvoltages due to the resonance illustrated earlier, these can also prolong the decay of the transients.
It is, therefore, best to apply capacitors at one voltage level
only. If these are applied at multivoltage levels, a rigorous switching transient analysis to predetermine the resonance points and
eliminate them is required. This requires lots of rigorous modeling
not generally undertaken when placing capacitors in the distribution systems.
FIGURE 6-20
137
Example 6-7 This example is an EMTP simulation of switching
transients of a transformer. The schematic single-line diagram is
shown in Fig. 6-22. The EMTP transformer models are described
in Chap. 14. The purpose of this example is to demonstrate that the
transformer inrush transients escalate in amplitude and their decay
is prolonged when a transformer and capacitor bank are energized
together.
Figure 6-23 shows the switching inrush current transient on
energizing the transformer when the 5-Mvar capacitor bank shown
on the secondary is disconnected.
Figure 6-24 depicts the transient escalation in magnitude and time
when the transformer and 5-Mvar capacitor bank on the secondary
of the transformer are simultaneously energized. The transient profile shows some periodic escalations due to some higher-frequency
resonance. This may not be a very practical situation. A load dependent or some other form of switching control of the capacitor bank
is adopted so that leading reactive power is not supplied into the
system and capacitor is switched off on loss of voltage.
Switching of a large capacitor bank when the system is unloaded
gives rise to steady-state overvoltages, which can be calculated from
the following expression:
%DV =
kvarc × % Z
kVAT
(6-35)
where %Z is the transformer percentage impedance and kVAT is
the transformer kVA rating. The operating voltages may change
by 10 percent for short periods, while adjustments are being
made to the new operating conditions with the switched capacitors. This becomes important for the application of surge arresters
(Chap. 20).
Voltage transient on 480-V bus 2, phase a, on switching of 6-Mvar capacitor bank, 200-kvar capacitor bank already energized, Fig. 6-18.
FIGURE 6-21
Current transient through 200-kvar capacitor bank.
F I G U R E 6 - 2 2 A simple circuit for switching transient of a transformer, with and without 5-Mvar capacitor bank.
FIGURE 6-23
138
A 20-MVA transformer switching current transient without secondary 5-Mvar capacitor bank.
TRANSIENTS OF SHUNT CAPACITOR BANKS
FIGURE 6-24
6-9
139
Current transients 20-MVA transformer and 5-Mvar bank switched together.
PHASE-TO-PHASE OVERVOLTAGES
The switching of capacitors can produce phase-to-phase overvoltages
at a remote location. Consider a capacitor bank switched on a bus
connected through a transmission line to a transformer. The surge
will double at the transformer and the surges produced on energizing
the capacitors are of opposite polarity on two phases; the transformer
at the remote end will experience phase-to-phase surges. The surge
arresters, normally connected phase-to-ground, will limit the phaseto-ground components, depending on their protective level, but the
phase-to-phase overvoltages will be twice this value.11 Restrikes in
switching devices controlling ungrounded wye-connected banks can
also generate high phase-to-phase voltages (Chap. 20).
Example 6-8 An electrical power system is shown in Fig. 6-25
for the simulation of capacitor bank switching transients. The following models are used:
Source impedance at 230 kV: This is simply a passive coupled
RL branch, modeled with positive- and zero-sequence source
impedance.
230-kV, 80-km line: A CP model is used, as discussed in Chap. 4.
40-MVA, 230- to 13.8-kV transformer: Transformer bushings,
windings, and interwinding capacities are modeled; see
Chap. 14, for transient models of transformers. The wye
windings of the transformer are grounded through a resistance of 20 Ω to limit the ground fault current to 400 A.
Surge arresters: The surge arresters considered are gapless zincoxide surge arresters, rated voltages as shown in Fig. 6-21.
Their models are discussed in Chap. 20.
400 ft of 3/C 500 KCMIL cable between the 13.8-kV bus and
2.5-MVA 13.8- to 0.48-kV transformer: This is a model with
characteristic impedance, length, and attenuation (Chap. 4).
7.5-Mvar capacitor bank: The bank is ungrounded and
switched at an instant when the voltage in phase a peaks.
There is no inrush current-limiting reactor.
Loads at 13.8-kV bus and low-voltage transformer secondary:
Passive load models consisting of appropriate RL elements and
their connections.
2.5-MVA transformer: It is the same type of model as for main
40-MVA transformers. This transformer is high-resistance
grounded; grounding resistance = 70 Ω.
The results of EMTP simulations are shown in Figs. 6-26
through 6-30.
Figure 6-26 shows the 13.8-kV three-phase voltages at bus V3
on capacitor bank switching. A sudden voltage dip and subsequent
recovery profile can be seen from this figure. The peak excursion is
approximately 18 kV from phase to ground.
Figure 6-27 illustrates phase a voltage on the primary of 2.5-MVA
low-voltage transformer at V4 for about 4 ms from the instant of
switching. The thick band is due to multiple reflections in the
400-ft cable. The voltage escalates and has high-frequency superimposed oscillations due to multiple reflections at the cable ends.
To capture these high-frequency oscillations, a time step of 1 µs is
used in EMTP simulations.
Figure 6-28 illustrated the secondary voltage V5 of 2.5-MVA
transformer, simulation for 30 ms only. The voltage has highfrequency oscillations and rises to 2900 V peak from line to
ground. Some resonant phenomena and amplification is occurring inside the transformer.
Figure 6-29 shows the 7.5-Mvar capacitor three-phase inrush
currents which have high-frequency components, and finally,
Fig. 6-30 depicts the 230-kV line current.
This is continued further in Chap. 20 to illustrate the control of
high voltage on the secondary of 2.5-MVA transformer.
140
CHAPTER SIX
FIGURE 6-25
A power system configuration for the study of switching transients.
6-10 CAPACITOR SWITCHING IMPACT ON
DRIVE SYSTEMS
An investigation of the failure of a drive system due to frequent
cycling of a capacitor bank in the utility system, which raised the
dc link voltage of a drive system to trip, is discussed in Ref. 12. This
has been a major concern in the industry.
Example 6-9 This example is an EMTP simulation of escalation of the dc link voltage of a six-pulse converter feeding
a dc motor load, Fig. 6-31, when a 6-Mvar capacitor bank is
switched. The simulation in Fig. 6-32 shows that the voltage rises
to approximately 2 pu. This can be controlled by all the means
that reduce the capacitor inrush transients; see Sec. 6-13.
6-11 SWITCHING OF CAPACITORS WITH MOTORS
Capacitors are, generally, applied for the power factor correction
of induction motors. The loaded induction motors operate at a
power factor of 80 to 90 percent approximately. The power factor
decreases for low-speed motors due to leakage reactance of stator
overhang windings.
Generally, the induction motors do not operate at full load,
which further lowers the operating power factor. Even though the
power factor of the motor varies significantly with load, its reactive
power requirement does not change much. Thus, with the application of power factor improvement capacitor, the motor power
factor from no-load to full load will not vary much. Figure 6-33
FIGURE 6-26
FIGURE 6-27
Voltage transients, 13.8-kV bus V3.
Voltage transient primary of transformer T2, V4.
141
FIGURE 6-28
FIGURE 6-29
142
Voltage transient on secondary of T2, V5.
Current transients through 7.5-Mvar capacitor bank.
TRANSIENTS OF SHUNT CAPACITOR BANKS
FIGURE 6-30
143
Line current through 230-kV line.
shows three methods of location of the capacitors. (a) The capacitors are connected directly to the motor terminals; (b) the capacitor
and motor are switched as a unit, and (c) the capacitor is switched
independently of the motor contactor through a separate switching
breaker interlocked with the motor starting breaker.
The switching of the capacitor and motor as a unit (second
method) can result in problems due to:
■
Presence of harmonic currents
■
Overvoltages due to self-excitation
■
Excessive transient torques and inrush currents due to out-ofphase closing
F I G U R E 6 - 3 1 A circuit diagram for the study of escalation of dc link
voltage in a drive system on switching of 6-Mvar capacitor bank.
Overvoltages due to self-excitation are important for the proper
application of capacitors with induction motors.
The magnetizing current of the induction motors varies with the
motor design. Premium high-efficiency motors operate less saturated than the previous U- or T-frame designs.13 The motor and
capacitor combination in parallel will circulate a current between
motor and capacitor corresponding to their terminal voltage. In this
manner, the network is said to self-excite.
This is shown in Fig. 6-34a and b. The same size of capacitor
applied to a standard and high-efficiency motor has different results
because of the motor magnetizing characteristics. In case of highefficiency design motor, it raises the terminal voltage to 680 V.
A capacitor size can be selected for the power factor improvement based on the following equation:
kvarc ≤ 3I 0 sin φ0
(6-36)
144
CHAPTER SIX
FIGURE 6-32
FIGURE 6-33
DC link voltage and current transients, Fig. 6-31.
Various methods of connection of capacitors with motors.
where kvarc is the maximum capacitor that can be applied, I0 is the
motor no-load current, and φ0 is the no-load current power factor
angle. This means that the capacitor size does not exceed the motor
no-load reactive kvar. However, this no-load excitation motor data
is not readily available and the size of capacitor application for a
specific motor design should be based on the manufacturer’s recommendations. The capacitors should not be directly connected to
the motor terminals when:
■
Solid-state starters are used
■
Open transition starting methods are applied; see Chap. 11
■
The motor is meant for repeated switching, jogging, inching,
or plugging
■
A reversing or multispeed motor is used
■
A high inertia load may drive the motor, that is, a broken
belt of a conveyor
6-12 INTERRUPTIONS OF CAPACITANCE CURRENTS
A breaker may be used for line dropping and interrupt charging
currents of cables open at the far end or shunt capacitor currents.
These duties impose voltage stresses on the breaker. A single-phase
TRANSIENTS OF SHUNT CAPACITOR BANKS
FIGURE 6-34
Self-excitation of motors with capacitors—typical motor saturation characteristics, (a) standard design, (b) high-efficiency design.
circuit for capacitive current interruption is in Fig. 6-35a. The distributed line capacitance is represented by a lumped capacitance
C2, or C2 may be a power capacitor. C1 is the source capacitance.
The current and voltage waveforms of capacitance current interruption in a single pole of a circuit breaker under following three
conditions are shown in Figs. 6-35b, c, and d.14
■
Without restrike
■
With restrike
■
With restrike and current chopping
After interruption of the capacitive current, the voltage across
the capacitance C2 remains at the peak value of the power frequency voltage:
u2 =
2 un
3
145
(6-37)
The voltage at the supply side oscillates at a frequency given by
supply side C1 and L1, about the driving voltage un. The difference of
these two voltages appears at the breaker pole. This can be more than
double the rated voltage, with no prior charge on the capacitors. If
the gap across poles of a circuit breaker has not recovered enough
dielectric strength, restrike may occur. As the arc bridges the parting contacts, the capacitor being disconnected is again reconnected
to the supply system. This results in a frequency higher than that of
the natural frequency of the source side system being superimposed
on the 60-Hz system voltage. The current may be interrupted at a
zero crossing in reignition process. Thus, the high-frequency voltage
at its crest is trapped on the capacitors. Therefore, after half a
cycle following the restrike, the voltage across the breaker poles
is the difference between the supply side and the disconnected
side which is at peak voltage of the equalizing process and a second restrike may occur. Multiple restrikes can occur, pumping the
capacitor voltage to three, five, and seven . . . times the system
voltage at each restrike. The multiple restrikes can terminate in two
ways: (1) these may cease as the breaker parting contacts increase
the dielectric strength; and (2) these may continue for a number of
cycles, until these are damped out.
A distinction should be made between reignitions in less than
5 ms of current zero and reignitions at 60-Hz power frequency.
Reignitions in less than 5 ms have a small voltage across the circuit
breaker gap and do not lead to overvoltages. Most breakers exhibit
current chopping; see Chap. 8. It is usually caused by the instability
of arc at low magnitude of currents due to high arc voltages. The
chopping currents of modern breakers have been reduced, but it
is clear that the capacitor charge will not be at peak if chopping
occurs. This will lower the recovery voltage peak across the breaker
gap. See Chap. 8 for recovery voltage profiles.
In Fig. 6-35d, the current is chopped before it reaches its natural
zero. The voltage on the disconnected side does not remain at the
service frequency peak voltage, but at a lower momentary value ua
of the driving voltage. Depending on the supply source impedance,
the chopping current ia creates an oscillation with an overvoltage,
and the voltage us across the breaker contacts can rise to:
u s = ua + u0 + λ ua2 +
L1 2
i
C1 a
where l is the damping coefficient <1.
(6-38)
F I G U R E 6 - 3 5 (a) A single phase circuit for capacitive current interruption. (b), (c), and (d ) Interruption with no restrike, with restrike, and with current
chopping, respectively.
146
TRANSIENTS OF SHUNT CAPACITOR BANKS
FIGURE 6-36
6-12-1
Sequence of creating trapped charges in an ungrounded three-phase capacitor bank. (a) Phase a clears first. (b) Phases b and c clear in series.
Disconnecting A Three-Phase Bank
Disconnecting a three-phase capacitor circuit is more complex. The
instant of current interruption and trapped charge level depends
on the circuit configuration. In an ungrounded three-phase wyeconnected bank, commonly applied at medium- and high-voltage
levels, let phase a current be first interrupted. This will occur when
the voltage of phase a is at its peak. Figure 6-36a shows that phase a
is interrupted first. The charge trapped in phase a is 1 per unit and
that trapped in phases b and c is 0.5 per unit.
The interruption of phase a changes the circuit configuration and
connects the capacitors in phases b and c in series. These capacitors
are charged with equal and opposite polarities. The current in phases b
and c will interrupt simultaneously as soon as phase-to-phase current
becomes zero. This will occur at 90° after the current interruption in
phase a at the crest of the phase-to-phase voltage so that an additional
charge of 3 / 2 is stored in the capacitors, as shown in Fig. 6-36b.
These charges will add to those already trapped on the capacitors in
Fig. 6-36a, and thus voltages across the capacitor terminals are:
Ea =1.0 per unit
Eb = 0.37 per unit
Ec = 1.37 per unit
Further escalation of voltages occurs if the phases b and c are
not interrupted after 90° of current interruption in phase a. The
voltage across the interrupting breaker pole will be the sum of supply system voltage and the charge trapped, maximum occurring in
phase c, equal to 2.37 per unit. The capacitor bank is considered
ungrounded and the stray capacitance to ground is ignored in the
above analysis. It is hardly possible to take into account all modes
of three-phase interruptions with restrikes.14
Advancements in the contact materials in vacuum interruption
technology has reduced the restrikes and prestrikes of initial years,
and so also the chopped currents.15 However, it cannot be said
that the restrikes are totally eliminated. The application of surge
arresters provides a safeguard against these overvoltages and consequent insulation failures.16
6-13
147
CONTROL OF SWITCHING TRANSIENTS
The capacitor-switching transients can be controlled by:
■
Using point-of-wave switching (synchronous breakers).
■
Implementing the application of surge arresters.
■
Dividing the capacitor bank into smaller size banks. The
smaller the size of the capacitor bank being switched, the
lesser is the transient.
■
Avoiding application of capacitors at multivoltage levels
to eliminate possibilities of secondary resonance. Metal-oxide
varisitors (MOVs) can be applied at lower voltage buses.
■
Converting the capacitor banks to capacitor filters; this is
a must when harmonic-generating loads are present. This is
one effective way to mitigate transients, eliminate harmonic
resonance, and control harmonic distortion. Active filters can
be used, depending on the size of the capacitive compensation
and harmonic mitigation required for a particular system.
■
Providing current-limiting reactors and chokes, which is a
must for back-to-back switching and to have acceptable capacitor switching duties on circuit breakers and switching devices.
■
Considering steady-state voltage rise due to the application
of capacitors. The transformer taps may have to be adjusted.
6-13-1 Resistance Switching
In ac current interruption technology, the use of switching resistors in high-voltage breakers is well implemented to reduce the
overvoltages and frequency of transient recovery voltage (TRV);
see Chap. 8. In medium voltage cubical-type or metal-clad circuit
breakers, as the switching resistors are not integral to the breakers,
two breakers can be used, as shown in Fig. 6-37, to preinsert the
resistor for a short duration.
Figure 6-38 shows a basic circuit of resistance switching. A resistor r is provided in parallel with the breaker pole and R, L, and C are
the system parameters on the source side of the break. Consider the
current loops in this figure. The following equations can be written:
u n = iR + L
di 1
+
dt C
∫ ic dt = ir r
■
Using series inrush current limiting reactors.
1
C
■
Using resistance switching.
i = ir + ic
∫ ic dt
(6-39)
(6-40)
(6-41)
148
CHAPTER SIX
The same result could have been arrived at directly from Chap. 2.
Again reverting to the switching of 6-Mvar capacitor bank, and
substituting the values, the transient disappears for a resistance
of 1.32 Ω.
The simulation is shown in Figure 6-39a and b for current and
voltage, respectively. A 1.32-Ω resistor is inserted for four cycles only.
This clearly shows the effect of resistance switching on damping out
the switching inrush transients. The current and voltage waveforms
are at fundamental frequency; only minor excursions are visible.
6-13-2 Point-of-Wave Switching or
Synchronous Operation
FIGURE 6-37
Two metal-clad indoor breakers organized for
resistance switching.
In all the examples, the transients are calculated with the switch
closed at the peak of the voltage wave. A breaker can be designed to
open or close with reference to the system voltage sensing and zero
crossing.17,18 An example of switching a transmission line with synchronous closing is discussed in Chap. 7. The switching device must
have enough dielectric strength to withstand system voltage until its
contacts touch on a closing operation. The consistency of closing
within ± 0.5 ms is possible. Grounded capacitor banks are closed
with three successive phase-to-ground voltages reaching zero, for
example, 60° separations. Ungrounded banks are controlled by
closing the first two phases at a phase-to-phase voltage of zero, and
then delaying the third phase 90°, when phase-to-ground voltage
is zero. The results obtained approximate resistance switching. See
Chap. 7 for an EMTP simulation of synchronous closing.
6-13-3 Surge Arresters
FIGURE 6-38
Diagram to explain resistance switching.
This gives:
d 2ir R 1 dir 1
R
+
+
i =0
+
+
dt 2 L rC dt LC rLC r
(6-42)
The frequency of the transient is given by:
fn =
1
2π
1
1 R 1
−
−
LC 4 L rC
■
On the switching circuit breakers to control the TRV when
the shunt capacitors are switched out. See Chap. 8.
2
(6-43)
In power systems, R is << L. If a parallel resistor across the
1
contacts of value r <
L /C is provided, the frequency reduces
2
to zero. The value of r at which frequency reduces to zero is called
the critical damping resistor. The critical resistance can be evaluated in terms of the system short-circuit current, Isc:
un
1
r=
2 I scω C
Chapter 20 is devoted to surge arresters. Here it can be said that
gap-type surge arresters in series with nonlinear resistors can be
exposed to high stresses when protecting capacitor banks. If a
transient triggers the arrester, the capacitors will discharge totally
and the energy is dissipated in the arresters. Conversely, gapless
metal oxide arresters will not discharge the capacitors below the
system-rated voltage, as there is smooth transition from conducting
to insulating condition.
The possibility of overvoltages due to lightning, switching surges,
and temporary overvoltages requires a detailed evaluation before
the application of surge arresters close to a capacitor bank.19
On an incoming surge, the capacitors will absorb the charge, not
much dependent on the rate of rise of the incoming voltage. Shunt
capacitor banks have low surge impedance and to an extent may be
self-protecting in case there are other surge arresters properly rated
for lightning surge duty. Depending on the substation configurations, additional surge arresters may be necessary.
The overvoltage protection should be considered at the following locations:
(6-44)
■
At the primary of transformer to limit phase-to-phase
voltage due to capacitor switching. See Chap. 14. Also,
on the secondary of the transformer windings close to the
switched capacitors, an example of which has been discussed
in this chapter.
■
At the end of transformer-terminated lines to limit the
phase-to-phase overvoltages due to capacitor switching.
■
■
On neutrals of ungrounded capacitor banks.
On coupled low-voltage systems; Example 6-6 given in this
chapter.
TRANSIENTS OF SHUNT CAPACITOR BANKS
FIGURE 6-39
(a) Capacitor switching current with resistor switching, Fig. 6-1. (b) 13.8-kV bus voltage with resistance switching.
149
150
6-14
CHAPTER SIX
SHUNT CAPACITOR BANK ARRANGEMENTS
Shunt capacitor banks are formed from standard unit capacitor sizes
available in certain kvar and voltage ratings. The unit sizes are generally limited to 100, 200, 300, and 400 kvar, and their voltage ratings
are: 21.6, 19.92, 14.4, 13.8, 13.28, 12.47, 9.96, 9.54, 8.32, 7.96,
7.62, 7.2, 6.64, and so on, all in kV. To form a capacitor bank at a
certain system voltage, a number of units are required to be connected in series and parallel combination, as shown in Fig. 6-40.
A capacitor bank for 500 kV can be formed with the following
alternative capacitor units:
TABLE 6-2 Minimum Number of Units in Parallel
per Series Group to Limit Voltage on the
Remaining Units to 110% with One
Unit Out
NUMBER
SERIES
GROUPS
GROUNDED
WYE OR
DELTA
UNGROUNDED
WYE
DOUBLE-WYE,
EQUAL
SECTIONS
1
—
4
2
2
6
8
7
3
8
9
8
4
9
10
9
OF
■
14 series strings of 21.6-kV capacitor units are required.
■
20 series strings of 14.4-kV capacitor units are required.
■
30 series strings of 9.54-kV capacitor units are required.
5
9
10
10
■
38 series strings of 7.62-kV capacitor units are required.
6
10
10
10
There are imitations on the formation of series strings and the
number of capacitor units in a parallel string. Figure 6-40 shows
that each capacitor unit is protected by a fuse. A minimum number
of capacitors in parallel should be placed per series group to limit
the overvoltages on the remaining units to 110 percent, in case one
capacitor goes out, say due to operation of its fuse. Table 6-2 shows
the minimum number of units in parallel per series group to limit
voltage on remaining units to 110 percent with one unit out.
Table 6-3 provides analytical expressions for the calculations of
fault current and voltage on each remaining group in series with
one group faulted.
Individual capacitor fusing is selected to protect the rupture/
current rating withstand capability of the capacitor can, and the
fuse operates to prevent a rupture of the capacitor can. The maximum
7
10
10
10
8
10
11
10
9
10
11
11
10
10
11
11
11
10
11
11
11
11
11
12 and above
TA B L E 6 - 3
BANK CONFIGURATION
60-Hz Fault Current and Voltages
with One Unit Shorted
FAULT CURRENT
VOLTAGE ON EACH REMAINING
GROUP IN SERIES WITH FAULTED
GROUP
Wye, grounded
S *
I
S −1 φ
Single, ungrounded
3S
I
3S − 2 φ
VLG
S −1
3VLG
3S − 2
Double, ungrounded
6S
I
6S − 5 φ
6VLG
6S − 5
S = Number of series groups.
I φ = Nominal phase current, A.
*
For S = 1, the current is the system line-to-ground fault current.
VLG = Line-to-ground voltage V. (Maximum value is used where appropriate).
number of capacitors that can be connected in parallel in a series
group is dictated by the energy liberated and fed into a fault
when a fuse operates. Figure 6-41 depicts that for a fault in one
of the parallel units, the stored energy in the parallel capacitor units is fed into the fault and the protecting fuse must be
able to handle this energy, depending on its characteristics. This
energy release may be approximately calculated from the following equations:
F I G U R E 6 - 4 0 Typical arrangement of the formation of a highvoltage capacitor bank.
E = 2 . 64 J/kvarc rated voltage
(6-45)
E = 2 . 64(1 . 10)2 J/kvarc 110 % voltage
(6-46)
E = 2 . 64(1 . 20)2 J/kvarc 120 % voltage
(6-47)
Normally with expulsion-type fuses, commonly used for outdoor rack-mounted capacitor banks, 3100 kvar of capacitors in
TRANSIENTS OF SHUNT CAPACITOR BANKS
FIGURE 6-41
151
Limitation of number of capacitor units in parallel with expulsion-type fuses.
total can be connected in a parallel group, that is, a maximum of
ten 300 kvar units. When current-limiting fuses are used, this limit
can be increased.
6-14-1 Connections and Grounding of
Capacitor Banks
The capacitor banks can be connected in a variety of three-phase
connections, depending on their size, optimum utilization of the
capacitor units, fusing, and protection. The following are the common connection methods:
rated for line-to-line voltage. A wye-ungrounded group can be
formed with one series group per phase when the required operating voltage corresponds to standard capacitor unit rating. For
example, for 13.8-kV service voltage, one series group is adequate with capacitors rated for 7.96 kV ( 3 × 7 . 96 = 13 . 8 kV )..
Grounded wye neutrals and multiple series groups are required
for higher voltages above 35 kV. As a rule of thumb, when the
system is effectively grounded, the capacitor bank neutral is
grounded. The grounded capacitor banks have the following
characteristics:
■
■
Multiple series groups, grounded wye connection
■
Ungrounded wye connections
■
Grounded double-wye neutrals
These provide a low-impedance path to ground for the
harmonic currents. The resulting harmonic currents may
cause interference with the communication systems if
the power lines are paralleled with the communication
circuits.
■
Delta connections
■
These connections are shown in Fig. 6-42. Delta connection
is common for the low-voltage systems, with one series group
FIGURE 6-42
An open phase produces zero sequence currents which
may cause ground fault relay operation.
■
Third-harmonic resonance could be a problem.
Grounding arrangements of three-phase capacitor banks.
152
CHAPTER SIX
■
As the neutral is grounded, the recovery voltages on current
interruption are reduced.
■
A low-impedance path is provided to lightning surge currents
and gives some protection from the surge voltages. Sometimes,
the bank can be operated without surge arresters.
On the other hand, the ungrounded banks have the following
characteristics:
■
Banks do not provide any surge voltage protection and
provide no path to ground for third-harmonic currents.
■
The entire bank, including the neutral, must be insulated for
line-to-line voltage.
When a bank is too large to meet the requirements of 3100 kvar
per group as a maximum for the application of expulsion-type fuses
or large enough to meet the minimum series group requirements,
the bank can be split into two wye sections. The two neutrals are
usually ungrounded.
PROBLEMS
1. A distribution system is shown in Fig. 6-P1. Calculate
the voltage and current transients on sudden switching
of 10-Mvar capacitor bank, when the bus section circuit
breaker is closed. Ignore the nonlinear load shown in dotted
lines.
2. Repeat Problem 1 with bus section circuit breaker open.
3. In Fig. 6-P1, the 10-Mvar capacitor bank is divided into
two banks of 5 Mvar each. If the total inductance between the
banks is 15 µH, calculate the inrush current and its frequency
on energizing a 5.0-Mvar bank when the other 5.0-Mvar bank
is in service.
FIGURE 6-P1
4. In Problem 3, calculate the inductance to drop the inrush
current and frequency of inrush current to 15 kA and 2000 Hz,
respectively.
5. Find the value of R for resistance switching in Problem 1
with bus section circuit breaker open, and then repeat with the
bus section circuit breaker closed.
6. Ignoring the nonlinear load, what is the Thévenin impedance
of the system, as seen from 13.8-kV bus A? Use complex R + jX
calculation to combine the component impedances.
7. Consider that the nonlinear load shown within dotted lines
has a harmonic current spectrum, as shown in Table 6-1. Find the
current in the capacitor bank at each of the harmonics 5th, 7th,
and 11th.
8. Calculate the current in the Thévenin impedance at each of
the harmonics 5th, 7th, and 11th. From this calculation, find the
harmonic current injected into 138-kV utility system at each of
the harmonics.
9. Why can the power factor of an induction motor not be
corrected to unity? Explain self-excitation and what gives rise
to it. How it can be avoided?
10. Form a 58-Mvar, 34.5-kV, neutral grounded, wye-connected
capacitor bank. Select a number of units in a parallel in each
group and total number of series units in parallel, using the
guidelines given in this chapter.
11. In Problem 10, calculate the fault current when one unit is
shorted. Calculate the voltage in each remaining group in series
with faulted group.
12. Figure 6-13 does not show the voltage waveform of
4.16-kV bus. Will it be the same as in Fig. 6-8? Will it be
much improved because of filter?
A power system configuration for problems.
TRANSIENTS OF SHUNT CAPACITOR BANKS
REFERENCES
1. J. F. Witte, F. P. DeCesaro, and S. R. Mendis, “Damaging
Long Term Overvoltages on Industrial Capacitor Banks Due
to Transformer Energization Inrush Currents,” IEEE Trans.
Industry Applications, vol. 30, no. 4, pp. 1107–1115, July/
Aug. 1994.
2. ANSI/IEEE Std. C37.06-1987 (R2000), AC High Voltage Circuit Breakers Rated on a Symmetrical Current Basis—Preferred
Ratings and Related Required Capabilities.
3 ANSI/IEEE Std. C37.012-1979 (R2000), IEEE Application
Guide for Capacitance Current Switching for AC High Voltage
Circuit Breakers Rated on a Symmetrical Current Basis.
4. H. M. Pflanz and G. N. Lester, “Control of Overvoltages on
Energizing Capacitor Banks,” IEEE Trans. PAS, vol. 92, no. 3,
pp. 907–915, May/June 1973.
5. R. S. Bayless, J. D. Selmen, D. E. Traux, and W. E. Reid,
“Capacitor Switching and Transformer Transients,” IEEE Trans.
PWRD, vol. 3, no. 1, pp. 349–357, Jan. 1988.
6. IEEE Report by Working Group 3.4.17, “Surge Protection of
High Voltage Shunt Capacitor Banks on AC Power Systems—
Survey Results and Application Considerations,” IEEE Trans.
PWRD, vol. 6, no. 3, pp. 1065–1072, July 1991.
7. IEEE Std. 1036-1992, IEEE Guide for Application of Shunt
Power Capacitors, 1992.
8. J. C. Das, “Passive Filters—Potentialities and Limitations,”
IEEE Trans. Industry Applications, vol. 40, no.1, pp. 232–241,
Jan./Feb. 2004.
9. IEEE Std. 519, IEEE Recommended Practice and Requirements for Harmonic Control in Electrical Power Systems,
1992.
10. Zabrosky and J. W. Rittenhouse, “Fundamental Aspects of
Some Switching Overvoltages in Power Systems,” AIEE,
pp. 822–830, Feb 1963.
11. R. A. Jones and H. S. Fortson, Jr., “Considerations of
Phase-to-Phase Surges in the Application of Capacitor
Banks,” IEEE Trans. PWRD, vol. PWRD-1, no. 3, pp. 240–
244, July 1986.
12. V. E. Wagner, J. P. Staniak, and T. L. Oreloff, “Utility Capacitor Switching and Adjustable Speed Drives,” IEEE Trans.
Industry Applications, vol. 27, no. 4, pp. 645–652, July/
Aug. 1991.
13. NEMA MG-1, Generators and Motors, 2003.
14. J. C. Das, “Analysis and Control of Large Shunt Capacitor Bank
Switching Transients,” IEEE Trans. Industry Applications, vol.
41, no. 6, pp. 1444–1451, Nov./Dec. 2005.
153
15. M. Gelinkowski, A. Greenwood, J. Hill, R. Mauro, and
V. Varneckes, “Capacitance Switching with Vacuum Circuit
Breaker—A Comparative Evaluation,” IEEE Trans. PWRD,
vol. 6, no.3, pp. 1088–1094, July 1991.
16. S. F. Farag and R. G. Bartheld, “Guidelines on the Application
of Vacuum Contactors,” IEEE Trans. Industry Applications, vol.
IA-22, no. 1, pp. 102–108, Jan./Feb. 1986.
17 R. W. Alexander, “Synchronous Closing Control for Shunt
Capacitor Banks,” IEEE Trans. PAS, vol. 104, no. 9,
pp. 2619–2626, Sep. 1985.
18 J. H. Brunke and G. G. Schockelt, “Synchronous Energization of Shunt Capacitors at 230 kV,” IEEE Trans. PAS,
vol. 97, no. 4, p. 1009, July/Aug. 1978.
19. M. P. McGranaghan, W. E. Reid, S. W. Law, D. W. Gresham,
“Overvoltage Protection of Capacitor Banks,” IEEE Trans.
PAS, vol. 103, no. 8, pp. 2326–2336, Aug. 1984.
20. IEEE. Std-18, IEEE Standard for Shunt Power Capacitors, 2002.
21. IEEE. Plo36/D 13a, Draft Guide for Application of Shunt
Power Capacitors, Sept. 2006.
FURTHER READING
E. W. Boehne and S. S. Low, “Shunt Capacitor Energization with Vacuum Interrupters—a Possible Source of Overvoltage,” IEEE Trans.
PAS, vol. 88, no. 3, pp. 1424–1443, Sep. 1969.
J. C. Das, “Effects of Medium Voltage Capacitor Bank Switching
Surges in an Industrial Distribution System,” in Conf. Record, IEEE
IC & PS Conf. Pittsburgh, pp. 57–64, 1992.
A. A. Girgis, C. M. Fallon, J. C. P. Robino, and R. C. Catoe, Jr., “Harmonics and TRV Due to Capacitor Switching,” IEEE Trans. Industry
Applications, vol. 29, no. 6. pp. 1184-1189. Nov./Dec. 1993.
A. Greenwood, Electrical Transients in Power Systems, John Wiley &
Sons, New York, 1994.
IEEE Working Group on Capacitance Switching, “Bibliography on
Switching of Capacitance Circuits Exclusive of Series Capacitors,”
IEEE Trans. PAS, vol. 89, no. 6, pp. 1203–1207, July/Aug. 1970.
M. McGranagham, W. E. Reid, S. Law, and D. Gresham, “Overvoltage
Protection of Shunt Capacitor Banks Using MOV Arresters,” IEEE
Trans. PAS, vol. 104, no. 8, pp. 2326–2336, Aug. 1984.
M. F. McGranaghan, R. M. Zavadil, G. Hensley, T. Singh, and
M. Samotyj, “Impact of Utility Switched Capacitors on Customer
Systems—Magnification at Low-Voltage Capacitors,” IEEE Trans.
PWRD, vol. 7, no. 2, pp. 862–868, April 1992.
R. P. O’ Leary and R. H. Harner, “Evaluation of Methods for Controlling the Overvoltage Produced by Energization of Shunt Capacitor Banks,” CIGRE 1988, Session Paper No. 13-05.
This page intentionally left blank
CHAPTER 7
SWITCHING TRANSIENTS AND
TEMPORARY OVERVOLTAGES
In Chap. 4, the reflection, refraction, and transmission factors for
various line terminations are calculated. Also, Ferranti effect, line
compensation, and some EMTP simulations of surge voltages on
lines and cables are examined. This investigation is continued in this
chapter. Surges occur because of sudden interaction of the trapped
charge with the system voltage. Sometimes the switching surges
are superimposed upon short-term power frequency overvoltage.
The charge is trapped in the line capacitance which is distributed
along the length of the line. This introduces 168complexity in
determining the shape and peak magnitude of the switching surges
due to reflections, similar to lightning surges. Underground cables
have a higher capacitance than overhead lines and the switching
surges of overhead lines terminated in cables or vice versa become
important. Akin to the switching of capacitors, most severe surges
occur from restrikes and reclosing when the supply waveforms
have reversed. An important factor of distributed capacitance and
inductance of the overhead lines is that surges originating at a point
take time to travel along a line and get reflected and re-reflected at
the impedance discontinuities. Consequently, the wave shapes of
the line-switching surges are quite different from the switching of
lumped elements.
To calculate the maximum switching surge voltage, it is necessary to determine the magnitude of the initial surge and then follow
it with appropriate delays and reflections at each discontinuity. The
analysis can be simplified by EMTP and other computer programs,
like TLTA.1
7-1
CLASSIFICATION OF VOLTAGE STRESSES
The voltage stresses in the electrical systems can be classified as
follows:
■
Continuous power frequency voltages vary in the power systems, and the limits are defined in the standards. For insulation
coordination, maximum system voltages are used (Chap. 17).
■
Lightning (fast front) overvoltages, caused by lightning
(Chap. 5).
■
Switching (slow front) overvoltages, caused by switching,
fault initiation, or remote lightning strikes (this chapter and
Chap. 8).
■
Temporary overvoltages, caused by faults, load rejection,
line energizing, resonant conditions, ferroresonance (this
chapter and Chaps. 8, 9, and 14).
■ Very fast front overvoltages usually associated with highvoltage disconnect switch operation and GIS, and cable connected motors (Chap. 18).
A diagrammatic representation of this classification is shown in
Fig. 7-1 with relative amplitudes of the voltages. This figure does
not show the time duration for which the overvoltage condition
can last. Also the shape of waveforms in each case can vary. Thus,
the figure is a simplified diagrammatic representation of the relative
magnitudes. Overvoltages sustained for a longer period are called
temporary overvoltages. This has some technical basis, in the sense
that the breakdown of insulation is not only a function of the electrical stress to which it is subjected, but also of the time duration for
which this condition lasts. A surge arrester will limit the transient
overvoltage to its protective level (Chap. 20), but may not impact
the temporary overvoltages of lower magnitude, though resonant
conditions must be considered. Surge arresters can be applied to
counteract the resonant conditions.
7-2
MAXIMUM SYSTEM VOLTAGE
The voltages in a power system and to the consumers must be maintained within certain narrow limits. The electrical systems generally
operate at 5 to 10 percent below the maximum system voltage for
which the system components are designed. The system operating
voltage is regulated by the utilities, and a 5 percent overvoltage
limit seems appropriate. This may be exceeded in some cases, that
is, close to a generating station.
The maximum system voltage is defined as the highest system
voltage for which equipment and other components are designed
for satisfactory continuous operation without any derating. Nominal system voltage is defined as the voltage by which a portion of the
system is designated and to which certain operating characteristics
of the system are related. Each nominal system voltage pertains
to a portion of the system bounded by transformers or utilization
equipment.
The term low voltage embraces voltages up to 1000 V, medium
voltage from 1000 V to 100 kV, and high voltage 100 to 230 kV.
155
156
CHAPTER SEVEN
act and tend to limit this voltage rise. A rigorous calculation
will require modeling of generator, governor, regulator, and
transmission-line parameters. For turbo generators, the
maximum speed rise on full load rejection is approximately
10 percent, and it occurs in less than 1 s. In water wheel
generators the maximum speed rise on full load rejection can
be as high as 60 percent, and it may take 10 s to reach it.
3. When a generator is suddenly off-loaded, say due to
isolation of a load, the voltage will rise. A rigorous study
with a transient generator model is included in Chap.12.
For an approximate calculation it can be assumed that
voltage behind subtransient reactance of the generator
remains unchanged, but after a few cycles, the voltage
E′d behind transient reactance becomes the driving voltage.
This gives the following relation:
f
E′d
V1 =
f
0
fX s
1 −
f0 X c
FIGURE 7-1
Relative magnitudes of temporary, switching, and
lightning overvoltages—a generalization.
Extra high voltage (EHV) is 345 to 765 kV and ultrahigh voltage
above 765 kV.
ANSI standard2 defines two sets of tolerance limits: range A,
which specifies the limits under most operating conditions, and
range B, which specifies minor excursions outside range A. Corrective action should be taken when the voltage is in range B to restore
it to range A. For transmission voltages over 345 kV, only the nominal and maximum voltages are specified, that is, 362 kV, which
is higher by approximately 5 percent. As an example for 13.8-kV
nominal voltage, range A = 14.19 to 12.46 kV, and range B = 14.5
to 13.11 kV. The control and regulation of the voltages is important
for the operations of the electrical equipment, and the analysis of
the steady-state voltage profiles in the power system are analyzed
by load-flow methods. For the application of the surge arresters,
maximum system voltages are considered.
7-3
TEMPORARY OVERVOLTAGES
The overvoltages can be classified with respect to the system operation. The overvoltages produced by the following operations may
be called temporary overvoltages:
1. Fault overvoltages, generally produced due to ground
faults. The system grounding plays an important role
(Chaps. 9 and 21). The significance of the coefficient of
grounding and earthling factor are discussed in Chap. 9 with
a rigorous calculation of coefficient of grounding (COG)
using the method of symmetrical components. In a four-wire
system, with neutral grounded at multiple points, the fault
current will divide between neutral conductor and earth; the
accuracy of a symmetrical component method for calculations
of overvoltages in multiple-grounded systems is discussed in
Chap. 19.
2. Load rejection overvoltages, which originate when a loaded
system is suddenly unloaded, say, due to load rejection. A system with relatively short lines and high short-circuit power will
have low overvoltages, while a system with long lines and low
short-circuit power will have high overvoltages. On a sudden
load rejection, the generators will speed up and the voltage will
rise. The speed governors and automatic voltage regulators will
(7-1)
where Xs is the reactance between E′d and V1, the sending
end voltage, Xc, is the capacitive input reactance of the
open-circuited line at the increased frequency, and f/f0 is the
ratio of the instantaneous frequency at the time maximum
voltage is reached and the supply system frequency. The problem occurs in estimating f.
4. Resonance and ferroresonance overvoltages arise because
of interaction of capacitive elements and inductive elements
having nonlinear characteristics, for example, transformers,
Chapter 14.
5. Overvoltages due to transformer energizing (Chap. 14).
6. Some other causes of overvoltages are: ferranti effect, discussed in Chap. 4 (also see Example 4-2), backfeed through
interconnected transformer windings, harmonic overvoltages.
The overvoltages usually precede the transient overvoltagecausing event, for example, a switching operation.
Another classification of the temporary overvoltages is based
upon the frequency characteristics. In Table 1-3, the temporary
overvoltages have been classified in to Group 1 (0.1 to 3 kHz,
low-frequency oscillations) and switching overvoltages into Group
II (50/60 to 20 kHz, slow front surges). Also consider:
■
Overvoltages with a frequency of oscillation equal to the
power frequency. Here the overvoltage is sinusoid or almost
a sinusoid, devoid of harmonics. Both types of overvoltages,
appearing phase-to-phase and phase-to-ground are considered.
Temporary overvoltages arising under linear conditions belong
to this category.
■
Overvoltages with a frequency of oscillation higher than the
power frequency. Overvoltages due to harmonics can only arise
if there is nonlinearity present in the system. This nonlinearity
can result from power electronics, saturated magnetic characteristics of transformers, shunt reactors, and measurement transformers.
■
Overvoltages with a frequency of oscillation lower than the
power frequency (Chap. 12.)
IEC3 classifies slow front overvoltages as the voltages arising from:
■
Line energization and re-energization
SWITCHING TRANSIENTS AND TEMPORARY OVERVOLTAGES
■
Faults and fault clearing
■
Load rejection
■
Switching of capacitive and inductive circuits
■
Distant lightning strokes to the conductor of overhead lines
The probability distribution of the overvoltages without surge
arresters is characterized by its 2 percent value, its deviation, and
truncation value. This can be approximated with gaussian distribution with a 50 percent value at truncation, above which no values
are assumed to exist (Chap. 17).
7-4
SWITCHING SURGES
Ignoring the distinction between temporary overvoltages and
switching overvoltages, some mechanisms of generating these are:
■
Charging an unloaded line, which has not been charged
before, and open at far end, as studied in Chap. 4.
■
Switching lines terminated in transformers.
■
Series capacitor compensated lines, static condenser (STATCON), SVCs, and other flexible ac transmission system (FACT)
devices, which are discussed in Chap. 15.
157
circuits on lines and systems above 300 kV. Less than 1 percent
short circuits are caused by switching surges.4 Switching overvoltages do not cause flashovers to the same extent as caused by
lightning. The frequency, point of occurrence, amplitude, and characteristics govern the selection of equipment, insulation level, and
economical design. The switching surges gain more importance as
the system voltage rises, and in EHV networks, it is the switching
surges which are of primary importance in insulation coordination. The switching surges have, generally, a power frequency and
a transient component, which bear certain relation to each other
and may be of equal amplitude in the absence of damping. The
nonsimultaneous closing of breaker poles can increase the transient
component. The EHV installations are primarily concerned with
the stresses imposed on the insulation by switching surges and the
coordination of the insulation is based upon these values. To lower
the costs, it is desirable to reduce the insulation levels at high voltages. On the transmission line towers, the flashover voltage cannot be allowed to increase along with service voltage, as beyond
a certain point the electrical strength of air gaps can no longer be
economically increased by increasing the clearances. Thus, while
the external lightning voltages are limited, the switching overvoltages become a primary concern.
Table 7-1 from ANSI/IEEE standard5 shows the switching surge
levels versus the BIL for power transformers. BIL levels commonly
used are shown in bold.
■
Auto-reclosing.
7-5-1
■
Load shedding.
■
VHF overvoltages in GIS (Chap. 15).
The clearance between the tower and conductors influences the
switching surge withstand capability (Fig. 7-2).6 For a particular
insulator suspension arrangement, that is, V-formation or vertical,
there is an upper limit of the surge-withstand voltage, which cannot be much varied by increasing the conductor clearance from
the tower. This occurs at 1600 kV.7,8 The horizontal suspension
arrangement provides the best conditions (Fig. 7-2). In this figure
k = ratio of the maximum amplitude of switching overvoltage to
the amplitude of the service voltage, the symbol (a) is for insulator
strings suspended vertically, (b) for insulator strings in V-formation
with 45° to vertical, and symbol (c) is for horizontal strings of
insulators.
Figure 7-2 also shows rapid increase in the number of insulator elements at higher voltages. To adhere to the limit of 1600 kV,
for 800-kV systems, the switching surge should be limited to two
times the peak value of the maximum voltage. The values shown
in Table 7-2 have been found satisfactory for systems above 362
kV. In the design of an economical tower, it is necessary to consider proximity effect of the grounded metal which accentuates
the saturation characteristics of the air gap. This is illustrated in
Fig. 7-3 for the center phase of a 735-kV tower; for outer phases
it will be less severe.9 Coordination must be achieved between
string length and clearances to tower metal. It is usually based
upon a dry positive switching impulse, with a wavefront giving
maximum CFO.
Thus, measures which reduce the switching surge, that is, resistor switching and synchronous closing, are very important at higher
voltages. The role of surge arrestors becomes equally important,
(Chap. 20). In order to keep the withstand levels as low as possible,
the surge arresters should be selected so that they operate at the
maximum switching surge and discharge the lines without damage
to themselves.
All equipment for operating voltages above 300 kV is tested
for switching impulses. No switching surge values are assigned to
transformers 69 kV and below (Table 7-1).
Table 7-3,10 shows rated line-closing switching surge factors for
circuit breakers specifically designed to control line-switching closing surge. Note that the parameters are applicable for testing with
standard reference transmission lines, as shown in this table.
■
Disconnection of large inductances, unloaded transformers,
reactors, and the like.
■
Flashovers of longitudinal insulation configuration. This is
an insulation configuration between terminals belonging to the
same phase, but temporarily separated into two independently
energized parts, for example, open switching devices with voltages on source and load sides.
■
Short circuit and fault clearance, that is, when phase-tophase or phase-to-ground faults are cleared.
■
Single-pole closing of circuit breakers.
The surges produced by all these operations vary in severity
and magnitude and are not equally dangerous to the system insulation. Compared to interrupting the low magnetizing currents of the
transformers and disconnections of shunt reactors by circuit breakers, the closing operations cause the highest overvoltages.
Overvoltages of the same peak value can be of different significance. Autoclosing of a line with trapped charge can cause
high overvoltage and precipitate a new fault. This can be avoided
by reclosing with a longer pause or using appropriate switching
devices. Faults and switching operations not only cause transients
of a higher frequency, but also a change in the power frequency.
Both the transient and the power frequency overvoltage define a
switching transient. Switching overvoltages are damped by leakage
resistance and conductivity. Generally 5 percent damping seems
appropriate during the first half wave of the transient frequency,
though a detailed simulation may give different results, that is, resonance is a distinct possibility.
7-5
SWITCHING SURGES AND SYSTEM VOLTAGE
The lightning surges are responsible for approximately 10 percent
of all short circuits in substations and almost 50 percent of short
Line insulation with respect to switching surges
158
CHAPTER SEVEN
TA B L E 7 - 1
Dielectric Insulation Levels for Class II Transformers
SWITCHINGIMPULSE LEVEL
(KV CREST)
4
INDUCED VOLTAGE TEST
(PHASE-TO-GROUND)
1-hr LEVEL
(KV rms)
5
ENHANCEMENT
LEVEL (KV rms)
6
APPLIED VOLTAGE
TEST LEVEL
(KV rms)
7
NOMINAL SYSTEM
VOLTAGE (KV)
1
BIL (KV CREST)
2
CHOPPED-WAVE LEVEL
(KV CREST)
3
15 and below
110
120
34
25
150
165
50
34.5
200
220
70
46
250
275
95
69
250
300
275
385
95
140
115
350
450
550
385
495
605
280
375
460
105
105
105
120
120
120
140
185
230
138
450
550
650
495
605
715
375
460
540
125
125
125
145
145
145
185
230
275
161
550
650
750
605
715
825
460
540
620
145
145
145
170
170
170
230
275
325
230
650
750
825
900
715
825
905
990
540
620
685
745
210
210
210
210
240
240
240
240
275
325
360
395
345
900
1050
1175
990
1155
1290
745
870
975
315
315
315
360
360
360
395
460
520
500
1300
1425
1550
1675
1430
1570
1705
1845
1080
1180
1290
1390
475
475
475
475
550
550
550
550
765
1800
1925
2050
1980
2120
2255
1500
1600
1700
690
690
690
800
800
800
a. For chopped wave tests, the minimum time to flashover shall be 3.0 µs, except for 110-kV BIL, in which case, the minimum time to flashover shall be 2.0 µs.
b. Although Col. 4 establishes phase-to-ground switching impulse levels, it is not always possible to test these levels on low-voltage windings.
c. Columns 5 and 6 provide phase-to-ground test levels, which would normally be applicable to wye windings. When the test voltage is to be measured phase to phase, as
is normally the case with delta windings, then the levels in Col. 5 are multiplied by 1.732 to obtain the requird phase-to-phase induced voltage test level.
d. The applied voltage test is not applicable to wye-windings terminals, unless they have been specified to be suitable for ungrounded systems.
e. The BIL levels in bold are commonly used.
Source: ANSI/IEEE Standard.5
7-6 CLOSING AND RECLOSING OF
TRANSMISSION LINES
The transient phenomena will vary according to the system configuration, the source type, line length, and terminations. For a
line open at the far end, three types of transients on switching are
shown in Fig. 7-4.
Figure 7-4a shows a transient which can be expected when the
source is mainly inductive, for example, a single line connected to
a transformer. It is single-frequency transient, and if switching takes
place at maximum voltage in a phase, the transient oscillates to almost
twice the value of the system voltage across the entire line length.
The losses in the system will dampen the transient by some
percentage.
Figure 7-4b shows a high-frequency transient which can be expected
with infinite source impedance. This means that the system from which
the line originates has a number of cables or lines connected to it, and
the line being switched is not longer than the incoming lines. Many
line terminations and connections at the point of origination of the line
being switched means that these terminations present an overall low
characteristic impedance compared to the line being switched. As a
result the transient occurs at its natural frequency.
Figure 7-4c shows the pattern of switching transient with complex source impedance, consisting of inductance of transformers
SWITCHING TRANSIENTS AND TEMPORARY OVERVOLTAGES
FIGURE 7-2
Relationship between the number of insulators in a string, their method of suspensions, and switching overvoltages at various voltage levels.
TA B L E 7 - 2
Highest system
voltage →
159
Highest Permissible Switching
Overvoltages with Respect to
Highest System Voltage
420
525
765
1150
Switching surge
2.5
overvoltage = highest
system voltage
multiplied by factor →
2.25
2
1.8 or 1.9
and the surge impedance of other lines and cables feeding the system. The transient overvoltage occurs at a number of frequencies.
Highest overvoltages occur when unloaded high-voltage transmission lines are energized and reenergized and this imposes voltage stresses on circuit breakers. Figure 7-5a shows closing of a line
of surge impedance Z0 and length l, open at the far end. Before the
breaker is closed, the voltage on the supply side of the breaker terminal is equal to the power system voltage, while the line voltage is zero.
At the moment of closing, the voltage at the sending end must rise
from zero to the power frequency voltage. This takes place in the form
of a traveling wave on the line with its peak at um interacting with supply system parameters. As an unloaded line has capacitive impedance,
the steady-state voltage at the supply end is higher than the system
voltage, and due to Ferranti effect, the receiving-end voltage is higher
than the sending end. Overvoltage factor can be defined as follows:
OVtotal =
um
un
(7-2)
FIGURE 7-3
Proximity effect of tower window on insulation strength
of single 900-V strings.9
TA B L E 7 - 3
RATED MAXIMUM
VOLTAGE (KV rms)
Rated Line-Closing Switching Surge Factors for Circuit Breakers, Specifically
Designed to Control Line-Closing Switching Surge
RATED LINE-CLOSING
SWITCHING SURGE
FACTOR
LINE LENGTH (mi)
PERCENTAGE SHUNT
CAPACITANCE DIVIDED
EQUALLY AT LINE ENDS
L1
L0/L1
R1
R0
C1
C1/C0
0
1.6
3
0.05
0.5
0.02
1.5
362
2.4
150
500
2.2
200
0
1.6
3
0.03
0.5
0.02
1.5
800
2.0
200
60
1.4
3
0.02
0.5
0.02
1.5
Maximum voltage and parameters of standard reference transmission lines.
L1 = Positive and negative sequence inductance in mH per mile; L0 = zero sequence inductance in mH per mile; R1 = positive and negative sequence resistance in ohms
per mile; R0 = zero sequence resistance in ohms per mile; C1 = positive and negative sequence capacitance in µF per mile; C0 = zero sequence capacitance in µF per mile.
Source: ANSI Standard.10
FIGURES 7-4
FIGURES 7-5
160
Profiles of switching surges on closing a line, dependent upon power system configuration.
(a) Switching a line open circuited at the far end. (b) and (c) Voltage profiles on bus and line side, respectively.
SWITCHING TRANSIENTS AND TEMPORARY OVERVOLTAGES
161
where um is the highest peak voltage at a given point and un is the
power-frequency voltage on the supply side of the breaker before
switching. The power-frequency overvoltage factor is given by:
OVpf =
u pf
un
(7-3)
This is the ratio of the power-frequency voltage upf after closure at
a point and power-frequency voltage un on the supply side before
closing. The transient overvoltage factor is:
OVtr =
um
u pf
(7-4)
The power-frequency overvoltage factor can be calculated by
known line parameters. This is given by:
1
cos αl − X s / Z0 sin αl
(7-5)
where the surge impedance and a are given by:
Z0 =
L1
C1
(7-6)
α = 2π f L1C1
The relation between sending- and receiving-end voltage is
1/cos al, as in Chap. 4.
This shows that the increase in power-frequency voltage depends
considerably on the line length. The transient voltage is not so simple to determine and depends upon the phase angle at the closing
instant, (Fig. 7-5). At instant t = t1, maximum superposition of the
transient and power-frequency voltages occurs.
7-6-1
Impact of trapped charges
Trapped charges occur on the transmission lines in three-pole
autoclosure operations. Contact-making of three poles of a circuit
breaker can be nonsimultaneous. Consider breakers at sending and
receiving end of a line and a transient ground fault, which needs
to be cleared by an auto-reclosure operation. The opening of the
breakers at the sending and receiving ends can be nonsimultaneous. The breaker which opens later must clear two line phases at no
load. These two phases can, therefore, remain charged at the peak of
the power-frequency voltage, which is still present when the closure
takes place. This means that after the dead time, one breaker has to
close with two phases still charged. If the closing instant happens to
be such that the trapped charge and the power frequency voltage are
of opposite polarity, maximum transient overvoltage will occur.
Figure 7-6 shows the closing and reclosing transient of a 400 kV
line, no surge arresters and no compensation. Figure 7-6a shows
closing without a prior charge, while Fig. 7-6b shows closing with a
trapped charge. Note that the overvoltage factor is 3.5 with line precharged versus 2 when there is no charge on the line. The voltage
on the line can, after reflection of the wave, theoretically rise up to
three times the system voltage. When three poles of a breaker close
nonsimultaneously, even higher voltages can occur.
Utilities reclose to restore power for temporary faults. In areas of
low lightning incidence, it may be single-shot reclosure, as majority
of faults may be permanent. In lightning-prone regions, it is common to clear the fault as many as four times. This may consist of
one fast and three delayed operations, or two fast and two delayed
operations. First reclosure interval may be instantaneous or 12 to
30 cycles delayed. An instantaneous reclosure may create some
conflicts with distributed generation trip times, as these will not
tolerate a return of voltage which may be in phase-opposition to the
generation voltage. Also single-pole reclosing is done to enhance
the stability limits (Chap. 12).
F I G U R E 7 - 6 (a) Receiving-end overvoltages on a 400-kV, 400-km line,
open at the far end without prior charge. (b) Overvoltages with prior charge.
Example 7-1 This example is an EMTP simulation of switching
of a 50-mi long 138-kV line, configuration and switching options
as shown in Fig. 7-7.
Figure 7-7a is the system configuration, the line is fed from a
230 to 138-kV step down transformer of 200 MVA, which is wyewye connected, with wye windings solidly grounded. The percentage
impedance = 10 percent and X/R ratio = 50. The source is modeled
with positive- and zero-sequence impedances. The transformer is
modeled as an ideal transformer. There are no surge arresters. A
CP model for the 138-kV line is used. The calculated parameters
of 138-kV line are given in Table 7-4. There are three methods of
switching, which are as follows:
■
Three-pole simultaneous closure, Fig. 7-7b
■
Closure on point of wave, synchronous breakers, Fig. 7-7c
■
Resistance switching, Fig. 7-7d
The switching transients in each of these closing methods are
examined. First consider a three-phase closure at the peak of the
voltage in phase a. The receiving-end and sending-end voltage transients in phase a are shown in Fig.7-8a and b, respectively. The
receiving-end voltage rises to a maximum peak of 280 kV, phase
to neutral, an overvoltage of 2.48 per unit (pu). It has superimposed transient frequency on the power frequency which decays
considerably in the first four cycles. The sending-end voltage peak
is 162 kV, phase to neutral, an overvoltage of 1.42 pu .The charging current is shown in Fig. 7-8c, peak of approximately 400 A.
162
CHAPTER SEVEN
FIGURE 7-7
(a) Power system configuration for EMTP simulation of transients on energizing a line. (b) Three-phase simultaneous closure.
(c) Synchronous closing. (d ) Resistance closing.
The simulations with other switching methods will follow in the
subsequent sections.
7-6-2
Phase-to-phase and phase-to-ground overvoltages
Figure 7-9 from Ref. 3 shows the range of 2 percent overvoltage
values in per unit of system peak line to ground voltage, which can
be expected at a location without the application of surge arresters.
Ue2 denotes the value of phase-to-earth voltages having a 2 percent
TA B L E 7 - 4
probability of being exceeded. This figure is based upon a number
of field results and studies and includes the effect of most of the
factors determining the overvoltages.
Three-phase reenergization may generate high slow-front overvoltages due to trapped charges. In normal systems, single-phase
reenergization does not generate overvoltages higher than those
from energization. However, for lines where resonance or Ferranti effects may be significant, single-phase reclosing can result in
higher voltages than three-phase energization.
138-kV Line Parameters for Examples 7-1, 7-4, and 7-5
VELOCITY
LOSSLESS (mi/S)
VELOCITY
mi/S
ATTENUATION
(Np/mi)
MODE
R W/mi
X/mi
S/mi
Z, REAL
Z, IMAGINARY
Z LOSSLESS
1
5.326E–01
2.589E–0
3.207E–06
8.983E+02
–9.056E+01
8.940E+02
1.318E+05
1.312E+05
2.901E–04
2
1.163E–01
7.897E–01
5.489E–06
3.780E+02
–2.7887E+02
3.762E+02
1.829E+05
1.824E+05
1.527E–04
3
1.150E–01
6.568E–01
6.876E–06
3.248E+02
–2.756E+02
3.236E+02
1.828E+05
1.824E+05
1.756E–04
Note: EMTP provides results up to 10 floating decimal points. The numbers are rounded off in the above table.
ACTUAL
SWITCHING TRANSIENTS AND TEMPORARY OVERVOLTAGES
FIGURE 7-8
163
(a) Receiving-end voltage of phase a on three-phase simultaneous closure. (b) Sending-end voltage, phase a. (c) Line charging current.
164
CHAPTER SEVEN
FIGURE 7-9
Range of 2 percent slow front overvoltages at the receiving end of the line on energization and re-energization. Source: IEC standard.3
FIGURE 7-10
Ratio between 2 percent slow front overvoltages phase-to-phase and phase-to-earth. Source: IEC standard.3
The 2 percent phase-to-phase overvoltages can be determined from
Figure 7-10.3 This figure shows the range of possible ratios between
2 percent phase-to-phase and phase-to-earth voltages. Up2 denotes
the value of phase-to-phase voltages having a 2 percent probability of
being exceeded. The upper limit applies to fast three-phase reenergization overvoltages, the lower limit to three-phase energization voltages.
The instant of phase-to-phase overvoltage peak gives the highest phase-to-phase overvoltage value, typically insulation between
windings and short air clearances. The phase-to-phase overvoltage
at the instant of phase-to-earth voltage peak gives lower overvoltages than the instant of phase-to-phase overvoltage peak, but it may
be more severe for some insulation configurations. Typical situations are large air clearances for which the instant of positive phaseto-earth peak is more severe, or gas-insulated substations for which
negative peak is more severe3.
7-7
OVERVOLTAGES DUE TO RESONANCE
The switching inrush current of transformers contains odd and
even harmonics (Chap. 14). When a line and transformer are
energized together, resonance overvoltages can occur. Figure 7-11
shows that a 765-kV line, 70-mi long is fed from a 400-kV system and has 800-MVA transformers at the sending and receiving ends. The system has a resonant frequency around third
harmonic. An EMTP simulation of the receiving end voltage at
transformer T2 primary (765 kV) is in Fig. 7-12. The saturation
of a transformer reduces the receiving-end voltage, but the resonant phenomenon counteracts it. It is seen that the receiving-end
voltage is 1470-KV peak, an overvoltage factor of 2.35. The effect
of transformer inrush current harmonics is clearly visible in this
figure. The nonlinearity can be supposed to give rise to harmonics, which, akin to fundamental frequency, can be modeled as
two-port networks.
Switching charging currents through transformers can be less
onerous than switching the same current directly. The capacitive
currents will oscillate with the transformer inductance, which
may also saturate. Switching through a transformer results in less
recovery voltage and a lower possibility of a restrike. The switching
overvoltage will also depend on the instant at which the breaker is
closed on the voltage wave. Closing at the voltage peak will produce the maximum overvoltages.
SWITCHING TRANSIENTS AND TEMPORARY OVERVOLTAGES
165
FIGURE 7-11
Configuration of 70-mi, 765-kV line terminated in a transformer, secondary open circuited, for EMTP simulation of receiving-end
voltage on energization by closing switch S1 at the sending end.
FIGURE 7-12
Receiving-end voltages in phases a, b, and c in system configuration of Fig. 7-11.
7-8 SWITCHING OVERVOLTAGES OF OVERHEAD
LINES AND UNDERGROUND CABLES
When a combination of overhead line and underground cable is
switched together, typically, the maximum surge voltage does not
exceed 3.0 pu of line-to-ground voltage.
This is applicable to a line or cable switched from the substation, a line switched from a line, or a cable switched from a cable.
When the cable is switched through a line or a line is switched
through a cable the maximum switching voltage can escalate to 4.0
pu. For EHV systems, the switching surge voltages must be limited
as stated before. Table 7-5 shows the maximum switching overvoltages normally encountered by switching of lines and underground
cables. The highest overvoltages occur when it is mixed overhead
and underground construction and particularly if the proportion
of one (i.e., line or cable) is small compared to the other. The procedure of tracking and accumulating reflections using ladder diagrams is fairly complex and time consuming. Computer programs
like EMTP and TLTA simplify the calculations.
The cable charging currents depend upon the length of cable,
cable construction, system voltage, and insulation dielectric constants. Appendix D gives the calculations of cable capacitances.
Prior to energizing, a cable is generally at ground potential or it may
have a prior charge. Much akin to switching devices for capacitor
banks, a cable is considered isolated if the maximum rate of change
with respect to time of transient inrush current on energizing an
166
CHAPTER SEVEN
TA B L E 7 - 5
SEVERITY
Typical
Moderate
Extreme
Maximum Switching Overvoltages
on Switching of Lines and
Underground Cables
DESCRIPTION
Line or cable switched
from station
Line switched from line
Cable switched from cable
MAXIMUM VOLTAGE PER
UNIT OF PHASE-TONEUTRAL VOLTAGE
3.0
3.0
3.0
Cable switched from line
Line switched from cable
Cable trough line switched
from station
4.0
4.0
4.0
Line trough cable switched
from the station
6.0
Cable surge impedance, which is much lower than that of
transmission lines. In Chap. 4, we estimated that it is of the
order of 50 Ω.
■
Cable capacitive reactance, system reactance, switching
voltage, and whether any damping devices, such as switching
resistors, are present in the circuit.
■
The cables may be switched back to back, much akin to
capacitor banks.
Transient currents of high magnitude and initial high rate of
change flow between cables when the switching circuit breaker is
closed or on restrikes on opening. For isolated cable switching, we
can use the following expression:
(7-7)
where um is the supply system voltage, ut is the trapped voltage on
the cable being switched, Z is the cable surge impedance, and L is
the source inductance. From Eq. (7-7) the maximum inrush current is:
ip =
u m − ut
Z
(7-8)
Equation (7-8) can be modified for back-to-back switching
i=
Z +Z
u m − ut
2
1 − exp − 1
t
Z1 + Z2
L
(7-9)
where Z1 and Z2 are the surge impedances of cable1 and cable 2,
respectively. Again, akin to back-to-back switching of capacitors,
the source reactance can be ignored.
The peak current is:
ip =
u m − ut
Z1 + Z2
(7-11)
where feq is the inrush frequency, Iir is the charging current of one
cable, L1 and L2 are the inductances of cables 1 and 2, respectively.
The switching of single cable forms a series circuit and the transient will be oscillatory, damped or critically damped. Based upon
Chap. 2:
µ m − µt
z 2 − 4 L /c
[e −α tm − e −β tm ]
for
Z > 4 L /c
where
■
Z
u m − ut
1 − exp − t
Z
L
u −u
m
t
feq = f
ω ( L1 + L2 )I ir
Im =
uncharged cable does not exceed the rate of change associated with
maximum symmetrical interrupting current of the switching device.
When switching a cable, the transient inrush current depends on:
i=
and its frequency is given by:
(7-10)
tm =
ln α /β
α−β
α=
Z
Z2
4
− 2 −
L
LC
L
(7-12)
β=
Z
Z2
4
+ 2 −
L
LC
L
(7-13)
The magnetic fields due to high inrush currents during backto-back switching can induce voltage in control cables by capacitive
and magnetic couplings. This is minimized by shielding the control
cables.
7-9
CABLE MODELS
The cable models for transient analysis depend upon the cable
construction and are discussed in Chap. 4. Consider a single-core
shielded 400-kV XPLE cable for modeling in EMTP; the manufacturer’s data for the cable are:
Conductor cross section = 1000 mm2
Diameter of conductor (copper) = 32.9 mm
Insulation thickness = 29.00 mm
Diameter over the insulation = 98.1 mm
Cross section of the screen = 185 mm2
Outside diameter = 114 mm
Inductance = 0.55 mH/km
Capacitance = 0.16 µF/km
Charging current per phase at 60 Hz = 13.56 A
Surge impedance = 34.5 Ω
Soil resistivity = 100 Ω-m
EMTP model requires the cable characteristics data and the
geometric layout of the cables must be modeled. Resistivity of the
conductor (ohm-meter), relative permeability and permittivity,
loss factor of the surrounding insulation system, and the like are
required to be modeled. For the physical configuration of the cable
shown in Fig. 7-13 and the cable data as above, the results of the
simulation are in Fig. 7-14.
Example 7-2 A 2-km cable length, FD model as derived in
Fig. 7-14 is impacted with a surge of peak voltage of 400 kV, rise
time 1 µs, tail half value at 50 µs, (arbitrary). There is no powerfrequency voltage present at the sending end. The resulting receivingend surge voltage profile with an EMTP simulation is shown in
Fig. 7-15. Note that there are six modes of propagation and the
phase-to-ground voltages are not identical in all the phases. The
receiving-end voltage is 2.25 pu.
Figure 7-16 illustrates the receiving-end voltage when the cable
length is 10 km, all other parameters remaining unchaged. Now,
the receiving-end voltage escalates to 3.75 pu. The voltage escalation
SWITCHING TRANSIENTS AND TEMPORARY OVERVOLTAGES
FIGURE 7-13
Physical layout and parameters of 400-kV cable for EMTP simulation.
FIGURE 7-14
EMTP simulation results of cable configuration in Fig. 7-13.
167
168
CHAPTER SEVEN
FIGURE 7-15
FIGURE 7-16
Receiving-end voltages of a 2-km-long cable, with input surge of 1/50 µs; model as developed in Fig. 7-14.
Receiving-end voltages of a 10-km-long cable, with input surge of 1/50 µs; model as developed in Fig. 7-14.
is the direct function of the cable length, the surge type, and dissipation of the wave energy will be dependent upon response to
transients and the distance the wave travels.11 Attenuation, distortion, and phase shift of the wave occur as demonstrated.
7-10
OVERVOLTAGES DUE TO LOAD REJECTION
Load flow in mainly reactive circuits requires a potential difference between the sending and receiving ends. When a load with
an inductive component at the end of a line is suddenly thrown off,
it results in the increase in power-frequency voltage at the end of
the line. An electromagnetic transient is superimposed upon it and
causes voltage surges in the system. The system can be simply modeled by reducing it to the short-circuit impedance at the point of
load connection. The short-circuit impedance is mostly inductive
and the load has also an inductive component, depending upon
its power factor. Load rejection results in cancellation of the voltage drop in the short-circuit impedance, and the generated voltage
appears on the system side of the breaker contacts. This voltage rise
can be approximately calculated from the expression:
Z
V1
P
= 1 + sc = 1 + L
V2
ZL
Psc
(7-14)
where V1, V2, Zs, and ZL are shown in Fig. 7-17. PL is the load
rejected and Psc is the short-circuit power. The type of load and
its ratio to the short-circuit power are the decisive factors for the
increase in the power-frequency voltage on load rejection. When a
number of lines and transformers are used in parallel and the load
is subdivided, the 100 percent load rejection becomes a remote
possibility.
SWITCHING TRANSIENTS AND TEMPORARY OVERVOLTAGES
169
■
Grading capacitors of high-voltage breakers (provided across
multibreaks per phase in high-voltage (HV) breakers for voltage
distribution) remaining in service when the breaker opens
■
Possibility of ferroresonance with a capacitive voltage transformer (CVT) or an electromagnetic potential transformer (PT)
under certain operating conditions
FIGURE 7-17
A schematic representation of load shed through an
impedance Zs.
Example 7-3
A 400-kV, 110-mi long transmission line is fed
from a step-up transformer of 138 to 400 kV, which is wye-wye
connected with grounded neutrals and tertiary delta windings, with
a rating of 500 MVA. The connected load at the end of the transmission line is 350 MW at a power factor of 0.8 (Fig. 7-18). If the load
is suddenly switched off, at the crest of the voltage in phase a at
10 ms, by opening switch S1, then the simulation of receiving-end
voltage at L2 is shown in Fig. 7-19a. The rise in receiving-end voltage is 1.5 times the voltage prior to load shedding. The voltage after
load shedding shows harmonic content, illustrating resonance with
a natural frequency of the system. The occurrence of resonance
phenomena depends upon whether the line and transformer reactances are tuned to one of higher harmonics of the inrush current.
The sending-end line current at L1 is depicted in Fig. 7-19b.
7-11
FERRORESONANCE
In the presence of system capacitance, certain transformer and reactor combinations can give rise to ferroresonance phenomena, due
to nonlinearity and saturation of the reactance. This is characterized
by peaky current surges of short duration which generate overvoltages. These overvoltages can be predominantly harmonic or subharmonic and reach amplitude of 2 pu. The phenomena may be
initiated by some system changes or disturbances, and the response
may be stable or unstable, which may persist indefinitely or cease
after a few seconds. The ferroresonance is documented in some
cases, which are as follows:
■
Transformer feeders on double circuits becoming energized
through the mutual capacitance between lines and going into
ferroresonance when one transformer feeder is switched out
■
Transformers losing a phase, say due to operation of a current limiting fuse on ungrounded systems
FIGURE 7-18
Figure 7-20a depicts the basic circuit of ferroresonance, a
nonlinear inductor, which may be PT or transformer windings, is
energized through a resistor and capacitor. The phasor diagram is
shown in Fig. 7-20b, as long as the reactor operates below its saturation level. In Fig. 7-20c, points A and C are stable operating points,
while point B is not. Point C is characterized by large magnetizing current and voltage. This overvoltage appears between line and
ground. The changeover from point A to point C is initiated by
some transient in the system, and can be a nuisance due to its random nature.
Figure 7-20d shows two lines with mutual capacitance couplings. The transformer forms a series ferroresonance circuit with
the line mutual capacitance. The ferroresonance can occur at
lower frequency than the fundamental frequency and can overheat the transformers. Switching transients will be superimposed
upon the ferroresonance voltages. The discussions are continued
in Chap.14, and Example 14-10 is an EMTP simulation of the ferroresonance overvoltages.
7-12
COMPENSATION OF TRANSMISSION LINES
The compensation of transmission lines involves steady-state and
dynamic/transient stability considerations. The line is compensated
by lumped series and shunt elements at the mid point, terminals or
in sections. Figure 7-21a illustrates midpoint compensation.12 Each
half-section of the line on either side of the compensating device
is represented by a p equivalent model. The circuit of Fig. 7-21a
can be redrawn as shown in Fig. 7-21b, and the phasor diagram is
in Fig. 7-21c. The degree of compensation for the center held at a
voltage equal to the sending-end or receiving end voltage is:
km =
bshcomp
0 . 5bsh
(7-15)
For equal sending- and receiving-end voltages:
P=
V2
sin δ
X sr (1 − s)
(7-16)
X sr bsh
(1 − km )
2 4
(7-17)
where:
s=
The midpoint voltage is:
Vm =
V cos(δ /2)
1− s
A power system configuration for EMTP simulation of 350-MW load shed.
(7-18)
170
CHAPTER SEVEN
FIGURE 7-19
(a) Receiving-end voltage on load shed; opening of switch S1 in Fig. 7-18. (b) Sending-end current.
SWITCHING TRANSIENTS AND TEMPORARY OVERVOLTAGES
171
FIGURE 7-20
(a) A circuit connection with nonlinear resistor and capacitor that can give rise to ferroresonance. (b) Phasor diagram. (c) Showing stable
operating points A and C, and unstable operating point B. (d ) A possible power system configuration for ferroresonance.
The equivalent circuit of the line with compensation is shown
in Fig. 7-21d. For s = 1, the midpoint compensation increases the
midpoint voltage, which tends to offset the series voltage drop in
the line. If the midpoint voltage is controlled by varying the susceptance of the compensating device, then the following relation for
the power transfer can be written:
P=
VmV
V2
sin δ =
sin δ
X sr (1 − s)
X sr cos(δ / 2)
V V
δ
= 2 m sin
X sr
2
(7-19)
If midpoint voltage is equal to the sending- and receiving-end voltage, that is, all three voltages are of the same magnitude:
V2
δ
sin
P=2
X sr
2
(7-20)
The power-transfer characteristics are sinusoids whose amplitude varies
as s varies, (Fig. 7-21e). Each sinusoid of increasing value means higher
power transfer: for P > 2 Pmax, angle δ > π / 2. As the transmission
angle increases, the compensator responds by changing the susceptance
to satisfy Eq. (7-20). The economic limit of a compensator to provide
effective capacitive susceptance may be much lower than the maximum
power transfer. When the compensator maximum limit is reached, it
acts like a fixed capacitor and cannot maintain a constant voltage.
The shunt compensation to satisfy Eq. (7-18) can be calculated
from the following equation:
bshcomp = −
δ b
4 V
cos + sh
1 −
X sr Vm
2 2
(7-21)
The characteristics of series and shunt compensation can be
summarized as follows:
■
Capacitive shunt compensation increases b, reduces surge
impedance, and increases power transfer. Inductive shunt
compensation has the opposite effect. It decreases b, decreases
power transfer, and increases surge impedance. A 100 percent
capacitive shunt compensation will, theoretically, increase the
surge impedance to infinity.
FIGURE 7-21
(a) A circuit diagram for midpoint compensation of a transmission line. (b). Reduced equivalent circuit. (c) Phasor diagram with series
and shunt compensation. (d ) Simplified equivalent circuit. (e) Power transfer characteristics.
172
SWITCHING TRANSIENTS AND TEMPORARY OVERVOLTAGES
■
Series capacitive compensation decreases surge impedance
and b and increases power-transfer characteristics. Series compensation is applied from steady-state and transient considerations, rather than for power factor improvement. It provides
better load division between parallel circuits, reduces voltage
drop, and provides better adjustments of line loadings. Shunt
compensation directly improves the load power factor. Both
types of compensations improve the voltages and, thus, the
power transfer capability.
7-13
OUT-OF-PHASE CLOSING
Out-of-phase closing places much stress on the system as well
as on the circuit breaker. Out-of-phase closing can occur, due to
human error, that is, two phases can be crossed over in a tie connection having voltage sources at either end. This will result in a
120° phase difference between two phases when closing the circuit
breaker, with voltages on the load and source side. Figure 7-22
shows two interconnected systems which are totally out of phase.
In Fig. 7-22a the two poles of a circuit breaker are shown arcing
and about to open, while the third pole is open. A voltage equal to
three times the system peak voltage appears across the breaker pole,
while in Fig. 7-22b, a ground fault exists on two different phases at
sending end and receiving end (rather an unusual condition). The
maximum voltage across a breaker pole is 2 × 3 times the normal
system peak voltage.
The present day high-speed relaying has reduced the tripping
time and, thus, the divergence of generator rotors on fast closing is reduced. Simultaneously, the high-speed auto-reclosing to
restore service and remove faults increase the possibility of out-ofphase closing, especially under fault conditions. The effect of the
increased recovery voltage when the two systems have drifted apart
can be stated in terms of the short-circuit power that needs to be
interrupted. If the interrupting capacity of a circuit breaker remains
unimpaired up to double the rated voltage, it will perform all events
satisfactorily as a tie-line breaker when the two sections of the system are completely out of synchronism. The short-circuit power to
be interrupted under out-of-step conditions is approximately equal
173
to the total short-circuit power of the entire system, but reaches
this level only if the two systems which are out of phase have the
same capacity.
If a breaker has an out-of phase switching rating, it is only
25 percent of the maximum short-circuit current in kiloamperes.
The ANSI/IEEE standard10 specifies the duty cycles. The conditions
for out-of-phase switching are:
■
Opening and closing operations in conformity with manufacturer’s instructions, and closing angle limited to maximum
out-of-phase angle of 90°
■
Grounding conditions of the system corresponding to those
for which the circuit breaker is tested
■
Frequency within ± 20 percent of the rated frequency of
the breaker
■
Absence of fault on either side of the breaker, that is, the situation depicted in Fig. 7-22b is not applicable
Where frequent out-of-phase closing is expected, the recovery
voltage should be evaluated. A special circuit breaker or the one
rated for higher voltage may be required. The severity of outof-phase closing can be reduced by using protective devices with
coordinated impedance-sensitive elements to control the tripping
instant, so that the interruption will occur substantially after or
substantially before the instant when the phase angle is 180°.
Polarity sensing and synchronous breakers can be employed.
7-14
OVERVOLTAGE CONTROL
The overvoltages in the system can be controlled by:
■
Resistance switching
■
Synchronous closing
■
Line compensation
■
Application of surge arresters
■
Application of surge capacitors
■
Protective relaying
We have discussed line compensation; the power frequency
component of the overvoltage is controlled by connecting highvoltage reactors from line to ground at the sending and receiving
ends of the transmission lines. In other words, the electrical length
of the line is reduced. The effect of the trapped charge on the line
can be eliminated if the closing takes place during that half cycle
of the power-frequency voltage, which has the same polarity as the
trapped charge. The high-voltage circuit breakers may be fitted
with devices for polarity-dependent closing. Controlling overvoltages with switching resistors is yet another method.
Lines with trapped charge and no compensation and no switching resistors in breakers may have overvoltages greater than three
times the rated voltage. Without a trapped charge, this overvoltage
will be reduced to 2.0 to 2.8 times the rated voltage. With single stage closing resistors and compensated line, overvoltages are
reduced to less than 2 times the rated voltage. With two-stage closing resistors or compensated lines with optimized closing resistors,
the overvoltage factor is further reduced to 1.5.
FIGURE 7-22
(a) Overvoltages due to two systems completely out of
phase, unfaulted condition; the maximum voltage is equal to three times the
peak system voltage. (b) Ground fault on different phases on source and load
sides; the maximum voltage is equal to 2 × 3 times the peak system voltage.
7-14-1
Synchronous Operation
A breaker for synchronous operation opens and closes with fixed
reference to the phase position of the system voltage or current
oscillations. An electronic device records the system voltage, and
174
CHAPTER SEVEN
the zero crossings of the voltage forms the reference point. Based
upon the operating time of the circuit breaker, the tripping pulse is
controlled so that the contacts touch or the contact separation takes
place at the desired voltage phase position, depending upon the
desired operation. In synchronous closing, the breaker is controlled
so that the contacts touch at voltage zero or are at maximum system
voltage. The contacts should close at voltage zero when energizing
capacitor banks. In synchronous opening, the breaker is controlled
so that current zero occurs at a definite contact gap. The maximums
and zeros in different phases occur at different times.
The breaker is, therefore, either operated or controlled with
individual mechanism for each pole, or its individual poles are
coupled with each other such that contacts touch and separation
occurs at different times. Independent pole operation is a standard
feature for circuit breakers of 550 kV, but can be made applicable
to circuit breakers of 138 KV. Figure 7-23 shows two effects on the
resulting receiving-end overvoltage: (1) the angle of closure from
source end voltage zero and (2) the effect of source impedance. The
overvoltage will be minimum for zero-closing angle and infinite
source impedance. Therefore, the problem of overvoltage control
in long lines with relatively low short-circuits power. This figure
also depicts that even a small deviation from the ideal closing angle
can make much difference in the resulting overvoltage factor. In a
practical implementation, the closing time of the breaker must be
considered and there can be variations in each pole.
Operations for which synchronous switching can be effective are:
■
Switching of capacitor banks
■
Unloaded transformers
■
Shunt reactors, that is, compensated transmission lines
■
Switching to mitigate effects of residual charge on transmission
lines.
Each of these operations has a different strategy as the switching
transients vary. When closing is undertaken to be at the same polarity as the source and line side, to counteract the effect of trapped
charge, the impact of the closing angle is not so critical. The success is dependent upon how the circuit breaker characteristics are
matched with that of the operation under consideration. The circuit
FIGURE 7-23
breaker parameters are the mechanical and electrical properties,
temperature, contact velocity, buildup of dielectric strength in the
contact gap, and wear and aging—which may be somewhat unpredictable. Note that neither the velocity of contact separation nor the
closing and opening times are constant, nor can they vary evenly
with the variations in the control voltage of the breaker.
Capacitance Switching An energization transient can be completely eliminated if there is no voltage across the breaker poles on
the load and source side, which may not be practical. It seems that
energization overvoltages can be well controlled if the closing occurs
within 1 ms before and after current zero.13,14,15 When capacitors are
ungrounded, the first pole can be closed at random, as there is no
current flow with only one pole closed. The second and third poles
can then be closed at their respective current zeros. Alternatively,
two poles can be closed simultaneously at current zeros
De-energizing a capacitor gap requires short arcing times
(Chap. 8), and the arc can be established when there is not enough
contact separation giving rise to restrikes. The contacts can be made
to separate sufficiently ahead of a current zero, say about one-fourth
of a cycle. With modern high-voltage circuit breakers of high speed,
the contacts separate fast and there does not seem to be a need for
synchronous de-energization.
Reactor Switching
The operation may be considered reverse
of capacitor switching. Generally on energization, the breakers may
experience a prestrike (Chap. 8); however, this voltage is limited in
magnitude and energization is not a concern, except during energization of a shunt-compensated line. In such cases, the frequency
across the breaker contacts has a beat frequency, and it will be desirable to sense the polarity of the trapped charge and close when the
voltage across the contacts is minimum. The synchronous operation on opening can reduce the overvoltages that may be generated
due to current chopping, or reignitions that may occur on opening
operation. The contacts are separated at a time which is larger than
the minimum arcing time required for operation of that particular
breaker, so that the contact gap is able to withstand the recovery
voltage. This may not be so easy to predetermine and incorporate
in the switching logic.
Example 7-4
Continuing with Example 7-1 with synchronous
closing of the poles, all other parameters remaining unchanged,
the switches in three phases are closed as shown in Fig. 7-7c.
Effect of angle of closure and source impedance on the receiving-end voltage of a 400-kV line, 400 km long. Curve a for infinite source,
curve b for 0.1-H source at 400 kV.
SWITCHING TRANSIENTS AND TEMPORARY OVERVOLTAGES
FIGURE 7-24
Receiving-end voltage of phase a synchronous closing, system configuration as in Fig. 7-7c.
The resulting receiving-end voltage, phase a, is illustrated in
Fig. 7-24. Comparing with Fig. 7-8b, it is seen that:
■
The amplitude is reduced from 2.48 to 1.24 pu.
■
The high-frequency transients are reduced.
7-14-2
Resistance Switching
Resistance switching is discussed in Chap. 6 in connection with
shunt capacitor bank switching. Circuit breaker resistors can be
designed and arranged for resistance switching to meet the following objectives:
■
175
To reduce switching surges and overvoltages
■
For potential control across multibreaks per phase in the
high-voltage breakers,
■
To reduce natural frequency effects and breaker recovery
voltage (see Chap. 8).
Opening resistors are also called switching resistors and are in
parallel with the main break and in series with an auxiliary resistance break switch. On an opening operation, the resistor switch
remains closed and opens with a certain delay after the main contacts have opened. The resistance switch may be formed by the
moving parts in the interrupter or striking of an arc, dependent
upon the circuit breaker design.
Figure 7-25 shows the sequence of opening and closing in a
circuit breaker provided with both opening and closing resistors.
The closing resistors control the switching overvoltage on energization of, say, long lines. An interrupting and closing operation is
shown. The main break is SB, the opening resistor is RB, the closing
resistor is RC, the auxiliary breaker contact is SC, and the resistor
closing contact is SR. On an opening operation, as the main contact
start arcing, the current is diverted through the resistor RB, which
is interrupted by contacts SC. In Fig. 7-25d the breaker is in open
position. Figures 7-25e and f show the closing operation. Finally,
the closed breaker is shown in Fig. 7-25a. The flow of main current
and diverted current and the circuit not carrying any current are
clearly depicted in this figure with different line weights.
Synchronous switching versus resistor switching is always a
point of discussion. While both technologies try to achieve the
overvoltage control, in synchronous switching the variations of
contact scatter and opening and closing times may considerably
alter the performance. In resistor switching the resistors are prefixed and for the tested conditions a uniform performance can be
expected. In synchronous switching it is possible to program and
adjust the contact operation.
Example 7-5 Example 7-1 is repeated with resistance switching
to examine the effect on the sending- and receiving-end voltages.
An auxiliary switch and a resistor equal to the surge impedance of
the line is used (Figure 7-7d). The auxiliary switch contacts close
in resistors at first voltage zero. Then the main contacts close in
one-quarter cycles after preinsertion resistors. The receiving-end
voltages are shown in Fig. 7-26.
Comparing Figs. 7-24 and 7-26, synchronous switching and
resistance switching, respectively, the results are almost identical.
7-15
STATISTICAL STUDIES
The surge phenomena are statistical in nature. Statistical analysis
is random data case, which is solved in the time domain. Many
time-domain studies can be carried out on EMTP, as a parameter of
interest varies, and a maximum and minimum values are obtained
within certain assigned variations.
A random function can be used to generate the data. Number
of simulations, maximum multiples of standard deviations, type of
random algorithm, for example, gaussian distribution, with mean
and standard deviations can be specified.
Example 7-6 Figure 7-12 is a simulation of the receiving-end
voltage in the system configuration depicted in Fig. 7-11. Let the
switch S1, all three poles, be modeled with Gaussian distribution,
mean deviation s = 4 ms and m (mean) = 28 ms. The statistical
simulation plots are shown in the following figures:
176
CHAPTER SEVEN
FIGURE 7-25
Schematic diagram of a high-voltage circuit breaker fitted with opening and closing resistors: (a) breaker closed, (b) and (c) breaker
opening, (d ) breaker open, (e) and (f ) breaker closing.
Figure 7-27. The maximum and minimum receiving-end voltages on phase a, for 100 simulations.
Figure 7-28. The maximum and minimum currents through the
closing switch S1, phase a.
Figure 7-29. A bar graph of the maximum and minimum
receiving-end voltages, phase a.
Figure 7-30. Cumulative distribution plot, maximum receivingend voltage, phase a. The calculated mean and standard deviation are shown on the top of the graph.
Figure 7-31. Histogram of receiving-end phase a voltage.
The statistical studies are powerful analytical tools and when
properly applied can give valuable information of the system
FIGURE 7-26
FIGURE 7-27
FIGURE 7-28
Receiving-end voltage, phase a resistance closing, system configuration as in Fig. 7-7d.
Statistical studies of system configuration in Fig. 7-11. Maximum and minimum receiving-end voltages for phase a; 100 simulations.
Statistical studies of system configuration in Fig. 7-11. Maximum and minimum current through switch S1, for phase a ; 100 simulations.
177
178
CHAPTER SEVEN
FIGURE 7-29
Statistical studies of system configuration in Fig. 7-11. Bar graph of maximum and minimum receiving-end voltages for phase a ;
100 simulations.
FIGURE 7-30
Statistical studies of system configuration in Fig. 7-11. Cumulative distribution function receiving-end voltages for phase a ;
100 simulations.
behavior without hundreds of simulations in the time domain. The
statistical data could be applied to each pole of the switch, and
the closing and opening operation can be made dependent upon
the operation of some other devices in the system, that is, a fault
simulation switch.
Generally the lines are modeled as perfectly transposed lines.
Asymmetry will introduce errors, which will vary. The pole span,
that is, the time difference between the first pole and the last pole to
close can be of the order of 5 ms, and that will introduce additional
errors in the modeled results with simultaneous closing of poles.
SWITCHING TRANSIENTS AND TEMPORARY OVERVOLTAGES
FIGURE 7-31
179
Statistical studies of system configuration in Fig. 7-11. Histogram of receiving-end voltages of phase a ; 100 simulations.
The trapped charge oscillation is quite different on a balanced and
on an untransposed line. A comparison of the statistical distributions of the overvoltages is one possibility to take into account the
effect of asymmetry. EMTP allows modeling of unsymmetrical lines.
In this chapter, various modes and switching operations that
result in overvoltages on the transmission lines and cables, and how
these overvoltages can be controlled, are studied. The importance
of switching surge overvoltages as the system voltage increases with
respect to line insulation stresses is examined. At and above 500 kV,
the switching transients gain importance over the lightning surges.
We also discussed out-of-phase closing, pole scatter and control
of switching transients through closing resistors, and synchronous
closing and line compensation. The transients on symmetrical and
unsymmetrical faults are carried over to Chap. 9.
PROBLEMS
1. A 200-mi-long transmission line is connected to a 400-kV
system having a three-phase short-circuit current of 30 kA rms
symmetrical, X/R = 23. The parameters of the transmission line
are resistance =0.06321 Ω/mi, inductance = 0.90325 Ω/mi, and
shunt capacitance reactance = 0.2 M Ω/mile. Calculate the optimum value of the resistor to control the receiving-end voltage.
FIGURE 7-P1
What is the sending-end voltage without the switching resistance? The line is open at the receiving end.
2. Calculate the inrush current of a 400-kV cable, 10 mil long;
the cable parameters are: resistance = 0.08 Ω/mi, reactance =
1.2 Ω/mi, Z = 28 Ω. The cable is connected to a source of
L =.0.015mH, and R = 0.022 Ω.
3. The cable in Prob. 2 is paralleled with another cable of the same
specifications. The inductance between cables is 0.002 mH.
What is the peak back-to-back switching current? What is the
frequency of this current?
4. Compare methods of switching overvoltage control described in
this chapter with respect to their applicability and limitations.
5. Consider a 400-mi-long transmission line, with b = 0.116°/mi.
What is the maximum power that can be transmitted on this line
as function of the natural line load? The line is compensated with
60 percent series compensation. How does the maximum power
transfer change? What is the new electrical length of the line?
6. Consider a system as shown in Fig. 7-P1. Calculate the maximum
and minimum current through the breaker S1 on closing.
Power system configuration for Prob 6.
180
CHAPTER SEVEN
7. The maximum switching overvoltage for 765 kV should be limited to 2, 2.15, 2.5, or 3 times the system voltage. What is the
correct answer? What is the maximum permissible switching
overvoltage for 400-kV systems?
8. A single conductor shielded solid dielectric cable has a conductor diameter of 25 mm, insulation thickness 10 mm, dielectric
constant of insulation (permittivity) = 4.2. Calculate its surge
impedance, electric length, and velocity of propagation.
9. J. Aubin, D. T. McGillis, and J. Parent, “Composite Insulation
Strength of 735 kV Hydro-Quebec 735 kV Towers,” IEEE Trans.
PAS, vol. 85, pp. 633–648, 1966.
10. ANSI Standard C37.06, AC High Voltage Circuit Breakers Rated
on Symmetrical Current Basis—Preferred Ratings and Related
Capabilities, 2000.
11. E. W. Greenfield, “Transient Behavior of Short and Long Cables,”
IEEE Trans. PAS, vol. 103, no. 11, pp. 3193–3203, Nov. 1984.
9. The maximum overvoltage will be obtained when:
A cable is connected to a short transmission line
A transmission line is connected to a short cable length.
Explain why it will be higher in one of the above two cases?
12. T. J. E. Miller, (ed.) Reactive Power Control in Electrical Power
Systems, John Wiley, New York, 1982. (Out of print, used copies can be purchased on Web site www.amazon.com)
10. Explain how the overvoltages on reswitching of lines and
cables, open circuited at the receiving end, which have trapped
charges due to first switching operation can be avoided.
13. B. J. Ware, J. G. Reckleff, G. Mauthe, and G. Schett,
“Synchronous Switching of Power Systems,” CIGRE Session,
Report No. 13-205,1990.
11. Compare resistance switching and point of wave switching.
Which is better and why? Show how two sets of resistors for
HV circuit breakers, one for closing and the other for interrupting,
are used.
14. G. Moraw, W. Richter, H. Hutegger, and J. Wogerbauer, “Point
of Wave Switching, Controlled Switching of High-Voltage Circuit
Breakers,” CIGRE 13-02, 1988 session.
12. Explain why the switching overvoltage transients on an OH
line are higher at the receiving end as compared to the sending
end. Can these be higher at the sending end in any operation?
13. Write a one-page note without mathematical equations on BIL
versus BSL as the system voltage increases.
14. List all the possible areas of transient simulations where statistical analyses can be recommended.
REFERENCES
1. N. Fujimoto, Transmission Line Transient Analysis Program,
TLTA, Ontario Hydro Research Division, March 1985.
2. ANSI Standard C84.1, Voltage Ratings of Electrical Power
Systems and Equipment (60 Hz.), 1989.
3. IEC 60071-2, Insulation Coordination, Part 2-Application Guide,
1996.
4. BBC Research Center—Surges in High-Voltage Networks, BBC
Symp. on Surges in High-Voltage Networks, Beden, Switzerland
1979.
5. ANSI/IEEE Standard C57.12, IEEE Standard for Standard General Requirements for Liquid Immersed Distribution, Power,
and Regulating Transformers, 2006.
6. H. Glavitsch, “Problems Associated with Switching Surges
in EHV Networks,” BBC Review, vol. 53, pp. 267–277,
April/May 1966.
7. A. Pigini, L. Thione, K. H. Week, C. Menemenlis, G. N. Alexandrov
and Y. A. Gersimov, CIGRE Working Group 33.03, “Part IISwitching Impulse Strength of Phase-to-Phase External Insulations,” ELECTRA, pp. 138–157, May 1979.
8. E. W. Boehne and G. Carrara, “Switching Surge Insulation
Strength of EHV Line and Station Insulation Structures,”
CIGRE Report 415, 1964.
15. R. W. Alexander, “Synchronous Closing Control for Shunt
Capacitors,” IEEE Trans. PAS, vol. 104, no. 9, pp. 2619–2625,
Sept. 1985.
FURTHER READING
G. W. Alexander and H. R. Armstrong, “Electrical Design of a 345 kV
Double Circuit Transmission Line Including Influence of Contamination,” IEEE Trans. PAS, vol. 85, pp. 656–665, 1966.
CIGRE Working Group 13-02, Switching Surge Phenomena in
EHV Systems, “Switching Overvoltages in Transmission Lines with
Special Reference to Closing and Reclosing Transmission Lines,”
Electra, vol. 30, pp. 70–122, 1973.
CIGRE Working Group 33-02, Internal Overvoltages, Document
33-78, 1978.
J. K. Dillard, J. M. Clayton, and L. A. Kilar, “Controlling Switching Surges on 1100-kV Transmission Systems,” IEEE Trans. PAS,
vol. 89, No. 8, pp. 1752–1759, 1970.
J. K. Dillard and A. R. Hileman, “Switching Surge Performance of
Transmission Systems,” Proc. CIGRE, Report 33-07, 1970.
E. W. Kimbark and A. C. Legate, “Fault Surge Verses Switching
Surge: A Study of Transient Overvoltages Caused by Line-toGround Faults,” IEEE Trans. PAS, PAS-87, pp. 1762–1769, 1968.
V. Koschik, S. R. Lambert, R. G. Rocamora, C. E. Wood, and G. Worner,
“Long Line Single Phase Switching Transients and their Effect on
Station Equipment,” IEEE Trans. PAS, vol. 97, pp. 857–964, 1978.
J. F Perkins, “Evaluation of Switching Surge Overvoltage on
Medium-Voltage Power Systems,” IEEE Trans. PAS, vol. 101, no. 6,
pp. 1727–1734, 1982.
L. Thione, “Evaluation of Switching Impulse Strength of External
Insulation,” Electra, pp. 77–95, May 1984.
Transmission Line Reference Book, 345 kV and Above, 2d ed., EPRI
Palo, Alto, CA, 1982.
J. A. Williams, “Overhead Versus Underground Analysis,” Proc.
Trans. Distri. World Expo, Atlanta, Nov. 1997.
CHAPTER 8
CURRENT INTERRUPTION
IN AC CIRCUITS
Current interruption in high-voltage ac networks has been intensively researched. Fundamental electrical phenomena occurring in
the electrical network and the physical aspects of arc interruption
process need to be considered simultaneously. Current interruption
characteristics have a different effect under different conditions,
and care must be exercised in applying generalizations.
The basic phenomena of interruption of transient currents are
derived from the electrical system configurations and the modifying
effect of the current interruption devices, that is, circuit breakers
and fuses. Current limiting fuses are discussed in Chap. 20.
The two basic principles of ac interruption are: (1) high-resistance
interruption or an ideal rheostatic circuit breaker; dc circuit breakers also employ high-resistance arc interruption, as discussed in
Chap. 23; (2) low-resistance or zero-point arc extinction, which is
discussed in this chapter.
8-1
ARC INTERRUPTION
The ionization of gaseous mediums and the contact space of circuit
breakers depends on:
■
Thermal ionization.
■
Ionization by collision.
■
Thermal emission from contact surfaces.
■
Secondary emission from contact surface.
■
Photoemission and field emission.
■ The arc models in circuit breakers are further influenced
by the contact geometry, turbulence, gas pressure, and arc
extinguishing devices.1
Deionization can take place by recombination, diffusion, and
conduction heat. The arc behaves like a nonlinear resistor with arc
voltage in phase with the arc current. At low temperature, the arc
has falling volt-ampere characteristics. At higher currents, voltage
gradient levels out, practically becoming independent of current.
Figure 8-1 shows radial temperature distribution between low- and
high-current arcs. At high currents, arc temperature of the order of
20000 K occurs and tends to be limited by radiant heat transfer.
The heat transfer and electrical conductivity have nearly constant
values within the arc column.
It is rather perplexing that when the arc is cooled, the temperature increases. This happens due to the reduction in the diameter
of the core, which results in higher current density (of the order of
several thousand amperes /cm2).
High- and low-pressure arcs can be distinguished. High-pressure
arcs exist at pressures above atmosphere and appear as a bright
column, characterized by a small burning core at high temperatures of the order of 20000 K. In low-pressure (vacuum arcs),
the arc voltages are low of the order of 40 V, and the positive
column of the arc is solely influenced by the electrode material,
while that of high-pressure arcs is made up of ionized gases from
arc’s surrounding medium.
The central core is surrounded by a column of hot gases. A first
attempt to relate the volt-ampere characteristic of a steady arc is
given by the following expression, still in use:
Varc = A + Bd +
C + Dd
I arc
(8-1)
where Iarc is the arc current; Varc is the voltage across the arc; d is
the length of the arc; and A, B, C, and D are constants. For small
arc lengths, the voltage across arc length can be neglected, and we
can write:
Varc = A +
D
I arc
(8-2)
Voltage across the arc reduces as the current increases. Energy
dissipated in the arc is:
Earc = Varc I arct
(8-3)
where t is the duration of arc in seconds. For a high-voltage current
zero circuit breaker with an interrupting time of 2 cycles, the arcing
time is 1 cycle. The approximate variation of arc resistance, r with
time t, is obtained for different parameters of the arc by experimentation and theoretical analysis.
181
182
CHAPTER EIGHT
The decay of temperature of arc is assumed due to thermal conduction, and the electrical conductivity of arc is dependent on
temperature:
1 dG 1 EI
=
− 1
G dt θ N 0
(8-6)
where:
θ=
Q0
N0
(8-7)
The validity of the theory during current zero periods is
acknowledged.
8-2-4 Cassie Mayr Theory
FIGURE 8-1
Arc temperature versus arc radius, low and high
1. Cassie’s period prior to current zero:
currents.
8-2
d 1 2 1 2 1
+ =
dt R 2 θ R 2 θ E0
ARC INTERRUPTION THEORIES
8-2-1 Slepian Theory
It was proposed in 1928, and states that arc extension process is
a race between the dielectric strength and restriking voltage. After
current zero, there is a hot residual column of ionized gases. If the
dielectric strength builds up quickly, so that it is always greater
than the restriking voltage, the arc does not restrike. If the dielectric strength is less, the arc restrikes. The theory assumes that the
restriking voltage and the buildup of dielectric strength are comparable quantities, which is not correct. Secondly, the theory does not
consider energy functions in the arc extinction process.
8-2-2
Cassie’s Theory
A differential equation describing the behavior of arc was presented
by A. M. Cassie in 1939.2 It assumes a constant temperature across
the arc diameter. As the current varies, so does the arc cross section, but not the temperature inside the arc column. Under given
assumptions, the conductance G of the model is proportional to
current, so that the steady-state voltage gradient E0 is fixed. The
time constant:
θ=
Q
N
(8-4)
where Q is energy storage capability and N is the finite rate of
energy loss which defines the time lag due to energy storage and
finite rate of energy loss. The following is the simplified Cassie’s
equation given in terms of instantaneous current:
d 2 2 I
(G ) =
θ E0
dt
2
(8-5)
For high-current region, there is a good agreement with the
model, but for current-zero region, agreement is good only for high
rates of current decay.
8-2-3
Mayr assumed arc temperature of 6000 K, but it is recognized to be
in excess of 20000 K. At these high temperatures, there is a linear
increase in gas conductivity. Assuming that before current zero, the
current is defined by driving circuit, and that after current zero,
the voltage across the gap is determined by arc circuit, we write the
following two equations:
Mayr’s Theory
O. Mayr considered an arc column where arc diameter is constant
and where arc temperature varies with time and radial dimensions.
2
(8-8)
2. Mayr’s period around current zero:
dR R
e2
− =−
dt θ
θN0
(8-9)
This has been extensively used in circuit breaker designs, however, constant q must be deduced from experimental results.
8-3
CURRENT-ZERO BREAKER
A circuit breaker does not operate instantaneously on a tripping or
closing signal, nor do the contacts part and close simultaneously.
There is a finite time before the switch/circuit breaker can interrupt
a transient current. In a current-zero circuit breaker, the interruption takes place during the passage of current through zero, though
there is some chopping of current because of instability of arc close
to current zero. Before interruption occurs, the arc may persist for
a number of cycles, depending on the design of the circuit breaker.
At some initial current zeros, the arc reignites because the contact
gap has not developed enough dielectric strength. We say that the
restriking voltage is higher than the electrical strength of the gap.
The dielectric strength of the arc gap is primarily a function of the
interrupting devices, while voltage appearing across parting contacts is a function of system constants.
An arc can keep burning and will not extinguish itself even at
some low amperes. The circuit breakers are called upon to interrupt
currents of the order of tens of kilo-amperes or even more. Generator circuit breakers having an interrupting capability of 250 kA
rms symmetrical are available. At the first current zero, the electrical conductivity of the arc is fairly high, and since the currentzero period is very short, the reignition cannot be prevented. The
time lag between current and temperature is commonly called arc
hysteresis.
When the current passes through zero, the arc voltage jumps
to a value equal to the instantaneous peak value of extinguishing
voltage from previous current loop, plus peak value of reignition
value of next loop, associated with the reversal of current. The most
favorable condition for interruption is that in which the applied
CURRENT INTERRUPTION IN AC CIRCUITS
voltage reaches zero when current is zero, that is, interrupting a
resistive current.
As the contact separation increases, the transient voltage of
the arc does not succeed in igniting the arc because the electrical
strength of the break gap increases. The gap can now withstand the
recovery voltage stress. All high-voltage breakers, whatever may be
the arc-quenching medium (oil, air, or gas), use current-zero interruption. In an ideal circuit breaker, with no voltage drop before
interruption, arc energy is zero. Modern circuit breakers approach
this ideal on account of short arc duration and low arc voltage.
The various arc-quenching mediums in circuit breakers for arc
interruption have different densities, thermal conductivities, dielectric strengths, arc time constants, and so on. We will briefly discuss
the arc interruption in SF6 in sec. 8-13.
Figure 8-2b shows a typical short-circuit current waveform
in an inductive circuit of Fig. 8-2a, short circuit applied at t = 0.
Short-circuit current is limited by the impedance R + j ω L and is
interrupted by breaker B. The waveform shows asymmetry, as
183
discussed in Chap. 2. At t2, the contacts start parting. The time
t2 – t0 is termed contact parting time (IEC minimum trip delay), and
consists of tripping delay, interval t1 – t0, and opening time interval
t2– t1. It takes some finite time for the breaker operating mechanism
to set in motion and the protective relaying to signal a fault condition. In ANSI/IEEE and IEC standards for breakers,3–5 this tripping
delay is considered equal to 1/ 2 cycle.
As the contacts start parting, an arc is drawn, which is intensely
cooled by the quenching medium (air, SF6, or oil). The arc current
varies for short duration and may have some oscillations. This voltage drop across the arc during arcing period is shown exaggeratedly
in Fig. 8-2d for clarity. The arc is mostly resistive and the voltage in
the arc is in-phase with the current. The contacts part at high speed
to prevent continuation of the arc. The peculiar shape of arc voltage, shown in Fig. 8-2d, is the result of volt-ampere characteristic
of the arc, and at a particular current zero, the dielectric strength
of the arc space is sufficiently high. When the dielectric strength
builds and a current zero occurs, the arc is interrupted. In Fig. 8-2c,
it occurs at t3, and the interval t3 – t2 is the arcing time. The interval t2 – t is the total interrupting time. With modern high-voltage
breakers, it is as low as 2 cycles or even lower, based on the system
power frequency.
It can be seen that the interruption process is much dependent
on the current being interrupted, resistive, inductive, or capacitive. The breakers and switching devices are tested at a low power
factor because the system inductance predominates and the shortcircuit currents which impose the maximum switching duties on
the circuit breakers are mostly reactive. ANSI standard defines the
rated interrupting time of a circuit breaker as the time between
trip circuit energization and power arc interruption on an opening
operation, and it is used to classify breakers of different speeds. The
rated interrupting time may be exceeded at low values of current
and for close-open operations; also, the time for interruption of
resistor current for interrupters equipped with resistors may exceed
the rated interrupting time. The increase in interrupting time on
close-open operation may be important from the standpoint of line
damage and possible instability.
The significance of interrupting time on breaker interrupting
duty can be seen from Fig. 8-2b. As the short-circuit current consists of decaying ac and dc components, the faster the breaker, the
greater the asymmetry and the interrupted current.
Interrupting current at final arc extinction is asymmetrical in
nature, consisting of an ac component and a dc component. The
rms value of the asymmetrical current is given by:
2
2
I rms,asym,total = I acrms
+ I dc
(8-10)
Table 18-1 shows the breaker interrupting times, contact parting time, and the asymmetrical current duties for breakers rated
according to ANSI/IEEE standards.
8-4
FIGURE 8-2
(a) Short circuit of an inductive circuit. (b) Asymmetrical short-circuit current profile. (c) Short-circuit current interruption. (d ) Arc
voltage profile.
TRANSIENT RECOVERY VOLTAGE
The essential problem of current interruption involves rapidly
establishing an adequate electric strength across the break after
current zero, so that restrikes are eliminated. Whatever may be the
breaker design, it can be said that it is achieved in most interrupting
mediums, that is, oil, air-blast, or SF6 by an intense blast of gas. The
flow velocities are always governed by aerodynamic laws. However,
there are other factors that determine the rate of recovery of the
dielectric medium: nature of quenching gases, mode of interaction of pressure and velocity of the arc, arc control devices, contact
shape, number of breaks, and the circuit in which the breaker is
connected.
At the final arc interruption, a high-frequency oscillation, superimposed upon the power-frequency voltage, appears across the
breaker contacts. A short-circuit current loop is mainly inductive,
184
CHAPTER EIGHT
TA B L E 8 - 1
Interrelation of Circuit Breaker Interrupting Time, Contact Parting Time, and
Asymmetrical Ratings (ANSI/IEEE, Circuit Breakers Rated on Symmetrical Current Basis)
TRIPPING DELAY
(CYCLES, 60-HZ BASIS)
BREAKER CONTACT
PARTING TIME (CYCLES,
60-Hz BASIS)
BREAKER OPENING
TIME (CYCLES,
60-HZ BASIS)
BREAKER ARCING
TIME (CYCLES,
60-Hz BASIS)
REQUIRED DC
COMPONENT (%)
CALCULATED AT
CONTACT PORTING TIME
2
0.5
1.5
1
1
58
3
0.5
2
1.5
1.5
49
5
0.5
3
2.5
2.5
32
BREAKER INTERRUPTING
TIME CYCLES
Primary contact parting time is considered equal to the sum of 1/2 cycle (tripping delay) and the lesser of :
•
Actual opening time of the circuit breaker, or
•
1.0, 1.5, 2.5 for breakers having an interrupting time of 2, 3, and 5 cycles, respectively.
and the power-frequency voltage has its peak at the current zero;
however, a sudden voltage rise across the contacts is prevented by
inherent capacitance of the system, and in simplest cases, a transient
of the order of some hundred to 10000 c /s can occur. It is termed
the natural frequency of the circuit. Figure 8-3 shows the recoveryvoltage profile after final current extinction. The two components of
the recovery voltage, (1) a high-frequency damped oscillation and
(2) the power-frequency recovery voltage, are shown. The highfrequency component is called the transient recovery voltage (TRV)
and sometimes the restriking voltage. Its frequency is given by:
fn =
1
(8-11)
2π LC
where fn is the natural frequency, and L and C are equivalent inductance and capacitance of the circuit, respectively.
If the contact space breaks down within a period of 1/4 cycle of initial arc extinction, the phenomena are called reignitions, and if the breakdown occurs after 1/4 of a cycle, the phenomena are called restrikes.
The transient oscillatory component subsides in a few microseconds and the power- frequency component continues. As an example,
an inductor of 2 mH, with small effective capacitance of 100 pF, has
its natural frequency of 356 kHz, a period of approximately 2.8 µs; see
FIGURE 8-3
Eq. (8-11). On a 138-kV system, neglecting damping, the voltage will
swing to twice the system voltage in half period, and the mean rate of
rise of the recovery voltage is 160 kV per µs, which is very high and
will cause restrikes in a circuit breaker. Capacitors and resistors are
used in high-voltage circuit breakers to damp out the recovery voltage.
The breakers are rated to withstand a certain recovery-voltage profile.
The calculation of the initial rate of rise is important and is not so
simple because of traveling-wave phenomena and multiple reflections
as a surge is impressed upon the two systems being disconnected
by the breaker. The recovery-voltage profiles can be considered for
fault currents, maximum and minimum, and the transformer-limited
fault currents. Also nonfault currents can be resistive, inductive, and
capacitive, and the circuit configurations play an important role, for
example, terminal faults and short-line faults. The recovery-voltage
profile varies in all these cases; the TRV profiles can be:
■
Mostly supply frequency with little buzz when large capacitance currents are interrupted
■
Overdamped
■
Oscillatory; occur when switching a shunt reactor,
unloaded transformer, or clearing a fault limited by transformer or series reactor
TRV and power-frequency recovery voltage components after current interruption.
CURRENT INTERRUPTION IN AC CIRCUITS
■
Triangular; occur in short-line faults
■
Entirely different problems and waveforms, with escalation of
voltage; occur if restrikes take place during the process
Consider that the two symmetrical three-phase networks are
interconnected through a circuit breaker. Let the positive-, negative-,
and zero-sequence impedances of left-hand and right-hand side
networks be W′, W″, W0 and Z′, Z″, Z0, respectively. Let UW1,
UW2, UW3 and UZ1, UZ2, UZ3 be the momentary values of the
phase voltages across the open poles of the breaker and similarly
iW1, iZ1, … be the phase currents. Then:
2l
t = k
v
(8-12)
k
where l is the first point of reflection and superscript k denotes
positive-, negative-, and zero-sequence modes. The shortest of
these times then determines the RRRV (rate of rise of recovery
voltage). Using symmetrical component transformations, for each
system W′, W′′, W 0, and Z′, Z′′, and Z0:
α Z,W
i1
1
γ
i2 =
3 Z,W
i3
β Z,W
β Z,W
α Z,W
γ Z,W
γ Z,W
β Z,W
α Z,W
(8-13)
1 1
1
+ +
Z′ Z′′ Z 0
βZ =
a a2 1
+ +
Z′ Z′′ Z 0
γZ =
1
a2 a
+ +
Z′ Z′′ Z 0
1.5
2 X 0 /X1
1 +[2 X 0 /X1]
(8-15)
without ground contact, the following expression can be written:
2( X + Y )X
0
0
1
1 . 5
1 +[2( X 0 + Y0 )/X1]
(8-16)
where X1 and X0 are the positive- and zero-sequence reactances of
the source side. Also, in Fig. 8-4, Y1 and Y0 are the sequence admittances of the load side. Currently, first pole to clear factor is 1.3 for
circuit breaker for solidly grounded systems above 100 kV. It varies
with type of fault. Say for a 550 kV breaker, it is 1.3 for terminal
fault, 1.0 for short-line fault, and 2.0 for out-of-phase fault.6
Figure 8-5 illustrates the slopes of tangents to three TRV waveforms of different frequencies. As the natural frequency rises, the
RRRV increases. Therefore, it can be concluded that:
2. There is a swing beyond recovery voltage value, the amplitude of which is determined by the circuit breaker and damping.
(8-14)
3. The higher the natural frequency of the circuit being
interrupted, the lower the breaker interrupting rating.
4. Interrupting capacity/frequency characteristics of the
breaker should not fall below that of the system.
The expressions for initial recovery voltage are provided in
Table 18-2.
8-4-1
exceeding 3 and can be calculated using symmetrical components.
The first pole to clear factor is defined as the ratio of rms voltage
between faulted phase and unfaulted phase and phase to neutral
voltage with the fault removed. Figure 8-4 shows first pole to clear
factors for three-phase terminal faults. The first pole to clear factor
for three-phase fault with ground contact is calculated as:
1. Voltage across breaker contacts rises slowly as RRRV
decreases.
where:
αZ =
185
First Pole to Clear Factor
TRV refers to the voltage across the first pole to clear because it is
generally higher than the voltage across the other two poles of the
breaker which clear later. Consider a three-phase ungrounded fault.
The voltage across the breaker phase, first to clear, will be 1.5 times
the phase voltage (Fig. 8-4). The arc interruption in three phases is
not simultaneous, as the three phases are mutually 120° displaced.
Thus, theoretically, the power-frequency voltage of the first pole to
clear is 1.5 times the phase voltage. It may vary from 1.5 to 2, rarely
TA B L E 8 - 2
PHASE TO CLEAR
1
The TRV is affected by many factors, amongst which the power
factor of the current being interrupted is important. At zero power
factors, maximum voltage is impressed across the gap at the instant
of current zero, which tends to reignite the arc in the hot arc
medium.
TRV can be defined by specifying the crest and the time to reach
the crest, and alternatively, by defining the segments of lines which
envelope TRV waveform.
The steepest rates of the rise in a system are due to short circuits
beyond transformers and reactors which are connected to a system
of high short-circuit power. In these cases, the capacitance which
retards the voltage rise is small; however, the breaking capacity
of the breaker for such faults need only be small compared to
Initial Transient Recovery Voltage
RECOVERY VOLTAGE ACROSS BREAKER UP TO ARRIVAL OF FIRST REFLECTION
U s = i1(t )
1
3(W 0 + Z 0 )(W ′+ Z′)(W ′′ + Z′′)
+ (W 0 + Z 0 )(W ′′ + Z′′) + (W ′ + Z′)(W ′′ + Z′′)
(W + Z )(W ′ + Z′)+
0
0
(W 0 + Z 0 )(W ′+ Z′) + (W 0 + Z 0 )(W ′′ + Z′′) + (W ′ + Z′)(W ′′+ Z′′)
W 0 + W ′ + W ′′ + Z 0 + Z′ + Z′′
2
U s = i2 (t )
3
1
U s = i3 (t ) (W 0 + W ′ + W ′′+ Z 0 + Z′ + Z′′)
3
3
2
i1 (t ), i2 (t ), and i3 (t ) are the currents injected into first, second, and third phases to clear. Us1, Us2, Us3 are initial TRVs.
186
CHAPTER EIGHT
FIGURE 8-4
(a) First pole to clear factor, three-phase terminal fault, no connection to ground. (b) Three-phase fault continuing power system on load
side. (c) Three-phase-to-ground fault, continuing power system on the load side.
The interrupting capacity of every circuit breaker decreases
with an increase in natural frequency. It can, however, be safely said
that the interrupting (or breaking) capacity for the circuit breakers decreases less rapidly with increasing natural frequency than
the short-circuit power of the system. The simplest way to make
the breaking capacity independent of the natural frequency is to
influence the rate of rise of recovery voltage across breaker contacts
by resistors, which is discussed further. Yet, there may be special
situations where the interrupting rating of a breaker may have to
be reduced or a breaker of higher interrupting capacity is required.
TRV is an important parameter for the specifications of circuit
breakers, and ANSI/IEEE and IEC standards specify TRV parameters in the rating structure of the breakers.
8-5
FIGURE 8-5
Effect of frequency of TRV on the RRRV (rate of rise of
recovery voltage).
short-circuit power of the system, as the current is greatly reduced
by the reactance of the transformers and reactors. It means that in
most systems, high short-circuit levels of current and high natural
frequencies may not occur simultaneously.
SINGLE-FREQUENCY TRV TERMINAL FAULT
A circuit of a single-frequency transient occurs for a terminal
fault in a power system composed of distributed capacitances and
inductances. A terminal fault is defined as a fault close to the circuit
breaker, and the reactance between the fault and the circuit breaker
is negligible. TRV can vary from low to high values in the range of
20 to 10000 Hz.
Figure 8-6a shows power system constants, that is, resistance,
inductance, and capacitance. The circuit shown may well represent the ∏ model of a transmission line (see Chap. 4). Figure 8-6b
shows the basic parameters of the recovery-voltage transient for a
terminal fault in simplified network of Fig. 8-6a. It shows behavior of recovery voltage, transient component, and power-frequency
CURRENT INTERRUPTION IN AC CIRCUITS
component. The amplitude of the power-frequency component is
given by:
α 2 u0
(8-17)
where α depends on the type of fault and the network, and u0 is the rated
system rms voltage. The rate of rise of recovery voltage (RRRV = S) is
the tangent to the transient recovery voltage starting from the zero
point of the unaffected or inherent transient recovery voltage (ITRV).
This requires some explanation. The TRV can change by the circuit
FIGURE 8-6
RRRV shown as S.
187
breaker design and operation. The TRV measured across terminals
of two circuit breakers can be different. The power system characteristics are calculated ignoring the effect of the breakers. This means
that an ideal circuit breaker has zero terminal impedance when carrying its rated current, and when interrupting short-circuit current,
its terminal impedance changes from zero to infinity instantaneously.
The TRV is then called inherent transient recovery voltage.
Figure 8-6c shows an enlarged view of the slope. Under a few
microseconds, the voltage behavior may be described by time
Recovery-voltage profile on a terminal fault. (a) System configuration. (b) Recovery-voltage profile. (c) Initial TRV curve, delay line and
188
CHAPTER EIGHT
delay td, which is dependent on the ground capacitance of the circuit.
The time delay td in Fig. 8-6c is approximated by:
t d = CZ0
(8-18)
where C is the ground capacitance and Z0 is the surge impedance.
Measurements show that often a superimposed high-frequency
oscillation appears. IEC specifications recommend a linear voltage
rise with a surge impedance of 450 Ω and no time delay when the
faulted phase is the last to be cleared in a single line-to-ground
fault. This gives the maximum TRV. It is practical to distinguish
between terminal faults and short-line faults for these phenomena.
8-5-1
TRV in Capacitive and Inductive Circuits
The TRV on interruption of capacitive and inductive circuits is
illustrated in Fig. 8-7. In a capacitive circuit when the current
passes through zero, Fig. 8-7a, the system voltage is trapped on
the capacitors; also see Fig. 6-35b. The recovery voltage, the difference between the source side and load side of the breaker, reaches
a maximum of 2.0 per unit after 1/2 cycle of current interruption,
FIGURE 8-7
Fig. 8-7b and c. The TRV oscillations are practically absent as large
capacitance suppresses the oscillatory frequency [Eq. (8-11)] and
the rate of rise of the TRV is low. This may prompt circuit breaker
contacts to interrupt, when there is not enough separation between
them and precipitate restrikes.
This is not the case when disconnecting an inductive load
(Fig. 8-7d, e, and f ). The capacitance on the disconnected side is
low and the frequency of the isolated circuit is high. The TRV, is,
therefore, oscillatory. The rate of rise of TRV after disconnection
is fairly high.
Above are examples of single-frequency transients which occur
when the electrical energy is distributed between capacitive and
inductive elements and no transmission line remains connected at the
bus after the short circuit. Surge voltage is neglected; there is no initial
charge on the capacitor or initial flow of current. Then the voltage at
the capacitor, which can be equated to TRV, from Chap. 2, is:
TRV =
1
V s
2
2
2
LC s + ω s + 1/LC
(8-19)
(a), (b), and (c) Interruption of capacitance current, circuit diagram, load- and source-side voltages, and TRV, respectively. (d), (e), and (f ).
Interruption of inductive current, circuit diagram, load- and source-side voltages, and TRV, respectively.
CURRENT INTERRUPTION IN AC CIRCUITS
By substituting:
2 per unit and no oscillations are observed. The tripping and closing resistors have conflicting requirements, and in HV breakers
there may be separate resistors for these functions or the resistance
value is optimized (Chap. 7).
ω0 = 1/LC
TRV =
V cos ω t − cos ω0t
LC
ω02 − ω 2
= V (1 − cos ω0t )
for
(8-20)
ω < < ω0
Here V is generally taken as 1.88 times the system rms voltage
based on a terminal fault. We discussed first pole to clear factor
[Eqs. (8-15) and (8-16)], and stated that the power frequency overvoltage can be 1.5 to 3.0 per unit, but it rarely exceeds 2.0.
This is the so called “1-minus-cosine” curve of ANSI specifications.
Reverting to TRV on disconnection of a capacitance, IEEE standard [C37.04] specifies that voltage across capacitor neutral, not
ground, during an opening operation should not exceed 3.0 per unit
for a general-purpose breaker.4 For the definite-purpose breaker
rated 72.5 kV and lower, this limit is 2.5 per unit. For breakers
rated 121 kV and above, capacitor banks are normally grounded
(Chap. 6), and the voltage is limited to 2.0 per unit. It was observed
that when interrupting capacitance current 2.0 per unit voltage
occurs at small contact separation, this can lead to restrikes. With
no damping, the voltage will reach 3.0 per unit (Fig. 6-35c). This
suggests that one restrike is acceptable for general-purpose breakers,
but not for definite-purpose breakers.
Some voltage-controlled methods are resistance switching and
surge arresters. The resistance switching was discussed in Chap. 6
(Fig. 6-39a), which shows that with 1.32-Ω resistor inserted for
4 cycles, the switching transients almost disappear. The effect on
voltage recovery is shown in the following example.
Example 8-1 This is an EMTP simulation of resistance switching to control recovery voltage. Again, consider 6-Mvar capacitor
bank, 1.32 Ω switching resistance. The system is in steady state and
the capacitor is energized. First open the switch at 4 ms to insert
1.32-Ω resistance in series with the break, and then at 8 ms open
the resistor circuit. The resulting source and load-side voltages and
TRV are shown in Fig. 8-8. This shows a TRV of approximately
FIGURE 8-8
189
8-6
DOUBLE-FREQUENCY TRV
A circuit with inductance and capacitance on both sides of the
circuit breaker gives rise to double-frequency TRV. After fault
interruption, both circuits oscillate at their own frequencies and
a composite double-frequency transient appears across the circuitbreaker contacts. This can occur for a short-line fault. Recovery
may feature traveling waves, depending on the faulted components
in the network.
The circuit breakers in systems above 121 kV are usually applied
in composite circuits where the faults can be fed from the transmission lines and transformers. Consider Fig. 8-9a where n transmission lines emanate from a bus; note that a transformer terminated
line is included. The bus is fed from a transformer and the source
reactance can be added to the transformer reactance; a three-phase
ungrounded fault occurs on the bus, as shown in the figure.
Figure 8-9b shows the transient network when the first pole
(in phase a) interrupts the fault, while the other two poles of the
breaker are still closed. The phase a voltage to ground is 1.0 per
unit and the phases b and c voltages are equal to –0.5 per unit. If
the voltage on the load side of the breaker pole is denoted as VL and
on the source side as VB, then the recovery voltage is the difference
of these two voltages.
To derive at an equivalent circuit, as shown in Fig. 8-9c, the
surge impedance of n lines in parallel is Z/n. The faulted line also
has its surge impedance Z, and C is the capacitance of the transformer, bus, and breaker, all lumped together. On the bus side, the
voltage VB is determined by the voltage drop across transformer
reactance Ls, bus capacitance C, and equivalent surge impedance
of n lines in parallel. On the fault side of the breaker pole, the path
is through phases b and c in parallel. This explains the bottom-half
of Fig. 8-9c.
The circuit is solved by current injection method. In current
injection method, a current equal and opposite to the short-circuit
EMTP simulation of TRV, resistance switching, interruption of capacitive currents, Example 18-1.
190
CHAPTER EIGHT
FIGURE 8-9
(a) A power system configuration. (b) Equivalent circuit drawn with first pole to clear; the other two poles still connected. (c) Development
of circuit for TRV. (d ) Simplification of the circuit in (c) for TRV calculations.
current that would have continued to flow in the event that interruption does not occur is flowing at the instant of current zero
when the current interruption takes place. All bus voltage sources
are equal to zero and a current pulse in injected into the breaker
pole, which is equal and opposite to the current that would have
flown if the breaker pole would have remained closed. Thus, 1/2
cycle of the three-phase fault current is injected into the open phase
of the breaker.
A further simplification is shown in Fig. 8-9d. This ignores the
capacitance, and the surge impedance of the faulted line which will
be relatively high. Ignoring capacitance is justified on the basis that
the surge impedance of the lines provides enough damping.
From Chap. 2, the operational impedance of the parallel circuit
is given by:
Zs =
1 . 5sL s Z n
Z n + sL s
(8-21)
where Zn = Z/n.
Therefore:
Zn
VTRV = 1 . 5 2 Iω
s(s + Zn /L )
(8-22)
CURRENT INTERRUPTION IN AC CIRCUITS
191
The initial rate of rise is obtained by taking a derivative of
Eq. (8-25), and at t = 0, this gives:
R 0 = 1 . 5 2Iω Z n
(8-26)
This means that initial TRV is directly proportional to fault current interrupted and inversely proportional to the number of transmission lines that remain connected to the bus.
8-7
FIGURE 8-10
Profile of TRV, equivalent waveform.
Or in the time domain:
VTRV = 1 . 5 2Iω L s (1 − e −αt )
where α = Z n /L s.
(8-23)
(8-24)
We can also write:
VTRV = 1 . 5
2
V (1 − e −αt )
3 rated
(8-25)
where Vrated is the maximum rated voltage of the device.
This voltage, as a traveling wave, will be reflected at the impedance discontinuity, and when it arrives at the point of the fault, its
effective value is the initial magnitude, multiplied by reflected and
refracted coefficients (Chap. 4). The TRV can then be found by first
plotting the initial exponential wave given by Eq. (8-25) and then
adding a time equal to approximately 30 km/s, a voltage equal to
the reflected and refracted coefficients (Fig. 8-10).
FIGURE 8-11
above.
ANSI/IEEE STANDARDS FOR TRV
According to ANSI/IEEE standards, for circuit breakers rated 100 kV
and below, the rated transient voltage is defined as the envelope
formed by 1-cosine wave shape using values of E2 and T2, as defined
in the standards. E2 is the peak of the TRV which is taken as 1.88 times
the maximum rated voltage and T2 is in microseconds to reach this
peak, and is variable, depending on the circuit-breaker type, shortcircuit type, and voltage rating. This is shown in Fig. 8-11a; for first
1/2 cycle, the power-frequency component is considered constant and
is represented by a straight line E2. The curve of Fig. 8-11a is called
1-minus cosine curve. The TRV is defined by the envelope formed by
the curve.
For breakers rated 100 kV and above, the rated TRV is defined
by higher of an exponential waveform and 1-cosine waveform,
Fig. 8-11b, which closely represents the waveform arrived at in
Fig. 8-10. For systems above 100 kV, most, if not all, systems are
grounded and a first pole to clear factor of 1.3 is considered. E1 =
1.06 V and E2 = 1.49 V. Envelope formed by the exponential curve
is obtained by reading the rated values E1, R, T1, E2, and T2 from
standards and applying these values at the rated short-circuit current
of the breaker. R is defined as the rated TRV rate ignoring the effect
of bus-side capacitance, at which recovery voltage rises across the
terminals of a first pole to interrupt for a three-phase, ungrounded
load-side fault under the specified rated conditions. The rate is a
close approximation of the de/dt in the rated envelope, but slightly
higher because the bus-side capacitance is ignored. The equations
are written as:
e1 = E1(1 − e −t / τ )
τ = E1 /R
e2 =
(8-27)
E2
[1 − cos(π t /T2 )]
2
(a) ANSI/IEEE 1-minus-cosine curve for breakers rated 100 kV and below. (b) ANSI/IEEE TRV profile for breakers rated 100 kV and
192
CHAPTER EIGHT
There has been an attempt to harmonize ANSI/IEEE standards
with IEC. Refer to IEEE unapproved draft standard for ac highvoltage circuit breakers rated on symmetrical current basis—preferred ratings and required related capabilities for voltage above
1000 V.7 A joint task force group was established to harmonize
requirements of TRV with that in IEC62271-100, including
amendments 1 and 2. This draft standard also publishes new rating
tables and completely revises the ratings and the nomenclature of
the circuit breakers which has been in use in the United States for
many years:
withstanding a TRV envelope where E2 value is higher and T2 value
is reduced. This is illustrated in Example 8-3.
Example 8-3 Calculate the TRV profile for the circuit breaker in
Example 8-2 at 75 percent of the rated short-circuit current.
This requires the calculation of multiplying factors for adjustment based on the curves in ANSI standard C37.06, 1997. Note
that the standard was revised in 1999, but this revised standard
did not contain the curves included in the 1979 issue and merely
referred to these curves. From these curves:
Kr = rate of rise multiplying factor = 1.625
■
Class S1 and S2 is used to denote traditional terms as
“indoor” and “outdoor.” The class S1 circuit breaker is for cable
systems; indoor circuit breakers are predominantly used with
cable distribution systems. Class S2 is for overhead line
systems.
■
The term “peak” is used—the term “crest” has been
dropped from the usage. All tables show “prospective” or
“inherent” characteristics of the current and voltages. The word
prospective is used in conformance to international standard.
■
Two and four parameter of representations of TRV is
adopted in line with IEC standards.
■
For class C0, general-purpose circuit breakers, no ratings
are assigned for back-to-back capacitor switching. For class C0,
exposed to transient currents for nearby capacitor banks during fault conditions, the capacitance transient current on closing
shall not exceed the lesser of either 1.41 times rated short-circuit
current or 50 kA peak. The product of transient inrush current
peak and frequency shall not exceed 20 kAkHz. Definite-purpose
circuit breakers are now identified as Class C1 and C2. Here the
manufacturer shall specify the inrush current and frequency at
which Class C1 or C2 performance is met.
Example 8-2
Plot the TRV characteristics of 550-kV breaker
based on the ANSI/IEEE standards. To start with, consult ANSI
standard C37.063 and the following ratings are specified:
K factor = 1
Consider breaker current rating of 2 kA.
Rated short-circuit current = 40 kA. The TRV should be
plotted for the actual available short-circuit current. For this
example, we will plot the curve for 40 kA.
T2 = 1,325 µs
R, rate of rise of recovery voltage = 2 kV/µs
Rated time delay T1 = 2 µs
E1 = 1 . 06 × rated maximum voltage = 583 kV
E2 = 1 . 49Emax = 819.5 kV
τ = E1 /R = 583 / 2 = 291.5 µs
Then from Eq. (8-27):
e1 = 583(1 − e −t / 291.5 )
e 2 = 409 . 8(1 − cos 0 . 135t 0 )
The calculated TRV profile is shown in Fig. 8-12a.
A circuit breaker should be capable of interrupting a shortcircuit current which is less than the rated current. This requires
K1 = E2 multiplying factor = 1.044
Kt = T2 dividing factor = 1.625
This gives:
E1 = 583 kV
E2 = (819.5) (1.044) = 855.5 kV
T2 = (1,325)/1.625 = 815.4 µs
T1 = 2 µs (unchanged)
R = (1.6)(1.625) = 2.60 kV/µs
τ = E1 /R = (583)/ 3 . 25 = 179.4 µs
The TRV for 75 percent fault current is also plotted in the
Fig. 8-12a and it is higher than the TRV for 100 percent fault current.
8-7-1 Definite-Purpose Circuit Breakers TRV
Example 8-3 suggests that there can be situations when the TRV
of a breaker may be exceeded. Consider, for example, a configuration, as shown in Fig. 8-13a. A three-phase ungrounded fault occurs
on the low side of the transformer, as shown, and the transformer
secondary winding is grounded. If we neglect the source impedance and its capacitance, the voltage on the transformer side of
the first pole to clear of the breaker is 1.0 per unit, while on the
fault side it is –0.5 per unit. Thus, voltage across the breaker pole
is 1.50 per unit. (These values can be found by circuit reduction,
first pole to open, as shown in Fig. 8-9.) The voltages on the transformer and fault side will oscillate at a frequency determined by
the inductance and capacitance of the transformer Fig. 8-13b. The
source-side voltage may reach a peak of 2 times and the fault side
a peak of 1.0 per unit. Thus, the TRV may hit a peak of 3.0 per
unit without damping.
For a three-phase grounded fault, delta-wye grounded transformer (Fig. 8-13c), the voltage on the fault side is 0, and the voltage on the transformer side of circuit breaker is 1.0 per unit. With
no damping, this voltage overshoots and oscillated about E, and is
2.0 per unit, and with damping, somewhat less (Fig. 8-13d).
The TRV profile in Fig. 8-13e shows the fault on a reactor that
will have a higher oscillation frequency because of lower capacitance. The effect of the source impedance and capacitance will be
to reduce the transients.
ANSI standard C37.06.18 is for Definite Purpose Circuit
Breakers for Fast Transient Recovery Voltages Rise Times. This is
somewhat akin to the specifications of definite-purpose breakers
for capacitor switching. Table 8-3 shows some comparisons of the
TRV specifications from the standard breakers and definite-purpose
breakers. The standard qualifies that:
1. No fast T2 values or tests are proposed for fault currents
> 30 percent of the rated short-circuit current.
CURRENT INTERRUPTION IN AC CIRCUITS
FIGURE 8-12
(a) Calculations of TRV profiles, Examples 8-2, 8-3, and 8-4, with superimposed IEC profiles (b) Initial rise, short-line fault.
2. The proposed T2 values are chosen to meet 90 percent of
the known TRV circuits, but even these fast values do not meet
the requirements of all fast TRV applications.
3. A circuit breaker that meets the requirements of definite
purpose for fast TRV may or may not meet the requirements
of definite-purpose circuit breakers for capacitor switching
(Chap. 6).
terminal faults higher than 30 percent of rating will result in TRV
characteristics that have a four-parameter envelope. The TRV
wave has an initial period of high rise, followed by a low rate
of rise. Such waveforms can be represented by a four-parameter
method:
u1 = first-reference voltage in kV
t1 = time to reach u1, in µs
Table 8-3 shows some specimen values for fast TRV definitepurpose circuit breakers.
uc = second-reference voltage, peak value of TRV
8-8
t2 = time to reach uc, in µs
IEC TRV PROFILES
Two and four parameter methods of representation of TRV are used
in IEC 62271–1009, which is also adopted in IEEE draft standard.7
8-8-1
193
Four-Parameter Method
Figure 8-14 shows the representation of TRV wave by four-parameter
method. Standards assume that for systems above 72.5 kV, clearing
IEC specifies values of u1, uc, t1, and t2 for the circuit breakers.
These values are also specified in Ref. 7. The amplitude factor kaf
is given for various test duties, T100, T60, T30, T10, for example.
The interrupting current tests are carried out on circuit breakers
with specified TRVs. The segments can be plotted, as shown in
Fig. 8-14, based on the parameters specified in standards. A table
194
CHAPTER EIGHT
FIGURE 8-13
(a) and (b) Three-phase-ungrounded fault on the secondary side of a delta-wye-grounded transformer and TRV profile, respectively.
(c) and (d ) Three-phase-grounded fault on the secondary side of a delta-wye-grounded transformer and TRV profile, respectively. (e) Situations (transformer
and reactor faults) where TRV can exceed the TRV capability curve of the breakers.
TA B L E 8 - 3
Specimen ANSI/IEEE Recovery Voltage Parameters of Definite-Purpose Circuit Breakers
(123 kV and Above)
DEFINITE-PURPOSE
TRV PARAMETERS
AT 30% OF RATED
SHORT-CIRCUIT CURRENT
DEFINITE-PURPOSE
TRV PARAMETERS AT 7% OF
RATED SHORT-CIRCUIT CURRENT
RATED MAXIMUM
VOLTAGE (KV)
K FACTOR
RATED SHORTCIRCUIT AND
SHORT-TIME
CURRENT (KA rms)
245
1
63
431
520
19
487
30.3
4.4
505
43.8
362
1
40
637
775
12
720
40.7
2.8
745
63.2
RATED RECOVERY VOLTAGE
PEAK VOLTAGE,
TIME TO
E2 (KV), PEAK PEAK, T2 (lS)
CURRENT
(KA rms)
PEAK VOLTAGE TIME TO
CURRENT
PEAK
TIME TO
(KV), PEAK PEAK (lS) (KA rms) VOLTAGE (KV) PEAK (lS)
362
1
63
637
775
19
720
37.1
4.4
745
55.7
550
1
40
968
1325
12
1094
49.0
2.8
1133
76.1
550
1
63
968
1325
19
1094
44.7
4.4
1133
63.9
in IEEE std. C37.011 provides factors for calculating rated TRV
profiles for terminal faults.6
uc = kaf × kpp × 2 / 3 × U r
(8-28)
where kpp is the first pole to clear factor. For T10 (10% of interrupting current):
uc (T10) = uc (T100) × Kuc
where Ur is the breaker-rated voltage.
(8-29)
8-8-2
Two-Parameter Representation
For terminal faults between 10 and 30 percent for systems above
72.5 kV and for all terminal fault currents for systems 72.5 kV and
below,7 the standard assumes a TRV profile defined by two parameters, uc and t3. Figure 8-15 shows the representation of TRV wave
by two-parameter method. This waveform occurs in systems less
than 100 kV or locations where short-circuit current is low compared to the maximum short-circuit current in the system. TRV can
be approximately represented by a single-frequency transient.
CURRENT INTERRUPTION IN AC CIRCUITS
FIGURE 8-14
195
IEC, four-parameter representation of TRV.
uc = peak of TRV wave, kV
t3 = time to reach peak, µs
The initial rate of rise of TRV is contained within segments drawn
according to two- or four-parameter methods by specifying the delay
line, as shown in Fig. 8-15. Thus, there can be many varying TRV
profiles depending upon (1) type of fault, (2) the system configuration
and location where the fault occurs, and (3) modifying behavior of
the circuit breaker interruption process. For a terminal fault and a
typical switchgear layout of overhead lines, local transformers, and
generators, the rate of rise of TRV can be estimated from:
S = 2π f 2 I k Z r
(8-30)
where Ik is short-circuit current and Zr is the resultant surge impedance. Zr can be found from sequence impedances. With n equal
outgoing lines:
Zr = 1 . 5( Z1 /n )
2 Z0 /Z1
1 + 2 Z0 /Z1
(8-31)
where Z1, Z0 are the surge impedances in positive and zero sequence
of individual lines and n is the number of lines emanating from the
substation. Factors 1.5 can be 1.3 in (Eq. 8.31). For plotting the
TRV profile, traveling wave phenomena must be considered. For
single-frequency transients, with concentrated components, IEC
tangent (rate of rise) can be estimated from:
S=
2 2 f nka f u0
0 . 85
(a) TRV measurements in a 400-kV system. (b) Representation by IEC methods.
FIGURE 8-16
(8-32)
where fn is the natural frequency and kaf is the amplitude factor. The
peak value uc in a four-parameter method cannot be found easily
due to many variations in the system configurations. The traveling
waves are partially or totally reflected at the points of discontinuity of the surge impedance. A superimposition of all forward and
reflected traveling waves gives the overall waveform.
Figure 8-16a shows the TRV profiles in a 400-kV system, with
a three-phase ground fault, and Fig. 8-16b shows a four-parameter
representation of the TRV according to IEC. The per unit voltage
is defined as ( 2 × 400)/ 3 . The variations in profiles of TRV are
noteworthy.
8-9
FIGURE 8-15
IEC, two- parameter representation of TRV.
SHORT-LINE FAULT
Faults occurring between a few kilometers to some hundreds of
kilometers from the breaker are termed short-line faults (SLF),
(Fig. 8-17a). The single-phase fault, the faulty phase being last to
be disconnected, is taken as the basis, as this gives the largest rate
of rise at the beginning of the recovery voltage. The line to the fault
point is represented by its surge impedance. After the short-circuit
current is interrupted, the breaker terminal at the line end assumes
a sawtooth oscillation shape, as shown in Fig. 8-17c. Note the small
time-delay td in this figure; this is because of the capacitance of the
line-side apparatus. The rate of rise of voltage is directly proportional to the effective surge impedance (that can vary between 35
and 450 Ω, the lower value being applicable to cables) and the rate
of rise of current at current zero. As the terminating impedance is
zero, the reflection coefficient is –1, and a negative wave is produced traveling toward the breaker. The component on the supply
196
CHAPTER EIGHT
FIGURE 8-17
TRV for a short-line fault. (a) System equivalent circuit. (b) Recovery voltage on the source side. (c) Recovery voltage on the load side.
(d ) Voltage across the breaker contacts.
side exhibits the same waveform as for a terminal fault (Fig. 8-17b).
The circuit breaker is stressed by the difference between these two
voltages (Fig. 8-17d). Because of the high-frequency oscillation of
the line-side terminal, the TRV has a very steep initial rate of rise.
In many breaker designs, the short-line fault may become a limiting
factor of the current-interrupting capability of the breaker.
IEEE Std. C37.044 specifies the TRV envelope and the time to
first peak, depending on the breaker rating. The circuit breaker
shall be capable of interrupting single-phase line faults at any distance from the circuit breaker on a system in which:
1. The voltage in the first ramp of the sawtooth wave is equal
to or less than that in an ideal system in which the surge
impedance and amplitude constants are as follows:
242 kV and below, single-conductor line: Z = 450, d = 1.8
362 kV and above, bundle conductors: Z = 360, d = 1
2. The amplitude constant d is the peak ratio of the sawtooth
component that will appear across the circuit breaker terminals
at the instant of interruption. The SLF TRV capability up to
first peak of TRV is: e = eL + eS, where eL is the line-side contribution and eS is the source-side contribution. The triangular
wave is defined as:
e L = d(1 − M )
2
E
3 max
e s = 2M(t L − t d )
(8-33)
(8-34)
CURRENT INTERRUPTION IN AC CIRCUITS
Also:
R L = 2ωMIZ × 10−6 kV/µ s
t L = e /R L µ s
(8-35)
where RL is the rate of rise, tL is the time to peak, M is the ratio of the
fault current to rated short-circuit current, I is the rated short-circuit
current in kA, V is the rated voltage, Z is the surge impedance, and
e is the peak voltage in kV.
We could write the frequency as:
f=
106
2(e /R L )
(8-36)
There is a delay of 0.5 µs for circuit breakers rated 245 kV and
above and 0.2 µs for circuit breakers rated below 245 kV. It is not
necessary to calculate SLF TRV as long as terminal-fault TRV is
within rating and transmission-line parameter is within those specified in the standards.
Example 8-4 In Examples 8-2 and 8-3, 550-kV breaker TRV profiles have been plotted in Fig. 8-12. Plot the short-line capability for
75 percent short-circuit current and a surge impedance of 360 Ω.
Based on the given data, M = 0.75, I = 40 kA, V = 550 kV,
Z = 360 Ω. Thus, e is:
e = 1 . 6(0. 75)(550)
2
= 179 . 6 kV
3
R L = 2 × 377 × 0 . 75 × 40 × 360 × 1 0−6 = 5 . 75 kV/µ s
Therefore, tL = 31.2 µs.
The TRV profile is superimposed in Fig. 8-12a, and an enlarged
profile is shown in Fig. 8-12b.
8-9-1
Control of Short-Line TRV
It is possible to reduce the voltage stresses of TRV by incorporating
resistances or capacitances in parallel with the contact break and
by synchronous switching (Chap. 7). Figure 8-18 shows some control methods. In (a) resistor switching is used. The main contacts
open leaving the resistor in the circuit, which is opened after about
1 cycle. The current has a parallel path through the resistor which
decreases the rate of rise. In (b) a shunt capacitor is provided. In (c) a
capacitor is applied across the open poles of the circuit breaker. Most
multibreak high-voltage circuit breakers (more than one breaker per
phase) use grading capacitors to ensure voltage division across the
197
multibreaks. The capacitor acts the same way as a shunt capacitor.
The sawtooth wave is delayed by the time constant ZC.
Sometimes, the grading capacitors can cause ferroresonance with
the potential transformer (PT) reactance on the same bus (Fig. 14-43a
and b). The grading capacitor and the bus capacitance act as a voltage divider, and the voltage on the bus is:
Vb =
C0
C0 + C B
(8-37)
where C0 is the equivalent capacitance across the breaker gaps. This
means that there will be some voltage imparted to a dead bus. With
a PT connected to the bus, the bus voltage is:
Vb =
Xm
XC − X m
(8-38)
0
Xm is nonlinear and the bus voltage is determined by the intersection of transformer saturation curve and the capacitance of the line.
Resistance can be introduced in the secondary circuit of the PT to
mitigate a ferroresonance problem.
8-9-2
Initial TRV
Circuit beakers rated 100 kV and above and short-circuit rating of
31.5 kA and above will have an initial TRV capability for phase-toground fault. This rises linearly from origin to first-peak voltage Ei
and time Ti given in Ref. 4. Ei is given by the expression:
Ei = ω × 2 × I × Zb × Ti × 10−6 kV
(8-39)
where Zb is the bus surge impedance = 450 Ω for outdoor substations, phase-to-ground faults and I is in the fault current in kA.
The term initial TRV refers to the conditions during the first microsecond or so, following a current interruption, when the recovery
voltage on the source side of the circuit breaker is influenced by
proximity of buses, capacitors, isolators, and so on. Akin to shortline fault, voltage oscillation is produced, but this oscillation has
a lower voltage-peak magnitude. The traveling wave will move
down the bus where the first discontinuity occurs. The initial slope
depends on the surge impedance and di/dt, and the peak of ITRV
appears at a time equal to twice the traveling wave time. There can
be as many variations of ITRV as the station layouts. Ti in µs, time
to crest, is given in IEEE Std. C37.04 with respect to maximum
system voltage: For 121, 145, 169, 362, 350, and 500 V, it is 0.3,
0.4, 0.5, 0.6, 0.8, 1.0, and 1.1, respectively.
The TRV capability envelope of a 550-kV breaker at 100 percent of its interrupting rating, as per Fig. 8 of IEEE Std. C37.011
is superimposed upon the calculated curves in Fig. 8a. The two
profiles shown relate to first pole to clear factor kpp of 1.3 and 1.5,
respectively. The parameters shown are from IEEE Std. C37.011.
This standard contains an example of TRV calculations in a practical electrical system, which an interested reader may refer to.
8-10 INTERRUPTION OF LOW INDUCTIVE
CURRENTS
FIGURE 8-18
Control of TRV on short-line faults. (a) Resistors
across circuit breaker main contacts inserted for a short duration during
opening. (b) Shunt capacitors. (c) Series grading capacitors across
multibreaks per phase in circuit breakers.
A circuit breaker is required to interrupt low inductive currents of
transformers at no-load, high-voltage reactors, or locked rotor currents of motors. Because of arc instability in a low-current region,
current chopping can occur, irrespective of the breaker interrupting
medium, though some mediums may be more prone to current
chopping, that is, vacuum technology compared to SF6 breakers. In
a low-current region, the characteristics of the arc lead to a negative
resistance which lowers the damping of the circuit. This sets up a
high-frequency oscillation, depending on the LC of the circuit.
Figure 8-19a shows the circuit diagram for interruption of
low inductive currents. The inductance L2 and capacitance C2 on
198
CHAPTER EIGHT
which oscillates at the natural frequency of the disconnected circuit:
f2 =
1
(8-42)
2π L2C 2
This frequency may vary between 200 and 400 Hz for a transformer. The maximum voltage on the load side occurs when all the
inductive energy is converted into capacitive energy:
u22 max
C2
C
L
= u22 2 + ia2 2
2
2
2
(8-43)
The source-side voltage builds up with the frequency:
f1 =
1
(8-44)
2π L1C1
The frequency f1 lies between 1 and 5 kHz. This is shown in
Fig. 8.19c.The linear expression of magnetic energy at the time of
current chopping is not strictly valid for transformers and should
be replaced with:
Bm
∫ HdB
Volume of transformer core ×
(8-45)
0
The load-side voltage decays to zero due to system losses. The
maximum load-side overvoltage is of concern (Fig. 8-19d) and
from simplified relation Eq. (8-43), it is given by:
u2 max = ua2 + ηmia2
L2
C2
(8-46)
Here we have added a factor ηm to account for saturation. The factor is approximately unity for air-core reactors and is of the order of
0.3 to 0.5 for transformers at no load. Eq. (8-46) ignores the effect
of circuit breaker behavior and is conservative. For low magnitude
of chopping current at the peak of the supply voltage:
ua = u n
2
3
(8-47)
Then, the overvoltage factor k is given by:
k = u2 /ua = 1 +
FIGURE 8-19
Interruption of low inductive currents. (a) The equivalent circuit diagram. (b) Chopped current ia at ua . (c) Source-side voltage.
(d ) Load-side voltage. (e) Voltage across breaker contacts. (f ) Phenomena
of repeated restrikes.
f3 =
1
CC
2π L 1 2
C1 + C2
(8-40)
Practically, no current flows through the load inductance L2.
This forces a current zero, before the natural current zero, and the
current is interrupted (Fig. 8-19b). This interrupted current ia is the
chopped current at voltage ua (Fig. 8-19c). Thus, the chopped current is not only affected by the circuit breaker, but also the properties of the circuit. The energy stored in the load at this moment is:
ia2
L2
C
+ ua2 2
2
2
(8-41)
2
(8-48)
If the current is chopped at the peak value, ua = 0, and:
u2 max = ia ηm
the load side can represent transformers and motors. As the arc
becomes unstable at low currents, the capacitances C1 and C2 partake in an oscillatory process of frequency:
L
3 ia2
ηm 2
2
2 un
C2
L2
C2
(8-49)
Thus, the overvoltage is dependent on the chopped current.
The chopped currents in circuit breakers have been reduced with
better designs and arc control. The voltage across the supply side
of the breaker, neglecting arc voltage drop, is us and it oscillates at
the frequency given by L and C1. The voltage across the breaker
contacts is us = u1 – u2 (Fig. 8-19e). The supply-side frequency is
generally between 1000 and 5000 Hz.
If the circuit-breaker voltage intersects the dielectric recovery
characteristics of the breaker, reignition occurs and the process is
repeated anew (Fig. 8-19f ). With every reignition, the energy stored
is reduced until the dielectric strength is large enough and further
reignitions are prevented. Overvoltages of the order of two to four
times may be produced on the disconnection of inductive loads.
The disconnection of high-voltage reactors may involve interrupting
reactive currents of the order of 100 to 200 A. The maximum overvoltage factor can be calculated from Eq. (8-49). Note that factor L /C
for the reactors is high, of the order of 50 kΩ. In most practical cases,
CURRENT INTERRUPTION IN AC CIRCUITS
the overvoltage factor will be less than 2.5. Surge arresters can be used
to limit the overvoltages (Chap. 20). In the previous equations for calculations of the overvoltage factors, the influence of the breaker itself is
ignored; however, the equations seem to be conservative, as the breaker
arc effects may lower the overvoltages given by the above equations.
The parallel compensated lines should be mentioned as the
recovery voltages can be high. The voltage on the disconnected
side oscillates with slight damping near the power frequency. The
voltage across the breaker contacts can be high, and restrike free
breakers are needed.
199
Example 8-5 An EMTP simulation of the recovery voltage of a
230-kV transmission line grounded at the far end, surge impedance of 300 Ω, is shown in Fig. 8-20. This shows the line-side
and source-side voltages and also the voltage across the breaker
contacts. The high-frequency recovery voltage is evident and the
maximum magnitude is 2.13 per unit.
Figure 8-21 shows the recovery profile when a 138-kV transmission line at no load is opened, arcing time ignored, ideal switch.
The maximum voltage is 2.52 per unit.
FIGURE 8-20
EMTP simulation of interruption of a line ground fault current. Voltages on the source and load side and the recovery voltage across
breaker contacts showing high-frequency transients, Example 8-5.
FIGURE 8-21
Simulation of the recovery voltage on interrupting a line at no load, Example 8-5.
200
8-11
CHAPTER EIGHT
INTERRUPTION OF CAPACITIVE CURRENTS
We discussed interruption of capacitor currents in Chap. 6 and 7.
The rate of rise of the recovery voltage is low, and a circuit breaker
will try to interrupt the current even at the first-current zero, when
the contact gap is small and still ionized and has not recovered
the dielectric strength. However, 1/2 cycle later, when the voltage
reaches 2.0 per unit, a reignition may occur. The shunt capacitor
being disconnected then discharges through the circuit breaker
and the amplitude of this current depends on the instantaneous
value of the capacitor charge. The high frequency of the current is
caused by the inductance between the capacitor bank and breaker.
This high-frequency current is superimposed upon the powerfrequency current and creates additional current zeros (Fig. 6-35c
and d). Some types of circuit breakers, vacuum and SF6, will operate
on these high-frequency current zeros.
Series reactors are employed to reduce the switching inrush currents of the capacitors (Chap. 6), but the discharge currents on
the capacitors can be even higher than back-to-back switching currents. Again these can be reduced by reactors. Though, the rate of
rise of the recovery voltage is low, its peak increases. The recovery
voltage depends on the capacitor bank connections as follows:
1. A three-phase grounded capacitor bank can be represented
by a single-phase circuit. The TRV across switching device
depends on the ratio of positive-sequence capacitance to zerosequence capacitance which is one for grounded banks. The
maximum-recovery voltage is 2.0 per unit.
2. An ungrounded capacitor bank has C1/C0 = infinity, and
the recovery voltage is 3.0 per unit. In Chap. 6, we discussed
the current interruption in a three-phase capacitor bank. For
overhead transmission lines, C1/C0 may be 1.5 to 2.0 per unit,
and TRV will be between 2 and 3 per unit. For grounded or
ungrounded capacitor banks, the recovery voltage profile is
given by ANSI/IEEE 1-cosine curve. The following observations are of interest with respect to interruption of capacitive
currents:
■
For grounded capacitor banks, a nonsimultaneous closing
of poles of the switching device by less than 1/4 cycle will result
in recovery voltages across any pole of no more than 2.5 per unit.
For 1/4 to 2/3 of a cycle of nonsimultaneous operation, the
recovery voltage on a pole can be as high as 3.0 to 4.0 per unit.
■
For ungrounded capacitor banks, the highest peak values
of recovery voltages, though higher than those when switching
grounded banks, are much lower than that in ungrounded banks,
regardless of the degree of nonsimultaneity between poles.
■
For a ratio of C1/C0 = 2 (for systems of 69 kV and lower),
maximum-recovery voltage in any one pole can be expected to
be 2.22 per unit, nonsimultaneity less than 1/6 cycle.
FIGURE 8-22
Prestrikes in circuit breakers.
■ For systems higher than 69 kV, C1/C0 will be less than
1.6 due to larger phase spacing, and recovery voltages with
1/6 cycle nonsimultaneity will be 2.15 per unit of the peak
recovery voltage.
8-12
PRESTRIKES IN CIRCUIT BREAKERS
A prestrike may occur on closing of a circuit breaker, establishing
the current flow before the contracts physically close. A prestrike
occurs in a current flow at a frequency given by the inductances
and capacitances of the supply circuit and the circuit being closed.
In Fig. 8-22, this high-frequency current is interrupted at t = t1.
Assuming no trapped charge on the capacitors, the voltage rises to
approximately 2 per unit. A high-frequency voltage given by source
reactance and stray capacitance is superimposed upon the recovering bus voltage. If a second prestrike occurs at t = t2, a further
escalation of the bus voltage occurs. Thus, the transient conditions
are similar as for restrikes; however, the voltage tends to decrease
as the contacts come closer in a closing operation. In Fig. 8-22, um
is the maximum system voltage, ur is the recovery voltage, and us is
the voltage across the breaker contacts.
8-13
BREAKDOWN IN GASES
The dielectric gases are (1) simple gases, for example, air, nitrogen,
helium; (2) oxide gases, for example, carbon dioxide; (3) hydrocarbon gases, for example, methane; and (4) electronegative
gases, for example, sulphur hexafluoride, SF6, and freon. If the
dielectric strength of helium is tested in a uniform electric field,
under 13.6 atm (1 atm = 101325 Pa), which is taken as unity, the
dielectric strength of nitrogen is 7.2, carbon dioxide 8, and for SF6
it is 16. The chemical stability, corrosion, dielectric loss, toxicity,
thermal conductivity, behavior under arcing, fire, and explosion
hazards are some other considerations when applied to electrical
equipment. SF6 has superior properties under effects of electrical
field and arcing.
Townsend (1900–1901) suggested that phenomena leading to
rupture of an insulating gas can be represented by:
γ [e αd − 1] = 1
(8-50)
where g is the number of charged particles formed as a result of
positive ion collision, also known as second Townsend coefficient;
a is number of charged particles formed by collision of negativecharged ions, also designated as first Townsend coefficient; and d is
the spacing of electrodes.
He studied that at low values of x/P, where x is the voltage gradient and P is the pressure of gas, the current increases as a linear
function of the gap distance:
i = i0 e α x
(8-51)
CURRENT INTERRUPTION IN AC CIRCUITS
where i0 is the current at zero plate separation; a also represents
number of new negative-charged particles created per centimeter of
path along direction of electric field, that is, slope of log (i0 /i) and
x and 1/a, thus represents average distance traveled by an electron to
produce a new ion pair. a varies in a linear relationship to pressure
up to 10 atm. For both air and nitrogen and in high-pressure range,
a decreases rapidly1 with increasing pressure and becomes negligible
at 30 atm. To account for breakdown and deviation from Pachen’s law
at high pressure, Townsend suggested that at higher values of x/P,
positive ions also ionize neutral atoms and molecules by impact.
The theory has been further modified by Loeb10 and conducting
particles can be created due to secondary liberation of electrons, photoelectric action at cathode, and field emission at contact surfaces.
The advantage of SF6 is that it is an electronegative gas. The
molecular structure of SF6 has to be studied to understand the electronegativity. SF6 is octahedral, with six fluorine atoms arranged
symmetrically around sulfur atom. The molecular shapes can be
explained in terms of mutual repulsion of covalent bonds. When
two atoms are bonded by a covalent bond, both of them share a pair
of electrons. The attraction that one of the atoms exerts on this shared
pair of electrons is termed electronegativity. Atoms with nearly filled
shells of electrons (halogens) tend to have higher electronegativity
than those with sparsely filled shells.
The electronegativity is the important characteristic in electrical
breakdown. Its ability to seize an electron and form a negative ion
is reverse of that of the ionization process. Thus, if the attachment
is equal to ionization, no breakdown is possible. The dissociation
equation of SF6 is:
SF6 → SF6+ + F −
(8-52)
The decomposition potential is 15.7 eV.
The molecular weight also plays a role. A gas of higher molecular
weight ionizes at a higher potential and exhibits a greater attachment rate. SF6 has a large collision diameter of the order of 4.77 Å.
Energy can be stored in viberational levels of SF6, forming ions of
low mobility. These ions can reduce positive space charge around
an electrode requiring a higher voltage to produce an arc across the
gap. The Townsend criterion of breakdown of an electronegative
gas can be written as:
γα (α −η )d
[e
− 1] = 1
α −η
(8-53)
where h is the attachment coefficient.
The attachment coefficient varies with v/P.
Another breakdown criterion is known as steamer criterion:11
e (α −η )d ≥ NC
(8-54)
where NC = 3.108 – 109, that is, breakdown will occur when a certain number of charge carriers in an avalanche head are exceeded.
The criterion may be extended to apply to nonuniform fields:
201
50-Hz breakdown voltage in SF6, homogeneous field,
in relation to distance between electrodes, at various pressures.
FIGURE 8-23
important for GIS, discussed in Chap. 18, where these particles can
cause a lowering of the dielectric strength and breakdown. Extreme
care is required in the field assembly of GIS.
Figures 8-23, 8-24, and 8-25 show the superior characteristics
of SF6.12 The following explanations apply:
1. Figure 8-23 shows 50-Hz breakdown voltage in SF6 homogeneous field in relation to distance between electrodes and pressure.
2. Figure 8-24a depicts heat-transfer coefficients of SF6 and
transformer oil under natural convection. Tan d, loss factor of
SF6 is low; less than 2 × 10–7 and SF6 has excellent heat transfer
characteristics. The heat absorption depends on the product of
specific heat and specific weight; while specific heat is lower
than that of air, its density is several times higher. Therefore,
as a heat-absorbing medium, SF6 is three times better than air.
Figure 8-24b compares breakdown strength of air, SF6, and
transformer oil, and Fig. 8-24c is corona onset voltage related
to pressure for air and SF6.
3. Figure 8-25a illustrates interrupting capability of air, air
and SF6 mixture, and SF6 versus pressure, and Fig. 8-25b is the
arc radius of SF6 and air versus temperature in K.
d
exp ∫ (α − η )dn ≥ NC
0
or
d
∫ [α( x ) − η( x )]dn ≥ ln NC
(8-55)
0
The breakdown characteristics in nonuniform fields will be different because ionization may be locally sustained due to regions of
high stress. This may be due to sharp corners, rough surfaces, and
semiconducting particles left during manufacture. This is especially
In ac circuit breakers, the phenomena of arc interruption are
complex. Arc plasma temperatures of the order of 25000 to 5000 K are
involved with conductivity changing billion times as fast as temperature in the critical range associated with thermal ionization.
Supersonic turbulent flow occurs in changing flow and contact
geometry at speeds from 100 to 1000 m/s in the arc. The contact
system should accelerate from a stationary condition to high speeds
in a very short duration.
With parabolic pressure distribution in the contact zone of a
double-nozzle configuration, a cylindrical arc with arc at temperatures nearing 25000 K exists. Due to low density of gas at high
temperatures, the plasma is strongly accelerated by axial pressure
202
CHAPTER EIGHT
F I G U R E 8 - 2 4 (a) Heat-transfer coefficient of SF6 and transformer oil under natural convection. (b) Breakdown strength of air, SF6, and transformer
mineral oil. (c) Corona onset voltage related to pressure for SF6 and air.
gradient. A so-called thermal arc boundary at temperature 300 to
2000 K exists. Arc downstream expands into nozzles, and in this
region, the boundary layer between arc and gas is turbulent with
the formation of vortices.
Two types of failures can occur: (1) dielectric failure which is
usually coupled with a terminal fault and (2) thermal failure which
is associated with a short-line fault. If after a current zero, RRRV is
greater than a critical value, the decaying arc channel is reestablished
by ohmic heating. This period, which is controlled by energy balance in the arc, is called the thermal interruption mode. Figure 8-26a
and b show successful thermal interruption and a thermal failure,
respectively. Within 2 ms after interruption, the voltage deviates
from TRV. It decreases and approaches arc voltage.
Following thermal mode, a hot channel exists at a temperature
from 300 to 5000 K, and the gas zone adjacent to arc diminishes at
a slow rate. Recovering system voltage distorts and sets the dielectric limits. After successful thermal interruption, if the TRV can
reach such a high-peak value that circuit breaker gap fails through,
it is called a dielectric failure mode. This is shown in Fig. 8-27a and b.
Figure 8-27a shows successful interruption, and 8-27b shows dielectric failure at the peak of the recovery voltage and rapid voltage decay.
The limit curves for circuit breakers can be plotted on log u
and log I basis, as shown in Fig. 8-28. In this figure, u is the system
voltage and I, the short-circuit current. The portion in thick lines
shows dielectric limits, while the vertical portion in thin lines
shows thermal limits. In thermal mode, (a) metal vapor production from contact surfaces, (b) di/dt, that is, the rate of decrease of
the current at current zero, (c) arc constrictions in the nozzle due
to finite velocity, (d) nozzle configurations, (e) presence of parallel
capacitors and resistors, and (f) type of quenching medium and its
pressure, are of importance. In the dielectric mode, the generation
of electrons in electric field is governed by Townsend’s equation:
dne −dne ve
=
+ (α − η ) ne ve
dt
dd
(8-56)
CURRENT INTERRUPTION IN AC CIRCUITS
203
where ne is number of electrons, ve is the electron drift velocity, and
other symbols are as described before.
SF6 breakers have an advantage as an electrical discharge causes
the gas to decompose to an extent proportional to the applied
energy. Part of the gas disintegrates in its atomic constituents:
SF6 D E ⇔ S + 6F
(8-57)
where D E is energy of the arc. When the temperature is lowered, the
reaction proceeds in the reverse direction, resulting in the reformation of SF6. The insulating properties are restored, provided there are
no secondary reactions and vaporized electrode material. Arc in SF6
has a fine core and its time constant may be expressed as:
θ = cπ r02
(8-58)
The cross section of arc decreases as the current is lowered. The
arc in SF6 is slender and well sustained even at lower currents (thus
reducing the possibility of current chopping). Advantage lies in
smaller thermal conductivity of arc core plasma for an equivalent
electrical conductivity, which means a lower energy is transferred
to the medium and a lower arc voltage is developed in the circuit.
As current goes zero, the arc becomes gradually narrow before disappearing. The time constant featuring the speed at which arc loses
its electrical conductivity is related to small volume occupied by the
plasma. Figure 8-25a shows superior arc-interrupting performance
and Fig. 8-24a shows high heat-transfer capacity and low ionization
temperature of SF6 compared to nitrogen. The time in which arc is
quenched is approximately 100 times smaller than that in air.
It is necessary to point out the decomposition products and
environmental effects. Metal fluorides such as CuF2 and sulfur fluorides such as S2F2 may be formed. These primary decomposition
products are good insulators so that the deposits on insulating surfaces do not impair operational efficiency. This is true so long as
there is no moisture. In presence of moisture, secondary products
are formed:
CuF2 + H 2O → CuO + 2HF
SF4 + H 2O → SOF2 + 2HF
SOF2 + H 2O → SO2 + 2HF
(8-59)
SO2 + 4HF → SF4 + 2H 2O
FIGURE 8-25
(a) Interrupting capacity of air, air and SF6 mixture,
and SF6. (b) Arc radius of nitrogen and SF6, and temperature.
FIGURE 8-26
Note that moisture can be produced by the arcing process itself.
HF products seriously attack materials containing silicone (glass
Thermal failure mode of a circuit breaker. (a) Successful interruption. (b) Failure in the thermal mode.
204
CHAPTER EIGHT
FIGURE 8-27
Dielectric failure mode of circuit breakers. (a) Successful interruption. (b) Failure at peak of TRV.
optimized by double motion principle; this consists of displacing
the two arcing contacts in opposite directions. This leads to further
reduction in the operating energy. In a thermal blast chamber with
arc-assisted opening, arc energy is used to generate the blast by
thermal expansion and also to accelerate the moving part of the
circuit breaker when interrupting high currents.11,13
Further descriptions of constructional features, interruptions
in other mediums, for example, current interruption in vacuum,
which has an entirely different conceptual base, are not discussed.
It is sufficient to highlight that the interruption of currents in ac
circuits is not an independent phenomenon; depending on the circuit conditions alone, it is seriously modified by the physical and
electrical properties of the interrupting mediums in circuit breakers
and the type of current being interrupted.
8-14
Limiting curves of the circuit breakers, plotted as log
u versus log I. V is the rated voltage of the breaker and I is the short-circuit
current; n indicates the number of interrupting chambers in series. Thick lines
show the dielectric mode and thin lines show the thermal mode of failures.
FIGURE 8-28
and porcelain), and lower valance fluorides of sulfur are toxic and
poisonous. In SF6 designs, the desiccators to absorb moisture are
provided, and SF6 density monitors are a standard feature, the
assemblies are highly leakproof, with leakage of the order of 10–6
or less. Special machining techniques and gaskets have been developed. A surface roughness of less than 0.8 microns is achieved.
The earlier designs of double-pressure breakers are obsolete, and
“puffer-type” designs were introduced in 1967. The gas is sealed in
the interrupting chamber at a low pressure and the contact movement itself generates a high pressure—part of the moving contact
forms a cylinder and it moves against a stationary piston, thus the
terminology puffer type—meaning blowing out the arc with a puff.
The last 20 years have seen the development of “self-blast technology” applicable to 800 kV. A valve was introduced between the
expansion and compression volume. When the interrupting current is low, the valve opens under effect of overpressure and the
interruption phenomena is similar to puffer design. At high-current
interruption, the arc energy produces a high overpressure in the
expansion volume and the valve remains closed. The overpressure
for breaking is obtained by optimal use of thermal effect and nozzle
clogging effect. The cross section of the arc significantly reduces
the exhaust of gas in the nozzle. The self-blast technology is further
STRESSES IN CIRCUIT BREAKERS
The stresses in a circuit breaker under various operating conditions
are summarized in Fig. 8-29. These stresses are shown in terms of
three parameters, current, voltage, and du/dt, in a three-dimensional
plane. Let the current stress be represented along x-axis, the du/dt
stress along y-axis, and the voltage stress along z-axis. We see that
a short-line fault (A1, A2, and A3) gives the maximum RRRV stress,
though the voltage stress is low. A terminal fault (B1, B2, B3) results
in the maximum interrupting current, while capacitor switching
(C) and out-of-phase switching (D) give the maximum voltage
stresses. All the stresses do not occur simultaneously in an interrupting process or in an electrical power system.
In this chapter, we continued the insight into current interruption and overvoltages gained in the previous chapters by addressing
the postrecovery overvoltages after disconnection of various types
of electrical circuits, modified by the circuit-breaker behavior. We
noticed that arc characteristics of circuit breakers are important
while disconnecting inductive currents, and on the other hand the
dielectric characteristics gain importance for capacitive circuits.
The recovery-voltage profiles in a number of cases, their impact on
circuit breaker ratings, and the need for careful analysis depending
on the applications are highlighted. The problems of interruption
of low levels of inductive currents, restrike, reignitions, and prestrikes in breakers are the related aspects. Also, superior properties
of SF6 as an interrupting medium, which has overtaken all other
interrupting mediums in high-voltage circuit breaker applications,
are discussed with some failure modes. Yet, this chapter is not a
guide for the application of circuit breakers where a number of
other characteristics come into consideration. It is interesting to
note that the failure rate of circuit breakers all over the world is
CURRENT INTERRUPTION IN AC CIRCUITS
FIGURE 8-29
205
Stresses in high-voltage circuit breakers in terms of short-circuit current, RRRV, and maximum overvoltage (see text).
decreasing because of better designs and applications. The failure
survey of circuit breaker control systems14 attributes most failures
to environmental effects.
PROBLEMS
1. Distinguish between reignition, restrike, prestrikes, and
current chopping in high-voltage circuit breakers.
2. What is a delay line in TRV representation by two-parameter
and four-parameter representation? Describe the parameters on
which it depends and its calculation.
3. Describe two accepted failure modes of circuit breakers.
Categorize the fault types that can lead to each of these two
modes.
4. Find the recovery voltage across the breaker contacts
while interrupting 4 A (peak) magnetizing current of 138-kV,
20-MVA transformer. Assume a capacitance of 4000 pF to
ground and an inductance of 0.25 H.
5. What is the value of a switching resistor to eliminate the
restriking transient in Prob. 4?
6. On the source side of a generator breaker, L = 1.5 mH and
C = 0.005 µF. The breaker interrupts a current of 20 kA. Find
(a) RRRV, (b) time to reach peak-recovery voltage, and (c) frequency of oscillation.
7. Explain the influence of power factor and first pole to clear
on TRV. What is the effect of frequency of TRV and load current on interrupting duty of a circuit breaker?
8. A synchronous breaker is required to control a large shunt
capacitor bank. Overvoltages can be reduced by closing the
breaker at (1) peak of the voltage or (2) at zero crossing of the
voltage. Which of the two statements is correct? Assume that
the capacitors do not have a residual charge.
9. Comment on the correctness of these statements. (1) Interrupting an asymmetrical current gives rise to higher TRV than
interrupting a symmetrical current. (2) As the current to be
interrupted reduces, so does the initial RRRV. (3) Thermal
mode of failure of breaker is excited when interrupting capacitor current due to higher TRV. (4) An oscillatory TRV occurs
for a fault on a transformer connected to a transmission line.
(5) Selecting a breaker of higher interrupting rating is an assurance that, in general, its TRV capability is better.
10. Describe a simple circuit element to control the RRRV
when interrupting a high-magnetizing current.
11. Why is the TRV of a circuit breaker higher for interruption
of short-circuit currents lower than its rated short-circuit current?
12. Compare the TRV profiles of ANSI/IEEE and IEC
standards.
13. Draw a circuit diagram for TRV, first pole to clear, for the
transformer secondary faults shown in Fig. 8-13.
14. An 18-kV, 200-MVA generator is connected through a
step-up transformer of 18 to 230 kV, and serves a load of
150 MVA on the high-voltage side of the step-up transformer.
The system runs in synchronism with the utility source. What
is the expected waveform of TRV when the generator load is
suddenly thrown off?
15. A breaker chops an inductive current of 5 A at its peak
(thus, the source-side voltage is zero). Calculate the approximate maximum overvoltage that can be generated.
206
CHAPTER EIGHT
16. Referring to Table 8-3, plot the TRV profile for a breaker
of maximum voltage of 362 kV, rated short-circuit current =
65 kA, when interrupting full short-circuit current, and when
interrupting 30 percent short-circuit current, and when interrupting 7 percent short-circuit current.
Influence of Cable Connections on TRV of System-Fed Faults,”
CIGRE, pp. 13–101, Aug. 2002.
12. J. C. Das, “SF6 in High-Voltage Outdoor Switchgear,” Proc. IE,
vol. 61, pt. EL2, pp. 1–7, Oct. 1980.
17. Plot the short-line fault profile of the TRV for the breaker
in Prob. 16 at 50 percent short-circuit current, surge impedance = 400 Ω. What is the frequency of the sawtooth wave?
13. D. Dufournet, F. Sciullo, J. Ozil, and A. Ludwig, “New Interrupting and Drive Techniques to Increase High Voltage Circuit
Breakers Performance and Reliability,” CIGRE Session 1998,
pp. 13–104.
18. Define tripping delay, opening time, arcing time, interrupting time, and contact parting time, as per ANSI/IEEE
standards. What is the arcing time of a 2-cycle breaker?
14. CIGRE WG A3.12, “Failure Survey on Circuit Breaker Controls
Systems,” Electra, no. 251, pp. 17–31, April 2007.
19. Explain the superior properties of SF6 as a dielectric
medium in HV circuit breakers, the nature of corrosive arcing
products, and the safeguards provided in the designs of the
circuit breakers.
FURTHER READING
20. Write a brief note on the development of operating mechanisms of SF6 circuit breakers.
REFERENCES
1. K. Ragaller, Current Interruption in High Voltage Networks,
Plenum Press, New York, 1978.
2. A. M. Cassie, “Arc Rupture and Circuit Theory,” CIGRE Report
no. 102, 1939.
3. ANSI Std. C37.06, AC High Voltage Circuit Breakers Rated
on Symmetrical Current Basis—Preferred Ratings and Related
Required Capabilities, 1979 and 2000.
4. IEEE Std. C37.04, IEEE Standard Rating Structure for AC
High-Voltage Circuit Breakers, 1999 (revision of 1979).
5. IEC Std. 60909-0, Short-Circuit Currents in Three-Phase AC
Systems, Calculation of Currents, 2001-07.
6. IEEE Std. C37.011, IEEE Application Guide for Transient
Recovery Voltage for AC High Voltage Circuit Breakers, 2005.
7. IEEE PC37.06, Draft: Standard AC High Voltage Circuit Breakers Rated on Symmetrical Current Basis—Preferred Ratings and
Related Required Capabilities for Voltages above 1000 Volts,
2008.
8. ANSI C37.06.1, Guide for High Voltage Circuit Breakers Rated
on a Symmetrical Current Basis Designated, Definite Purpose
for Fast Transient Recovery Voltage Rise Times, 2000.
9. IEC Std. 62271-100, High Voltage Alternating Current Circuit
Breakers, 2001.
10. L. B. Loeb, Fundamental Processes of Electrical Breakdown in
Gases, John Wiley, New York, 1975.
11. D. Dufournet, “Generator Circuit Breakers: SF6 Breaking
Chamber-Interruption of Current with Non-Zero Passage.
A. Braun, A. Eidinger, and E. Rouss, “Interruption of Short-Circuit
Currents in High-Voltage AC Networks,” Brown Boveri Review,
vol. 66, pp. 240–245, April 1979.
CIGRE Working Group 13-02, “Switching Overvoltages in EHV
and UHV Systems with Special Reference to Closing and Reclosing
Transmission Lines,” Electra, vol. 30, pp. 70–122, Oct. 1973.
J. C. Das, Power System Analysis, Chapter 5, Marcel Dekker,
New York, 2002.
A. Greenwood, Electrical Transients in Power Systems, Wiley Interscience, New York, 1991.
W. Hermann and K. Ragaller, “Theoretical Description of Current
Interruption in Gas Blast Circuit Breakers,” IEEE Trans. PAS, vol. 96,
pp. 1546–1555, 1977.
W. Hermann, K. Ragelschatz, L. Niemeyer, K. Ragaller, and E.
Schade, “Investigations on Physical Phenomena Around Current
Zero in HV Gas Blast Circuit Breakers,” IEEE Trans. PAS, vol. 95,
no. 4, pp. 1165–1178, 1976.
IEEE Std. C37.09, IEEE Test Procedure for AC High Voltage Circuit
Breakers Rated on a Symmetrical Current Basis 1999 (R2007).
J. Kopainsky and E. Ruoss, “Interruption of Low Inductive and
Capacitive Currents in High Voltage Systems,” BBC Review, vol. 66,
pp. 255–261, 1979.
NEMA SG-4, Alternating Current High Voltage Circuit Breakers,
1995.
L. V. D. Sluis and A. L. J. Jansen, “Clearing Faults Near Shunt Capacitor
Banks,” IEEE Trans. PD, vol. 5, no. 3, pp. 1346–1354, July 1990.
B. W. Swanson, “Theoretical Models for the Arc in Current Zero
Regimes” in Current Interruption in High Voltages Networks, Plenum
Press, New York, 1978.
H. Toda, Y. Ozaki, and I. Miwa, “Development of 800 kV Gas
Insulated Switchgear,” IEEE Trans. PD, vol. 7, no. 1, pp. 316–322,
Jan. 1992.
C. L. Wagner and H. M. Smith, “Analysis of Transient Recovery Voltage Rating Concepts,” IEEE Trans. PAS, vol. 103, pp. 3354–3364,
1984.
CHAPTER 9
SYMMETRICAL AND
UNSYMMETRICAL
SHORT-CIRCUIT
CURRENTS
Short circuits in power systems cause decaying current transients,
generally much above the load currents. The synchronous generators are the major source of short-circuit currents and we will
discuss short-circuit of a synchronous generator in Chap. 10. The
other sources of short-circuit currents in the power systems are:
■
Asynchronous generators and motors.
■
Synchronous motors.
■
According to IEC standards the static converters in rolling mills
contribute to the initial symmetrical short-circuit current and peak
current (ANSI/IEEE close and latch current, expressed in peak
kiloamperes), but not to the breaking (interrupting) current; exception is when the rotational masses of the motors and static equipment provide reverse transfer of energy for deceleration (a transient
inverter operation). Hitherto ANSI/IEEE standards ignore any contributions to the short-circuit currents contributed by drive systems
fed through static converters. The nonrotating loads and capacitors
in parallel or series do not contribute to the short-circuit currents.
There are many facets of the short-circuit studies and calculations, for example, the switching devices should be able to carry
and interrupt the short-circuit currents, and the equipments should
be designed to have adequate short-circuit withstand capabilities
according to relevant standards. With respect to transient analysis,
the stability of interconnected systems to remain in synchronism
until the faulty section of the system is isolated is important.
We discussed short circuit of a simple RL circuit in Chap. 2,
origin of the dc component, its decay, and asymmetrical nature of
the short-circuit currents. We also alluded to the fact that the reactances of a generator from the instant of short circuit until steady
state are not constant and vary over a period of short time giving
rise to ac decay. The ac decay will vary based on how far removed
from the generator the fault is and on the intervening impedance between the generator and the fault point. The short-circuit
currents of induction and synchronous motors are also decaying
transients.
Rarely a simulation of short-circuit current in time domain is
undertaken. The short-circuit currents for rating the switching
devices are calculated using empirical methods according to prevalent standards.1–3 The dynamic simulation, even for a relatively
small power system, demands extensive system modeling and computing resources. Though such a study, for example, using EMTP,
can validate the results obtained from an empirical calculation.
We will not get into details of the empirical short-circuit calculations, which have the primary objective of properly selecting the ratings
of switching devices and providing input to the protective relaying.
9-1
SYMMETRICAL AND UNSYMMETRICAL FAULTS
In a three-phase system when all the phases are equally involved, it
is a symmetrical fault. The term bolted fault is in common use and
it implies that the three phases are connected together with links of
zero impedance, that is, the fault current is only limited by the system and the machine impedances and the resistance to fault is zero.
Bolted three-phase faults are rather uncommon. These generally
(not always) give the maximum short-circuit currents in the system
and form the basis of short-circuit ratings of the equipment.
Faults involving one phase, or more than one phase, and ground
are called unsymmetrical faults. Under certain conditions a single line-toground or double line-to-ground fault current can exceed the threephase symmetrical fault current. Unsymmetrical faults are more
common as compared to three-phase symmetrical faults. The most
common type is a line-to-ground fault. Approximately 70 percent of
the faults in power systems are single line-to-ground faults.
The magnitude of fault currents in a system is related to the
relative values of positive, negative, and zero sequence impedances
as seen from the fault point. This is shown in Fig. 9-1.2 To study
unsymmetrical fault currents a basic knowledge of symmetrical
component theory and matrices is required.4–9 The section below
provides basic concepts of the symmetrical component theory.
207
208
CHAPTER NINE
numbers each having n components, that is, a total of n2 components. Fortescue demonstrated that an unbalanced set on n phasors
can be resolved into n–1 balanced phase systems of different phase
sequence and one zero sequence system, in which all phasors are of
equal magnitude and cophasial:
Va = Va1 + Va 2 + Va 3 + + Van
Vb = Vb1 + Vb2 + Vb 3 + + Vbn
(9-1)
Vn = Vn1 + Vn 2 + Vn 3 + + Vnn
FIGURE 9-1
Magnitude of short-circuit currents depending upon
the sequence impedances. k 1: single phase-to-ground; k 2: phase-to-phase,
k 2E: double phase-to-ground, k 3: three-phase fault currents. For Z1/Z2 ≤ 0.5,
Z2/Z0 ≤ 0.65, single line-to-ground current is the maximum.2
where Va, Vb, . . ., Vn are original n unbalanced voltage phasors. Va1,
Vb1, . . ., Vn1 are the first set of n balanced phasors, at an angle of 2p/n
between them. Va2, Vb2, . . ., Vn2 are the second set of n balanced phasors at an angle 4p/n. And the final set Van, Vbn, . . ., Vnn is the zero
sequence set, all phasors at n(2p/n) = 2p, that is, cophasial.
In a symmetrical three-phase balanced system, the generators
produce balanced voltages which are displaced from each other by
2p/3 = 120°. These voltages can be called positive sequence voltages. If a vector operator a is defined which rotates a unit vector
through 120° in a counterclockwise direction, then a = –0.5 +
j0.866, a2 = –0.5 – j0.866, a3 = 1, 1 + a2 + a = 0. Considering a
three-phase system, Eq. (9-1) reduces to:
Va = Va 0 + Va1 + Va 2
(9-2)
Vb = Vb0 + Vb1 + Vb2
9-2
SYMMETRICAL COMPONENTS
The method of symmetrical components was originally presented
by C.L. Fortescue in 191810 and has been popular ever since—it
provided new dimensions to the electrical system modeling. It has
been widely used in the analysis of unbalanced three-phase systems, unsymmetrical short-circuit currents, and rotating electrodynamic machinery.
Unbalance occurs in three-phase power systems due to faults,
single-phase loads, untransposed transmission lines, or nonequilateral conductor spacing. In a three-phase balanced system, it is
sufficient to determine the currents and voltages in one phase,
and the currents and voltages in the other two phases are simply
phase displaced. In an unbalanced system the simplicity of modeling a three-phase system as a single-phase system is not valid.
A convenient way of analyzing unbalanced operation is through
symmetrical components. Even the so-called balanced systems
are not perfectly balanced. The three-phase voltages and currents, which may be unbalanced are transformed into three sets
of balanced voltages and currents, called symmetrical components.
The impedances presented by various power system components, that is, transformers, generators, transmission lines are
decoupled from each other, resulting in independent networks for
each component. These form a balanced set. This results in simplicity of calculations.
The basic theory of symmetrical components can be stated as a
mathematical concept. A system of three coplanar vectors is completely defined by six parameters; the system can be said to possess
six degrees of freedom. A point in a straight line being constrained
to lie on the line possesses but one degree of freedom, and by the
same analogy, a point in space has three degrees of freedom. A
coplanar vector is defined by its terminal and length and therefore possesses two degrees of freedom. A system of coplanar vectors having six degrees of freedom, that is, three-phase unbalanced
current or voltage vectors, can be represented by three symmetrical
systems of vectors each having two degrees of freedom. In general,
a system of n numbers can be resolved into n sets of component
Vc = Vc0 + Vc1 + Vc2
We can define the set consisting of Va0, Vb0, and Vc0 as the zero
sequence set, the set Va1, Vb1, and Vc1, as the positive sequence set,
and the set Va2, Vb2, and Vc2 as the negative sequence set of voltages.
The three original unbalanced voltage vectors give rise to nine voltage vectors, which must have constraints of freedom and are not
totally independent. By definition of positive sequence, Va1, Vb1, and
Vc1 should be related as follows, as in a normal balanced system:
Vb1 = a2Va1, Vc1 = aVa1.
Note that Va1 phasor is taken as the reference vector. The negative sequence set can be similarly defined, but of opposite phase
sequence:
Vb2 = aVa2, Vc2 = a2Va2 .
Also Va0 = Vb0 = Vc0. With these relations defined, Eq. (9-2) can be
written as:
1
Va
Vb = 1
Vc
1
1
a2
a
1
a
a2
Va 0
Va1
Va 2
(9-3)
or in the abbreviated form:
Vabc = TsV012
(9-4)
where the matrix Ts is the transformation matrix. Its inverse will
give the reverse transformation:
V012 = Ts−1Vabc
(9-5)
Similar expressions apply for currents. The matrix
Ts−1 =
1 1 1
1 a
3
1 a2
1
a2
a
Ts−1
is:
(9-6)
SYMMETRICAL AND UNSYMMETRICAL SHORT-CIRCUIT CURRENTS
The impedance transformation is given by:
Zabc = Ts Z012Ts−1
lagging the component of phase a, and component of phase b
leading the component of phase a.
(9-7)
Z012 = Ts−1ZabcTs
While this simple explanation may be adequate, a better insight into
the symmetrical component theory can be gained through matrix
concepts of similarity transformation, diagonalization, eigenvalues,
and eigenvectors. It can be shown that:
■
Eigenvectors giving rise to symmetrical component transformation are the same though the eigenvalues differ. Thus,
these vectors are not unique.
■
The Clarke component transformation (Chap. 4) is based
upon the same eigenvectors, but different eigenvalues.11
■
The symmetrical component transformation does not
uncouple an initially unbalanced three-phase system. Prima
facie, this is a contradiction of what we said earlier, that the
main advantage of symmetrical components lies in decoupling unbalanced systems, which could then be represented
much akin to three-phase balanced systems (see App. D,
where the application to a three-phase system with unequal
phase impedances shows that decoupling is not possible). In
application for the fault analysis it is assumed that the system
was perfectly symmetrical prior to the fault, and asymmetry
occurs only at the fault point. In other words the unbalance
part of the network is connected to a balanced system at the
point of fault.
9-2-1
Characteristics of Symmetrical Components
Matrix equations [Eqs. (9-4) and (9-5)] are written in the expanded
form:
Va = V0 + V1 + V2
Vb = V0 + a 2V1 + aV2
(9-8)
Vc = V0 + aV1 + a V2
2
and
1
V0 = (Va + Vb + Vc )
3
1
V1 = (Va + aVb + a 2Vc )
3
209
(9-9)
1
V2 = (Va + a 2Vb + aVc )
3
V0, V1, and V2 are defined as follows:
■ V0 is the zero sequence voltage. It is of equal magnitude in
all the three-phases and is cophasial.
■ V1 is the system of balanced positive sequence voltages, of
the same phase sequence as the original unbalanced system of
voltages. It is of equal magnitude in each phase, but displaced
by 120°, component of phase b lagging the component of
phase a by 120° and component of phase c leading the component of phase a by 120°.
■ V2 is the system of balanced negative sequence voltages. It
is of equal magnitude in each phase, and there is 120° phase
displacement between the voltages, the component of phase c
Therefore, the positive and negative sequence voltages (or
currents) can be defined as the order in which the three-phases
attain a maximum value. For positive sequence, the order is “abca,”
while for the negative sequence, it is “acba.” We can also define
positive and negative sequence by the order in which the phasors pass a fixed point on the vector plot. Note that the rotation
is counterclockwise for all three sets of sequence components, as
was assumed for the original unbalanced vectors (Fig. 9-2). Sometimes, this is confused and negative sequence rotation is said to
be reverse of positive sequence. The negative sequence vectors do
not rotate in a direction opposite to the positive sequence vectors,
though the negative phase sequence is opposite to the positive
phase sequence.
In a symmetrical system of three phases, the resolution of voltages or currents into a system of zero, positive, and negative components is equivalent to three separate systems. Sequence voltages
act in isolation and produce zero, positive, and negative sequence
currents and the theorem of superposition applies. The following
generalizations of symmetrical components can be made:
1. In a three-phase unfaulted system in which all the loads are
balanced and generators produce positive sequence
voltages, only positive sequence currents flow, resulting in
balanced voltage drops of the same sequence. There are no
negative sequence or zero sequence voltage drops.
2. In symmetrical systems, the currents and voltages of
different sequences do not affect each other, that is, positive
sequence currents produce only positive sequence voltage
drops. By the same analogy, the negative sequence currents
produce only negative sequence drops, and zero sequence
currents produce only zero sequence drops.
3. Negative and zero sequence currents are set up in
circuits of unbalanced impedances only, that is, a set of
unbalanced impedances in a symmetrical system may be
regarded as a source of negative and zero sequence current.
Positive sequence currents flowing in an unbalanced system
produce positive, negative, and possibly zero sequence voltage
drops. The negative sequence currents flowing in an unbalanced
system produce voltage drops of all three sequences. The same
is true about zero sequence currents.
4. In a three-phase three-wire system, no zero sequence currents appear in the line conductors. This is so because
I0 = (1/3) (Ia + Ib + Ic), and therefore there is no path for the
zero sequence current to flow. In a three-phase four-wire system
with a neutral return, the neutral carries out of the balance
current, that is, In = (Ia + Ib + Ic). Therefore, it follows that In = 3I0.
At the grounded neutral of three-phase wye system, positive
and negative sequence voltages are zero. The neutral voltage is
equal to the zero sequence voltage or product of zero sequence
current and three times the neutral impedance, Zn.
5. From what has been said in point 4 above, phase
conductors emanating from ungrounded wye- or deltaconnected transformer windings cannot have zero sequence
current. In a delta winding, zero sequence currents, if
present, set up circulating currents in the delta windings
itself. This is because the delta winding forms a closed
path of low impedance for the zero sequence currents; each
phase zero sequence voltage is absorbed by its own phase
voltage drop and there are no zero sequence components at
the terminals.
210
CHAPTER NINE
FIGURE 9-2
9-2-2
Symmetrical component transformations.
Power Invariance
The symmetrical component transformation is power invariant.
The power is:
S = Va I a* + VbI b* + Vc I c*
(9-10)
where I a* is conjugate of Ia. This can be shown to be equal to:
S = 3(V1I1* + V2I 2* + V0I 0* )
(9-11)
9-3 SEQUENCE IMPEDANCE
OF NETWORK COMPONENTS
The impedance encountered by the symmetrical components
depends upon the type of power system equipment, that is, a generator, a transformer, or a transmission line. The sequence impedances are required for component modeling and analysis. Zero
sequence impedance of overhead lines depends upon presence of
the ground wires, tower footing resistance, and the grounding. It
may vary between two and six times the positive sequence impedance. The line capacitance of overhead lines is ignored in shortcircuit calculations. Appendix D details three-phase matrix models
of transmission lines, bundle conductors, and cables and their transformation to symmetrical components. While estimating sequence
impedances of power system components is one problem, constructing the zero, positive, and negative sequence impedance networks is
the first step for unsymmetrical fault current calculations.
9-3-1 Construction of Sequence Networks
A sequence network shows how the sequence currents will flow
in a system, if these are present. Connections between sequence
component networks are necessary to achieve this objective. The
sequence networks are constructed as viewed from the fault point,
which can be defined as the point at which the unbalance occurs in
a system, that is, a fault or load unbalance.
The voltages for the sequence networks are taken as line-toneutral voltages. The only active network containing the voltage
source is the positive sequence network. Phase a voltage is taken as
the reference voltage and the voltages of the other two phases are
expressed with reference to phase a voltage.
The sequence networks for positive, negative, and zero sequence
will have per phase impedance values which may differ. Normally,
the sequence impedance networks are constructed based upon per
unit values on a common MVA base, and a base MVA of 100 is
in common use. For nonrotating equipment like transformers, the
impedance to negative sequence currents will be the same as for
positive sequence currents. The impedance to negative sequence
currents of rotating equipment will be different from the positive
sequence impedance and, in general, for all apparatuses, the impedance to zero sequence currents will be different from the positive
or negative sequence impedances. For a study involving sequence
components, the sequence impedance data can be:
1. Calculated by using subroutine computer programs
2. Obtained from manufacturer’s data
3. Calculated by long-hand calculations or
4. Estimated from tables in published references
The positive directions of current flow in each sequence network are outward at the faulted or unbalance point. This means
that the sequence currents flow in the same direction in all three
sequence networks.
SYMMETRICAL AND UNSYMMETRICAL SHORT-CIRCUIT CURRENTS
FIGURE 9-3
Representation of positive, negative, and zero sequence networks.
Sequence networks are shown schematically in boxes in which
the fault points from which the sequence currents flow outward
are marked as F1, F2, and F0 and the neutral buses are designated
as N1, N2, and N0, respectively, for the positive, negative, and zero
sequence impedance networks. Each network forms a two-port
network with Thévenin sequence voltages across sequence impedances. Figure 9-3 illustrates this basic formation. Note the direction of currents. The voltage across the sequence impedance rises
from N to F. As stated before, only the positive sequence network
has a voltage source, which is the Thévenin equivalent. With this
convention, appropriate signs must be allocated to the sequence
voltages:
Z0
0
V0
V1 = Va − 0
0
0
V2
0
Z1
0
0
0
Z2
I0
I1
I2
(9-12)
Based on the discussions so far, we can graphically represent
the sequence impedances of various system configurations, though
some practice is required. This will be illustrated by construction of
sequence impedances for unsymmetrical faults.
9-3-2
211
that is, if the fault does not exist, and V1, V2, and V0 are the corresponding sequence component voltages. Similarly, Ia, Ib, and Ic are
the line currents, and I1, I2, and I0 are their sequence components.
A fault impedance of Zf is assumed in every case. For a bolted
fault, Zf = 0
9-4-1
Zero Sequence Impedance of Transformers
The positive and negative sequence impedances of a transformer
can be taken equal to its leakage impedance. As the transformer is a
static device, the positive or negative sequence impedances do not
change with phase sequence of balanced applied voltages. The zero
sequence impedance can, however, vary from an open circuit to a
low value, depending upon the transformer winding connection,
method of neutral grounding, and transformer construction, that
is, core or shell type. Figure 9-4 shows the sequence impedances of
two-winding transformers, and Figure 9-5 for three-winding transformers of various winding arrangements and grounding.
9-4 FAULT ANALYSIS USING
SYMMETRICAL COMPONENTS
While applying the symmetrical component method to fault
analysis, we will ignore the load currents. This makes the positive
sequence voltages of all the generators in the system identical and
equal to prefault voltage.
In the analysis to follow, Z1, Z2, and Z0 are the positive, negative,
and zero sequence impedances as seen from the fault point. Va, Vb,
Vc are the phase-to-ground voltages at the fault point, prior to fault,
Line-To-Ground Fault
Figure 9-6a shows that phase a of a three-phase system goes to
ground through an impedance Zf . The flow of ground fault current
depends upon the method of system grounding. A solidly grounded
system with zero ground resistance is assumed. There will be some
impedance to flow of the fault current in the form of impedance
of the return ground conductor or the grounding grid resistance.
A ground resistance can be added in series with the fault impedance Zf. The ground fault current must have a return path through
the grounded neutrals of generators or transformers. If there is no
return path for the ground current, Z0 = ∞, and the ground fault
current is zero. This is an obvious conclusion.
Phase a is faulted in Fig. 9-6a. As the load current is neglected,
currents in phases b and c are zero, and the voltage at the fault
point Va = Ia Zf. The sequence components of the currents are given
by:
1 1
I0
1
1 a
I1 =
3
I2
1 a2
1
a2
a
I
Ia
1 a
I
0 =
3 a
0
Ia
(9-13)
Therefore:
I 0 = I1 = I 2 =
1
I
3 a
(9-14)
and
3I 0 Z f = V0 + V1 + V2 = −I 0 Z0 + (Va − I1Z1 ) − I 2 Z2
(9-15)
which gives:
I0 =
Va
Z0 + Z1 + Z2 + 3Z f
(9-16)
The fault current Ia is:
I a = 3I 0 =
3Va
Z0 + Z1 + Z2 + 3Z f
(9-17)
212
CHAPTER NINE
FIGURE 9-4
Positive, negative, and zero sequence circuits of two-winding transformers. Connections 8 and 9 are for core type transformers and
connections 7 and 10 are for shell type transformers.
SYMMETRICAL AND UNSYMMETRICAL SHORT-CIRCUIT CURRENTS
FIGURE 9-5
Positive, negative, and zero sequence circuits of three-winding transformers.
This shows that the equivalent fault circuit using sequence
impedances can be constructed as shown in Fig. 9-6b. In terms of
sequence impedances network blocks, the connections are shown
in Fig. 9-6c. Voltage of phase b to ground under fault conditions is:
3a 2 Z f + Z2 (a 2 − a ) + Z0 (a 2 − 1)
(9-18)
( Z1 + Z2 + Z0 )+ 3Z f
Similarly, the voltage of phase c can be calculated. An expression
for the ground fault current for use in grounding grid designs and
system grounding is as follows:
3Va
Ia =
(R 0 + R1 + R 2 + 3R f + 3RG ) + j( X 0 + X1 + X 2 )
where Rf is the fault resistance, and RG is the resistance of the grounding grid. R0, R1, and R2 are the sequence resistances and X0, X1, and
X2 are sequence reactances.
9-4-2
Vb = a 2V1 + aV2 + V0
= Va
213
(9-19)
Line-To-Line Fault
Figure 9-7a shows a line-to-line fault. A short circuit occurs
between phases b and c, through a fault impedance Zf. The fault
current circulates between phases b and c, flowing back to source
through phase b and returning through phase c. Ia = 0 and Ib = – Ic .
The sequence components of the currents are:
I0
1 1 1
1
I1 =
1 a a2
3
I2
1 a2 a
0
0
−I c = 1 −a + a 2
3
Ic
−a 2 + a
(9-20)
214
CHAPTER NINE
FIGURE 9-6
(a) Single line-to-ground fault. (b) Line-to-ground fault equivalent circuit connections. (c) Connections of sequence networks.
FIGURE 9-7
(a) Line-to-line fault. (b) Line-to-line fault equivalent circuit connections. (c) Connections of sequence networks.
SYMMETRICAL AND UNSYMMETRICAL SHORT-CIRCUIT CURRENTS
From Eq. (9-20), I0 = 0 and I1 = –I2. Therefore:
Vb − Vc = 0 1 − 1
Va
Vb = 0 1 − 1
Vc
= 0 a2 − a a − a2
1 1
1 a
1 a2
V0
V1
V2
This gives the equivalent circuits of Fig. 9-8b and c. The fault current is:
1
a2
a
V0
V1
V2
I1 =
Va
Z1 +[Z2 || ( Z0 + 3Z f )]
=
Z1 +
(9-21)
9-4-4
This gives:
Vb − Vc = (a 2 − a )(V1 − V2 )
(9-22)
= (a 2I1 + aI 2 )Z f
= (a − a )I1Z f
2
(9-30)
Va
Z 2 ( Z 0 + 3Z f )
Z 2 + Z 0 + 3Z f
Three-Phase Fault
The three phases are short circuited through equal fault impedances Zf (Fig. 9-9a.) The vector sum of fault currents is zero, as a
symmetrical fault is considered, and there is no path to ground:
Ia + Ib + Ic = 0
(9-31)
I0 = 0
As the fault is symmetrical:
Therefore:
(V1 − V2 ) = I1Z f
(9-23)
The equivalent circuits are shown in Fig. 9-7b and c. Also:
I b = (a 2 − a )I1 = − j 3I1
(9-24)
and:
Va
Vb
Vc
=
Zf
0
0
0
Zf
0
0
0
Zf
Va
I1 =
Z1 + Z2 + Z f
(9-25)
Ia
Ib
Ic
(9-32)
The sequence voltages are given by:
V0
= Ts−1
V1
V2
Zf
0
0
0
Zf
0
0
0 Ts I1
I2
Zf
I0
=
Zf
0
0
I0
0
Zf
0
0
0
Zf
I1
I2
(9-33)
The fault current is:
I b = −I c =
9-4-3
215
This gives equivalent circuits of Fig. 9-9b and c.
− j 3Va
Z1 + Z2 + Z f
(9-26)
Double Line-To-Ground Fault
(9-27)
Thus:
1 1 1
V0
1
1 a a2
V1 =
3
V2
1 a2 a
Va + 2Vb
Va
1
Vb =
Va + (a + a 2 )Vb
3
Vc
Va + (a + a 2 )Vb
(9-28)
which gives V1 = V2 and
1
V0 = (Va + 2Vb )
3
1
= [(V0 + V1 + V2 ) + 2(I b + I c )Z f ]
3
1
= [(V0 + 2V1 ) + 2(3I 0 )Z f ]
3
= V1 + 3Z f I 0
I b = a I1
2
A double line-to-ground fault is shown in Fig. 9-8a. Phases b and c
go to ground through a fault impedance Zf. Current in ungrounded
phase is zero, that is, Ia = 0. Therefore, I1 + I2 + I0 = 0.
So
Vb = Vc = (I b + I c )Z f
I a = I1 =
(9-29)
Va
Z1 + Z f
(9-34)
I c = aI1
Example 9-1 The calculations using symmetrical components
can best be illustrated with an example. Consider a subtransmission
system as shown in Fig. 9-10. A 13.8-kV generator G1 voltage is
stepped up to 138 kV. At the consumer end, the voltage is stepped
down to 13.8 kV and generator G2 operates in synchronism with the
supply system. Bus B has a 10000 hp motor load. A line-to-ground
fault occurs at bus B. It is required to calculate the fault current
distribution throughout the system and also the fault voltages. The
resistance of the system components is ignored in the calculations.
Impedance Data The reactance data of the system components
is shown in Table 9-1, and all resistances are ignored for simplicity
of calculations. Generators G1 and G2 are shown solidly grounded,
which will not be the case in a practical installation. A high impedance grounding system is used by utilities for grounding generators in
step-up transformer configurations. Generators in industrial facilities,
directly connected to the load buses are low resistance grounded, and
the ground fault currents are limited to 200–400 A. The simplifying
assumptions in the example are not applicable to a practical installation, but clearly illustrate the procedure of calculations.
First step is to examine the given reactance data. Generatorsaturated subtransient reactance is used in the short-circuit calculations and this is termed positive sequence reactance. A 138-kV
transmission line reactance is calculated from the given data of conductor size and equivalent conductor spacing. The zero sequence
216
CHAPTER NINE
FIGURE 9-8
(a) Double line-to-ground fault. (b) Double line-to-ground fault equivalent circuit connections. (c) Connections of sequence networks.
SYMMETRICAL AND UNSYMMETRICAL SHORT-CIRCUIT CURRENTS
217
FIGURE 9-10
A power system for calculations of single line-toground fault for Example 9-1.
FIGURE 9-9
(a) Three-phase fault. (b) Three-phase fault equivalent
circuit connections. (c) Connections of sequence networks.
reactance of the transmission line cannot be completely calculated
from the given data and is estimated based upon certain assumptions, that is, a soil resistivity of 100 Ω-m.
Compiling the impedance data of the system under study from
the given parameters, from manufacturers’ data or by calculation
and estimation, can be time consuming. Most computer-based
analysis programs have extensive data libraries and companion
programs for calculation of system impedance data and line constants, which have partially removed the onerous task of generating the data from step-by-step analytical calculations. Appendix D
TA B L E 9 - 1
EQUIPMENT
provides models of line constants of coupled transmission lines,
bundle conductors, and line capacitances.
Next, the impedance data is converted to a common MVA base. The
voltage transformation ratio of transformer T2 is 138 to 13.2 kV, while
a bus voltage of 13.8 kV is specified, which should be considered in
transforming impedance data on a common MVA base. Table 9-1 shows
raw impedance data and its conversion to sequence impedances.
For a single line-to-ground fault at bus B, the sequence impedance network connections are shown in Fig. 9-11, with reactance
data of components clearly marked. This figure is based upon the
fault equivalent circuit shown in Fig. 9-6b, with fault impedance
Zf = 0. The calculation is carried out in per unit, and the units are
not stated in every step of calculation.
The positive sequence reactance to the fault point is:
j0 . 37 × j1 . 67
j(0 . 37 + 1 . 6 7 )
Z1 =
j0 . 37 × j1 . 67
j(0 . 25 + 0 . 18 + 0 . 04 + 0 . 24 ) +
j(0 . 37 + j1 . 6 7 )
= j0 . 212
j(0 . 25 + 0 . 18 + 0 . 04 + 0 . 24 ) ×
Impedance Data for Example 9-1
DESCRIPTION
IMPEDANCE DATA
PU IMPEDANCE 100-MVA BASE
G1
13.8-kV, 60-MVA, 0.85 power factor generator
Subtransient reactance = 15%
Transient reactance = 20%
Zero sequence reactance = 8%
Negative sequence reactance = 16.8%
X1 = 0.25
X2 = 0.28
X0 = 0.133
T1
13.8–138 kV step-up transformer, 50/84 MVA,
delta-wye connected, wye neutral solidly
grounded
Z = 9% on 50-MVA base
X1 = X2 = X0 = 0.18
L1
Transmission line, 5 mi long, 266.8 KCMIL, ACSR
Conductors at 15 ft (4.57 m) equivalent spacing
X1 = X2 = 0.04
X0 = 0.15
T2
138–13.2 kV, 30-MVA step-down transformer,
wye-delta connected, high-voltage wye neutral
solidly grounded
Z = 8%
X1 = X2 = X0 = 0.24
G2
13.8-kV, 30-MVA, 0.85 power factor generator
Subtransient reactance = 11%
Transient reactance = 15%
Zero sequence reactance = 6%
Negative sequence reactance = 16.5%
X1 = 0.37
X2 = 0.55
X0 = 0.20
M
10000-hp induction motor load
Locked rotor reactance = 16.7% on motor base kVA
(consider 1 hp, 1 kVA)
X1 = 1.67
X2 = 1.80
X0 = ∞
218
CHAPTER NINE
FIGURE 9-11
Circuit connections for single line-to-ground fault.
Z2 can be similarly calculated to the fault point and this gives X2 =
j0.266 and Z0 = j0.2. Therefore:
I1 =
E
= − j1 . 475 pu
Z1 + Z2 + Z0
I1 = I2 = I0 = –j1.475,
Ia = –j4.425
As a base of 100 MVA is selected at 13.8 kV, 1 pu = 4.184 kA.
Therefore, the single-phase line-to-ground fault current is 18.51 kA.
The three-phase bolted fault current is given by the positive
sequence reactance alone = j4.717 pu = 19.73 kA. Fault currents in
phases b and c are zero:
Ib = Ic = 0
The sequence voltage to the fault point can therefore be calculated by:
V0 = −I 0 Z0 = − 0 . 295
V2 = −I 2 Z2 = − 0 . 392
V1 = E − I1Z1 = I1( Z0 + Z2 )
= 1 − (− j1 . 475 × j0 . 212) = 0 . 687 pu
The results can be checked. At the fault point Va = 0:
Va = V0 + V1 + V2 = 0
SYMMETRICAL AND UNSYMMETRICAL SHORT-CIRCUIT CURRENTS
The voltages of phases b and c at the fault point can be calculated as:
Vb = V0 + aV1 + a 2V2 = − 0 . 4425 − j0 . 9344
Vb = 1 . 034 pu
Vc = V0 − 0 . 5(V1 + V2 ) + j0 . 866(V1 − V2 )
219
Currents in Motor M The zero sequence current in the motor
is zero. In the United States the wye winding point of the motors is
not grounded, irrespective of the size of the motor, thus:
I a (M ) = I1(M ) + I 2 (M )
= − j0 . 1875 − j0 . 2191
= − 0 . 4425 + j0 . 9344
= − j0 . 4066 = 0 . 40
0 66 pu
Vc = 1 . 0 3 4 pu
I b (M ) = − 0 . 5(− j0 . 4066) − j0 . 866(0 . 0316)
Calculations of Current Flows The distribution of the
sequence currents in the network is calculated from the known
sequence impedances. The positive sequence current contributed
from the right side of the fault, that is, by G2 and motor M is:
j(0 . 25 + 0 . 18 + 0 . 04 + 0 . 24 )
− j1 . 475
j0 . 37 × j1 . 67
j(0 . 25 + 0 . 18 + 0 . 04 + 0 . 24 ) +
j(0 . 37 + 1 . 67 )
This gives –j1.0338. This current is composed of two components:
one from the generator G2 and the other from the motor M. The
generator component is:
j1 . 67
= − j0 . 8463
(− j1 . 0388)
j(0 . 37 + 1 . 67 )
The motor component is similarly calculated and is equal to
–j0.1875. The positive sequence current from the left side of bus B is:
− j1 . 475
j0 . 37 × j1 . 67
j(0 . 37 + 1 . 67 )
j0 . 37 × j1 . 67
j(0 . 25 + 0 . 18 + 0 . 04 + 0 . 24 ) +
j(0 . 37 + 1 . 67 )
This gives –j0.441. The currents from the right side and the left
side should sum to –j1.475. This checks the calculation accuracy.
The negative sequence currents are calculated likewise and are as
follows:
In generator G2
In motor M
From left side, bus B
From right side
= –j0.7172
= –j0.2191
= –j0.5387
= –j0.9363
= 0 . 0274 + j0 . 20
0 33
I c (M ) = − 0 . 0274 + j0 . 2033
I b (M ) = I c (M ) = 0 . 2051 pu
The summation of the line currents in the motor M and generator
G2 are:
I a (G2 ) + I a (M ) = − j3 . 4451
I b (G2 ) + I b (M ) = − 0 . 084 − j0 . 490
I c (G2 ) + I c (M ) = 0 . 084 − j0 . 490
Currents from the left side of the bus B are:
I a = − j0 . 441 − j0 . 5387 = − j0 . 98
I b = − 0 . 5(− j0 . 441 − j0 . 538 7 )
− j0 . 866(− j0 . 441 + j0 . 5387 ) = 0 . 084 + j0 . 490
I c = − 0 . 0 8 4 + j0 . 490
These results are consistent as the sum of currents in phases b
and c at the fault point from the right and left side is zero, and the
summation of phase a currents gives the total ground fault current
at b = –j4.425. The distribution of the currents is shown in threeline diagram, Fig. 9-13
Continuing with the example, the calculations of currents and
voltages in the transformer T2 windings must consider the phase
shifts introduced in the primary and secondary vectors. We will not
get into the phase shifts introduced in various types of transformer
winding connections, and Refs. 12 to 14 provide further reading.
This phase shift depends on:
The results are shown in Fig. 9-11. Again verify that the vector
summation at the junctions confirms the accuracy of calculations.
■
Transformer winding connections
Currents in Generator G2
■
Sequence of the applied vectors.
I a (G2 ) = I1(G2 ) + I 2 (G2 ) + I 0 (G2 )
= − j0 . 8463 − j0 . 7172 − j1 . 475
= − j3 . 0385 = 3 . 0385 pu
I b (G2 ) = I 0 − 0 . 5(I1 + I 2 ) − j0 . 866(I1 − I 2 )
= − 0 . 1118 − j0 . 6933 = 0 . 7023 pu
I c (G2 ) = I 0 − 0 . 5(I1 + I 2 ) + j0 . 866(I1 − I 2 )
= 0 . 1118 − j0 . 6933 = 0 . 702 3 pu
This large unbalance is noteworthy. It gives rise to increased thermal
effects due to negative sequence currents and results in overheating
of the generator rotor. A generator will be tripped quickly on negative
sequence currents.
Figure 9-12 shows the phase shifts for wye-delta and delta-wye
connections according to ANSI/IEEE standards.13 The low-voltage
side vectors, whether in wye or delta connection, have a phase shift
of 30° lagging with respect to high-voltage side phase to neutral
voltage vectors.
The negative sequence currents and voltages undergo a phase
shift which is reverse of positive sequence currents and voltages. We will
correctly apply the phase shifts for positive and negative sequence
components when passing from delta secondary to wye primary of
the transformer. The positive and negative sequence current on wye
side of transformer T2 are:
I1( p ) = I1 < 30 ° = − j0 . 441 < 30 ° = 0 . 2205 − j0 . 382
I 2( p ) = I 2 < − 30 ° = − j0 . 539 < − 30 ° = − 0 . 2695 − j0 . 4668
220
CHAPTER NINE
vectors. Similarly, the negative sequence component undergoes a
positive phase shift. The currents on the delta side of transformer
T1 and T2 are identical in amplitude and phase. Figure 9-13 shows
the distribution of currents throughout the distribution system.
The voltage on the primary side of transformer T2 can be calculated. The voltages undergo the same phase shifts as the currents. Positive sequence voltage is the base fault positive sequence
voltage, phase shifted by 30°(positive) minus the voltage drop in
transformer reactance due to positive sequence current:
V1( p ) = 1 . 0 < 30 ° − jI1( p ) X1t
= 1 . 0 < 30 ° − ( j0 . 441 < 30 °)(− j0 . 24 )
F I G U R E 9 - 1 2 Phase shift in three-phase transformer winding
connections, according to ANSI/IEEE standard.13
= 0 . 958 + j0 . 553
V2( p ) = 0 − I 2( p ) X 2t
= −(0 . 539 < − 30 °)(0 . 24 < 270 °)
Also, the zero sequence current is zero. The primary currents are:
I a( p ) = I 0 + I1( p ) + I 2( p ) = − 0 . 049 − j0 . 8487
Thus:
I b( p ) = a 2I1( p ) + aI 2( p ) = − 0 . 0979
Va( p ) = 0 . 958 + j0 . 553 + 0 . 112 − j0 . 0647
I c( p ) = aI1( p ) + a 2I 2( p ) = − 0 . 049 − j0.. 8487
= 1 . 0697 + j0 . 4883 = 1 . 17 < 24 . 5 °
Currents in the lines on the delta side of the transformer T1
are similarly calculated. The positive sequence component, which
underwent a 30° positive shift from delta to wye in transformer
T2, undergoes a –30° phase shift; as for an ANSI connected transformer, it is the low-voltage vectors which lag the high-voltage side
FIGURE 9-13
= 0 . 112 − j0 . 0647
Vb( p ) = − 0 . 5(V1( p ) + V2( p ) ) − j0 . 866(V1( p)) − V2( p ) )
= − j0 . 9763
Vc( p ) = − 0 . 5(V1( p ) + V2( p ) ) − j0 . 866
6(V2( p ) − V1( p ) )
= 1 . 17 < 155 . 5 °
Distribution of currents for a single line-to-ground fault.
SYMMETRICAL AND UNSYMMETRICAL SHORT-CIRCUIT CURRENTS
Note the voltage unbalance caused by the fault. Figure 9-13 shows
the calculation of the currents throughout the distribution. It can
be observed that short-circuit current transients result in associated
voltage transients. We observed that while the voltage of the faulted
phase is zero, that of the other two phases rises by 3.4 percent. This
voltage rise is a function of the system grounding (Chap. 21).
9-5 MATRIX METHODS OF SHORT-CIRCUIT
CURRENT CALCULATIONS
The step-by-step sequence component method illustrated above,
though academically instructive, is rarely used in practice. Even for
a simple system, the calculations are tedious and lengthy. For large
networks consisting of thousands of nodes and branches these are
impractical and matrix methods are used. The commercial computer programs use Z impedance matrix methods.
The network equations can be written in the bus (or nodal) frame
of reference, in the loop frame of reference, and in the branch frame
of reference. The bus frame of reference is important. For n-node
system, the performance is described by n – 1 linear independent
equations, and the reference node is at ground potential. In Chap. 2.
(Sec. 2-13), we wrote the Y matrix by mere inspection. The impedance
matrix cannot be written by mere inspection. It is formulated by:
■
Inversion of Y matrix which is rarely done in computer
applications.
■
By open-circuit testing
■
From graph theory15
■
By step-by-step formulation
While the Y matrix is a sparse matrix and has a large number
of zero terms, as a bus is not connected to every other bus in the
system, a Z matrix is fully populated. Some matrix techniques are:
triangulation and factorization—Crout’s method, solution by forwardbackward substitution, and sparsity and optimal ordering. These
are not discussed here.
If we denote the sequence matrices by Z1ss , Z ss2 , and Z ss0 then:
For a line-to-ground fault:
Iss0 = Iss1 = Iss2 =
1
Z1ss + Z ss2 + Z ss0 + 3Z f
(9-35)
The voltage at bus j of the system is given by:
V j0
1
Z1ss + Z ss2 + Z f
(9-36)
0
V 1j = 1
0
V j2
Ixy0
Z1ss +
Is0 = −
Is2 =
Z ss2
+ ( Z ss0 + 3Z f )
0
Z1js
0
0
0
Z 2js
Is1
Is2
−
Vx0 − Vy0
0
1
Yxy
0
Vx1 − Vy1
0
Yxy2
0
(9-39)
Vx2
(9-40)
− Vy2
where:
0
I12
0
Ixy0 = I13
.
0
I mm
(9-41)
and
Y120 ,12
Y120 ,13
Y120,mn
Yxy0 = Y130 ,12
Y130 .13
Y130,mn
0
Ymn
,12
0
Ymn
,13
0
Ymn
,mn
(9-42)
where Yxy0 is the inverse of primitive matrix of the system. Similar
expressions apply to positive sequence and negative sequence currents and voltages.
Example 9-2 We will illustrate the application of matrix techniques to Example 9-1, same system data. Figure 9-14a can be
drawn for the positive sequence network and converted to Fig. 9.14b
in terms of admittances. By inspection the positive sequence bus
admittance matrix can be written as:
1
Ybus
1
Yaa
Y1
= ca1
Yda
1
Yba
A
=C
D
B
Yac1
Ycc1
Ydc1
Ybc1
1
Yad
Ycd1
Yd1d
1
Ybd
1
Yab
Ycb1
1
Ydb
1
Ybb
A
C
D
B
j5 . 55
− j9 . 55
0
0
j5 . 55 − j30 . 55
0
j25
0
− j29 . 17 j4 . 17
j25
0
0
j4 . 17 − j7 . 47
(9-37)
The inversion of this matrix gives the positive sequence bus
matrix:
I1s
Z1bus
The phase currents are calculated by:
Isabc = Ts Is012
Is0
0
Ixy2
Z ss2 + ( Z ss0 + 3Z f )
(−Z ss0 + 3Z f )
Z ss2
0
0
Ixy1 =
1
Z ss2 ( Z ss0 + 3Z f )
Z ss2
I1
+ ( Z ss0 + 3Z f ) s
0
0
Yxy
and for a double line-to-ground fault:
Is1 =
Z 0js
where j = 1, 2, . . . s, . . . . m The fault currents from bus x to y are
given by:
For a two-phase fault:
Iss1 = − Iss2 =
221
(9-38)
A
= C
D
B
A
j0 . 188
j0 . 144
j0 . 134
j0 . 075
C
j0 . 144
j0 .2
2 48
j0 . 231
j0 . 129
D
j0 . 134
j0 . 231
j0 . 252
j0 . 141
B
j0 . 075
j0 . 129
j0 . 141
j0 . 212
222
CHAPTER NINE
FIGURE 9-14
(a) Positive sequence network for a single line-to-ground fault. (b) Circuit of Fig. 9-14a reduced to admittance network.
All the elements are populated, there are no negative terms and the
matrix is symmetric. Similarly, the negative sequence network can
2
be drawn and the negative sequence Ybus
matrix is:
2
Ybus
A
= C
D
B
A
C
D
B
− j9 . 12
0
0
j5 . 55
0
j5 . 55 − j30 . 55
j25
− 29 . 17 j4 . 17
0
j25
0
0
j4 . 17 − j6 . 55
Z 0bus, cd = C
D
The inversion of this matrix gives:
Z 2bus
A
= C
D
B
A
j0 . 212
j0 . 169
j0 . 159
j0 . 101
C
j0 . 169
2 78
j0 .2
j0 . 262
j0 . 167
D
j0 . 159
j0 . 262
j0 . 285
j0 . 181
B
j0 . 101
j0 . 167
j0 . 181
j0 . 268
The formation of the zero sequence impedance is not so straightforward. At nodes A and B, the delta connection of the transformer
results in an open circuit and thus no zero sequence current
can flow from these nodes into the rest of the system (Fig. 9-15).
FIGURE 9-15
Thus, the zero sequence impedance at buses A and B is that of
generators G1 and G2, respectively, that is, 0.133 pu and 0.20 pu,
respectively.
A fault at buses C or D results in circulation of zero sequence
currents through the wye-connected neutrals of the transformers.
The zero sequence impedance of nodes C and D can be calculated similarly or by inversion of Y matrix. For buses C and D, this
gives:
Zero sequence network for a single line-to-ground
fault, showing discontinuities.
C
j0 . 123
j0 . 076
D
j0 . 076
j0 . 139
We can therefore write the overall matrix as follows:
Z 0bus
A
= C
D
B
A
j0 . 133
open
open
open
C
open
j0 . 123
j0 . 076
open
D
open
j0 . 07 6
j0 . 139
open
B
open
open
open
j0 . 20
The computer-based solutions address this discontinuity by
maintaining the integrity of nodes. A fictitious bus R is created,
and the delta-wye connected transformer can be modeled as
illustrated in Fig. 9-16. In Fig. 9-16a, a delta-wye transformer is
shown, and its zero sequence impedance when viewed from
bus 1 side is an open circuit. Two possible approaches for computer solutions are shown in Fig. 9-16b and c. A fictitious bus R is
created and the positive sequence impedance modified by dividing the positive sequence impedance into two parts, for high-and
low-voltage windings. Infinite impedance at the junction of these
impedance to bus R is connected (in computer calculations this
is simulated by a large number, e.g., 999 + j9999) on a per unit
basis. The zero sequence impedance is treated in a similar manner.
Figure 9-16c shows another approach for maintaining the integrity
of nodes.
SYMMETRICAL AND UNSYMMETRICAL SHORT-CIRCUIT CURRENTS
FIGURE 9-16
223
Computer methods to restore a node for an impedance discontinuity due to modeling of zero sequence impedance circuits of
transformers.
Having generated the bus impedance matrices, it is easy to calculate the short-circuit currents using the equations derived above.
A review of the matrices shows that the sequence impedances of
bus B are:
The line current in phase a is –j4.425, as calculated before, and line
currents in phases b and c are zero. Sequence voltages at bus B are:
VB0
VB1 = 1
Z1BB = j0 . 212
VB2
Z2BB = j0 . 268
Therefore:
= I1B
= I B2
0
0
I B0
0
Z1BS
0
I1B
0
0
2
Z BS
I B2
−
−
0
1
=
= − j1 . 475 pu
j0 . 212 + j0 . 268 + j0 . 20
=
The line currents are given by:
I abc
= Ts I B012
B
0
Z BS
0
0
= 1
Z0BB = j0 . 20
I B0
0
j0 . 20
0
0
0
j0 . 212
0
0
0
j0 . 268
− j1 . 475
− j1 . 475
− j1 . 475
− 0 . 295
0 . 687
− 0 . 392
Then the line voltages are:
− j1 . 425
I Ba
1
1
I Bb
I Bc
= 1
a
2
a
− j1 . 425
1
a
a2
− j1 . 425
1
1
− 0 . 295
0
VBb = 1 a 2
a
0 . 687
0
VBc
a2
− 0 . 392
− j4 .4
4 25
=
VBa
1 1
1 a
0
=
− 0 . 4425 − j0 . 9344
− 0 . 4425 + j0 . 9344
224
CHAPTER NINE
TA B L E 9 - 2
Single Line-to-Ground Fault at Bus B—Computer Simulation, for Example 9-3
CONTRIBUTION
FROM BUS
LINE-TO-GROUND FAULT
TO BUS
VOLTAGE (%)
Va
Vb
POSITIVE AND ZERO SEQUENCE IMPEDANCES
KA
Vc
Ia
Bus B
Total
0.0
102.91
103.29
18.334
Bus D
Bus 4
70.40
105.50
70.92
3.932
G2
Bus 4
100.0
100.0
100.0
M
Bus 4
104.55
104.55
104.55
TA B L E 9 - 3
12.69
1.712
18.334
0
18.334
0
R1
X1
7.02E – 001
2.16E + 001
2.40E + 000
7.36E + 001
1.22E + 000
3.67E + 001
5.17E + 000
1.81E + 002
R0
X0
6.67E – 001 2.00E + 001
6.67E – 001 2.00E + 001
POSITIVE SEQUENCE (W)
NEGATIVE SEQUENCE (W)
ZERO SEQUENCE (W)
A
0.00991 + j 0.36179
0.00991 + j 0.40671
0.00635 + j 0.25392
B
0.41059 + j 0.41081
0.01372 + j 0.51163
0.01270 + j 0.38088
C
1.51051 + j 48.06746
1.50439 + j 53.44850
0.78716 + j 23.92366
D
1.55162 + j 49.12745
1.53554 + j 54.87076
0.94393 + j 28.07056
COMPUTER-BASED CALCULATIONS
OVERVOLTAGES DUE TO GROUND FAULTS
We discussed the temporary overvoltages in previous chapters
and remarked that the overvoltages due to ground faults are an
important parameter for electrical system analysis and application
of surge arresters. These overvoltages depend on:
■
3I0
BUS ID
The hand calculations of short-circuit currents, whether using symmetrical component methods or matrix methods, is a tedious exercise but establishes the basis of underlying methodology. Practically,
the electrical systems are large, may consist of thousands of buses,
generators, transformers, and a variety of load characteristics, and
digital computers are invariably applied to such calculations. The
basis of calculations are Z impedance matrices and matrix reduction techniques as stated earlier.
Example 9-3 A commercial short-circuit program is used to calculate the short-circuit currents and the results of calculation are in
Table 9-2. We ignored the resistance component of all impedances
in the hand calculations. A computer program will not accept a
zero entry for the resistance, it has to be finite number, otherwise,
it results in an indeterminate matrix due to division by zero. This
table shows the flow of current from the adjacent bus D and also
the currents contributed by generator G2 and motor M. Note that
the zero sequence current contributed by the motor (windings not
grounded) and from bus D (delta-wye transformer) are zero.
The calculated sequence impedances in ohms are shown in
Table 9-3. The results shown closely agree with the matrices developed in Example 9-2. These calculations do not show any transients.
This is because the calculations are based on the fixed values of the
impedances, using algebraic equations. In order to simulate transients, the dynamic models of generators, motors, and loads are
required.
9-7
IMPEDANCE 100 MVA BASE (%)
Calculated Bus Sequence Impedances
This is the same result as in Example 9-1. In matrix techniques, it
is easy to calculate the symmetrical and asymmetrical fault currents
on any of the buses, using the calculated sequence impedances.
9-6
SYM. rms
Sequence impedance to faults, which also dictate the
ground fault currents
■
The fault resistance
■
The method of system grounding, that is, solidly grounded,
resistance grounded, high resistance grounded or ungrounded systems (Chap. 21).
The duration of overvoltages is dependent upon the fault
clearance times; resonances can occur due to capacitive inductive
couplings in ungrounded systems, and for application of surge
arresters (Chap. 20), an estimation of the duration and magnitude
of these overvoltages is required. In Example 9-1, the voltages on
the unfaulted phases at the fault point rise by 3.4 percent.
9-7-1 Coefficient of Grounding
A measure of this overvoltage is the coefficient of grounding,
defined as a ratio of ELg /ELL in percentage, where ELg is the highest rms voltage on an unfaulted phase, at a selected location,
during a fault effecting one or more phases to ground, and ELL is
the rms phase-to-phase power frequency voltage obtained at the
location with the fault removed. In a solidly grounded system, no
intentional impedance is introduced between system neutral and
ground. These systems, generally, meet the definition of “effectively
grounded systems” in which the ratio X0 /X1 is positive and less
than 3.0 and the ratio R0 /X0 is positive and less than 1.0, where
X1, X0, and R0 are the positive sequence reactance, zero sequence
reactance, and zero sequence resistance, respectively. These systems
are, generally, characterized by COG of 80 percent. Approximately,
a surge arrester with its rated voltage calculated on the basis of the
system voltage multiplied by 0.8 can be applied (Chap. 20).
The single line-to-ground fault is the most important cause
of overvoltages in the power systems. This type of fault produces
the maximum fault voltages for all values of R0 /X1. Sometimes we
define EFF (IEC standards, earth fault factor). It is simply:
EFF = 3COG
(9-43)
In an ungrounded system, there is no intentional connection to
ground except through potential transformers and metering devices
of high impedance. Therefore, in reality, the ungrounded system is
coupled to ground through the distributed phase capacitances. It is
SYMMETRICAL AND UNSYMMETRICAL SHORT-CIRCUIT CURRENTS
difficult to assign X0 /X1 and R0 /X0 values for ungrounded systems.
The ratio X0 /X1 is negative and may vary from low to high values.
The COG may approach 120 percent. For values of X0 /X1 between
0 and –40, the possibility of resonance with consequent generation
of high voltages exits.
Figure 9-17 from Ref. 16 shows the overvoltages with respect to
sequence impedances. The curves are applicable for X1 = X2. Also
the curves include the effect of fault resistance. For each point, a
fault resistance is chosen so that it produces maximum COG. In
general, fault resistance will reduce COG, except in low-resistance
systems. The numbers on the curves indicate coefficient of grounding for any type of fault in percent of unfaulted line-to-line voltage
for the area bonded by the curve and the axes. All impedances must
be on the same MVA base.
Figure 9-18 from Ref. 16 shows the maximum line-to-ground
voltage during fault for isolated neutral systems as a function of
X0 /X1. COG can be calculated by the equations described below
and more rigorously by the sequence component matrix methods,
as illustrated above.
FIGURE 9-17
225
Single line-to-ground fault:
1 3k
COG(phase b) = −
+ j1
2 2 + k
1 3kk
COG(phase c) = −
− j1
2 2 + k
(9-44)
Double line-to-ground fault:
COG(phase a ) =
3k
1 + 2k
(9-45)
where k is given by:
k=
Z0
Z1
(9-46)
Maximum line-to-ground voltage at fault locations for grounded neutral systems; for any fault condition: (a) voltage conditions neglecting positive and negative sequence resistance; (b) voltage conditions for R1 = R2 = 0.1X1; (c) voltage conditions for R1 = R2 = 0.2X1.16
226
CHAPTER NINE
FIGURE 9-18
Maximum line-to-ground voltage at fault location for isolated neutral systems during fault.16
To take into account the fault resistance, k is modified as follows:
Single line-to-ground fault:
k = (R 0 + R f + jX 0 )/(R1 + R f + jX1 )
(9-47)
For double line-to-ground fault:
k = (R 0 + 2R f + jX 0 )/(R1 + 2R f + jX1 )
(9-48)
If R0 and R1 are zero, then the above equations reduce to:
For single line-to-ground fault:
COG =
k2 + k + 1
k+2
(9-49)
For double line-to-ground fault:
k
2k + 1
(9-50)
where k = X 0 /X1
(9-51)
COG =
Example 9-4 Calculate the COG at the faulted bus B in
Example 9-1. If generator G2 is grounded through a 400-A resistor,
what is the COG?
In Example 9-1, all resistances are ignored. From Fig. 9-17 the
COG cannot be clearly read. But using Eq. (9-49), it is 0.57 (k =
0.9434). Also a voltage of 1.034 pu was calculated on the unfaulted
phases, which gives a COG of 0.597. This is more accurate.
If the generator is grounded through 400-A resistor, then R0 =
19.19 Ω, the positive sequence reactance is 0.4 Ω, and the zero
sequence reactance is 0.38 Ω, which is much smaller than R0. In
fact, in a resistance grounded or high resistance grounded system,
the sequence components are relatively small and the ground fault
current can be calculated based upon the grounding resistor alone.
The total ground fault current at bus 4 will reduce to approximately
400 A. This gives a COG of approximately 100 percent. This means
that phase-to-ground voltage on unfaulted phases will be equal to
line-to-line voltage.
Example 9-5 Though the dynamic models of generators and
motors are covered in the chapters to follow, this example illustrates short-circuit transients in a power system (Fig. 9-19). The
ratings of the major components are shown in this figure, the component models are discussed in other chapters.
Transients for a three-phase fault and then a single line-toground fault are simulated for a fault at 115-kV bus 1. Either fault
occurs at 0.5 s and is removed at 1.5 s; fault duration of 1s. For a
three-phase fault at bus 1, the results of EMTP simulations are:
Figure 9-20a shows voltage at the fault point. During the
three-phase fault the voltage is not reduced to zero, because
of some fault resistance considered in the model. The recovery of voltage after the fault is cleared at 1 s shows superimposed frequency beats (phenomena as shown in Fig. 2-20b).
This is because of cyclic transients in the torque pulsations of
generator and synchronous motor after the fault is cleared.
Figure 9-20b depicts the current transients in generator G1. The
fault current rises during the fault duration, but shows the same
behavior as the voltage to fault point, after the fault is cleared.
Figure 9-20c is the current transients, phases a, b, and c in the
induction motor IM. At the instant of fault, the motor contributes
high short-circuit current (maximum peak approximately 10 kA =
nearly 12 times the motor full load current), which quickly decays.
The transients show similar pattern as in Fig. 9.20a and b.
Figure 9-20d is the electrical torque of the generator and
synchronous motor load. As the torque pulsates, the machines
draw power and supply power into the system at a certain
frequency, which explains the nature of the transients. The load
SYMMETRICAL AND UNSYMMETRICAL SHORT-CIRCUIT CURRENTS
FIGURE 9-19
FIGURE 9-20
227
A power system for EMTP study of short-circuit transients.
Transients for a three-phase fault on bus 1, which occurs at 0.5 s and is cleared at 1.5 s, fault duration of 1 s: (a) voltage at bus 1,
phases a, b, and c ; (b) generator G1 current (pu), phases a, b, and c ; (c) induction motor IM currents. (d) electrical torque of generator G1 and synchronous
motor load (pu); (e) power angle of generator G1 and synchronous motor load; (f ) slip of the induction motor IM.
228
CHAPTER NINE
FIGURE 9-20
(Continued )
SYMMETRICAL AND UNSYMMETRICAL SHORT-CIRCUIT CURRENTS
FIGURE 9-20
(Continued )
229
230
CHAPTER NINE
current cycles with respect to the bus voltage and it contributes
to the accentuation of transients. Figure 9-20e is the power
angle curve of generator G1. This figure and Fig. 9-20d depict
that generator G1 and synchronous motor loads are unstable.
Figure 9-21a illustrates the voltage at the fault point in phases
a, b, and c. Here the pattern after the fault clearance is entirely
different because the torque pulsations of synchronous
machines damp out after the fault is cleared (Figure 9-21c).
Figure 9-20f depicts the induction motor slip transient. Note
the speed oscillations as the motor tries to speed up after the
fault is removed.
Figure 9-21b depicts the current transients in generator G1.
Comparing this with Fig. 9-20b, there are no continued beat
frequency transients.
Now consider a single phase-to-ground fault, phase a, at the
same location. The transients are shown in Fig. 9-21 and are
described as follows:
Figure 9-21c illustrates the torque transients in the generator and
synchronous motor load. These decay quickly after the fault is
removed, and Fig. 9-21d shows the slip of the induction motor.
F I G U R E 9 - 2 1 Transients for a single line-to-ground fault, phase a on bus 1, which occurs at 0.5 s and is removed at 1.5 s, fault duration of 1 s;
(a) voltage at bus 1, phases a, b, and c ; (b) generator G1 current, phases a, b, and c ; (c) electrical torque of generator G1 and synchronous motor load (pu);
(d) slip of the induction motor IM.
SYMMETRICAL AND UNSYMMETRICAL SHORT-CIRCUIT CURRENTS
FIGURE 9-21
Fault duration of 1 s for three-phase fault considered in the
simulation is rather large. Practically, the three-phase faults in a
system as illustrated will be covered in differential zone of protection, operating time of the protective relaying of the order of one
cycle or less. Add to it the breaker operating time. Figure 9-22
shows the simulation, voltages at the fault point, for three-phase
231
(Continued )
fault duration of 0.3 s (18 cycles). This shows normal recovery
voltage after the fault, and the swings in generator G1 recover
quickly after the fault is cleared. Transient stability is of major
consideration while evaluating the fault transients, which constitute severe disturbance to the system. This is followed up in the
subsequent chapters.
232
CHAPTER NINE
FIGURE 9-22
Transients for a three-phase fault on bus 1, that occurs at 0.5 s and is removed at 0.8 s, fault duration of 18 cycles.
PROBLEMS
1. A wye-wye connected step-down transformer has a primary
voltage rating of 138 kV and the secondary voltage rating
of 13.8 kV. The primary wye-connected winding neutral is
ungrounded, while the secondary 13.8 kV neutral is solidly
grounded. A single line-to-ground fault occurs on the 13.8 kV
side. Does zero sequence current flow in the grounded neutral?
2. A wye-wye connected transformer with tertiary delta has a
single line-to-ground fault on the secondary windings. Both wyeconnected neutrals are grounded. Draw a zero sequence circuit of
the transformer and show the current flows in all the windings of
the transformer as well as in the lines connected to the transformer.
3. The unbalance voltages in a three-phase system are 0.8 pu,
phase a, and 1.0 pu in phases b and c. Find the sequence
components of the voltages and show the original voltages as
well as zero sequence voltages in a sketch. Convert back from
sequence voltages to original unbalance voltages.
FIGURE 9-P1
4. A 138 to 13.8 kV, wye-wye connected transformer, with
tertiary delta, 138-kV wye winding is solidly grounded and the
13.8-kV winding is ungrounded. A 15-Ω resistor is connected
between phases a and b of the 13.8-kV windings. Show the
flow of all currents in the transformer.
5. A simple distribution system is shown in Fig. 9-P1. The
major equipment ratings are shown, but not the impedances.
Assume practical values of impedances for all power system elements. Calculate three-phase, single line-to-ground
and double line-to-ground faults at locations F1, F2, and
F3, using method of symmetrical components and then the
matrix methods. Calculate the voltages on all phases.
6. What are the COG factors in Prob. 5 for each case of
calculation?
7. Repeat Probs. 5 and 6 when the transformer T2 is grounded
through a resistance of 1 Ω.
Power system connections for Probs. 5, 6, and 7.
SYMMETRICAL AND UNSYMMETRICAL SHORT-CIRCUIT CURRENTS
REFERENCES
1. ANSI/IEEE Std. C37.010, Guide for AC High Voltage Circuit
Breakers Rated on Symmetrical Current Basis, 1999.
2. IEC 60909-0, Short-Circuit Currents in Three-Phase AC
Systems, Part-0, Calculation of Currents, 2001; also IEC
60909-1, Factors for Calculation of Short-Circuit Currents in
Three-Phase AC Systems According to IEC 60909-0, 1991.
3. IEEE Std. 551 (Violet Book), Calculating Short-Circuit Currents
in Industrial and Commercial Power Systems, 2006.
4. W. E. Lewis and D. G. Pryce, The Application of Matrix Theory to
Electrical Engineering, E&FN Spon, London, 1965.
5. L. J. Myatt, Symmetrical Components, Pergamon Press, Oxford,
London, 1968.
6. J. L. Blackburn, Symmetrical Components for Power System Engineering, Marcel Dekker, New York, 1993.
7. H. E. Brown, Solution of Large Networks by Matrix Methods,
Wiley Interscience, New York, 1975.
233
10. C. L. Fortescue, “Method of Symmetrical Components Applied
to the Solution of Polyphase Networks,” AIEE Trans, vol. 37,
pp. 1027–1140, 1918.
11. E. Clarke, Circuit Analysis of Alternating Current Power Systems,
vol. 1, Wiley, New York, 1943.
12. Transformer Connections (including Auto-transformer
Connections), General Electric, Publication No. GET-2H,
Pittsfield, MA, 1967.
13. ANSI/IEEE Std. C57.12.00, General Requirements of Liquid
Immersed Distribution, Power and Regulating Transformers, 2006.
14. ANSI Std. C57.12.70, Terminal Markings and Connections for
Distribution and Power Transformers, 2000.
15. J. C. Das, Power System Analysis Short-Circuit, Load Flow, and
Harmonics, Marcel Dekker, New York, 2002.
16. WESTINGHOUSE Electrical Transmission and Distribution Reference Book, 4th ed., Westinghouse Electric Corporation, East
Pittsburgh, PA, 1964.
8. G. O. Calabrase, Symmetrical Components Applied to Electric
Power Networks, Ronald Press Group, New York, 1959.
FURTHER READING
9. C. F. Wagnor and R. D. Evans, Symmetrical Components,
McGraw Hill, New York, 1933.
W. D. Stevenson, Elements of Power System Analysis, 4th ed.,
McGraw-Hill, New York, 1982.
C. A. Gross, Power System Analysis, John Wiley, New York, 1979.
This page intentionally left blank
CHAPTER 10
TRANSIENT BEHAVIOR OF
SYNCHRONOUS GENERATORS
The study of transients in generators has been carried out ever since
the earlier nineteenth century. As the complexity of transmission
and grid systems grew, so did the synchronous generator models
to represent their behavior under steady-state and transient conditions. Synchronous generators are the prime source of power
production and single shaft units of 1500 MVA, and more are in
operation, while research continues on the development of larger
superconducting units. In the utility systems, the synchronous
generators are connected directly through a step-up transformer
to the transmission systems, Fig. 10-1. In this figure, the ratings of
generators and transformers are not shown for generality. Note that
generators 1 and 4 do not have a generator breaker and the generator and transformer are protected as a unit with overlapping zones
of differential protection (not discussed here). Generators 2 and
3 have generator breakers, which allow generator step-up transformers to be used as step-up down transformers during cold
start-up. The power to the generation of auxiliary loads is duplicated with auto switching of a bus section breaker, and there is also
a third standby power source. The auto switching of motor loads is
discussed in Chap. 16.
Figure 10-2 shows a generator of 81.82 MVA, 12.47 kV, 0.85
power factor directly connected to a 12.47-kV bus, also powered by a
30/40/50 MVA, 115 to 12.47-kV utility transformer. The two sources
are run in synchronism, and the plant running load is 45 MVA; the
excess generated power is supplied into the utility system. The size of
a generator that can be bus connected in an industrial distribution,
primary distribution voltage of 13.8 kV, is approximately limited to
100 MVA, as an acceptable level of short circuit should be maintained
at the medium voltage switchgear and the downstream distributions.
A utility or industrial generator is subjected to load regulation,
near to the generator and far from generator faults, switching transients, and a worst-case scenario of terminal fault.
Under any perturbation from the steady-state operation, the currents in stator, rotor, field, and damper currents undergo transients.
Swings occur in generator’s active and reactive power output—
electromagnetic torque, torque angle, frequency, and speed vary.
A number of transient models to address these transients can be
developed. The principles of the operation of the synchronous
generators in the steady state form the background for development
of the transient models; conversely, the steady-state models can
be derived from the transient models. This chapter assumes that a
reader has basic knowledge of the synchronous machine theory.
10-1
THREE-PHASE TERMINAL FAULT
A three-phase short circuit on the terminals of a generator is the
largest perturbation to the operation of a generator and its survival
to continue in operation after the protective relays clear the fault
(assuming that the fault is not in the generator itself), and this transient is of practical importance too. We will study this transient as it
leads to definitions of synchronous generator reactances. Short circuit has twofold effects. (1) Large disruptive forces are brought into
play in the generator itself, and the generator should be designed
to withstand these forces. (2) Short circuits should be removed
quickly to limit fault damage and improve stability of the interconnected systems. The circuit breakers for generator application see a
fault current of high asymmetry and must be rated to successfully
interrupt such short-circuit currents, where a current zero may not
occur at the contact parting time.
According to NEMA standards,1 a synchronous generator shall
be capable of withstanding, without injury, a 30-s, three-phase
short circuit at its terminals when operating at rated kVA and power
factor at 5-percent overvoltage, with fixed excitation. With a voltage
regulator in service, the allowable duration t in seconds is determined from the following equation, where the regulator is designed
to provide ceiling voltage continuously during a short circuit:
Nominal field voltage
t =
× 30 s
Exciter ceiling voltage
2
(10-1)
The generator should also be capable of withstanding without
injury any other short circuits at its terminals for 30 s, provided (1)
the following values of I 22t specified for the type of construction:
I 22t = 40 for salient pole machines
I 22t = 30 for air-ccooled cylindrical rotor machines
(10-2)
are not exceeded, and (2) the maximum current is limited by external means so as not to exceed the three-phase fault. I2 is the negativesequence current due to unsymmetrical faults.
235
236
CHAPTER TEN
FIGURE 10-1
A single line diagram of connections of large synchronous generators in a utility generating station.
FIGURE 10-2
System configuration of a bus-connected industrial generator in cogeneration mode.
TRANSIENT BEHAVIOR OF SYNCHRONOUS GENERATORS
Synchronous generators are major sources of short-circuit currents in power systems. The fault current depends on:
1. The instant at which the short circuit occurs
2. The load and excitation of the generator immediately before
the short circuit
3. The type of short circuits, that is, whether three phases or
one or more than one phase and ground are involved
4. Constructional features of the generator, especially leakage
and damping
5. The interconnecting impedances between generators
An insight into the physical behavior of the generator during
short circuit can be made considering the theorem of constant
flux linkages. For a closed circuit with resistance r and inductance
L, ri + Ldi/dt must be zero. If resistance is neglected, Ldi/dt = 0, that
is, flux linkage Li must remain constant. In a generator, the resistance is small in comparison with inductance, the field winding is
closed on the exciter, and the stator winding is closed due to short
circuit. During the initial couple of cycles following short circuit,
the flux linkages with these two windings must remain constant.
On a terminal fault, the generated EMF acts on a closed circuit of
stator windings and is analogous to an EMF being suddenly applied
to an inductive circuit. Dynamically, the situation is more complex,
that is, the lagging stator current has a demagnetizing effect on the
field flux, and there are time constants associated with the penetration of the stator flux and decay of short-circuit currents.
10-2 REACTANCES OF A SYNCHRONOUS
GENERATOR
The following definitions are applicable:
10-2-1
Leakage Reactance, Xl
The leakage reactance can be defined but cannot be tested. It is the
reactance due to flux set up by armature windings, but not crossing the air gap. It can be divided into end-winding leakage and
slot leakage. A convenient way of picturing the reactances is to
view these in terms of permeances of various magnetic paths in
the machine, which are functions of dimensions of iron and
copper circuits and independent of the flux density or the current
loading. The permeances, thus calculated, can be multiplied by a
factor to consider the flux density and current. For example, the
leakage reactance is mainly given by the slot permeance and the
end-coil permeance.
Subtransient Reactance, X d′′
Subtransient reactance equals the leakage reactance plus the reactance due to the flux set up by stator currents crossing the air gap
and penetrating the rotor as far as the damper windings in a laminated pole machine or as far as the surface damping currents in
a solid pole machine. The subtransient conditions last for 1 to 5
cycles on a 60-Hz basis.
10-2-2
10-2-3
Transient Reactance, X d′
Transient reactance is the reactance after all damping currents in
the rotor surface or amortisseur windings have decayed, but before
the damping currents in the field winding have decayed. The transient reactance equals the leakage reactance plus the reactance
due to flux set up by the armature which penetrates the rotor to
the field windings. Transient conditions last for 5–200 cycles on
a 60-Hz basis.
10-2-4
237
Synchronous Reactance, Xd
Synchronous reactance is the steady-state reactance after all damping currents in the field windings have decayed. It is the sum of leakage reactance and a fictitious armature reaction reactance, which is
much larger than the leakage reactance. Ignoring resistance, the per
unit synchronous reactance is the ratio of per unit voltage on an
open circuit divided by per unit armature current on short circuit
for a given field excitation. This gives saturated synchronous reactance. The unsaturated value of the synchronous reactance is given
by the per unit voltage on air-gap open circuit line divided by per
unit armature current on short circuit. If 0.5 per unit field excitation produces full-load armature current on short circuit, the saturated synchronous reactance is 2.0 per unit. The saturated value
may be only 70 to 90 percent of the unsaturated value.
Quadrature Axis Reactances, X q′′ , X q′ , X q
Quadrature axis reactances are similar to direct axis reactances,
except that they involve the rotor permeance encountered when
the stator flux enters one pole tip, crosses the pole, and leaves the
other pole tip. The direct axis permeance is encountered by the flux
crossing the air gap to the center of one pole, then crossing from
one pole to the other pole and entering the stator from that pole.
Figure 10-3 shows the armature reaction components. The total
armature reaction Fa can be divided into two components, Fad and
Faq. Fad is directed across the direct axis and Faq, across the quadrature axis. As these MMFs act on circuits of different permeances,
the flux produced varies. This is the basis of two-reaction synchronous machine theory discussed in many texts.2 If damper windings
across pole faces are connected, X ″q is nearly equal to X″d.
10-2-5
10-2-6
Negative-Sequence Reactance, X2
The negative-sequence reactance is the reactance encountered by
a voltage of reverse phase sequence applied to the stator, with the
machine running. Negative-sequence flux revolves opposite to the
rotor and is at twice the system frequency. Negative-sequence reactance is practically equal to the subtransient reactance as the damping currents in the damper windings or solid pole rotor surface
prevent the flux from penetrating farther. The negative-sequence
reactance is generally taken as the average of subtransient direct
axis and quadrature axis reactances:
X2 =
10-2-7
X ′′d + X ′′q
2
(10-3)
Zero-Sequence Reactance, X0
The zero-sequence reactance is the reactance effective when rated
frequency currents enter all three terminals of the machine simultaneously and leave at the neutral of the machine. It is approximately
equal to the leakage reactance of the machine with full-pitch coils.
With two-thirds-pitch stator coils, the zero-sequence reactance will
be a fraction of the leakage reactance.
10-2-8
Potier Reactance, Xp
Potier reactance is a reactance with numerical value between transient and subtransient reactances. It is used for the calculation of
field current when open circuit and zero power factor curves are
available. Figure 10-4 shows the saturation characteristics of a synchronous generator. Triangle XGS is the Potier triangle. Point S on
the x-axis is field excitation to produce full-load current on short
circuit, which is approximately 90°lagging. OS = Fa + Fx, where
Fa represents direct demagnetizing armature reaction and Fx represents the field amperes to circulate current through the leakage
reactance, which gives a voltage drop of iXl. As we move up on
the open circuit and zero power factor curves, S′G′ is not exactly
238
CHAPTER TEN
FIGURE 10-3
Resolution of total armature reaction in a salient-pole generator into direct-axis and quadrature-axis components.
equal to SG and also GX and G′X′ are not exactly identical due to
different saturation of the curves. The value of Xl obtained from it is
called the Potier reactance, and it exceeds the value based on pure
armature leakage flux. We will return to saturation characteristics
of the generator in Chap. 13. Due to different slopes of open circuit
and zero power factor curves, G′X′ in Fig. 10-4 is slightly larger
than GX and the value of reactance obtained from it is known as
Potier reactance.
10-3
SATURATION OF REACTANCES
Saturation varies with voltage, current, and power factor. The saturation factor is usually applied to transient and synchronous reactances; in fact, all other reactances change, though slightly, with
saturation. The saturated and unsaturated synchronous reactances
are already defined above. In a typical generator, transient reactances may reduce from 5 to 25 percent on saturation. Saturated
reactance is sometimes called the rated voltage reactance and is
denoted by subscript v added to d and q axes, that is, X ″dv and X ″qv
denote saturated subtransient reactances in direct and quadrature
axes, respectively.
10-4 TIME CONSTANTS OF SYNCHRONOUS
GENERATORS
10-4-1 Transient Open-Circuit Time Constant, Tdo′
Transient open-circuit time constant expresses the rate of decay or
build up of field current when the stator is open-circuited and there
is zero resistance in the field circuit.
10-4-2 Subtransient Short-Circuit Time Constant, Td′′
Subtransient short-circuit time constant expresses the rate of decay
of the subtransient component of current under a bolted (zero
resistance), three-phase short circuit at the generator terminals.
10-4-3 Transient Short-Circuit Time Constant, Td′
Transient short-circuit time constant expresses the rate of decay
of the transient component of the current under a bolted (zero
resistance), three-phase short circuit at the generator terminals.
Manufacturers supply transient time constants for line-to-line and
TRANSIENT BEHAVIOR OF SYNCHRONOUS GENERATORS
FIGURE 10-4
Potier reactance and other saturation characteristics of a generator.
line-to-neutral short-circuit currents also. To distinguish these time
constants, a number is added to the subscript, that is, T d′3 denoting
three-phase short-circuit transient time constant, T d′2, denoting lineto-line short-circuit transient time constant, and T d′1 denoting lineto-neutral short-circuit time constant.
10-4-4
Armature Time Constant, Ta
Armature time constant expresses the rate of decay of the dc component of the short-circuit current under the same conditions. Again
this is specified for three-phase, two-phase, and line-to-neutral
faults. Table 10-1 shows electrical data, reactances, and time constants of a 13.8-kV, 112.1-MVA, and 0.85 power factor generator.
In this table, all reactances are in per unit on generator MVA base
and all time constants are in seconds.
10-5 SYNCHRONOUS GENERATOR BEHAVIOR
ON TERMINAL SHORT-CIRCUIT
The time immediately after short circuit can be divided into three
distinct periods:
■
■
239
The subtransient period lasting from 1 to 5 cycles
The transient period which may last up to 100 cycles or
more
■
The final or steady-state period follows after the transients
have decayed and the terminal short circuit is limited by the synchronous reactance of the generator. Normally, the generator will
be removed from service by protective relaying, much before the
steady-state period is reached.
In the subtransient period, the conditions can be represented by
the flux linking the stator and rotor windings. Any sudden change
in the load or power factor of a generator produces changes in the
MMF, both in direct and quadrature axes. At the moment of short
circuit, the flux linking the stator from the rotor is trapped in the
stator, giving a stationary replica of the main-pole flux. The rotor
poles may be in a position of maximum or minimum flux linkage,
and as these rotate, the flux linkages tend to change. This is counteracted by a current in the stator windings. The short-circuit current is, therefore, dependent on rotor angle. As the energy stored
can be considered a function of armature and field linkages, the
torque fluctuates and reverses cyclically. The dc component giving
rise to asymmetry is caused by the flux trapped in the stator windings at the instant of short circuit, which sets up a dc transient in
the armature circuit. This dc component establishes a component
field in the air gap which is stationary in space, and which, therefore, induces a fundamental frequency voltage and current in the
synchronously revolving rotor circuits. Thus, an increase in the
stator current is followed by an increase in the field current. The
field flux has superimposed on it a new flux pulsating with respect
240
CHAPTER TEN
TA B L E 1 0 - 1
Manufacturer’s Data of a 112.1-MVA Generator
DESCRIPTION
SYMBOL
DATA
Per unit reactance data, direct axis
Saturated synchronous
Unsaturated synchronous
Saturated transient
Unsaturated transient
Saturated subtransient
Unsaturated subtransient
Saturated negative sequence
Unsaturated negative sequence
Saturated zero sequence
Unsaturated zero sequence
Leakage reactance, overexcited
Leakage reactance, underexcited
Xdv
Xd
X d′v
X d′
X ″dv
X ″d
X2v
X2I
X0v
X0I
XLM,OXE
XLM,UEX
1.949
1.949
0.207
0.278
0.164
0.193
0.137
0.185
0.092
0.111
0.164
0.164
Per unit reactance data, quadrature axis
Saturated synchronous
Unsaturated synchronous
Unsaturated transient
Saturated subtransient
Unsaturated subtransient
Xqv
Xq
X q′
X ″qv
X ″q
1.858
1.858
0.434
0.140
0.192
Field time constant data, direct axis
Open circuit
Three-phase short-circuit transient
Line-to-line short-circuit transient
Line-to-neutral short-circuit transient
Short-circuit subtransient
Open-circuit subtransient
T d′o
T d′ 3
T d′ 2
T d′1
T ″d
T ″do
5.615
0.597
0.927
1.124
0.015
0.022
Field time constant data, quadrature axis
Open circuit
Three-phase short-circuit transient
Short-circuit subtransient
Open-circuit subtransient
T q′o
T q′
T ″q
T ″qo
0.451
0.451
0.015
0.046
Armature dc component time constant data
Three-phase short-circuit
Line-to-line short-circuit
Line-to-neutral short-circuit
Ta 3
Ta 2
Ta 1
0.330
0.330
0.294
Generator
112.1 MVA, 2-pole, 13.8 kV, 0.85 pF, 95.286 MW, 4690 A,
235 V, field voltage, wye-connected
SCR = 0.56
All impedances in per unit on generator MVA base. All time constants in seconds.
to field windings at normal machine frequency. The single-phaseinduced current in field can be resolved into two components, one
stationary with respect to stator which counteracts the dc component of the stator current, and the other component travels at twice
the synchronous speed with respect to stator and induces a second
harmonic in it.
The armature and field are linked through the magnetic circuit,
and the ac component of lagging current creates a demagnetizing
effect. However, some time must elapse before it starts becoming
effective in reducing the field current and the steady-state current is
reached. The protective relays will normally operate to open the generator breaker and simultaneously the field circuit for suppression of
generated voltage.
The above is rather an oversimplification of the transient phenomena in the generator on short circuit. In practicality, a generator
will be connected in an interconnected system. The generator
terminal voltage, rotor angle, and frequency all change, depending on the location of fault in the network, the network impedance, and the generator parameters. The generator output power
will be affected by the change in the rotor winding EMF and the
rotor position in addition to any changes in the impedance seen
at the generator terminals. For a terminal fault, the voltage at the
generator terminals is zero and, therefore, power supplied by the
generator to load reduces to zero, while the prime mover output cannot change suddenly. Thus, the generator accelerates. In
a multi-machine system with interconnecting impedances, the
speeds of all machines change, so that these generate their share
of synchronizing power in the overall impact, as these strive to
reach a mean retardation through oscillations due to stored energy
in the rotating masses.
TRANSIENT BEHAVIOR OF SYNCHRONOUS GENERATORS
In a dynamic simulation of short-circuit and transient stability calculations (Chaps. 12 and 13), the following are generally considered:
241
Therefore, Eq. (10-4) can also be written as:
1
1/Lad + 1/l f + 1/lkD
■
Network before, during, and after the short circuit
L′′d = ll +
■
Dynamic modeling of induction motors, with zero excitation
Similarly, the quadrature-axis subtransient reactance is given by:
■
Dynamic modeling of synchronous machine, considering
saturation
■
Modeling of excitation systems
■
Turbine and governor models
10-5-1
Equivalent Circuits During Fault
Figure 10-5 shows an envelope of decaying ac component of the shortcircuit current wave, neglecting the dc component. The extrapolation of
the current envelope to zero time gives the peak current. Note that immediately after the fault, the current decays fast and then more slowly. Only
the upper-half of the transient is shown; the lower-half is symmetrical.
Transformer equivalent circuits of a salient-pole synchronous
generator in the direct and quadrature axes at the instant of short
circuit and during subsequent time delays help to derive the shortcircuit current equations and explain the decaying ac component of
Fig. 10-5. Based on the earlier discussions, these circuits are shown
in Fig. 10-6, in the subtransient, transient, and steady-state periods.
As the flux penetrates into the rotor, and the currents die down, it
is equivalent to opening a circuit element; that is, from subtransient
to transient state, the damper circuits are opened.
The direct-axis subtransient reactance is given by:
1
X ′′d = X l +
1/X ad + 1/X f + 1/X kD
X F = X f + X ad
L D = lkD + Lad
FIGURE 10-5
1
1/X aq + 1/X kQ
(10-5)
where Xaq is the reactance corresponding to fundamental space
wave in the quadrature axis, and XkQ is the reactance of the damper
winding in the quadrature axis, akin to the leakage reactance. Xl
is considered identical in the direct and quadrature axes, and the
leakage reactance giving rise to Xl is ll. That is:
ll = ld = lq
The quadrature-axis rotor circuit does not carry a field winding,
and this circuit is composed of damper bars or rotor iron in the
inter-polar axis of a cylindrical rotor machine.
The direct-axis and quadrature-axis short-circuit time constants
associated with decay of the subtransient component of the current
are:
Td′′ =
X ad X f X l
1
+ X kD
ω rD X ad X f + X f X l + X ad X l
Td′′ =
Ladl f ll
1
+ lkD
rD Ladl f + l f ll + Ladll
Tq′′ =
1 X aq X l
+ X kQ
ω rQ X aq + X l
Tq′′ =
1 Laqll
+ lkQ
rQ Laq + ll
(10-6)
or
(10-4)
where Xad is the reactance corresponding to the fundamental space wave
of armature in the direct axis, Xf is the reactance of the field windings,
Xkd is the reactance of the damper windings in the direct axis, and Xl
is the leakage reactance. Xf and XkD are also akin to leakage reactances.
The inductance giving rise to Xf is lf, and to XkD is lkD. We write:
L F = l f + Lad
X ′′q = X l +
(10-7)
or
where rD and rQ are resistances of the damper windings in the direct
and quadrature axes, respectively.
Decaying ac component of the short-circuit current from the instance of occurrence of fault to steady state. The subtransient, transient,
and steady-state periods and decay characteristics of short-circuit current are shown.
242
CHAPTER TEN
FIGURE 10-6
Equivalent circuits of a synchronous generator during subtransient, transient, and steady-state periods after a terminal fault.
When the flux has penetrated the air gap, the effect of the eddy
currents in the pole face cease after a few cycles given by shortcircuit subtransient time constants. The resistance of damper circuit
is much higher than that of the field windings. This amounts to
opening of the damper winding circuits, and the direct-axis and
quadrature-axis transient reactances are given by:
X ′d = X l +
X X
1
= ad f + X l
1/X ad + 1/X f X f + X ad
X ′q = X l + X aq
(10-8)
(10-9)
The direct-axis transient time constant associated with this decay is:
Td′ =
1 X ad X l
+ X f
ω rF X ad + X l
where rF is the resistance of the field windings.
(10-10)
Finally, when the currents in the field winding have also died
down, given by transient short-circuit time constant, the steadystate short-circuit current is given by the synchronous reactance:
X d = X l + X ad
X q = X l + X aq
(10-11)
Xl, the leakage reactance in the direct and quadrature axes, is known
to be nearly equal, as stated before. The reactances Xad and Xaq are
the mutual reactances between the stator and rotor, and Xd and Xq
are total reactances in the two axes. Equations (10-9) and (10-11)
show that X′q is equal to Xq. The relative values of X′′q , X ′q , and Xq
depend on generator construction. For cylindrical rotor generators,
Xq is >> X′q. Sometimes, one or two damper windings are modeled
in the q-axis.
Reverting to Fig. 10-5, the direct-axis transient reactance determines the initial value OA of the symmetrical transient envelope
ACD and the direct-axis transient short-circuit time constant T′d
determines the decay of this envelope. The direct-axis transient time
TRANSIENT BEHAVIOR OF SYNCHRONOUS GENERATORS
243
constant T′d is the time required by the transient envelope to decay
to a point where the difference between it and the steady-state envelope GH is 1/e (= 0.368) of the initial difference GA. Similar explanation applies to decay of the subtransient component in Fig. 10-5.
The open-circuit direct-axis transient time constant is:
10-5-2
The short-circuit direct-axis transient time constant can be
expressed as:
Fault-Decrement Curve
Based on Fig. 10-5, the expression for decaying ac component of
the short-circuit current of a generator can be written as:
iac = Decaying subtransient component
+ decaying transient component
+ steady-state component
(10-12)
The subtransient current is given by:
E′′
X ′′d
(10-13)
where E″ is the generator internal voltage behind subtransient
reactance.
E′′ = Va + X ′′d sin φ
(10-14)
where Va is the generator terminal voltage, and f is the load power
factor angle, prior to fault.
Similarly, the transient component of the current is given by:
i′d =
E′
X ′d
(10-15)
where E′ is the generator internal voltage behind transient reactance.
E′ = Va + X ′d sin φ
(10-16)
The steady-state component is given by:
V i
id = a F
X d iFg
(10-17)
(10-18)
where Ta is the armature short-circuit time constant, given by:
Ta =
1 2X′′d X ′′q
ω r X′′d + X′′q
(10-19)
where r is the stator resistance.
The open-circuit time constant describes the decay of the field
transient when the field circuit is closed and the armature circuit is
open. The direct-axis subtransient open circuit time constant is:
′′ =
Tdo
1 X ad X f
+ X kD
ω rD X ad + X f
(10-20)
And the quadrature-axis subtransient open-circuit time constant is:
′′ =
Tqo
1
( X + X kQ )
ω rQ aq
(10-22)
(10-23)
It may be observed that the resistances have been neglected in
the previous expressions for current, but these can be included,
that is, the subtransient current is:
E′′
rD + X ′′d
(10-24)
where rD is defined as the resistance of the amortisseur windings
on salient-pole generators and analogous body of cylindrical rotor
generators. Similarly, the transient current is:
i′d =
E′
rf + X ′d
(10-25)
As the resistance is much smaller compared to the reactances, the
impact on the magnitude of the calculated current is negligible.
Example 10-1 Consider a 13.8-kV, 100-MVA, 0.85 power factor
generator. Its rated full-load current is 4184 A. Other data are:
Saturated subtransient reactance, X″dv
= 0.15 per unit
Saturated transient reactance, X′dv
= 0.2 per unit
Synchronous reactance, Xd
= 2.0 per unit
Field current at rated load, if
= 3 per unit
Field current at no-load-rated voltage, ifg
= 1 per unit
Subtransient short-circuit time constant, T ″d = 0.012 s
where iF is the field current at given load conditions (when regulator action is taken into account) and iFg is the field current at noload-rated voltage.
The dc component is given by:
idc = 2i′′d ε −t/Ta
1
[X + X f ]
ω rF ad
X′
X′
d
′
′ d
Td′ = Tdo
= Tdo
Xd
( X ad + X l )
i′′d =
= (i′′d – i′d )ε −t/Td′′ + (i′d – id )ε −t/Td′ + id
i′′d =
′ =
Tdo
(10-21)
Transient short-circuit time constant, T′d
= 0.35 s
Armature short-circuit time constant, Ta
= 0.15 s
Effective resistance*
= 0.0012 per unit
Quadrature-axis synchronous reactance*
= 1.8 per unit
A three-phase short circuit occurs at the terminals of the generator when it is operating at its rated load and power factor. It is
required to construct a fault decrement curve of the generator for
(a) ac component, (b) dc component, and (c) total current. Data
marked with an asterisk are intended for Example 10-4.
From Eq. (10-14), the voltage behind subtransient reactance at
the generator-rated voltage, load, and power factor is:
E′′ = V + X ′′d sin φ = 1 + (0 . 15)(0 . 527 ) = 1 . 079
From Eq. (10-13), the subtransient component of the current is:
i′′d =
E′′ 1 . 079
=
pu = 30.10 kA
X ′′dv
0 . 15
Similarly from Eq. (10-16), E′, the voltage behind transient
reactance is 1.1054 per unit, and from Eq. (10-15), the transient
component of the current is 23.12 kA.
From Eq. (10-17), current id at constant excitation is 2.09 kA
rms. For a ratio of if /iFg = 3, current id = 6.28 kA rms. Therefore,
244
CHAPTER TEN
F I G U R E 1 0 - 8 Representation of magnetically coupled coils; a
two-winding transformer.
FIGURE 10-7
Calculated fault decrement curves of generator,
Example 10-1.
the following equation can be written for the ac component of the
current:
iac = 6 . 98e −t / 0.012 + 20 . 03e −t / 0.35 + 2.09 kA
With full-load excitation:
iac = 6 . 98e −t / 0.012 + 16 . 84e −t / 0.35 + 6.28 kA
The ac decaying component of the current can be plotted from
these two equations, with lowest value of t = 0.01 s to t = 1,000 s.
The dc component is given by Eq. (10-18):
idc = 2i′′d e −t / Ta = 42 . 57e −t / 0.15 kA
At any instant, the total current is:
2
2
iac
+ idc
kA rms
The fault decrement curves are shown in Fig. 10-7. Short-circuit
current with constant excitation is 50 percent of the generator fullload current. This can occur for a stuck voltage regulator condition.
Though this current is lower than the generator full-load current,
it cannot be allowed to be sustained. Voltage restraint or voltagecontrolled overcurrent generator backup relays (ANSI/IEEE device
number 51V) or distance relays (device 21) are set to pick up on
this current. The generator fault decrement curve is often required
for the appropriate setting and coordination of these relays with the
system relays.
10-6
CIRCUIT EQUATIONS OF UNIT MACHINES
The behavior of machines can be analyzed in terms of circuit theory, which makes it useful not only for steady-state performance
but also for transients. The circuit of machines can be simplified in
terms of coils on the stationary (stator) and rotating (rotor) parts,
and these coils interact with each other according to fundamental
electromagnetic laws. The circuit of a unit machine can be derived
from the consideration of generation of EMF in coupled coils due
to (a) transformer EMF, also called pulsation EMF, and (b) the EMF
of rotation.
Consider two magnetically coupled, stationary, coaxial coils,
as shown in Fig. 10-8. Let the applied voltages be v1 and v2 and
currents i1 and i2, respectively. This is, in fact, the circuit of a twowinding transformer, the primary and secondary being represented
by single-turn coils. The current in primary coil (any coil can be
called a primary coil) sets up a total flux linkage Φ11. The change
of current in this coil induces an EMF given by:
e11 = −
dΦ11
dΦ di
di
= − 11 1 = −L11 1 = −L11pi
dt
di1 dt
dt
(10-26)
where L11 = –dΦ11 /di1 is the total primary self-inductance and the
operator p = d/dt.
If Φ1 is the leakage flux and Φ12 is the flux linking with secondary coil, then the variation of current in the primary coil induces in
the secondary coil an EMF:
e12 = −
di
dΦ12
dΦ di
= − 12 ⋅ 1 = −L12 i = −L12 pi1
dt
di1 dt
dt
(10-27)
where L12 = –dΦ12 /di1 is the mutual inductance of the primary coil
winding with the secondary coil winding.
Similar equations apply for the secondary coil winding. All the
flux produced by the primary coil winding do not link with the secondary. The leakage inductance associated with the windings can
be accounted for as:
L11 = L12 + L1
(10-28)
L22 = L21 + L2
The mutual inductance between coils can be written as:
L12 = L21 = L m = ( L11 − L1 )( L22 − L2 ) = k L11L22 (10-29)
Thus, the equations of a unit transformer are:
v1 = r1i1 + ( L m + L1 )pi1 + L m pi2
(10-30)
v2 = r2i2 + ( L m + L2 )pi 2 + L m pi1
Or, in the matrix form:
va
r + ( L1 + L m )p
Lm p
= 1
vb
Lm p
r2 + ( L2 + L m )p
i1
i2
(10-31)
TRANSIENT BEHAVIOR OF SYNCHRONOUS GENERATORS
To summarize, a pulsation EMF is developed in two coaxial coils
and there is no rotational EMF. Conversely, a rotational EMF is developed in two coils at right angles, but no pulsation EMF. If the relative
motion is at an angle θ , the EMF of rotation is multiplied by sinq.
If the magnetic axes of the coupled coils are at right angles, no
mutually induced pulsation or transformer EMF can be produced by
variation of currents in either of the windings. However, if the coils
are free to move, the coils with magnetic axes at right angles have an
EMF of rotation, er, induced when the winding it represents rotates:
e r = ωr Φ
245
e r = ωr Φ sin θ
(10-32)
(10-33)
The equations of a unit machine may be constructed based on
the simple derivation of EMF in the coils. Consider a generator with
direct- and quadrature-axes coils, as shown in Fig 10-9a, and its
resolution into Figs. 10-9b and c. Note that the armature is shown
rotating, and it has two coils, D and Q, at right angles to each other
in dq axes. The field winding F and the damper winding kD are
shown stationary in the direct axis. All coils are single-turn coils. In
the direct axis, there are three mutual inductances, that is, of D with
kD, kD with F, and F with D. A simplification is to consider that these
are all equal; inductance L ad. Each coil has a leakage inductance of
its own. Consequently, the total inductances of the coils are:
where w r is the angular speed of rotation and Φ is the flux. This
EMF is maximum when the two coils are at right angles to each
other and zero when these are cophasial.
Coil D: (ld + Lad)
Coil kD: (lkD + Lad)
Coil F: (lf + Lad)
(10-34)
The mutual linkage with armature coil D when all three coils
carry currents is:
λd = Lad (iF + iD + id )
(10-35)
where iF, iD, and id are the currents in the field, damper, and directaxis coils, respectively. Similarly, in the quadrature axis:
λq = Laq (iq + iQ )
(10-36)
The EMF equations in each of the coils can be written based on
these observations. Field coil: No q-axis circuit will affect its flux,
nor do any rotational voltages appear. The applied voltage vf is:
v f = rF iF + ( Lad + l f )piF + Lad pi D + Lad pid
(10-37)
Stator coil kD is similarly located as coil F:
v D = rDi D + ( Lad + lkD )pi D + Lad piF + Lad pid
(10-38)
Coil kQ has no rotational EMF, but will be affected magnetically by
any current iQ in coil Q:
vQ = rQiQ + ( Laq + lkQ )piQ + Laq piq
(10-39)
Armature coils D and Q have the additional property of inducing rotational EMF:
vd = rd id + ( Lad + ld )pid + Lad piF + Lad pi D
+ Laqωr iQ + ( Laq + lq )ωr iq
vq = rqiq + ( Laq + lq )piq + Laq piQ − Ladωr iF
FIGURE 10-9
− Ladωr i D − ( Lad + ld )ωr id
(a) Development of circuit of a synchronous generator;
general machine theory and concepts of unit machine. (b), (c) Resolution of
circuit of Fig. 10-9a into direct and quadrature axes.
vf
vD
vQ =
vd
vq
rF + ( Lad + l f )p
Lad p
.
Lad p
(10-40)
These equations can be written in a matrix form:
.
.
rD + ( Lad + lkDD )p
.
rQ + ( Laq + lkQ )p
Lad p
.
iF
Lad p
.
.
Laq p
iD
iQ
id
iq
Lad p
Lad p
Laqωr
rd + ( Lad + ld )p
( Laq + lq )ωr
−Ladωr
−Ladωr
Laq p
−( Lad + ld )ωr
rq + ( Laq + lq )p
(10-41)
246
10-7
CHAPTER TEN
PARK’S TRANSFORMATION
Park’s transformation greatly simplifies the mathematical model of
synchronous machines. It describes a new set of variables, such as
currents, voltages, and flux linkages, obtained by transformation of
the actual (stator) variables in three axes: 0, d, and q. The d and q
axes are already defined, the 0 axis is a stationary axis.
10-7-1 Reactance Matrix of a Synchronous Generator
Consider the normal construction of a three-phase synchronous
generator, with three-phase stationary ac windings on the stator
and the field and damper windings on the rotor, Fig. 10-10. The
stator inductances vary, depending on the relative position of the
stator and rotor. Consider that the field winding is cophasial with
the direct axis, and also the direct axis carries a damper winding.
The q-axis has also a damper winding. The phase windings are
distributed, but are represented by single-turn coils aa, bb, and
cc in Fig. 10-10. The field flux is directed along d-axis, and therefore the machine-generated voltage is at right angles to it, along
q-axis. For generator action, the generated voltage vector E leads
the terminal voltage vector V by an angle, and from basic machine
theory we know that it is the torque angle. At t = 0, the voltage
vector V is located along the axis of phase a, which is the reference axis in Fig. 10-10. The q-axis is at an angle d, and the d-axis
is at an angle δ + π /2 . For t > 0, the reference axis is at an angle
ωr t with respect to the axis of phase a. The d-axis of the rotor is
therefore at:
θ = ωrt + δ + π /2 rad
(10-42)
For synchronous operation, ωr = ω0 = constant.
Consider phase a inductance. It is a combination of its own selfinductance Laa and its mutual inductances Lab and Lbc with phases
b and c. All three inductances vary with the relative position of the
rotor with respect to stator because of saliency of air gap. When
the axis of phase a coincides with direct axis, that is, θ = 0 or π ,
the resulting flux of coil aa is maximum in the horizontal direction
and its self-inductance is maximum. When at right angles to d-axis,
θ = π / 2 or 3π / 2, its inductance is a minimum. Thus, Laa fluctuates
twice per revolution and can be expressed as:
Laa = L s + L m cos θ
(10-43)
Similarly, self-inductance of phase b is maximum at θ = 2π / 3 and
of phase c at θ = −2π / 3:
π
L bb = L s + L m cos 2 θ − 2
3
π
Lcc = L s + L m cos 2 θ + 2
3
(10-44)
Phase-to-phase mutual inductances are also a function of q. Lab
is negative and is maximum at θ = −π /6. This can be explained as
follows: For the direction of currents shown in coils aa and bb, Lab is
negative. When the angle is – π /3, the current in phase b coil generates the maximum flux, but the linkage with phase a coil is better when
the angle is zero degrees. However, at this angle the flux is reduced.
The maximum flux linkage can be considered to take place at an
angle which is the average of these two angles, that is, π /6.
π
Lab = − M s + L m cos 2 θ +
6
π
L bc = − M s + L m cos 2 θ −
2
(10-45)
π
Lca = − M s + L m cos 2 θ + 5
6
Stator-to-rotor mutual inductances are the inductances between
stator windings and field windings, between stator windings and
direct-axis damper windings, and between stator windings and
quadrature-axis damper windings. These reactances are:
From stator phase windings to field windings:
LaF = M F cos θ
L bF = M F cos(θ − 2π / 3)
(10-46)
LcF = M F cos(θ + 2π / 3)
From stator phase windings to direct-axis damper windings:
LaD = M D cos θ
L bD = M D cos(θ − 2π / 3)
(10-47)
LcD = M D cos(θ + 2π / 3)
And from stator phase windings to damper windings in the quadrature
axis:
LaQ = MQ sin θ
L bQ = MQ sin(θ − 2π / 3)
(10-48)
LcQ = MQ sin(θ + 2π / 3)
The rotor self-inductances are LF, LD, and LQ. The mutual inductances are:
LDF = M R
L FQ = 0
LDQ = 0
(10-49)
The mutual inductance between field windings and direct-axis
damper windings are constant and do not vary. Also d and q axes
are 90° displaced and the mutual inductances between the field and
direct-axis damper windings and quadrature-axis damper windings
are zero.
The inductance matrix can therefore be written as:
FIGURE 10-10
Representation of dq axes, windings, and reference
axis of a synchronous generator.
L=
Laa
LRa
LaR
LRR
(10-50)
TRANSIENT BEHAVIOR OF SYNCHRONOUS GENERATORS
247
where Laa is a stator-to-stator inductance matrix.
Laa =
LaR =
LtRa
−M s − L m cos 2(θ + π / 6) −M s − L m cos 2(θ + 5π / 6)
L s + L m cos 2θ
−M s − L m cos 2(θ + π / 6) L s + L m cos 2(θ − 2π / 3) −M s − L m cos 2(θ − π / 2)
−M s − L m cos 2(θ + 5π / 6) −M s − L m cos 2(θ − π / 2) L s + L m cos 2(θ + 2π / 3)
M F cos θ
M D cos θ
MQ sin θ
= M F cos(θ − 2π / 3) M D cos(θ − 2π / 3) MQ sin(θ − 2π / 3)
M F cos(θ + 2π / 3) M D cos(θ + 2π / 3) MQ sin(θ + 2π / 3)
To transform the stator-based variables into rotor-based variables, define a matrix as follows:
(10-52)
LRR
(10-53)
The inductance matrix of Eq. (10-51) shows that the inductances vary with the angle q. By referring the stator quantities to
rotating rotor dq axes through Park’s transformation, this dependence on q is removed and a constant reactance matrix emerges.
10-7-2
ia
id
ib
iF
0
0
LQ
MR
LD
0
i0
iq
LRR rotor-to-rotor inductance’s matrix is:
LF
= MR
0
iD
iD
iQ
iQ
λ0dq
2
2π
cos θ +
3
2π
sin θ +
3
ia
ib
ic
(10-58)
=B i
λabc
= P 0
0 1
λFDQ
λFDQ
= P 0
0 1
Laa
LaR
LRa
LRR
P −1
0
0
1
P 0
0 1
iabc
iFDQ
(10-59)
This transformation gives:
λ0
λd
λq
1
2
2
i0
2π
2
cos θ cos θ −
id =
3
3
iq
2π
sin θ sin θ −
3
iF
where 1 is 3 × 3 unity matrix and 0 is 3 × 3 zero matrix. The original
rotor quantities are left unchanged. The time-varying inductances can
be simplified by referring all quantities to rotor frame of reference:
Park’s transformation describes a new set of variables, such as currents, voltages, and flux linkages in 0dq axes. The stator parameters are transferred to the rotor parameters. For the currents, this
transformation is:
1
ic
= P 0
0 1
Transformation of Reactance Matrix
1
(10-51)
(10-54)
λF
λD
λQ
=
L0
0
0
0
Ld
0
0
0
Lq
0 kM F
0
0 kM D
0
0
0 kMQ
0
0
0
kM F kM D 0
0
0 kM q
LF
MR
0
MR
LD
0
0
0
LQ
i0
id
iq
iF
iD
iQ
(10-60)
Define:
Using matrix notation:
3
L
2 m
3
Lq = L s + M s − L m
2
L0 = L s − 2M s
Ld = L s + M s +
i0dq = P iabc
(10-55)
Similarly:
k=
v0dq = Pvabc
(10-56)
λ0dq = Pλabc
where λ is the flux linkage vector. The abc currents in the stator
windings produce a synchronously rotating field, stationary with
respect to rotor. This rotating field can be produced by constant
currents in the fictitious rotating coils in dq axes. P is nonsingular
and P −1 = P t :
2
2
3
3
2
The inductance matrix is sparse, symmetric, and constant. It
decouples the 0dq axes, as will be illustrated further.
10-8
PARK’S VOLTAGE EQUATION
The voltage equation in terms of current and flux linkages is:
v = −R i −
dλ
dt
(10-62)
or
1
P −1 = P t =
(10-61)
1
2
1
2
cos θ
sin θ
2π
2π
cos θ − sin θ −
3
3
2π
2π
cos θ + sin θ +
3
3
(10-57)
va
r
vb
0
0
vc
=
0
vF
0
vD
0
vQ
0
r
0
0
0
0
0 0
0 0
r 0
0 rF
0 0
0 0
0
0
0
0
rD
0
0
0
0
0
0
rQ
ia
λa
ib
λb
ic
di λc
−
iF
dt λF
iD
λD
iQ
λQ
(10-63)
248
CHAPTER TEN
This can be partitioned as:
The torque equation can be written as:
iabc
di λabc
−
iFDQ
dt λFDQ
vabc
r
=−
rFDQ
vDFQ
The transformation is given by:
B−1 vB = −R B−1 iB −
d −1
(B λB )
dt
(10-65)
where:
B
B
P
0
0
1
λabc
λFDQ
=B
=
B
λ0dq
λFDQ
i0dq
iabc
=
= iB
iFDQ
iFDQ
= λB
v0 = ri0 −
(10-75)
Direct axis:
(10-67)
First evaluate:
dP −1
0 = P
dθ
0
0
0 0 0
dP −1
= 0 0 1
dθ
0 −1 0
vd = −rid −
dλ
dθ
λ − d
dt q dt
vF = rF iF +
dλF
dt
v D = rD iD +
(10-76)
dλ D
=0
dt
Quadrature axis:
0
(10-68)
0
It can be shown that:
P
d λ0
dt
(10-66)
d −1
(B λB )
dt
dP −1
dθ
0
(10-69)
We can write:
vq = −riq +
d λq
dθ
λd −
dt
dt
vQ = rQiQ +
dλQ
=0
dt
(10-77)
The decoupled equations relating to flux linkages and currents are:
Zero sequence:
λ0 = L 0 i 0
dB−1 dB−1 dθ
=
dt
dθ dt
(10-70)
0 0
0 0
dB−1
B
= 0 −1
0 0
dθ
0 0
0 0
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
(10-71)
dθ
dt
Direct axis:
λd
Ld kM F kM D
λF = kM F L F
MR
λD
kM D M R
LD
λq
λQ
(10-72)
Substituting in Eq. (10-67), the voltage equation becomes:
0
λq
dλB
dθ −λ
vB = R iB −
d −
dt 0
dt
0
0
(10-78)
id
iF
iD
(10-79)
Quadrature axis:
We write:
dB−1
dB−1
B
= B
dt
dθ
(10-74)
From the previous treatment, the following decoupled voltage
equations can be written as follows:
Zero sequence:
Equation (10-65) can be written as:
dB−1
= P 0
B
dθ
0 1
TE = [i0 , id , iq , iF , i D , iQ ] −λd = id λd − iq λq
0
0
0
10-9 CIRCUIT MODEL OF SYNCHRONOUS
GENERATORS
v0dq
vabc
=
= vB
vFDQ
vFDQ
vB = −BRB−1 − B
0
λq
(10-64)
=
Lq
kMQ
iq
kMQ
LQ
iQ
This decoupling is shown in equivalent circuits in Fig. 10-11. It
can be shown that:
Direct axis:
vd = −rid − ld id − Lad (id + iF + iD )
−vF = rF iF − l f iF − Lad (id + iF + iD )
(10-73)
When the shaft rotation is uniform, dq/dt is a constant, and
Eq. (10-73) is linear and time invariant.
(10-80)
(10-81)
v D = −rDi D − lkDiD − Lad (id + iF + iD )
where ld , l f , l D = self-inductance in armature field and damper circuits and, Lad is defined as:
Lad = L D − l D = Ld − ld = L F − l f = kM F = kM D = M R (10-82)
TRANSIENT BEHAVIOR OF SYNCHRONOUS GENERATORS
FIGURE 10-11
Decoupled circuits of a synchronous generator in 0dq axes.
Quadrature axis:
vq = −rqiq − lqiq − L aq (iq + iQ ) + ωλd
vQ = 0 = −rQiQ − lkQiQ − L aq (iq + iQ )
(10-83)
where:
Laq = Lq − lq = LQ − lkQ = kMQ
249
(10-84)
Figure 10-12a and b depict d and q equivalent circuits. Figure 10-12c
and d are commonly used simplified circuits, which do not show voltage-speed terms. These are adequate to derive λd and λq, including
their derivatives.
10-10 CALCULATION PROCEDURE
AND EXAMPLES
There are three steps involved:
1. The problem is normally defined in stator parameters, which
are of interest. These are transformed into 0dq axes variables.
These three steps are inherent in any calculation using transformations. For simpler problems, it may be advantageous to solve directly in
stator parameters. Figure 10-13 illustrates two-way transformations.
Example 10-2 Calculate time variation of direct-axis, quadratureaxis voltages and field current, when a step function of field voltage is
suddenly applied to a generator at no load. Neglect damper circuits.
As the generator is operating without load, iabc = i0dq = 0. Therefore, from Eqs. (10-78)–(10-80):
λ0 = 0
λd = kM F iF
λF = L F iF
λq = 0
From Eqs. (10-75)–(10-77):
v0 = 0
d λd
di
= −kM F F
dt
dt
diF
vF = rF iF + L F
dt
vq = ω0 λd = ω0kM F iF
vd = −
2. The problem is solved in 0dq axes parameters, using Park’s
transform or other means.
Therefore, as expected, the time variation of field current is:
3. The results are transformed back to abc variables of interest,
using inverse Park’s transformation.
iF =
vF
(1 − e (−rF / LF )t )
rF
250
CHAPTER TEN
FIGURE 10-12
(a) and (b) Commonly used dq axes circuits of a synchronous generator, terminal voltage relations. (c) and (d ) Flux relations.
The direct-axis and quadrature-axis voltages are given by:
vd = −
kM F vF −(rF /LF )t
e
LF
ω kM F vF
(1 − e −(rF /LF )t )
vq = −
rf
This is a simple case of transformation using Eq. (10-57):
1
The phase voltages can be calculated using Park’s transformation.
Example 10-3 A generator is operating with balanced positive
sequence voltage of va = 2 | V | cos(ω0t+ <V ) across its terminals.
The generator rotor is described by:
θ = ω1t +
π
+δ
2
Find v0, vd, and vq.
1
2
v0
vd =
vq
1
2 |V |
3
2
2
2π
2π
cos θ cos θ − cos θ +
3
3
sin θ
cos(ω0t + <V )
2π
cos ω0t + <V −
3
4π
cos ω0t + <V −
3
2π
sin θ −
3
2π
sin θ +
3
TRANSIENT BEHAVIOR OF SYNCHRONOUS GENERATORS
FIGURE 10-13
Park’ s transformation and inverse Park’s transformation of circuits of a synchronous generator.
Therefore, Va can be written as:
A solution of this equation gives:
vd = 3 | V | sin[(ω0 − ω1 ) t + <V − δ]
vq = 3 | V | cos[(ω0 − ω1 ) t + <V − δ]
(10-85)
These relations apply equally well to derivation of id, iq, λd, and λq.
For synchronous operation, w1 = w0, and the equations reduce to:
vd = 3 | V | sin[<V − δ]
vq = 3 | V | cos[<V − δ]
(10-86)
Note that vq and vd are now constant and do not have the slip frequency term w1 – w0.
We can write:
vq + jvd = 3 | V | e j(<V − δ ) = 3Va e − jδ
251
(10-87)
v
v
q
Va =
+ j d e jδ = (Vq + jVd ) e jδ
3
3
(10-88)
where:
Vq = vq / 3 ,
Vd = vd / 3
(10-89)
This is shown in the phasor diagram of Fig. 10-14. We can write
these equations in the following form:
Re Va
cos δ
=
Im Va
sin δ
Vq
Vd
=
− sin δ Vq
cos δ Vd
cos δ sin δ
− sin δ cos δ
Re Va
Im Va
(10-90)
(10-91)
252
CHAPTER TEN
FIGURE 10-14
Phasor diagram illustrates relationship of dq axes
voltage to terminal voltage.
10-11 STEADY-STATE MODEL OF
SYNCHRONOUS GENERATOR
Based on previous equations, we can derive a steady-state model of
a synchronous generator and its phasor diagram.
In the steady state, all the currents and flux linkages are constant.
Also i0 = 0 and rotor damper currents are zero. The Eqs. (10-78)–
(10-80) reduce to:
vd = −rid − ω0 λq
vq = −riq + ω0 λd
(10-92)
vF = rF iF
The phasor diagram is shown in Fig. 10-15a. The open-circuit
voltage on no load is a q-axis quantity and is equal to the terminal
voltage.
To facilitate the location of q-axis, Fig. 10-15b is drawn. The
terminal voltage, current, and power factor of the generator will
be normally known. As the components Id and Iq are not initially
known, the phasor diagram is constructed by first laying out the
terminal voltage Va and line current Ia at correct phase angle φ , then
adding the resistance drop and reactance drop Ia Xq. At the end of
this vector, quadrature axis is located. Now the current is resolved
into direct-axis and quadrature-axis components. This enables construction of vectors Iq Xq and Id Xd.
Figure 10-15c is further elucidation of the construction. The
relations of triangle BCD in Fig. 10-15b and its construction are
clearly shown in this figure.
Example 10-4 Consider generator data of Example 10-1. Calculate the direct- and quadrature-axis components of the currents
and voltages and machine voltage E when the generator is delivering its full-load-rated current at its rated voltage. Also calculate all
the angles shown in phasor diagram Fig. 10-15a. If this generator
is connected to an infinite bus through an impedance of 0.01 + j0.1
per unit (100-MVA base), what is the voltage of the infinite bus?
The generator operates at a power factor of 0.85 at its rated voltage of 1.0 per unit. Therefore, f = 31.8°. The generator full-load
current is 4183.8 A = 1.0 per unit. The terminal voltage vector can
be drawn to scale, Ir drop (= 0.0012 per unit) is added and vector
Ia Xq = 1.8 per unit drawn to locate the q-axis. Current I can be
resolved into direct-axis and quadrature-axis components and the
phasor diagram completed, as shown in Fig. 10-16, and the values of
Vd, Id, Vq, Iq, and E can be read from it. This requires that the phasor
diagram is constructed to scale. The analytical solution is as follows:
The load current is resolved into active and reactive components, Ir = 0.85 per unit and Ix = 0.527 per unit, respectively.
Then, from the geometric construction shown in Fig. 10-16:
X I + rI
q r
x
(δ − β ) = tan −1
V
rI
X
I
+
−
r
q x
a
(1 . 8)(0 . 85) + (0 . 0012)(0 . 527 )
= tan −1
= 38 . 14 °
1 + (0 . 0012)(0 . 85) + (1 . 8)(0 . 527 )
where:
λd = Ld id + kM F iF
λF = kM F id + LF iF
(10-93)
λq = L q i q
I q = I a cos(δ − β − φ ) = 0 . 343 pu, iq = 0 . 594 pu
Substitute values of λd and λq, and then from Eqs. (10-88) and
(10-89), we can write the following equation:
Va = −r(I q + jI d )e + ω0 Ld I d e − jω0 LqI qe +
jδ
jδ
jδ
1
2
ω0 M F iF e
jδ
(10-94)
I d = −I a sin(δ − β − φ ) = − 0 . 939 pu, id = − 1 . 626 pu
And
Vq = Va cos(δ − β ) = 0 . 786 pu, vq = 1 . 361 pu
Vd = −Va sin(δ − β ) = − 0 . 618 pu, vd = 1 . 070 pu
The machine-generated voltage is:
where:
id = 3 I d ,
Note that the resistance can even be ignored from the above
calculation without an appreciable error. Thus, δ − β + φ = 69.93°.
This is the angle of current vector with q-axis. Therefore:
iq = 3 I q
(10-95)
The infinite bus voltage is simply the generator terminal voltage
less the IZ drop subtracted as a vector:
Define:
2 E = ω0 M F iF e jδ
(10-96)
This is the no-load voltage or the open-circuit voltage with generator current = 0. Then, we can write:
E = Va + rI a + jX d I d e jδ + jX qI qe jδ
E = Vq + rI q − X d I d = 2 . 66 pu
(10-97)
V∞ = Va∠0 ° − I a∠31 . 8 ° Z∠84 . 3 ° = 0 . 94∠− 4 . 8 °
The infinite bus voltage lags the generator voltage by 4.8°. Practically, the infinite bus voltage will be held constant and the generator
voltage changes, depending on the system impedance and generator
output.
TRANSIENT BEHAVIOR OF SYNCHRONOUS GENERATORS
253
FIGURE 10-15
(a) Phasor diagram of a synchronous generator in steady state. (b) An alternate form of the phasor diagram. (c) Details of construction,
and location of q-axis in phasor diagram of Fig. 10-15b.
FIGURE 10-16
Phasor diagram for solution of Example 10-4.
10-12 SYMMETRICAL SHORT CIRCUIT OF A
GENERATOR AT NO LOAD
The equations for the terminal three-phase short circuit of a generator at no load are important, in the sense that ANSI/IEEE calculations in [Ref. 3] are based on it. The ANSI/IEEE calculations for
calculating of short-circuit duties on switching devices do not consider
prior loading. We will ignore damper circuit and resistances and
neglect the change in speed during short circuit.
Ignoring the damper circuit means that the subtransient effects are
ignored. As the generator is operating at no load, prior to the fault,
iabc = i0dq = 0.
Subsequent to fault instant, vabc =v0dq = 0. We will also ignore
all resistances.
254
CHAPTER TEN
From Eq. (10-76) for t ≥ 0.
Note that k =
Zero sequence:
iabc = P i0dq
di0
=0
dt
v0 = − L 0
With θ = ω0t + π / 2 + δ , the short-circuit current in phase a is:
Direct axis:
vd = −ω0 λq −
vf =
1
X q − X ′d
X q − X ′d
ia = 2 E sin(ω0t + δ ) −
sinδ −
sin(2ω t + δ )
2 X ′d X q
2 X ′d X q
X ′d
d λd
=0
dt
dλF
dt
(10-103)
Quadrature axis:
v q = ω 0 λd −
d λq
dt
=0
The flux linkages can be expressed in terms of currents by using
Eqs. (10-79) and (10-80):
did
di
+ kM F F = 0
dt
dt
did
diF
v f = kM F
+ LF
dt
dt
diq
=0
−ω0 Ld id − ω0kM F iF + Lq
dt
ω 0 L q iq + L d
(10-98)
These equations can be solved using Laplace Transform. The
initial conditions are:
id (0− ) = iq (0− ) = 0
iF (0
−
The first term is normal-frequency short-circuit current, the second term is dc or unidirectional term, and the third term is doublefrequency short-circuit current. The 120-Hz component imparts a
nonsinusoidal characteristic to short-circuit current waveform. It
rapidly decays to zero and is ignored in the calculation of shortcircuit currents.
When damper winding circuit is considered, the short-circuit
current can be expressed as:
1
sin(ω t + δ ) + 1 − 1 e −t / Td′ sin(ω t + δ )
X d
X ′d X d
1
( X ′′d + X ′′q ) −t / T
1 −t / Td′′
e a sin δ
ia = 2 E + − e
sin(ω t + δ ) −
2 X ′′d X ′′q
X ′′d X ′d
( X ′′d − X ′′q ) −t / T
e a sin(2ω t + δ )
−
′′
′′
2
X
X
d q
(10-104)
■
The first term is final steady-state short-circuit current.
■
) = iF0
Also from Eq. (10-96) we demonstrated that at no load, prior
to fault, the terminal voltage is equal to the generated voltage, and
this voltage is:
2 Ea = ω 0 M F i F e j δ
and this is a quadrature axis quantity, also:
kM F = Lad = X ad /ω
L F = ( X f + X ad )/ω
sLd
3 / 2 . Apply:
skM F
skM F
sL F
−ω0 Ld −ω0kM F
ω0 Lq
0
sLq
id
kM F
iF = L iF0
F
iq
0
(10-99)
Solution of these equations, after simplification, will give:
id (t ) =
3Ea (0)
(cos ω0t − 1)
X ′d
(10-100)
iq (t ) =
3Ea (0)
sin ω0t
Xq
(10-101)
X X
iF (t ) = d − d − 1 cos ω 0 t iF0
X ′d X ′d
(10-102)
The second term is normal-frequency decaying transient
current.
■
The third term is normal-frequency decaying subtransient
current.
■
The forth term is asymmetric decaying dc current.
■
The fifth term is double-frequency decaying current.
Example 10-5 Calculate the components of short-circuit currents at the instant of three-phase terminal short circuit of the generator, particulars as shown in Table 10-1. Assume that phase a
is aligned with the field at the instant of short circuit, maximum
asymmetry, that is δ = 0. The generator is operating at no load prior
to short circuit.
The calculations are performed by substituting the required
numerical data from Table 10-1 in Eq. (10-104).
Steady-state current = 2.41 kA rms
Decaying transient current = 20.24 kA rms
Decaying subtransient current = 5.95 kA rms
Decaying dc component = 43.95 kA
Decaying second-harmonic component = 2.35 kA rms
Note that second-harmonic component is zero if the direct-axis
and quadrature-axis subtransient reactances are equal. Also, dc
TRANSIENT BEHAVIOR OF SYNCHRONOUS GENERATORS
component in this case is equal to 40.44 kA. These are the current
values at the instant of short circuit.
10-13
MANUFACTURER’S DATA
The relation between the various inductances and the data commonly supplied by a manufacturer for a synchronous generator is
not obvious. Following relations hold:
Lad = Ld − ll = kM F = kM D = M R
Laq = Lq − ll = kMQ
Lad ( L′d − ll )
( Ld − L′d )
(10-105)
(10-106)
and
L F = l f + Lad
(10-107)
The damper leakage reactance in the direct axis is:
L kD =
Ladl f ( L′′d − ll )
Ladl f − L F ( L′′d − ll )
(10-108)
and
L D = lkD + Lad
L kQ =
Laq ( L′′q − ll )
(10-109)
( Lq − L′′q )
In the quadrature axis, the damper leakage reactance is:
LQ = lkQ + Laq
(10-110)
The field resistance is:
rF =
LF
′
Tdo
(10-111)
The damper resistances in direct axis can be obtained from:
Td′′ =
( L D L F − L2ad ) L′′d
rD L F
L′d
(10-112)
and in the quadrature axis:
L′′
q
Tq′′ =
Lq
L
Q
rQ
Laq = Xq – Xl = 1.858 – 0.164 = 1.694 per unit = kMQ
lf = (1.785)(0.278 – 0.164)/(1.964 – 0.278) = 0.121 per unit
LF = 0.121 + 1.785 = 1.906 per unit
lkD = (1.785)(0.121)(0.193 – 0.164)/{(1.785)(0.164)
– 1.096(0.193 – 0.164)} = 0.026 per unit
LD = 0.026 + 1.785 = 1.811 per unit
Here, ll is the leakage inductance corresponding to Xl in Eq. (10-4).
Lad is the mutual inductance between the armature and rotor, which
is = mutual inductance between field and rotor, which is = mutual
inductance between damper and rotor. Similar relations are assumed
in the q-axis. In some texts, different symbols are used. Field leakage
reactance lf is:
lf =
255
(10-113)
In some texts, different symbols are used:
Lffd = total field inductance = Lfd (field leakage inductance) + Lafd
(mutual field inductance to d-axis).
This is identical to Eq. (10-107). Similarly, in the damper circuit (Lkkd = Lkd + Lakd; Lkkq =Lkq + Lakq), these are equivalent to Eqs.
(10-109) and (10-110).
Example 10-6 Using the manufacturer’s data given in Table 10-1,
calculate the generator parameters in d-q axes.
Applying the equations derived above:
Lad = Xd – Xl = 1.949 – 0.164 = 1.785 per unit = kMF = kMD = MR
lkQ = (1.694)(0.192 – 0.164)/(1.858 – 0.192) = 0.028 per unit
LQ = 0.028 + 1.694 = 1.722 per unit
T′do = 5.615 s = 2116.85 rad
rF = 1.906/2116.85 = 1.005 × 10-5 per unit
rD =
(1 . 811)(1 . 906) − 1 . 7852 0 . 19 3
= 0.0131 per unit
(0 . 015)(377 )(1 . 906) 0 . 278
0 . 192 1 . 722
rQ =
= 0.031 per unit
1 . 858 0 . 015 × 377
Per unit system for synchronous generators is not straightforward, and variations in literature exist.4
10-14 INTERRUPTION OF CURRENTS WITH
DELAYED CURRENT ZEROS
Large generators have high effective X/R ratios, and combined with
other generator time constants and parameters, a current zero may
not be obtained at contact parting of the circuit breaker, that is
the dc component of the short-circuit current at the contact parting time is higher than the peak ac component. This is well documented in Refs. 5–7.
ANSI/IEEE Std. C37.0107 cautions that the longer dc time constants can cause a problem with SF6- type puffer circuit breakers.
The interrupting window, which is the time difference between the
minimum and maximum arcing times, may be exceeded because of
delayed current zero, and arc energy and interruption window are
of concern. The calculation methods described in this standard are
qualified that the E/Z method of calculation with adjustments of ac
and dc decrements can be used, provided the X/R does not exceed
45 at 60 Hz, that is, the dc time constant is not more than 120 ms,
yet this qualification is mostly ignored in the industry.
IEEE Std. C37.0138 for generator circuit breakers specifies that
the the degree of asymmetry from generator source does not exceed
110 percent. It states that at the time of current interruption, the arc
fault resistance will add to the generator armature resistance. This
reduces the time constant of the dc component and forces it to decay
faster:
Ta =
X ′′d
2π f (R a + R add )
(10-114)
where Ta is the armature time constant, Ra is the armature resistance, Radd is the added arc resistance, X″d is the subtransient reactance, and f is the system frequency. Figure 10-17 shows this effect
on decay of the dc component and the current zero obtained at
the contact parting time. However, the performance with arc fault
resistance is difficult to simulate and demonstrate even in a test
station.
When no current zero is obtained, the current interruption in
this mode will be equivalent to that of interrupting a dc current
without current zero crossing. The high-voltage circuit breakers
have limited interrupting capability in this mode of operation,
unless specifically designed to introduce resistance in the arc fault
256
CHAPTER TEN
F I G U R E 1 0 - 1 7 Illustrates that a current zero may be brought by arc
resistance added at the time of current interruption, forcing a current zero.
path at current zero. Generator circuit breakers capable of interrupting with 130 percent asymmetry at the contact parting time
are commercially available. Current technologies in some SF6
breaker designs use arc rotation techniques to force a current zero.
The vacuum interruption technology may also achieve the same
results. The available continuous current rating and the interrupting symmetrical rating of generator breakers at the upper end is 50
kA and 250 kA, respectively.
IEC standards9 do not discuss the asymmetry at the contact parting time of the breaker. The IEC standard showing the examples of
short-circuit calculations, part 4, is yet to be published. IEC may
adopt IEEE Std. C37.0138 for the generator breakers.
TA B L E 1 0 - 2
Consider faults at locations F1 and F2 in Fig. 10-1. For a fault
at F2, there are three contributions of the short-circuit currents:
(1) from the utility source, (2) from the auxiliary distribution system rotating loads through UAT (unit auxiliary transformer), (3)
from the generator itself. However, the generator breaker sees only
the component (3). Similarly for fault at F1, the generator breaker
sees the sum of the utility source and auxiliary distribution system
short-circuit current contributions, but not the contribution from
the generator itself. While selecting a generator breaker, the higher
of these two fault currents at F1 and F2 is considered. Generally, the
generator contribution for fault at F2 gives rise to higher asymmetry
than the fault at F1 because large generators have a higher X/R ratio
compared to X/R ratios in the utility systems.
Example 10-7 This example demonstrates the calculations and
EMTP simulations of a terminal fault of a generator data, as shown
in Table 10-2. Using these data and considering a 5-cycle breaker,
with contact parting time of 3 cycles, consisting of 1/2 cycle tripping
delay and 2.5 cycles opening time, the calculated short-circuit currents, from Eq. (10-104) are:
■
Close and latch = 112.2 kA peak
■
Generator source ac symmetrical interrupting current =
30.9 kA rms
■
Dc component = 59.22 kA
■
Total rms asymmetrical interrupting current at contact parting = 66.80 kA
■
Asymmetry factor = 135.5 percent and the current zero is not
obtained.
Generator Data for Example 10-7
DESCRIPTION
SYMBOL
DATA
Per unit reactance data, direct axis
Synchronous
Transient
Subtransient
Saturated negative sequence
Leakage reactance, overexcited
Leakage reactance, underexcited
Xdv
X d′v
X ″dv
X2v
XLM,OXE
XLM,UEX
2.120
0.230
0.150
0.150
0.135
0.150
Per unit reactance data, quadrature axis
Synchronous
Transient
Subtransient
Generator effective X/R
Xqv
X q′v
X ″qv
X/R
1.858
0.434
0.140
125
Field time constant data, direct axis
Open circuit
Three-phase short-circuit transient
Short-circuit subtransient
Open-circuit subtransient
T d′o
T d′
T ″d
T ″do
5.615
0.597
0.015
0.022
Field time constant data quadrature axis
Open-circuit
Open-circuit subtransient
T q′o
T ″qo
0.451
0.046
Generator
234 MVA, 2-pole, 18 kV, 0.85 pF, 198.9 MW, 7505 A, 60 Hz,
0.56 SCR, 350 field V, wye-connected, high impedance
grounded through a distribution transformer, grounding
current at 18 kV limited to 9A
TRANSIENT BEHAVIOR OF SYNCHRONOUS GENERATORS
257
The asymmetry factor a is given by:
dc component
α=
2 symmetrical interrupting current
(10-115)
And the total asymmetrical interrupting current is given by:
I total,asym = (ac sym )2 + (dc )2
(10-116)
An important parameter of calculation is the X/R ratio. The effective
resistance of the generator used in the short-circuit calculations is
calculated from the following expression:3
RG =
X 2v
2π f Ta
(10-117)
where RG is the generator effective resistance, and all the symbols
have been described in Table 10-2. Using appropriate values from
Table 10-2, this gives an X/R of 125, which correlates with the data
supplied by the manufacturer.
There are analytical and conceptual differences between the
ANSI/IEEE methods of short circuit calculations and IEC,10–13
which are not discussed here.
EMTP uses Park’s transformations and calculates the transformed parameters based on the input manufacturer’s data. It can
also accept the transformed parameters in 0dq axes directly. Also,
the system inertia constant and mechanical damping have been
modeled.
The three-phase short-circuit current profile is shown in Fig. 10-18,
for phases a, b, and c. It is seen that in phase c, current zero is not
obtained for a number of cycles. The comparative results of calculations are shown in Table 10-3.
10-14-1
The Effect of Power Factor
The load power factor (lagging) in IEC equations (not discussed
here) does not change the asymmetry at the contact parting time.
However, the asymmetry does change with the power factor and
prior load. This is clearly shown in Fig. 10-19b, with generator
absorbing reactive power, that is, operating at leading power factor
of 0.29. Generator load prior to short circuit = 28 MW, 92.4 Mvar.
It is seen that the current zeros are further delayed, as compared to
generator operating at no load. Fig. 10-19a shows the short-circuit
current profile in phase c at no load, while Fig. 10-19b shows it
with leading load. The prior leading power factor loading further
delays the occurrence of current zeros.
Thus, there are differences in the calculations using the same
data.
The example of calculation demonstrates that asymmetry at
contact parting time can be even 130 percent or more. The delayed
current zeros can also occur on short circuits in large industrial
systems, with cogeneration facilities, as shown in Fig. 10-2. In this
figure, the generator parameters are:
X ′′d = 0 . 162, X ′d = 0 . 223, X d = 2 . 01, X ′′q
0 15, Td′ = 0 . 638, Ta = 0 . 476
= 0 . 159, Td′′ = 0 .0
All reactances are in per unit on generator MVA base of 81.82 and
all time constants are in seconds. This gives an asymmetry factor of
132 percent at the contact parting time, 5-cycle symmetrical rated
breaker.
The opening of a circuit breaker can be delayed till the current
zeros occur. This can also lower the short-circuit duty on the circuit
breaker.14 However, stability and increased fault damage is of concern,
as discussed in Chaps. 12 and 13. A circuit breaker capable of interrupting with higher asymmetry should normally be applied, and generator
circuit breakers to meet this requirement are commercially available.
FIGURE 10-18
EMTP simulation of transients for a terminal fault of
generator, Example 10-7. Current zero does not occur for a number of cycles
in phase c as current interruption.
See also Example 16-4 which shows delayed current zeros due
to out-of-phase synchronization.
10-15 SYNCHRONOUS GENERATOR
ON INFINITE BUS
Figure 10-20 shows a synchronous generator with load connected
to an infinite bus, with local load represented as a shunt and finiteseries impedance. If we ignore damper windings and amortisseur
effect, the model is simplified, but it cannot be used for transient
stability analysis, following a large disturbance in the system. We
consider only small perturbations around the original operating
point; the system parameters are assumed unchanged and the
system can be linearized.
258
CHAPTER TEN
TA B L E 1 0 - 3
Comparison of Calculations Using IEEE/IEC Standards
and EMTP Simulations
CALCULATED PARAMETER
Close and latch, kA peak (IEC peak short-circuit current)
zeros are further delayed.
112.2
IEC
EMTP
131.60
132.05
Generator source interrupting kA sym. RMS
(IEC symmetrical breaking current ibsym.)
30.90
38.50
33.59
DC component, kA
59.22
60.73
62.50
Total asymmetrical, kA RMS (IEC ibasym)
66.80
71.90
70.90
Asymmetry factor
FIGURE 10-19
IEEE
135%
112%
131%
Comparison of the simulated transient in (a) and (b) shows that when a generator is operating at leading power factor (b), the current
TRANSIENT BEHAVIOR OF SYNCHRONOUS GENERATORS
259
Eliminating Vd and Vq, we get:
Id
R2 −X2
1
=
Iq
R1R 2 − X1 X 2 − X1 R1
(10-123)
−(GX + BR )
E′q − Vs siin δ
cos
δ
1 + RG − BX
where:
R1 = R − (GX + BR )X ′d
R 2 = R − (GX + BR )X q
(10-124)
X1 = X + (1 + RG − BX )X ′d
FIGURE 10-20
A generator connected to an infinite bus through an
impedance and also supplying load connected to its terminals.
X 2 = X + (1 + RG − BX )X q
Because we are considering small disturbances, the equations
can be linearized:
I d = I do + D I d
I q = I qo + D I q
E′q = E′qo + D E′q
δ = δo + D δ
(10-125)
After some manipulations the equations are reduced to:
D Id
Y
F
= d D E′q + d D δ
D Iq
Yq
Fq
(10-126)
where:
Yd ≅ [−R 2 (BR + GX ) − X 2 (1 + GR − BX )]/(R1R 2 − X1 X 2 )
Yq ≅ [X1(BR + GX ) − R1(1 + GR − BX )]/(R1R 2 − X1 X 2 )
FIGURE 10-21
A simplified phasor diagram for development of
small-signal model of a generator.
From Fig. 10-20, and the phasor diagram (Fig. 10-21) of the
generator connected to infinite bus, we have:
I = YVt + (Vt − Vs )/Z
(10-118)
ZI = ZYVt + (Vt − Vs )
(R + jX )(I d + jI q ) = (R + jX )(G + jB)(Vd + jVq )
− Vs (sin δ + j co s δ )
(10-119)
v f = rF iF +
dλF
dt
(10-128)
dλ
v f = rF λ f /L F + ( L F /rF ) F /L F − kM F id /L F
dt
(10-129)
3EFD ≅ 3ω0 M F v f / 2 rF
1 + GR − BX −(GX + BR ) Vd
sin δ
− Vs
1 + GR − BX Vq
cos δ
GX + BR
(10-120)
(10-130)
and
3E′q ≅
3
ω M λ /L
2 0 F F F
From these equations:
We know that:
Vq = E′q − X ′d I d
(10-121)
EFD = [E′q (1 + sTdo′ )]+ ( X d − X ′d )I d
(10-131)
where:
Or in matrix form:
0
Vd
=
Vq
− X ′d
Field circuit, neglecting dampers:
Also:
− X Id
R Iq
Vd = X qI q
Fq ≅ − Vs ( X1 cos δ0 + R1 sin δ0 )/(R1R 2 − X1 X 2 )
Then, the vf can be written as:
This can be written as:
=
(10-127)
λF = L F iF + kM F id
or
R
X
Fd ≅ − Vs (R 2 cos δ0 + X 2 sin δ0 )/(R1R 2 − X1 X 2 )
Xq
0
Id
+ 0 E′q
Iq
1
(10-122)
Tdo′ =
LF
rf
L′d = Ld −
L2ad
LF
ω0 Ld = X d
ω0 L′d = X ′d
(10-132)
260
CHAPTER TEN
Linearizing Eq. (10-131):
This can be written as:
′ ) + ( X d − X ′d )D I d
D EFD = D E′q (1 + sTdo
D Vt = K 5D δ + K 6 D E′q
′ ]D E′q + ( X d − X ′d )Fd D δ
= [1 + ( X d − X ′d )Yd + sTdo
(10-133)
This can be written as:
′ K3 )
D E′q = (D EFD − K 4 D δ )K 3 /(1 + sTdo
(10-134)
where:
K 3 = 1 / [1 + ( X d − X ′d )Yd ]
(10-135)
K 4 = ( X d − X ′d )Fd
2
2
Vt = Vd + Vq
2
(10-136)
2 Vt 0 D Vt = 2Vd 0 D Vd + 2Vq0 D Vq
K6 =
Vd 0 X q Fq − Vq0 X ′d Fd
Vt 0
Vd 0 X qYq + Vq0 (1 − X ′d Yd )
(10-141)
Vt 0
Torque equation:
Te = (Vd I d + VqI q )/ω0 (ω0 = 1 per unit)
(10-142)
By linearizing:
+ D I q (E′d 0 − X ′d I d 0 ) + I q0 (D E′q − X ′d D I d )
(10-137)
(10-143)
By some manipulations, this can be written as:
We know that:
D Vd = X q D I q = X qYq D Eq + X q Fq D δ
D Vq = D E′q − X ′d D I d = D E′q − X ′d (Yd D E′q + Fd D δ )
(10-138)
D Te = K1D δ + K 2 D E′q
(10-144)
where:
K1 = ( X q − X ′d )(I q0 Fd + I d 0 Fq ) + E′q0 Fq
Substituting these equations into Eq. (10-137):
Vd 0[X q (Yq D E′q + Fq D δ )] + vq0[D E′q − X ′d (Yd D E′q + Fd D δ )]
Vt0
(10-139)
FIGURE 10-22
K5 =
D Te = X q (I q0 D I d + I d 0 D I q )
By linearizing:
D Vt =
where:
= X qI qI d + (E′q − X ′d I d )I q
Voltage equation:
(10-140)
K 2 = I q0 + ( X q − X ′d )(II q0Yd + I d 0Yq ) + E′q0Yq
(10-145)
Based on the above equations, the block diagram of synchronous machine is shown in Fig. 10-22. Consider IEEE type 1
Control circuit block diagram of a generator, small-signal perturbation model, with AVR and input from PSS.
TRANSIENT BEHAVIOR OF SYNCHRONOUS GENERATORS
FIGURE 10-23
261
Control circuit block diagram, based on Fig. 10-22, with added control circuit block diagram of excitation system.
excitation system15 and power system stabilizer (Chaps. 12 and
13), and incorporation of these makes the total block diagram
of Fig. 10-23.
Example 10-8 A generator of specifications as in Table 10-1 is
connected through a step-up transformer, 13.8–138 kV, delta-wye
connected, of 10 percent impedance and operated in isolation to
supply a 90 MW load at 0.85 power factor.
The load is suddenly dropped at 10 ms. The resulting transients are
shown in Figs. 10-24a through e. These show generator terminal voltage, phases abc currents, currents in dq axes, generator active power
transients, and currents in the damper circuits, respectively. The simulation time is 200 ms, and all transients have decaying trends.
No voltage regulator or excitation system is modeled. Fast excitation systems can even accentuate the initial transients (Chap. 13).
F I G U R E 1 0 - 2 4 Transients on sudden unloading of a 112.1 MVA generator data in Table 10-1. (a) Generator terminal voltage, (b) phase currents,
(c) currents in dq axes, (d ) active power, and (e) damper currents, Example 10-8.
262
CHAPTER TEN
FIGURE 10-24
(Continued )
TRANSIENT BEHAVIOR OF SYNCHRONOUS GENERATORS
FIGURE 10-24
PROBLEMS
1. Calculate the fault decrement curves of the generator using
the data given in Table 10-1. Calculate (a) ac decaying component, (b) dc component, and (c) total current. Plot the results
similar to Fig. 10-7.
2. Consider a generator supplying power through an impedance, Fig. 10-P1, and the following generator data:
X ′′dv = 0 . 16, X ′′d = 0 . 18, X ′d = 0 . 20, X d = 2 . 0, X l = 0 . 15
X q = 1 . 90, X ′q = 0 . 26, X ′′q = 0 . 178, rD = 0 . 015
′ = 4 . 8s, X /R = 110
rQ = 0 . 025, Tdo
All above reactances are in per unit on generator MVA base.
Calculate (a) prefault voltages behind reactances Xd , X′d and X″d
for faults at G and F, and (b) largest possible dc component for
faults at G and F.
263
(Continued )
5. Write a numerical expression for the decaying ac component of current for fault at G and F in Prob. 2. What is the ac
component of the fault current at 0.05 s and 0.10 s?
6. Transform the calculated direct-axis and quadrature-axis
voltages derived in Example 10-2 into stator voltages using
Park’s transformation.
7. Draw a general steady-state phasor diagram of a synchronous generator operating at (a) leading power factor and (b)
lagging power factor.
8. Construct a simplified dynamic phasor diagram (ignoring
damper circuit and resistances) of a synchronous generator using
Park’s transformations. How does it differ from the steady-state
phasor diagram?
9. Show that first column of P′ is an eigenvector of L11 corresponding to eigenvalue Ld = Ls– 2Ms.
10. Prove that the transient inductance L′d = Ld − L2ad /L F .
11. Form an equivalent circuit similar to Fig. 10-11 with
numerical values using the generator data from Table 10-1.
12. Given the parameters of the generator in Table 10-1 and
considering that the generator is connected to an infinite bus
through an impedance of 0.01 + 020 per unit and supplies its
rated power at rated power factor in the system configuration
of the figure, calculate all K constants in Fig. 10-22
3. Calculate field current in Prob. 2 on application of short
circuit.
13. The generator data shown in Table 10-1 is connected to
a transformer of 120 MVA, Z1 = 10 percent, X/R = 40, 13.8–
138 kV, delta–wye grounded, in step-up configuration. The
three-phase symmetrical short-circuit current of the 138-kV system is 30 kA, X/R = 15. Calculate total three-phase short-circuit
currents when (a) a three-phase fault occurs on the 138 kV side
of the transformer and (b) a fault occurs on 13.8 kV side of the
transformer. Plot short-circuit current profiles: ac symmetrical,
dc component, and total current, till the steady state is reached.
4. Calculate three-phase short-circuit subtransient and transient time constants in Prob. 2 for fault at F.
14. Table 10-2 gives the manufacturer’s data of generator for
Example 10-7. Convert it into dq0 axes.
F I G U R E 1 0 - P 1 Generator supplying load through an impedance
circuit for Probs. 2 through 6.
264
CHAPTER TEN
REFERENCES
1. NEMA MG-1, Large Machines–Synchronous Generators,
Part 22, 2003.
2. A. E. Fitzgerald, S. D. Umans, and C. Kingsley, Electric Machinery,
McGraw-Hill Higher Education, New York, 2002.
3. ANSI/IEEE Std. C37.010, Guide for AC High Voltage Circuit
Breakers Rated on Symmetrical Current Basis, 1999.
4. P. M. Anderson and A. Fouad, Power System Control and Stability, IEEE Press, New York, NY, 1991.
5. J. C. Das, “Study of Generator Source Short-Circuit Currents
with Respect to Interrupting Duty of Generator Circuit Breakers, EMTP Simulation, ANSI/IEEE and IEC Methods,” Int.
J. Emerging Elect. Power Syst., vol. 9, no. 3, article 3, 2008.
6. I. M. Canay and L.Warren, “Interrupting Sudden Asymmetrical
Short-Circuit Currents Without Zero Transition,” BBC Rev.
vol. 56, pp. 484–493, 1969.
7. D. Dufournet, J. M. Willieme, and G. F. Montillet, “Design and
Implementation of a SF6 Interrupting Chamber Applied to Low
Range Generator Breakers Suitable for Interrupting Currents
Having a Non-Zero Passage,” IEEE Trans. Power Delivery,
vol. 17, pp. 963–969, Oct. 2002.
8. IEEE Std. C37.013, IEEE Standard for Generator Circuit
Breakers Rated on Symmetrical Current Basis, 1997; and IEEE
Std. C37.013a, Amendment 1, Supplement for Use With
Generators Rated 10-100 MVA, 2007.
9. IEC 60909-0, Short-Circuit Currents in Three-Phase AC
Systems, Calculation of Currents, 2001–07; and IEC 60909-1,
Factors for Calculation of Short-Circuit Currents in ThreePhase AC Systems According to IEC 60909-0, 1991.
10. J. C. Das, “Short-Circuit Calculations—ANSI/IEEE & IEC
Methods: Similarities and Differences,” Proc 8th International
Symposium on Short-Circuit Currents in Power Systems, Brussels,
pp. 25–31, 1988.
11. J. C. Das, Power System Analysis, Chapter 8, Short-Circuit
Calculations According to IEC Standards, Marcel Dekker,
New York, 2002.
12. G. Knight and H. Sieling, “Comparison of ANSI and IEC 909
Short-Circuit Current Calculation Procedures,” IEEE Trans. Industry Applications, vol. 29, no. 3, pp. 625–630, May/June 1993.
13. A. Berizzi, S. Massucco, A. Silvestri, and D. Zanin, “ShortCircuit Current Calculations: A Comparison Between Methods
of IEC and ANSI Standards Using Dynamic Simulation as
Reference,” IEEE Trans. Industry Applications, vol. 30, no. 4,
pp. 1099–1106, July/Aug. 1994.
14. J. C. Das, “Reducing Interrupting Duties of High-Voltage
Circuit Breakers by Increasing Contact Parting Time,” IEEE
Trans. Industry Applications, vol. 44, no. 4, pp. 1027–1033,
July/August 2008.
15. IEEE Std. 421.2, IEEE Guide for Identification and Evaluation
of Dynamic Response of Excitation Control Systems, 1990.
FURTHER READING
ATP Rule Book, Canadian/American EMTP User Group, Portland,
OR, 1987–92.
B. Adkins, The General Theory of Electrical Machines, Chapman and
Hall, London, 1964.
P. M. Anderson, Analysis of Faulted Power Systems, Chapter 6, Iowa
State University Press, Ames, 1973.
ANSI/IEEE Std. C37.09, IEEE Standard Test Procedure for AC
High-Voltage Circuit Breakers Rated on a Symmetrical Current
Basis, 1999.
I. Boldea, Synchronous Generators, CRC Press, Boca Raton, FL, 2005.
A. Braun, A. Edinger, and E. Rouss, “Interruption of Short-Circuit Currents in High Voltage AC Networks,” BBC Rev, vol. 66, pp. 321–332,
April 1979.
I. M. Canay, “Comparison of Generator Circuit Breaker Stresses
in Test Laboratory and Real Service Condition,” IEEE Trans. Power
Delivery, vol. 16, pp. 415–421, 2001.
C. Concordia, Synchronous Machines, Wiley, New York, 1951.
J. R. Dunki-Jacobs, B. P. Lam, and R. P. Stratford, “A Comparison of
ANSI-Based and Dynamically Rigorous Short-Circuit Current Calculation Procedures,” Trans. IEEE, Industry Applications, vol. 24, no. 6,
pp. 1180–1194, Nov./Dec. 1988.
N. N. Hancock, Matrix Analysis of Electrical Machinery, Pergamon
Press, Oxford, 1964.
IEEE Committee Report, “Recommended Phasor Diagram for Synchronous Machines,” IEEE Trans. PAS, vol. 88, pp. 1593–1610, 1963.
A. T. Morgan, General Theory of Electrical Machines, Heyden & Sons,
London, 1979.
R. H. Park, “Two Reaction Theory of Synchronous Machines,
Part 1,” AIEE Trans., vol. 48, pp. 716–730, 1929.
R. H. Park, “Two Reaction Theory of Synchronous Machines, Part II,”
AIEE Trans., vol. 52, pp. 352–355, 1933.
CHAPTER 11
TRANSIENT BEHAVIOR
OF INDUCTION AND
SYNCHRONOUS MOTORS
In this chapter, we will study transient behavior of induction
and synchronous motors, terminal short-circuits, and starting
and switching transients. The voltage stability of the motors is an
important criterion, addressed in Chap. 12. Also some other transients associated with the motors, during autobus transfer of motor
loads, harmonics, cogging and crawling, and torsional vibrations
are addressed in Chap. 16. This chapter may be considered parallel to Chap. 10 on synchronous generators, in the sense that the
same basic approach is used in developing the transient models
and analysis. A synchronous machine, whether it is a generator or
motor, has the same theoretical and practical basis of analysis, and
can be similarly modeled. The starting of synchronous motors must
be addressed separately; while a synchronous generator is driven to
the rated speed, a synchronous motor must accelerate and synchronize. A synchronous motor is started like an induction motor, but
there are differences in the starting characteristics.
■
It cannot be applied to machines with both rotor and stator of
salient pole construction, such as an inductor alternator, as
dq axis cannot be fixed with respect to stator or rotor. Another
limitation is that the nonsalient pole part of the machine must
have balanced windings. A single-phase generator has
unbalanced windings, and the theory cannot be applied.
New approaches to machine analysis are: (a) energy state functions and (b) field equations. Much alike a synchronous machine in
Chap. 10, here, an induction machine model is derived in terms of
dq axes. Both the stator and rotor are cylindrical and symmetrical.
The d-axis is chosen arbitrarily as the axis of phase a. The threephase winding is converted into a two-phase winding so that the
axis of the second phase becomes the q-axis.
Consider the transformation of a three-phase machine (Fig. 11-1a)
to a two-phase machine (Fig. 11-1b). For the three-phase machine we
can write:
11-1 TRANSIENT AND STEADY-STATE MODELS
OF INDUCTION MACHINES
i A = I m cos ωt
We can study a rotating machine in steady state, depending upon
its specific type, that is, synchronous, induction, dc, and the like,
and arrive at its behavior using equations and models specific to the
machine type. The generalized machine theory attempts to unify
the piecemeal treatment of rotating machines, led by Park’s two-axis
equations for synchronous machines (Chap. 10). These ideas were
further developed by Kron and others,1,2 and treatment of electrical
machines using tensors or matrices and linear transformation is the
basis of generalized machine theory. Transformation here means that
an old set of variables is transformed into a new set of variables and
vice versa. One set of equations is good to describe the steady state
and transient behavior. Yet, the theory has its limitations:
iC = I m cos(ωt + 120 ° )
■
It cannot model saturation, brush contact resistance, commutation effects, surge phenomena, skew, eddy current losses,
stray load losses, and mechanical features such as vibrations,
torsion, noise, critical speeds, and the like.
iB = I m cos(ωt − 120 ° )
(11-1)
For a two-phase machine:
iα s = I m cos ωt
iβ s = I m cos(ωt − 90 ° )
(11-2)
The rotary and stationary coils are denoted with subscripts
r and s, respectively. While deriving equivalence, we have three
choices:
■
Keep effective turns on the coils the same and use multiplying factors for power and impedance.
■
Keep current the same.
■
Keep impedance the same.
265
266
CHAPTER ELEVEN
q-axis
bs
iC
C
wr
iqs
ibs
wr
C
icr
wr
br
A
q
iqr
as
ibr
d-axis
b
a
iA
ias
iar
iB
d
ar
ids
idr
iar
B
(a)
FIGURE 11-1
(b)
(c)
(a) Three-phase induction machine, stator, and rotor coils. (b) Transformation to a two-phase machine, a and b axes. (c) Transformation
to d and q axes.
The parameters of equivalence in three cases are shown in
Table 11-1. Case 3 is normally used. Referring to Fig. 11-1a, b and
c for the stator, a b axes and dq axes coincide. Phase A-axis of threephase machine coincides with phase-a axis of the two-phase machine.
Thus, d-axis quantities apply to a-axis of two-phase machine or
A-axis of three-phase machine. We define a transformation matrix
A, so that:
iα s , iβ s , i0 s = A i A , iB , iC
i A , iB , iC = A −1 iα s , iβ s , i0 s
This will be zero for a three-phase balanced system. The matrix A
is given by:
cos 0 °
A=
2
sin 0 °
3
1
2π
3
2π
sin
3
1
cos
2
(11-3)
2
4π
3
4π
sin
3
1
cos
(11-5)
2
For power invariance in the two systems, it can be shown that:
Note that we add another parameter:
i0 = ia + ib + ic
(11-4)
TA B L E 1 1 - 1
At A = 1
(11-6)
A −1 = A t
Transformation from Three-phase to Two-phase—Option
of Parameters for Equivalence
TWO-PHASE PARAMETERS
THREE-PHASE PARAMETERS
CASE 1 (N SAME)
CASE 2 (I SAME)
CASE3 (Z SAME)
3/2 I
I
3 /2 I
Turns N
N
3/2N
Flux φ
φ
φ
3 /2 N
φ
Voltage per phase V
V
3/2V
3 / 2V
Power per phase VI
3/2VI
3/2VI
3/2VI
Current I
Total power 3VI
3VI
3VI
3VI
Impedance Z
2/3Z
3/2Z
Z
TRANSIENT BEHAVIOR OF INDUCTION AND SYNCHRONOUS MOTORS
Now we will transform from rotating a b 0 axes to pseudostationary
axis dq0 (see Fig. 11-1c). In the dq axis:
idr
cos θ
iqr = − sin θ
0
i
0r
(11-7)
i = C i′
(11-8)
v ′ = C *t v
z ′ = C*t zC
(11-9)
Where the * shows a conjugate. For proofs of these transformations, Ref. 2 provides further reading. We will use these transformations to derive a model of induction machine. For the stator:
3 − φ abc ⇔ 2 − φ αβ 0 ⇔ 2 − φ dq 0
2
0
3
1
1
−
2
3
2
1
2
2
1
(11-10)
(11-11)
2
The air gap is uniform, therefore:
Lds = Lqs = L s
(11-17)
Ldr = Lqr = Lr
vdr = 0 = vα r cos θ + vβr sin θ
(11-18)
vqr = 0 = vα r sin θ + vβr cos θ
Thus, idr and iqr are reversed. With change of signs, the following
matrix can be written:
rs + L s p
vds
=
Mp
0
0
Mωr
−Mp
ids
rs + L s p
−Mp
iqs
−Mωr −(rr + Lr p )
L rω r
idr
− L rω r
Mp
−(rr + Lr p ) iqr
(11-19)
11-1-1
Steady-State Operation
For the steady-state operation:
ω r = (1 − s)ω
ids 1 0 0 iα s
iqs = 0 1 0 iβ s
i0 s 0 0 1 i0 s
(11-12)
3 − φ abc ⇔ 2 − φ αβ 0 ⇔ 2 − φ dqo
(11-13)
Thus we can write:
vds
vqs
0
0
iα r
iar
iβr = A ibr
icr
i0 r
rs + X s
=
jX m
(1 − s)X m
− jX m
rs + jX s
−(1 − s)X m
jX m
ids
iqs
− jX m
−(rr + jX r ) (1 − s)X r idr
−(1 − s)X r −(rr + jX r ) iqr
(11-21)
(11-14)
There is no difference in d and q axes except of time, therefore:
and Eq. (11-7) gives transformation to dq rotor axis.
From the basic concepts of coils on the stator and rotor, we can
write the following matrix:
rds + Lds p
=
(11-20)
p = jω
where s is the motor slip, wr is the actual operating speed of the
motor in radians, and w is 2 π f. This gives:
For the rotor:
vdr
vqr
(11-16)
Md = Mq = M
vqs
1
−
2
iA
3
i
−
2 B
iC
1
and:
vds
vqs
rdr = rqr = rr
Rotor coils are short-circuited:
and:
i0 s
This can be simplified. As the coils are balanced and identical:
rds = rqs = rs
sin θ 0 iα r
cos θ 0 iβr
0
1 i0 r
Some other useful transformations to relate old current, voltage,
and impedance to the new transformation axes are necessary. We
define a connection matrix C, so that:
iα s
iβ s =
267
Md p
rqs + Lqs p
Mq p
Md p
− M qω r
rdr + Ldr p
M dω r
Mq p
Ldrω r
(11-22)
iqr = jidr
Write the following transformation matrix:
ids
iqs
− Lqrω r idr
rqr + Lqr p iqr
ids
iqs
(11-15)
where p is the differential operator d/dt.
iqs = jids
idr
iqr
1 0
j 0 is
=
0 1 ir
0
j
(11-23)
268
CHAPTER ELEVEN
The transformation of impedance is given by Eq. (11-9). Thus:
z ′ = Ct zC
1 0
1 −j 0 0
j 0
z′ =
z
0 0 1 −j 0 1
0 j
v′ = z ′ i′
(11-24)
− jX m
− rr − jsX r
=
1 −j 0
0 0 1 −j 0
0
vds − jvqs
0
=
=
(11-25)
vs
0
rs + jX s
jsX m
− jX m is
− rr − jsX r ir
(11-29)
=
rs + jX s
jX m
− jX m
is
− rr / s − jX r ir
(11-30)
This gives the equivalent circuit of the induction motor, shown in
Fig.11-2a and b.
The leakage reactances of the stator and rotor are:
v ′ = C *t v
=
0
This nonsymmetric matrix can be made symmetric:
The transformation of voltage is given by:
vds
0 vqs
(11-28)
Therefore:
vs
After simplification and manipulation of the matrices, this transformation gives:
r + jX s
z′ = 2 s
jsX m
We also know that the transformed voltages and currents are related
with transformed impedance:
(11-26)
X s = ( Ls − M )
X r = ( Lr − M )
2v s
0
The Torque Equation
(11-31)
The torque equation in general can be
written as:
because
vds = vs , vqs = jvs , and − jvqs = + vs .
FIGURE 11-2
(11-27)
Te =
P
= i tG i
ω
(11-32)
(a) and (b). Equivalent circuit of a single-cage induction motor in steady state. (c) Equivalent circuit of a double-cage rotor induction motor.
TRANSIENT BEHAVIOR OF INDUCTION AND SYNCHRONOUS MOTORS
where G is the torque matrix and is a rotational inductance matrix.2
For an induction motor:
0
0
G=
0
0
0
− Mq
0
0
0
− Lqr
0
Ldr
0
Md
0
0
(11-33)
Thus, the motor torque T in newton-meters can be written as:
r
vs2 r
s
1 2 rr
1
T=
ir ≈
2
ωs s ωs
rr
2
rs + s + ( X s + X r )
rr
s=±
Pe = Re[ i G i ]
r + (Xs + Xr )
2
s
*t
i*qs
i*dr
i*qr G
ids
iqs
(11-34)
idr
i qr
Tm =
(11-35)
Te = Re[ j2Mi*r is ]
≈
rr
(Xs + Xr )
vs2
2
(
rs2 + ( X s + X r
)
2
± rs
jX m
vs
rs + jX s
0
11-1-2
(11-37)
Substituting these values in Eq. (11-35)
v*
v r
Te = Re j2M s* (− jX m ) s r + jX r
s
D
D
2 X 2 v v* r
= Re m s s* r
ω D D s
2 r 2 r
= Re ir i*r r = ir2 r
s ω s
ω
(11-43)
(11-36)
vs rr
+ jX r
D s
vs
( jX m )
D
v*
i*r = *s ( jX m )
D
(11-42)
where K may be considered a constant. The negative sign in Eq. (11-42)
is related to the operation as induction generator.
where D is determinant of Z. This gives:
ir =
(11-41)
At small slip rr /s is comparatively large compared to other terms in
Eq. (11-40). Therefore, we can write:
T = sK
also:
is =
2
The maximum torque is obtained by inserting the value of s in
Eq. (11-40)
The solution of Eq. (11-34) gives:
r
is 1 r + jX r
=
s
ir D
jX m
(11-40)
The slip for maximum torque is obtained from above equation by
dT/ds = 0, which gives:
The steady-state torque is:
= Re i*ds
269
Double Cage Rotors
From Eq. (11-40) the maximum torque is proportional to the
square of the applied voltage; it is reduced by stator resistance and
leakage reactance, but is independent of rotor resistance. The slip
at the maximum torque is directly proportional to the rotor resistance [Eq. (11-41)]. In many applications it is desirable to produce
higher starting torque at the time of starting. External resistances
can be introduced in wound rotor motors which are short-circuited
when the motor speeds up. In squirrel-cage designs, deep rotor
bars or double-cage rotors are used; a typical slot design is shown in
Fig. 11-3. The top bar is of lower cross section and has higher resistance than the bottom bar of larger cross section. The flux patterns
shown in Fig. 11-3 make the leakage resistance of the top cage negligible compared to the lower cage. At starting, the slip frequency
is equal to the supply system frequency and most of the starting
current flows in the top cage, and the motor produces high starting
(11-38)
For a three-phase machine
Te =
3 2 rr
i
ω r s
Mechanical power developed is the power across the air gap minus
copper loss in the rotor, that is,
(1 − s)Pg
(11-39)
FIGURE 11-3
construction.
Flux patterns in a double-cage induction motor rotor
270
CHAPTER ELEVEN
torque. As the motor accelerates, the slip frequency decreases and
the lower cage takes more current because of its low leakage reactance compared to the resistance. Following the same procedure as
in the development of a single-cage induction motor, the equivalent
circuit of a double-cage rotor is shown in Fig. 11-2c.
rs
(11-44)
L md
L md + Lr1
L md
L md
L md
L md + Lr 2
(11-45)
where Lmd = d-axis linkage reactance, Ls, Lr1, and Lr2 are direct axis
stator, rotor first-cage, and rotor second-cage leakage reactances,
FIGURE 11-4
The circuit in the direct axis is in Fig. 11-4b.
The saturation is a function of current in the circuits. A piecewise
linear approximation can be used to take account of the saturation.
The magnetizing characteristics can be defined by a number of segments, and the monotonically increasing characteristics account for
saturation of the magnetic branch. The unsaturated mutual flux is:
2
2
+ φmq
φm = φmd
also:
φd
L md + L s
φD1 = L md
φD 2
L md
0 = −rr1i D1 − (ω − ω r )φQ1 − Lr1 pi D1 − L md p(i D1 + i D 2 + id )
(11-46)
A double-cage machine model in dq0 axis can be represented as
shown in Fig. 11-4a. We can write the following voltage equation
in the direct axis:
ωφq
pφd
0 0 ids
0 = − 0 rr1 0 i D1 − (ω − ω r )φQ1 − pφD1
0
0 0 rr 2 i D 2 (ω − ω r )φQ 2 pφD 2
Vds = − rsid − L s pid − L md p(i D1 + i D 2 + id ) − ωφq
0 = − rr 2i D 2 − (ω − ω r )φQ 2 − Lr1 pi D 2 − L md p(i D1 + i D 2 + id )
11-2 INDUCTION MACHINE MODEL
WITH SATURATION
Vds
respectively. From Eqs. (11-44) and (11-45):
(11-47)
The flux saturates to account for cross-magnetization, that is,
the two axes affect each other. The leakage reactance becomes high
when the motor takes starting currents. The skin effects in the
deep bars change with the motor slip. A deep bar factor DF is
defined as:
DF = d 2ωµ0σ
(a) Induction motor circuit in dq0 axes. (b) Equivalent circuit diagram.
(11-48)
TRANSIENT BEHAVIOR OF INDUCTION AND SYNCHRONOUS MOTORS
where d is the thickness of deep bars and s is the conductivity. The
effective rotor impedance as a function of slip is given by:
rr + jX r =
rr ( slip = 0 )
2
θ
sinh θ + sin θ + j(sinh θ − sin θ )
cosh θ − cos θ
(11-49)
where θ = slipDF. EMTP uses above equations for modeling
saturation.3
11-3
INDUCTION GENERATOR
If we plot torque slip characteristics of an induction machine for a
negative slip, Fig. 11-5 results. An induction motor will act as an
induction generator with the negative slip. At s =0, the induction
motor torque is zero, and if it is driven above its synchronous speed,
the slip becomes negative and generator operation results. The
negative rs in Eq. (11-42) represents the maximum torque required
to drive the machine as generator. The maximum torque is independent of the rotor resistance. For subsynchronous operation, the
rotor resistance does affect the slip at which the maximum torque
occurs. For maximum torque at starting, s =1 and
rr ≈ rs2 + ( X s + X r )2
(11-50)
For supersynchronous operation (generator operation), the maximum torque is independent of rr, same as for the motor operation,
but increases with the reduction of both the stator and the rotor
reactances. Therefore, we can write:
Tm,gen (supersyn )
Tm,motor (subsyn )
=
rs2 + ( X s + X r )2 + rs
rs2 + ( X s + X r )2 − rs
≈
X s + X r + rs
X s + X r − rs
(11-51)
The approximation holds as long as rs << Xs. The torque-speed
characteristics of the machine above synchronism are similar to that
FIGURE 11-5
271
for running as an induction motor. If the prime mover develops
a greater driving torque than the maximum counter torque, the
speed rises into an unstable region and the slip increases. At some
high value of the slip, the generating effect ceases and the machine
becomes a brake.
Induction generators do not need synchronizing and can run
in parallel without hunting and at any frequency; the speed variations of the prime mover are relatively unimportant. Thus, these
machines are applied for wind power generation (Chap. 24).
An induction generator must draw its excitation from the supply
system, which is mostly reactive power requirement. On a sudden
short circuit the excitation fails, and with it the generator output; so
in a way the generator is self-protecting.
As the rotor speed rises above synchronous speed, the rotor
EMF becomes in phase opposition to its subsynchronous position because the rotor conductors are moving faster than the
stator rotating field. This reverses the rotor current also and the
stator component reverses. The rotor current locus is a complete circle. The stator current is clearly a leading current of
definite phase angle. The output cannot be made to supply a
lagging load.
An induction generator can be self-excited through a capacitor
bank, without external dc source, but the frequency and generated
voltage will be affected by speed, load, and capacitor rating. For an
inductive load the magnetic energy circulation must be dealt with
by the capacitor bank as induction generator cannot do so.
11-4 STABILITY OF INDUCTION MOTORS
ON VOLTAGE DIPS
From Eq. (11-40) it can be inferred that the motor torque varies approximately as the square of the voltage. If the load torque
remains constant and the voltage dips, there has to be an increase
in the current to meet the load requirements. For the induction
motors loads, the assumption that a balanced decrease in the terminal voltage results in a corresponding increase in the line current
is conservative for stability studies, and is generally adopted in the
load models.
Torque-slip characteristics of induction machines. The characteristics in negative slip region relates to operation as an induction generator.
272
CHAPTER ELEVEN
FIGURE 11-6
Torque-slip characteristics of an induction motor at rated voltage and reduced voltages.
Figure 11-6 shows typical torque-slip characteristics of an
induction motor at rated voltages (curve 1), and reduced voltages
(curves 2 and 3). The definitions of locked rotor torque, minimum
accelerating torque, and breakdown torque during the starting
cycle can be provided based upon this figure:
■
OAis locked rotor torque or starting torque.
■
CDis breakaway torque. There is a cusp or reverse curvature in accelerating torque curve, which gives the minimum
accelerating torque or breakaway torque.
■
EFis maximum torque, also called the breakdown torque.
It occurs at slip sm, the maximum slip at the breakdown torque.
■
Pis normal operating full-load point at full-load slip sf . The
starting load characteristics are shown for a fan or blower, and it
varies widely depending upon the type of load to be accelerated.
The operating point and the full-load slip vary with the change in
the load.
where Eph is the phase emf, Kw is the winding factor, f is the system
frequency, Tph are the turns per phase, and Φ is the flux. Maintaining the voltage constant, a variation in frequency results in
an inverse variation in the flux. Thus, a lower frequency results
in overfluxing the motor and its consequent derating. In variable
frequency drive systems V/f is kept constant to maintain a constant
flux relation.
From the transient analysis considerations, a motor can be stable even under complete collapse of voltage provided it is returned
to normal soon enough. Consider the situation shown in Fig. 11-6.
Assume that the load torque remains constant under a voltage dip.
A voltage dip occurs that reduces the breakdown torque of the
motor equal to load torque T′. Then we can write:
T ′ /T = (V /Vr )2
(11-53)
Assume that the load torque remains constant, for example, in
a conveyor motor, when a voltage dip occurs. The slip increases
and the motor torque will be reduced. It should not fall below the
load torque to prevent a stall. Considering a motor break down
torque of 200 percent, the maximum voltage dip to prevent stalling is 29.3 percent.
Figure 11-7 is a comparison of the torque-speed characteristics
for NEMA design motors, A, B, C, D, and F. A proper choice of
motor type with respect to load is exercised; this is not discussed
further.
The effect of voltage variations on induction motor’s steady-state
performance is shown in Table 11-2. We are not much concerned
with the effect of frequency variation in load flow analysis, though
this becomes important in harmonic analysis. The emf of a threephase ac winding is given by:
Eph = 4 . 44 K w fTph Φ ( V )
(11-52)
FIGURE 11-7
Torque-speed characteristics of NEMA design A, B, C,
D, and F induction motors.
TRANSIENT BEHAVIOR OF INDUCTION AND SYNCHRONOUS MOTORS
TA B L E 1 1 - 2
273
Effects of Voltage Variations on Operation of Induction Motors
PERFORMANCE AT RATED VOLTAGE (1.0 PU) AND OTHER THAN RATED VOLTAGE
CHARACTERISTICS OF INDUCTION MOTOR
VARIATION WITH V
0.8
0.95
1.0
1.05
1.10
Torque
=V
0.64
0.90
1.0
1.10
1.21
Full-load slip
=1/V 2
1.56
1.11
1.0
0.91
0.83
Full-load current
≈1/V
1.28
1.04
1.0
0.956
0.935
0.88
0.915
0.92
0.925
0.92
0.90
0.89
0.88
0.87
0.86
0.80
0.95
1.0
1.05
1.10
0.016
0.023
0.025
0.028
0.030
0.16
0.226
0.25
0.276
0.303
2
Full-load efficiency
Full-load power factor
Starting current
=V
No load losses (W)
=V
2
No load losses (vars)
=V
2
where Vr is the reduced voltage and T′ is torque at reduced voltage.
A relation between the torque and the maximum slip Sm is:4,5
(11-54)
Then from Eqs. (11-53) and (11-54)
2k
( s / sm ) + ( sm / s)
(11-55)
where:
k = (Tp /Tl )(V /Vr )2
(11-56)
For the voltage dip that reduces Tp = Tl, k = 1. The time to decelerate
from the full-load slip sf to su is given by:
su
t = 2H ∫
sf
− ds
1 − (T ′ /Tl )
su
= 2sm H ∫
sf
(
s f , su = sm Tp /Tl ± (Tp /Tl )2 − 1
2
T /Tp =
( s / sm ) + ( sm / s)
T ′ /Tl =
The limits sf and su are given by:
s / sm + sm / s
d(s /sm )
(s /sm + sm /s) − 2k
)
(11-60)
Example 11-1 Consider a 2000-hp, six-pole, 60-Hz load inertia
= 16780 lb-ft2; total inertia including motor inertia = 20000 lb-ft2,
breakdown torque Tp = 150 percent, and critical slip sm = 10 percent. Calculated H = 3.6 s, sf = 3.8 percent, and su =26.2 percent.
The calculated stability on voltage dips using Eqs. (11-57) and
(11-59) is shown in Fig. 11-8.5 This figure also shows the effect
of H, and the curve for H = 7.2 s is included for comparison. A
higher inertia makes the machine more stable on voltage dips, due
to stored energy in the rotating masses and the speed falls more
slowly.
11-4-1
Negative-Sequence Characteristics
Figure 11-9 depicts the negative-sequence-equivalent circuit of an
induction motor. When a negative-sequence voltage is applied, the
mmf wave in the air gap rotates backward at a slip of 2.0 pu. The
(11-57)
= 2sm HT
where H is the inertia constant, defined as the kinetic energy at
rated speed in kilowatts-seconds per kilovolt-ampere. It is given
by:
H=
(0 . 231)(WR 2 )(r / min)2 × 10−6
s
kVA
(11-58)
where WR2 is the motor and load inertia in lb-ft2.
T = s /sm + k ln[s /sm (s /sm + sm /s − 2k )]
+
s
u
s /s − k
tan −1 m
1 − k 2 s
1 − k2
2k 2
f
(11-59)
FIGURE 11-8
on voltage dips.
Calculated stability limits of a 2000-hp induction motor
274
CHAPTER ELEVEN
FIGURE 11-9
Equivalent circuit of an induction motor for negative slip.
slip of the rotor with respect to the backward rotating field is 2 s.
This results in a retarding torque component, and the net motor
torque reduces to:
r I2 I2
T = r r − 22
ωs s 2 − s
T0′ =
(11-61)
Z2 = [(rs + rr / (2 − s))2 + ( X s + X r )2 ]1/ 2
(11-64)
≈
X′
Xs + Xm
X′
ω rr
(11-65)
The time constant for the decay of dc component is:
11-5 SHORT-CIRCUIT TRANSIENTS
OF AN INDUCTION MOTOR
Following the analogy of synchronous machines, the transient reactance of an induction machine is defined as:
Xm Xr
Xm + Xr
T ′ = T0′
(11-62)
Therefore, approximately, the ratio Z1/Z2 = Is/If, where Is is the starting current or the locked rotor current of the motor and If is the full
load current (s =1 at starting). For an induction motor with locked
rotor current is generally six times the full load current, and the
negative sequence impedance is one-sixth of the positive sequence
impedance. A 5 percent negative sequence component in the supply system will produce 30 percent negative sequence current in the
motor, which gives rise to additional heating and losses. Equations
(11-62) are a simplification; the rotor resistance will change with
respect to high rotor frequency and rotor losses are much higher
than the stator losses. A 5 percent voltage unbalance may give rise
to 38 percent negative sequence current with 50 percent increase
in losses and 40° C higher temperature rise as compared to operation on a balanced voltage with zero negative sequence component.
Also, the voltage unbalance should not be confused with negative
sequence component. NEMA definition of percent voltage unbalance is maximum voltage deviation from average voltage divided by
average voltage as a percentage. Operation above 5 percent unbalance is not recommended.6
The zero sequence impedance of motors, whether the windings
are connected in wye or delta, is infinite. The motor windings are
left ungrounded, as per industry practices in the United States.
X′ = Xs +
Xr + Xm
ω rr
Short-circuit transient time constant is:
where I22 is the current in the negative-sequence circuit. From
equivalent circuits of Figs. 11-2 and 11-9, we can write the approximate positive- and negative-sequence impedances of the motor as:
Z1 = [(rs + rr /s)2 + ( X s + X r )2 ]1/ 2
This is also the motor-locked rotor reactance. The open-circuit
transient time constant is:
Tdc =
(11-66)
The ac symmetrical short-circuit component is:
iac =
E −t /T ′
e
X′
(11-67)
and the dc component is:
idc = 2
E − t / Tdc
e
X′
(11-68)
Example 11-2 Consider a 900-hp, 2.3-kV, 4-pole motor with
the following data: full-load efficiency = 94.7 percent, full-load
power factor = 88 percent, full-load current = 202A, stator resistance 0.08 Ω, rotor resistance = 0.09 Ω, stator leakage reactance =
0.32 Ω, rotor leakage reactance at locked rotor = 0.45 Ω, magnetizing reactance, both direct and quadrature axis = 16 Ω, magnetizing
resistance = 100.00 pu, full load slip = 0.15 percent, H = 1 s.
The motor is connected in a system configuration as depicted in
Fig. 11-10a and is running in the steady state; switch S2 is closed
for a long time. A three-phase short-circuit is created by closing the
switch S1 at 10 ms. (Figure 11-10b pertains to Example 11-3.)
Figure 11-11 shows the EMTP simulation of three-phase motor
currents. The current at the instant of short circuit is approximately
14 times the motor’s full-load current.
11-6
(11-63)
X′
ω rs
STARTING METHODS
From the equivalent circuit of an induction motor in Fig. 11-2, and
neglecting the magnetizing and eddy current loss circuit, the starting
TRANSIENT BEHAVIOR OF INDUCTION AND SYNCHRONOUS MOTORS
275
current or the locked rotor current of the motor is:
Is =
F I G U R E 1 1 - 1 0 (a) System configuration for starting and terminal
short circuit of a 900-hp motor. (b) Motor and load speed-torque characteristics.
FIGURE 11-11
V
(rs + rr ) + j( X s + X r )
(11-69)
The locked rotor current of squirrel-cage induction motors is,
generally, six times the full-load current on across the line starting, that is, full-rated voltage applied across the motor terminals
with the motor at standstill. Higher or lower values are possible
depending upon motor design. Wound rotor motors may be started
with an external resistance in the rotor circuit to reduce the starting
current and increase the motor-starting torque. The resistance may
be cut out in steps as the motor speeds up. Synchronous motors
are asynchronously started and their starting current is generally 3
to 4.5 times the rated full-load current on across the line starting.
The starting currents are at a low power factor and may give rise to
unacceptable voltage drops in the system and at motor terminals.
On large voltage dips, the stability of running motors in the same
system may be jeopardized, the motors may stall or the magnetic
contactors may dropout, and other sensitive loads like adjustable
speed drives (ASDs) may shutdown.
As the system impedances or motor reactances cannot be
changed, impedance may be introduced in the motor circuit to
reduce the starting voltage, and therefore, the starting current. This
starting impedance is removed from the starting circuit as soon as
the motor has accelerated to approximately 90 percent of its rated
speed. Within certain limits, motors of lower locked rotor currents
can be specified in the design stage of the project.
Table 11-3 shows a summary of the various starting methods.
System network stiffness, acceptable voltage drops, starting reactive
power limitations, motor and load parameters need to be considered when deciding upon a starting method. The characteristics of
starting methods (Table 11-3), and the associated diagram of starting connections (Fig. 11-12) are summarized as follows:
Full Voltage Starting (Fig. 11-12a) This is the simplest
method for required starting equipment and controls and is the
most economical. It requires a stiff supply system because of
mainly reactive high starting currents. The motor terminal voltage during starting and, therefore, the starting torque will be
reduced, depending upon the voltage drop in the impedance of
the supply system. It is the preferred method, especially when
high inertia loads requiring high breakaway torques are required
EMTP simulation of the terminal short circuit of a 900-hp induction motor.
276
CHAPTER ELEVEN
TA B L E 1 1 - 3
Starting Method of Motors
STARTING METHOD
REFERENCE
FIGURE NO.
I STARTING
T STARTING
COST RATIO
Full-voltage starting
Fig. 11-12a
1
1
1
Simplest starting method giving highest starting
efficiency, provided voltage drops due to inrush currents
are acceptable
Reactor starting
Fig. 11-12b
a
a2
2.5
Simple switching closed transition, torque per kVA is
lower as compared to autotransformer starting. A single
reactor can be used to start a number of motors.
Krondrofer starting
Fig. 11-12c
a2
a2
3.5
Closed-circuit transition requires complex switching:
(a) close Y, then S; (b) open Y; (c) close R; and
(d) open S. Applicable to weak electrical systems,
where the reduced starting torque of motor can still
accelerate the loads.
Part-winding starting
Fig. 11-12d
a
a2
Shunt capacitor starting
Fig. 11-12e
Varies
Varies
Shunt capacitor in
conjunction with other
reduced voltage starting
Fig. 11-12f
Varies
Varies
Low-frequency starting
Fig. 11-12g
Varies
(150–200%
of load
current)
Slightly
more than
load torque
Pony motor
Fig. 11-12h
-
-
to be accelerated. Conversely, a very fast run up of low inertia
loads can subject the drive shaft and coupling to high mechanical
torsional stresses.
Reactor Starting (Fig. 11-12b) A starting reactor tapped at 40,
65, and 80 percent and rated on an intermittent duty basis is generally used. It allows a smooth start with an almost unobservable
disturbance in transferring from the reduced to full voltage (when
the bypass breaker is closed). The reactor starting equipment and
controls are simple, though the torque efficiency is poor. Reactance
of the reactor for a certain tap can be approximately calculated by
the expression: X = (1 −R)/R, where R is the tap ratio or the voltage
ratio in per unit of the rated voltage. Thus, the starting current at a
particular tap is given by:
Is =
I
Zs + Zm + ZL
(11-70)
Varies
3
QUALIFICATIONS
Inrush current depends upon design of starting winding.
Closed-circuit transition by switching the parallel stator
winding by closing R. The starting torque cannot be
varied and fixed at the design stage. Start: close S.
Run: close R.
May create harmonic pollution (harmonic filters are
required). Capacitors switched off by voltage/current
control when the speed approaches approximately
95 percent of the full-load speed (bus voltage rises
as the motor current falls). Start: close S 1, S2.
Run: open S2.
Varies
6–7
Varies
A reactor starting with shunt capacitors has twofold
reduction in starting current, due to reactor and
capacitor. The motor terminal voltage and torque
is increased as compared to reactor start.
May create harmonic pollution, not generally used
due to high cost. Gives a smooth acceleration.
The current from supply system can be reduced to
150–200% of the full load current. One low-frequency
starting equipment can be used to start a number of
motors in succession by appropriate switching.
Not generally used. The starting motor is high-torque
intermittent-rated machine. Applicable when load
torque during acceleration is small. Synchronizing
required at R.
It is in per unit based upon the motor rated voltage. Zs, Zm, and
ZL are the system, motor, and reactor impedances, reduced to a
common base, say motor starting kVA base, and are vector quantities; respectively, they also give the starting power factor. As these
impedances act as a potential divider, the starting voltage at the
motor terminals is simply Is Zm.
The motor starting impedance can be calculated by (V / 3 × I s ),
where V is the motor-rated line-to-line voltage and Is is the starting
current at the motor at starting power factor.
Krondroffer Starting (Fig. 11-12c) An advantage of this
method of starting is high torque efficiency, at the expense of additional control equipment and three switching devices per starter.
Current from the supply system is further reduced by factor a, for
the same starting torque obtained with a reactor start. Though close
transition reduces the transient current and torque during transition, a quantitative evaluation is seldom attempted. The motor
FIGURE 11-12
Starting methods of motors.
277
278
CHAPTER ELEVEN
voltage during transition may drop significantly. For weak supply
systems, this method of starting at 30 to 45 percent of the voltage
can be considered, provided the reduced asynchronous torque is
adequate to accelerate the load.
Part-Winding Starting (Fig. 11-12d) The method is applicable
to large synchronous motors of thousands of horsepower designed for
part-winding starting. These have at least two parallel circuits in the
stator winding. This may add 5 to 10 percent to the motor cost. The
two windings cannot be exactly symmetrical in fractional slot designs,
and the motor design becomes specialized regarding winding pitch,
number of slots, and the coil groupings. The starting winding may be
designed for a higher temperature rise during starting. Proper sharing
of the current between paralleled windings, limiting temperature rises,
and avoiding hot spots become a design consideration. Though no
external reduced voltage starting devices are required and the controls
are inherently simple; the starting characteristics are fixed and cannot
be altered. Part-winding starting has been applied to large thermomechanical pulping (TMP) synchronous motors of 10000 hp and
above, yet some failures have been known to occur.
Capacitor Starting (Fig. 11-12e and f) The power factor of
the starting current of even large motors is low, rarely exceeding 0.25.
Starting voltage dip is dictated by the flow of starting reactive power
over mainly inductive system impedances. Shunt-connected power
capacitors can be sized to meet a part of the starting-reactive kvar,
reducing the reactive power demand from the supply system. The
voltage at the motor terminals improves and, thus, the available asynchronous torque. The size of the capacitors selected should ensure a
certain starting voltage across the motor terminals, considering the
starting characteristics and the system impedances. As the motor
accelerates and the current starts falling, the voltage will increase and
the capacitors are switched off at 100 to 104 percent of the normal
voltage, sensed through a voltage relay. A redundant current switching
is also provided. For infrequent starting, shunt capacitors rated at
60 percent of the motor voltage are acceptable. When harmonic
resonance is of concern, shunt capacitor filters can be used.
Capacitor and reactor starting can be used in combination
(Fig. 11-12f ). A reactor reduces the starting inrush current and a capacitor compensates part of the lagging starting kvar requirements. These
two effects in combination further reduce the starting voltage dip.7
Low-Frequency Starting or Synchronous Starting
(Fig. 11-12g) Cycloconverters and load-commutated invert-
ers (LCI) have also been used for motor starting.8,9 During starting
and at low speeds, the motor does not have enough back EMF, so
to commute the inverter, thyristors and auxiliary means must be
provided. A synchronous motor runs synchronized at low speed,
with excitation applied, and accelerates smoothly as LCI frequency
increases. The current from the supply system can be reduced to 150
to 200 percent of the full-load current, and the starting torque need
only be slightly higher than the load torque. The disadvantages are
cost, complexity, and large dimensions of the starter. Tuned capacitor filters can be incorporated to control harmonic distortion and
possible resonance problems with the load-generated harmonics.
Large motors require a coordinated starting equipment design.
Figure 11-12g shows that one starter can be switched to start a
number of similar rated motors. In fact, any of the reduced-voltage
systems can be used to start a number of similar motors, though
additional switching complexity is involved.
Starting Through an Auxiliary Motor (Fig. 11-12h) It is an
uncommon choice, yet a sound one in some circumstances involving a large machine in relation to power supply system capabilities.
No asynchronous torque is required for acceleration and the motor
design can be simplified. The starting motor provides an economical solution only when the load torque during acceleration is small.
Disadvantages are increased shaft length and the rotational losses of
the starting motor, after the main motor is synchronized.
11-6-1
Starting Considerations
When deciding upon a starting method, considerations include
load characteristics, frequency of starting, motor and power system characteristics, and maximum acceptable voltage dip. When
the motors are started on utility systems with no nearby generators,
the starting voltage dip lasts approximately for the entire duration
of starting. When there is a generator running in synchronism with
a utility source, it will share a part of the starting kvar requirement,
and the voltage recovery will be faster. The voltage recovery profiles
in these two cases, therefore, differ widely.
Acceptable Voltage Dips A large starting voltage dip may have
the following adverse effects:
■
It may reduce the net accelerating torque of the motor
below the load torque during acceleration and result in lockout
and unsuccessful starting or synchronizing.
■
DC motor contactors in NEMA E1 and E2 medium-voltage
motor controllers10 may tolerate a voltage dip of 30 percent
or more; however, the auxiliary control relays may drop out
earlier. The low-voltage motor contactors will be more
susceptible to voltage dips and may drop out in the first cycle
at a lower voltage dip. The exact drop out value is difficult to
estimate because of residual flux trapped in the contactor coil.
Drop out between 20 and 70 percent of the voltage can occur.
■
Induction motors experience a higher slip, and the torque
angle of synchronous motors increases. On restoration of the
voltage, the induction motors will reaccelerate, increasing the
current demand from the supply system, which will result in
more voltage drops. This phenomenon is cumulative and the
resulting large inrush currents on reacceleration may cause a
shutdown.
AC motors can tolerate a much higher voltage dip for a longer
duration, as compared to electronic systems. The lower tolerance
limits to abort a process interruption will be set by these systems,
rather than the stability of ac motors on voltage dips.
Limitations of the Supply System The utilities may impose
restrictions on the reactive power demand and acceptable voltage
dips in their systems during starting of large motors.
Motor Characteristics Only a limited choice can be exercised
in a particular design to alter the starting characteristics, that is, a
reduction in starting current will affect the complete starting torquespeed characteristics. In a synchronous motor, the starting winding
should have a high resistance to develop a higher starting torque,
and the same winding acts as a damper winding, after the motor is
synchronized. To rapidly damp out the torque angle pulsations on
a disturbance or fluctuating load, this winding should have lower
resistance, which conflicts with higher torque starting requirements.
Compromises are, therefore, necessary. A solid-pole synchronous
motor, generally, has a higher starting power factor as compared to
the laminated-pole motor, which reduces the reactive kvar demand
per kVA of starting impact.
Number of Starts and Load Inertia NEMA6 specifies two
starts in succession with the motor at ambient temperature and
for the WK2 of load and the starting method for which the motor
was designed, and one start with the motor initially at a temperature not exceeding its rated temperature when loaded. If
the motor is required to be subjected to more frequent starts, it
should be so designed. The starting time is approximately given
by the expression:
t=
2 . 74∑ WK 2 N s2105
Pr
dn
− Tl
a
∫T
(11-71)
TRANSIENT BEHAVIOR OF INDUCTION AND SYNCHRONOUS MOTORS
where t is the accelerating time in seconds, Pr is the rated output,
and the other terms used have already been described before. As
per Eq. (11-71), accelerating time is solely dependent upon the
load inertia and inversely proportional to the accelerating torque.
The normal inertia loads of the synchronous and induction motors
are tabulated in Ref. 6. For a synchronous machine it is defined by
the following equation:
WK 2 =
0 . 375(hp rating )1.15
(speed rpm/1000)2
lb -ft 2
(11-72)
The heat produced during starting is given by the following
expression:
h = 2 . 74∑ WK 2 N s210−6 ∫
Ta
sds
Ta − Tl
(11-73)
where h is the heat produced in kW-sec, and, again, it depends on load
inertia. The importance of load inertia on the starting time and accelerating characteristics of the motor is demonstrated in Eq. (11-73).
11-7
STUDY OF STARTING TRANSIENTS
The methodology for evaluating the starting performance and transients of motors varies, depending on the specific needs of the system study. This requires simple to complex modeling, depending
upon the nature of the study. Following is the industry practice:
1. Snapshot study. Many times the initial voltage dip on starting is of only interest. This can be simply done by a load-flow
algorithm. While no idea of the transients or starting time and
profiles of torque, slip, or current can be made, the load-flow
algorithms give a steady-state picture for the specified loading
conditions. The starting impact load of the motor is modeled
and the system voltage dips for various switching conditions
can be calculated, after the base case is established. This is also
called the static motor starting study and is not of interest here.
2. Dynamic motor starting. The dynamic motor starting will
plot out the starting motor torque, current, slip, accelerating time, and the like. A more detailed model of the load and
motor torque-slip characteristics and inertia is required.
3. Transient stability–type programs. Transient stability–type
programs (Chaps. 12 and 13) can be used. These will analyze the transients in the generators, load buses, and running
motors on starting impact load of a motor (Example 11-5).
4. EMTP-type programs. EMTP-type programs give the real
nature of transient behavior of the motors during starting in
time or frequency domain.
Example 11-3 Dynamic starting of a 900-hp motor of specifications of Example 11-2 is simulated. The motor drives a boiler
induced draft (ID) fan; H of the motor and load = 3.37 s. The system configuration is shown in Fig. 11-10a, and the motor and load
starting torque profile is in Fig. 11-10b. Switch S2 is closed to start
the motor, and switch S1 is open.
The starting transients are plotted in Fig. 11-13. These show
motor kW and kvar demand and kW output; motor and load
torque and the accelerating torque; the slip; the starting current;
and the bus voltage. The starting time is 16 s. Some boiler ID fans
may take 50 to 60 s to accelerate due to high load inertia.
Example 11-4 Example 11-3 is repeated with EMTP simulation.
The motor is started unloaded to reduce the starting time, H = 1 s.
The purpose is to illustrate the nature of transients and the difference
with respect to conventional dynamic starting study. Figure 11-14a,
279
b, and c shows the motor current in phase a, electromagnetic torque
in Newton-meter (N-m), and the motor slip; respectively. Generally,
EMTP simulation is not used due to complexity.
11-8
SYNCHRONOUS MOTORS
Synchronous motors of the revolving-field-type can be divided into
two major types:
■
Salient solid-pole synchronous motors. These are provided
with concentrated field windings on the pole bodies
■
Cylindrical rotor synchronous motors. These have distributed
phase windings over the periphery of the rotor which is used for
starting and excitation.
The salient-pole synchronous motor can again be classified into
two types. The solid-pole type has poles in one-piece of solid mass,
made of cast steel, forged steel, or alloy steel. The starting torque is
produced by eddy currents induced in the pole surface. Sometimes,
slots are provided in the pole surface to absorb thermal stresses. A
solid-pole construction offers high thermal and mechanical reliability, and its large starting torque makes this construction suitable for
starting high inertia loads, for example blowers, compressors, and
sintering machines.
Salient-laminated-pole type has poles of punched sheet steel,
laminated, compressed, and formed. The pole head may be
equipped with starting windings of the deep-slot squirrel-cage type
or double squirrel-cage type. A low-resistance starting winding will
give low starting torque but high pullout torque, and vice versa. A
double-cage winding can give high starting torque, while limiting
the inrush currents, and when synchronous speed is reached, the
low-resistance cage functions to produce large pull-in torque.
The performance characteristics can be depicted by V curves,
extended into generator region to show the reversible nature of synchronous machines (Fig. 11-15). The effect of excitation on stability
is apparent, and we will return to this topic in Chap. 13. A synchronous motor is more stable when operating at a leading power factor;
conversely, a generator is more stable when operating at a lagging
power factor, that is, supplying reactive power into the system.
A brief reference is made to synchronous induction motors, which
can again be of a salient-pole or cylindrical rotor type. The rotor is
constructed similar to a wound rotor induction motor, though the air
gap is larger than that of an induction motor to increase the pullout
torque. The rotor winding is of low resistance and can be connected
to external resistors for starting, permitting an easy and smooth start
even with heavy loads and giving highest torque efficiency. These
motors can be designed to operate as induction motors for a short
period when these fall out of step, that is, due to a sudden reduction
in system voltage or excessive load torque and resynchronize automatically on reduction of load torque or restoration of voltage. The
motor can operate as an induction motor for 10 to 15 s, when the
system voltage has dipped to 45 percent of the rated voltage. Automatic resynchronizing on restoration of voltage to 90 percent of the
rated value is possible. Some disadvantages are small thermal capacity of the rotor, special low-voltage excitation systems, and added
starting, excitation, and control equipment costs. These have been
used in rolling mills and mine ventilating fans; but are getting out of
favor due to complexity of starting equipment and controls.
The starting of synchronous motors should consider similar factors as discussed for the induction motors, with the addition of
synchronization, pulling out of step, and resynchronization.
The synchronous motor design permits lower starting currents
for a given starting torque as compared with a squirrel-cage induction motor, typically, in ratio of 1:1.75. This may become an important system design consideration, when the starting voltage dips in
the power system have to be limited to acceptable levels.
280
CHAPTER ELEVEN
FIGURE 11-13
Dynamic starting study of 900-hp motor starting transients. FLA, full load current.
Based upon the motor rating and speed, a general application of
synchronous and induction motors is depicted in Fig. 11-16. For
low-speed applications, motor efficiency becomes of consideration—
the induction motor efficiency drops because of leakage reactance
of the stator winding overhangs. For a relative comparison, the efficiency of a 16-pole induction motor and synchronous motor may be
92 percent versus 96.5 percent.
11-8-1
Starting Characteristics
Figure 11-17 depicts the starting characteristics of two basic types
of synchronous motors: salient pole and laminated pole. Salientpole motors have higher starting torque (curve a) and pulsating or
oscillating torque (curve b). The cylindrical rotor machines have
starting torque characteristics akin to induction motors (curve c)
and smaller oscillating torque (curve d). Salient-laminated-pole construction with damper windings may produce a characteristic somewhere in-between the solid-pole and cylindrical rotor designs.
Referring to Fig. 11-17, Ta is the asynchronous torque of the
motor analogous to the induction motor starting torque, as a synchronous motor is started asynchronously. The rotor saliency causes
another torque Tp, which pulsates at a frequency equal to twice the
slip frequency. Considering a supply system frequency of f Hz,
and a rotor slip of s, the magnetic field in the rotor has a frequency
of sf. Due to saliency it can be divided into two components:
TRANSIENT BEHAVIOR OF INDUCTION AND SYNCHRONOUS MOTORS
(a) a forward-revolving field at frequency sf in the same direction
as the rotor, and (b) a field revolving in reverse direction at sf. Since
the rotor revolves at a speed (1 −f )s, the forward field revolves at
(1 −s)f + sf, that is, at fundamental frequency with respect to stator,
in synchronism with the rotating field produced by the stator threephase windings. The interaction of this field with the stator field
produces the torque Ta in a fixed direction. Negative sequence field
revolves at: (1 −f )s −sf =(1 −2f )s This is as viewed from the stator
and, thus, it has a slip of f −(1 −2s)f =2sf with respect to the field produced by the exciting current. Figure 11-18 shows these relative rotations of stator and rotor fields in a synchronous motor during starting.
The total torque produced by the synchronous motor is therefore:
Tm = Ta + Tp cos 2sωt
FIGURE 11-14
(11-74)
281
The currents corresponding to the positive and negative fields are Ia
and Ip, respectively. The current Ia is at fundamental frequency and
Ip is the pulsating current at (1 −2s)f Hz. The total current is given
by the expression:
I = I a cos(ωt − φ ) + I p cos(1 − 2s)ωt
(11-75)
where φ is the power factor angle at starting.
The above treatment of the asynchronous torque during starting of the synchronous motors with solid poles or laminated poles
and damper windings is not exhaustive. The asynchronous torque
can be considered to have three components, generated by direct
axis and quadrature axis circuit, and the single-axis motor-exciting
winding also contributes to the starting torque. Due to electrical
(a) Phase a current, (b) electromagnetic torque, and (c) slip of 900-hp motor starting transients.
282
CHAPTER ELEVEN
FIGURE 11-14
FIGURE 11-15
(Continued )
V curves showing the reversible nature of synchronous machines.
TRANSIENT BEHAVIOR OF INDUCTION AND SYNCHRONOUS MOTORS
FIGURE 11-18
283
Relations of rotating fields in a synchronous motor,
during starting.
FIGURE 11-16
General application guidelines of synchronous and
induction motors based upon motor rating and number of poles.
less than 0.5, the direction of the torque changes; this produces a
characteristic saddle. The average starting torque and the starting
current can be calculated based upon the direct axis and quadrature
axis equivalent circuits of the synchronous machine.1,2
Comparison of the starting torque speed characteristics of the
cylindrical rotor versus solid-pole motors in Fig. 11-17 indicates
that a solid-pole motor produces highest torque at the starting
instant. The load curves follow mostly square law characteristics.
The cylindrical rotor design has the following advantages as compared to solid-pole designs:12,13
1. At speeds close to the synchronizing speeds, the torque of
a salient-pole motor reduces; this may make the synchronizing
difficult.
2. The solid-pole motor has a considerably large pulsating
torque as compared to a cylindrical rotor machine, as the magnetic asymmetry in the later type is minimized. These higher
pulsating torques stress the shaft, motor, and drive system.
3. The first natural frequency of a motor-driven load lies
between 5 and 25 Hz. Thus, higher torsional stresses will
occur in solid-pole motors, every time these are started.
4. A cylindrical rotor machine, in principle, is suitable for
asynchronous running, and depending upon the design of the
starting winding, the motor can be operated at 50 to 90 percent
of its rated output. The salient-pole motors have no continuous
asynchronous running ratings, as the saliency causes torque
pulsations, and slip-proportional losses lead to overheating of
pole surfaces and the starting windings.
F I G U R E 1 1 - 1 7 Torque-speed characteristics of synchronous motors.
Curves a and b starting and pulsating torque of solid-pole synchronous
motors, curves c and d starting and pulsating torque of cylindrical rotor synchronous motors, and curve e load torque curve.
Conversely the solid-pole motors give a higher breakaway
torque, and lesser heat energy is produced in the solid-pole rotors
during starting. Solid-pole motor designs have been successfully
applied in large four-pole motors of 25000 hp or higher.
and magnetic asymmetry, Ta develops a sudden change near 50 percent speed, resulting in a singular point. This is called the Gorges
phenomenon.11 The shape and size of this dip are governed by the
machine data and the power system. If resistance is zero, the saddle
disappears. Solid-poles motor without damper windings and sliprings will give a more pronounced saddle, while the saddle is a
minimum in cylindrical rotor and laminated-pole constructions
with damper windings. The external resistances during asynchronous starting impact all Ta, Tp, and the saddle. At slip s =0.5, the
reverse rotating field comes to a halt as viewed from the stator, and
torque Tp becomes zero, so also the pulsating current Ip. For slip
11-8-2
Pullin Torque of a Synchronous Motor
Figure 11-17 also shows the load torque Tl during starting (curve e).
The accelerating torque is Ta − Tl and the motor will accelerate till
point A, close to the synchronous speed. At this moment, pullin
torque refers to the maximum load torque under which the motor will
pull into synchronism while overcoming inertia of the load and the
motor when the excitation is applied. The torque of the motor during
acceleration as induction motor at 5 percent slip at rated voltage and
frequency is called nominal pullin torque. Pullin and pullout torques
of salient-pole synchronous motors for normal values of load inertia
are specified in NEMA standards.6 For motors of 1250 hp and above,
284
CHAPTER ELEVEN
speeds 500 to 1800 rpm, the pullin torque should not be less than 60
percent of the full-load torque. The maximum slip at pullin can be
approximately determined from the following inequality:
s<
242
Ns
Pm
∑ WK
2
(11-76)
f
where Ns is the synchronous speed in rpm, f is the system frequency, Pm is the maximum output of the synchronous motor with
excitation applied, when pulling into synchronism, and WK2 is the
inertia of the motor and driven load in kg-m2.
It is necessary to ascertain the load torque and operating requirements before selecting a synchronous-motor application. For example, wood chippers in the paper industry have large pullout torque
requirements of 250 to 300 percent of the full-load torque. Banbury
mixers require starting, pullin, and pullout torques of 125 percent,
125 percent, and 250 percent, respectively. Thus, the load types are
carefully considered in applications. Load inertia impacts the heat
produced during starting and the starting time. NEMA6 gives the
starting requirements of pumps and compressors and inertia ratios.
11-8-3
Synchronization Transients
A synchronous motor is synchronized during the starting cycle
by application of the field excitation at (a) proper rotor speed and
(b) proper rotor angle. The rotor speed is sensed by the frequency
of induced currents in the field windings during starting, when the
rotor has accelerated close to 92 to 97 percent of the rated speed.
The rotor angle is sensed by the point where induced current passes
through zero going from negative to positive and the excitation is
applied with correct polarity so that maximum torque is obtained
at the pullin. Application at wrong polarity will result in swinging.
The successful synchronization is dependent upon:
1. Slip
2. Opposing torque
3. Field current applied
4. Machine data
A lightly loaded motor can synchronize without external excitation due to reluctance torque. Excitation system should also provide
a discharge path for the current induced in the field during starting.
FIGURE 11-19
Excitation can be boosted during shock loads and system voltage
depressions to counteract the possibility of the motor pulling out
of step. If the motor does pull out of step, the excitation should be
removed.
Earlier excitation systems were of the rotary type consisting of a
special dc generator with a shaft-mounted commutator, and the dc
voltage was applied to the motor through brushes and slip rings.
These were replaced with single-phase or three-phase diode bridges,
and the excitation could only be varied through taps on the rectifier transformer. Phase-controlled rectifiers and brushless excitation
systems were subsequent developments.
The excitation system of a synchronous motor must provide a
discharge path for the currents induced in the field windings of the
motor during starting and open the discharge resistor when the
excitation is applied, reinserting it in the circuit when the motor
pulls out and the excitation is removed. At standstill, field windings
are open circuited, and high voltages of the order of 10 to 40 kV
can be induced in the field windings, which act akin to the open
circuited secondary of a transformer.
The discharge resistor has also an effect upon the torque near the
synchronous speed; this effect is more pronounced in salient-pole
construction. A compromise in the resistor value is made depending upon the motor design.
11-8-4
Brushless Excitation Systems
Figure 11-19 shows a brushless excitation system which meets
the above criteria. The ac output of the rotating armature exciter is
converted into dc, but the control circuit blocks SCR1 from firing
until the induced frequency in the rotor circuit is low. When the
field terminal MF1 is positive, with respect to MF2, the diode D
conducts, and on the reverse cycle SCR2 conducts during starting and connects the discharge resistor FD across the motor field
windings MF. This protects the motor windings and electronics
from high induced voltages. As the induced frequency of the current in the field windings decreases, the frequency part of the control circuit blocks SCR2, and simultaneously SCR1 conducts to
apply the field excitation. A zero slip circuit is included to apply
excitation if the motor synchronizes on reluctance torque.
On first half cycle after pullout, the induced field voltage
across SCR1 switches it off, removing the motor excitation, and
SCR2 conducts to reconnect the discharge resistor across the
field windings. If the motor does not synchronize, it will slip a
pole; the induced field voltage opposes the exciter voltage causing current to go to zero, turning off SCR1. The SCR2 is turned
Brushless excitation system for a synchronous motor.
TRANSIENT BEHAVIOR OF INDUCTION AND SYNCHRONOUS MOTORS
285
on only at a voltage higher than the exciter voltage and will not
be conducting when SCR1 is conducting. There is a positive
interlocking between SCR1 and SCR2. Figure 11-20 shows voltages during one cycle and Figs. 11-21 and 11-22 depict the field
current and field voltage transients during starting. The circuit of
Fig. 11-20 can be applied to brush type as well as to brushless
type of excitation systems.
11-9
STABILITY OF SYNCHRONOUS MOTORS
The simplified current and power diagram of a synchronous motor
is depicted in Fig. 11-23a. The derivation follows from Fig. 11-15,
and is also arrived analytically in many texts.4 The reactive power can
be varied by control of excitation. The variation range of the excitation current Ie is limited by maximum operating temperature of the
stator and rotor and by the stability limit of the motor. In this figure
the stator temperature limit is shown by a dotted arc, and the rotor
temperature limit is shown by a solid arc. The underexcited stability
limit is given by dotted line. The horizontal lines parallel to x-axis
F I G U R E 1 1 - 2 0 Relations during one cycle in the brushless excitation system of Fig. 11-19.
FIGURE 11-21
Field current from brushless excitation system of Fig. 11-19, during starting.
FIGURE 11-22
Field voltage from brushless excitation system of Fig. 11-19, during starting.
286
CHAPTER ELEVEN
F I G U R E 1 1 - 2 3 (a) Simplified current and power diagram of a synchronous motor. (b) excitation controllers, constant current excitation controller,
(c) power factor excitation controller, (d ) and (e) reactive power and voltage excitation controllers, respectively.
are constant-power output lines. At point A the motor operates at
the maximum excitation current at its leading power factor φ . The
stator current can be resolved into active and reactive components.
The active power drawn from the system depends upon the load
torque required, and the reactive power can be varied by control of
excitation.
The unregulated controllers are the simplest in terms of hardware and are brush type. A fixed rectifier transformer with offload tap adjustments supplies excitation power through a field
contactor. The reactive power output at no load will exceed that
at the full load. The system voltage can fluctuate, depending
upon the size of the motor and the Thévenin impedance as seen
from the bus to which the motor is connected. For fluctuating
loads and large motors, this can give rise to instability on overloads, that is, a crusher motor connected to a weak electrical
system. Four major types of regulated excitation systems are:
■
Constant field current. This considers the variation of the
field winding resistance as the motor is loaded; due to temperature rise, the resistance rises and the current falls. A constant
field current is maintained by adjusting the conduction angle
of SCRs (Fig. 11-23b).
■
Constant power factor. The kvar output rises as the motor is
loaded, and this will tend to raise the motor bus voltage. An
impact load will cause power factor to dip and the controller will
respond with a boosted output. This will enhance the stability
limit. In brushless excitation systems, the time constants associated with the pilot exciter and the motor-field windings may
not allow the excitation to respond quickly. Oscillations may
occur on swinging loads and the stability may be jeopardized.
The power factor controllers can be used to regulate the system
power factor, rather than the individual motor (Fig. 11-23c).
■
Constant reactive power output. The motor bus voltage will
be maintained constant from no-load to full load. If a number
of motors are connected to the same bus, the constant reactive
power outputs of the running motor reduce the bus voltage
dip when a motor is started (Fig. 11-23d).
■
Constant voltage controller. The characteristics are similar to
that of var controllers Fig. 11-23e.
Figure 11-24 shows the capability of a synchronous motor to
ride through voltage dips under two conditions: (a) with excitation
held constant, dotted lines for H =5 and 1, and (b) with excitation
TRANSIENT BEHAVIOR OF INDUCTION AND SYNCHRONOUS MOTORS
TA B L E 1 1 - 4
Typical Time Constants of
Excitation System
SYMBOL
F I G U R E 1 1 - 2 4 Stability of a synchronous motor on voltage dips, with
excitation held constant and with excitation varying in direct proportion to supply
system voltage dip. Curves for inertia constants of H = 5 s and 1 s are shown.
reducing in direct proportion to the supply system voltage, full lines
for H =5 and 1. On sudden reduction of voltage, the motor internal
emf will not change instantaneously, and the motor tends to maintain a constant output by increasing the line current. The power factor swings to more leading before it goes lagging. The motor pullout
torque can reduce below the load torque and the motor can still
be stable provided the voltage is restored before the torque angle
swings to the critical limit. In the transient stability studies, the synchronous motors are sometimes modeled with fixed excitation, but
it can give erroneous results. The block circuit diagram of IEEE type
AC5A exciter is shown in Fig. 11-25.14 Typical time constants are in
Table 11-4.15
Example 11-5 This example applies transient stability study to
motor starting. Consider the configuration in Fig. 11-26. There
are three synchronous generators, two utility tie transformers,
and loads consisting of induction and synchronous motors. Total
installed capacity is 164.7 MVA and the load demand is 109 MVA.
The induction motor loads are lumped and connected through
equivalent impedance representing transformers and cables. A
20000-hp synchronous motor is started on 13.8-kV bus M1 (as
an induction motor, synchronizing transients not considered),
while all the generators and motor loads L1, L2, L3, and L4 are in
operation. The impact of starting a large 20000-hp motor on the
stability of smaller 2000-hp, 4-kV synchronous motor, connected
to 3.75-MVA transformer T3, as well as on the stability of running
FIGURE 11-25
287
RANGE OF VALUES
KA
400–500
TA
0.003–0.08
KF
0.005–0.054
TF 1
0.22–0.65
TF 2
0.04–0.1
TF 3
0–0.004
KE
1
TE
0.55
SE, max
1.2–2.2
SE, 0.75 max
1.0–2.0
induction motor loads is examined. All motors are modeled with
their inertia constants and load torque characteristics. All generators use subtransient models, and IEEE type ST1 excitation systems (Chap. 13).
This system configuration is for the purpose of an illustrative
example. When such large motors are to be started, these are connected to dedicated buses, so that the starting impacts are not
passed on to the smaller loads on the same buses. It implies that
small system loads and large motor loads are connected to separate
buses for better stability limits.
The starting impact of the 20000-hp motor is 15.2 MW of
active and 72 Mvar of reactive power. The transients are shown in
Fig. 11-27a through h.
1. Active and reactive power swings in running 2000-hp
synchronous motor SM2 are depicted in Fig. 11-27a. These
transients are of larger magnitude toward the lapse of starting
period than at the instant of starting impact. Mechanical load is
assumed constant.
2. Figure 11-27b shows the voltage at bus M1 and 2000-hp
motor terminals SM2, which dips by 16 percent below rated
voltage. Generator G1 terminal voltage dips by 13.5 percent.
The starting time is approximately 5 s, and the voltage
recovers to 95 percent within 1 s after starting impact. This
is because of the generators excitation system response
and generators taking a considerable impact of the starting
demand. Note the overshoot in the voltage recovery profile,
which is very typical.
Control circuit block diagram of IEEE type AC5A excitation system.
288
CHAPTER ELEVEN
FIGURE 11-26
Circuit diagram for study of starting impact of a 20000-hp synchronous motor.
3. Figure 11-27c shows torque angle swings of 20000-hp
synchronous motor and generator G1; the torque angle recovers quickly, showing stability.
4. Swings in the active and reactive power output of G1 can
be noted in Fig. 11-27d. The reactive power of the generator
jumps to approximately 60 Mvar in response to the starting
reactive power demand. Generators G2 and G3 also experience
similar transients, not shown.
5. Figure 11-27e illustrates that field current of the generator
jumps to 6.2 times, and similar excursion in the field voltage,
5.2 pu, occurs. The other two generators’ excitation systems
experience similar transients to a lesser extent, not shown.
6. Active and reactive power oscillations in the 115 kV utility
are depicted in Fig. 11-27f; note the post starting transients.
7. Figure 11-27g illustrates that speed of induction motors
lumped on bus M1, which dips on the starting impact, recovers through an upward excursion of the speed transient.
8. Finally, Figure 11-27h shows active and reactive power
oscillations of the induction motor loads connected to bus M2.
The simulation illustrates that the motor can be started; however, the bus M1 experiences a voltage dip of approximately
14 percent, which may not be acceptable for the stability of some
of the loads connected to that bus.
PROBLEMS
1. Derive the equivalent circuit of a double-cage induction
motor shown in Fig. 11-2c, following the mathematical model
developed for single-cage rotor in the text.
2. The standstill impedances of the inner cage and outer cage of
a double-cage induction motor are: inner cage = 0.15 + j1.6 Ω,
outer cage = 0.5 + j5 Ω.Compare the relative currents and
torques of these two cages at standstill and at a 4 percent slip.
3. A 1000-hp, 4-pole, 60-Hz induction motor has a breakdown torque of 175 percent, critical slip sm =10 percent,
full load slip = 2 percent, and H = 3.3 s. Assume that the
motor and load speed-torque characteristics are as shown in
Fig. 11-10b. Calculate the stability curve under voltage dips
similar to the one shown in Fig. 11-8.
4. A three-phase squirrel cage induction motor takes a starting
current six times the full-load current and has a full-load slip
of 3 percent. Calculate: (1) starting torque in terms of full-load
torque, (2) slip at the maximum torque, and (3) the maximum
torque in terms of full-load torque.
5. Consider the induction motor of Example 11-2. Calculate
short-circuit current profiles, ac symmetrical component, dc
component, and the total current over a period of eight cycles
from the instant of short circuit, and compare the results with that
of EMTP simulation shown in Fig. 11-11. Why do these differ?
F I G U R E 1 1 - 2 7 (a) Active and reactive power transients in synchronous motor SM2. (b) Bus M1 voltage and the voltage at the terminals of synchronous motor SM2. (c) Torque angle transients, synchronous
motor SM1 and generator G1. (d ) Active and reactive power transients, generator G1. (e) Field current and voltage generator G1. (f ) Active and reactive power flow from the utility source. (g) Speed transient of induction
motor loads L2. (h) Active and reactive power transients, induction motor loads L3. (Continued )
289
290
FIGURE 11-27
(Continued )
TRANSIENT BEHAVIOR OF INDUCTION AND SYNCHRONOUS MOTORS
291
6. Compare the starting characteristics of cylindrical rotor and
salient pole synchronous motors. What are the relative advantages
and disadvantages? What is Gorges phenomena and what causes it?
7. G. S. Sangha, “Capacitor–Reactor Start of Large Synchronous
Motor on a Limited Capacity Network,” IEEE Trans. Industry
Applications, vol. IA-20, no. 5, Sept./Oct. 1984.
7. A 2000-hp, three-phase, 2.3-kV, 4-pole, 60-Hz induction motor is connected to the secondary of a 2.5-MVA, 13.8
to 2.4-kV transformer; transformer percentage impedance =
5.5 percent, and X/R =10. The transformer is served from a
13.8-kV system; source positive sequence impedance = 0.03 +
j 0.3 pu on a 100-MVA base. The motor starting current is
2600 A at a power factor of 0.10. The total load and motor H =
3.64 at the motor speed. Full-load slip =1.5 percent. Consider
that the load torque and motor torque-speed characteristics are
given by the curves in Fig. 11-10b.
Plot the starting current, bus voltage, and motor slip for the
following methods of starting:
8. J. Langer, “Static Frequency Changer Supply System for Synchronous Motors Driving Tube Mills,” Brown Boveri Review,
vol. 57, pp. 112–119, March 1970.
Across the line starting
Reactor starting at 0.5 tap
Autotransformer starting at 0.5 tap
Capacitor starting, with a shunt capacitor of 5 Mvar. Consider that the capacitor is disconnected when the motor has
reached 95 percent speed.
8. A three-phase short circuit occurs at the terminals of an
induction motor. Will the short-circuit current vary with the
system impedance to which the motor is connected?
9. A synchronous motor connected to a weak electrical system
drives a fluctuating load. What type of excitation controller
will be appropriate? Will it be desirable to resort to field forcing as the load torque cycles?
10. In Fig. 11-27h, why does the reactive power of the running induction motor dip severely, and then recover rapidly?
Explain the upward excursion in transients at the termination
of the starting time.
REFERENCES
1. B. Adkins, General Theory of Electrical Machines, Chapman and
Hall, London, 1964.
2. A. T. Morgan, General Theory of Electrical Machines, Heyden &
Sons Ltd., London, 1979.
3. G. J. Rogers and D. Shirmphammadi, “Induction Machine
Modeling for Electromagnetic Transient Program,” IEEE Trans.
on Energy Conversion, vol. EC-2, no. 4, Dec. 1987.
4. A. E. Fitzgerald, S. D. Umans, Jr., and C. Kingsley, Electrical
Machinery, McGraw Hill Higher Education, New York, 2002.
5. J. C. Das, “Effects of Momentary Voltage Dips on Operation of
Induction and Synchronous Motors,” IEEE Trans. Industry Applications, vol. 36, no. 4, July/Aug. 1990.
6. NEMA MG-1, Motors and Generators, Large Machines, Parts
20 and 21, 2003.
9. C. P. LeMone, “Large MV Motor Starting Using AC Inverters,”
in ENTELEC Conf. Record, TX. May 1984.
10. NEMA ICS 2-324, AC General Purpose HV Contactors and
Class E Controllers, 50 Hz and 60 Hz, 1974.
11. G. L. Godwin, “The Nature of AC Machine Torques,” IEEE
Trans. PAS, vol. PAS-95, pp. 145–154, Jan./Feb. 1976.
12. J. Bredthauer and H. Tretzack, “HV Synchronous Motors with
Cylindrical Rotors,” Siemens Power Engineering, vol. V, no. 5,
pp. 241–245, Sep./Oct. 1983.
13. H. E. Albright, “Applications of Large High Speed Synchronous
Motors,” IEEE Trans. Industry Applications, vol. IA 16, no. 1,
pp. 134–143, Jan./Feb. 1980.
14. IEEE Std 421.5, “IEEE Recommended Practice for Excitation
System Models for Power System Stability Studies,” 1992.
15. J. C. Das and J. Casey, “Effects of Excitation Controls
on Operation of Large Synchronous Motors,” in Conf.
Record, IEEE I&CPS Technical Conference, Sparks, Nevada,
May, 1999.
FURTHER READING
K. Albrccht and K. P. Wever, “A Synchronous Motor with Brushless
Excitation and Reactive Power Control,” Siemens Review, no. 11,
pp. 577–580, 1970.
M. Canny, “Methods of Starting Synchronous Motors,” Brown Boveri
Review, vol. 54, pp. 618–629, Sept. 1967.
C. Concordia, Synchronous Machines—Theory and Performance, John
Wiley, New York, 1951.
J. C. Das and J. Casey, “Characteristics and Analysis of Starting of
Large Synchronous Motors,” in Conf. Record, IEEE I&CPS Technical
Conference, Sparks, Nevada, May, 1999.
J. C. Das, “Application of Synchronous Motors in Pulp and Paper
Industry,” TAPPI Proc., Joint Conf. Process Control, Electrical and
Information, Vancouver, BC, Canada, 1998.
J. R. Linders, “Effect of Power Supply Variations on AC Motor Characteristics,” IEEE Trans. Industry Applications, vol. IA-8, pp. 383–400,
July/Aug. 1972.
O. P. Malik and B. J. Croy, “Automatic Resynchronization of Synchronous Machines,” Proc. IEE, vol. 113, pp. 1973–1976, Dec.
1966.
G. E. Publication GEH-5201, Synchronous Motor Control with CR192
Microprocessor Based Starting and Protection Module, General Electric,
Mebane, NC, 1985.
This page intentionally left blank
CHAPTER 12
POWER SYSTEM STABILITY
In this chapter, the stability of power systems is discussed and
analyzed. The texts on transients consider power system stability a
separate subject, yet inclusion of this subject in this book provides
an insight into an important aspect of transient behavior of power
systems.
A power system is highly nonlinear and continuously experiences disturbances. From the stability point of view, these can be
classified into two categories:
1. Contingency disturbances due to lightning, short circuits,
insulation breakdowns, and incorrect relay operations. These
can be called large perturbations or event disturbances.
2. Load disturbances because of random variations in the load
demand.
There are many definitions of the power system stability in the
literature, however, with respect to fault disturbances and an initial
(prefault) steady-state equilibrium point (s.e.p), it explores whether
the postfault trajectory will settle down to a new equilibrium point
in an acceptable steady state. The definition of the final steady state is
important. For example, if the postfault state has periodic oscillations,
this will not be acceptable. Even small fluctuations in the voltage and
frequency will be undesirable. Nor subsynchronous resonance, which
may occur due to conversion of mechanical energy into electrical
energy associated with subharmonic mode and electromagnetic oscillations (due to interactions between magnetic fields), can be tolerated.
12-1 CLASSIFICATION OF POWER
SYSTEM STABILITY
The classification of the stability is necessary in view of:
1. The size of disturbance
2. Correct modeling and analysis of the specific disturbance
3. The time span for which the disturbance lasts
4. The system parameter which is most affected
The power system stability is classified into the following categories:
12-1-1
Rotor Angle Stability
This is large disturbance stability and concerned with the ability of
interconnected synchronous machines to remain in synchronism
after being subjected to a perturbation. This can be further subdivided into two categories:
1. Small-signal or small disturbance stability (sometimes
termed dynamic stability)
2. Large disturbance rotor angle stability
As the nomenclature suggests, the small signal stability considers
that the disturbances are small and the system equations can be linearized. Sometimes, the small rotor angle stability is termed dynamic
stability. In modern systems, it is largely a problem of insufficient
damping of the systems. The study is conducted for 10 to 20 s and
sometimes even for a longer period after a disturbance.
Conditions for oscillations between major subsystems may depend
on many variable factors, that is, loading of generators, load levels,
and system voltages, which are difficult to predict with precision.
The subharmonic frequencies can be reduced with the application of power system stabilizers (PSS). When a PSS is not applied,
a fast-acting or wider-band excitation system has greater chance of
destabilizing local-machine system oscillations. The National Electric Regulatory Council (NERC) recommends PSS for generators that
exceed 30 MVA or a group of generators that exceeds 75 MVA.
The large rotor angle stability, or transient stability, as it is normally termed, is concerned when the power systems are subjected
to large perturbations, that is, system faults. The resulting system
response involves large excursions of rotor angle swings, and the
system equations are nonlinear.
Classically, it was thought that due to insufficient damping
torque, the instability occurs during the first swing (Fig. 12-1,
curve a). In large power systems, transient instability may not
occur during the first swing. It can be a result of superimposition
of several oscillation modes, which may result in larger deviation of
rotor angle in subsequent swings, Fig. 12-1, curve b. The curve c
of Fig. 12-1 shows the transient stability as the rotor angle swings
damp out. The time frame of interest may be 1 to 3 s.
The transient mode can sometimes lead to dynamic mode. The rotor
angle may continue to swing at lower frequencies, that is, inter-area
oscillations. Figure 12-2 shows dynamic instability as the oscillations
increase with time. With the application of a PSS, these can be damped,
as shown in the figure. The application of PSS is discussed in Chap. 13.
12-1-2 Voltage Instability
Voltage instability can again be categorized into the following two
categories:
293
294
CHAPTER TWELVE
FIGURE 12-3
Simplified phasor diagram of a generator, resistances
neglected.
FIGURE 12-1
Rotor angle stability under different power system
transients. Curve a, instability during first swing; curve b, instability due to
larger rotor angle swings after a number of swings; curve c, decaying rotor
angle transient depicting stability.
flow in a mainly reactive tie circuit requires a difference of voltage
at the tie ends, DV. A system is said to be stable if V-Q sensitivity
is positive for every bus and unstable if V-Q sensitivity is negative for at least one bus. This V-Q relation is further discussed in
Sec. 12-12.
12-1-3
Static Stability
The term static stability may seem a misnomer for the dynamic
nature of the electrical systems, yet it can be assumed that the
response of a system to a gradually occurring change is without an
oscillation. Practically, this is not correct, but it forms the basis of
some fundamental concepts.
The power angle characteristic of a synchronous generator can be
derived from the basic phasor diagram shown in Fig. 12-3. All resistances and losses are neglected, and all parameters are as defined in
Chap. 10. It can be shown that:
P=
EV sin δ 1 2 1
1
+ V
−
sin 2δ
Xd
2 Xq Xd
cos 2 δ sin 2 δ
EV cos δ
Q=
− V2
+
Xd
Xq
Xd
FIGURE 12-2
Dynamic instability, swings controlled by application
of a PSS (power system stabilizer).
Large Disturbance Instability
The voltages in the system should be controlled following large disturbances, such as
faults, loss of generation, or circuit contingencies, which may
force the power flow through alternate routes of higher impedances. The generators may hit their reactive power capability
limit. The loads have certain voltage tolerance limits for successful ride-through capability of the disturbance before these will fall
out of operation.
The analysis requires nonlinear dynamic performance of the
system over a period of time that can extend to minutes. The rotor
angle instability can lead to voltage instability. The gradual loss
of synchronism, as the rotor angles between the machines depart
more than 180°, would result in low voltages in the network close
to the electrical center.
Small Disturbance Voltage Instability The instability is
concerned with system ability to control voltages following small
perturbations, that is, incremental changes in the system load.
This is essentially of a steady-state nature. The reactive power
(12-1)
The second terms in these equations disappear if saliency is
neglected and Xd = Xq. The saliency gives some element of stability
even when the excitation of the generator is removed.
This shows that for a gradual increase in the power output of
the generator, the torque angle should increase, with phase of V
fixed. In this way, the energy balance is maintained. We say that the
generator is statically stable if:
∂P
>0
∂δ
(12-2)
In fact, this ratio is called the synchronizing power and develops
with every small variation of shaft power output, which results in a
change in d. From Eq. (12-1), the synchronizing power is:
Ps =
1
EV cos δ
1
− V2
−
cos 2δ
xd
Xd Xq
(12-3)
Whenever there is any perturbation to the steady-state operation of a synchronous machine, the synchronizing power is brought
into play, tending to counteract the disturbance and bring the system to a new stable point.
POWER SYSTEM STABILITY
12-2
295
EQUAL AREA CONCEPT OF STABILITY
Equation (12-1) for the power output can be plotted as a powerangle relation, as shown in Fig. 12-4. The angle d is called the
torque angle. The second term in the power output relation has a
sin 2d term, which makes the power-angle curve of the generator
peaky in the first half cycle. Referring to Fig. 12-4, if the output
shaft power demands an increase, from P1 to P2, the torque angle
increases from d1 to d2. The limit of d2 is reached at the peak of the
torque angle curve, dp, then at dp synchronizing power is zero. If
the load is increased very gradually and there are no oscillations
due to a step change, then the maximum load that can be carried is
given by torque angle dp. This maximum limit is much higher than
the continuous rating of the generator and the operation at this
point will be very unstable—a small excursion of load will result
in instability.
It is obvious that excitation plays an important role [Eq. (12-1)].
The higher the E, the greater is the power output. On a simplistic
basis, torque angle curves of a synchronous machine can be drawn
with varying E. Neglecting second frequency term, these will be
half sinusoids with varying maximum peak.
Practically, the situation will not be as depicted in Fig. 12-4. On
a step variation of the shaft power (increase), the torque angle will
overshoot to a point d3 (Fig. 12-5), which may pass the peak of
the stability curve, dp. It will settle down to d2 only after a series of
oscillations. If these oscillations damp out, we say that the stability
will be achieved; if these oscillations diverge, then the stability will
be lost. Note that:
1. The inertia of the synchronous generators and prime
movers is fairly large.
2. The speed and power-angle transients are much slower than
electrical current, and voltage transients.
In Fig. 12-5, the area of triangle ABC translates into the acceleration area due to variation of the kinetic energy of the rotating
masses:
δ2
A accelerating = ABC = ∫ (Tshaft − Te )dδ
(12-4)
δ1
F I G U R E 1 2 - 5 Torque angle swings on a sudden change of generator load, equal area criterion of stability.
The area CDE is the deacceleration area:
δ3
Bdeaccelerating = CDE = ∫ (Tshaft − Te )dδ
(12-5)
δ2
In accelerating and decelerating, the machine passes the equilibrium point given by d2, giving rise to oscillations that will either
increase or decrease. If the initial impact is large enough, the
machine will be unstable in the very first swing.
If:
A accelerating = Bdeaccelerating
(12-6)
Then there are chances of the generator remaining in synchronism. The asynchronous torque produced by the dampers has been
neglected in this analysis; also the synchronizing power is assumed
to remain constant during the disturbance. It is clear that at point
C, the accelerating power is zero, and assuming a generator connected to an infinite bus, the speed continues to increase. It is more
than the speed of the infinite bus, and at point E the relative speed
is zero and the torque angle ceases to increase, but the output is
more than the input and the torque angle starts decreasing; rotor
decelerates. But for damping, these oscillations can continue. This
is the concept of equal area criterion of stability.
Figure 12-6 shows low-frequency oscillations in a multi-machine
system, which has not completely died out even after 14 s. Such
prolonged oscillations are not acceptable.
12-2-1
FIGURE 12-4
Power angle characteristics of a salient-pole generator.
Critical Clearing Angle
From the equal area criterion, it is easy to infer that the disturbance, say a fault, should be removed quickly enough for the
machine stability. The critical clearing angle is defined as the maximum angle at which the faulty section must be isolated to maintain
stability of the system. Figure 12-7 shows three P/d curves, which
are, under normal operation, during fault, and after fault clearance; curves marked A, C and B, respectively. Note that during
296
CHAPTER TWELVE
FIGURE 12-6
Oscillations, dynamic stability, in a multi-machine system.
fault, some synchronizing power can be transmitted, depending
on the nature of fault and the system configuration. For the condition that area A1 = A2 (same results if we make rectangle abcd =
dfghbc, because abcd = A1 + kebc and dfghbc = A2 +kebc), this
gives the following equation:
δc
δm
δ0
δc
(δ m − δ 0 )Ps = ∫ r1Pm sin δ dδ + ∫ r2 Pm sin δ dδ
(12-7)
Substituting:
Ps = Pm sin δ
(12-8)
and referring to Fig. 12-7, during fault, maximum power Pm is
reduced by a factor r1, and after fault it is r2Pm. This gives:
cos δ c =
(δ m − δ 0 )sin δ 0 − r1 cos δ 0 + r2 cos δ m
r2 − r1
(12-9)
where δ c is the critical clearing angle. If the actual clearing angle is
greater than the critical clearing angle, the system will be unstable.
This brings an important factor in transient stability, that is, fast
protective relaying and circuit breakers with lower interrupting
time. The clearing time of the fault will be the relay operating time
plus the breaker interrupting time.
From Fig. 12-7:
Ps = Pm sin δ 0 = r2 Pm sin δ m = r2 Pm sin(π − δ m )
Thus:
sin δ 0 = r2 sin(π − δ m )
sin δ 0
δ m = π − sin −1
r2
F I G U R E 1 2 - 7 To illustrate critical clearing angle under fault conditions, and application of equal area criterion of stability.
(12-10)
Note that Ps, the synchronizing power, is assumed constant during the disturbance and after the disturbance.
Example 12-1 Figure 12-8a illustrates a system configuration
and b is the power-angle diagram for single-phase auto reclosing.
Many line-to-ground faults are of intermittent nature, and utilities
resort to autoclosing to clear such faults. Two or more autoclosing attempts may be made before the reclosures (shown as 52R
POWER SYSTEM STABILITY
FIGURE 12-8
(a) A tie line transient fault, and (b) equal area criterion of stability, Example 12-1.
at either end of the line) lock out for a permanent fault. Consider
that a transient single line-to-ground fault occurs on the transmission line interconnecting two stations as shown. The tie line
reclosures open and then close after a short time delay; this time
delay is called the dead time of the circuit breaker. Some synchronizing power flows through two unfaulted phases during a single
line-to-ground fault, and no power flows during the dead time.
The dead time of a circuit breaker on fast reclosing implies a time
interval sufficient for the arc fault path to become deionized. In
Fig. 12-8b, d2 − d1 is the dead time. Applying equal area criterion
of stability, if shaded area 1 is equal to shaded area 2, stability is
possible.
12-3
297
FACTORS AFFECTING STABILITY
The factors affecting stability are dependent on the type of stability
problem. The considerations for large rotor angle instability, voltage
instability, interarea oscillations, and turbine generator torsional
problems are quite different. The following is a general list:
1. Short-circuit ratio of the generator (see Chap. 13).
2. Inertia constant H, as defined in Chap. 11.
3. Transient reactance of the generator, though all other generator parameters, as discussed in Chap. 10, impact to some
extent. For example, single and double dampers.
4. Interconnecting system impedances between machines in a
multi-machine system; the postfault system reactance, as seen
from the generator.
5. The prior loading on the generator, which determines the
initial torque angle, prior to disturbance. The higher the loading, the closer will be the generator to its Pm.
6. The type of fault or perturbation; a three-phase fault at the
terminals of the machines will be a worst-case scenario for
the large rotor angle stability of the synchronous generator.
The transient stability on such faults is sacrificed due to
economic reasons. The fault types in decreasing order of
severity will be: two-phase-to-ground, phase-to-phase, and
phase-to-ground.
7. The nature of the loads served; the presence of rotating
motor loads may profoundly impact the results.
8. Speed of protective relaying.
9. Interrupting time of the circuit breakers; 1-cycle synchronous breakers have been developed.
10. Excitation system and voltage regulator types and
response; redundant voltage regulators with bumpless transfer
on failure, PV, or constant kvar controls.
11. Fast load shedding (frequency dependent with undervoltage settings).
12. Control system response of turbines, prime movers, governing systems, boilers, power system stabilizers, and voltage
regulators. Power system stabilizers play a major role in the
small signal stability.
298
CHAPTER TWELVE
13. The system interconnections, the parameters of
transmission lines, and characteristics and ratings of other
machines, relative to the stability of machine/machines under
consideration.
prevalent in the United States:
14. Auto reclosing; single-pole switching has been used to
enhance transient stability (Chap. 7). Only the faulted phase is
tripped and the unfaulted phases support transfer of synchronizing power. This works well as approximately 70 percent
of the faults in the transmission lines are of single phase-toground type. This may, however, impose negative-sequence
loading on the generators in operation; it can excite 120-Hz
torque oscillations and result in secondary arcing phenomena
and overvoltages1 (Chap. 7).
H does not vary over a large limit for various machines. Typical
data for steam and hydro units of various sizes are provided in Ref. 4.
We are more interested in writing the swing equation in terms of
angular position of the rotor in electrical degrees, d, with reference
to a synchronously rotating reference d0, at t =0. Angle d is easily
interpreted from the phasor diagrams of the machine:
15. Series and shunt compensation of transmission lines, SVCs,
and flexible ac transimission systems (FACTs) (Chap. 15).
16. Steam turbine fast valving (applicable to thermal power
plants) involves rapid opening and closing of the steam valves
in a predetermined manner to reduce generator accelerating
power, following a severe transmission line fault. The reheat
intercept valves in a turbine may control up to 70 percent of
unit power, and rapid opening and closing of these valves can
significantly reduce the turbine output.2,3
17. Fast tripping of a generator after it pulls out of step, as
keeping it on line, results in avoidable stresses to the generator itself and the system as it draws power from and supplies
power into the system, Example 12-5. While the unit is
tripped from the system, the turbine is not tripped; turbine
controls limit the overspeed, and the unit can be again brought
on line quickly.
18. System separation and islanding the faulty section can prevent a major cascade and prevent propagating the disturbance
to the rest of the system. Modern relays with adaptive controls
have been applied. Much power is generated in dispersed
generation and cogeneration facilities that run in synchronism
with the utilities, and fast isolation is of importance.
19. Application of NH-SSR (Narain Hingorani subsynchronous resonance suppressor) (Chap. 15).
12-4
SWING EQUATION OF A GENERATOR
The swing equation relates the motion of the rotor, which we can
write as:
J
d 2ω r
= Tm − Te
dt 2
(12-11)
where J is the total moment of inertia in kg-m2, ω r is angular
displacement of rotor, mechanical in rad, and Tm and Te are the
mechanical and electrical torques in N-m.
This can be converted into a per unit form by noting the relation
between H, the inertia constant, and J, the moment of inertia:
d ω ru
= Tmu − Teu
dt 2
2
2H
(12-12)
where:
H=
2
Jω om
and ω ru = ω r /ω 0
2VA base
(12-13)
The subscript u indicates per unit values. H is the inertia constant, as defined in Eq. (11-58). It is repeated here in terms of units
H=
2 . 31 × RPM2 × WR 2 (lb/ft 2 ) × 10−10
MW-s /MVA (12-14)
hine
MVA rating of mach
δ = ω rt − ω 0t + δ 0
.
δ = ωr − ω0 = Dωr
..
.
δ = ω 0 ω ru
(12-15)
Thus, we can write:
2H d 2δ
= Tmu − Teu
ω 0 dt 2
(12-16)
We add another term to this equation to account for damping,
proportional to the speed. Then the equation becomes:
2H d 2δ
= Tmu − Teu − K Dω ru
ω 0 dt 2
(12-17)
Equation (12-17) is called the swing equation. It can be represented in terms of two differential equations of the first order:
dω r
1
=
(T − Te − K D D ω r )
dt
2H m
dδ
= ω0Dωr
dt
(12-18)
The additional subscript u has been dropped and the equation
is understood to be in per unit.
Linearizing:
1
.
[D Tm − K1 D δ − K D D ω r ]
D ωr =
. 2H
Dδ = ω 0 D ω r
(12-19)
K1 (per unit DP/rad) = synchronizing coefficient.
The term K1Dd may be called synchronizing power, which acts to
accelerate and decelerate the inertia to bring it to the stable operating point, if one exists. For small deviations, K1 is the slope of the
transient power angle curve, at the particular steady-state operating
point, as shown in Fig. 12-9:
K1 =
VEq′
dP
cos δ 0
=
dδ δ
X d′ + X e
(12-20)
0
Referring to Fig. 12-10 of a synchronous generator connected
to an infinite bus through a reactance Xe, and ignoring saliency, Eq′
is internal voltage behind transient reactance, Eq is internal voltage behind synchronous reactance, V is infinite bus voltage, Vt is
generator terminal voltage, and d is the angle, as shown, between
Eq′ and V.
Equation (12-17) governs the dynamic response, having an
oscillation frequency of approximately:
ωn ≈
K1ω s
rad/ s
2H
(12-21)
POWER SYSTEM STABILITY
299
4. Damping or asynchronous power is neglected.
5. The mechanical rotor angle of the machine coincides with
the angle of voltage behind transient reactance.
These assumptions may not be always valid, but they are illustrative of the methodology of simple stability calculations.
The swing equation reduces to:
2H d 2δ
= Pm − Pe
ω s dt 2
(12-22)
The general network equations are:
Ig
0
FIGURE 12-9
Power angle curve showing derivation of synchroniz-
ing coefficient K1.
=
Y 11 Y1 j E
Y j1 Y jj V
(12-23)
where Ig is the vector of generator currents, E is the vector of internal generator voltages, and V the vector of bus voltages; Y11 is n × n
matrix, Y1 j is n × m matrix, Y j1 is m × n matrix, and Y jj is m × m
matrix.
We eliminate all load nodes and are interested only in the generator currents.
From Eq. (12-23):
0 = Y j1E + Y jjV
(12-24)
or
−1
jj
V = − Y Y j1E
Also:
Ig = Y11E + Y1 jV
= (Y11 − Y1 jY jj−1Y j1 )E
(12-25)
=YE
F I G U R E 1 2 - 1 0 (a) A generator connected to an infinite bus through
external impedance. (b) Phasor diagram of generator on an infinite bus.
12-5
CLASSICAL STABILITY MODEL
In the classical treatment of stability, the following assumptions are
made:
1. The generator model is type 1, with all its assumptions
represented by an internal generator voltage behind a transient
reactance (Sec. 12-9).
The Y matrix changes with the system conditions. In the prefault state, the load flow study is conducted to determine the E
and the angles d. At the instant of fault, the system configuration
changes and the matrix is modified and again modified a second
time after the fault is cleared. Thus, there are three distinct conditions in the solution.
Example 12-2 A system configuration, as illustrated in Fig. 12-11a,
is considered. Two generators are connected to duplicate feeders;
their transient reactances are as shown. Also, the feeder’s reactances
are shown. The resistances are neglected.
Figure 12-11b converts reactances to susceptances, and the full
admittance matrix is:
Y11 Y12
Y21 Y22
Y31 Y32
Y41 Y42
Y13
Y23
Y33
Y43
Y14 − j5
0
0
j5
Y24
0 − j6 . 7
0
j6 . 7
=
Y34
0
j5
− j10
j5
Y44
0
j6 . 7
j5 − j1 1 . 7
Here:
Y11 =
− j5
j0
j0 − j6 . 7
Y1 j =
j5
0
0
− j10
j5
= Y j1 Y jj =
j6 . 7
j5 − j11 . 7
2. The loads are represented as constant impedance loads.
3. The excitation systems, governing systems are not modeled.
The mechanical power remains constant.
Y1 jY jj−1Y j1 =
− j3 . 179 − j1 . 821
− j1 . 821 − j4 . 879
300
CHAPTER TWELVE
Postfault condition
Consider that the faulty line is isolated by tripping the circuit breakers at either end (Fig. 12-11c). Then, one line remains in service
and the full impedance matrix is:
− j5
0
j5
0
0 − j6 . 7
0
j6 . 7
Y=
j5
0
− j7 . 5 j2 . 5
0
j6 . 7
j2 . 5 − j9 . 2
Following the same procedure as before:
Y=
− j1 . 335 j1 . 335
j1 . 335 − j1 . 335
Thus:
Pe = 1 . 335 sin δ
12-5-1
FIGURE 12-11
Circuit for Example 12-2. (a) Prior to fault, (b) during
fault, (c) after fault clearance, one tie line opened.
Therefore, prefault Y is:
Y=
− j1 . 821
j1 . 82
j1 . 82 − j1 . 821
Pe = E1E2Y12 sin δ
If we assume that the voltages at both ends are maintained the
same (which is not practical for reactive power transfer), then:
Pe = 1 . 821 sin δ
During a three-phase bolted fault close to bus E1, on one of the
tie lines, the breakers at both ends open (Fig. 12-11b). The bus
voltage goes to zero during fault, and no power can be transferred.
This can be illustrated by forming Y matrix. As node 3 voltage goes
to zero, this amounts to eliminating third row and column from the
original matrix as follows:
− j5
0
0
0 − j6 . 7
j6 . 7
0
j6 . 7 − j11 . 7
Now the reduced matrix Y following the same procedure is:
Y=
− j5
0
0 − j6 . 7
−
−1
0
− j11 . 7 0
j6 . 7
The modern power systems are complex with lots of interconnections. The effects of modeling of excitation systems, governing
systems, generator saturation, and prime mover, that is, steam or
hydraulic governing systems are well documented.5,6
In a multi-machine system, the situation is complex. An incident
impact will be unevenly distributed amongst various synchronous
machines. Each machine will produce synchronizing power, and
the total synchronizing power brought about by the impact may
be considered a sum of the individual synchronizing powers. The
rigid machines will take a higher share of impact, while the softer
machines will share a smaller portion of the total impact. Under
this impact, every machine is retarded or accelerated:
α=
The power transferred between nodes 1 and 2 or 2 and 1 is:
j6 . 7 =
− j5
0
0 − j2 . 88
As the matrix Y12 =0, the power transmitted is zero.
Limitation of the Classical Method
ν2
Dδ
ω
(12-26)
where ν is the natural frequency of oscillation and α is the initial
retardation.
The synchronizing forces brought into play cause all machines
to strive for some mean retardation (Fig. 12-12). Each machine
undergoes further oscillations to accomplish this. After decay of
oscillations, the smaller machines are more retarded than they were
under the first impact and are loaded to a higher degree. The larger
machines are less retarded than initially, and are partially relieved
of their overload. The final torque angle may be smaller or larger
than the initial impact.
Figure 12-13 depicts this behavior. The initial angle d0 swings to
d1, given by the initial impact angle D δ , and the machine produces
its share of synchronizing power in the overall impact. All masses
strive for some mean retardation which changes the angle to d2.
This ultimate value is achieved only after some damped oscillations, in which torque angle swings to d3.
Figure 12-14 is a simplified picture of oscillations in a multimachine system. The behavior depends on the rating of the machine,
natural frequency, and the system stiffness. This figure shows that a
smaller machine, which took a rather small swing under the initial
impact because it produced a relatively small synchronizing power,
may become unstable and fall out of step.
This is of importance in current impetus for “green energy” and
smaller generating units (dispersed generation), when these operate
in synchronism with the utility. The survival of these smaller units
under system disturbances becomes a major consideration. Fast
isolation from the utility systems on system disturbances becomes
important. Generally, the following protective relay applications are
used for system isolation:
POWER SYSTEM STABILITY
FIGURE 12-12
FIGURE 12-13
301
Illustration of relative swings of machines in a multi-machine system and mean retardation.
Damped oscillations around new stable position d1
on an impact.
■
Frequency relays, device 80
■
Voltage relays, device 27/59
■
Reverse current directional relays, device 67,67N
■
Intertripping through fiber optic interfaces
■
Differential current relays, device 87
F I G U R E 1 2 - 1 4 Relative swings in a multi-machine system, and a
soft machine with relatively smaller rating and synchronizing power falling
out of step. The impedance between the oscillating machines is considered
minimal.
12-6 DATA REQUIRED TO RUN A TRANSIENT
STABILITY STUDY
A practical stability study starts with a converged load flow case.
This will establish the prefault voltages, the torque angles of generators, and the active and reactive power flows through various
branches and nodes throughout the power system.
302
CHAPTER TWELVE
In the second step, the disturbance to be studied is simulated.
This may be a fault in the system, opening of a tie line, loss of generation, or sudden load increase, or any other transient condition.
Any perturbation in the system will result in a dynamic response
through oscillations (Example 10-8).
Next, the postfault or disturbance condition can be simulated.
The data required for conducting a transient stability is rather
extensive, and it can be categorized as follows:
12-6-1
System Data
1. Impedance data of all significant components, generators,
transformers, transmission lines, cables, reactors, and so on.
All the sequence impedances will be required, depending
on the type of study, that is, a line-to-ground fault requires
positive-, negative-, and zero-sequence data.
2. kVA rating, nominal voltage ratios, winding connections,
tap settings on the transformers, regulating equipment, and
auto transformers.
3. Short-circuit capabilities, Mvar ratings of shunt and series
capacitors, SVCs, STATCOM data, and their control parameters
for modeling.
4. Various switching data, normal and alternate operations.
12-6-2
Rotating Machine Data
1. The generator models can be simple to complex. All
transient reactances, reactive capability curves, inertia constants, saturation information, Potier reactance, excitation
system controls, voltage regulator, governing system, and
prime mover data and control circuit block diagrams are
required. Data for PSS and their control circuits are required,
as applicable.
2. Large induction and synchronous motors are modeled
dynamically; their ratings, inertia constants, torque speed
characteristics, load data, method of starting, and so on.
We discussed the transient models of rotating machines in
the previous chapters.
12-6-3
Disturbance Data
1. The disturbance data to be studied, that is, fault type, protective relaying operating times, breaker interrupting times,
limits of acceptable voltage, frequency, and power swings.
12-6-4
dδ
.
= ω − ω0
x1 = x 2 =
dt
d 2δ w
.
x 2 = 2 = s (Ps − Pp )
2H
dt
(12-29)
The state vector:
| ω1 , δ1ω 2 , δ 2 …ω n , δ n |t
(12-30)
is a vector of 2n × 1 dimensions, where n is the number of generators. The generator power is a function of d. Thus:
.
x1 = f1 ( x1 , x 2 )
.
x 2 = f 2 ( x1 , x 2 )
12-8
(12-31)
NUMERICAL TECHNIQUES
The state Equations (12-31) can be solved using Euler’s method,
modified Euler method, Runge–Kutta (R-K) method, trapezoidal
rule, and so on. Consider a first-order differential equation:
dx
= f ( x, t )
dt
(12-32)
Referring to Fig. 12-15, we can approximate the curve representing the true solution by its tangent having a slope (see also
Chap. 2):
dx
dt
= f ( x 0 , t0 )
x =0
dx
Dx =
dt
(12-33)
Dt
x =0
Then, the value of x at t = t1 = t 0 + D t is given by:
x1 = x 0 + D x = x 0 +
dx
dt
Dt
(12-34)
x =0
The method is equivalent to using the first two terms of the Taylor
series. To give sufficient accuracy, the time step must be small.
Study Parameters
1. The required study parameters are duration of study, integrating interval, and required data output.
12-7
STATE EQUATIONS
The swing equation of p-th generator is:
d 2δ p
dt 2
ωs
(P − P )
2H s p
q= n
ω
= s Ps − ∑ Ep EqYpq cos(δ pq + δ p − δ q )
2H
q =1
=
(12-27)
These are n-coupled nonlinear differential equations of the second
order. In the state form, let:
x1 ≈ δ
x2 =
.
dδ
=δ
dt
(12-28)
FIGURE 12-15
Estimation of a function using Taylor’s series.
POWER SYSTEM STABILITY
12-8-1
12-8-2
Modified Euler’s Method
In the Euler’s method, inaccuracies may result, as the derivative at
the beginning of the interval is applied throughout the interval. The
modified Euler’s method uses derivatives at the beginning and end
of each period and averages these in the following steps.
An initial condition X 0 is assumed. The derivative X k = f ( X k )
is computed.
The first estimate of the state vector is:
.
X k ±1 = X k + X k D t
(12-35)
The second estimate of the state vector is:
.
X k +1 = f ( X k +1 )
Evaluate the second estimate of the state vector:
.
X k +1 = X k + X kavg D t
Runge-Kutta Method
The R-K method approximates the Taylor series, but does not
require explicit solution of higher-order derivates, other than the
first. The effect of higher-order derivatives is included by several
evaluations of the first-order derivative. There are R-K methods of
different orders. A fourth-order R-K method has an error of the
order of Dt.5
An R-K method calculates the following eight constants and can
be applied to multi-machine system:
K1k = f1 ( x1k , x 2k )D t
l1k = f2 ( x1k , x k2 )D t
(12-36)
The average of the state derivatives is:
.
.
1 .
X k avg = ( X k + X k +1 )
2
303
(12-37)
(12-38)
Repeat within the time t. The flowchart of the modified Euler’s
method is shown in Fig. 12-16.
1
1
K 2k = f1 x1k + K1k , x 2k + l1k D t
2
2
1
1
l2k = f2 x1k + K1k , x 2k + l1k D t
2
2
(12-39)
1
1
K k3 = f1 x1k + K 2k , x k2 + l2k D t
2
2
1
1
lk3 = f2 x1k + K 2k , x 2k + l2k D t
2
2
Simiilarly, K k4 , lk4 .
The change in state vector is calculated as:
(
1
.
D x1k = K1k + 2K 2k + 2K k3 + K k4
6
.k 1 k
D x 2 = l1 + 2l2k + 2lk3 + lk4
6
)
)
(
(12-40)
The new state vector is evaluated as:
.
x1k +1 =
.
x k2+1 =
.
.
x1k + D x1k
.
.
x k2 + D x k2
(12-41)
The time constant is advanced to k +1 and check if k >kmax. If
not, then the step 2 of calculating eight constants is repeated.
Example 12-3 A machine with Pm = 3.0 per unit, under fault
r1Pm = 1.5, is considered, with H =4.0 and a time step Dt =0.02 s.
The generator is operating at Pe = 1.0 per unit. The rotor angle and
angular frequency at the end of 0.02 s are determined as follows:
Euler’s Method
δ 0 = sin −1
1
= 19 . 47 ° = 0 . 34 rad
3
Initial angular velocity = ω 0 = δ = 0:
dδ p
dt
dω p
dt
= ω p − 2π f
=
πf
πf
(P − P ) =
(1 − 1 . 5 sin δ ) = 47 . 1(1 − 1 . 5 sin δ )
4
H s e
Determine derivatives at t =0:
FIGURE 12-16
solution.
Flowchart of Euler’s modified method, numerical
.
δ =0
.
ω = 47 . 1(1 − 1 . 5 sin 19 . 47 ° ) = 23 . 55
304
CHAPTER TWELVE
Then:
Therefore:
δ11 = δ10 +
dδ t
D t = 0 . 34 + 0 = 0 . 34 rad
dt
and
ω11 = 23 . 55Dt = 23 . 55 × 0 . 02 = 0 . 471
There is no change in d and the power generated remains the
same. Again evaluate derivate of d and angular velocity:
.
δ = 0 . 471 ω = 23 . 55
0 + 0 . 47
δ avg =
= 0 . 235
2
.
23 . 5 5 + 23 . 55
= 23 . 55
ω avg =
2
These results can be reasonably compared with modified Euler’s
method, as calculated earlier. Here we have used only a four-segment
method.
12-9 SYNCHRONOUS GENERATOR MODELS
FOR STABILITY
These can be directly derived from the treatment of synchronous
generators discussed in Chap. 10. The simplest generator model
represents a machine with a transient reactance behind a voltage
source. This is sometimes called the generator model 1.
12-9-1
E ′q Model
The reader may refer to the flux and voltage equations of the synchronous generator in Chap. 10. If we assume that:
New estimate of variables is:
δ11 = δ10 + δ avg Dt = 0 . 34 + 0 . 235 × 0 . 02 = 0 . 3447
ω = ω + ω avg Dt = 0 + 23 . 55 × 0 . 02 = 0 . 471
0
1
1
1
ω 1 = ω 0 + D ω = 0 . 4689
.
λd
and
.
λq
are << ω 0 λd
and ω 0 λq
(12-42)
And still neglect the damper circuits:
Runge-Kutta method
.
vd = − r id − θλd
.
vq = − riq + θλd
We can write:
K1k = f1 (δ k , ω k )D t
l1k = f2 (δ k , ω k )D t
1
1
K 2k = f1 δ k + K1k , ω k + l1k
2
2
We see that except for the third equation, we need not calculate
the rotor-based terms and can work with the stator quantities. We
can express λF in stator terms as follows:
Therefore:
λF = kM F id + L F iF
K10 = 0
l10 = 47 . 1(1 − 1 . 5 sin 0 . 34 ) rad
D t = 0 . 471
K 20 = (377 + 0 . 2355 − 377 )0 . 02 = 0 . 00471
l = 0 . 471
0
2
K 30 = 0 . 00471
[ − 1 . 5 sin(0 . 34 + 0 . 00236) rad]0 . 02 = 0 . 4679
l30 = 47 . 11
K 04 = 0 . 4679 × 0 . 02 = 0 . 00936
Eq′ =
)
(
Therefore:
δ 1 = 0 . 34 + 0 . 0034 = 0 . 3434
(
2 LF
e jδ λF
(12-45)
Eq′ =
ω 0kM F2
2 LF
e jδ id +
ω0MF
2
e jδ iF
(12-46)
This can be reduced by substitution, as follows (Chap. 10):
1 k
K + 2K 2k + 2K k3 + K k4
6 1
1
= (0 + 4 × 0 . 00471 + 0 . 00936) = 0 . 0034
6
)
1 k
l + 2l2k + 2lk3 + lk4
6 1
1
= (0 . 471 + 2 × 0 . 471 + 2 × 0 . 4679 + 0 . 4647 ) = 0 . 4689
6
DX 2k =
ω 0MF
Using Eq. (12-43), this can be written as:
l = 47 . 11
[ − 1 . 5 sin(0 . 34 + 0 . 00236 + 0 . 00236) rad]× 0 . 0 2
= 0 . 4647
(12-44)
Define a stator voltage E′, given by:
0
4
DX1k =
(12-43)
dλ
vF = rF iF + F
dt
id = 3I d , k = 3 / 2 , E = ω 0 M F e jδ iF / 2 ,
Ld′ = Ld − (kM F )2 /L F
(12-47)
We have the following expression for E′:
Eq′ = ω 0 ( Ld − Ld′ )I d e jδ + E
= j( X d′ − X d )I d e jδ + E
(12-48)
Or:
jδ
Eq′ = Va + rI a + jX d′ jI d e + jX qI qe
= Va + rI a + jX d′ I d + jX qI q
jδ
POWER SYSTEM STABILITY
Now from differential Equation (12-43), and multiplying vF
ωM
throughout 0 F , we get:
2 rF
ω0MF
2 rF
vF =
ω0MF
2rF
rF iF +
ω 0 M F dλ F
2 rF dt
(12-49)
Define:
ω0MF
2 rF
show that:5
e d′′ = −( X q − X q′′)iq − e d
where:
e d = ω Laq iQ
The model equations are:
vF = E fd
(12-50)
Ed′′ =
Then:
dEq′
L dE ′
E fd = E + F d = E + Tdo′
rF dt
dt
(12-51)
dt
=
1
(E − E)
Tdo′ fd
(12-52)
Efd may be considered as vF in equivalent stator terms. The number of differential equations increased by one compared to model 1.
The phasor diagram is shown in Fig. 12-17a. The equivalent circuit
is obtained by ignoring dampers in circuits of Fig. 10-12.
12-9-2 E ″ model
We neglected the damper circuits and q-axis rotor circuits. In E″
model, these are considered. Terms λd′ and λq′ are neglected, and
L′′d = L′′q , λd′′ = λd − L′′d id and in the quadrature axis, λ ′′ = λq − Lq′′iq .
These flux linkages produce EMFs e ′′d = ωλd′′, e ′′q = ωλq′′. It can be
FIGURE 12-17
λD =
−( X q − X q′′)I q
(1 + Tqo′′ s)
3[Eq′ + ( X d′ − X l )]I d
(1 + Tdo′′ s)
X ′′ − X
1 X ′′d − X l
l
E′q +
1 −
λD
E′′q = d
3 X ′d − X l
X ′d − X l
Rearranging:
dEq′
305
(12-53)
(12-54)
(12-55)
The differential equations cannot be shown in the phasor
models of Fig. 12-17b.
Figure 12-18 from IEEE Std. 11107 shows the various synchronous generator models of varying complexity. In this drawing, all
symbols are as defined in Chap. 10. Note that Lf1D and Lf12D, the reactance between the field and dampers, is approximately equal to Lad.
Example 12-4 Based on the previous discussions, this example
is a study to demonstrate stability of a simple system under fault
conditions and the effect of fast load shedding. It is demonstrated
that without fast load shedding, the generator is unstable; however,
with fast load shedding, the stability can be maintained.
The system configuration is shown in Fig. 12-19. A generator of
30 MW and a utility transformer of 30/50 MVA run in synchronism
(a) Phasor diagram of a generator E ′q model. (b) Phasor diagram of a generator E ″ model.
306
FIGURE 12-18
Synchronous generator models for stability studies, adapted from ANSI/IEEE Std. 1110.
POWER SYSTEM STABILITY
on a 13.8-kV bus, and supply a composite load of 50 MVA. Following data are applicable:
Case 2: As case 1, except that fast load shedding occurs at
0.1 s, dumping a load of 37.75 MW by opening breaker 1
(Fig. 12-19). 4.71 MW of load, representing the generator
auxiliary load and essential service load, connected through
breaker 2 remains in service.
1. 138 kV, bus 1 three-phase short-circuit level 11 kA rms
symmetrical, X/R =14, line-to-ground fault =8.5 kA rms symmetrical, X/R = 10.6.
2. Transformer: 30/50 MVA (OA/FA/FA–50 MVA is maximum
65ºC fan-cooled rating), 138-13.8 kV, primary windings deltaconnected, secondary wye-connected, resistance grounded, Z =
9 percent, X/R = 24. Transformer is provided with ±2.5 percent
and ±5 percent taps on the 138-kV winding. The transformer
taps are at −2.5 percent to provide secondary voltage boost to
maintain bus 2 voltage close to the rated voltage. The operating bus 2 voltage is 99.84 percent, close to the rated voltage of
13.8 kV. A prior load flow is conducted to establish operating
conditions prior to the fault.
3. Generator: 30 MW, 13.8 kV, 0.85 power factor and X d′′ =
12 percent, X d′ = 23 percent, X2 = X0 = 11.5 percent, X/R = 49,
Xd = 110 percent, Xq = 108 percent, Tdo′ = 5.5 s, X1 = 11 percent. Generator saturation is modeled (see Chap. 13), H =5.5
(including prime mover and coupling), and no exciter, governor, or prime mover controls are modeled.
4. Load: 50 MVA, composite, 80 percent constant kVA,
20 percent constant Z, no dynamic models of the load, which
includes essential load served from breaker 2.
5. Disturbance data: A three-phase fault occurs, as shown on
a bus tie breaker load side, at 0.05 s, which is cleared in 0.4 s.
(Practically the fault clearing time will be much less. Assume
that the first level of protection does not operate.)
Consider:
Case 1: Study for 3 s, no other switching action takes place,
except fault placement at 0.05 s and fault clearance at 0.45 s;
fault remains active for 0.4 s.
FIGURE 12-19
307
Figure 12-19 also shows the results of load flow prior to
opening breaker 1 at t = 0–. The generator supplies 30 MW
and 18 Mvar to the load; the transformer load is 12.5 MW and
9.0 Mvar. Approximately 0.7 Mvar losses occur through the
transformer.
The results of simulation are plotted in Figures 12-20 and
12-21.
■ Figure 12-20a shows transients in generator active and
reactive power, terminal current, rpm, and generator relative
power angle. By the time the fault is cleared, the generator power angle has already swung to 178° and the speed
goes on increasing with undulations. The active and reactive
power and current swing violently. Examination of power
angle (torque angle) swing of the machine gives a clear idea of
instability.
■
Figure 12-20b shows corresponding swings in generator bus voltage, bus 2, which again does not show any trend
of recovery. It oscillates as the generator supplies power and
draws power from the system.
■
Figure 12-21a depicts similar transients as Fig. 12-20a but
with major load shed at 0.1 s. Note that the power angle swing
has been arrested (152° in the first swing) and the transients
have a decaying trend, though slowly. These show that for the
same fault clearance time, stability is obtained with fast load
shedding.
■ Figure 12-21b depicts the transients in the generator bus
voltage, which is recovering to normal operating voltage through
oscillations.
A power system configuration for transient stability study, Example 12-4.
308
CHAPTER TWELVE
The following explanation of the criterion for stability are valid:
1. A disturbance can be related to a power unbalance. A threephase fault is, generally, the most severe condition; the fault
current is mostly reactive; the voltage at the fault point falls to
zero, while at other points in the system it will depend on the
FIGURE 12-20
relative impedances and the current flows to the fault point.
Due to severe voltage dips, the loads may drop out totally
or rotating loads may take a proportionally higher current,
for example, induction motors, which for a balanced voltage
reduction, demand proportionally higher currents (Chap.11).
These higher currents will aggravate the stability situation.
Transients for simulation of fault condition, without load shed, Example 12-4, when fault is cleared in 0.2 s. (a) Transients in generator G1.
(b) Recovery transient of the bus voltage. The transients show instability of the system. (Continued )
POWER SYSTEM STABILITY
FIGURE 12-20
2. The frequency will swing, and this will create further oscillations in load current. As an approximation, a load decrease
proportional to frequency may be considered.
3. Rotors of the synchronous machines swing, as accelerating
and deaccelerating torques are exerted, and a machine may
“slip a pole.”
4. Loss of synchronism can happen in stages. A primary disturbance may give rise to a secondary disturbance; for example, a
tie line in a transmission system carrying considerable amount
of power can be interrupted, giving rise to superimposed transients, while the first set of transients may not have decayed.
5. The angle difference (not the absolute angle) between the
swinging machines is the criterion of instability. Two machines
of similar characteristics, on the same bus, may swing together.
The larger the impedance between the swinging machines, the
greater could be the divergence of angle between them.
Without load shedding, the generator torque angle keeps oscillating after the fault has been cleared. The reactive and active power
output of the generator, bus voltage, and current shows violent
cyclic swings. Once a generator falls out of synchronism, it is subjected to cyclic torques, stresses, current, and power swings that
occur with respect to the electrical center, somewhere out in the
system. A generator can be severely stressed due to these violent
swings that impact the shaft, mechanical systems, and also the
foundations of the machine.
ANSI/IEEE device 78, out-of-step protection, will trip out
the generator on the first swing after it falls out of step. This can
309
(Continued )
prevent much damage and stresses to the electrical and mechanical systems and foundations. The out-of-step protective relays are
impedance-single blinder-type, and a plot of the impedance locus
is required for appropriate settings; the stable and unstable swings
must be distinguished.
Figure 12-22 is the impedance plot in R-X plane of a generator
as it continues to swing after it pulls out of step.
Example 12-5 A three-bus system, as shown in Fig. 12-23, is considered for transient stability. As a first step, the bus voltages, loads,
and load flow data at t =0– are superimposed in Fig. 12-23. Then,
it can be converted to impedances and admittances (Fig. 12-24).
The loads are replaced by constant impedances. In stability study,
it is essential to have dynamic models of the rotating loads, that is,
induction and synchronous motors, as these impact the results significantly. Here we consider all loads of constant impedance type,
for simplicity. The impedance data of the transmission lines are
shown in Table 12-1.
Prior load flow results are inputted; for example, generator 1
voltage can be calculated from:
*
P + jQ1
Vg1 = V1 + j(rg + X d ) 1
V1
Based on Fig. 12-24, the system equations can be written as:
Y11V1 + Y12V2 + Y13V3 + Y14Vg1 + Y15V∞ = 0
Y22V2 + Y21V1 + Y23V3 + Y26Vg 2 = 0
Y33V3 + Y31V1 + Y32V2 = 0
310
CHAPTER TWELVE
F I G U R E 1 2 - 2 1 Transients for simulation of fault condition, Example 12-4, when fault is cleared in 0.2 s, but 37.75 MW of load shed at 0.1 s.
(a) Transients in generator G1. (b) Transient of the bus recovery voltage. The transients show stability of the system, with fast load shedding. (Continued )
POWER SYSTEM STABILITY
FIGURE 12-21
FIGURE 12-22
(Continued )
Impedance locus of a generator in R-X plane, as it goes on swinging after pulling out of step.
311
312
CHAPTER TWELVE
FIGURE 12-23
A power system configuration for transient stability study, Example 12-5.
And Y-matrix can be written as:
0 . 033 + j1 . 47
0
The source impedance is combined with the 40-MVA transformer impedance. The results of the load flow pertain to t =0-.
The loads, voltages, generation, and angles will be calculated in the
specified interval at each incremental K.
The generator swing equations can be written in the state form
and solved with the modified Euler’s method for transient stability
calculations. A flowchart is given in Fig. 12-25.
Case 1: A three-phase fault is simulated at bus 2 at t =0.1 s and
cleared at 0.3 s, that is, the fault is sustained for 0.2 s.
The transients are shown in Fig. 12-26. It is obvious that generator 2 is more susceptible to fall out of step as compared to
0
0
0 . 033 − j1 . 47
generator 1. Because it is closer to the fault location, it undergoes
much larger swings, though it has a larger rating compared to generator 1. Though under normal operating conditions, little power
is drawn from the utility source through 40-MVA transformer, but
under a disturbance, the utility source tends to support the system
from falling out of step. It is, however, interesting to note that
though swings of generator 1 are much lower than that of generator 2, these show diverging trend, giving rise to dynamic stability
problems.
Case 2: The fault is now cleared at 0.4 s, that is, it is sustained
for 0.3 s. Generator 2 falls out of step; transients depicted in
POWER SYSTEM STABILITY
FIGURE 12-24
The system in Fig. 12-23 converted to admittances.
TA B L E 1 2 - 1
ITEM DESIGNATION
313
System Data for Example 12-5
RAW IMPEDANCE DATA
Power grid
3500 MVA, three-phase symmetrical short circuit, X/R=15
G1
23.53 MVA, 13.8 kV, 0.85 power factor, 2-pole X ′d=23%, Xd=200%, Xq=190%, Xl=11.0%, X /R=48,
total H including coupling and prime mover =5.5 (WR 2 =43226 lb-ft2), K1 =5%, saturation modeled,
S100 =1.070, S120 =1.12, Sbreak =0.80, resistance grounded. Excitation and speed governing not modeled
G2
35.3 MVA, 13.8 kV, 0.85 power factor, 2-pole, X ′d=23%, Xd=200%, Xq=190%, Xl=11.0%, X /R =48, total
H including coupling and prime mover =5.5 (WR 2 43226 lb-ft2), K1=5%, saturation modeled, S100=1.070,
S120=1.12, Sbreak =0.80, resistance grounded. Excitation and speed governing not modeled
Transformer T1
40.0 MVA, 138–13.8 kV, Z=9%, X /R=27.30
Line L1
1033.50 KCMIL, ACSR, 54 strands, 5' flat spacing, GMD =6.3 ft, GMR=0.042 ft, outside diameter =1.246",
one ground wire, placed 6 ft above phase conductors, height of conductors 30 ft, soil resistivity =100 Ω/m,
untransposed conductors, calculated impedance per mile: positive and negative sequence=0.099 + j 0.608 Ω,
Y =7.11281 mS, zero-sequence per mile: 0.06007 + j 2.68652 Ω, line length =10560 ft
Lines L2 and L3
Same data as line L1, except length =7920 ft each
Fault
Three-phase bolted fault occurs at bus at 0.1 s
Fault clearance
Study conducted for two cases, fault cleared at 0.3 s, i.e., lasting for 0.2 s and cleared at 0.4 s, i.e., fault lasting
for 0.3 s
314
CHAPTER TWELVE
FIGURE 12-25
A flowchart of stability calculations, using Euler’s modified method.
Fig. 12-27. The situation is similar to that depicted in Fig. 12-21a,
Example 12-3. Its torque angle has increased to approximately 180°
at the fault clearance time and then keeps on oscillating violently.
There are violent swings in the speed, currents, and power. Generator 1 remains stable and rides through the disturbance, though
its torque angle is settling very slowly—thus, it keeps swinging for
a long time after the perturbation is removed. The voltage of bus
1 slowly recovers, while bus 2 has large swings, in synchronism
with the generator power angle swings as it draws power from and
supplies power into the electrical system. Practically, the protective
relays will take the generator off-line on the first swing, device 78,
as discussed earlier.
Chapter 13 continues with this example and shows that in
the same configuration and same fault condition lasting for
0.3 s, stability can be achieved by addition of a fast-response
exciter.
POWER SYSTEM STABILITY
F I G U R E 1 2 - 2 6 Transients in generators G1 and G2 for simulation of fault condition, Example 12-5; three-phase fault on bus 2 is cleared in 0.2 s.
The transients show stability of both the generators G1 and G2.
315
316
CHAPTER TWELVE
F I G U R E 1 2 - 2 7 Transients in generators G1 and G2 for simulation of fault condition, Example 12-5; three-phase fault on bus 2 is cleared in 0.3 s.
The transients show instability of generator G2, while generator G1 is stable. Bus voltage transients are also depicted.
POWER SYSTEM STABILITY
12-10
SMALL-SIGNAL STABILITY
The following types of subsynchronous frequency oscillations are
recognized:
■
Local plant mode oscillations
■
Interarea mode oscillations
■
Torsional mode oscillations
■
Control mode oscillations
12-10-1
Local Mode Oscillations
Local mode oscillations occur when units at a generating station
oscillate with respect to the rest of the power system. The typical
frequency of oscillation is 1 to 2 Hz, depending mainly on the
impedance of the transmission system. Stronger transmission systems tend to have a higher local mode frequency. The oscillations
are termed local because behavior is mainly localized at one point,
with the rest of the system experiencing much less effects. Spontaneous local mode oscillations tend to occur when a very weak
transmission link exists between a machine and its load center.
An example can be an isolated power station (wind power
generation), sending power along a long transmission line. The
systems can be usually modeled accurately for the study. Consider
the following parameters:
H = 4 kW-s/kVA
δ 0 = 45 °
X d′ = 0 . 25, X e = 0 . 45 pu
Eq′ = 1 . 05 pu, and V = 1 . 0 pu
Then from Eq. (12-20), K1 = 1.0605 and from Eq. (12-21),
ω n = rad/s = 1.125 Hz.
If oscillations of this frequency are experienced at the generating
plant, these will most likely be local mode oscillations. An external
reactance of approximately 0.50 per unit or less, including impedance of the step-up transformer, means that the undamped local
mode oscillations will not be a problem.
12-10-2
Interarea Oscillations
As the name suggests, interarea oscillations are associated with
machine in one part of the system oscillating against machines in
the other part of the system. These are more complex and mean that
a combination of the machine in one part of the system is swinging
against machines in another part of the system. The simplest form
of representation is interlinking two separate power systems or a
group of generators through transmission tie lines.
The frequency of oscillations is in the range of 0.1 to 1 Hz. This
is lower than local mode oscillations because of the high inertia of
a large group of machines.
The modeling for interarea oscillations can be complex. A
power system containing n generators has (n − 1) normal modes of
oscillations, with their own natural frequency and profiles of oscillations. Separating these and finding which one is easily excitable
and has potential of undamped oscillations can be a difficult task.
Frequency domain techniques using state–space analysis have been
used. Most oscillation modes in generators are positively damped,
and thus attention is focused on those modes that contain enough
negative damping to give rise to persistent rotor oscillation or the
oscillations increasing with time.
Even when the system is unstable on large signal perturbations,
the natural damping of the system, represented by positive KD term
in Eq. (12-17), prevents any sustained oscillations.
317
It is recognized that normal feedback control action of voltage
regulators and speed governors has the potential of contributing to
negative damping, which can cause undamped modes of dynamic
oscillations.
12-10-3
Torsional Oscillations
Torsional oscillations are due to interactions of the generating
units’ excitation systems with prime mover controls, that is, speedgoverning systems (see Chap. 16).
12-10-4
Control Mode Oscillations
Control mode oscillations are due to poorly tuned controls of excitation systems, SVCs, and prime movers. These are the usual causes
of instability of control modes.
12-11
EIGENVALUES AND STABILITY
An introduction to matrix theory is first provided to proceed with
this section. Consider a square matrix A . Then the matrix A − λ I
is called the characteristic matrix. L is a scalar and I is a unit matrix.
The determinant | A − λ I | , when expanded, gives a polynomial
which is called the characteristic polynomial of A, and the expression | A − λ I | = 0 is called the characteristic equation of matrix A.
The roots of the characteristic equation are called the characteristic
roots or eigenvalues.
■
Any square matrix and its transpose have the same
eigenvalues.
■
The sum of the eigenvalues of a matrix is equal to the trace
of the matrix. The sum of the elements on the principal diagonal is called the trace of the matrix.
■
The product of the eigenvalues of a matrix is equal to the
determinant of the matrix. If λ1 , λ2 ,..., λn are the eigenvalues of
A, then the eigenvalues of:
kA are kλ1 , kλ2 ,..., kλn
A m are λ1m , λ2m ,..., λnm
A
−1
(12-56)
are 1/λ1 , 1/λ2 ,...,1/λn
■
Zero is a characteristic root of the matrix only if matrix is
singular.
■
The characteristic roots of the triangular matrix are
diagonal elements of the matrix.
■
The characteristic roots of a real symmetric matrix are all real.
12-11-1
Characteristic Vectors
Each characteristic root l has a corresponding nonzero vector
x, which satisfies the equation:
A − λI x = 0
(12-57)
The nonzero vector is called the characteristic vector or eigenvector.
The eigenvectors are therefore not unique.
Now consider the linearization of dynamic system state equations (see Chap. 2). We can write:
.
x~ = Ax~ + Br~
or
(12-58)
.
D x = AD x + BD r
318
CHAPTER TWELVE
Taking Laplace transform into consideration:
s D x ( s ) − D x (0 ) = A D x ( s ) + B D r ( s )
or
(12-59)
D x(s) = (s I − A )−1[D x(0) + BD r(s)]
Then the characteristic equation is:
(12-60)
det(s I − A ) = 0
■
A real eigenvalue corresponds to a nonoscillatory mode.
■
A negative eigenvalue corresponds to a decaying mode.
■
A positive eigenvalue represents aperiodic instability.
■
Complex eigenvalues occur in conjugate pairs, and
each pair corresponds to an oscillatory mode. Also see
Chap. 3.
ς=
(12-61)
This is of the form:
.
x = Ax + Br
(12-62)
The block diagram representation is illustrated in Fig. 12-28,
from which:
Dδ =
ω0
s
(12-63)
KD
K1 2Hω 0
(12-66)
Example 12-6 A 18-kV, 100-MVA generator connected through a
step-up transformer of 100 MVA to two parallel 230-kV lines is considered, (Fig. 12-29a). The system data are in Table 12-2, and the
results of load flow with calculated bus voltages are superimposed in
this figure. The 230-kV lines have a charging requirement of 78.26
Mvar at no load; also see Chap. 4. The small-signal stability characteristics of the system are analyzed when line 2 is lost by opening
breakers at either end at 0.1 s; there is no fault in the system. Then,
only one line remains in service. The bus voltages at load flow after
L2 is taken out of service are shown in Fig. 12-29 b. Therefore:
Et = 1 . 0
Eg is the voltage behind generator transient reactance and Et is
the bus voltage. For simplicity of hand calculation, we will ignore
resistance component; then Xe =0.39 per unit.
ω
K
KD
sD δ + 1 ω 0 D δ = 0 D Tm
2H
2H
2H
The characteristic equation is:
s2 D δ +
s2 +
1 KD
1
=
2 2Hω n 2
δ = 29 . 76 °
Eg = 1 . 11
1
Dδ
− K1 D δ − K D s
+ D Tm
ω0
2Hs
Or
A control block circuit diagram of the swing equa-
The undamped natural frequency is given by ω n, and the damping ratio is:
We can write the two swing equations in the matrix form:
.
K
K
1
D ωr − D − 1 Dωr
. = 2H 2H
+ 2H D Tm
Dδ
Dδ
ω0
0
0
FIGURE 12-28
tion of a generator.
Kω
KD
s+ 1 0 = 0
2H
2H
(12-64)
Referring to Chap. 3 and comparing with Eq. (3-1), it is reproduced as follows:
s2 + 2ςω n s + ω n2 = 0
(12-65)
TA B L E 1 2 - 2
DESIGNATION
K1 =
1 . 11 × 1
cos 29 . 76 ° = 2 . 447 pu torque/rad
0 . 39
From Eq. (12-61):
.
D ω r − 0 . 5 − 0 . 2447 D ω r 0 . 1
. =
D Tm
+
Dδ
Dδ
377
0
0
System Data for Example 12-6
DATA
Power grid
An infinite bus
G1
18 kV, 60 Hz, 2-pole, 100 MVA, X ′d = 25%, Xd= Xq = 200%, X /R = 60, H = 5.0, KD = 5 (machine MVA base)
Transformer T1
100.0 MVA, 18–230 kV, delta, wye, solidly grounded, Z = 10% (100-MVA base), X /R = 34
Line L1, 200 mi
1351 ACSR, 2 ground wires, soil resistivity = 100 Ω/m. Z + = 0.07003 Ω (25°C) + j 0.75996 Ω/mi
and Y = 5.64688 mS/mi. Only positive is sequence impedance considered in calculations
Lines L2, 100 mi
Data same as for L1
POWER SYSTEM STABILITY
319
F I G U R E 1 2 - 2 9 (a) Power system configuration of a generator connected to an infinite bus through duplicate tie lines. (b) One tie line opened
suddenly, without a fault, Example 12-6.
The eigenvalues of the state matrix are:
For:
− 0. 5 − λ
377
λ = − 0 . 250 − j9 . 596
− 0 . 2447
=0
−λ
λ 2 + 0 . 5λ + 92 . 25 = 0
Therefore:
ω n = 92 . 25 = 9 . 60 rad/s = 1 . 513 Hz
ς=
0.5
= 0 . 026 0 4
2 × 9 . 60
377 . 0φ11 + (0 . 250 + j9 . 596)φ21 = 0
We know that eigenvectors corresponding to eigenvalues are
not unique; assume:
φ21 = 1 . 0
φ11 = − 0 . 000663 + j0 . 0254
Similarly, for:
The damped frequency is:
λ = − 0 . 250 − j9 . 596
ω d = ω n 1 − 0 . 02604 2 = 1 . 509 Hz
φ22 = 1
λ1 , λ2 = − 0 . 250 ± j9 . 596
φ12 = − 0 . 000663 − j0 . 0254
The right eigenvector model matrix is:
Write the state equation:
( A − λ I )φ = 0
− 0 . 000663 + j0 . 0254 − 0 . 000663 − j0 . 0254
1
1
The left model matrix is:
Thus:
− 0 . 5 − λ1
377
φ=
− 0 . 2447 φ11
=0
φ21
− λ1
φ −1 =
− j19 . 841 0 . 5 − j0 . 013
j19 . 841 0 . 5 + j0 . 013
320
CHAPTER TWELVE
FIGURE 12-30
Simulation of transients, Example 12-6; opening of a parallel tie line.
The time response is given by:
D ω r (t ) = (− 0 . 000663 + j0 . 0254 )(0 . 02 − j0 . 000052)e ( −0.250 + j9.596 )t
c e λ1t
D ω r (t )
=φ 1 λt
Dδt
c2 e 2
+ (− 0 . 000663 − j0 . 0254 )(0 . 02 + j0 . 000052)e ( −0.250 − j9.596 )t
= − 0 . 0001e −0.250t sin 9 . 596t
where:
c1
D ω r (0 )
= φ −1
c2
D δ (0 )
Consider that D ω r = 0, D δ = 0 . 04 rad, at t = 0. Then:
c1 − j19 . 841 0 . 5 − j0 . 013 0
=
c2
j19 . 841 0 . 5 + j0 . 013 0 .0
04
=
0 . 02 − j0 . 00052
0 . 02 + j0 . 00052
Then:
Similar expression can be written for d. This is a second-order
system with oscillatory response, having a damped frequency of
9.596 rad/s =1.527 Hz. The oscillations decay with a time constant
of 1/0.25 s.
Figure 12-30 shows simulated transients. The decay of the transients is much faster compared to the calculations because of simplifying assumptions; that is, we are neglecting resistance, capacitance,
and saturation in the calculations.
The small-signal stability simulations, when applied to large
multi-machine systems, become fairly involved due to the requirements of simultaneous solution of differential and algebraic equations representing:
1. Synchronous machines
D ω r (t ) = φ11c1e
D δ (t ) = φ21c1e
Substituting the values:
λ1t
λ1t
+ φ12c2e
+ φ2 2 c 2 e
λ2 t
λ2 t
2. Excitation system and stabilizers
3. Interconnecting transmission networks
POWER SYSTEM STABILITY
321
4. Other devices such as SVCs, HVDC converters, and so on
5. Prime mover speed governors
6. Static and dynamic loads such as induction and synchronous motors
These equations must be solved simultaneously. The state variables required for simulation may run into thousands; this is well
outside the range of conventional eigenvalue analysis. Techniques
like selected subset of eigenvalues associated with the complete system response, such as AESOPS (Analysis of Essentially Spontaneous Oscillations in Power Systems),8 have been developed. PEALS
(Program for Eigenvalue Analysis of Large Systems) uses AESOPS
and modified Arnoldi method.9,10
AESOPS computes the eigenvalues associated with rotor angle
modes, one complex conjugate pair at a time. This is done by
applying to the generator an external sinusoidal torque, expressed
in terms of initial estimate of the eigenvalue. Then, the complex
frequency response is calculated and a revised estimate of eigenvalue arrived at by steady-state response. The process is repeated
until following estimates converge with a specified tolerance. The
resulting analysis indicates eigenvalues of the mode of oscillations
in which the selected generator participates significantly.
12-12
VOLTAGE STABILITY
A power system must be able to maintain its voltage profile under
various operating conditions. ANSI Std. C84.1-1989 specifies the
preferred nominal voltages and associated nonstandard nominal
system voltages in the United States. The electrical equipment operate within a certain narrow range of voltage variations, and utilities
strive to maintain the voltages at the consumer premises within
the specified limits and according to statuary regulations. Thus, the
voltage and power flow should be controlled simultaneously. The
voltage stability here excludes large voltage dips that may occur on
faults and considers the instability due to slow variations in network and load characteristics. The operation of load tap changing
equipment on transformers, voltage regulators, automatic generation control, load shedding, and switchable reactive power devices
(capacitors) are rather slow acting. This implies that the dynamics
of load variation are slower than the dynamics occurring in the state
vector of stability model.
Other important factors are the contingencies, event disturbances, and dynamic load response to the voltage variations. We
can, therefore, analyze the problem in two possible manners:
1. Dynamic framework, using dynamic models of the loads
and voltage-correcting devices
2. Steady-state framework, that is, load flow
The voltage instability/voltage collapse can be generally analyzed using a time-domain stability program, though it requires
extensive computational effort. We may say that with respect to
original stable operating point, the system is voltage stable relative
to slow or dynamic problem if the postdisturbance system trajectory approaches stable steady states where voltage magnitudes are
acceptable, as well as the transient voltage magnitudes are acceptable. The task of accessing voltage stability is, therefore, to find that
s.e.p that addresses both—the static and dynamic aspects.
12-12-1
P-Q Characteristics, Critical Reactance
Let us consider a simple load flow situation first. We talk about P-V
and Q-V relations. The basic concept can be gathered by considering load flow over a transmission line, ignoring the capacitance
effects (Fig. 12-31a).
F I G U R E 1 2 - 3 1 (a) Power flow over a tie line. (b) Voltage instability,
power factor, and critical reactance.
The load demand is shown as P +jQ, the series admittance Ysr =
gsr +bsr, and Z = Rsr +jXsr. The power flow from the source bus is
given by:
P + jQ = Vr e − jθ [(Vs − Vr e jθ )( g sr + jbsr )]
= [(VsVr cos θ − Vr2 )g sr + VsVr b sr sin θ]
(12-67)
+ j[(VsVr cos θ − V )bsr − VsVr g sr sin θ]
2
r
If we neglect resistance
.
P = VsVr bsr sin θ
.
Q = (VsVr cos θ − Vr2 )bsr
(12-68)
We could replace θ with d, the difference between the sending-end and receiving-end voltage angle. If the receiving-end load
changes by a factor DP + DQ
D P = (Vsbsr sin θ )D V + (VsVr bsr cos θ )D θ
D Q = (Vs cos θ − 2Vr )bsr D V − (VsVr bsr sin θ )D θ
(12-69)
where Vr is the scalar change in voltage Vr and D θ change in angular
displacement. If θ is eliminated from Eq. (12-69) and resistance is
neglected, a dynamic voltage equation of the system is obtained as
follows:
Vr4 + Vr2 (2QX sr − Vs2 ) + X sr2 (P 2 + Q 2 ) = 0
(12-70)
The positive real roots of this equation are:
1/ 2
− 2QX sr + Vs2 1
(2QX sr − Vs2 )2 − 4 X sr2 (P 2 + Q 2 )
Vr =
±
2
2
(12-71)
This equation shows that in a lossless line, the receiving-end
voltage Vr is a function of sending-end voltage Vs, series reactance
322
CHAPTER TWELVE
Xsr, and receiving-end real and reactive power. Voltage problems are
compounded when reactive power flows over heavily loaded active
power circuits. If reactive power is considered 0 and the sendingend voltage is 1 per unit, then Eq. (12-71) reduces to:
2
(12-72)
For two equal values of Vr:
(1 − 4 X P )
2
sr
Vs
X sr
(12-77)
This assumes that the resistance is << reactance. At no load,
Vr = Vs; therefore:
V
V
∂Q
=− r =− s
X sr
X sr
∂V
=0
2 1/ 2
I rsc =
1/ 2
1
1 − 4X P
Vr = ±
2
2
2
sr
If the three phases of the line connector are short-circuited at
the receiving end, the receiving-end short-circuit current is:
(12-78)
Thus:
That is:
Xsr = 1/2P
(12-73)
This value of Xsr may be called a critical reactance. Figure 12-31b
shows characteristics of receiving-end voltage against system reactance for constant power flow at lagging and leading power factors,
with sending-end voltage maintained constant. This figure shows, for
example, that at a power factor of unity, voltage instability occurs for
any reactance value exceeding 0.23 per unit. This reactance is the critical reactance. For a system reactance less than the critical reactance,
there are two values of voltages, one higher and the other lower. The
lower voltage represents unstable operation, requiring large amount
of source current. For a system reactance close to the critical reactance, voltage instability can occur for a small positive excursion in
the power demand. As the power factor improves, a higher system
reactance is permissible for the power transfer. The voltage instability
can be defined as the limiting stage beyond which the reactive power
injection does not elevate the system voltage to normal. The system
voltage can only be adjusted by reactive power injection until the
system voltage stability is maintained. From Eq. (12-71), the critical
system reactance at voltage stability limit is obtained as follows:
(2QX sr − Vs2 ) = 4 X sr2 (P 2 + Q 2 )
4 X sr2 P + 4 X srQVs2 − Vs4 = 0
(12-74)
The solution of this quadratic equation gives:
X sr,critical =
Vs2
2
Q ± P2 + Q2
P2
(12-75)
V2
= s (− taan φ + sec φ )
2P
where φ is the power factor angle.
Enhancing the thermal capacity of radial lines by use of shunt
capacitors, SVC, and synchronous condensers is increasingly common. However, there is a limit to which capacitors can extend the
load-carrying capability.
In practice, the phenomena of collapse of voltage is more complex. Constant loads are assumed in the previous scenario; however,
the load dynamics are a very important factor. At lower voltages,
the loads may be reduced, though this is not always true, that is, an
induction motor may not stall until the voltage has dropped more
than 25 percent, and even then, the magnetic contactors in the
motor starter supplying power to the motor may not drop out. This
lockout of the motors and loss of some loads may result in voltage
recovery, which may start the process of load interruption afresh, as
the motors try to reaccelerate on the return voltage.
From Eq. (12-69), as θ is normally small:
D Q Vs − 2Vr
=
DV
X sr
(12-76)
∂Q
= current
∂V
(12-79)
Alternatively, we could say that:
D Vs D Vr D Q
≈
=
V
V
Ssc
(12-80)
where Ssc is the short-circuit level of the system. This means that
the voltage regulation is equal to the ratio of the reactive power
change to the short-circuit level. This gives the obvious result that
receiving-end voltage falls with the decrease in system short-circuit
capacity or increase in system reactance. A stiffer system tends to
uphold the receiving-end voltage.
The voltage-reactive power stability problem is more involved
than portrayed earlier. The power flow has to be considered from
the generation level to the transmission, subtransmission level, and
finally to the consumer level. As reactive power does not travel well
over long distances, it becomes a local problem. The utility companies operate with an agreed voltage level at intertie connections,
and provide for their own reactive power compensation to meet
this requirement. It can be said that there are no true hierarchical
structures in terms of reactive power flow.
The voltage instability is not a single phenomenon and is closely
coupled to the electromagnetic stability and shares all aspects of
active power stability, though there are differences.
Consider the equations of active and reactive power flow, and
Eq. (12-67) for the short line. Let the voltages be fixed. The angle
(phasor difference between the sending-end and receiving-end voltage
vectors) varies with receiving bus power, as shown in (Fig. 12-32a).
Beyond the maximum power drawn, there is no equilibrium point.
Below the maximum power drawn, there are two equilibriums, one in
the stable state and the other in the unstable state. A load flow below
the maximum point is considered statically stable.
A similar curve can be drawn for reactive power flow (Fig. 12-32b).
The angles are fixed, and the bus voltage magnitude changes. The
character of this curve is the same as that of active power flow curve.
A reactive power demand above the maximum reactive power results
in a nonexistence of a load flow situation. The point DV U is statically
unstable, corresponding to D δ U . If we define:
P(max) − P < ε
Q(max) − Q < ε
(12-81)
Then, howsoever small ε may be, there will always be two equilibrium points. Such an equilibrium point may be called a bifurcation point.
The derivatives ∂p/∂d, ∂Q/∂V are zero at the static stability limit.
The goal of the local bifurcation theory is to investigate static
solutions, and stability property of static solutions may alter the
dynamic behavior.
POWER SYSTEM STABILITY
323
We can write:
J R = ε r Λεl
(12-86)
where ε r , ε l , and Λ are the right eigenvector matrix, the left eigenvector matrix, and diagonal eigenvector matrix, respectively. Note
that ε r−1 = ε l .
From these equations:
DV = ∑
i
ε ri ε li
DQ
λi
(12-87)
where each eigenvalue li and the corresponding right and left
eigenvectors, ε ri , ε li , define i-th mode of Q-V response. Also:
v = Λ −1q
(12-88)
where:
v = ε l D V is the vector of modal voltage variations (12-89)
q = ε r D Q is the vector of modal reactive power variations
(12-90)
FIGURE 12-32
(a) and (b) Real power flow and reactive power flow
instability, respectively.
∂ Vk
ε ε
= ∑ rki lki
∂ Qk
λi
i
Power systems are normally operated near s.e.p. When the system parameters are away from the bifurcation values, but change
slowly and continuously, it is likely that s.e.p changes position but
remains a s.e.p or the old s.e.p lies in the stability boundary of new
s.e.p. The ways in which the system may lose stability are: (1) It
may happen that one s.e.p may coalesce into another s.e.p and disappear in a saddle-node bifurcation. (2) A s.e.p and unstable limit
cycle coalesce and disappear, and an unstable equilibrium point
(u.e.p) emerges. (3) The s.e.p bifurcates into an u.e.p surrounded
by a stable limit cycle.
12-12-2
For dynamic analysis, the general structure of the equations is:
differential equations
I ( x, V ) = YN V alggebraic equations
f (x, ρ) = g
x=
(12-84)
And
D V = J R−1 D Q
(12-85)
The voltage stability characteristics can be ascertained by computing eigenvalues and eigenvectors of the reduced Jacobian matrix.
V P
− =0
θ Q
(12-92)
where x is the system state vector and ρ is the parameter vector,
given by:
(12-83)
– – – –
where J ( J Pq, J PV, J Qq, J QV) are Jacobian matrices.
For DP = 0, the reduced Jacobian matrix JR is:
J R = J QV − J Q−θ1 J PV
Shortest Distance to Instability
This involves finding smallest load in MW and Mvar, which
imposed on the initial conditions, cause the power flow Jacobian to
be singular. The power flow equations can be organized as:
(12-82)
where YN is node admittance matrix, and V , I are voltage vectors.
From Newton–Raphson decoupled load flow:11
J P J PV D θ
DP
= θ
D Q J Qθ J QV D V
(12-91)
Equation (12-91) shows that the V-Q sensitivities cannot identify individual voltage collapse modes J R , YN as symmetrical if resistances are neglected; then, eigenvalues and eigenvectors
– of J R are
real, and right and left eigenvectors of an eigenvalue of JR are equal.
The magnitude of eigenvalues can provide an estimate of proximity
to instability. The application of modal analysis determines how
stable the system is and how much extra load can be added. At the
stability critical point, areas and elements that participate in each
mode can be identified.
12-12-3
Proximity to Instability
.
x = f ( x, V )
The V-Q sensitivity at bus k is:
V
,
θ
ρ=
P
Q
(12-93)
Let J x , J ρ be the Jacobian matrices of function f. For a given
parameter ρi, a system state vector xi can be obtained by solving
Eq. (12-92). The system reaches its voltage stability critical limit
if parameter vector ρ* and the corresponding state vector x* are
such that Jacobian J x is singular. This is done for a given operating
point (x0, ρ0) by finding the parameter vector ρ* on surface S so
that distance between ρ0 and ρ*, k = (ρ* − ρ0), is a minimum. The
Jacobian becomes singular when:
ρ* = ρ0 + kε l
(12-94)
324
CHAPTER TWELVE
Thus, starting from an initial estimate of ε, stress the system by
increasing ρ in direction of εl, and iterate until εl converges to critical ε*. Then ρ* = ρ0 + k*ε* is the equilibrium condition.
12-13
LOAD MODELS
Load modeling has a profound impact on stability. Figure 12-33
shows the effect of change of operating voltage with respect to constant current and constant MVA for three load types: (1) constant
KVA, (2) constant current, and (3) constant impedance. Heavy
industrial motor loads are approximately constant MVA loads, while
commercial and residential loads are mainly constant impedance
loads. Classification into commercial, residential, and industrial is
rarely adequate, and one approach has been to divide the loads
into individual load components. The other approach is based on
measurements. Thus, the two approaches are:
■
Component-based models
■
Models based on measurements
FIGURE 12-33
A component-based model is a bottom-up approach in the sense
that different load components comprising the loads are identified.
Each load component is tested to determine the relations between
real and reactive power requirements versus voltage and frequency.
A load model in exponential or polynomial form can then be developed from the test data.
The measurement approach is a top-down approach in the sense
that the model is based on the actual measurement. The effect of
the variation of voltage on active and reactive power consumption
is recorded and, based on this load model, is developed.
A composite load, that is, a consumer load consisting of heating, air-conditioning, lighting, computers, and television is approximated by combining load models in certain proportions based on
load surveys. This is referred to as load window. Construction of a
load window requires certain data, that is, load saturation, composition, and diversity data. Any number of load windows can be
defined.
The load models are normalized to rated voltage, rated power,
and rated frequency, and are expressed in per unit. The exponential
Behavior of loads on voltage dips, with respect to percent load current and MVA, depending on the load type.
POWER SYSTEM STABILITY
325
load models are:
P
V
=
Pn Vn
αv
Q Q0 V
=
Pn P0 Vn
f
fn
βv
αf
(12-95)
f
fn
βf
(12-96)
where V is the initial value of voltage and P0 is the initial value of
power. Vn is the adjusted voltage and Pn is the power corresponding
to this adjusted voltage. The exponential factors depend on the load
type. The frequency dependence of loads is ignored for load flow
studies, but can be important for transient and dynamic stability
studies. Another form of load model is polynomial model.
Consider the equation:
P = Vn
(12-97)
For all values of n, P =0 when V =0, and P =1 when V =1, as
it should be. Differentiating:
dP
= nV n −1
dV
(12-98)
For V =1, dP/dV = n. The value of n can be found by experimentation if dP/dV, that is, change in active power with change in
voltage, is obtained. Also, by differentiating P =VI:
dP
dI
= I+V
dV
dV
(12-99)
For V and n equal to unity, the exponential n from Eqs. (12-98)
and (12-99) is:
n =1+
DI
DV
(12-100)
The exponential n for a composite load can be found by experimentation if the change in current for a change in voltage can be
established. For a constant power load, n =0; for a constant current
load, n = 1; and for a constant MVA load, n = 2. The composite
loads are a mixture of these three load types and can be simulated
with values of n between 0 and 2. Following are some quadratic
expressions for the various load types.12,13
Air conditioning:
P = 2 . 18 + 0 . 268V − 1 . 45V −1
Q = 6 . 31 − 15 . 6V + 10 . 3V 2
(12-101)
Fluorescent lighting:
P = 2 . 97 − 4 . 00V + 2 . 0V 2
Q = 12 . 9 − 26 . 8V + 14 . 0V 2
(12-102)
Induction motor loads:
P = 0 . 720 + 0 . 109V + 0 . 172V −1
Q = 2 . 08 + 1 . 63V − 7 . 60V 2 + 4 . 08V 3
F I G U R E 1 2 - 3 4 Voltage stability characteristics, as a function of
pre- and postdisturbance V-Q characteristics and reactive power support.
(12-103)
In sequential load method of analysis, the stability situation is
examined in certain time windows: (1) In the first second, motors slow
down and generator voltage regulators operate, (2) 1 to 20 s, when
the excitation limits occur, (3) 20 to 60 s when generator overexcitation limits operate, and (4) 1 to 10 min or longer when the ULTC
(under load tap changing), AGC (automatic generation contsol),
and phase angle regulators operate.
In Fig. 12-34, consider a system operating at point a, prior to
disturbance, intersection of V-Q characteristics, and dynamic load
curve Qs. A disturbance reduces V-Q operating point to b. However,
at b the reactive power load demand is greater than what can be
supplied. This load demand can only be met by lowering the operating voltage, and the operating point is now at c.
Now consider that postdisturbance reactive power support is
added, as shown in the figure. The operating point will shift to d at
higher voltage. This depends on how fast the postdisturbance reactive power support is restored. The operating point can as well be
d′ for slower restoration of the reactive power support.
At point d, if the reactive load demand is lower than the supply
system capability, the voltage will recover. Conversely at point d′,
if the load demand exceeds the supply system, the voltage will collapse monotonically.
We highlighted the importance of reactive power flow demand
as an important contributing factor to voltage instability. Usually, the voltage collapse involves highly overloaded lines or loss
of a line. Other initiating causes are loss of a generation, sudden
increase in load due to contingency load flow, outage of an SVC
or large reactive power compensating unit, and failure of ULTC on
transformers or voltage regulators.
The voltage instability can be prevented by the proper application of reactive power compensating devices, control of generator
reactive power output capability, ULTC, undervoltage and underfrequency load shedding, and coordination and protection.
Example 12-7 A system configuration of Fig. 12-35 is considered, with system data, as shown in Table 12-3. Generators G1 and
G2, each rated at 200 MW, step up their power output to 400 kV,
and are interconnected through a 400-kV line, 150 mi long. The
load flow balance and calculated bus voltages are shown. The load
consists of a 20000-hp motor at 13.8 kV and a 50-Mvar capacitor
bank, in addition to 350 MVA of load at 0.85 power factor connected to 400-kV system, bus 3. The generators are modeled with
type AC2 excitation systems and speed-governing models type ST
(see Chap. 13).
326
CHAPTER TWELVE
FIGURE 12-35
A three-bus system for dynamic stability study. Breaker 52 suddenly opened to isolate generator G2, Example 12-7.
TA B L E 1 2 - 3
Data for Example 12-7
DESIGNATION
DATA
400-kV utility source
Z1=Z2=0.0995 + j 0.995 (pu 100-MVA base) Z0=0.100 +j1.9975 (pu 100-MVA base)
G1 and G2
200 MW, 0.85 pF, Xd=110%, Xq=108%, T ′do=5.6 s, X ″d=12%, X ′d =23%, Xl=11%, model saturation,
model exciter type AC2A, model governing system type ST; see Chap. 13
H=2.5 (reactances on machine MVA base), high-resistance grounded through a distribution transformer,
ground current =8 A
Transformers T1 and T2
250 MVA, two-winding, low voltage delta, 400 kV wye-grounded, 30° standard phase shift, set taps at 400 kV
at +5% (420 kV), Z=10% (on transformer MVA base), X/R =50
Transformer T3
50 MVA, two-winding, 400-kV delta-connected, 13.8-kV wye-connected, low-resistance grounded, Z=14.5%,
on transformer MVA base, set tap on high side = −2.5% (390 kV)
Capacitor bank
Provides 50 Mvar at rated voltage of 400 kV
20000-hp motor
Full-load current =738 A, efficiency =95.12%, full-load power factor =94%, full-load speed =1768 rpm, locked
rotor current =637% of full-load current, locked rotor pf=6.76%, double age, X/R =89.152, T ′d =1.225 s,
H=1.925, polynomial load model=100 w2
Consider now that breaker 1 is suddenly opened at 0.1 s, with
no fault in the system. This isolates generator G2 and the load
demand must be met by the utility source through 150-mi transmission line and remaining generator G1 in service.
Figure 12-36 shows transients in generator G1 which gradually diverge over a period of time. This generator pulls out
of step at around 8 to 9 s and keeps oscillating. Figure 12-37
depicts transients in the 20000-hp motor, which escalate at the
time the generator G1 pulls out of step; the motor ultimately
locks out. Figure 12-38 illustrates bus voltage transients. The
field voltage and current transients, not shown, are of similar
patterns.
Though not illustrated graphically, even if generator G1 is disconnected from the system by protective relaying, the 20000-hp
motor still locks out and does not recover. In any interconnected
power system, such dynamic behavior is unacceptable.
FIGURE 12-36
Diverging transients in generator G1, simulated for 30 s, Example 12-7.
FIGURE 12-37
Transients in 20000-hp induction motor, Example 12-7.
328
CHAPTER TWELVE
FIGURE 12-38
12-14
Bus voltage transients, Example 12-7.
DIRECT STABILITY METHODS
The time-domain methods described earlier for the analysis of
stability problems may involve solving thousands of algebraic and
nonlinear differential equations, complexity depending on the
models used and the power system studied. This may be fairly time
consuming and may slow down the computing speed.
The time-domain methods analyze the prefault, faulted, and the
postfault systems. The direct methods integrate the faulted system
only and determine, without examining the postfault system, whether
the system will be stable after fault clearance. The system energy, when
the fault is cleared, is compared to a critical energy value.
The reader may study Appendix E before proceeding with this
section.
The differential equations of stability problems have a general
structure given by:
.
x(t ) = f [x (t )]
(12-104)
The state vector x(t) is in the Euclidean space R n and function f:
R n → R n satisfies the condition of existence and uniqueness of
solutions.
A state vector x̂ is called an equilibrium point of Eq. (12-104) if:
f (xˆ ) = 0
(12-105)
An equilibrium point is hyperbolic if the Jacobian of f (⋅) at x̂,
denoted by J f (xˆ ), has no eigenvalues with a zero real part. It is
an asymptotically stable equilibrium point if all eigenvalues of its
corresponding Jacobian have negative real parts; otherwise it is an
unstable equilibrium point, u.e.p.
If the Jacobian of the equilibrium point x̂ has exactly one eigenvalue with a positive real part, it is called type-one equilibrium point.
For a type k equilibrium point, Jacobian has exactly k eigenvalues
with positive real parts.
The stable and unstable manifolds are described as:
W s ( xˆ ):= { x ∈ R n : Φt ( x ) → xˆ t → ∞ }
W u ( xˆ ):= { x ∈ R n : Φt ( x ) → xˆ t → −∞ }
(12-106)
Every trajectory in stable manifold converges to x̂ as t → +∞,
and every trajectory in the unstable manifold also converges to x̂ as
t → −∞. For a s.e.p, there exists a number d >0 so that:
|| x 0 − xˆ ||< δ
Φ t ( x 0 ) → xˆ , as t → ∞
(12-107)
If d is arbitrarily large, then x̂ is called a global stable equilibrium point. There can be many physical systems containing stable
equilibrium points but not the global stable equilibrium points.
POWER SYSTEM STABILITY
A stability region for these systems is defined as:
A( x s ):= x ∈ R n : lim t →∞ Φt ( x ) = x s
Consider a power system with:
(12-108)
The stability region, also called the region of attraction, A( x s ),
is an open invariant and connected set. Its boundary is called the
stability boundary of x s and denoted as ∂A( x s ).
12-14-1
Stability Boundary
If an energy function exists that has an asymptotically stable equilibrium point x s , but not globally asymptotically stable, then the
stability boundary ∂A( x s ) is contained in the set which is a union
of the stable manifolds of the u.e.p’s on the stability boundary
∂A( x s ).
∂ A( x s ) ⊆ ∪ x ∈E∩∂A( x ) W s ( x i )
i
s
(12-109)
Transient Stability Models for Direct Analysis
The two
prevalent models are:
1. Network reduction models, where all loads are constant
impedance loads and the entire system is reduced to generator
internal buses (Example 12-4)
2. Network preserving models to overcome shortcomings of
network reduction models14
We will discuss only network reduction models. The transient
stability model can be written in the compact form as:15
∂U
.
Tx = −
( x, y) + g1 ( x, y)
∂x
.
y=z
.
∂U
Mz = − Dz −
( x, y) + g 2 ( x, y)
∂y
(12-110)
(12-111)
If along every nontrivial trajectory x(t), y(t), z(t) with bounded
function value W, x(t) is also bounded, then W(x, y, z) is an energy
function of Eq. (12-110).
12-14-2 Controlling u.e.p Method
The controlling u.e.p method has been around since 1970s and
is the most viable method for direct analysis of practical power
systems.16–18 The four basic steps are:
■
An energy function is constructed for the postfault system.
■
Energy is computed immediately after the fault clearing
time is reached.
■
■
Prefault SEP = X spre
Fault trajectory X f (t )
Postfault SEP = X
(12-112)
post
s
Let there be an energy function for the postfault system, and
X spre lies inside the stability region of X spost. Then, the controlling
u.e.p with respect to the fault on trajectory X f (t ) is the u.e.p of
the postfault system, whose stable manifold contains the exit point
of X f (t ). A sustained fault on the trajectory must exit the stability
boundary ∂A( x s ) of a postfault system. The exit point must lie on
the stable manifold of the u.e.p. This u.e.p is the controlling u.e.p
of the fault on the trajectory.
The controlling u.e.p method is applied in the following steps:
1. The controlling u.e.p, X co, is found for a given fault on the
trajectory.
2. The critical energy is the value of energy function at controlling u.e.p:
3. vcr = V ( X co )
4. The stability boundary is established for the fault on the
trajectory by using connected energy surface of the energy
function passing through controlling u.e.p, X co . This boundary
contains the s.e.p, Xs.
5. Calculate the value of energy function at the fault clearance
time, using fault on the trajectory.
6. v f = V ( X f t f )
where x ∈ R n , y and z ∈ R m . T, M, and D are positive diagonal
matrices, g1 (x, y) and g2 (x, y) are transfer conductance of the
reduced network, and U(x, y) is a smooth function.
A condition for existence of the energy function for the system
with zero-transfer conductance (gij =0) is:
W( x, y, z ) = K(z ) + U( x, y)
1
= z t M z + U( x, y)
2
329
The energy is computed for the fault on trajectory.
The energy of the state, when the fault is cleared, is compared
to a critical energy for stability assessments.
7. If v f < vcr , then the point Xf(cl) is located within the stability
boundary and the postfault system is stable; otherwise it may
be unstable. Thus, an approximation of the stability boundary of the postfault system is carried out to which the fault
trajectory is heading. It uses the connected controlling energy
surface passing through the controlling u.e.p to establish the
stability boundary. If, when the fault is cleared, the system state
lies inside the stability boundary, then the postfault system is
stable.
Figure 12-39 illustrates this. In this figure, Xco is the controlling
u.e.p with respect to the fault on the trajectory Xf(t). Xcl is the closest u.e.p on the postfault system Spost. Xe is the exist point of the
sustained fault on trajectory Xf(t), which is contained in the stable
manifold Ws(Xco) of the controlling u.e.p. Xco, X1, . . .∂S[V ( X co )] and
Xco. ∂S[V ( X cl )] are the constant energy surfaces passing through Xco
and Xcl, respectively. The sustained fault on the trajectory must first
hit ∂S[V ( X co )], then ∂S[V ( X cl )], and finally the stability boundary
at exit point Xe.
The task of calculating the exit point, and controlling u.e.p in
Fig. 12-39, is complex and requires iterative procedure in timedomain approach.
The energy function consists of kinetic energy and potential
energy terms. Even when the system is stable, some amount of
kinetic energy may not be absorbed. Some of the kinetic energy is
responsible for intermachine motion between the generators and
does not contribute to the separation of the severely disturbed generators from the system. The potential energy terms in the energy
function have a path-dependent term, which is approximated.
12-14-3
BCU Method
The difficulty of calculating the controlling u.e.p is overcome in
the BCU method, which does not calculate the u.e.p of the original
330
CHAPTER TWELVE
FIGURE 12-39
Illustration of controlling u.e.p method, direct stability analysis method.
model, but of a reduced state model. BCU stands for boundary of
controlling u.e.p.19–21
In applying this method for a power system, an associated
reduced-state model is first developed, so that:
FIGURE 12-40
1. The location of equilibrium points in the reduced-state
model correspond to that in the original system.
2. The type of equilibrium points are the same as that in the
original system.
Four steps in the numerical BCU method of direct stability analysis method.
POWER SYSTEM STABILITY
3. The reduced system has an energy function.
331
8. What are the limitations of “equal area criterion” of stability?
4. An equilibrium point on the reduced model lies on the stability boundary of the reduced system only if the equilibrium
point is on the stability boundary of the original system.
9. Based on Fig. 12-17a, construct block diagrams of synchronous generator, using data as shown in Table 10-2. Also
construct phasor diagram.
5. Without resorting to the time domain iterative approach,
it is possible to detect when a projected fault on the trajectory
hits the stability boundary.
10. Does system neutral grounding impact stability? Illustrate
with an example.
The various steps of calculation in a numerical network preserving BCU method are shown in Fig. 12-40. Steps 1 through
3 calculate the controlling u.e.p of the reduced-state system and
step 4 relates the controlling u.e.p of the reduced state to the original system. In step 1, the exit point of the projected fault trajectory
is calculated by first local maxima of the potential energy along the
sustained fault trajectory. In step 3, minimum gradient point (MGP)
is used to search for controlling u.e.p. MGP can be used as an initial
guess, and if it is close to controlling u.e.p, it will converge to the
controlling u.e.p, otherwise it may converge to another equilibrium
point or even diverge. A robust nonlinear solution is required.
This provides a brief overview of the direct methods. The cited
references provide further reading. This chapter is an overview of
the power system stability, and the concepts are continued further
in Chap. 13. The power system stability remains one of the subjects of great interest to electrical engineers, especially in the utility industry. Many industrial facilities have their own generation.
These machines and embedded generation run in synchronism
with the utility systems and have their own problems of stability
(Example 13-3).
PROBLEMS
1. A generator delivers 1.0 pu power to an infinite bus, which
reduces to 0.6 under a fault. The prefault maximum power is
2 pu, and postfault (after fault clearance) it is 1.25 pu. Neglect
saliency and saturation. Determine critical clearing angle for
H =5 and critical clearing time of the breakers for stability. The
breakers have an interrupting time of 3 cycles. Plot the swing
curve.
2. A 150 MW, 0.85 power factor, H =5.5 generator runs at
20 MW, 0.8 pF. The power load suddenly changes to 100 MW.
Determine acceleration and deacceleration of the rotor.
3. A 100 mi transmission line has the following parameters:
R =0.1094 Ω, X = 0.7654 Ω, Y = 5.456 µS (Siemens).
If the sending-end and receiving-end voltages are kept the
same, what is the steady-state stability limit of the line?
4. Obtain a Y matrix and a reduced Y matrix for the system
shown in Fig. 12-19 and calculate the generator internal voltage.
11. A transmission line has the following parameters:
length =200 km, voltage = 400 kV three-phase line-toline, reactance = 0.4 Ω/km, Bc = 5.0 mS (Siemens)/km,
a=0.00006 Np/km, b = 0.0013 rad/km.
Plot a curve showing power transmitted on x-axis versus the
ratio of receiving-end voltage to sending-end voltage at unity
power factor and 0.8 power factor lagging.
12. Consider a system described by:
Pm = 2.5 pu, during fault r1Pm = 0.80 pu, after fault clearance
r2Pm = 2.0 pu, H = 3.0, f = 60 Hz, Dt = 0.03 s, Pe = 1.25 per unit.
Calculate rotor angle and angular velocity at the end of 0.03 s
using Runge–Kutta and Euler’s modified method.
13. Drive the system equations for E″ model, step by step
(Eqs. 12-53 to 12-55).
14. In Example 12-5, a simple opening of a generator breaker
results in instability of a generator 150 mi away. Is it an
example of bad system design? Consider that all system components are designed for emergency load flow conditions and
have enough load carrying capability. What could be done to
improve stability?
15. Write a one page description of V-Q sensitivity analysis
without mathematical equations. What is implied by “distanceto-voltage instability?”
16. Write a one page comparison of controlling u.e.p and BCU
direct stability methods without mathematical equations.
REFERENCES
1. A. J. Gonzales, G. C. Kung, C. Raczkowski, C. W. Taylor, and
D. Thonn, “Effects of Single- and Three-Pole Switching and
High Speed Reclosing on Turbine Generator Shafts and Blades,”
IEEE Trans. PAS-103, pp. 3218–3228, Nov. 1984.
2. CIGRE SC38-WG02 Report, “State of the Art in Non-Classical
Means to Improve Power System Stability,” Electra, no. 118,
pp. 88–113, May 1988.
3. IEEE Working Group Report, “Turbine Fast Valving to Aid System Stability: Benefits and Other Considerations,” IEEE Trans.
PWRS-1, pp. 143–153, Feb. 1986.
5. A generator with 0.3 pu transient reactance supplies power
to an infinite bus through a line of 0.4 pu reactance. The
generator no-load voltage is 1.1 pu, and that of infinite bus is
1.0 pu. H =3.5. If the generator is loaded to 80 percent, what
is the natural frequency of oscillation and maximum power
transfer capability for small perturbations?
4. Electrical Transmission and Distribution Handbook, 4th ed., Westinghouse Electric Corporation, PA, 1964.
6. A two-pole 200-MVA generator has moment of inertia of
the rotor = 150,000 kg-m2. Convert it into H.
6. P. Kundar, Power System Stability and Control, McGraw Hill,
New York, 1994.
7. 150 MW of power is transmitted over a line which has a
static stability limit of 300 MW. Calculate the maximum load
that can be switched without loss of stability.
7. IEEE Std. 1110, IEEE Guide for Synchronous Generator Modeling Practices and Applications in Power System Stability
Analyses, 2002.
5. P. M. Anderson and A. A. Fouad, Power System Control and
Stability, IEEE Press, NJ, 1994.
332
CHAPTER TWELVE
8. R. T. Byerly, R. J Bennon, and D. E. Sherman, “Eigenvlaue
Analysis of Synchronizing Power Flow Oscillations in Large
Power Systems,” IEEE Trans. PAS-101, pp. 235–243, Jan. 1982.
9. N. Martins, “Efficient Eigenvalue and Frequency Response
Methods Applied to Power System Small-Signal Stability
Studies,” IEEE Trans. PWRS-1, pp. 217–225, Feb. 1986.
10. P. Kundur, G. J. Rogers, D. Y. Wong, L. Wang, and M. G.
Lauby, “A Comprehensive Computer Program for Small
Signal Stability Analysis of Power Systems,” IEEE Trans.
PWRS-5, pp. 1076–1083, Nov. 1990.
11. J. C. Das, Power System Analysis, Chapter 12, “Load Flow Methods,” Marcel Dekker, New York, 2002.
12. D. J. Hill, “Nonlinear Dynamic Load Models with Recovery for
Voltage Stability Study,” IEEE Trans. Power Systems, vol. 8, no. 1,
pp. 166–176, 1993.
13. EPRI, Load Modeling for Power Flow and Transient Stability
Computer Studies, Report EL-5003, 1987.
14. A. R. Bergen and D. J. Hill, “A Structure Preserving Model for
Power Stability Analysis,” IEEE Trans. PAS-100, pp. 25–35, 1981.
15. H. D. Chiang, C. C. Chu, and G. Cauley, “Direct Stability
Analysis of Electrical Power Systems Using Energy Functions:
Theory, Applications, and Perspective,” Proc. IEEE vol. 83,
no. 11, pp. 1497–1529, 1995.
16. A. A. Fouad and V. Vittal, Power System Transient Stability Analysis Using the Transient Energy Function Method, Prentice Hall,
Englewood Cliffs, NJ, 1991.
17. T. Athay, R. Podmore, and S. Virmani, “A Practical Method for
Direct Analysis of Transient Stability,” IEEE Trans. PAS-98, no. 2,
pp. 573–584, 1979.
18. M. A. Pai, Energy Function Analysis for Power System Stability,
Kluwer Academic Publishers, Boston, MA, 1989.
19. H. D. Chiang, F. F. Wu, and P. P. Varaiya, “A BCU Method for
Direct Analysis of Power System Transient Stability,” IEEE Trans.
Power Syst., vol. 8, no. 3, pp. 1194–1208, 1994.
20. F. A. Rehimi, M. G. Lauby, J. N. Wrubel, K. L. Lee, “Evaluation of
Transient Energy Function Method for On-Line Dynamic Security
Assessment,” IEEE Trans. PS, vol. 8, no. 2, pp. 497–507, 1993.
21. EPRI, User Manual for Direct Version 4.0 EPRI TR-105886s, Palo
Alto, CA, December 1995.
FURTHER READING
V. Ajjarapu and B. Lee, “Voltage Stability and Long Term Stability Working Group, Bibliography on Voltage Stability,” IEEE Trans.
Power Systems, vol. 13, no. 1, pp. 115–125, 1998.
W. T. Carson, Power System Voltage Stability, McGraw Hill,
New York, 1994.
H. D. Chaing, J. S. Thorp, I. Dobson, R. J. Thomas, and L. Fekih-Ahmed,
“On the Voltage Collapse in the Power Systems,” IEEE Trans. Power
Systems, vol. 5, no. 2, pp. 601–611, 1990.
H. D. Chiang, F. F. Wu, and P. P. Varaiya, “Foundations of Direct
Methods for Power System Stability Analysis,” IEEE Trans. Circuits
Syst., CAS-34(2), pp. 160–173, 1987.
CIGRE Task Force 38.02.05, Load Modeling and Dynamics,
Electra, May 1990.
S. B. Crary, Power System Stability, vol. 2, Wiley, New York, 1947.
P. L. Dandeno, R. L. Hauth, and R. P. Schulz, “Effects of Synchronous Machine Modeling in Large Scale System Studies,” IEEE Trans.
PAS-92, pp. 926–933, 1973.
EPRI Report EL-5798, The Small Signal Stability Program
Package, vol. 1. Final report of Project 2447-1, Nov. 1990.
F. P. de Mello, J. W. Feltes, T.F. Laskowski, L. J. Oppel, “Simulating
Fast and Slow Dynamic Effects in Power Systems,” IEEE Computer
Applications, Power, vol. 5, no. 3, pp. 33–38, 1992.
J. Deuse and M. Stubbe, “Dynamic Simulation of Voltage Collapses,”
IEEE Trans. Power Systems, vol. 8, no. 3, pp. 894–900, 1993.
IEEE Committee Report, “Dynamic Stability Assessment Practices in North America,” IEEE Trans. Power Systems, vol. 3, no. 3,
pp. 1310–1321, 1988.
IEEE Committee Report, “Supplementary Definitions and Associated Tests for Obtaining Parameters for Synchronous Machines
Stability Simulations,” IEEE Trans. PS, PAS-99, pp. 1625–1633,
1980.
E. W. Kimbark, Power System Stability, vol. 3, Wiley, New York,
1956.
K. Ogata, State-Space Analysis of Control Systems, Prentice Hall,
Englewood Cliffs, NJ, 1967.
R. J. O’Keefe, R. P. Schulz, and N. B. Bhatt, “Improved Representation of Generator and Load Dynamics on Study of Voltage Limited
Power System Operations,” IEEE Trans. Power Systems, vol. 12, no.
1, pp. 304–312, 1997.
W. W. Price, K. A. Wirgau, A. Murdoch, J. V. Mitsche, E. Vaahedi, and
M. A. El-Kady, “Load Modeling for Power Flow and Transient Stability Computer Studies,” IEEE Trans. PS, vol. 3, no. 1, pp. 180–187,
1988.
V. A. Venikov, Transient Phenomena in Electrical Power Systems,
Pergamon Press, Macmillan, New York, 1964.
C. C. Young, “Equipment and System Modeling for Large Scale
Stability Studies,” IEEE Trans. PAS-91, vol. 1, pp. 99–109, 1972.
CHAPTER 13
EXCITATION SYSTEMS AND
POWER SYSTEM STABILIZERS
The correct modeling and tuning of the excitation systems have
a profound effect on power system stability—both transient and
dynamic. Consider a synchronous machine operating on an infinite
bus of constant voltage and frequency. There is no external impedance added between the generator and the infinite bus, and the
saliency is neglected. We will study the effect of variation of generator excitation in such a system. By definition of the infinite bus, its
voltage V is fixed and is independent of the generator operation.
(A large generator in close proximity of the system under study
does impact the voltage and frequency.) The synchronous impedance of generator is Zs, where:
Z s = r + X l + X ad = r + X d
(13-1)
Xad is the reactance due to armature reaction, and Xl is the leakage
reactance (Chap. 10). Zs is assumed to be constant for the following
discussions.
If the generator is running at no load, and its emf is adjusted
by field excitation, exactly equal to the terminal voltage, then
neglecting no-load and core losses, no current flows in or out of
the generator (Fig. 13-1a).
If generator is underexcited then E is less than the terminal voltage V; a leading current Ir flows out of the generator which adds to
the field ampere turns by direct armature reaction. This current is
entirely reactive as no power is being supplied to or taken out of
the generator (Fig. 13-1b).
If the excitation is increased, then E is greater than the terminal
voltage V, and a lagging demagnetizing current circulates in the
stator, which reduces the net excitation, so that again there is no
power flow into or out of the machine (Fig. 13-1c).
Consider now that the generator supplies current into the infinite bus. Figure 13-1d shows the operation when the generator
supplies current exactly at unity power factor, Fig. 13-1e when it is
underexcited, and, finally, Fig. 13-1f when it is overexcited. When
the generator is underexcited, current leads the voltage, and when
overexcited, the current lags the voltage. In overexcited and underexcited conditions, a component of current Ir adds to the active
component Ia, so that the voltage triangle E, V, and the drop IaZs,
and Ir Zs satisfy the required conditions.
For a constant power output, the Ia and IaZs are constant. The
variation of Ir changes component IrZs, that is, the operating power
factor of the generator. Changes in load or excitation change the
power angle or torque angle d; it reverses when the generator
acts like a motor, and when d increases excessively, the machine
becomes unstable.
13-1 REACTIVE CAPABILITY CURVE (OPERATING
CHART) OF A SYNCHRONOUS GENERATOR
With these basic concepts the so-called reactive capability curve
of the generator can be constructed. Consider Fig. 13-2, where I
is the generator load current at a power factor of f, and V is the
terminal voltage which is equal to the infinite bus voltage. E and d
are as defined before.
For constant current and MVA, IXd is constant (here we neglect
resistance to demonstrate the simplicity of construction), and
therefore its locus is a circle with center at V. If excitation is held
constant, then its center is at point O. Then we can write:
Vq ≡ MVA
qp ≡ Mvar
(13-2)
Vp ≡ MW
For zero excitation E = 0, IXs =V, and I is purely reactive, leading,
and corresponding to VI vars per phase. For static stability limit
d = 90°, and therefore the horizontal line through O gives the
stability limit.
Using these observations, an operating chart (commonly called
reactive capability curve) can be constructed, as shown in Fig. 13-3.
Consider a synchronous reactance of 167 percent. For zero excitation current 100/167 = 60 percent of full-load value, which fixes
point O in Fig. 13-3. This also represents 60 percent of the full-load
MVA, in the form of leading Mvar, which fixes all the MVA and Mvar
scales. A horizontal line from V gives MW. Circles drawn with V as
center give MWs, and those drawn with center O give excitation
levels. Hundred percent excitation corresponds to fixed terminal
voltage OV.
333
334
CHAPTER THIRTEEN
F I G U R E 1 3 - 1 A synchronous machine on infinite bus. Generator at no load, (a) normal, (b) underexcited, and (c) overexcited. Generator at full load,
(d ) unity power factor, (e) underexcited, and (f ) overexcited.
The working area of the generator can now be marked, with
known generator specifications. Consider that the generator provides
rated output at 0.9 power factor. This fixes the part of curve pq. If we
assume that the excitation limit is 260 percent, then arc mn can be
described, and the limitation of the stator current corresponding to
maximum MW gives arc nq, with center V.
The line pq cannot be continued to the stability limit, as a small
excursion in load will cause instability. The other consideration is
the core heating when the generator absorbs reactive power from
the system and acts like a reactor. Point v on the stability limit
shows a MW of 60 percent at 100 percent excitation. Reduce it
by 10 percent to give point w and point u on the operating area.
EXCITATION SYSTEMS AND POWER SYSTEM STABILIZERS
FIGURE 13-2
Generator on infinite bus, showing generator operation,
constant current, and constant excitation loci.
FIGURE 13-3
335
This procedure can be followed at all points where the excitation
circles are crossing the stability line, giving 10 percent MW in hand
before the instability is reached.
A practical reactive capability curve is as shown in Fig. 13-4;
the underexcitation limiter (UEL) is an auxiliary control to limit the
underexcited reactive power current. The UEL uses synchronous
generator voltage and current inputs to determine the limit start
point and provide necessary feedback. This limit rises well above
the steady-state limit, curve A, given by the construction as shown
in the Fig. 13-4. The term UEL is synonymous with underexcited
reactive volt-ampere limit (URAL) and manufacturer’s excitation
limit (MEL). The excitation systems may have an overexcitation
limiter also, to prevent overheating of the generator rotor. According to ANSI/IEEE standards, a generator shall operate successfully
at its rated kVA, frequency, and power factor at any voltage not
more than 5 percent above or below the rated voltage, but not
necessarily in accordance with the standards established for rated
voltage operation.
The generator capability curves for voltages other than the rated
voltage will differ. For hydrogen-cooled generators, two or three
curves are supplied, depending upon the hydrogen pressure. The
dotted curve C in Fig. 13-4 shows operation at higher than the rated
voltage. On a short-time basis, it may be permissible to increase
reactive power capability within the thermal limits of the generator
stator, rotor, and the exciter. Curve C shows a 20-min capability.
This comes handy as the generators are the primary source of
Operating chart of a turbogenerator.
336
CHAPTER THIRTEEN
FIGURE 13-4
Reactive capability (P-Q ) curve of a generator, showing steady-state stability limit, URAL, and stability limit with fast excitation system.
Curve C shows emergency, 20-min reactive capability.
voltage regulation and may be called upon to supply greater reactive
power under contingency conditions. The UEL limit can be circular
type, straight-line type, or of multiple segments. The other limits
imposed on the excitation system are field current or overexcitation
limit and volts per hertz limit (V/Hz).
13-2
STEADY-STATE STABILITY CURVES
A generator has Xd =1.78 pu and operates through an external reactance Xe = 0.4 pu, then the steady-state stability curve is given by:
Center P = 0
Radius =
V2
2
Q=
V2
2
1
1
X − X = j0 . 97 pu
e
d
1
1
X + X = 1 . 53pu
d
e
(13-3)
The permissible vars for any active power output can be calculated
from:
(
V 2 Xd − Xe
P + Q −
2 Xd Xe
2
)
2
X + Xe
= V 2 d
2 X d X e
2
(13-4)
This is the equation of the circle of steady state stability illustrated
in Fig. 13-4. At P =0, the permissible vars, the generator operating
at rated voltage = 0.969 pu.
These equations can be derived from the equivalent circuit of
a generator, with a synchronous reactance of Xd, connected to an
infinite bus through an external reactance of Xe.
13-3
SHORT-CIRCUIT RATIO
The short-circuit characteristics of a generator relate the armature
reaction to the field excitation. The field excitation produces a
small flux that generates an emf to circulate the short-circuit current through the resistance and leakage reactance. At high values of
short-circuit currents, nonlinearity can arise, which is ignored here.
Referring to Fig. 13-5a, the short-circuit ratio is defined as:
SCR =
Fv
Fsc
(13-5)
where Fv = field excitation to generate rated voltage on open-circuit characteristics, and Fsc = field excitation to circulate shortcircuit current equal to rated current of the generator on terminal
short circuit.
The SCR is, therefore, the ratio of the pu excitation for rated voltage on open circuit and pu excitation for rated armature current on
short circuit. Short-circuit ratio is approximately reciprocal of the
synchronous reactance, defined in per unit value for normal voltage
and current. However, synchronous reactance for a given load is
affected by the saturation, while SCR is unique to the machine.
The significance of higher SCR can be examined with reference
to Fig. 13-5b and c. Figure 13-5b shows a generator with stronger field (larger field flux) which requires a larger short-core. Fa
is the armature mmf, and the field mmf Ft must partly oppose Fa,
and the resultant Fe develops the gap flux on which internal voltage E depends. With fewer armature turns Fa is reduced, so that
gap length is increased to absorb Fe. Figure 13-5c shows the opposite, a larger Fa, that is, larger armature turns. The comparison of
Fig. 13-5b and c shows that a stronger field and larger air gap gives
a smaller torque angle δ, that is, a stiffer machine. Thus, SCR is a
measure of relative stability.
EXCITATION SYSTEMS AND POWER SYSTEM STABILIZERS
337
interface with the machine models. Signals with per unit
synchronous machine terminal voltage must be normalized to
the same base, the exciter output current in per unit on the
field current base, and the exciter output voltage in per unit
on field voltage base.
The earlier reciprocal system is not in use. The non-reciprocal
system is much in use, and the base voltage, vFb, is the voltage on
the air-gap line to produce a no-load voltage equal to the generator
terminal voltage.
Consider that a field current IF = 1000 A at field voltage vF = 200 V
is required to produce rated generator voltage at no-load on the
air-gap line; then in the nonreciprocal pu system, the base values
of field voltage and current by definition are VFb = 200 V and
IFb = 1000 A. In the reciprocal system if Lad (unsaturated) = 1.8 pu,
and rF =0.0014 pu, then:
ifb(recip) = Lad IFb = 1.8 × 1000 = 1800 A
ufb(recip) =
Lad
V = 1 . 8 200 = 257 . 1 kV
rF Fb 0 . 0014
13-5 NOMINAL RESPONSE OF THE EXCITATION
SYSTEM
FIGURE 13-5
(a) Short-circuit ratio of a generator, (b) effect of relative construction: large flux, and small long-core, and (c) effect of small field
flux and large short-core on torque angle d.
Over the course of years the SCR of synchronous generators has
reduced to around 0.5 or sometimes, lower. The enhancement in
stability limit is obtained by modern fast-response excitation systems (Fig. 13-4).
13-4
PER UNIT SYSTEMS
In constructing the above reactive capability chart of the generator,
we used an excitation voltage limit, that is, ceiling excitation voltage of 2.6 times the rated voltage. This requires some explanation.
In defining rated voltage of the excitation system, there are some
choices: (1) the rated voltage of the exciter, (2) the rated load field
voltage, and (3) the voltage required to circulate the field current
on the air-gap line. Anderson1 recommends using (2), but IEEE
standard 421.52 embraces all these definitions and even enlarges
them. The ceiling voltage under load is determined with excitationsupplying ceiling current, which is the maximum current the excitation system can supply for a specified time. For excitation systems
whose supply depends upon synchronous machine voltage and
current, the nature of disturbance and specific machine parameters should be considered. For rotating exciter, the ceiling voltage
is determined at rated speed.
Synchronous machine currents and voltages are defined
in per unit. Rated stator current and rated terminal voltage
of the machine are one per unit quantities. The rated field
current is the current required to produce rated terminal
voltage on air-gap line, and one per unit field voltage is the
corresponding voltage. The excitation system models must
The excitation system response is determined from the curve shown
in Fig. 13-63. In this figure the rate of increase or decrease of the
excitation output voltage is given by line ac, so that area acd is equal
to area abd. This means that the rate of rise, if maintained constant,
will develop the same voltage-time area as obtained from the curve
for a specified period, 0.5 s shown in the figure. The response ratio
is (ce-ao)/[(ao)0.5] pu V/s. Nominal response is used as a figure of
merit for comparing different types of excitation systems; misleading results can occur if different types of limiters or different values
of inductances are permitted.
The response ratio is an approximate measure of the rate of rise
of the exciter open-circuit voltage in 0.5 s, if the excitation control
is adjusted suddenly in the maximum increase position. This can be
considered more like a step input of sufficient magnitude to drive
the exciter to its ceiling voltage, when the exciter is operating under
no-load conditions.
13-5-1
Fast-Response Systems
The time of 0.5 s in IEEE standards was chosen because it approximates to one-half period of natural electromechanical oscillation of
average power system. Modern fast systems may reach ceiling voltage
in much smaller time. Fast-response systems are defined as the
FIGURE 13-6
ing to Ref 2.
Determination of excitation system response, accord-
338
CHAPTER THIRTEEN
FIGURE 13-7
Open-loop frequency response, stability of excitation systems.
ones which reach ceiling voltage in a time of 0.1 s or less, and oe in
Fig. 13-6 is replaced by 0.1 s.
13-5-2 Stability of the Excitation Systems
The excitation system stability refers to the ability of the system to
control the field voltage of the generator, so that transient changes
and oscillations in the regulated voltage are suppressed. This leads
from one stable operation to another. Some factors that impact
FIGURE 13-8
stability are the speed of operation, the nature of response, whether
over damped or under damped, rise time, and overshoots and settling time. Concepts of stability of control systems discussed in
Chap. 3 are applicable. The small-signal criteria are used to evaluate the performance of closed-loop excitation control systems.
Typical open-loop frequency response, in the form of Bode plot
of the excitation system with synchronous machine open circuited,
is shown in Fig. 13-7.3 The closed-loop frequency response is shown
in Fig. 13-8. In general, a gain margin Gm of 6 dB or more and a
Closed-loop frequency response, stability of excitation systems.
EXCITATION SYSTEMS AND POWER SYSTEM STABILIZERS
FIGURE 13-9
339
Basic control circuit block diagram of excitation systems.
phase margin of fm 40° or more is recommended for most feedback
control systems (also see Chap. 3).
Relative stability of the closed-loop control system can be determined from properties of the open-loop transfer function, provided
open-loop transfer function does not have poles and zeros in the
right half s-plane.
With respect to closed-loop frequency response, peak value MP
in decibels of the amplitude response is also a measure of stability. A high value of MP > 1.6 dB is indicative of oscillatory system
exhibiting large overshoot. In general, 1.1 dB ≤MP ≤1.6 dB is an
acceptable design.
13-6 BUILDING BLOCKS OF EXCITATION SYSTEMS
Figure 13-9 shows basic block diagram of the excitation systems.
The explanation of each block function is as follows (Fig.13-10):
1. Voltage transducer. The generator voltage is sensed by a PT,
which is rectified, and these blocks can be represented by
Fig.13-10a:
Vc =
K R × VT
1 + sTR
(13-6)
where VT is the terminal rms voltage Vc is the output dc voltage,
KR is the proportionality constant, and TR is the time constant of
PT and rectifier assembly (this is small).
Figure 13-11 shows a variation, where load compensator is
present. Note that only one time constant is recognized in the
model shown, though load sensing may have different time constants. When load sensing is not there, Rc = Xc = 0, and the system returns to that of Fig. 13-10a. The values of Rc and Xc can
take positive or negative values. In most cases, the value of Rc
is negligible. The input variables of synchronous machine voltage and current must be in the phasor form for the comparator
calculations.
2. Comparator. The comparator compares the Vc against a
fixed reference VREF, and generates an output voltage VE, the
error voltage. It could be an electronic difference amplifier with
negligible time constant or a nonlinear bridge circuit with
practically zero time constant; the control circuit block diagram
is shown in Fig. 13-10b.
VE =
K
(V − Vc )
1 + sT REF
(13-7)
where K is the gain in the regulator, VREF is the reference voltage,
and T is approximately equal to 0 for a passive circuit.
3. Amplifier. The amplifier takes the error signal. Also the
summation point receives a signal from the stabilizer, which
is added, and also a signal from the excitation stabilizer, which
is a negative feedback and is subtracted (Fig. 13-9). The
amplifier may be a rotating amplifier, a magnetic amplifier, or
an electronic amplifier. Considering linear voltage amplification,
KA is the gain with time constant TA. The saturation value of the
amplifier is given within limits, VRMIN < VR < VRMAX (Fig. 13-10c).
VR =
FIGURE 13-10
Building blocks of an excitation system.
KA
V
1 + sTA E
(13-8)
where VR is the regulator output voltage, KA is the linear voltage
gain, and TA is the time constant.
340
CHAPTER THIRTEEN
FIGURE 13-11
Terminal voltage transducer and optional load compensation elements.
4. Exciter. The exciter output voltage is a function of the regulator voltage. The block diagram in Fig. 13-10d represents this
operation. The exciter is a boost-buck system:
EFD =
VR − EFDSE
K E + sTE
(13-9)
where EFD is the exciter output voltage, KE is the exciter proportionality constant, TE is the exciter time constant, and SE is the
exciter saturation function.
The constant TE is explained further in Sec. 13-7.
5. Excitation compensator. The compensation circuit in the control system adds to the stability. It can be a feedback or lead/lag
compensation. The block diagram representing the comparator
is shown in Fig. 13-10e.
VF =
sK F
E
1 + sTF FD
(13-10)
where VF is the exciter feedback signal, KF is the rate feedback
constant, and TF is the time constant of feedback system.
represent the increase in exciter excitation requirements due to
saturation, illustrated in Fig. 13-12. At a given exciter output
voltage, quantities, A, B, and C are defined as the excitation to
produce that voltage on the constant resistance load saturation
curve, on air-gap line, and on no-load saturation open circuit
curve, respectively.2 The constant resistance load saturation is
used for all dc commutator exciters and ac exciters type AC5A
(see Sec. 13-9).
SE (EFD ) =
A−B
B
(13-12)
Two values of dc commutator exciter voltage are applicable: EFD1
and EFD2. Voltage EFD1, for which SE(EFD1) is specified, is near the
exciter ceiling voltage and voltage EFD2, for which SE(EFD2) is specified at a lower value, commonly near 75 percent of EFD1.
Consider saturation characteristics, (shown in Fig. 13-12).
Define saturation as Se (Ex). Then, change in field current Ief is function of Ex and the saturation factor is given by:
DIef = E x Se (E x )
(13-13)
6. Generator. The final element in the control system is
the generator itself, whose terminal voltage is a function
of the exciter output voltage. The generator is at load. When
the generator is open-circuited, the open-circuit time constant, Tdo, applies. When the generator is short-circuited, Td′
applies. The time constant dependent upon load is designated by TG. The block diagram is shown in Fig. 13-10f.
VT =
KG
E
1 + sTG FD
(13-11)
where KG is the generator gain from exciter voltage and TG is the
generator time constant, which varies between two extremes of
no-load and short-circuit time constant.
13-7 SATURATION CHARACTERISTICS
OF EXCITER
The open-circuit characteristics (OCC) relate terminal voltage at
open circuit and normal speed to field excitation. Under these
conditions, the terminal voltage measured is induced emf, which
depends upon the total flux linking the armature. It is a measure
of the saturation in the magnetic circuit. At low levels of excitation,
the OCC is linear, and the main reluctance in the circuit is that of
air gap. The part of the excitation devoted to the gap is defined as
air line.
As the excitation is increased, the iron parts suffer a considerable
decline in permeability, and the OCC for upper range of field excitation has a smaller slope. There is definite knee point linking the
two curves. The saturation increases as the excitation is increased.
13-7-1 DC Exciters
For dc commutator exciters’ two saturation functions, SE (EFD)
is defined as a multiplier of per unit exciter output voltage to
FIGURE 13-12
saturation curves.
(a) Separately excited dc exciter. (b) Exciter load
EXCITATION SYSTEMS AND POWER SYSTEM STABILIZERS
Ief0 and Ex0 correspond to an operating point in pu. Then, from
Eq. (13-9):
Also in the field circuit, we can write the equation:
Eef = R ef I ef + Lef
dI ef
dt
341
(13-14)
Eef = E x[K E + SE (E x )] + TE
dE x
dt
(13-21)
Also:
where:
I ef =
E
Ex
+ D I ef = x + E x Se (E x )
Rg
Rg
(13-15)
where Rg is the slope of the air-gap line. Thus, combining the above
relations, we can write:
R
1 dE x
Eef = ef + R ef Se (E x ) E x +
R
K
dt
g
E
(13-16)
KE =
R ef
Rg
S E ( E x ) = Se ( E x )
Block circuit diagram in Fig. 13-13a shows the dc exciter
representation. For small-signal analysis, it can be simplified to
Fig. 13-13b and then c.
Let generator base field voltage be Efb:
D Eef = D E f
Exb = Efb
I efb =
Efb
Rg
(13-17)
R gb = R g
K=
In per unit the saturation factor is:
Se ( E x ) = R g Se ( E x )
(13-18)
Eef =
R ef
1 dE x
E [1 + Se (E x )] +
Rg x
K e dt
(13-19)
1/Ke is inverse of a time constant:
L I
L
1
= ef ef 0 = ef = TE
K e R g Ex 0 R g
FIGURE 13-13
(13-20)
(1 + sT )
K
1
SE (E x 0 ) + K E
(13-23)
T = KTE
(13-24)
Thus, for small signal deviation, the dc exciter is represented by a
single time constant. Both K and T vary with the operating point.
For self-excited dc exciter, the model is similar but KE = Ref/Rg − 1.
13-7-2
Equation (13-16) is reduced to:
(13-22)
R ef
Rg
AC Exciters
The ac exciters generate the dc power required for generator field
windings, through an ac alternator and either stationary or rotating rectifiers (brushless systems). The rectifier system is generally
a three-phase bridge circuit; these sources have an internal impedance which is predominantly inductive. The Vf (If ) curve of the
rectifier is non-linear and depends upon the diode commutation;
the overlapping angle and the alternator reactance plays a major
role. The rectifier regulation characteristics are determined from
the equations in Fig. 13-14.2 Three operation modes are recognized. For small values of KC, only mode 1 needs be modeled, that
is, for type ST1A exciter model, IN should not be greater than 1.
(a) Block circuit diagram of a dc exciter, (b) and (c) simplification of the block circuit diagram for small signal deviations.
342
CHAPTER THIRTEEN
FIGURE 13-14
Rectifier regulation characteristics.2
The quantities EFD, IFD, VE, and KC are all in per unit on a synchronous machine field base.
For ac exciters (except for exciter type AC5A), the saturation
factor SE (Vf) is calculated from no-load saturation curve and the
air-gap line of the ac exciter. From Fig. 13-12,
SE (VE ) =
C−B
B
(13-25)
Again two voltages VE1 and VE2 are defined for the alternatorrectifier excitation voltage. VE1 voltage, for which SE (VE1) is specified, is close to the exciter open-circuit ceiling voltage and the
voltage VE2, for which SE(VE2) is defined, is at a lower value, nearly
75 percent of VE1.
and the following limiting action applies:
LN < v < L X
then y = v
v ≥ LX
then y = L X
v ≤ LN
then y = L N
For the nonwindup limit, the system equation is:
f=
u−v
T
(13-28)
and the following limiting action applies:
13-7-3 Windup and Nonwindup Limits
Figure 13-15a and b shows the windup and nonwindup limiters
applied to a single-time block constant. For the windup limit, the
system equation is:
dv u − v
=
dt
T
(13-26)
(13-27)
LN < y < L X
dy
=f
dt
dy
then
=0
dt
dy
then
=0
dt
then
y ≥ LX
and
f >0
y ≤ LN
and
f <0
y = LX
y = LN
(13-29)
EXCITATION SYSTEMS AND POWER SYSTEM STABILIZERS
343
F I G U R E 1 3 - 1 5 (a) and (b) Windup and nonwindup limiters applied to a single-time block constant. (c) Lead-lag function with nonwindup limits.
(d ) Physical realization of (c).
Lead-lag function with nonwindup limits is shown in Fig. 13-15c,
and its physical realization is shown in Fig. 13-15d. Following relations apply in these cases:
LN ≤ v ≤ L x
then y = v
v > LX
then y = L X
v < LN
then y = L N
13-7-4
(13-30)
Gating Functions
Gating functions are used to allow control of one of the two input
signals, depending upon their relative size with respect to each
other. In Fig. 13-16a. For the LV gate:
u≤v
u>v
y=u
y=v
(13-31)
For the HV gate in Fig. 13-16b:
u≥v
u<v
TYPES OF EXCITATION SYSTEMS
An earlier IEEE report4 classified the excitation systems into four
types: (1) type 1 excitation system represented continuously acting regulator and exciter, (2) type 2 system represented rotating
rectifier (brushless) system, (3) type 3 represented static system with terminal potential and current supplies, and (4) type 4
represented noncontinuously acting regulator. These models
are still in use, and their control circuit diagrams are not shown.
Currently the types of excitation systems and AVR models can
be described according to IEEE standard,2 which classifies these
into three major categories, based upon the excitation power
source:
■
DC excitation systems utilize a dc current generator with a
commutator for the excitation power source (e.g., IEEE types
DC1A, DC2A, and DC3A).
■
AC excitation systems use an alternator and either stationary or rotating rectifiers (brushless) to produce the dc
power (e.g., IEEE types AC1A, AC2A, AC3A, AC4A, AC5A,
and AC6A).
■
ST type excitation systems use static controlled rectifiers for
the dc power supply (e.g., IEEE types ST1A and ST2A).
y=u
y=v
FIGURE 13-16
13-8
(13-32)
(a) LV and (b) HV gates.
The type designations in parenthesis are from IEEE standard,3
which describes excitation system models for the stability studies.
This reference gives the block circuit diagrams of each of the exciter
types and also typical time constants. Manufacturers specify the
time constants and data based upon the IEEE models, and this
data may differ from the specimen data included in IEEE standards.
For any rigorous stability study, the manufacturer’s data should
be used. Further, many models may be manufacturer-specific
and may not exactly confirm to IEEE types, especially for equipment
of European origin.
344
CHAPTER THIRTEEN
FIGURE 13-17
13-8-1
A dc commutator exciter system with manual control and regulator transfer, represented by DC1A.
The DC Exciter
The dc exciters are being replaced with ac exciters; earlier dc exciters were extensively used for machines in the range of 100 MVA
and below. The commutators and brushes in the rotating dc exciters
require much maintenance. A typical exciter is shown in Fig. 13-17;
The shaft is coupled with the main generator, and the excitation is
supplied to the generator field windings through slip rings. The dc
excitation systems are not being built currently, though many old
systems are still in use. The dc exciters use a main dc exciter, which
may be separately mounted (motor generator set) or shaft mounted
(with static amplifier). A rotating amplifier (amplydine) was earlier
used. These have a relatively slow response. The exciters may be
noncontinuously acting type, that is, the control action is not continuous and changes in steps—in other words “raise-lower” mode,
with a change in terminal voltage of the machine large enough to
exceed the threshold. These exciters have basically two different
rates, depending upon the magnitude of the voltage error. For small
changes, the adjustments are made with a motor-operated rheostat.
Large voltage deviation results in a resistor being shorted.
Type DC1A Excitation System Figure 13-17 shows a dc generator exciter with static magnetic amplifier deriving its power from
a permanent magnet generator (PMG) set. Often the frequency is
increased to 420 Hz to increase the amplifier response. The exciter
has two fields, one for buck and another for boost. A third field
provides for the manual operation.
The control circuit block diagram of a continuously acting dc
commutator exciter type DC1A is shown in Fig. 13-18. This model
represents many commercial excitation systems that have been in use,
namely, Westinghouse types (Mag-A-Stat™, Rototrol™, Silverstat™,
and TRA™), GE types (GDA and amplidyne regulators), and Brown
Boveri types (AB and KC regulators).
As shown in this diagram, the principal input VC, from the terminal voltage transducer and load compensator at the junction, is
subtracted from VREF; then the stabilizing voltage VS is added and
the feedback voltage VF is subtracted to form an error signal, which
is amplified. KA and TA are the major time constants associated with
amplifier; TC and TB are small and can be neglected. In steady state
VS and VF are zero. The voltage regulator utilizes power sources
which are essentially unaffected by brief transients of the synchronous machine and auxiliary buses.
The exciter may be separately excited or self-excited. When selfexcited, the value of KE is selected so that VR is initially equal to zero.
This represents operator action for tracking the voltage regulator.
The saturation function is as discussed before. A common expression for Vx is:
Vx = A EX e BEX EX
(13-33)
The block diagram of Fig. 13-13a can be reduced as shown in
Fig. 13-13b and c, by considering small signal response. As the
operators track the voltage regulator by manual adjustments, it
means that KE is not fixed, but varies with operating condition.
Example 13-1 A generator is operating with EFD = 1.7 pu and
Vt = 1.0 pu. Consider AEX = 0.01 and BEX = 1.5. Find KE and VREF = Eef.
KE takes a value so that VREF = 0. Thus:
K E EFD = −Vx
= − A EX e BEX EX = − 0 . 01e1.5×1.7
KE = −
1 . 281
= − 0 . 75
1.7
Under steady-state VREF = VC = VT = 1.0 pu. Typical data with selfexcited exciter is:
K A = 400
13-8-2
TA = 0 . 89
TE = 1 . 15
The Static Exciters
A static exciter schematic is shown in Fig. 13-19. The potential
source for the excitation power is derived from the generator bus
itself. The ac voltage through the power potential transformer (PPT)
is rectified through controlled rectifiers and is proportional to the
generator bus voltage. Due to static controls and components, the
response is fast. These systems are modeled with IEEE model type
ST1. Some examples of this model are Westinghouse-type PS static
excitation with WTA or WHS regulators, and Canadian General
Electric Silcomatic exciters. The model ST2 is for a compound
source static exciter, where the current support is added in addition
to voltage through a short-circuit CT (SCT). A phasor combination
of the terminal voltage and current is formed. One example of this
excitation system is the GE SCT-PPT type excitation system, which
has been popular. On a short circuit close to the generator terminals, the voltage will be much reduced, and as PPT is connected
to the same generator bus, its output is much reduced. On the
other hand, short-circuit current increases, and the current support
EXCITATION SYSTEMS AND POWER SYSTEM STABILIZERS
FIGURE 13-18
345
A dc commutator exciter, type DC1A.
through an SCT can hold the excitation voltage better, enhancing
the stability limit. We will concentrate on ST1 type exciters, and
there are many commercial exciter types which meet this model.
The computer model for stability analysis is shown in Fig. 13-20.
The inherent time constants are small. The transient gain reduction can be implemented in the forward path via time constants TB
and TC (in which case KF is set to zero) or through feedback path
by suitable choice of KF and TF. Time constants TC1 and TB1 allow
for possibility of representing transient gain increase, and TC1 is
normally > TB1.
The input-output relation is assumed to be linear by proper
choice of KA. In some systems, the bridge relationship is not linearized, though a linearization of the characteristics is generally
satisfactory.
In many cases, the internal limits on V1 can be neglected. The
field voltage limits, which are a function of both terminal voltage and
synchronous machine current, should be modeled. As a result of
the high forcing capability of the system, a field current limiter is
sometimes employed to protect the generator rotor and exciter. The
limit start setting is defined as ILR and the gain as KLR. To ignore this
F I G U R E 1 3 - 1 9 A static excitation system with the potential source employing controlled rectifiers, where the excitation power is supplied through slip
rings, represented by ST1A.
346
CHAPTER THIRTEEN
FIGURE 13-20
A static exciter system, type ST1A.
limit set KLR = 0. The model is also applicable to systems with halfcontrolled bridge, in which case VRMIN = 0.
Figure 13-19 shows a manual regulator in addition to the automatic control regulator. In case of failure of the automatic regulator, a
transfer can be automatically made to manual mode. It is possible to
have a step-less autotransfer to manual, in case the automatic regulator fails. The automatic regulators can also be duplicated in redundant
mode for large machines. For large generators above, say, 80 MW, it is
usual to have redundant fully automatic regulators in automatic transfer mode. There is no hard and fast limit with respect to the rating of
FIGURE 13-21
the machine, and the power supply reliability, depending upon the
usage of the generator, dictates the choice. The PT supplies to regulators are invariably arranged through redundant PTs with autotransfer,
in case a PT fuse operates or the output power of one PT is lost.
13-8-3
The AC Exciter Type AC2A
The brushless ac exciters, using a PMG, require low auxiliary
power to control the field of the rotating ac pilot exciter, which has
a rotating armature and stationery field (Fig. 13-21). This provides
A brushless rotating rectifier exciter system, represented by AC1A or AC2A.
EXCITATION SYSTEMS AND POWER SYSTEM STABILIZERS
FIGURE 13-22
347
Control circuit exciter type AC2A.
the black start capability. These systems can be represented with
IEEE type AC1A or AC2A models. The brush type ac exciters have
a shaft-connected ac pilot exciter. These may have controlled or
noncontrolled stationary rectifier assemblies. These are modeled
with IEEE type AC3 or AC4A models.
The AC2 model represents a high initial response system, and its
block circuit diagram is shown in Fig. 13-22. The alternator main
exciter is used with noncontrolled rectifiers. The model is similar to AC1A, but has two additional field current feedback loops.
An example of this exciter is Westinghouse high initial response
brushless excitation system. The demagnetizing effect of load current IFD on exciter alternator output voltage VE is accounted for in
the feedback path that includes the constant KD. This is a function
of the generator’s synchronous and transient reactances. The exciter
voltage drop due to excitation is simulated by inclusion of constant
KC, which is a function of commutating reactance and the rectifier
regulation curve (Fig. 13-14).
VFE proportional to the exciter field current is derived from the
summation of signals from the exciter output voltage VE, multiplied
by KE + SE[VE] which represents saturation and IFD multiplied by the
demagnetization term KD. The exciter field current signal VFE is used
as the input to the excitation system stabilizing block with output VF.
The exciter time constant compensation consists of a direct feedback VH, around the exciter field time constant, reducing its effective value, thereby increasing the small signal response bandwidth
of the excitation system. The time constant is reduced proportional
to the product of gains KB and KH of the compensation loop and
is normally more than an order of magnitude lower than the time
constant without compensation. To obtain a high response, a very
high forcing voltage VRMAX is applied to the exciter field. A limitsensing exciter field current serves to allow high forcing but limits
the current.
Other exciter models, their time constants, and their circuit diagrams are in Ref. 2. Manufacturers will usually include a control
circuit diagram of their excitation system and AVR at the time of
equipment purchase with all the relevant time constants and data
applicable to the specific machine.
Example 13-2 We will continue with Example 12-5. Referring
to Fig.12-27, generator G2 is unstable for a three-phase fault on
Bus 2, fault duration 0.3 s. The generators were modeled without
excitation systems. Now add a type AC2 exciter only on generator
G2 which lost stability. The AC2 exciter parameters are the same as
shown in Table 13-2.
Figure 13-23a and b depicts transients in generator G2 and also
field circuits. G2 power angle swings to 152° in the first swing, but
recovers in the subsequent swings which show stability. Also Bus 2
voltage, which had collapsed to zero during the fault, recovers on
fault removal (Fig. 13-23c). These transients can be compared with
those shown in Fig. 12-27.
Example 13-3
Figure 13-24 depicts a power system with load
flow data and the system data is tabulated in Table 13-1. It shows
the normal load flow and bus voltages with both generators in
service.
A three-phase fault occurs on Bus 4. The critical fault clearance time is calculated with four excitation system models: AC1A,
AC2A, DC3A, and ST1A, and the results are given in Table 13-2,
which also shows typical data of the excitation system models.
348
CHAPTER THIRTEEN
The plots of transients are not included. The maximum difference
in the stability limit is seen to be 0.029 s (1.74 cycles), exciter
model AC2 giving maximum critical clearance time. The results of
this example should not be generalized, much will depend upon the
power system being studied and the nature of disturbance.
FIGURE 13-23
Example 13-4
This example is a study of transient stability of
two small generators of 3.125 MVA and 5.0 MVA connected in a
power system of Fig. 13-25.5 The generators pull out of step for
faults and voltage dips in the 44-kV weak utility system (threephase short circuit at 44 kV = 3 kA rms symmetrical). The system
(a) G1 and G2 transients and field circuit transients, with an exciter type AC2A applied to G2. (b) Recovery transients of the bus voltage.
EXCITATION SYSTEMS AND POWER SYSTEM STABILIZERS
FIGURE 13-23
FIGURE 13-24
(Continued )
A power system configuration for study of critical clearing time of exciter types DC3A, ST1A, AC1A, and AC2A.
349
350
CHAPTER THIRTEEN
TA B L E 1 3 - 1
System Data for Transient Stability Study
DESCRIPTION
DATA
Utility source, 138 kV
Z 1 = Z 2 = 0.0995 + j 1.989, Z 0 = 0.374 + j 5.9885, 100-MVA base
Transformer T 1
30-MVA, 138-kV winding = delta-connected, 13.8-kV winding wye connected and resistance grounded through
400-A resistor, standard phase shift =−30°, Z = 10% on 30-MVA base, X/R = 23.7, set primary tap at −2.5
(134.55 kV)
Loads
Bus 1-25 MVA, 0.9 PF, Bus 2-20 MVA, 0.85 PF, Bus 3 = 30 MVA, 0.85 PF, constant Z type
Current-limiting reactors
R1, R2, and R 3
2000 A, 0.4 Ω, Q =60
G1
21.5 MVA, 2 pole, 60 Hz, 0.85 PF, Model 3, X″d = 14.4, X″q = 13.9, X 2 = 13.5, X 0 = 12, X d = 227, X q = 213,
X dv = 242, X qv = 226, X ′d = 21.9, X ′q = 53.6, X l = 15.7 all on generator base MVA of 21.5
T ′do = 4.8 s, T ″do = 0.023 s, T ′qo = 0.404 s, T ″qo = 0.055 s, damping = 5%
H = 4.6
G2
48 MVA, 2 pole, 60 Hz, 0.85 PF, Model 3, X″d = 14.4, X ″q = 13.9, X 2 = 13.5, X 0 = 12, X d = 227, X q = 213,
X dv = 242, X qv = 226, X ′d = 21.9, X ′q = 53.6, X l = 15.7 all on generator base MVA of 21.5
T ′do = 4.8 s, T ″do = 0.023 s, T′qo = 0.404 s, T ″qo = 0.055 s, damping = 5%
H = 4.7
TA B L E 1 3 - 2
EXCITER
TYPE
Calculated Critical Clearing Time
and Exciter Data
CRITICAL FAULT
CLEARING TIME*
EXCITER PARAMETERS†
AC1A
0.232 s
VRMAX = 14.5, VRMIN = −14.5,
SE MAX = 0.1, SE 0.75 = 0.03, E FD = 4.18,
KA = 400, KC = 0.2, KD = 0.38, KE = 1,
KF = 0.03, TA = 0.02, TB = TC = 0,
TE = 0.8, TF = 1, TR = 0
AC2A
0.234 s
VRMAX = 105, VRMIN = −95, SEMAX = 0.04,
SE0.75 = 0.01, E FD = 4.4, VAMAX = 8,
VAMIN = −8, KA = 400, KB = 25,
KC = 0.28, KD = 0.35, KE = −1,
KF = 0.03, KH =1, KL = 1, TA = 0.01,
TB = TC = 0, TE = 0.6, TF = 1, TR = 0,
VOEL = 11 (SE MAX and SE 0.75 = the
value of excitation fuction at EFDMAX
and EFD0.75 to simulate saturation)
DC3A
0.220 s
VRMAX = 1, VRMIN = 0, SEMAX = 0.28,
SE0.75 = 0.07, EFD = 3.03, KE = 0.05,
KV = 0.05, TE = 0.5, TR = 0,
TRH = 20
ST1A
0.205 s
VRMAX = 4.6, VRMIN = 0, VMAX = 2.4,
VMIN = −2.4, KA = 52, KC = 0.05,
KF = 0.114, TA = 0.01, TB = 0.92,
TC1 = 0, TB1 = 0 TC = 0, TF = 0,
TR = 0
*Three-phase fault on Bus 4 (Fig. 13-24).
†
Control circuit diagrams: AC2A, Fig. 13-22; ST1A, Fig. 13-20. For control
circuit diagrams of AC1A and DC3A, see Ref. 2.
F I G U R E 1 3 - 2 5 A power system single-line diagram for study of
stability of generator G1 (5.0 MVA) and G2 (3.125 MVA).
EXCITATION SYSTEMS AND POWER SYSTEM STABILIZERS
data, generator, turbine, and exciter models are not shown. The
following relaying data is applicable:
■
Eighty percent of 44-kV line is protected, in first zone of
distance protection, where utility breaker interrupting time is
three cycles, relaying time is one cycle, and fault is cleared in
four cycles.
■
The second zone of distance protection extends to remaining 20 percent of line; partly looking into primary windings of
transformers T1, T2, and T3, fault clearance time is 18 cycles,
including interrupting time of breaker, second zone distance
timer, and relay operating time.
■ Breakers A and B of 4.16 kV have reverse current protection
(device 67) to isolate generators from the utility source when
reverse flow of current is fed into the utility system on a fault—
these are proven to be too slow to affect separation before
pullout conditions.
FIGURE 13-26
351
The analysis shows that stability cannot be achieved by any means
for three-phase faults in the utility—fast load shedding (practical limit
is set by breaker interrupting time, fault sensing, and some operational delay, say minimum of five cycles), replacement with modern
fast excitation systems, and fast intertripping in about four cycles,
that is, simultaneous fault clearance. After three-phase faults, in order
of decreasing severity, the fault types are: (1) double line-to-ground
fault, (2) phase-to-phase fault, (3) single line-to-ground fault.
Figure 13-26a and b depict the behavior of voltage and frequency, respectively, for a phase-to-phase fault on the generator
bus. These transients are plotted on the basis that phase-to-phase
fault is cleared in the first zone and second zone of distance protection. Generation is separated in 18 cycles maximum time from the
instance of fault occurrence, and simultaneously 15.65 khp of loads
are shed, leaving 5 khp essential loads (Fig. 13-25).
Note that for a fault cleared in 18 cycles in the second zone of distance protection, the frequency does not dip below 59.40 Hz, while
for a fault cleared in 4 cycles it dips to 55.75 Hz. The voltage behaves
opposite to frequency; it dips by 34 percent for the fault cleared in
(a) Voltage and (b) frequency transients.
352
CHAPTER THIRTEEN
FIGURE 13-27
(a) Active and reactive power and (b) field current and voltage transients.
four cycles and dips by 55 percent for a fault cleared in 18 cycles. This
provides the appropriate settings on voltage and frequency relays:
■
An underfrequency relay is set at 59 Hz and time delay
of two cycles.
■ An instantaneous three-phase undervoltage relay is set
at 0.6-pu voltage in conjunction with timer with a delay of
four cycles.
These time delays are purposeful, in order to ride through fast
system transients. Figure 13-27a and b illustrate active and reactive
power transients and field current and voltage transients, respectively. Fig. 13-28a and b show transients in the equivalent 5-khp
motor load that is retained in service.
This example illustrates that it is not always practical to design
for and achieve stability for the worst fault type. The underfrequency
and undervoltage load shedding schemes should be considered in
combination. Some other strategies of enhancement of stability, such
as speed of relaying or intertripping, may not always be feasible.
13-9
POWER SYSTEM STABILIZERS
PSS acts through the automatic voltage regulator of an excitation
system and provides positive damping to generator rotor angle
swings. These swings are in broad range of frequencies:
■
Intertie mode. 0.1 to 1.0 Hz
■
Local mode. 1 to 2 Hz
■
Interplant mode. 2 to 3 Hz
Typically, a PSS tuning study is performed to optimize damping for
a broad range of frequencies.
EXCITATION SYSTEMS AND POWER SYSTEM STABILIZERS
FIGURE 13-28
Transients in the 5-khp motor load retained in service.
Historically, the measurements of rotor speed, bus frequency,
and electrical power signals have been used as input signals. Some
considerations are gain, phase compensation, susceptibility to
other interactions, and noise in the transducers. Consider a generator under so-called PV control. The voltage regulator adjusts the
generator excitation in response to the terminal voltage. A decrease
in generator terminal voltage results in a boost of the excitation and
more reactive power is produced in the system to control the voltage, and, conversely, for a rise in the voltage, a generator may act
even as a reactor to absorb reactive power from the system. While
this is the most common mode of operation, the generators are
sometimes operated under constant reactive power mode also.
The reactance of generator field windings delays rapid build up
of generator terminal voltage. The swing equation can be modified
to show changes in the machine flux D Eq′ :
2H d 2δ K D dδ
+
+ K1 D δ + K 2 D Eq′ = 0
ω dt 2 ω dt
353
(13-34)
The term K 2 D Eq′ is mainly determined by the changes in the excitation level. Consider the phasor diagram of Fig. 13-29. The vertical
axis represents the synchronizing axis. The components of restoring power along this axis, in the positive direction, tend to increase
the frequency of dynamic oscillations. The x axis is the damping
axis. Components of restoring power which are in phase with the
machine speed or frequency provide damping to these oscillations. Components which are out of phase with machine speed and
frequency and lie in the first quadrant tend to cancel the natural
damping. In Fig. 13-29, the dynamic oscillations will be damped,
as the resultant forcing action for oscillations points to left of vertical axis. The angle D δ lags the speed deviation by Dw = 90° and the
terminal voltage deviation DV by 180°. Figure 13-29 is for excitation system under manual control.
Under automatic voltage regulator control, the generator terminal voltage deviation DV creates the error signal De, which
initiates the control action to correct the terminal voltage with
certain time constants. If the machine is connected to a weak
transmission system, the phase lags between the error signal and
354
CHAPTER THIRTEEN
Thus, the field flux variations produce a negative synchronizing
torque component if:
K1 ≤ K 2 K 3 K 4
(13-38)
The system becomes monotonically unstable.
13-9-1
PSS and Oscillatory Stability
It seems pertinent, therefore, that a supplementary signal can be
provided which can increase damping by sensing some measurable quantity. Not only the undamping effect of voltage regulator is
cancelled, but the steady-state stability can also be enhanced. The
supplementary signals are changes in the shaft speed, frequency,
and electrical power: ( D ω , D f , D Pe ).
Consider the Eq. (13-35); at higher oscillating frequencies, the
last term becomes:
FIGURE 13-29
Phasor relationships of signals and torque compo-
nents, fixed excitation.
D Te = −
generator flux may result in a forcing action which points in the
negative region, giving rise to undamped oscillations; these may
grow in magnitude.
A fast response excitation system and a high effective gain will
act to magnify the negative damping contribution. This results in
oscillatory instability. When the power angle is above 70°, between
the generator internal voltage and infinite bus voltage, the unit
tends to have local mode stability problems under voltage control.
In Chap. 10, we have derived a generator model on infinite bus
with constants K1, K2, K3, K4, K5, and K6. See Fig. 10-22. We
showed that:
D Te = K1 D δ + K 2 D Eq′
D Eq′ =
(13-35)
K3
( D EFD − K 4 D δ )
1 + sT3
where T3 is written in place of T′dO k3. Combining these two
equations:
D Te = K1 D δ +
KKK
K 3K 2
D EFD − 2 3 4 D δ
1 + sT3
1 + sT3
(13-36)
The last term is variation in Eq′ , transients caused by electromagnetic
torque due to power angle variation. At steady state, or low oscillating frequency, and for ω < T13 :
D Te ≈ K1 D δ − K 2 K 3K 4 D δ
(13-37)
FIGURE 13-30
K 2 K 3K 4
KKK
D δ = 2 3 4 ( jD δ )
1 + sT3
ωT3
(13-39)
The air-gap torque deviations caused by Eq′ lead power angle deviation by 90° and thus are in phase with speed variations, Dωr. The
field winding flux linkage variation produces a positive damping
torque component.
A block circuit diagram of PSS is shown in Fig. 13-30. The
transducer converts the sensing signal into a voltage signal. This
output is phase shifted by an adjustable lead-lag network, which
compensates the time delays in generator field and excitation system. The resulting signal is amplified and sent through a washout
module which continuously balances the PSS output and prevents
it from biasing the generator voltage for prolonged frequency or
power excursions. The signal limiter causes the output signal to
limit on-load rejection and retain beneficial effect of forcing during
disturbances.
Figure 13-31 shows a typical phase relationship. The change
D ω is phase shifted by φ1 in the lead-lag network. This is the PSS
output signal which is applied to the voltage regulator. The time
delays in the generator and excitation result in a forcing function
which has a large damping component. By increasing PSS amplifier
gain, this forcing action can be increased subject to the limiting
action of the signal limiter.
13-9-2
IEEE-Type PSS1A Model
This model is shown in Fig. 13-32 and has a single input (VS1),
power frequency or speed. T6 may be used to represent a transducer time constant; stabilizer gain is set by KS, and signal washout by T5. Next, A1 and A2 allow some of the low-frequency effects
of high-frequency torsional filters, used in some stabilizers, to be
accounted for. This block can also be used for shaping the gain
and characteristics of the stabilizer. The next two blocks allow for
Major elements of a power system stabilizer.
EXCITATION SYSTEMS AND POWER SYSTEM STABILIZERS
355
The parameters used for these two types vary considerably.
For each input, two washouts can be represented: TW1 and TW4,
along with transducer or integrator time constant: T6, T7. For
the first type of stabilizer, K S3 will normally =1, and K2 will be
T7/2H, where H is the inertia constant. Input VS11 would normally represent speed or frequency, and VS12 would be a power
signal. The indices N (an integer up to 4) and M (an integer up
to 2) allow a ramp-tracking or simpler filter characteristics to be
represented. Phase compensation is provided by two lag-lead or
lead-lag blocks T1 and T4.
13-10
TUNING A PSS
This has been a subject of much research over the past 20 years.6,7–10
The following is a brief description:
FIGURE 13-31
Phasor relationships of signals, generator undervoltage regulator control with PSS.
lead-lag compensation, as set by T1 to T4. Stabilizer output can be
limited in many ways, and the model shows simple output limits:
VSTMAX and VSTMIN.
13-9-3
IEEE-Type PSS2A Model
The block diagram is shown in Fig. 13-33. The design represents
stabilizers with dual inputs, and in particular the model can be
used for:
1. Stabilizers, which in the frequency range of system oscillations,
act as electrical power input stabilizers. These use the speed or
frequency input for generation of an equivalent mechanical signal,
to make the total signal insensitive to mechanical power change.
2. Stabilizers that use a combination of speed (or frequency)
and electrical power. These systems usually use the speed
directly, without phase-lead compensation and add a signal
proportional to the electrical power.
FIGURE 13-32
Phase compensation method. The stabilizer is adjusted for
phase lags through the generator and excitation system, so
that the torque changes are in phase with the speed changes.
This is the simplest approach.
Root locus method. This involves shifting the eigenvalues
associated with the power system mode of oscillation by
adjusting the poles and zeros in the s plane. The approach
works directly with the closed-loop characteristics of the
system as opposed to open-loop nature of the phase compensation method.
State-space approach. It is a powerful mathematical tool. A
gain matrix of the multiple variable control system can be
calculated and an objective function, such as integral of the
squared error over time, can be minimized.
Basic concepts. To provide damping, the PSS must produce a
component of electrical torque on the rotor which is in phase
with speed variations. In other words, the transfer function of
PSS must compensate for the gain and phase characteristics
of the exciter, generator, and the power system.
Figure 13-34, which shows a linearized small signal model of
a single machine, is from a paper by Concordia and deMello.11
(This is a slight modification of Fig. 10-22). This figure shows an
Single-input power system stabilizer PSS1A.
356
CHAPTER THIRTEEN
FIGURE 13-33
FIGURE 13-34
Dual-input power system stabilizer PSS2A.
Small signal model of a generator with PSS and AVR inputs.
EXCITATION SYSTEMS AND POWER SYSTEM STABILIZERS
357
integral of accelerating power type PSS, which is synthesized from
measurements of speed and electrical power:
1
1
dω
=
(TM − TE ) =
(T )
2H ACC
dt 2H
(13-40)
We can divide the control circuit into two parts. The upper part
shows the relation between the accelerating torque and speed and
angle deviations. D is the damping associated with dampers, amortisseurs, and system loads. K1 is inherent synchronizing coefficient.
The lower part of the figure is a representation of the generator flux
dynamics, T′do, K3, AVR, and PSS. Ignoring PSS for a moment, the
lower part involving flux dynamics and AVR forms a loop, which
can be thought to be in parallel with K1 and D. This loop has a
component which is in phase with damping D and also K1 and it
adds or subtracts from these terms. An uncompensated system can
be considered with switch Y open, and for changes in speed, D ω ,
the changes in electrical torque are considered. If changes in torque
are in phase with speed, we have a pure damping term D. In practice, a detailed model for transient stability study is used to calculate frequency response.
Figure 13-35 shows the frequency and gain plots of the uncompensated system, shown in solid lines. This can be divided into two
components. The first term is from AVR input to electrical torque,
D TE / D EREF , and the second part is transfer function from speed
to PSS input signal, D∫ PACC / D ω . We see that the major component
in the phase lag is the AVR loop. The PSS input does not alter the
phase lag curve significantly.
The objective is choosing the phase compensation and leadlag functions so that the total compensated phase between speed
and torque is zero or slightly lagging. We concentrate on frequency
range of interest where power system oscillations exist, that is, are
between 0.1 and 3.0 Hz. This is shown in Fig. 13-36.
The PSS gain settings can be done using root-locus method.
The closed-loop poles will migrate from open-loop system poles to
open-loop system zeros as the gain is increased from zero to infinity
(Chap. 3). This means that instability will develop at some value of
the gain. Thus, an optimum condition can be defined as the one at
FIGURE 13-36
Phase angle plot of a compensated system.
which the damping is the maximum. A sequence of eigenvalues,
roots of the closed-loop system including PSS, are plotted on s plane.
The root-loci vary with:
■
External reactance. The local mode frequency is higher for
the strong system and lower for the weak system.
■
AVR settings KA and KF. For large values of regulator KA,
the eigenvalues will be toward the right of the j-ω axis and
will move toward the left as feedback gain is increased.
■
Excite mode. As the local mode damping is increased,
sometimes another mode called excite mode is brought
into play, which decreases the damping. If PSS gain is
increased, and it crosses over to the right half plane, instability will occur.
■
Torsional oscillations. The high frequency gain can affect the
turbine-generator torsional oscillations.
Example 13-5
The example considers the application of a PSS
to a small signal oscillation problem. Consider a generator of 235.3
MVA, 18 kV, with data as shown in Table 13-3. The generator is
connected through a step-up transformer of 200 MVA, 18 to 230
kV, and system configuration as shown in Fig. 13-37. It supplies a
load of 100 MVA at 0.85 power factor from 230-kV Bus 1, and the
rest of the load is supplied into the utility system through a system
impedance Xe = 40 percent. Bus 2 of 230 kV is created halfway
TA B L E 1 3 - 3
DESCRIPTION
G1
System Data for Example 13-5
DATA
235.3 MVA, 2 pole, 18 kV, 60 Hz, 0.85 PF,
HR grounded through a distribution transformer,
ground fault current limited to 10 A.
X″d = 15, X2 = 12, X0 = 12, ra = 0.15, r2 = r0 = 0.12,
Xd = 211, Xq = 201, X′d = 23, X ′q = 46, Xl = 13,
X ″q =12, T ′do = 6.8, T″do = 0.04 s, T ″qo = 0.08,
T′qo = 0.59, H = 5, damping = 5%. All reactances
on generator MVA base.
F I G U R E 1 3 - 3 5 Bode plot of tuning of a PSS for small angle stability
and phase and gain plots of an uncompensated system.
PSS1A
VSI = speed, KS = 3.15, VSTMAX = 0.9, VSTMin = −0.9,
A1 = A2 = 0, T1 = 0.76, T2 = 0.1, T3 = 0.76, T4 = 0.1,
T5 = 1, T6 = 0.1
Exciter
AC2A, data as in Table 13-2
358
CHAPTER THIRTEEN
FIGURE 13-37
A 235.3-MVA generator connected to an infinite bus through a reactance and supplying load.
between the supply system impedance of 40 percent to plot the
nature of transients.
Large utility generators are connected through a step-up transformer, and the system impedance Xe partly represents the impedance of the step-up transformer and partly the utility high-voltage
system source impedance.
First, consider that the generator is provided with IEEE
exciter type AC2A, and no PSS. Breaker 52 in Fig. 13-34 is suddenly opened to remove the load. The resulting transients are
shown in Fig. 13-38a and b. The terminal current, generatorrelative power angle, exciter current, and Bus 1 and Bus 2 voltages
decay slowly. For example, even after 10 s, the current has
decayed to only 13 percent of its original value and so also the
other transients.
Next, apply PSS parameters as shown in Table 13-3. This is
IEEE-type PSS1A, control circuit diagram as shown in Fig. 13-32.
The transients are replotted with PSS in service (Fig. 13-39a and b),
and this shows that transients practically vanish within 3 s.
13-11
MODELS OF PRIME MOVERS
In the above discussions, we referred to models of prime movers
and speed governors. Example 12-7 uses a simple steam turbine
model. A steam turbine during start-up can initially pick up about
10 percent of its rated output quickly, and then the load can only
be increased slowly, approximately at the rate of 2 to 3 percent
per minute. The thermal shock to the turbine is the limiting factor.
Same is true about a boiler. An increase in steam flow demanded by
the turbine results in pressure drop, and an increase in fuel to the
boiler is required to restore pressure. The speed-governing systems
have a response time delay of 3 to 5 s. The response of hydraulic
turbines will be even slower.
Therefore, the models of prime movers and speed-governing
systems may not be required for large rotor angle study, period of
study couple of seconds, but these are required for small signal
stability and long-term dynamic studies for operational procedures.
In some studies which involve the loss of generation or load, the
response of prime movers has been demonstrated to have an important effect on tie-line loading.
The prime mover models,12–16 depending upon the prime
mover (steam, gas, or hydraulic turbines or diesel engines), are
even more varied than the excitation system models. Manufacturers put forward control circuit models specific to their product. The models vary, for example, single reheat or double reheat,
simple or compound steam turbine, number of turbine sections
in tandem, that is, high pressure (HP), intermediate pressure
(IP), and low pressure (LP), time constants of crossover piping,
and inlet volumes. In addition, models of surge tanks and boilers are also incorporated in the studies. Figure 13-40 shows a
compound double reheat steam turbine model, with some typical
time constants.
13-12
AUTOMATIC GENERATION CONTROL
The objective of automatic generation control (AGC) is to regulate frequency to the nominal value and to maintain interchange
of power between the control areas by adjusting the output of the
selected generators. This control is commonly referred to as load
frequency control (LFC). Associated with this is the unit commitment and economical dispatch of power, discussed in many power
system texts.16–18
The frequency in the power systems is closely regulated and
does not vary much. Based solely on the frequency alone, a utility
company may island a cogeneration facility if the frequency falls,
say, below 59.5 Hz for about 12 cycles. This varies, and the numbers
are provided only as a typical example.
The composite power frequency characteristics of a power system depend upon the combined effects of the droop characteristics of speed governors (which allow the units to share the load
demand). The steady-state frequency deviation following a load
change may be written as:
D f ss =
− D PL
− D PL
=
(1 / R1 + 1 / R 2 ) + ( D1 + D2 ) 1 / R eq + D
(13-41)
where D is the load damping, and Req is defined as the ratio (in
percent) of the percentage speed or frequency change and percent
power output change, that is, R = D f / D P. The characteristics of a
composite load may be defined as:
D Pe = D PL + DD ω r
(13-42)
where DPL is the nonfrequency-sensitive load change, DD ω r is the
frequency-sensitive load change, and D is the load damping factor.
From Eq. (13-41), the frequency response characteristics are:
β=
− D PL
1
=
+D
D f ss
R eq
(13-43)
b is expressed in megawatts per hertz and is a measure of the stiffness
of the system. Consider two interconnected areas. The change of load
in Area 1, results in frequency reduction in both the areas and a tie line
flow of power between Areas 1 and 2. This flow is due to the regulation
characteristics of the areas. For change in Area 1 load, we write:
D P12 =
D PL1β2
β1 + β2
Df =
− D PL1
β1 + β2
(13-44)
Similarly, a change in Area 2 is negative of the change in load in
Area 1:
D P12 = − D P21 =
D PL 2 β2
β1 + β2
Df =
− D PL 2
β1 + β2
(13-45)
EXCITATION SYSTEMS AND POWER SYSTEM STABILIZERS
359
F I G U R E 1 3 - 3 8 (a) Generator terminal current, relative power angle (deg.) and exciter current (pu). (b) Bus 1 and Bus 2 voltages. Sudden disconnection
of 100-MVA load in Fig. 13-37. No PSS is provided.
360
CHAPTER THIRTEEN
FIGURE 13-39
Fast decay of generator and bus transients in Fig. 13-38, with PSSIA, data as in Table 13-3.
EXCITATION SYSTEMS AND POWER SYSTEM STABILIZERS
FIGURE 13-40
Control circuit diagram of a compound double reheat steam turbine.
From a control strategy point of view, the above situation is not
desirable. We should control each area so that the controls correct
for changes in that area only. This can be done by adding a control
component of tie-line load flow deviation to frequency deviation,
weighted by a bias factor. This control signal is called area control
error (ACE). For an area we can write:
ACE1 = A1 D P12 + β1 D f = 0
(13-46)
For a change in frequency due to load change in Area 1, the following expression holds:
− D PL1
DfR =
β1 + β2
361
13-12-1
Underfrequency Load Shedding
When the areas are islanded, to prevent prolonged operation on
underfrequency, which may have a detrimental effect on the turbines (Chap. 16), underfrequency load shedding is resorted to. The
two parameters that determine the rate of frequency decay are:
■
Frequency-sensitive characteristics of the loads
■
Inertia constant H
The frequency decay is given by:
D f = − D L(1 − e − t / T ) (1 / D )
(13-47)
Equation (13-46) will give ACE2 = 0 for Area 2, which signifies, that
load change in Area 1 does not impact the supplementary control
in Area 2.
When more than two areas are interconnected, the power flows
could split over parallel paths, and are not necessarily confined to tie
lines. Under an abnormal condition, it may happen that the generation-load mismatch is not corrected in all the areas, say due to insufficient generation. The other areas may take over and power transfers
above the scheduled values may occur, and frequency may deviate.
The controls are limited by the amount of stored energy in the generating units and how fast the generation can be changed.17–19
A factor that needs to be considered is the dead band of the
speed governor. IEEE standards specify a maximum dead band of
0.06 percent (0.036 Hz) for governors of large steam turbines,17 and
maximum speed dead band of 0.02 percent and maximum blade
control dead band of 1.0 percent for hydraulic turbines.18 If the frequency deviation is small, it may remain in the dead band, though
the response of individual generating units will be random.
(13-48)
where D is the load damping constant and T = 2H/D.
The procedural details for frequency load shedding are described
in Ref. 20. The load may be shed based upon frequency alone, or
for larger imbalances, it is shed in increments as the rate of frequency decay increases.
13-13
ON-LINE SECURITY ASSESSMENTS
Power system security refers to the capability of the system to
withstand sudden disturbances, faults, loss of generation, tie lines,
transformers, and other power equipment. Due to the very nature
of power systems, the time frame of change varies from very short
intervals (under fault conditions) to even days (unit outage, load
management forecast, and dispatch).
We talk of online static and dynamic contingency security assessments (SSA and DSA), though these are somewhat
related.21–24 In the static security assessments, a set of credible contingencies which are likely to occur are gathered and the system
response ascertained. The objective is to ensure that the system
operates in a secure state. Software packages of varying complexity
362
CHAPTER THIRTEEN
have been implemented in the energy management systems (EMS) to
meet this objective. However these operate on steady-state analysis.
In modern power systems, SSA is evidently not enough and DSA
must be integrated. DSA is concerned with power system stability as
system conditions and operations change due to contingencies. This
requires handling of a large set of nonlinear differential equations in
addition to the nonlinear algebraic equations involved in SSA. This
could be a stupendous task. Thus, potential contingencies which may
give rise to instabilities should be categorized, in a two-step process:
1. Screening to ascertain that the contingency is definitely
stable. A detailed assessment of these can then be performed.
Screening a large number of contingencies and filtering out the
ones that need further analysis is a fundamental step that makes
DSA feasible. Reliability, speed, efficiency, and online computation are some of the essential requirements for classifying. There
are two approaches: artificial intelligence (AI) approach and
energy function approach. AI techniques, like artificial neural
networks, pattern recognition, and decision tree techniques,
first perform off-line computations and try to capture the essential stability features of the system—this may not always be
applicable to online simulations. Sequences of BCU classifiers
for dynamic security assessment have been developed.
2. Contingencies which are undecided or identified as unstable are then sent to a time-domain stability program.
Thus, the architecture of DSA consists of state monitors, estimators, and powerful contingency screening to send the undecided or
unstable cases to online time-domain stability analysis. The outputs
will be corrective or preventive actions.
PROBLEMS
1. Draw the reactive capability curve of 200-MW generator
to scale, following the construction of Fig. 13-4. Consider
Xd = 200 percent (on machine MVA base), ceiling excitation
voltage = 255 percent, and the rated power factor of the
machine = 0.85.
2. The generator in Prob. 1 is connected to an infinite bus
through an impedance of 0.4 pu on 100-MVA base. Draw the
static stability limit curve.
3. Why do the manufactures today offer synchronous generators with lower SCR compared to their predecessors? Comment on SCR with respect to stability.
4. Figure 13-P1 shows the control circuit block diagram of
an excitation system, Type 1.4 Write state-space equations.
FIGURE 13-P1
5. A 200-MW, 0.85-power factor, 18-kV generator has:
Lad = Laq = Lfd = 1 . 56, ld = 0 . 12, rF = 0 . 0005, and r = 0 . 002,
all in pu on generator MVA base. The field current required to
generate rated voltage on air-gap line is 600 A, and the corresponding field voltage = 80 V. What are the base values for EFD
and iF in per unit nonreciprocal and reciprocal systems?
6. What is the kinetic energy stored by a 50-MW, 60-Hz,
two-pole generator with H = 4 kW/kVA? If the generator
electrical load suddenly changes to 20 MW, will the rotor
accelerate or decelerate? What will be the generator speed
after 10 cycles?
7. In an existing system consisting of a generator, step-up
transformer, and given load, what measures will be the most
practical to implement to enhance stability?
8. Define a high-response excitation system according to
IEEE. Describe why high-response excitation system can give
rise to negative damping and contribute to instability?
9. Explain why it is necessary to use undervoltage settings
along with underfrequency settings for effective load shedding
for enhancing stability.
10. Study two control circuit block diagrams of steam turbines,
and write a one-page explanation of each circuit. Define reheat
time constant and time constant of a steam vessel.
REFERENCES
1. P. M. Anderson and A. A. Fouad, Power System Control and Stability, IEEE Press, NJ, 1994.
2. IEEE Std. 421.5, IEEE Recommended Practice for Excitation
System Models for Power System Stability Studies, 1992.
3. IEEE Std. 421.2, IEEE Guide for Identification, Testing, and
Evaluation of Dynamic Performance of Excitation Control
Systems, 1990.
4. IEEE Committee Report, “Computer Representation of
Excitation System,” IEEE Trans. PAS, vol. 87, pp. 1460–1464,
June 1968.
5. J. C. Das, “Transient Stability of Small Generators Connected
to a Weak Utility System, A Case Study,” IEEE Trans. Industry
Applications, vol. 41, no. 1, pp 155–162, Jan./Feb. 2005.
6. K. E. Bollinger, A. Laha, R. Hamilton, and T. Harras, “Power
System Stabilizer Design Using Root Locus Methods,” IEEE
Trans. PAS, vol.-94, pp. 1484–1488, Sept./Oct. 1975.
Excitation system Type 1.
EXCITATION SYSTEMS AND POWER SYSTEM STABILIZERS
363
7. E. V. Larsen and D. A. Swann, “Applying Power System Stabilizers, Part 1: General Concepts,” Paper 80, SM 558-7, in Conference Record, IEEE PES Summer Meeting, Minneapolis, July 1980.
20. H. E. Lokay and V. Burtnyk, “Application of Underfrequency
Relays for Automatic Load Shedding,” IEEE Trans., vol. PAS-87,
pp. 776–783, March 1968.
8. Ibid, “Part II: Performance Objectives and Tuning Concepts,”
Paper 80, SM 559-5.
9. Ibid, “Part III: Practical Considerations,” Paper 80, SM, 560-3.
21. D. H. Berry, R. D. Brown, J. J. Redmond, and W. Watson,
“Underfrequency Protection of Ontario Hydro System,” CIGRE
paper 32-14, Aug./Sept. 1970.
10. F. P. DeMello, J. S. Czuba, P. A. Rusche, and J.Wills, “Developments in Application of Stabilizing Measures Through Excitation Control,” CIGRE Paper 38–05, 1986.
22. S. C. Savulescu, Real-Time Stability Assessment in Modern Power
System Control Centers, IEEE Press, Series on Power Engineering, NJ, February 2009.
11. F. P. De Mello and C. Concordia, “Concepts of Synchronous
Machine Stability as Affected by Excitation Control,” IEEE
Trans.PAS, vol. 88, pp. 316–329, April 1969.
23. B. Scott, O. Alsac, and A. J. Monticelli, “Security Analysis and Optimization,” Proc. IEEE, vol. 75, no. 12, pp. 1623–1644, 1987.
12. IEEE Committee Report, “Dynamic Models of Steam and Hydro
Turbines in Power System Studies,” IEEE Trans., vol. PAS-92,
pp. 1904–1951, Nov./Dec. 1973.
13. IEEE Working Group Report, “Hydraulic Turbine and Turbine
Control Models for System Dynamic Studies,” IEEE Trans., vol.
PWRS-7, no. 1, pp. 167–179, Feb. 1992.
14. IEEE Working Group Report, “Dynamic Models for Fossil
Fueled Steam Units in Power System Studies,” IEEE Trans., vol.
PWRS-6, no. 2, pp. 753–761, May 1991.
15. P. L. Dandeno, P. Kundur, and J. P. Bayne, “Hydraulic Unit
Dynamic Performance Under Normal and Island Conditions—
Analysis and Validation,” IEEE Trans., vol. PAS-97, pp. 2134–2143,
Nov./Dec. 1978.
16. EPRI Report EL-6627, Long Term Dynamic Simulation:
Modeling Requirements, Dec. 1989.
17. IEEE Standard 122, Recommended Practice for Functional
and Performance Characteristics of Control Systems for Steam
Turbine-Generator Units, 2003.
18. IEEE Standard 125, Recommended Practice for Preparation of
Equipment Specifications for Speed Governing for Hydraulic
Turbines Intended to Drive Electrical Generators, 2007.
19. IEEE AGC Task Force Report, “Understanding Automatic
Generation Control,” IEEE Trans., vol. PWRS-7, no. 3,
pp. 1106–1122, Aug. 1992.
24. Y. Mansour, E. Vaahedi, A. Y. Chang, B. R. Corns, B. W. Garrett, K.
Demaree, T. Athay, and K. Cheung, “BC Hydro’s on Line Transient
Stability Assessment (TSA) Model Development, Analysis, and
Post Processing,” IEEE Trans., vol. PS10, pp. 241–253, 1995.
FURTHER READING
ANSI/IEEE Std. 421.1, IEEE Standard Definitions of Excitation
Systems for Synchronous Machines, 1986.
W. T. Carson, Power System Voltage Stability, McGraw Hill, New
York, 1994.
H. D. Chiang and R. Jean-Jumeau, “Towards a Practical Performance Index for Predicting Voltage Collapse in Power Systems,”
IEEE Trans., vol. PS10, no. 2, pp. 584–592, 1995.
J. C. Das, Power System Relaying Wiley Encyclopedia of Electrical
and Electronic Engineers, vol. 17, pp. 71–86, 2002.
J. Deuse and M. Stubbe, “Dynamic Simulation of Voltage
Collapses,” IEEE Trans., vol. PS8, no. 3, pp. 894–900, 1993.
IEEE Tutorial Course, Power System Stabilization via Excitation
Control, 81-EHO 175-0 PWR, Sep. 1980.
P. Kundur, Power System Stability and Control, McGraw Hill, New
York, 1993.
J. A. Momoh, Electrical Power System Applications of Optimization,
Marcel Dekker, New, York, 2001.
Voltage Stability and Long Term Stability Working Group,
Bibliography on Voltage Stability, IEEE Trans. PS, vol. 13, no. 1,
pp. 115–125, 1998.
This page intentionally left blank
CHAPTER 14
TRANSIENT BEHAVIOR
OF TRANSFORMERS
Transients in the transformers originate due to saturation, switching
and lightning, high-flux densities, energy storage between inductance and capacitance of the windings, part-winding resonances,
and winding connections.
A power transformer is an important component of the power
system. The transformation of voltages is carried out right from generating voltage to transmission, subtransmission, and distribution,
and also consumer level. The installed capacity of the transformers in a power system may be seven to eight times the generating
capacity. The special class of transformers includes furnace, converter,
regulating, rectifier, phase shifting, traction, welding, and instrument (current and potential transformers). Saturation of current
transformers is important for relaying applications, which is not
discussed here.
14-1
FREQUENCY-DEPENDENT MODELS
Transformer models for transients must consider nonlinearity and
frequency-dependent behavior. Table 14-1 from CIGRE modeling
guidelines1 shows the importance of modeling of various parameters. Further, the modeling and ascertaining of the test results for
modeling are also dependent upon the transformer winding connections and core construction. Ascertaining the modeling parameters for a particular model based on the nameplate details is not
adequate and special tests may be required.2
The concept of leakage flux, and total flux, mutual and self reactances in a circuit of two magnetically coupled coils is described in
Chap. 10, and a matrix model can be written as:
V1 r11 r12
V2 r21 r22
=
.
.
.
Vn rn1 rn 2
. r1n
. r2 n
. .
. rnn
i1
i2
.
in
+
L11
L21
.
L n1
i1
L12 . L1n
L22 . L2 n d i2
. . . dt .
in
L n 2 . L nn
(14-1)
I = YV
(14-2)
where R, and ω L are real and imaginary parts of the impedance
matrix. In case of low magnetization currents, the transformer
(14-3)
For transient simulation, this expression becomes:
[d i /dt] = L−1V + L−1R i
(14-4)
These models are linear, neglect saturation, and have limited application with respect to transients.
14-2 MODEL OF A TWO-WINDING
TRANSFORMER
A two-winding transformer model can be derived from the circuit
diagram shown in Fig. 14-1 and the corresponding phasor diagram
shown in Fig. 14-2. The transformer supplies a load current I2 at a
terminal voltage V2 and lagging power factor angle φ2 . Exciting the
primary winding with voltage V1 produces changing flux linkages.
Though, the coils in a transformer are tightly coupled by interleaving the windings and are wound on a magnetic material of high
permeability, all the flux produced by primary windings does not
link the secondary. The winding leakage flux gives rise to leakage
reactance. In Fig. 14-2, Φ m is the main or mutual flux, assumed
constant. The EMF induced in the primary winding is E1, which
lags Φ m by 90°. In the secondary winding, the ideal transformer
produces an EMF E2 due to mutual flux linkages. There has to be
a primary magnetizing current, even at no load, in time phase with
its associated flux to excite the core. The pulsation of flux in the
core produces losses. Considering that the no-load current is sinusoidal, which is not true under magnetic saturation, it must have a
core loss component due to hysteresis and eddy currents:
I 0 = I m2 + I e2
For transient calculations, we can write:
V = R i + L[d i /dt]
should be described by an admittance matrix:
(14-5)
where Im is the magnetizing current, Ie is the core loss component
of the current, and I0 is the no-load current. Im and Ie are in phase
quadrature. The generated EMF because of flux Φ m is given by:
E2 = 4 . 44 fn2 Φ m
(14-6)
365
366
CHAPTER FOURTEEN
TA B L E 1 4 - 1
GROUP 1
0.1 HZ TO ò3 KHZ
TRANSFORMER
Modeling Guidelines for Transformers*
GROUP 2
60 HZ TO ò3 KHZ
GROUP 3
10 KHZ TO ò3MHZ
GROUP 4
100 KHZ TO ò50 MHZ
Short-circuit impedance
Very important
Very important
Important only for surge transfer
Negligible
Saturation
Very important
See note below
Negligible
Negligible
Frequency-dependent series losses
Very important
Important
Negligible
Negligible
Hysteresis and iron losses
Important only for
resonance phenomena
Important only for
transformer energizing
Negligible
Negligible
Capacitance coupling
Negligible
Important for
surge transfer
Very important for
surge transfer
Very important
for surge transfer
Note: Very important for transformer energizing and load rejection with high-voltage increases, otherwise negligible.
*
These guidelines are based on CIGRE recommendations.1
FIGURE 14-1
(a) Equivalent circuit of a two-winding transformer. (b), (c), and (d ) Simplifications to the equivalent circuit.
TRANSIENT BEHAVIOR OF TRANSFORMERS
367
Now the transformer is an ideal transformer with no losses and
has a turn’s ratio of unity and no secondary resistance or reactance.
By transferring the load impedance also to the primary side, the
unity ratio ideal transformer can be eliminated and the magnetizing
circuit is pulled out to the primary terminals without appreciable
error (Fig. 14-1b and c). In Fig.14-1d, the magnetizing and core
loss circuit is altogether omitted. The equivalent resistance and
reactance are:
R1 = r1 + n 2r2
(14-9)
X1 = x 1 + n 2 x 2
Thus, on a simplified basis, the transformer positive or negative
sequence model is given by its percentage reactance specified by
the manufacturer, generally, on the transformer natural cooled MVA
rating base. This reactance remains fairly constant and is obtained
by a short-circuit test on the transformer. The magnetizing circuit
components are obtained by an open-circuit test.
The expression for hysteresis loss is:
Ph = K h fBms
(14-10)
where Kh is a constant, and s is the Steinmetz exponent, which varies from 1.5 to 2.5, depending upon the transformer core material;
generally it is = 1.6. The eddy current loss is:
Pe = K e f 2 Bm2
FIGURE 14-2
Phasor diagram of a two-winding transformer.
where E2 is in volts when Φ m is in weber per square meter, n2 is
the number of secondary turns, and f is the frequency. As primary
ampere turns must be equal to the secondary ampere turns, that is,
E1 I1 = E2 I2 we can write:
E1 n1
=
=n
E2 n 2
and
(14-7)
I1 n2 1
≈
=
I 2 n1 n
where n1 is the number of primary turns and n is the transformation ratio. The current relation holds because the no-load current is
small. The terminal relations can now be derived. On the primary
side, the current is compounded to consider the no-load component
of the current, and the primary voltage is equal to −E1 (to neutralize
the EMF of induction) and I1r1 and I1x1 drop in the primary windings. On the secondary side, the terminal voltage is given by the
induced EMF E2 − I2r2, and I2x2 drops in the secondary windings.
The equivalent circuit is therefore as shown in Fig. 14-1a. The transformer is an ideal lossless transformer of turn ratio n.
The secondary resistance and reactance can be referred to the
primary side. The secondary windings of n2 turns can be replaced
with an equivalent winding referred to primary, where the copper
loss in the windings and the voltage drop in the reactance are the
same as in the actual winding. The resistance and reactance of the
equivalent windings are denoted as r′2 and x′2:
I12r2′ = I 22r2
where Ke is a constant. Eddy current loss occurs in core laminations, conductors, tank, and clamping plates. The core loss is the
sum of eddy current and hysteresis loss. In Fig. 14-2, the primary
power factor angle φ1 is > φ2 .
We discussed the sequence impedances of transformers in Chap. 9
(Figs. 9-4 and 9-5). We know that the transformer winding connections have a profound effect on the zero-sequence impedance which
can be an open circuit. A phase shift occurs between the primary and
secondary voltages of a three-phase transformer, depending upon the
winding connections, as discussed in Chap. 9.
The model thus derived is adequate for power frequency operation. For 60-Hz load flow and short-circuit calculations, the transformer is represented with equivalent impedance as derived above.
This model cannot be used for any transient studies. Note that no
capacitance between the windings or to the core and ground, no
saturation, and no core losses are considered. The transfer of power
takes place through inductive couplings and capacitances are
neglected. The tap adjustments can be taken care of by the equivalent P or T circuit, as discussed below.
14-3
EQUIVALENT CIRCUITS FOR TAP CHANGING
Figure 14-3a shows an ideal transformer, with a series impedance
as derived above. Then:
Vs = (Vr − ZI r )/n
VsI *s + (Vr − ZI r )I *r = 0
Then substituting Is /(−Ir) =n, Y =
2
I2
n
x 2′ = x 2 22 ≈ x 2 1 = n 2 x 2
n2
I1
(14-8)
(14-12)
As the power through the transformer is an invariant:
2
I2
n
r2′ = r2 22 ≈ r2 1 = n 2r2
n2
I1
(14-11)
I s = [n(n − 1)Y]Vs + nY (Vs − Vr )
I r = nY (Vr − Vs ) + [(1 − n )Y]Vr
(14-13)
1
Z
(14-14)
These equations give the equivalent circuits illustrated in Fig. 14-3b
and c for the equivalent T and P circuits.
368
CHAPTER FOURTEEN
FIGURE 14-3
14-4
(a) Circuit of an ideal tap-changing transformer. (b) and (c) Equivalent T and P circuits of a tap-changing transformer.
INRUSH CURRENT TRANSIENTS
For economy in design and manufacture, transformers are operated close to the knee point of saturation characteristics of magnetic
materials. Figure 14-4 shows the B-H curve and the magnetizing
current waveform. A sinusoidal flux wave required by sinusoidal
applied voltage demands a magnetizing current with a harmonic
content. Conversely, with sinusoidal magnetizing current, the
induced EMF is peaky and the flux is flat topped.
An explanation of the generation of the peaky magnetizing
current considering third harmonic is provided in Fig. 14-5. A
sinusoidal EMF Ea generates a sinusoidal current flow, Ia in lagging phase-quadrature with Ea. This sets up a flat topped flux wave,
φ1 —which can be resolved into two components, φa , the fundamental flux wave, and φ3, the third harmonic flux wave, (higher
harmonics are neglected). The third harmonic flux can be supposed
to produce a third harmonic EMF E3 and corresponding third harmonic current I3, which when summed up with Ia makes the total
current drawn peaky.
On energizing a power transformer, a large magnitude of inrush
current will flow, which can be resolved into harmonics including
a dc component. Figure 14-6 depicts three conditions of energizing a power transformer: (1) the switch closed at the peak value of
the voltage, (2) the switch closed at zero value of the voltage, and
(3) energizing with some residual trapped flux in the magnetic core
due to retentivity of the magnetic materials. These three situations are
depicted in Fig. 14-6a, b, and c, respectively. Figure 14-6d shows the
waveform of magnetizing inrush current, which resembles a rectified current. The peak value may reach 8 to15 times the transformer
full-load current, mainly depending upon the transformer size. The
asymmetrical loss due to conductor and core heating rapidly reduces
the flux wave to symmetry about the time axis, and typically, the
inrush currents last for a short duration of approximately 0.1 s.
The inrush current is rich in the second harmonic; also third,
fourth, and fifth harmonics are generated in addition to a dc bias.
Presence of power capacitors increases the transients and their
decay time. Differential relays used for protection of transformers
inhibit switching current harmonics to prevent operation of the
switching devices under inrush conditions.
14-5 TRANSIENT VOLTAGES IMPACTS
ON TRANSFORMERS
Transformers normally operate under steady-state excitation and
voltages are controlled to specific limits. The generated fundamental frequency EMF is given by:
V = 4 . 44 fTph Bm A c
(14-15)
TRANSIENT BEHAVIOR OF TRANSFORMERS
FIGURE 14-4
B-H curve of a magnetic material and peaky transformer magnetizing current.
where Tph is the number of turns in a phase, Bm is the flux density
(consisting of fundamental and higher-order harmonics), and Ac
is the area of core. Thus, the factor V/f is a measure of the overexcitation, though these currents do not normally cause a wave
distortion of any significance. Exciting currents increase rapidly
with voltage and ANSI/IEEE standard C57.12.00 requires that
transformers are capable of operating continuously at 10 percent
above rated secondary voltage at no load without exceeding limiting temperature rise.3 Under certain system upset conditions, the
transformers may be subjected to even higher voltages and overexcitation. An example is a transformer connected to a generator
in step-up configuration (GSU—generator step-up transformer).
Overexcitation of transformers in steady state can produce harmonics. Also consider that:
1. A total load rejection of a generator will subject the transformer to higher voltages and overexcitaion. The protection is
provided by V/f relays (device 24).
FIGURE 14-5
369
2. The transformers supplying nonsinusoidal loads have
increased eddy current, pulsation, and core losses and are derated according to ANSI/IEEE standard4 and UL Standard.5 This
is not discussed in this book.
3. Dynamic voltages to which the transformers may be subjected refer to low-frequency voltages 0 to 1500 Hz, which are
damped oscillatory voltages.
4. Excitation by switching and lightning surges and fault voltages may give rise to chopped voltage waveforms and higher
stresses.
5. The term “very fast transients” encompasses excitation with
voltages of rise time in the range of 50 to100 ns (Chaps. 1 and 18).
6. Transformers often have high internal winding ringing
frequencies. Certain switching operations can excite these frequencies so that voltage escalation occurs deep inside
Origin of a flat-topped flux wave in a transformer and peaky magnetization current.
370
CHAPTER FOURTEEN
7. Power systems, transformers, and circuit breakers can form
a dynamic system during switching operation, and on rare
occasions this may require action to mitigate transient frequencies produced during switching. Circuit breakers may impose
frequencies on transformers that may be resonant with or in
power system elements.
8. The surge voltages across the windings have unequal distribution and tend to concentrate on the first few turns.
9. A phenomenon of oscillating neutrals occurs in ungrounded
wye-wye connected transformers. In delta-connected windings, the impedance to third harmonics is negligible, and
a very small third harmonic EMF is required to circulate
the third harmonic current additive to the fundamental frequency. This maintains sinusoidal flux. In wye-wye connected
transformers with isolated neutrals, all the third harmonics
are either directed inward or outward; these cancel between
the lines, no third harmonic currents flow, and the flux wave
is flat topped. The effect on the ungrounded wye neutral is
to make it oscillate at three times the fundamental frequency,
giving rise to distortion of the phase voltages. Practically,
wye-wye ungrounded connection is not used. Even when the
windings are grounded, a tertiary delta winding is provided to
circulate the third harmonic currents. Sometimes this tertiary
winding can be designed to serve load at a different voltage.
The power frequency, lightning impulse, switching surge, and
chopped-wave test voltages according to ANSI/IEEE standards are
described in Chap. 17.
14-5-1
Electromagnetic Forces
In a power transformer, the vector sum of MMFs is zero at each
instant, neglecting the small amount required to magnetize the
core. Under short-circuit conditions, the force can be expressed by
the equation:
1
1
Ft = Fmax + e −2t / τ − 2e − t / τ cos ωt + cos 2ωt
2
2
(14-16)
The total force Ft consists of:
■
Two unidirectional components: one constant and the other
decreasing with time.
■
Two alternating components: one of fundamental frequency,
decreasing with time, and the other of double frequency with a
smaller but constant magnitude.
FIGURE 14-6
Inrush current transients: (a) switch closed at the
peak of the applied voltage, (b) switch closed at voltage zero crossing,
(c) with prior trapped magnetic flux in the core, and (d ) profile of transient
inrush current.
transformer windings, creating excessive intera-winding
stresses. Traditional surge arresters applied at transformer
terminals are ineffective in stopping this phenomena, and resistance and capacitance snubber circuits have been shown to be
effective. Also see Example 20-3.
It is necessary to calculate flux patterns to determine the forces.
Figure 14-7a and b illustrates flux and force patterns in core-type
and shell-type transformers, respectively. The forces are repulsive in
pairs of windings having MMFs in opposite directions, that is, carrying currents in opposite directions. In the concentric windings,
core-type transformers, forces act mostly in the radial direction.
There is no significant axial contribution over approximately twothirds of the total winding length. In the shell-type transformers,
forces act mostly perpendicularly to pancake coil surfaces. At the
end of the coils, where the magnetic field lines bend, forces exhibit
significant components that are axial in core-type transformers and
parallel to pancake surface in shell-type transformers.
The forces tend to move the windings apart due to opposing
MMFs. Figure 14-7c and d illustrates the short-circuit current and the
corresponding electromagnetic force transients, respectively. Shortcircuit stresses under through fault conditions can result in winding
failures. The transformer manufacturers in the United States should
meet the through-fault withstand capability of transformers specified
TRANSIENT BEHAVIOR OF TRANSFORMERS
FIGURE 14-7
371
(a) Magnetic flux and (b) force patterns in a core-type and shell-type transformer. (c) Transient short-circuit current and (d ) electromag-
netic force waveforms.
in ANSI/IEEE Standard C37.916 for liquid-immersed transformers and
the ANSI/IEEE “Guide for Dry-Type Transformers”7 for dry-type transformers. There are four categories, depending upon the transformer
kVA rating, as follows:
■
Category I. 5 to 500 kVA single phase and 15 to 500 kVA
three phase
■
Category II. 501 to 1667 kVA single phase and 501 to
5000 kVA three phase
■
Category III. 1668 to 10,000 kVA single phase and 5001 to
30,000 KVA three phase
■
Category IV. Above 10,000 kVA single phase and above
30,000 kVA three phase
Figure 14-8 shows the through-fault curves for Category III
transformers. Curve (a) is applicable for faults that will occur
frequently, typically more than five in transformer lifetime
(transformer connected to overhead systems), and curve (b)
is applicable for faults that will occur less frequently, typically
less than five in transformer lifetime. The transformers in the
industrial distribution systems are connected through cables.
The curves consider both thermal and mechanical damage.
Curve (b) shows that the transformer must withstand a maximum through-fault current of 25 times the rated base current
(full-load current based upon rated KVA), for 2 s. In curve (a),
the through-fault withstand for 2 s is a function of the transformer impedance as shown in Fig. 14-8. The distribution of
currents in the windings depends upon their connections. A
three-phase fault is considered. In some applications, for example, UAT (unit auxiliary transformers in generating stations)
higher through-fault withstand capability as compared to standard capability may be required.
14-6
MATRIX REPRESENTATIONS
The matrix representation of transformers can be written based
on short-circuit and excitation test data. Consider a single-phase
372
CHAPTER FOURTEEN
Through-fault withstand capability of Category III transformers, according to ANSI/IEEE standard.6 Curve (a) shows frequent faults and
curve (b) shows infrequent faults in the lifetime of the transformer.
FIGURE 14-8
two-winding transformer. If magnetizing reactance is not considered:
R=
R1
0
0
R2
and
ω L−1 =
1/ X − 1/ X
− 1/ X 1/ X
(14-17)
Equation (14-17) is written in pu. If the short-circuit impedance of
the transformer is 0.005 + j0.10 pu, then:
R=
0 . 0025
0
0
0 . 0025
ω L−1 =
10 − 10
− 10 10
(14-18)
Here R1 pu is assumed equal to R2 pu. This can be converted to
actual values.
The positive and negative sequence circuits of three-winding transformers are shown in Fig. 9-5. Consider a wye-grounded H, delta L, and
delta M connection. The positive sequence connection is a wye connection. The manufacturers specify short-circuit data, for example, as:
X HL = 0.117
X LM = 0.241
X HM = 0.115 pu
XH, XL, XM can be found from the following expressions:
1
X H = ( X HL + X HM − X LM )
2
1
X L = ( X LM + X HL − X HT )
2
1
X M = ( X HM + X LM − X HL )
2
(14-19)
Using these equations:
X H = − 000045
X L = 0 . 001215
X M = 0 . 001195
Convert these to delta equivalent.
D HL = 889 . 484
D HM = 904 . 371
DLM = − 33 . 495
We can write:
D HL + DHM
ω L = − DHL
− D HM
−1
− D HL
DHL + DLM
− DLM
− DHM
− DLM
D HM + DLM
17 . 9385 − 8 . 8948 − 9 . 0437
0 . 3349
= − 8 . 8948 8 . 5599
− 9 . 0437 0 . 3349
8 . 7088
(14-20)
In steady state, Eq. (14-1) can be written as:
V1 Z11
V2 Z21
=
.
.
Vn Z n1
Z12
Z22
.
Zn2
. Z1n I1
. Z2 n I 2
.
. . .
. Z nn I n
(14-21)
TRANSIENT BEHAVIOR OF TRANSFORMERS
As per matrix theory, if all coils are open circuited and coil k is energized, the measured values of Ik and Vi (V1, V2…Vn) give:
Zik = Vi /Ik
(14-22)
Continuing with Eq. (14-18), short-circuit impedance of 0.005 +
j0.10 pu can be divided into two equal parts, and then, the magnetizing impedance which is relatively high, say 99.0 pu, can be
connected in the middle. This gives a T circuit of the transformer.
Then, the input impedance = 99.5 pu, and the matrix equation in
the steady state is:
V1 0 . 0025
0
99 . 5 99 I1
=
+j
V2 0
0 . 0025
99 99 . 5 I 2
(14-23)
The difference between the elements is small, and it could lead
to ill-conditioned network, Z becoming infinity for zero exciting
current. This problem is solved by constructing Y-matrix.
I1
I2
.
In
=
Y11
Y21
Y12 .
Y22 .
.
.
Yn 2 .
.
Yn1
Y1n
Y2 n
(14-24)
.
Ynn
Then:
L−1 = jω Y
(14-25)
The Y matrix can be built as follows from reduced matrices, shortcircuit data. For transient analysis, R and X are separated.
n −1
Yin = Yni = −∑ Yik( reduced )
for i ≠ n
k =1
(14-26)
n −1
Ynn = −∑ Yin
i=1
This is the same matrix as in Eq. (14-20). For three-phase n-coil
transformers, we can write:
Zs
Zm
Zm
Zm
Zs
Zm
Zm
Zm
Zs
(14-30)
where Z s is the self-impedance of the coil on one leg, and Z m is its
mutual impedance to the coils on the other two legs. As in transmission lines:
1
(Z + 2Z+ )
3 0
1
Z m = ( Z0 − Z + )
3
Zs =
(14-31)
For transient analysis, the resistance and inductance parts are separated. This can be done from the short circuit test data. The winding resistance forms a diagonal matrix and L−1 = jω Y . The matrix Y
is built from reactance values jω L.
14-7
EXTENDED MODELS OF TRANSFORMERS
The transient behavior of transformers has been a subject of much
study and research over the last 100 years, and the literature is
rich on this subject. An exact representation may be very complex.
A transient transformer model should address saturation, hysteresis, eddy current, and stray losses. Saturation plays an important role in determining the transient behavior of the transformer.
Extended transformer models can be very involved, and these are
not required in every type of study (Table 14-1). The models in
Fig. 14-9 for each category in Table 14-1 are based upon CIGRE
guidelines with surge transfer.1 A model not suited to this type of
transient study may be prone to errors. For lightning and switching transients’ studies, it is necessary to include capacitance of the
transformers as high-frequency surges will be transferred more
through electrostatic couplings rather than the electromagnetic
couplings. There are many approaches to the models, some of
which are briefly discussed.
14-7-1 EMTP Model Satura
The equation is in pu. This can be illustrated by recalculating the
matrix arrived in Eq. (14-20):
X reduced = j
X HM
XM
XM
0 . 1150 0 . 1195
=j
X LM
0 . 1195 0 . 2 4 10
(14-27)
Find inverse:
Yreduced =
373
1 17 . 9385 − 8 . 89484
j − 8 . 8948
8 . 5599
(14-28)
Figure 14-10 shows a single-phase model. RMAG remains constant,
and it is calculated from excitation losses. The nonlinear inductor
is modeled from transformer excitation data and its nonlinear V-I
characteristics. The transformer’s core saturates sharply and there is
a definite knee point. Often a two-slope piece-wise linear inductor
is adequate to model such curves, though complete analytical functions for representation of saturable elements have been proposed.1
The saturation data is not supplied as a flux-current relation, but as
a rms-voltage and rms-current curve. The Satura routine in EMTP
converts this voltage-current relation to flux-current data. The
input data is presented in per unit values with regard to winding
connections and base current and voltage:
1/ 2
This gives:
−1
L
17 . 9385 − 8 . 89484 −(17 . 93856 − 8 . 8948) = − 9 . 0 4 372
= ω − 8 . 89484 8 . 55989 −( − 8 . 89484 + 8 . 55989) = 0 . 3 3 495
− 9 . 04372 0 . 33495 −( − 9 . 04372 + 0 . 33495) = 8 . 7 0 877
17 . 9385 − 8 . 89484 − 9 . 04372
= ω − 8 . 89484 8 . 559 8 9
0 . 33495
− 9 . 04372 0 . 33495
8 . 70877
(14-29)
2
I mag = I ex
− (Pex /Vex )2
Vex2
Rm =
2
Pex − RI ex
(14-32)
where R = ac resistance considered in excitation test, Pex = excitation
in watts, Iex = excitation current, Vex = excitation voltage, and Rm =
magnetizing resistance representative of core losses, considered constant. There is a linear interpolation between the assumed values and
finite-difference approximation to sinusoidal excitation. The hysteresis is ignored.
374
CHAPTER FOURTEEN
FIGURE 14-9
Transformer models based upon CIGRE.1 Figures (a), (b), (c), and (d ) for Group I, II, III, and IV transients, respectively.
Example 14-1 Consider a 50-kVA, 2400/240-volt, two-winding,
single-phase, 60-Hz transformer. Its saturation test data is given in
Table 14-2. The following relations apply:
Vbase = 240 V
S base = 50 kVA
I base = 208 . 33 A
Vmag =
Vex
Vbase
(14-33)
FIGURE 14-10
Using Eq. (14-33) the input data for Satura is shown in Table 14-3.
The calculated I-l data in EMTP subroutine, nonlinear inductor
is shown in Table 14-4 and Fig. 14-11. This is a two-slope curve
and is modeled as a sequence of points, with linear interpolation
between assumed values and finite-difference approximation to
sinusoidal excitation. This representation is considered adequate
except that for ferroresonance phenomena, a more detailed representation of the saturation characteristics may be required.
Single-phase transformer, EMTP model Satura.
TRANSIENT BEHAVIOR OF TRANSFORMERS
FIGURE 14-11
375
(a) Given RMS excitation data, voltage verses current. (b) Conversion of the excitation data into two-piece I-λ curve (saturation curve).
TA B L E 1 4 - 2
EXCITATION
VOLTAGE, Vex (V, rms)
Saturation Test Data for
a Single Phase Transformer
TA B L E 1 4 - 4
Results of Calculation
(Current versus Flux)
EXCITATION
CURRENT, Iex (A, rms)
EXCITATION
POWER, P(W)
2.27128591E+00
8.10284685E−01
216
1.75
150.66
8.49859062E+00
8.59802082E−01
229
3.45
169.63
1.24164919E+01
9.00316316E−01
240
5.41
186.00
1.80862562E+01
9.45332132E−01
252
8.07
205.07
2.44179342E+01
9.72341621E−01
259
10.48
216.95
3.05139341E+01
9.90347948E−01
264
12.72
225.06
TA B L E 1 4 - 3
VMAG (PU)
CURRENT (A)
FLUX (V-S)
Calculated Magnetization
Voltage and Current for Input
to Satura, EMTP
IMAG (PU)
0.9
0.007709
0.955
0.01619
1.0
0.02570
1.05
0.03855
1.08
0.05012
1.1
0.06091
The transformer is connected to a 2400-V single-phase ac source
and serves a load of 50 kVA at 0.9 power factor (Fig. 14-12). It is
energized by closing switch S1 at 0.0125 s and then the load is
applied by closing switch S2 at 0.833 s.
Figure 14-13a depicts the primary current flow from the 2400-V
source transients, while Fig. 14-13b shows excitation current and
secondary load current transients. The excitation current resembles
a rectified wave-shape.
F I G U R E 1 4 - 1 2 A circuit for study of switching transients in a
single-phase, 2400 to 240-V transformer.
14-7-2
EMTP Model Hysdat
In this model, the hysteresis loop, represented in 4 to 5 points to 20
to 25 points, can be modeled:
■
Level 1. 4 to 5 data points
■
Level 2. 10 data points
■
Level 3. 15 data points
■
Level 4. 20 to 50 data points.
376
CHAPTER FOURTEEN
FIGURE 14-13
(a) Primary transformer current, and (b) excitation and load current transients, EMTP routine Satura.
The saturation current and flux in volt-seconds (V-s) is required
to be specified. The scaling of the loop depends upon the geometry,
the number of turns, and other constructional factors of the transformer. This scaling can be fully specified by location of the positive saturation point. This is the point on the first quadrant where
hysteresis loop changes from being multivalued to single valued
(Fig. 14-14). One way of determining these coordinates from the
dc magnetizing curve is as follows.
Beginning at the right, that is, the linear part on the normal magnetization curve, a straight edge is used to extrapolate this line back to the
left. The point where this line and the actual curve first begin to diverge
is taken as the positive saturation point. Similarly the negative saturation point can be plotted; the positive and negative saturation points are
shown with dark circular dots. A dc magnetizing curve is more readily
available from a transformer manufacturer than the hysteresis loop.
Example14-2
The transients in Example 14-1 are recalculated
with hysteresis data shown in Table 14-5. The switching sequence,
the loading data, and the transformer data remains the same. The
primary excitation current is now shown in Fig. 14-15.
14-7-3
Another Model of the Hysteresis Loop
The locus of the midpoints of the loop is obtained by measurements at four points and its displacement by a consuming function,
whose maximum value is ob.8 The segment ef changes periodically
by half-wave symmetry (Fig. 14-16). The consuming function can
be written as:
f ( x ) = −ob sin ωt
(14-34)
TRANSIENT BEHAVIOR OF TRANSFORMERS
TA B L E 1 4 - 5
Computation of Hysteresis
Curve, Using EMTP
Hysteresis Routine*†
CURRENT (A)
FIGURE 14-14
Hysteresis loop and EMTP model Hysdat.
377
FLUX (V-S)
−6.09855000E+00
−9.43743706E−01
−7.62318750E−01
−8.93982674E−01
4.57391250E−01
−8.23630871E−01
1.06724625E+00
−6.4061788E−01
2.05826063E+00
5.54806906E−01
3.20173875E+00
7.32116329E−01
5.48869500E+00
8.40789847E−01
1.01388394E+01
9.15145412E−01
2.43942000E+01
9.72342000E−01
3.35420250E+01
9.78061659E−01
*ARMCO silicon steel stampings
†
Level 2—10 data points
The periphery can be represented by 16 line segments:
i = (ik − mkφk ) + mkφ − ob sin ωt
φk −1 < | φ | ≤ φk
14-7-4
k = 1, 2, . . ., 16
(14-35)
EMTP Model Becatran
Another popular transformer model is Becatran. It can be used to
derive a linear [A]-[R] or [R]-[wL] representation of a single-phase or
three-phase, core-type or shell-type, two-winding, three-winding,
or multiple-winding transformers. (The matrix A is an inverse of L.)
FIGURE 14-15
Test data from excitation test and short-circuit test is required for
the model. For three-phase transformers, having one or more deltaconnected windings, the core construction, shell or core type, is
important. A closed delta acts like a short-circuited circuit to zero
sequence currents. It is, therefore, assumed that all delta connections are open during the zero sequence excitation tests. Excitation
losses can be taken into account or neglected. For low-reluctance
transformers, that is, (i) transformers banks of single phase,
(ii) three-phase, shell-type transformers, and (iii) three-phase, four-limb
Excitation current transient, EMTP model Hysdat.
378
CHAPTER FOURTEEN
FIGURE 14-16
Piecewise hysteresis loop curve fitting.
or five-limb transformers, flux closes its path over core material and
the reluctance is low. The zero sequence excitation current is small.
In three-limb core-type transformers, the homopolar flux will close
its path through the air and the tank, and the reluctance of the path
is high. The zero sequence excitation current is important and the
resulting excitation losses cannot be ignored. This is illustrated in
Fig. 14-17. In a core-type transformer (Fig. 14-17a), the sum of
the fluxes in each phase in a given direction along the cores is zero;
however, the flux going up in one limb must return through the
other two, that is, the magnetic circuit is completed through the
other two phases in parallel. Now consider the zero sequence flux,
which will be directed in one direction only in each of the three
limbs. The return path lies not through the core, but through the
insulating medium and tank. In three separate single-phase transformers connected in three-phase or shell-types transformers, the
magnetic circuits of each phase are complete in itself and do not
interact, Fig. 14-17(b).
Stray capacitances are again ignored in this representation. Thus,
the model is applicable to a few kHz. The inductive and resistive parts
of the short-circuit impedance are treated separately by this model,
and therefore the model holds for low frequencies (a few kHZ).
The nonlinear behavior cannot be included in the Becatran
model properly, but can be taken into account by elements, in
Satura or Hysdat, connected to the windings close to the core. The
saturable transformer model of EMTP (not discussed here) works
well for two-winding transformers, but can become numerically
unstable for three-winding transformers.
For a low value of the magnetizing current, the admittance
matrix becomes nearly singular and the output option [R]-[wL]
cannot be used.
Example 14-3 Consider a 40-MVA, 138 to 13.8-kV three-phase,
wye-wye-connected transformer, both wye-connected windings are
grounded. Following test data is available: Excitation loss = 19 kW,
excitation current = 3 A, excitation voltage = 13.2 kV, short-circuit
losses = 195 kW, short-circuit current = 160 A, short-circuit voltage =
36 kV. (Excitation test conducted from the low-voltage winding side.)
Homopolar measurements are: excitation losses = 120 kW, excitation current = 500 A, excitation voltage = 1.5 kV, short-circuit
losses = 9 kW, short-circuit current = 80 A, short-circuit voltage = 3 kV.
It is required to calculate the transformer parameters for input into
Becatran routine. The calculation is straightforward; based upon
the given data:
13 . 8
= 3 . 136 A
I excpositive = 3
13 . 2
3 × 13 . 8
× 100 = 0 . 1874 percent
40
I excpositive (%) = 3 . 136 × 10−3 ×
and:
2
13 . 8
= 20 . 77 kW
loss excpositive = 19
13 . 2
Similarly:
I exczero =
500
13 . 8
×
= 885 A
3
3 × 1. 5
I exczero (%) = 88 5 × 10−3 ×
3 × 13 . 8
× 100 = 52 . 88 percent
40
and:
2
13 . 8
loss exzero = 120
= 3385 kW
3 × 1 . 5
36
40
×
× 100 = 27 . 28 percent
0 . 160
3 × 1382
3 × 103
40
= 3×
×
× 100 = 23 . 63 percent
80
1382
Z positive =
Z zero
TRANSIENT BEHAVIOR OF TRANSFORMERS
379
From the short-circuit test and dividing the resistance in 50 percent
ratio on the primary and secondary side, the winding resistances are:
1 195000
= 1 . 269 Ω
R1 = 0 . 5 ×
1602
3
2
13 . 8
R 2 = 1 . 269
= 0 . 0127
138
This data can be inputted to Becatran routine in EMTP. The calculated inductance matrix is shown below, each element truncated to
five digits only.
−1
L
0 . 00102 − 0 . 01018 0 . 00005
0 . 00005
0 005
− 0 . 0005
− 0 .0
− 0 . 01018 0 . 10638
− 0 . 0005
0 . 00956
− 0 . 0005
0 .0
0 0956
0 . 00005
− 0 . 0005
0 . 00102 − 0 . 01018 0 . 00005
−0
0 . 0005
=
− 0 . 0005
0 . 00956 − 0 . 01018 0 . 10638 − 0 . 0000 5 0 . 00956
0 . 00005
− 0 . 0005
0 . 00005 − 0 . 00005 0 . 001 0 8 − 0 . 01017
− 0 . 0005
0 . 00956
− 0 . 0005
0 . 00956 − 0 . 0 1 017 0 . 10638
(14-36)
Note that this matrix is symmetrical.
Nonlinearity in Core Losses Figure 14-18 depicts a frequencydomain approach and considers that winding resistance and leakage
reactance remain constant and the nonlinearity is confined to the
core characteristics.9 The core loss is modeled as a superimposition
of losses occurring in fictitious harmonic and eddy current resistors. The magnetizing characteristics of the transformer are defined
by a polynomial expressing the magnetizing current in terms of
flux linkages:
iM = A 0 + A1λ + A 2 λ 2 + A 3λ 3 +
(14-37)
Only a specific order of harmonic currents flow in to the appropriate Gh resistors. From Eqs. (14-10) and (14-11), the core loss
equation is:
Pfe = Ph + Pe
(14-38)
= K h B s f + K e B2 f 2
F I G U R E 1 4 - 1 7 (a) Core-type three-phase transformer, flux paths
for zero sequence currents. (b) Shell-type of transformer, zero sequence
flux paths.
FIGURE 14-18
For a sinusoidal voltage, this can be written as:
Pfe = kh f 1− s E s + ke E2 (kh ≠ K h
and
ke ≠ K e ) (14-39)
Transformer nonlinear shunt model with superimposition of harmonic currents in resistors.
380
CHAPTER FOURTEEN
This defines two conductances: Gh for hysteresis loss and Ge for
eddy current loss, given by:
Gh = kh f
14-8
1− s
E
s− 2
Ge = k e
(14-40)
EMTP MODEL FDBIT
A frequency-dependent transformer model is shown in Fig. 14-19a
and b. The component building blocks are:
Power frequency module (BCTRAN, TOPMEG, and TRELEG)
Hysteresis/saturation module
Eddy current module
High-frequency transformer (HFT) module
It represents the behavior of the transformer over a wide
range of frequency. The problem is generating the data and
fitting it in the transformer model. Raw input data can be in
the form of field measurements of Y(w)—the frequency scan
measurements of nodal admittance matrix of the transformer.
Then it has to be approximated with rational functions to be
represented as FDB branches, see Fig. 14-19b. As an example,
a two-winding, three-phase transformer can be represented
by a two-port three-phase pi circuit, with nodal admittance
–
(a) Transformer model FDBIT in EMTP. (b) The high-frequency module realized with RLC network. (c) Real and imaginary parts of Y 11
(positive sequence). Small dots show measured data.
FIGURE 14-19
TRANSIENT BEHAVIOR OF TRANSFORMERS
FIGURE 14-20
A power system model for study of transformer inrush current transients and sympathetic inrush.
matrix portioned in 3 × 3 blocks.
Y=
Y11 Y12
Y21 Y22
measured data. Similar curves are obtained for Y11-zero sequence.
The model provides:
(14-41)
where Yij is a 3 ×3 matrix of the form shown below and is assumed
to be balanced,
ys
Yij = ym
ym
ym
ys
ym
381
ym
ym
ys
(14-42)
Elements of pi circuit are described by balanced matrices; these can
be modeled using positive and zero sequence parameters. The FDB
branches represent approximations by rational functions of Yshunt
and Yseries of the pi circuit in zero and positive sequence.
The elements of Y are approximated with rational functions
which contain real as well as complex conjugate poles and zeros.
These are then realized with RLC networks, combined to produce
the parameters of an equivalent P circuit (Fig. 14-19b). Specimen
measured data points of real and imaginary parts of Y11 are shown in
this figure with small dots. The actual curves are fitted based upon
FIGURE 14-21
■
The inductive behavior at low frequencies which includes
frequency-dependent effects due to skin effects and iron core
eddy current losses.
■ Series and parallel resonances from mid to high frequencies
caused by winding-to-winding and winding-to-ground capacitances.
■
Predominantly, capacitive behavior at high frequencies.
Example 14-4 A power system configuration is shown in Fig. 14-20.
Two 200-MVA, 230–69 kV transformers of single-phase banks,
winding connections as shown in this figure are connected at the
end of a 16-mi, 230-kV untransposed line for which CP model is
used. There are three simulation switches: S1, S2, and S3. Transformer T1 serves an unbalanced load if switches S1 and S3 are
closed. The transformer models consider excitation characteristics.
First consider that all switches are open and the inrush transients of transformer T1 at no load on closing switch S1 at 8.33 ms
are simulated. Figure 14-21 shows the switching current transients
for time duration of 200 ms, in three phases.
Transformer T1 inrush current transients, phases a, b, and c.
382
CHAPTER FOURTEEN
FIGURE 14-22
14-9
Sympathetic inrush current in transformer T 1 on switching transformer T 2 of Fig. 14-20.
SYMPATHETIC INRUSH
When a transformer is energized on the same bus to which an existing operating transformer is connected, the operating transformer
experiences a surge in current on switching the transformer being
energized. This phenomenon is called sympathetic inrush and is
illustrated in the following example.
Example 14-5 The power system configuration is as in Fig. 14-20.
The switches S1 and S3 remain closed for a long time, that is,
transformer T1 is in a steady state and supplies unbalance load
FIGURE 14-23
with an unbalance = 12 percent maximum. Transformer T2
does not serve any load and is energized by closing switch
S2 at 50 ms. The impact of energizing T2 on the current transients in T1 is illustrated in Fig. 14-22, which shows that
the already energized transformer T1 on the same bus experiences a transient inrush which increases its current by a factor
of 2.6.
The harmonic current measurements of the transformer T2, in
its primary neutral circuit, are shown in Fig. 14-23 which is a plot
of second, third, fourth, and fifth harmonics.
Harmonic currents in transformer T 2 neutral on switching.
TRANSIENT BEHAVIOR OF TRANSFORMERS
FIGURE 14-24
383
Cobra-type hysteresis characteristics with capaci-
tance effects included.
14-10
HIGH-FREQUENCY MODELS
The initial surge transfer through a transformer is a function of the transformer and secondary-side external stray capacitance. Thus, knowledge
of the transformer capacitances is required. Most of the time this data
may not be readily available, and it is a function of transformer winding
construction, end-turn reinforcement, and whether the transformer is
of shell- or core-type construction. For an accurate analysis, this data
should be obtained from the manufacturer and can also be estimated
from constructional details.10,11 Table 14-1 shows that modeling of transformer capacitances is important for some slow transient phenomena,
like ferroresonance. These capacitances can confound measurements
of transformer excitation characteristics, causing a “cobra” flux curve
(Fig. 14-24). The capacitive transfer of voltages to low-voltage winding may be described as a capacitive voltage division.
At higher frequencies, the simplest circuit as seen from the lowvoltage winding side consists of an EMF source in series with a transfer
capacitance. The equivalent EMF on the secondary side is reduced by a
factor, which is not so well defined. The loading of the secondary cables
and switchgear bus, connected to the secondary side of the transformer
adds lumped capacitance to the circuit, and the circuit acts like a voltage divider, reducing the transferred overvoltage peak (Figure 14-25).
With the transformer isolated from the distribution system, the
lumped capacitance is dependent upon the resonant frequency of
the transformer and will change in ratio f/f0, where f is the frequency
of the impressed oscillation and f0 is the natural resonant frequency
of the transformer windings.
A very detailed model may include each winding turn and turnto-turn inductances and capacitances. A disk-layer winding or pancake sections are shown in Fig. 14-26a.12 Each numbered rectangular
block represents cross section of a turn. Winding line terminal is at A
and winding continues beyond E. Each section can be represented by
a series of inductance elements with series and shunt capacitances as
shown in Fig. 14-26b. Though the model looks complex, the mutual
inductances are not shown, resistances are not represented, and all
interturn capacitances are omitted. This circuit will be formidable in
FIGURE 14-25
through the transformer.
An elementary model for surge transference
F I G U R E 1 4 - 2 6 (a) Winding turns in a pancake coil. (b) Circuit of
winding inductances and capacitances. (c) Simplified circuit model.
terms of implementation. For most applications, representation of
each turn is not justified, and by successive lumping, a much simpler model is obtained (Fig. 14-26c). Figure 14-27 shows a further
simplified model of the capacitances associated with a two-winding
transformer. The symbols in this figure are defined as follows:
Cbh. High-voltage bushing capacitance
Cb. Secondary bushing capacitance
Chg. Distributed capacitance of the high-voltage windings
Clg. Distributed capacitance of the low-voltage winding
Chl. Distributed capacitance between the high- and low-voltage
winding
FIGURE 14-27
capacitances.
Circuit model of a two-winding transformer with
384
CHAPTER FOURTEEN
The transformer model described in Ref. 12 determines how
a voltage applied to one set of terminals is transferred to the
other set of terminals. This high-frequency model duplicates
transformer behavior over a wide range of frequencies and acts
like a filter suppressing some harmonics and passing others. For
example, the use of frequency-dependent model is important
when determining the surge that will appear on a generator bus
(secondary side of the transformer), and when a steep-fronted
surge impinges on the high-voltage terminals of the generator
step-up transformer.
FIGURE 14-28
Circuit model of a transformer with transformer
capacitances, external load capacitance, and primary and secondary surge
arresters.
By combining the bushing capacitance into the winding capacitances, the model is further simplified as shown in Fig. 14-28,
which considers:
Cac. Surge capacitors on the secondary side of the transformer,
if provided, to limit the transferred surge voltage
Cld. Capacitance of the load, (cables and distribution system),
connected to the secondary of the transformer.
Sp and SS. primary and secondary surge arresters, respectively
This simplified model can be used for capacitance surge transfer. Table 14-6 shows typical capacitances of core- and shell-type
transformers. It is seen that these capacitances vary over a wide
range.
TA B L E 1 4 - 6
TRANSFORMER
MVA
The lightning and switching surges can be transferred from one voltage level to another through transformer couplings.13 A distribution
system, which may not be directly exposed to the overvoltages of
atmospheric origin, but is connected to a utility system through a
transformer of high turns ratio will be exposed to overvoltages on
the secondary side due to overvoltages on the primary windings.
The resulting stresses on the distribution system may exceed the
BIL levels, unless surge arresters are provided to limit the transferred voltages.
The most common primary distribution voltage in industrial systems is 13.8 kV. However, for large power demands,
the utility system voltage may be as high as 230 kV. The surge
transfer through the transformers depends upon the voltage,
turn ratio, and electrostatic and electromagnetic couplings of
the windings.
The lightning and steep-fronted waves are partially transferred
through the electromagnetic coupling, which is the mechanism
that governs the transformer operation at power frequencies and
depends upon the turn ratio. The transfer of surges of this nature
is less than 40 percent of the magnitude by using conventional
Typical Capacitance of Transformers (Capacitance in nF)
CORE TYPE
SHELL TYPE
Chg
Chl
Clg
1
1.2–14
1.2–17
3.1–16
2
1.4–16
1–18
3–16
5
1.2–14
1.1–20
5.5–17
7
2.7–11
3.5–17
8–16
10
4–7
4–11
8–18
25
2.8–4.2
2.5–18
5.2–20
4–6.8
50
14-11 SURGE TRANSFERENCE THROUGH
TRANSFORMERS
AUTOTRANSFORMERS
Chg
Chl
Clg
Chg
4–7
10–17
4–8
8–18
Chl
Clg
3.5–8
3–8
3.4–11
3–24
6–9
8–16
4–15
5.5–10
5.3–13
6–17
75
3.5–7
5.5–13
2.8–30
7–13
7–17
4–25
7–11
6–20
11–18
100
3.3–7
5–13
4–40
6–14
7–19
5–30
8.5–12
9–20
12–17
200
4.5–18
8–25
5–27
8–40
7–22
16–26
300
5.5–21
11–22
20–40
6–40
5–24
12–32
400
8–24
14–21
17–45
6–25
5–20
11–23
500
6.5–30
17–24
18–46
6–22
5–20
10–24
600
5–40
16–29
16–46
6–20
4.5–20
14–26
700
4–39
15–30
14–43
6–18
5–20
12–28
1000
4–41
11–30
6–54
6–12
7–23
16–30
TRANSIENT BEHAVIOR OF TRANSFORMERS
385
turn ratio, and hence electrostatic effects dominate the coupling
of transients from the primary to the secondary windings. For
slower switching surges the electromagnetic coupling effect predominates, and the surges due to electromagnetic couplings can
be estimated:
The switching surge transferred through the inductive coupling
is given by Ref. 14:
2nZ2
− ( Z n2 Z / L ( Z + n2 Z )t
[− ( Z + n2 Z )/ L ]t
Vss =
× Vps[e 1 2 m 1 2 − e 1 2 s ]
2
Z1 + n Z2
(14-43)
where Z1 is the primary surge impedance, Z2 is the secondary surge
impedance, n is the turn ratio, Lm is the transformer magnetizing
inductance, Ls is the transformer leakage inductance, Vss is the
switching surge transferred to the secondary, and Vps is the peak
value of the switching surge on the primary, limited by the primary
surge arrester.
There are other factors, that is, the surge arrester lead length, the
location of arrester with respect to the protected transformer, and
the effectiveness of grounding, which also impact the surge transference (Chap. 20). The selection of an appropriate surge arrester is
an important consideration. In a multiplegrounded system, a part
of the lightening impulse to the primary system could travel to the
ground through the secondary neutral conductor. This ground path
could induce current in the secondary conductors that could enter
the low-voltage side and cause failure of the high-voltage windings.
In industrial systems, the secondary neutral is commonly grounded
through 200- to 400-A resistor and, thus, the secondary windings
can be considered isolated.
First, a simplified approach to the estimation of the initial
voltage spike transferred to secondary windings, due to lightning
strokes, is discussed without detailed system modeling. The transformer is provided with primary (high-voltage) surge arresters, a
circuit model as shown in Fig. 14-28. The initial voltage spike can
be calculated from the following expression (see Chap. 20 for the
surge arrester characteristics):
Vls = SpVpl
(14-44)
where Vls is the lightning surge transferred to the secondary of the
transformer, Sis the factor depending upon the transformer winding capacitance and capacitance of the low-voltage side connections, p is the factor which allows superimposition of lightening
surge voltage over power frequency voltage. pis 1.05 for wye-wye
and delta-delta connected transformers, and pis 1.15 for delta-wye
connected transformers. Vpl is the primary surge protective level of
the surge arresters. With the transformer energized at no load, the
factor S is given by:
Chl
S=
(Chl + Clg + Cext )
(14-45)
where Cext is the secondary-side external capacitance, that is, of
cables connected to the secondary of the transformer.
Equations (14-44) and (14-45) show that the initial voltage
spike is independent of the transformer turn ratio, and it is simply
a function of Chl, Clg, and the external capacitance. This results in
a simplified transformer model, neglects all saturation, but it is not
accurate.
Example 14-6 A 40-MVA, 230 to 13.8-kV transformer has primary windings in delta connection and the secondary windings are
wye-connected. The primary windings have a BIL of 900-kV and
the secondary winding BIL is 110-kV. The 230-kV system is solidly grounded and the 13.8-kV system is low-resistance grounded
FIGURE 14-29
Power system connection diagram for study of
switching transients.
through a 400-A resistor. Let the primary winding be protected
with a metal oxide, station-class surge arrester of 180-kV rated voltage. Consider that Chg = 10 nF and Clg = 20 nF. The primary surge
protective level of 180 kV surge arrester = 468 kV (See Chap. 20).
Then from Eqs. (14-44) and (14-45), the secondary voltage spike =
179 kV, which is superimposed upon power frequency voltage, that
is, a peak of 198.5 kV. This is much above the secondary BIL of 110
kV, commonly applied for a 13.8-kV system.
Example 14-7 This example illustrates EMTP simulations of a
lightning surge transferred through a transformer when: (a) no primary or secondary surge arresters are provided, (b) only primary
surge arresters are provided, and (c) both primary and secondary
surge arresters are provided. The configuration for the study is shown
in Fig. 14-29; the transformer secondary is open circuited. A direct
lightning stroke occurs on phase a conductor of the transmission
line. The following models are used:
■
Transformer. Capacitance model as shown in Fig. 14-28,
percentage impedance = 9 percent on 40-MVA base, capacitance values are: Chg =10 nF, Clg = 20 nF, and Chl = 10 nF.
■
230-kV transmission line. Flat conductor layout with one
overhead ground wire. A constant parameter traveling wave
model (see Chap. 4).
■
Source impedance. Lumped impedance behind a voltage
source.
■
Direct lightning stroke. The stroke on phase a on 230-kV side
at the bus labeled VL1 is modeled using EMTP single exponential model for the transient. Surge current = 20 kA with 8/20 µs
wave at t = 0.4667 ms, at the peak of the phase a voltage (See
Chap. 20).
■
Surge arrester models. These are discussed in Chap. 20.
386
CHAPTER FOURTEEN
F I G U R E 1 4 - 3 0 (a) Voltage transients on transformer primary windings in phases a, b, and c, and (b) voltage transient in phase a of the secondary
windings, no surge arresters.
(a) Model with no primary or secondary surge arresters.
The voltage profiles on 230-kV and 13.8-kV sides are shown
in Fig. 14-30a and b, respectively. Figure 14-30a shows the
surge voltages for all three phases on the transformer primary
windings, while Fig. 14-30b shows the secondary surge voltage
for phase a only, for clarity. It is seen that multiple peaks occur
due to traveling wave phenomenon and reflections from the
source end of the 230-kV line. The negative maximum of the
primary voltage in phase c occurs after approximately 0.25 ms
of the positive maxima in phase a.
The maxima of phase a voltage, directly struck shows
a voltage of 5400-kV peak (phase-to-neutral). The phases
b and c soon get coupled and the negative maximum is
4060-kV. The BIL level of the primary insulation is 900-kV
peak. The voltage transferred to secondary reaches a peak
of 2000-kV (phase-to-neutral), a very high transferred
voltage indeed for a 13.8-kV (rms) secondary winding,
which has a BIL of 110-kV. Thus, without surge arresters
on the primary of the transformer a very high surge voltage impacts the windings, which can result in immediate
failure. The simulation demonstrates the importance of
primary surge arrester, provisions of which are a standard
practice in the industry.
(b) Model with only primary surge arresters provided.
A 180-kV metal oxide gapless surge arrester, characteristics
as discussed in Chap. 20, is provided on the primary terminals of the transformer, directly mounted on the transformer,
TRANSIENT BEHAVIOR OF TRANSFORMERS
FIGURE 14-31
387
Voltage transients on transformer (a) primary and (b) secondary windings in phases a, b, and c; primary surge
arresters only.
which is a usual installation. This ignores the arrester lead
lengths. Figure 14-31a and b depicts the transients on the
primary (230-kV) windings and the surge voltage transferred
to the secondary (13.8-kV) windings, respectively, in all the
three phases. The model of the surge arrester is discussed in
Chap. 20; the manufacturer’s data is used. The surge voltages
are reduced:
■
230-kV windings. 465 kV peak to ground
■
13.8-kV windings. 160 kV peak to ground
The primary surge arresters have drastically reduced the surge
voltage on the primary windings and also the voltage transferred
to secondary windings. Though the primary insulation is protected, the secondary is not. It is exposed to a stress equal to
1.45 times the BIL of 110 kV.
(c) Model with primary and secondary arresters provided.
In addition to the primary arrester, a secondary arrester of
15-kV rated voltage, metal oxide, gapless type is mounted
directly on the transformer terminals. The simulations of
transients in this case are shown in Fig. 14-32a and b. The
primary surge voltage pattern remains unaltered as in case
(b), but the secondary surge voltage is reduced to a peak of
34.5 kV.
Example 14-8 This example is a continuation of Example 14-7
and is a simulation of the surge transferred to the secondary when
in addition to the primary and secondary surge arresters a secondary surge capacitor of 2 µF is also provided.
The simulation in Fig. 14-33 shows that the secondary voltage
is further reduced to 27 kV peak, phase-to-ground. Example 14-7
illustrates that the transformers must be protected with primary
388
CHAPTER FOURTEEN
FIGURE 14-32
Voltage transients on transformer (a) primary and (b) secondary windings in phases a, b, and c; primary and secondary surge arresters.
F I G U R E 1 4 - 3 3 Voltage transients on transformer secondary windings in phases a, b, and c; primary and secondary surge arresters, and 2-µF
secondary surge capacitor.
TRANSIENT BEHAVIOR OF TRANSFORMERS
FIGURE 14-34
A capacitance ladder network for distribution of surge voltage across transformer windings.
and secondary arresters, even if a rigorous study is not conducted.
In fact the selection of appropriate surge protection may lower
the required BIL for the transformer windings, resulting in cost
savings.
This will give:
14-12 SURGE VOLTAGE DISTRIBUTION ACROSS
WINDINGS
and
The surge distribution across a transformer winding from the line to
neutral terminal is nonlinear, and the line-side turns are exposed
to a much steeper voltage gradient. For study of such surge distribution, we could derive the circuit of Fig. 14-34 from Fig. 14-26c by
eliminating reactance portion of windings altogether, and retaining
only the capacitances. For a distributed parameter line, Eq. (4-11) is
reproduced below:
V = V1e γ x + V2e − γ x
(14-46)
By analogy, we can write a similar equation for the circuit of Fig. 14-34:
E = A1e px + A 2e − px
(14-47)
where:
p=
1 Cg
l Cs
(14-48)
and A1 and A2 are the constants depending upon the terminal conditions. Consider that the neutral terminal is grounded in Fig. 14-34,
then at x =0, E =0, and at x =l, E =V.
This gives:
A1 = − A 2 =
V
V
=
− pl
2 sinh α
e −e
pl
(14-49)
where:
α = pl =
Cg
Cs
A1 = A 2 =
E=
(14-51)
If the neutral is isolated, then at x =l, E =V and at x =0, Is =0 or
dE/dx =0
V
2 cosh α
(14-52)
V cosh(α l /x )
E=
cosh α
Curves of distribution from line end to neutral can be plotted. The
distribution will not be uniform, and the voltage will be much
higher on the winding turns toward the line side; the steepness
depends upon a.
Example 14-9 Referring to Fig. 14-34, there are four sections,
with series capacitance of 1 nF and shunt capacitance to ground of
5 nF. A surge voltage ramp of 100 kV, approximately 4 µs duration
is applied to the line terminal, while the neutral is grounded. The
results of the EMTP simulation, with the surge voltage distribution
at the beginning of each section are shown in Fig. 14-35. The surge
voltage distribution is highly nonlinear.
Now model the four sections each with a series reactance of 0.01
mH (Fig. 14-26c). The surge voltage distribution across each section is illustrated in Fig. 14-36. This shows an oscillatory response
and unequal surge distribution; sections 2 and 3 have exactly the
same oscillatory pattern.
In this model, the capacitances and reactances are identical in
each of the four sections. The capacitance of the windings is a function of the winding geometry. Practically, the winding capacitance
will vary, and so also the surge distribution.
Earlier the end turns of the transformers were reinforced and
strengthened to protect them from high insulation stresses. This did
not prove to be effective in most cases. Currently, metallic shields in
strategic positions are placed adjacent to the coils. These shields are
so placed and connected that the capacitance current flowing through
them and the transformer windings tends to compensate for the ground
capacitance current, thereby making the current through the series
capacitance more uniform. Another method is to adjust capacitance
distribution depending upon how the windings are interconnected.
14-13
(14-50)
Substituting in Eq. (14-47) gives:
V
(e px − e − px )
2 sinh α
V sinh(α x /l )
=
sinh α
389
DUALITY MODELS
Duality-based models, also called topology-based models, can be
used to represent transformers.15 These models are based upon core
topology and utilize the correspondence between electric and magnetic circuits, as expressed by the principle of duality. Voltage, current, and inductance in electrical circuits correspond to flux, MMF,
and reluctance, respectively, in the magnetic circuit.
V
R
MMF MMF
Φ=
=
l /µµ0a
S
I=
(14-53)
390
CHAPTER FOURTEEN
FIGURE 14-35
Simulation of surge voltage distribution, four capacitance, sections with ground capacitances.
where l is the length of the magnetic path, a is the cross-sectional
area, and S is the reluctance, which is analogous to resistance in
electrical circuit and determines the MMF necessary to produce a
given magnetic flux. Permeance is reverse of reluctance.
Figure 14-37a shows electrical equivalent circuit of a threewinding core-type transformer, portraying magnetic coupling in
three-limbed and five-limbed transformers.15 Nonlinear inductances
FIGURE 14-36
correspond to iron flux paths in the magnetic circuit, permitting
each core limb to be modeled separately. Each Lk represents top and
lower yokes and each Lb represents a wound limb. L0 represents flux
path through the air, outside the core, and around the windings.
Finally, the ladder network between linear inductances, L0 and Lb,
represents winding leakages through the air. Inductances Lh and Ly
represent unequal flux linkages between turns due to finite winding
Simulation of surge voltage distribution; four capacitance and inductance sections with ground capacitances.
TRANSIENT BEHAVIOR OF TRANSFORMERS
FIGURE 14-37
391
(a) Duality-based model for a core-type, three-winding transformer. (b) Simplified circuit derived from Fig. (a).
radial build and these are small compared to L0 and Lb. This model
is simplified as shown in Fig. 14-37b. The various inductances are
calculated based upon short-circuit tests.
Duality models can be used for low-frequency transient studies,
such as short circuits, inrush currents, ferroresonance, and harmonics. The model can be implemented in EMTP TOPMAG data calculation function. For three-limbed and five-limbed units, each limb
is modeled individually and interfaced to an admittance matrix,
reproducing the exact magnetic coupling between the windings. An
additional three-phase fictitious winding is required for this interface, since core limbs are electrically isolated from the windings.
N (N−1)/2 positive sequence short-circuit test values are required
for an N-winding five-limbed or single-phase transformers. For
three-limbed transformers zero sequence short-circuit test impedance or zero sequence excitation current is required.15
transformer windings through grounded neutrals (Fig. 14-38), and
bias the transformer core to half-cycle saturation. As a result, the
transformer magnetizing current is greatly increased. Harmonics
increase and these could cause reactive power consumption, capacitor overload, and false operation of protective relays.
A GIC model is shown in Fig.14-39;16 four major flux paths are
included. All R elements represent reluctances in different branches.
Subscripts c, a, and t stand for core, air, and tank, respectively, and 1,
2, 3, and 4 represent major branches of flux paths. Branch 1 represents
sum of core and air fluxes within the excitation windings, branch 2
represents flux path in yoke, branch 3 represents sum of fluxes entering the side leg, part of which leaves the side leg and enters the tank,
and branch 4 represents flux leaving the tank from the center leg. An
iterative program is used to solve the circuit of Fig. 14-39 so that nonlinearity is considered.
14-14
14-15
GIC MODELS
Geomagnetically induced currents (GIC) flow on the earth’s surface
due to solar magnetic disturbance (SMD), and these are typically of
0.001 to 0.1 Hz and can reach peak values of 200 A. They can enter
FERRORESONANCE
Ferroresonance can occur when a nonlinear inductance (iron-core
reactance of a transformer) is excited in parallel with capacitance
through high impedance (Chap. 7). Overvoltages up to three to four
392
CHAPTER FOURTEEN
FIGURE 14-38
GIC entering the grounded neutrals of wye-connected transformers.
times the nominal voltage can occur. Ferroresonance occurs because
of reactance of a distribution transformer Xm, and the capacitance
of the bushings and underground cables form a resonant circuit.
Highly distorted voltage waveforms are produced which include a
60-Hz component. Considerable harmonics are generated. We may
postulate, based upon the current literature, that:
■
High overvoltages of the order of 4.5 pu can be created.
■
Resonance can occur over a wide range of Xc/Xm,17 possibly
in the range 0 . 1 < X c /X m < 40 .
■
Resonance occurs only when the transformer is unloaded, or
very lightly loaded. Transformers loaded to more than 10 percent
of their rating are not susceptible to ferroresonance.
The capacitance of cables varies between 40 to 100 nF
per 1000 ft, depending upon conductor size. However, the
FIGURE 14-39
Transformer model for GIC simulation.
FIGURE 14-40
(a) A circuit for possible ferroresonance. Equivalent circuit derived with (b) one phase closed and (c) two phases closed.
TRANSIENT BEHAVIOR OF TRANSFORMERS
393
magnetizing reactance of a 35-kV transformer is several times
higher than that of a 15-kV transformer; the ferroresonance
can be more damaging at higher voltages. For delta-connected
transformers, the ferroresonance can occur for less than 100 ft
of cable. Therefore, the grounded wye-wye transformer connection has become the most popular in underground distribution
system in North America. It is more resistant, though not totally
immune to ferroresonance.
Series Ferroresonance Figure 14-40a shows a basic circuit of
ferroresonance. Consider that current-limiting fuses in one or two
lines operate. Xc is the capacitance of the cables and transformer
bushings to ground. Also the switch may not close simultaneously
in all the three phases, or while opening, the phases may not open
simultaneously. We can draw the equivalent circuits with one phase
closed and also with two phases closed as shown in Fig. 14-40b
and c, respectively.
Similar equivalent circuit can be drawn for wye-wye ungrounded
transformer. The minimum capacitance to produce ferroresonance
can be calculated from Xc/Xm = 40, say:
Cmres =
2 . 21 × 10−7 MVA transf I m
Vn2
(14-54)
where Im is the magnetizing current of the transformer as a percentage of the full-load current. Typically, magnetizing current of a
distribution transformer is 1 percent to 3 percent of the transformer
full-load current. MVAtrasf is the rating of transformer in megavoltamperes, Cmres is the minimum capacitance for resonance in picofarads, and Vn is the line-to-neutral voltage in kilovolts. Table 14-7
gives the approximate values of Cmres.
Parallel Ferroresonance A less common condition of ferroresonance is illustrated in Fig. 14-41a and b.18 This involves the
mutual Xm formed between the windings at the same voltage level
in four- or five-leg core-type transformers. These may resonate even
TA B L E 1 4 - 7
F I G U R E 1 4 - 4 1 (a) Mutual coupling ferroresonance. (b) Equivalent
circuit for mutual coupling ferroresonance.
when connected in grounded wye. However, the overvoltages are
limited to 1.5 pu, because equivalent circuit is a parallel LC combination, and Xm limits the voltage by saturation.
Example 14-10
The curve of Fig. 7-20c can be represented
by two-piece saturation characteristics of a nonlinear reactor
Capacitance Limits for Ferroresonance (Cmres in Picofarads)
SYSTEM VOLTAGE (KV)
TRANSFORMER KVA
SINGLE PHASE
8.32/4.8
12.5/7.2, 13.8/7.99
25/14.4, 27.8/16
THREE PHASE
Cmf
Cmf
Cmf
15
5
72
26
16
25
10
119
43
11
339
86
21
50
75
25
100
358
129
32
477
172
43
150
50
719
258
64
225
75
1070
387
97
300
100
1432
516
129
500
167
2390
859
215
750
250
3580
1290
322
4770
1720
430
1000
1500
7190
2580
645
2000
9550
3440
859
394
CHAPTER FOURTEEN
FIGURE 14-42
A piecewise curve of an iron core (nonlinear) reactor.
(Fig. 14-42). The reactor is energized through a 60-Hz voltage of
240 V and a parallel capacitor of 1.7 µF in two cases: (a) with no
prior magnetic flux, and (b) 0.07 Wb of initial flux. The simulation
results of the voltage across the reactor and the current through it
are shown in Fig. 14-43a and b, respectively. Without a prior flux,
there are no current or voltage transients. With initial flux, the voltage rises to 4 pu of the applied voltage and the current waveshape
can be compared with that of Fig. 14-15.
14-16
TRANSFORMER RELIABILITY
When properly specified and applied for the specific applications, a
transformer is a fairly reliable piece of equipment. IEEE standard19
gives a failure rate l = 0.0030 per year. However, the downtime
associated with this failure rate is high, r (downtime in hours per
failure) = 342 for repairs of the faulty unit and r = 130.0 if the unit
is replaced. These data are applicable for transformers of 601 to
F I G U R E 1 4 - 4 3 Simulation of transients with a parallel capacitor of 1.7 µF, (a) non-linear reactor and (b) voltage and current transients respectively
with no prior magnetic flux and with 0.07 Wb of magnetic flux. (Continued )
TRANSIENT BEHAVIOR OF TRANSFORMERS
FIGURE 14-43
15 kV. For reliable power supply systems, it is common practice to
design the systems so that failure of one unit does not precipitate in
complete loss of power, and it is customary to provide standby or
redundant transformers. Transformers may be operated in parallel
and sized, so that on loss of one of the parallel running unit entire
load can be supplied. The protective relaying can ensure that the
faulty unit is automatically taken out of service, with least interruption to the load, for example, bus transfer systems discussed in
Chap. 16.
PROBLEMS
1. A 30-MVA, 138 to 13.8-kV, delta-wye-connected transformer has a percentage impedance of 9 percent. What is
the magnitude and duration of short-circuit currents that it
should withstand according to ANSI/IEEE standards, both
for frequently occurring faults and less frequently occurring
faults?
2. In Example14-3, consider that a transformer of the same
specifications is connected in delta-wye grounded configuration. How will it impact the test data?
3. Explain the zero sequence flux patterns and impedances
in three-limbs, core-type, five-limb core-type and shell-type
three-phase transformers. Compare core-type construction
with shell-type construction.
4. The transformer in Prob. 1 is provided with ±2.5 and
±5 percent off-load taps on the high-voltage winding. Construct
equivalent T and P impedance circuits in ohms when the transformer primary windings are at plus 5 percent taps.
5. The tests on a 3000-kVA, 13.8 to 4.16-kV, delta-wyeconnected transformer give a copper loss of 20 kW on the
delta side and 18 kW on the wye side. Find winding resistances,
and refer secondary winding resistances to primary windings.
If the total reactance is 5.5 percent, find primary and secondary
reactances, assuming that these are divided in the same ratio as
the resistances.
395
(Continued )
6. The transformer of Prob. 5 is tested on open circuit on the
4.16-kV side. Rated primary voltage at power input = 12 kW,
and no load current =3 A. Find magnetizing circuit parameters.
7. What is the predominant harmonic in the inrush current of
a transformer?
8. The following points relate to the excitation test data supplied by a manufacturer for a transformer of 750 MVA, with a
wye-connected, high-voltage winding of 400 kV, and a deltaconnected, low-voltage winding of 18 kV:
Vex = 22.76, Iex = 9.0, Pex = 210.5
Vex =35.2, Iex = 80.75, Pex = 580
Convert these values to Vrms and Irms per unit base, similar to
conversion of Tables 14-2 and 14-3.
9. Two 10-MVA transformers of the same impedance of
5.5 percent, but with voltage ratios of 138 to 13.8 kV and 138
to 13.2 kV, are suddenly paralleled by closing a switch at the
crest of secondary voltage. Derive a time-current equation of
the circulating current.
10. Consider a transformer with five winding sections and the
ratio a in Eq. (14-50) =3. Calculate the voltage across each
section of the winding for a surge of 250-kV peak applied to
the line terminals, neutral grounded and ungrounded.
11. Explain sympathetic inrush.
12. Draw circuit diagrams of single-phase transformers:
(1) ignore all saturation and losses, (2) include saturation,
(3) include hysteresis, (4) include saturation, hysteresis, and
core loss, (5) include winding capcitances to ground, and
(6) include all other capacitances.
13. A transformer is represented with a capacitance of 15 nF,
where the secondary is an open circuit, the surge impedance =
300 ohms, and the capacitance to ground = 10 nF. What is the
396
CHAPTER FOURTEEN
magnitude of the surge transferred to the secondary for (1) delta-wye-connected transformer, and (2) wye-wye transformer?
13. J. C. Das, “Surge Transference Through Transformers,” IEEE
Industry Magazine, vol. 9, no. 5, pp. 24–32, Oct. 2003.
14. The transformer of Prob. 1 is operated at 50 Hz. What can
be expected with respect to its continuous operation at this
frequency?
14. A. Greenwood, Electrical Transients in Power Systems, John
Wiley, New York, 1991.
15. Without conducting a rigorous study, recommend installation of surge arresters for surge protection of the transformer
windings. What is the role of a secondary surge capacitor?
15. A. Narang and R, Brierley, “Topology-Based Magnetic Model for
Steady State and Transient Studies for Three-Phase Core-Type
Transformers,” IEEE Trans. PS, vol. 9, no. 3, pp. 1337–1349,
Aug. 1994.
16. Draw a sketch showing the distortion in phase voltages on
phenomenon of oscillating neutrals in ungrounded wye-wyeconnected transformers.
16. S. Lu, Y. Liu, and J. D. R. Ree, “Harmonics Generated from a
DC Biased Transformer,” IEEE Trans. PD, vol. 8, pp. 725–731,
1993.
17. Why is an admittance matrix, rather than an impedance
matrix, used in formation of the transformer winding data for
transient analysis?
17. R. H. Hopkinson, “Ferroresonance During Single-Phase Switching of Three-Phase Distribution Transformer Banks,” IEEE
Trans. PAS, vol. 84, pp. 289–293, 1965.
REFERENCES
1. CIGRE Working Group 33.02, Guidelines for Representation of
Network Elements When Calculating Transients, CIGRE
Brochure 39, 1990.
2. IEEE Modeling and Analysis of System Transients Using Digital
Programs, Document TP-133-0, 1988.
3. ANSI/IEEE Std. C57.12, General Requirements for Liquid
Immersed Distribution, Power and Regulating Transformers, 2006.
4. ANSI/IEEE Std. C57.110, IEEE Recommended Practice for
Establishing Transformer Capability When Supplying NonSinusoidal Loads, 1998.
5. UL Standard 1561, General Purpose and Power Transformers,
1990.
6. ANSI/IEEE Std. C37.91, IEEE Guide for Protecting Power
Transformers, 2008.
7. ANSI/IEEE, IEEE Guide for Dry-Type Transformer Through
Fault Current Duration, 2006.
8. C. E. Lin, J. B. Wei, C. L. Huang, and C. J. Huang, “A New
Method for Representation of Hysteresis Loops,” IEEE Trans.
PD., vol. 4, pp. 413–419, 1989.
9. J. D. Green and C. A. Gross, “Non-Linear Modeling of
Transformers,” IEEE Trans. Industry Applications, vol. 24,
pp. 434–438, 1988.
10. T. Adielson, A. Carlson, H. B. Margolis, J. A. Halladay.
“Resonant Overvoltages in EHV Transformers: Modeling and
Applications,” IEEE Trans. PAS, vol. PAS-100, no. 7,
pp. 3563–3572, 1981.
11. P. S. Maruvada and N. H Cavallius, “Capacitance Calculations
for Some Basic High Voltage Electrode Configurations,” IEEE
Trans. PAS, vol. 94, no. 5, pp. 1708–1713, Sept./Oct. 1975.
12. W. J. McNutt, T. J. Blalock, R. A. Hinton, “Response of Transformer Windings to System Transient Voltages,” IEEE Trans.
PAS, vol. PAS-93, pp 457–467, 1974.
18. D. R. Smith, S. R. Swanson, and J. D. Borst, “Overvoltages
with Remotely Switched Cable Fed Grounded Wye-Wye
Transformers,” IEEE Trans. PAS, vol. PAS-94, pp. 1843–1853,
1975.
19. ANSI/IEEE Std. 493, IEEE Recommended Practice for Design
of Reliable Industrial and Commercial Power Systems, 2007.
FURTHER READING
Canadian/American EMTP User Group, ATP Rule Book, Portland,
OR, 1987–1992.
X. Chen and S. S. Venkta, “A Three-Phase Three-Winding CoreType Transformer Model for Low-Frequency Transient Studies,”
IEEE Trans. PD, vol. 12, pp. 775–782, 1997.
F. de Leon and A. Semlyen, “Complete Transformer Model for Electromagnetic Transients,” IEEE Trans. PD, vol. 9, no. 1, pp. 231–239,
1994.
F. de Leon and A. Semlyen, “Efficient Calculations of Elementary Parameters of Transformers,” IEEE Trans. PD, vol. 7, no. 1,
pp. 376–383, Jan. 1992.
A. Morched, L. Marti, and J. Ottenvangers, “A High Frequency
Transformer Model for EMTP,” IEEE Trans. PD, vol. 8, no. 3,
pp. 1615–1626, 1993.
G. C. Paap, A. A. Alkema, and L. van der Sluis, “Overvoltages in
Power Transformers Caused by No-Load Switching,” IEEE Trans.
PD, vol. 10, no. 1, pp. 301–307, Jan. 1995.
C. W. Plummer, G. L. Goedde, E. L. Pettit Jr, J. S. Godbee,
M. G. Hennessey, and W. I. Pawaukee. “Reduction in Distribution
Transformer Failure Rates and Nuisance Outages Using Improved
Lightning Protection Concepts,” IEEE Trans. PWRD, vol. 10, no. 2,
pp. 768–777, 1995.
E. J. Tarasiewicz, A. S. Morched, A. Narang, and E. P. Dick, “Frequency Dependent Eddy Current Models for Non-linear Iron
Cores,” IEEE Trans. PS, vol. 8, no. 2, pp. 588–597, May 1993.
P. M. Vaseen, “Transformer Model for High Frequencies,” IEEE
Trans. PWRD, vol. 3, no. 4, pp. 1761–1768, 1988.
CHAPTER 15
POWER ELECTRONIC
EQUIPMENT AND FACTS
Nonlinear loads are on the increase, and it is estimated that in the
next 7 to 8 years 60 percent of the loads served from the utility
systems will be of nonlinear nature. These loads are a source of
electrical noise and harmonics, and while polluting the power supply, are themselves less tolerant to the poor power quality. Power
electronics are already impacting the electrical utility industry in
the form of flexible ac transmission systems (FACTS), which can
mitigate some of the inherent problems of conventional ac transmission systems. Some examples of nonlinear loads are:
■
Adjustable speed drive systems
■
Cycloconverters
■
Arc furnaces, which are further discussed in Chap. 16
■
Switch mode power supplies (SMPs) (Chap. 19)
■ Copy machines, television sets, computers,
and peripherals
■
Static var compensators
■
HVDC transmission
■
Electric traction
■
Wind and solar power generation
■
Battery charging, fuel cells, and UPS systems
■ Slip frequency recovery schemes of large induction
motors
■
Fluorescent lighting and electronic ballasts
It is not the intention to go into discussions of the operation of
these equipments. From the power quality point of view, the harmonic generation from these loads is of concern. From the application point of view, the FACTS controllers are used to enhance the
performance of electrical power transmission, mitigate oscillations,
and improve transient stability.
15-1
THE THREE-PHASE BRIDGE CIRCUITS
Figure 15-1 shows a three-phase fully controlled six-pulse current source converter circuit and current and voltage waveforms.
The sequential firing of the thyristors is shown in Table 15-1.
At any one time, two thyristors conduct. The firing frequency is
six times the fundamental frequency, and the firing angle a can
be measured from the point O shown in Fig. 15-1. With a large
reactor the output current can be assumed to be continuous and
the input current is rectangular of pulse width 2p / 3 duration and
amplitude Id. A Fourier analysis of the input current waveform
gives:
ia =
2 3
1
1
I cos ω t − cos 5ω t + cos 7ω t
π d
7
5
−
1
1
cos11ω t + cos 13ω t − ...
11
13
(15-1)
In general, the theoretical order of harmonics is given by:
h = pm ± 1 m = 1, 2,...
(15-2)
where h is the order of the harmonic, and p is the pulse number,
which is defined as the total number of successive nonsimultaneous commutations occurring within the converter during each
cycle when operating without phase control. The harmonics given
by Eq. (15-2) are an integer of the fundamental frequency and
are called characteristic harmonics. Certain type of pulsed loads
and integral cycle controllers produce distorted waveforms having
a submultiple of power frequency. Some loads like arc furnaces,
arcing devices, fluorescent, and mercury and sodium vapor lighting produce waveforms which are aperiodic. If the operations are
kept constant over a length of time, the waveform may be almost
periodic. Cycloconverters and arcing loads produce “interharmonics,”
which are defined as “between the harmonics of the power frequency
voltage and current, further frequencies can be observed, which
are not integers of the fundamental frequency. These appear
as discrete frequencies or wide-band spectrum.” This has attracted
much attention in recent times.
397
398
CHAPTER FIFTEEN
FIGURE 15-1
certain delay angle a.
(a) Circuit diagram of three-phase, fully controlled six-pulse current source converter (b) Voltage and line-current waveforms for a
TA B L E 1 5 - 1
Firing Sequence of Thyristors
in Six-Pulse Converter
CONDUCTING THYRISTOR
5,3
1,5
6,1
2,6
4,2
3,4
Thyristor to be fired
1
6
2
4
3
5
Thyristor turning off
3
5
1
6
2
4
Also from Eq. (15-1) the theoretical magnitude of a harmonic
is given by:
Ih =
I1
h
firing angles and three-phase circuits. These are called noncharacteristic harmonics.
The ripple content in the output voltage wave is shown in
Fig. 15-2. The form factor is the measure of the shape of the output
voltage or current and is defined as:
FF =
I rms
I dc
(15-4)
The ripple factor, which is a measure of the ripple content of the
output current or voltage, is defined as the rms value of the output voltage or current, including all harmonics, divided by average
value:
(15-3)
where h is the order of the harmonic, and I1 is the fundamental frequency current. Thus, a six-pulse three-phase converter produces
harmonics of the order of: 5th =20 percent, 7th =14.28 percent,
11th =9.09 percent and so on. Practically, the harmonics will be
much lower, as discussed further. The second-order and third-order
harmonics are ideally absent, but practically, converters do produce
a small percentage of these harmonics due to some asymmetry in
2
I
RF = rms − 1 = FF2 − 1
I dc
(15-5)
The ripple factor of a six-pulse converter, with zero firing
angle is 0.076, and the lowest harmonic in the dc output of the
converter is sixth. Thus, a converter may be considered a splitter
of harmonics, odd harmonics going into the line side and even
POWER ELECTRONIC EQUIPMENT AND FACTS
FIGURE 15-2
Ripple content in the output dc voltage of a six-pulse converter.
harmonics into the load side. As the pulse number increases, the
ripple in the dc output voltage and the harmonic content in the
input are reduced.
15-1-1
Phase Multiplication
The winding connections of the input transformer impact the input
current waveform. The harmonic spectrum in Eq. (15-1) is obtained
when there is 0° phase shift between the voltage vectors of the primary and secondary windings of the input transformer Fig. 15-1a.
The angular displacement in windings of polyphase transformers
was discussed in Chaps. 9 and 14.
Consider now a 30° phase shift in the transformer winding connections, that is, a delta-wye or wye-delta connected transformer.
For example, Fig. 15-1b shows this alternate waveform in dotted
lines, with this phase shift. A Fourier analysis of this waveform
gives:
2 3
1
1
ia =
I cos ω t + cos 5ω t − cos 7ω t
π d
5
7
−
1
1
cos11ω t + cos 13ω t + ...
11
13
(15-6)
If we combine the two waveforms of the input currents, the harmonics of the order of 5th, 7th, 17th, and 19th cancel out. Practically,
approximately 75% cancellation is achieved. Figure 15-3 shows the
combination of these two waveforms; and a closer approximation
to sinusoidal wave shape is achieved. The combination acts like a
12-pulse system.
The concept is widely used to reduce the harmonic distortion
in the input current waveforms, say in HVDC and ASD systems. A
24-pulse operation can be obtained with four transformers having
a 15° phase shift. This will eliminate, though not totally, all lowerorder harmonics of the order of below 23rd.
Some other technologies for harmonic mitigations, for example,
multilevel converters, interphase reactors, and active current shaping are not discussed.
15-1-2
399
Commutation and Overlap Angle
Figure 15-1 assumes that the conduction of current from one SCR
to another is instantaneous. The commutation is delayed by an angle
m due to source inductance, and during this period short circuit
occurs through the conducting devices, the circulating current being
limited by the source impedance. The angle m is called the overlap
angle. When a = 0, the short-circuit conditions correspond to the
maximum asymmetry and m is large, that is, slow initial rise. At 90°
the conditions are that of zero asymmetry with its fast rate of rise of
current. Figure 15-4 shows the effect of overlap angle. Note that the
slow rise of current reduces the harmonics.
Commutation produces two primary notches per cycle and four
secondary notches of lesser magnitude, which are due to notch
reflection from the other legs of the bridge. Figure 15-5 shows the
voltage notching in the fully controlled bridge with large output
reactor. The notch area must be limited according to standards1 by
adding additional source reactors, if required.
The depth of the notch is given by the commutation angle:
µ = cos −1[cos α − ( X s + X t )I d ] − α
(15-7)
where Xs and Xt are the system and input transformer reactances,
respectively, and Id is the dc current in per unit on converter base.
Figure 15-6 illustrates four waveforms:
1. Rectangular current waveform or ideal textbook waveform
(Fig. 15-6a)
2. Waveform modified by commutation angle (Fig. 15-6b)
3. Waveform with ripple content (Fig. 15-6c)
4. A discontinuous waveform due to large firing angle, giving
rise to much higher harmonics in the input supply system.
(Fig. 15-6d)
These line harmonics can be estimated using the methodology
described in Refs 1, 2 and 3. The dc voltage is given by:
3
Ed = 2
2π
3 3
E cos α
Em cos ω td(ω t ) =
π m
− π / 3 +α
π / 3 +α
∫
(15-8)
The output voltage can be reduced to zero and with increasing
control angle, the converter will act as an inverter. A bidirectional
400
CHAPTER FIFTEEN
FIGURE 15-3
(a) Circuit diagram of harmonic elimination with phase multiplication. (b) Input current waveform with ideal commutation.
FIGURE 15-4
Effect of commutation angle m on the input current waveform.
POWER ELECTRONIC EQUIPMENT AND FACTS
FIGURE 15-5
401
Voltage notching due to commutation in a six-pulse current source converter and the input current waveform.
fundamental of ac current and voltage, and is strongly dependent
upon the firing angle a. The commutation process also introduces
further displacement of the ac current. Figure 15-7 shows that the
converter is consuming reactive power both in the rectifier and
inverter mode. In addition, a certain amount of reactive power is
lost in the rectifier transformers too. The reactive power demand,
for a single converter operation, is usually 50 to 60 percent of the
transmitted active power.
For HVDC transmission, which requires conversion of ac to dc
and dc to ac, these converters have been extensively used, though
these may lead to commutation failures. The reactive power is managed through switched capacitor filters; it can be drawn from the
system and can even be controllable, and load-dependent controls
can be provided. An advantage of thyristors is that these can handle
two to three times the power that gate turn-off (GTO), integrated
gate-commutated thyristors (IGCTs), or MOS turn-off thyristors
(MTO) can handle. In the late 1990s, HVDC transmission using
voltage source converters with pulse width modulation (PWM)
was introduced and commercially called HVDC-light. Figure 15-8
shows solid-state converter developments, thyristors and IGBTs
over the years.
15-2
FIGURE 15-6
(a) A rectangular ideal input current waveform, (b) a
waveform with commutation angle, (c) a waveform with ripple content, and
(d ) a discontinuous waveform due to large delay angle control.
flow of active power is possible from ac to dc and dc to ac, but a
line-commutated current source converter, with thyristors (turn-on
control devices only), draws reactive power from the supply system (Fig. 15-7). This reactive power is due to phase shift between
VOLTAGE SOURCE THREE-PHASE BRIDGE
The FACTS use voltage source bridge, rather than current source
configuration. The requirements of FACTS controllers are:
■
The converter should be able to act as an inverter or
rectifier with leading or lagging reactive power, that is, fourquadrant operation is required, as compared to the current
source line commutated converter which has two quadrant
operations.
■ The active and reactive power should be independently controllable with control of phase angle.
402
CHAPTER FIFTEEN
FIGURE 15-7
Reactive power requirements of current source converters.
FIGURE 15-9
FIGURE 15-8
Developments of solid-state technology: thyristors
and IGBTs.
The principle is illustrated with respect to single-valve operation (Fig. 15-9). Consider that dc voltage remains constant and the
turn-off device is turned on by gate control. Then the positive of dc
voltage is applied to terminal A, and the current flows from +Vd to
A, that is, inverter action. If the current flows from A to +Vd, even
when device 1 is turned on, it will flow through the parallel diode,
rectifier action. Thus, the power can flow in either direction. A
valve with a combination of turn-off device and diode can handle
power in either direction.
Figure 15-10a extends this concept for a fully controlled singlephase bridge and shows the conduction of the devices. With 1 and
A single-valve voltage source converter.
2 turned on, the output voltage Vab =+Vd, and with 3 and 4 turned
on it is –Vd. This voltage waveform occurs Fig. 15-10b, irrespective
of the ac current flow magnitude and phase angle. The respective
conduction of devices is shown and when the current reverses, it
flows through diodes 1′, 2′. The ac current flow is an interaction of
the square wave generated by the converter, the ac voltage, and the
impedance. Figure 15-10c shows that the current flow from the ac
system is sinusoidal, Iab leading Vab by angle q. Figure 15-10d shows
the current waveform of Id and Fig. 15-10e shows the voltage across
the valve elements.
15-3
THREE-LEVEL CONVERTER
Figure 15-11 shows the circuit of a three-level converter and associated waveforms. In Fig. 15-11a, each half of the phase leg is split into
two series-connected circuits, midpoint connected through diodes,
which ensure better voltage sharing between the two sections.
Waveforms in Figs. 15-11b through e are obtained corresponding
to one three-phase leg. Waveform Fig. 15-11b is obtained with 180°
POWER ELECTRONIC EQUIPMENT AND FACTS
FIGURE 15-10
403
(a) Single-phase full-wave voltage source converter connection diagram. (b), (c), (d ), and (e) Operational waveforms.
conduction of the devices. Waveform Fig. 15-11c is obtained if 1 is
turned off and 2A is turned on at an angle a earlier than for 180°
conduction. The ac voltage Va is clamped to zero with respect to
mid point N of the two capacitors. This occurs because devices 1A
and 2A conduct and, in combination with diodes, clamp the voltage to zero. This continues for a period of 2a, until 1A is turned off
and 2 is turned on and voltage is now −Vd/2, with both the 2 and
2A turned off and 1 and 1A turned on. The angle a is variable and
output voltage Va is square waves s=180° −2a°. The converter
is called a three-level converter as dc voltage has three levels, Vd/2,
0, and −Vd/2. The magnitude of the ac voltage can be varied without changing the magnitude of the dc voltage by varying angle a.
Fig. 15-11d shows the voltage Vb, and Fig. 15-11e, the phase-tophase voltage Vab.
The harmonic and fundamental rms voltages are given by:
Vh =
hα
2 2 Vd 1
sin
π 2 2
2
Vf =
α
2 2 Vd
sin
π 2
2
Vf =0 at a=0 and maximum at a=180°.
(15-9)
404
CHAPTER FIFTEEN
FIGURE 15-11
15-3-1
(a) A three-level, three-phase voltage source converter. (b), (c), (d ), and (e) Operational waveforms.
Pulse Width Modulation
Consider one-phase leg of the three-level converter in Fig. 15-11a.
Figure 15-12 shows the PWM signals, which are produced using
sawtooth wave (triangular) shown at nine times the fundamental
frequency. Turn-off and turn-on pulses to the conducting devices
correspond to the crossing of the sawtooth wave with the sine wave
of the corresponding phase. The negative slope of the sawtooth
wave crossing sine wave of phase a results in turn-on pulse for
device 1 and turn-off for device 2, and vice versa for the positive
slope of the sawtooth wave. The resulting ac voltage with respect to
midpoint N is shown in shaded blocks.
Any even multiple of sawtooth frequency will create asymmetry
about zero crossing. The ac voltage can be changed by increasing
or decreasing the amplitude of the sine wave, considering sawtooth
voltage wave of constant magnitude. Increasing amplitude of sine
wave will increase conduction of device 1 and decrease conduction
POWER ELECTRONIC EQUIPMENT AND FACTS
405
time of device 2. The ac voltage varies linearly with variation of ac
control voltage from zero to maximum. If the control ac voltage
peak and the sawtooth voltage peak are the same, the middle notch
will disappear. The output voltage can become a rectangular wave
per cycle. Harmonics are produced, though even harmonics and
triplen harmonics are absent due to symmetry. Developments of
five-level converters are described in Refs. 4 and 5.
15-4
STATIC VAR COMPENSATOR (SVC)
The var requirements in transmission lines swing from lagging to
leading, depending upon the load. Shunt compensation by capacitors and reactors is one way. However, it is slow, and power circuit
breakers have to be derated for frequent switching duties. This
does not provide variable control of the reactive power requirements, and the compensation can be varied only in some discrete
steps. A compensator can not only provide variable fast reactive
power compensation, but it can also regulate the bus voltage and
improve transient stability. In Chap. 7, we discussed that for a
transmission line the best location for the var compensation is at
the midpoint of the line. More recently gate turn-off devices have
been used to supply and absorb reactive power without the use of
capacitors and inductors.
The IEEE and CIGRE definition of a static var generator (SVG)
embraces different semiconductor power circuits with their internal control enabling them to produce var output proportional to
an input reference. A SVG becomes an SVC when equipped with
external or system controls which derive its reference from power
system operating requirements and variables. SVCs can be classified into the following categories:
■
Thyristor-controlled reactor(TCR) (Fig. 15-13a)
■
Thyristor-switched capacitor (TSC) (Fig. 15-13b)
■ Fixed capacitor and thyristor-controlled reactor (FC-TCR)
(Fig. 15-13c)
■ Thyristor-switched capacitor and thyristor-controlled reactor
(Fig. 15-13d )
15-4-1
FC-TCR
An FC-TCR (Fig. 15-13c) provides discrete leading vars from the
capacitors and continuously lagging vars from thyristor-controlled
reactors. The capacitors are used as tuned filters, as considerable
harmonics are generated by thyristor control. The design parameters consider the following:
■ Stabilization of the system voltage, within certain limits,
around the rated voltage under normal operating conditions
■ Reduction of voltage fluctuations following a system
disturbance
■ Control of the reactive load flow between the network and
FC-TCR
F I G U R E 1 5 - 1 2 Pulse width modulation (PWM), triangular wave
frequency nine times the fundamental frequency. One phase leg of three-level
converter in Fig. 15-11a is shown.
■
Damping power swings in the system
■
Compensation or reduction of reactive power unbalance
■
Improvements in transient stability
The steady-state characteristics of an FC-TCR are shown in
Fig. 15-14. The control range is AB with a positive slope, determined by the firing angle control.
Qa = | bc − b1(α ) | V 2
(15-10)
406
CHAPTER FIFTEEN
producing a 90° lagging current (ignoring the resistance). If the
gating is delayed, the waveforms in Fig. 15-15b will result. The
instantaneous current through the reactor can be written as:
V
(cos α − cos ω t ) for α < ω t < α + β
X
= 0 for α + β < ω t < α + π
i= 2
(15-11)
where V is the line-to-line fundamental rms voltage, a is the gating
angle, and b is the conduction angle. The fundamental component
can be written as:
If =
β − sin β
V
πX
(15-12)
Assuming balanced gating angles, only odd harmonics are produced; their rms value is given by:
Ih =
4V sin(h + 1)α sin(h − 1)α
sinh α
+
− cos α
π X 2(h + 1)
h
2(h − 1)
(15-13)
Harmonic filters are provided to mitigate the harmonics.
15-4-2 TSC-TCR
FIGURE 15-13
Conceptual circuit diagrams: (a) Thyristorcontrolled reactor (TCR). (b) Thyristor-switched capacitor (TSC). (c) Thyristorcontrolled reactor with fixed capacitors. (d ) Thyristor-controlled reactor and
thyristor-switched capacitor (TSC-TCR).
where bc is the susceptance of the capacitor, and b1(a ) the susceptance of the inductor at firing angle a. As the inductance is varied,
the susceptance varies over a large range. The voltage varies within
limits V ± DV. Outside the control interval AB, the FC-TCR acts
like an inductor in the high-voltage range and like a capacitor in
the low-voltage range. The response time is of the order of one to
two cycles. The compensator is designed to provide emergency
reactive and capacitive loading beyond its continuous steady-state
rating.
Consider a TCR, controlled by two thyristors, as shown in
Fig. 15-15a. If both thyristors are gated at maximum voltage, the
reactor is directly connected across the supply system voltage,
A TSC-TCR provides thyristors control for both the reactive power
control elements, the capacitors and reactors. Improved performance under large system disturbances and lower power loss are
obtained. Figure 15-16 shows the V-I characteristics. A certain
short-time overload capability is provided both in the maximum
inductive and capacitive regions (shown for the inductive region in
Fig. 15-16). Voltage regulation with a given slope can be achieved
in the normal operating range. The maximum capacitive current
decreases linearly with the system voltage, and the SVC becomes
a fixed capacitor when the maximum capacitive output is reached.
The voltage support capability decreases with a decrease in system
voltage.
The SVCs are ideally suited to control the varying reactive power
demand of large fluctuating loads, that is, rolling mills and arc furnaces, dynamic overvoltages due to load rejection, and in HVDC
converter stations for fast control of reactive power flow.
Compensation by sectionalizing is based upon a midpoint
dynamic shunt compensator. With a dynamic compensator at the
midpoint, the line tends to behave like a symmetrical line. The
power transfer equation for compensated lines was discussed in
Chap. 7. The advantage of static compensators is apparent. The
midpoint voltage will vary with the load, and an adjustable midpoint susceptance is required to maintain constant voltage magnitude. With rapidly varying loads, the reactive power demand
should be able to be corrected fast, with least overshoot and voltage
rise. Figure 15-17 shows transient power angle curves for uncompensated line, with phase angle shift, shunt compensation, and
series compensation. With the midpoint voltage held constant, the
angles between the two systems can each approach 90°, for a total
static stability limit angle of 180°.
The power system oscillation damping can be obtained by rapidly changing the output of the SVC from capacitive to inductive,
so as to counteract the acceleration and deceleration of interconnected machines. The transmitted electrical power can be increased
by capacitive vars when the machines accelerate, and it can be
decreased by reactive vars when the machines decelerate.
The SVCs do not have capability to control the active power
flow. The first application of the SVC to voltage control was demonstrated on the Tri-State G&T system in 1977 by General Electric
Co. Another SVC designed by Westinghouse and EPRI was operational in 1978.
POWER ELECTRONIC EQUIPMENT AND FACTS
FIGURE 15-14
FIGURE 15-15
Steady-state V-Q characteristics of a fixed capacitor and thyristor-controlled reactor (FC-TCR).
(a) Basic circuit of a thyristor-controlled reactor. (b) Current waveforms due to varying conduction and firing angles.
407
408
CHAPTER FIFTEEN
Example 15-1
Figure 15-18 is a simplified system configuration
connection for application of an SVC. Consider that a two-phase
short circuit occurs at t=0.1 s by closing switch SW and subsequently opening this switch at t=0.2 s, that is, the short-circuit
duration is 0.1 s. The SVC is rated for ± 50 Mvar and is controlled
in the line voltage control mode.
Figure 15-19 shows the associated transients and EMTP simulation of the system. Figure 15-19a shows voltages on 230-kV
bus 1, Fig. 15-19b shows the phase voltages at the load in per unit,
Fig. 15-19c shows the active and reactive power output of SVC and
load, and Fig. 15-19d shows the two-phase fault current. It is seen
that the SVC supplies 40 Mvar reactive transiently, yet the voltages
under fault conditions dip severely.
15-5
F I G U R E 1 5 - 1 6 V-I characteristics of a SVC (TSC-TCR) showing
reduced output at lower system voltages.
FIGURE 15-17
SERIES CAPACITORS
Series compensation is used for (1) voltage stability, as it reduces
the series reactive impedance to minimize the receiving-end voltage variations and the possibility of voltage collapse, (2) improvement of transient stability by increasing the power transmission by
maintaining the midpoint voltage during swings of the machines,
and (3) power oscillation damping by varying the applied compensation so as to counteract the accelerating and decelerating
P-d characteristics. A: uncompensated line; B: with phase-angle regulator; C: with midpoint shunt compensation; and D: with
series compensation.
FIGURE 15-18
Application of a ±50 Mvar SVC for study of transients under two-phase–to–ground fault conditions.
POWER ELECTRONIC EQUIPMENT AND FACTS
swings of the machines. A fixed type of series compensation can,
however, give rise to subsynchronous oscillations.
An implementation schematic of the series capacitor installation
is shown in Fig. 15-20. The performance under normal and fault
conditions should be considered. Under fault conditions, voltage
across capacitor rises, and unlike a shunt capacitor, a series capacitor sees many times its rated voltage due to fault currents. A zinc
oxide varistor in parallel with the capacitor may be adequate to
limit this voltage. In some applications, the varistor will reinsert
the bank immediately on termination of a fault. For locations with
high fault currents, a parallel fast-acting triggered gap is introduced
which operates for more severe faults. When the spark gap triggers,
it is followed by closure of bypass breaker. Immediately after the
fault is cleared, to realize the beneficial effect of series capacitor on
409
stability, it should be reinserted quickly, and the main gap is made
self-extinguishing. A high-speed reinsertion scheme can reinsert
the series capacitors in a few cycles. The bypass switch must close
at voltages in excess of nominal, but not at levels too low to initiate main gap spark-over. The varistor should be properly chosen,
based on:
■ Maximum voltage appearing across capacitor at specified
current, normally determined by system studies.
■ Energy-handling capability, which is the thermal
capability—the maximum temperature at which the varistors
can continue to operate and withstand capability, that is, maximum short-time energy that can be withstood.
F I G U R E 1 5 - 1 9 (a) Phase voltages on 230-kV bus 1 of Fig. 15-18. (b) Phase voltages at load. (c) SVC P and Q and load Q transients. (d ) Two-phase
fault currents, fault cleared in 100 ms. (Continued )
410
CHAPTER FIFTEEN
FIGURE 15-19
■ Extremely large currents at high frequency will be present,
and these may produce a large overpressure within the enclosure. The varistors are a special design for the series capacitor
application.
The discharge reactor limits the magnitude and frequency of the
current through the capacitor when the gap sparks-over. This prevents damage to the capacitors and fuses. A series capacitor must be
capable of carrying the full line current. Its reactive power rating is:
I 2 X c per phase
(15-14)
Thus, the reactive power output varies with the load current.
Figure 15-21 shows the impact of series versus shunt compensation
(Continued )
at midpoint of a transmission line. Both systems are, say, designed to
maintain 95 percent midpoint voltage. The midpoint voltage does
not vary much when an SVC is applied, but with series compensation, it varies with load. However, for a transfer of power higher
than the SVC control limit, the voltage falls rapidly as the SVC hits
its ceiling limit, while series compensation holds the midpoint voltage better.
A series capacitor has a natural resonant frequency given by:
fn =
1
2π LC
(15-15)
where fn is usually less than the power system frequency. At this frequency, the electrical system may reinforce one of the frequencies of
POWER ELECTRONIC EQUIPMENT AND FACTS
FIGURE 15-20
FIGURE 15-21
Schematic diagram of a series capacitor installation.
Series versus shunt compensation; power transfer characteristics for a midpoint compensated line.
the mechanical resonance, causing subsynchronous resonance (SSR).
If fr is the subsynchronous resonance frequency of the compensated
line, then at resonance
2π fr L =
1
2π frC
411
(15-16)
fr = f K sc
This shows that the subsynchronous resonance occurs at frequency
fr, which is equal to normal frequency multiplied by the square
root of the degree of compensation, typically, between 15 to 30 Hz.
As the compensation is in 25 to 75 percent range, fr is lower than f.
The transient currents at subharmonic frequency are superimposed
upon power frequency component and may be damped out within
a few cycles by the resistance of the line. Under certain conditions,
subharmonic currents can have a destabilizing effect on rotating
machines. If the electrical circuit oscillates, then the subharmonic
component of the current results in a corresponding subharmonic
field in the generator. This field rotates backward with respect to the
main field and produces an alternating torque on the rotor at the difference frequency f-fr. If the mechanical resonance frequency of the
shaft of the generator coincides with this frequency, damage to the
generator shaft can occur. A dramatic voltage rise can occur if the generator quadrature axis reactance and the system capacitive reactance
are in resonance. There is no field winding or voltage regulator to
412
CHAPTER FIFTEEN
control quadrature axis flux in a generator. Magnetic circuits of
transformers can be driven to saturation and surge arresters can fail.
The inherent dominant subsynchronous frequency characteristics of
the series capacitor can be modified by a parallel connected TCR.
If the series capacitor is thyristor- or GTO-controlled, then the
whole operation changes. It can be modulated to damp out any subsynchronous as well as low-frequency oscillations.
Example 15-2 Consider a 300-MVA, 22-kV generator, connected to a step-up transformer of 350 MVA, which is delta-wye
connected, 22–400 kV, wye windings solidly grounded, which
feeds into a 400-mi long line. A CP model of the transmission line
is modeled. A series capacitor compensation of 50 percent at the
midpoint of the transmission line is provided. For subsynchronous
FIGURE 15-22
oscillations, the shaft mass system of steam turbine generators is
modeled with a number of masses of certain inertia constants connected together through spring constants. External torques can
be applied to each of the masses, for example, turbine, generator,
and exciter masses (see Chap. 16). An EMTP simulation of the frequency scan at the 400-KV side of the step-up transformer is shown
in Fig. 15-22a. This shows resonances at 19 Hz and close to the
fundamental frequency. A three-phase fault occurs at the secondary
of the transformer at 1 s, and cleared at 1.1 s, fault duration of
6 cycles. The resulting torque transients in the 300-MVA synchronous machine masses are shown in Fig. 15-22b, total simulation time
5 s. It is seen that these transients do not decay even after 4 s of fault
clearances and depending upon the system parameters, can even
(a) Frequency scan of 400-kV line. (b) Shaft transients for three-mass model. (c) Angular speed transient mass 1, with no external torque.
POWER ELECTRONIC EQUIPMENT AND FACTS
FIGURE 15-22
413
(Continued )
F I G U R E 1 5 - 2 3 (a) GTO-controlled series capacitor. (b) Turn-off delay control. (c) Compensating voltage versus current characteristics with voltage
control mode. (d ) Reactance control mode.
diverge, imposing stresses on the generator shaft and mechanical
systems. The angular frequency of mass 1 (zero external torque
which will give maximum swings) is plotted in Fig. 15-22c. This
shows violent speed variations. The frequency relays or vibrations
probes may isolate the generator from the system.
15-5-1
GTO-Controlled Series Capacitor
A series capacitor can be controlled by parallel thyristors/GTOs.
Figure 15-23a shows a GTO-controlled series capacitor (GCSC)
scheme, which changes the impedance of the circuit. The objective
414
CHAPTER FIFTEEN
is to control the voltage Vc across the capacitor at a given line current I. When the GTO is conducting, then the voltage across the
capacitor is zero, and when nonconducting it is at the maximum.
For controlling the voltage, the closing and opening of the GTO
can be controlled in synchronism with the power frequency; a positive half cycle control is shown in Fig. 15-23b. The GTO valve is
controlled to close whenever the capacitor voltage crosses zero. The
turnoff in each half cycle is controlled by turn-off delay angle a
(0 ≤ α ≤ π / 2). Capacitor voltage at a=0 and at a finite angle a is
clearly shown. The capacitor voltage can be expressed as:
ωt
Vc =
I
1
i(t )dt =
(sin ω t − sin α )
ωC
C α∫
(15-17)
The voltage can, therefore, be continuously controlled. Varying
the fundamental capacitor voltage at a fixed line current can be
considered variable capacitive impedance. We can write that the
fundamental capacitor voltage is equal the capacitive reactance as a
function of delay angle a.
Vc (α ) = X c (α ) =
2
1
I
1 − α − 2α
ω C π
π
(15-18)
The two modes of operations are voltage control mode and the
impedance compensation mode, which are shown in Fig. 15-23c
and d, respectively. In the voltage compensation mode, Xc is selected
to maintain rated compensating voltage at Imin. As the current
increases, the delay angle is increased to reduce the capacitor injection, thereby maintaining the compensating voltage with increased
current. In the impedance compensation mode, maximum Xc
is maintained at any line current up to the maximum. Xc is chosen to provide maximum compensation at rated current, that is,
Xc = Vcmax/Imax. For zero compensating impedance, the capacitor is
bypassed by the GTO, and for the maximum compensation, GTO
is open and the capacitor is fully inserted. Harmonics analogous to
TCR are produced:
Vh =
I 4 sin α cos(hα ) − n cos α sin(hα )
,
ω C π
h(h 2 − 1)
where n = 2k + 1
k = 1, 2, 3 .....
15-6
(15-19)
FACTS
The concept of flexible ac transmission systems was developed by
EPRI and many FACTS operating systems are already implemented.6
The world’s first thyristor-controlled series capacitor was put in service on Bonneville Power Authority’s 500-KV line in 1993. FACTS
are made possible by modern high-power electronics and the fast
speed of operation. We refer to the devices used in the transmission
systems, voltage levels 121 kV and upward, as FACTS, and the
devices applied at 3 to 34 kV, Distribution custom power.
We have examined the problem of power flow over transmission
lines and role of SVCs series and shunt compensation to change
the impedance of the line or its transmission angle. Advances in
recent years in power electronics, software, microcomputers, and
fiber optic transmitters that permit signals to be sent to and fro from
high-voltage levels make possible the design and use of fast FACTS.
Another thrust leading to FACTS is the use of electronic devices in
processes, industry, and the home which has created an entirely new
demand for power quality that the energy providers must meet. Power
quality problems include voltage sags and swells, high-frequency
line-to-line surges, steep wave fronts or transients caused by switching of loads, harmonic distortions, and outright interruptions, which
may extend over prolonged period (see Chap. 19). The tolerance of
TA B L E 1 5 - 2
APPLICATION
Applications of FACTS Devices
STATCOM
SSSC
UPFC
Voltage control
x
x
x
Var compensation
x
NGR-SSR
DAMPER
x
Series impedance control
x
x
MW flow control
x
x
x
Transient stability
x
x
x
x
Dynamic stability
x
x
x
x
x
x
x
x
x
System isolation
Damping of oscillations
x
processes to power quality problems are being investigated more
thoroughly, however, the new processes and electronic controls are
more sensitive to power quality problems.
The basic electronic devices giving rise to this thrust in the
power quality are tabulated in Table 15-2, with their applications.
FACTS devices control the flow of ac power by changing the impedance of the transmission line or the phase angle between the ends
of a specific line. FACTS controllers can provide the required fast
control by increasing or decreasing the power flow on a specific
line and responding almost instantaneously to stability problems.
FACTS devices can be used to dampen the subsynchronous oscillations which can be damaging to rotating equipment, that is, generators. These devices and their capabilities are briefly discussed in
this chapter.
15-7
SYNCHRONOUS VOLTAGE SOURCE
A solid-state synchronous voltage source (SS) can be described
analogous to a synchronous machine. A rotating synchronous condenser has a number of desirable characteristics, that is, high capacitive output current at low voltages and source impedance that does
not cause harmonic resonance with the transmission network. It
has a number of shortcomings too, that is, slow response, rotational
instability, and high maintenance.
An SS can be implemented with voltage source inverter using
GTOs. An elementary six-pulse voltage source inverter with a dc
voltage source can produce a balanced set of three quasi- square
waveforms of a given frequency. The output of the six-pulse inverter
will contain harmonics of unacceptable level for transmission-line
application, and multipulse inverters can be implemented by a variety of circuit arrangements.
The reactive power exchange between the inverter and the
ac system can be controlled by varying the amplitude of the
three-phase voltage produced by an SS. Similarly, the real power
exchange between the inverter and the ac system can be controlled
by phase-shifting the output voltage of the inverter with respect to
the ac system. Figure 15-24a shows the coupling transformer, the
inverter, and an energy source which can be dc capacitor, battery,
or superconducting magnet.
The reactive and real power generated by the SS can be controlled
independently and any combination of real-power generation/
absorption with var generation and absorption is possible as shown
in Fig. 15-24b. The real power supplied/absorbed must be supplied
by the storage device, while the reactive power exchanged is internally generated in the SS. The reactive power exchange is controlled
by varying the amplitude of three-phase voltage. For a voltage
greater than the system voltage, the current flows through the reactance from the inverter into the system, that is, the capacitive power
is generated. If the amplitude of output voltage is reduced below
POWER ELECTRONIC EQUIPMENT AND FACTS
F I G U R E 1 5 - 2 4 (a) Basic circuit of a shunt-connected static synchronous source (SS). (b) Possible modes of active and reactive power
compensation.
that of system voltage, the inverter absorbs reactive power. The reactive power is, thus, exchanged between the system and the inverter,
and the real power input from the dc source is zero. In other words,
the inverter simply interconnects the output terminals in such a way
that the reactive power currents can freely flow through them.
The real power exchange is controlled by phase shifting the output voltage of the inverter with respect to the system voltage. If the
inverter voltage leads the system voltage, it provides real power to
the system from its storage battery. This results in a real component
of the current through tie reactance, that is, in phase opposition to
the ac voltage. Conversely, the inverter will absorb real power from
the system to its storage device if the voltage is made to lag the system voltage. This bidirectional power exchange capability of the SS
makes possible the complete temporary support of the ac system.
15-8
STATIC SYNCHRONOUS COMPENSATOR
The three-phase 12-pulse bridge (Fig. 15-11) can be used in the
schematic of an inverter-based shunt static synchronous compensator (STATCOM), sometimes called static condenser (STATCON).
415
Its power and control circuit is essentially shown in Fig. 15-25. It
is a shunt reactive power compensating device and can be considered as an SS with storage device as a dc capacitor. A GTO-based
power converter produces an ac voltage in-phase with the transmission line voltage. When the voltage source is greater than the
line voltage (V < V0), leading vars are drawn from the line and the
equipment appears as a capacitor; when voltage source is less than
the line voltage (V>V0 ), lagging reactive current is drawn. The
basic building block is a voltage-source inverter which converts dc
voltage at its terminals to three-phase ac voltage. A STATCON may
use many six-pulse inverters, output phase-shifted and combined
magnetically to give a pulse number of 24 or 48 for the transmission systems. Using the principle of harmonic neutralization, the
output of n inverters, with relative phase displacements, can be
combined to produce an overall multiphase system. The output
waveform is nearly sinusoidal, and the harmonics present in the
output voltage and input current are small. This ensures waveform
quality without passive filters. Figure 15-26 shows the output
voltage and current waveform of a 48-pulse STATCON, generating
reactive power.
The V-I characteristics are shown in Fig. 15-27. As compared to
the characteristics of an SVC, a STATCON is able to provide rated
reactive current under reduced voltage conditions. It also has transient overload capacity, both in the inductive and capacitive region;
the limit is set by the junction temperature of the semiconductors.
By contrast a SVC can only supply diminishing output current with
decreasing system voltage. The ability to produce full capacitive
current at low voltages makes it ideally suitable for improving the
first swing (transient) stability. Dynamic performance capability far
exceeds that of a conventional SVC. It has been shown that the
current system can transition from full-rated capacitive to full-rated
inductive vars in approximately a quarter cycle.
A STATCON, just like an SVC behaves like an ideal midpoint
compensator, until the maximum capacitive output current is
reached. The reactive power output of a STATCON varies linearly
with the system voltage, while that of an SVC varies with the square
of the voltage. In an SVC, thyristor-controlled reactors produce
high harmonic content, as the current waveform is chopped off in
the phase-controlled rectifiers and passive filters are required. A
STATCON uses phase multiplication or pulse-width modulation
and the harmonic generation is a minimum. Figure 15-28 shows
PWM, the reference voltage, the triangular carrier, and the desired
output voltages. The PWM signals are produced using two-carrier
triangular signals; two different offsets of opposite sign are added
to the triangular waveform to give the required carriers. These are
compared with the reference voltage waveform, and the output and
its inverse is used for the gating signals—four gating signals, one for
each IGBT in a leg. Compare this with Fig. 15-12.
The gating signals for the GTOs are generated by the internal
converter control in response to the demand for reactive power
and/or real power reference signals. The reference signals are provided by the external or system control, from operator intervention,
and system variables, which determine the functional operation of
STATCOM. If it is operated as an SVC, the reference input to the
internal control is the reactive current. The magnitude of the ac
voltage is directly proportional to the dc capacitor voltage. Thus,
the internal control should establish the required dc voltage on the
capacitor.
The internal controls must establish the capability to produce a
synchronous output voltage waveform that forces the real and reactive power exchange with the system. As one option, the reactive
output current can be controlled indirectly by controlling the dc
capacitor voltage (as magnitude of ac voltage is directly proportional
to the dc capacitor voltage),which is controlled by the angle of the
output voltage. Alternatively, it can be directly controlled by internal
voltage control mechanism, that is, PWM of the converter, in which
case, the dc voltage is kept constant by control of the angle.
416
CHAPTER FIFTEEN
FIGURE 15-25
Schematic diagram of a STATCON (or STATCOM) with internal control circuit block diagram.
must absorb from the system to supply losses. Summarizing, the
following advantages are obtained:
■
Interface real power sources
■
Higher response to system changes
■
Mitigation of harmonics as compared to an FC-TCR
■
Superior low-voltage performance
A STATCON of ±100 Mvar is installed at TVA system at Sullivan.6
15-9 STATIC SERIES SYNCHRONOUS
COMPENSATOR
FIGURE 15-26
Output voltage and current waveforms for a
48-pulse converter generating reactive power.
The control circuit in Fig. 15-25 shows a simplified block circuit
diagram of an internal control. The inputs to the internal control
are V, the system voltage (obtained through potential transformers),
and the output current of the converter I0, which is broken into
active and reactive components. These components are compared
with an external reactive current reference, determined from the
compensation requirements, and the internal real current reference, derived from dc voltage regulation loop. Voltage V operates a
phase-locked loop that produces the synchronizing signal angle q.
The reactive current error amplifier produces control angle a. After
amplification, the real and reactive current signals are converted
into magnitude and angle of the required converter output voltage.
The dc voltage reference determines the real power the converter
A static series synchronous compensator (SSSC) may also be called
a series power flow controller (SPFC). The basic circuit is that of
an SS which is in series with the transmission line (Fig. 15-29). We
have observed that conventional series compensation can be considered as reactive impedance in series with the line, and the voltage across it is proportional to the line current. A series capacitor
increases the transmitted power by a certain percentage, depending
upon the series compensation for a given load. In contrast, a SSSC
injects a compensating voltage, Vq, in series with the line irrespective
of the line current. The transmitted power is:
P=
δ
V2
V
sin δ +
V cos
2
X sc
X sc q
(15-20)
The transmitted power is increased by a fixed percentage
over the power capability of an uncompensated line, in the range
0 ≤ δ ≤ 90 °. While a capacitor can only increase the transmitted power, the SSSC can also decrease it by simply reversing the
POWER ELECTRONIC EQUIPMENT AND FACTS
FIGURE 15-27
FIGURE 15-28
V-I characteristics of a STATCON.
(a) Offset triangular carrier waves and reference voltage waveform. (b) Phase and (c) line voltages.
polarity of the injected voltage. The reversed voltage adds directly
to the reactive power drop in the line, as if the reactive line impedance is increased. If this reversed polarity voltage is larger than the
voltage impressed across the line, by sending and receiving end
systems, that is:
| Vq | > | Vs − V | + IX L
417
(15-21)
the power flow will reverse.
Thus, stable operation of the system is possible with positive
and negative power flows, and due to response time being less
than a cycle, the transition from positive to negative power flow
is smooth and continuous. Figure 15-30a and b compares the P/d
curves of a series capacitor and SSSC. Figure 15-30b shows reversal
of power with the SSSC.
Therefore, the SSSC can negotiate both the reactive and active
power with ac system, simply by controlling the angular position
of the injected voltage with respect to the line current. One important application is simultaneous compensation of both reactive and
resistive elements of the line impedance. By applying series compensation, the X/R ratio decreases. As R remains constant the ratio
is now (XL − Xc)/R. As a result, the reactive component of the current supplied by the receiving-end system progressively increases,
while the real component of the current transmitted to the receiving end progressively decreases. An SSSC can inject a component
of voltage in antiphase to that developed by the line resistance
418
CHAPTER FIFTEEN
F I G U R E 1 5 - 2 9 Functional block diagram of static synchronous
series compensator (SSSC), with voltage source converter.
drop to counteract the effect of resistive voltage drop on the power
transmission.
The dynamic stability can be improved, as the reactive line compensation with simultaneous active power exchange can dampen
power system oscillations. During periods of angular acceleration
FIGURE 15-30
(increase of torque angle of the machines), an SSSC with a suitable
energy dc supply (which can be from a bus or any other source)
can provide maximum capacitive line compensation to increase the
active power transfer and also absorb active power, acting like a
damping resistor in series with the line.
The problems of subsynchronous resonance stated in Section 15-5
are avoided. SSSC is essentially an ac voltage source which operates only at the fundamental frequency, and its output impedance at
other frequencies, theoretically, will be zero, though SSSC does have
a small inductive impedance of the coupling transformer. An SSSC
does not form a series resonant circuit with the line inductance,
rather it can damp out the subsynchronous oscillations that may be
present due to existing series capacitor installations.
Figure 15-31 shows the characteristics of an SSSC. The VA
rating is simply the product of maximum line current and the
maximum series compensating voltage. Beyond the maximum
rated current, the voltage falls to zero. The maximum current rating is practically the maximum steady-state line current. In many
practical applications, only capacitive series line compensation is
required, and an SSSC can be combined with a fixed series capacitor. If the device is connected to a short line with infinite buses,
unity voltages at sending and receiving ends, and constant phase
angle difference, the characteristic can be represented by a circle7
in P-Q plane with:
S0 Z *
2R
S Z*
Radius = 0
2R
Center =
(15-22)
(a) P-d characteristics of series capacitor compensation. (b) P-d characteristics of SSSC as a function of the compensating voltage Vq.
POWER ELECTRONIC EQUIPMENT AND FACTS
419
versus SSSC. As SSSC can decrease the power transfer by behaving
inductively, it acts akin to phase angle regulator (PAR). The portion of the characteristic to the left of origin shows power reversal
capability of an SSSC.
15-10
FIGURE 15-31
SSSC V-I characteristics with overload capability
shown in dotted lines.
where Z* is the complex conjugate of Z, the line series impedance =
R + j XL and S0 =P0 +jQ0 is theuncompensated power flow. The
operating characteristics are defined by the edge of the circle only.
From Eq. (15-22) the maximum theoretical power amplification is
defined as the ration:
| S / S0 | =
Z*
2R
(15-23)
This is approximately 50 percent of the X/R ratio. A comparison can be made with series variable compensation, with respect to
Fig. 15-32, which shows the characteristics for series compensation
UNIFIED POWER FLOW CONTROLLER
A unified power controller consists of two voltage source-switching
converters, a series and shunt converter, and a dc link capacitor
(Fig. 15-33). This can be considered a combination of an SSSC
and a STATCON. The arrangement functions as an ideal ac-to-ac
power converter in which real power can flow in either direction
between ac terminals of the two converters and each converter
can independently generate or absorb reactive power at its own
terminals. Converter 2 injects an ac voltage Vpq with controllable
magnitude and phase angle (0 to 360°) at the power frequency in
series with the line. This injected voltage can be considered as an
SS. The current I and Vpq result in an active and reactive power
exchange between it and the ac system. The real power exchanged
at the ac terminal is converted into dc power which appears as dc
link voltage.
The basic function of Converter 1 is to absorb the real power
demanded by Converter 2 at the dc link. This dc link power is
converted back to ac and coupled to a transmission line through
a shunt transformer. Converter 1 can also generate or absorb controllable reactive power, and thereby provide independent shunt
reactive compensation of the line. The real power supplied to the
system by the series converter must be taken from the system by
Converter 1.
Consider the power transfer characteristics in a two-machine
system through a reactance with a UPFC connecting two infinite
buses, unity voltage. If the injected voltage Vpq is zero, the system is
like a conventional system. The control characteristics can be illustrated as follows, with respect to Fig. 15-34. If we make Vpq = ±D V
(angle q =0), that is, change only the magnitude with constantly
variable in-phase and antiphase injection, terminal voltage regulation is obtained (Fig. 15-34c). This is like an under load tap changing (ULTC) transformer with an infinite number of taps in the
control region.
Series reactive compensation (Fig. 15-34d) is obtained by injecting Vpq=Vc in quadrature with current I. This is similar to series
compensation obtained by series capacitive and inductive line compensation attained by the SSSC. The injected series voltage can be
kept constant, independent of the current variation. Alternatively, it
can be varied in proportion to the line current to obtain compensation, much akin to a series capacitor.
Phase angle control is shown in Fig. 15-34e. Here Vpq = Vb is
injected with an angular relationship with respect to Vs. This
achieves the desired phase shift b (advance or retard), without
change in the magnitude. Thus, UPFC can act as a perfect phase
angle regulator, which can supply reactive power with internal var
generation.
Finally, Fig. 15-34f shows an operation unique to UPFC. Multifunction power flow control based upon terminal voltage regulation (Fig. 15-34c), series capacitive compensation (Fig. 15-34d),
and phase shifting Fig. 15-34e can be combined:
Vpq = D V + VC + Vβ
(15-24)
With no injection of Vpq, and in terms of normalized maximum
power, we can write:
V2
sin δ = sin δ (V 2 /X ) = 1
X
V2
Q=
(1 − cos δ ) = 1 − cos δ
X
P=
FIGURE 15-32
Operating characteristics of SSSC in P-Q plane
showing comparison with variable series capacitor compensation.
(15-25)
420
CHAPTER FIFTEEN
FIGURE 15-33
Schematic of UPFC controller with two voltage source converters and dc link.
F I G U R E 1 5 - 3 4 (a) Basic circuit to illustrate UPFC action and injected voltage Vpq in a two-bus system. (b) Phasor diagram and relevant angles.
(c) Voltage regulation only. (d ) Line impedance compensation. (e ) PAR (phase angle regulator). (f ) Control of voltage, impedance, and angle.
POWER ELECTRONIC EQUIPMENT AND FACTS
Therefore:
(15-26)
[Q(δ ) + 1]2 + [P(δ )]2 = 1
which is the equation of a circle (Fig. 15-35a). With compensation through UPFC, Vpq, the transmitted power P and the reactive
power –jQ, supplied by receiving end is given by:
Vs + Vpq − Vr *
P − jQ = Vr
jX
(15-27)
The asterisk means conjugate of the complex number. The power
transfer characteristics of a UPFC for two-machine system connected through a short line of reactance X can be represented by a
circle on P-Q plane, described by:
V × Vpq max
(PR − P0 )2 + (QR − Q0 )2 =
X
FIGURE 15-35
2
(15-28)
421
where P0, and Q0 are the line uncompensated real and reactive
power, respectively. The center is at the uncompensated power level
S0 and radius is Vpq/X.
The operation of P-Q control is shown with respect to transmission angles d of 0°, 60°, and 90°, in Fig. 15-35b, c, and d, respectively.
Consider Vpq max =0.5 pu, X=1.0 pu, V = 1 pu, that is, the UPFC
circle =0.5 pu, which can be placed at any transmission angle. At
d=0°, no active and reactive power can be transmitted, and UPFC
will improve active power flow by 0.5 pu in either direction, without impacting reactive power flow. This assumes that the sendingand receiving-end sources should be able to absorb the active power
without change of angle, though UPFC can force the system to
supply or absorb reactive power from the other end. At d=60°, the
control range of active and reactive power is given by P1 −P2 and
0 −Q1. Figure 15-35d shows the controllable region for d=90°.
The allowable operating range with UPFC is anywhere inside the
circle, while the SPFC operating range is the circle itself (Fig. 15-36).
A comparison with phase angle regulator and series capacitors is
superimposed in this figure. These devices provide one-dimensional
(a) P-Q plot of an uncompensated line. (b) UPFC compensation placed at d = 0˚, (c) 60˚, and (d ) 90˚.
422
CHAPTER FIFTEEN
15-11
F I G U R E 1 5 - 3 6 Relative control characteristics in P-Q plane of
UPFC: variable series capacitor and PAR.
control, while UPFC provides simultaneous and independent P and
Q control over a wide range. This figure is drawn for:
■
UPFC with Vpq=0.25 pu
■
Fixed plus variable capacitor with 30 to 50 percent
compensation
■
Phase angle regulator with a symmetrical no-load shift of
14.4°.7
FIGURE 15-37
NGH-SSR DAMPER
Subsynchronous resonance can occur with series compensation
Section 15-5. Many countries around the world including the
United States and Canada use series compensation for the transmission lines, but SSR and possible higher stresses on machine shafts is
of consideration. NGH-SSR (Narain Hingorani—the inventor) subsynchronous resonance suppressor counteracts subsynchronous
resonance. The principle of operation can be explained with reference to Fig. 15-37a. The subsynchronous voltage VC, when combined with 60-Hz voltage wave Vf, produces a voltage Va, shown in
dotted lines in this figure. Note that some half-cycles of Va become
longer than the normal half-cycle period of 8.333 ms. These distorted waveshapes represent the voltage across the capacitor. This
unbalance charge on the capacitor interacts with system inductance
to produce oscillations. If this unbalance charge is eliminated,
the system will be detuned to any other frequency, other than the
fundamental.
The basic scheme (Fig. 15-37b) consists of an impedance in
series with thyristor switch is connected across the capacitor. The
impedance is a small resistance determined from the peak current
capability of the thyristor switch in series with a inductor, the value
of which is dictated by di/dt limit of the thyristors. The thyristor
switch is controlled so that when a current zero is detected, the
following half-cycle period is timed. If the half-cycle exceeds the
set time of 8.33 ms, the corresponding thyristor is turned on to
discharge the capacitor and bring about a current zero sooner. The
switch stops conducting when the current zero is obtained. At each
capacitor voltage zero, a new count starts.
With advancements in modern power electronics and control,
FACTS are becoming more attractive for improving the operation
of power systems at all levels of electrical energy. Table 15-2 shows
application of FACTS controllers, while Table 15-3 shows custom
power solutions that can be applied at utility end and customer
(a ) Superimposition of a 60-Hz wave on a subsynchronous oscillation. (b ) Principle of NGH-SSR damper.
POWER ELECTRONIC EQUIPMENT AND FACTS
TA B L E 1 5 - 3
Custom Power Solutions of Power Quality Problems
DISTURBANCE
UTILITY-SIDE SOLUTIONS
CONSUMER-SIDE SOLUTIONS
Voltage sags
Dynamic voltage restorer (DVR)
Static condenser
DSTATCON
Line conditioner
UPS systems
Voltage swells
DVR
Fault current limiter
High-energy surge arrester
Line conditioner
UPS
Voltage regulator
Interruption
Solid-state circuit breaker
DSTATCON
UPS
M-G set
Harmonic distortion
Active and passive filters
DVR
DSTATCON
Harmonic filters
Line conditioner
Noise
-
Grounding and shielding
Filters
Line conditioner
Transients
Surge arresters
Surge suppressors
Line conditioner
end. We see that the DVR and DSTATCOM are synonymous with
FACTS-UPFC and STATCOM controllers.
15-12
The fundamental power relations, when the current and voltage
waveforms are distorted, due to any reason—applications of nonlinear loads, power electronics, and harmonic resonance—need to
be redefined. Nonlinearity also occurs in conventional power systems, for example, saturation, tooth ripples, and harmonic torques
in motors, switching of transformers, which produce distortions in
the current and voltage waveforms.
For sinusoidal waveforms, by definition:
= P sec φ = P /cosφ
In terms of fundamental currents and voltages (no harmonics and
distortions):
Q = V f I f sin(φ − δ )
(15-31)
S = Vf I f
where Vf, and If are the fundamental rms currents and voltages,
respectively. In presence of harmonics, change definition of reactive
power as:
∞
Sh = V f I 2f + ∑ Ih2 = P 2 + Q 2 + D 2 = S 2f + D 2
h =2
(15-32)
2
=
1
1 + THDi
cos φ
(15-33)
π
q
sin
π
q
(15-34)
where q is the number of converter pulses and π/q is the angle in
radians, q ≠ 1. This ignores commutation overlap and no phase
retards and neglects transformer magnetizing current. For a sixpulse converter it will be 0.955. For a 12-pulse converter, the theoretical power factor will be 0.988. With commutation overlap and
phase retard, the power factor is:10
PFt =
P = V f I f cos(φ − δ )
S +D
2
f
This means total power factor is conventional power factor multiplied by displacement power factor. The current harmonic distortion THDi is defined in Chap. 6. The other theories with respect to
nonsinusoidal power relations are Fryze theory8 and Kusters and
Moore theory.9 The maximum theoretical power factor of a converter is given by the expression:
PFt =
(15-30)
Pf
= PFf × PFdisplacement
(15-29)
where S is the apparent power, P is the active power, and Q is the
reactive power. The power factor angle under these conditions is
defined as:
S
Q
φ = tan −1 = cos −1
P
P
Based upon Eq. (15-32), the power factor is:
PFT =
DISPLACEMENT POWER FACTOR
S = P 2 + Q 2 = P 2 + (P tan φ )2 = P (1 + tan φ 2 )
423
Ed′ I d
3ELI L
=
3
π
Ex
cos α − E
3 f ( µ, α )
do
1
(15-35)
where
Ed′ = Ed + Et + E f
Edis theaverage direct voltage under load, Etis theresistance
drop, Ef is thetotal forward drop per circuit element, Idis thedc
load current in average amperes, EL is theprimary line-to-line ac
voltage, IL is theac primary line current in amperes, α is thephase
retard angle, µ is theangle of overlap or commutation angle, Edois
424
CHAPTER FIFTEEN
thetheoretical dc voltage, and Ex is thedirect voltage drop due to
commutation reactance, and
sin µ[2 + cos(µ + 2α ) − µ[1 + 2 cos α cos(µ + α )
[2π cos α − cos(µ + α )]2
(15-36)
f (µ, α ) =
µ 2 + sin 2 µ − 2 µ sin µ cos µ
(15-37)
cosφ1 = cos[arc cosφ1′ + arc tan(1mag /I1 )]
(15-38)
where cos φ1′ is the displacement power factor, not including transformer magnetization current. See Ref. 1 for further details.
The instantaneous reactive power theory as propounded by Nabae
and Akagi11,12 is of much interest in control algorithms of switching compensators. It uses Clark’s transformation (Chap. 4) to transform three-phase quantities to two orthogonal axes, called here a
and b. The zero sequence components in the matrix are omitted.
The description of power properties of circuits, using instantaneous
voltage and current values, without use of Fourier transforms and
harmonic analysis, has drawn much interest and simplified the
mathematical operations. In the two coordinate system:
eb
iβ
2
=
3
1 −
1
2
−
1
2
3
3
−
0
2
2
(15-39)
ec
q
=
eα e β
iα
−e β e α
iβ
ib
(15-40)
ic
(15-41)
dW
dt
(15-42)
To define instantaneous reactive power, the space vector of imaginary power is defined as:
q = e α iβ + e β iα
1
3
(15-44)
[ia (e c − e b ) + ib (e a − e c ) + ic (e b − e a )]
−1
eα e β
p
−e β e α
0
+
eα e β
−e β e α
iα
iβ
iα p
=
0
q
iβ p
iαq
+
(15-45)
(15-46)
i βq
where iap is the a-axis instantaneous active current:
eα
p
e α2 + e β2
(15-47)
and iap is the a-axis instantaneous reactive current:
iα q =
eα
q
e α2 + e β2
(15-48)
also ibp is the b-axis instantaneous active current:
eα
p
e α2 + e β2
(15-49)
and ibp is the b-axis instantaneous reactive current:
eα
q
e + e β2
(15-50)
2
α
p = e α iα p + e β iβ p ≡ Pα p + Pβ p
(15-51)
0 = e α iα q + e β iβq ≡ Pα q + Pβq
p = e α iα + e β iβ
=
q
The following equations exist:
ia
Here p and q are not conventional watts and vars. These are defined
by the instantaneous voltages in one phase and the instantaneous
current in the other phase.
= e a ia + e b ib + e c ic =
p
−e β e α
This can be written as:
iβq =
Define instantaneous real and reactive powers as p and q, respectively, then:
p
=
iβ p =
ea
and:
iα
=
iα p =
15-13 INSTANTANEOUS POWER THEORY
eβ
iα
iβ
The above equations neglect the effect of transformer magnetizing currents. The correction for transformer magnetizing current is
approximately given by:
eα
iβ
eα e β
−1
sin 2 µ
1
1
1 −
−
2
2
2
=
3
3
3
−
0
2
2
−1
iα
This can be divided into two kinds of currents:
The displacement power factor is:
cos φ1′ =
Equation (15-43) can be written as:
(15-43)
where a-axis instantaneous active and reactive powers are:
Pα p =
−eα e β
e α2
p Pα q = 2
q
e + e β2
e α + e β2
2
α
(15-52)
The b-axis instantaneous active and reactive powers are:
Pβ p =
e β2
e +e
2
α
2
β
p Pβq =
eα e β
e + e β2
2
α
q
(15-53)
The sums of instantaneous active powers in the two axes coincides
with the instantaneous real power in the three-phase circuit, and
the instantaneous reactive powers cancel each other and make no
contributions from the source to the load.
This needs some explanation. In a converter, the instantaneous
reactive power is the power circulating between the source and
converter, while the instantaneous reactive power on the output
is the instantaneous reactive power between the converter and the
load. Therefore, there is no relation between the reactive powers on
the input and the output sides, and instantaneous imaginary power
POWER ELECTRONIC EQUIPMENT AND FACTS
on the input is not equal to the instantaneous imaginary power on
the output side. Assuming zero active power loss in the converter,
the active power on the input is equal to the active power output.
15-14
ACTIVE FILTERS
Mitigation of harmonics has been discussed using passive filters,
phase multiplication, or higher pulse number converters. Active
current shaping and active filters are yet other alternatives.
In active current shaping, the input current of the converters
can be forced to follow a sinusoid in phase with voltage, addressing the need for reactive power compensation as well as harmonic
elimination.13
Active filters inject harmonic distortion into the coupling point
of the nonlinear load which is of opposite polarity to the distortion
caused by the nonlinear load. These can be classified according to
their connections in the circuit:
425
equivalent circuit, and it can be implemented with a voltage-fed
PWM inverter to inject a harmonic current of the same magnitude
as the load, but of harmonics of opposite polarity. In the shunt connection (Fig. 15-38a), the load current will be sinusoidal so long
as the load impedance is much higher than the source impedance.
This means that the injected harmonic cancellation current Ifl flows
only in the source impedance Zs and none in the load impedance
IL, that is, the load impedance ZL is infinite. Practically, this will not
be achieved. A shunt connection with voltage source cancellation
inverter will be more effective where the output reactor resists the
change of current.
In a series connection, a voltage Vf is injected in the series with
the line and compensates the voltage distortion produced by the
nonlinear load. A series active filter is more suitable for harmonic
compensation of diode rectifiers where the dc voltage of the inverter
is derived from a capacitor, which opposes the change of voltage.
■
In series connection
■
In parallel shunt connection
1. Mathematically derive Eqs. (15-1), (15-6), and (15-8) of the text.
■
Hybrid connection of active and passive filters
2. The voltage underload flow at certain bus in an interconnected system dips by 10 percent, while the voltages on
adjacent buses are held constant. The available short-circuit
current at this bus is 21 kA, rms symmetrical, and voltage is
230 kV. Find the reactive power injection to restore voltage to
its rated value of 230 kV.
An obvious advantage of active filters is that the harmonics are eliminated at the source. The cost and available size are of consideration.14
The series and shunt connections are shown in Fig. 15-38a
and b. A harmonic current source can be represented by a Norton
PROBLEMS
3. Draw the circuit of a current-source six-pulse converter
with input transformers of 0° phase shift. Plot current profiles
in the input transformer windings—primary and secondary,
line currents, currents in each leg of the bridge circuit, and
the output current. Calculate their relative magnitudes. Repeat
with input transformer of −30° phase shift in the input transformer windings.
4. A 100-MVA load at 0.8 power factor and at 13.8 kV is supplied through a short transmission line of 0.1 pu reactance
(100-MVA base). Calculate the reactive power loss and the load
voltage. Size a capacitor bank at load terminals to limit the
voltage drop to 2 percent at full load. What are the capacitor
sizes for three-step switching to maintain the load voltage no
more than 2 percent below the rated voltage as the load varies
from zero to full load?
5. A 200-MW, 18-kV, 0.85-power factor generator is connected through a 200-MVA step-up transformer of 18 to
500 kV and of 10 percent reactance to 500 kV system. The
transformer primary windings are provided with a total of five
taps, two below the rated voltage of 2.5 and 5 percent, and two
above rated voltage of 2.5 and 5 percent and one at the rated
voltage. Assuming that initially the taps are set at rated voltage
of 18 to 500 kV, what is the generation voltage to take fullrated reactive power output from the generator? If the operating voltage of the generator is to be limited to the rated voltage,
find the tap setting on the transformer. Find the reactive power
loss through the transformer in each case. Neglect resistance.
6. A 100-mi long (160-km) line has series R=0.3 Ω,
L=3 mH, and shunt capacitive reactance = 0.2 MΩ /mi. It
delivers a load of 100 MVA at 0.85 power factor at 138 kV. If
the sending-end voltage is maintained at 145 kV, find the Mvar
rating of the synchronous condenser at receiving end at no
load and at full load.
FIGURE 15-38
(a) Shunt connection of an active filter. (b) Series
connection of an active filter.
7. Why have current source converters been in use for HVDC
transmission in the past? Explain the recent shift to voltage
source converters.
426
CHAPTER FIFTEEN
8. Plot P-d curves of 230-kV uncompensated line, with
midpoint shunt compensation of 0.6 and also with series compensation of 0.6. The line is 200-mi long and has a series reactance of 0.8 Ω/mi with a susceptance y=5.4 × 10-6 S/mi.
11. H. Akagi, Y. Kanazawa, and A. Nabae, “Generalized Theory of
Instantaneous Reactive Power in Three-Phase Circuits,” Proc.
International Power Electronics Conference, pp. 1375–1386,
Tokyo.
9. Compare the performance of a conventional SVC device
with STATCON. Draw their relative V-I curves.
12. H. Akagi, E. H. Watanbe, and M. Aredes, Instantaneous
Power Theory and Applications to Power Conditioning,
Wiley–Intersciences, 2007.
10. Compare UPFC with STATCON and SCCC. Can a
STATCON be used in a transmission line for active power
control?
11. Make a table of all the electronic and conventional devices for
the reactive power generation and their relative characteristics.
12. In Fig. 15-33, (a), Can converter 1 supply active power
to the system? (b) Can converter 2 supplies active power
to the system? (c) Can both converters supply active power
to the system. Choose the correct option and explain the
reasoning.
REFERENCES
1. IEEE Std. 519, IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems,
1992.
2. J. C. Das, “Estimating Line Harmonics-Appendix G,” Power
System Analysis: Short-Circuit, Load Flow, and Harmonics, Marcel
Dekker, 2002.
3. A. D. Graham and E. T. Schonholzer, “Line Harmonics of Converters with DC-Motor Loads,” IEEE Trans. Industry Applications,
vol. 19, pp. 84–93, 1983.
4. N. Hatti, Y. Kondo, and H. Akagi, “Five Level Diode-Clamped
PWM Converters Connected Back-to-back for Motor Drives,”
IEEE Trans. Industry Applications, vol. 44, no. 4, pp. 1268–1276,
July/Aug. 2008.
5. H. Akagi, H. Fujita, S. Yonetani, and Y. Kondo, “ A 6.6 kV
Transformer-Less STATCOM Based on a Five Level DiodeClamped PWM Converter: System Design and Experimentation of 200-V, 10 kVA Laboratory Model,” IEEE Trans.
Industry Applications, vol. 44, no. 2, pp. 672–680, March/
April 2008.
6. C. Schauder, M. Gernhard, E. Stacey, T. Lemak, L. Gyugi, T.W.
Cease, and A. Edris, “Development of a 100 Mvar Static Condenser for Voltage Control of Transmission Systems,” in Conf.
Record, IEEE/PES 1994 Summer Meeting, San Francisco, CA,
1994.
7. R. J. Nelson, J. Bian, and S. L. Williams, “Transmission Series
Power Flow Control,” IEEE Trans. PD, vol. 10, no. 1, pp. 504–510,
Jan. 1995.
8. IEEE Std. 1459, IEEE Trial-Use Standard Definitions for
the Measurement of Electrical Power Quantities Under
Sinusoidal, Non-Sinusoidal, Balanced or Unbalanced Conditions,
2000.
9. N. L. Kusters and W. J. M. Moore, “On the Definition of
Reactive Power Under Non-Sinusoidal Conditions,” IEEE
Trans., vol. PAS-99, pp. 1845–1854, 1980.
10. IEEE Std. 519, IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems,
1992.
13. H. Akagi, “Trends in Active Filters for Power Conditioning,”
IEEE Trans. Industry Applications, vol. 32, pp. 1312–1322, 1996.
14. J. C. Das, “Passive Filters—Potentialities and Limitations,” IEEE
Trans. Industry Applications, vol. 40, no. 1, pp. 232–241, Jan./
Feb. 2004.
FURTHER READING
H. Akagi, “New Trends in Active Filters for Power Conditioning,”
IEEE Trans. on Industry Applications, vol. 32, no. 6, pp. 1312–1322,
Nov./Dec. 1996.
J. Arrillaga, High Voltage Direct Current Transmission, IEEE Press,
London, 1983.
M. H. Baker, “An Assessment of FACTS Controllers for Transmission System Enhancement,” CIGRE-SC14, International Colloquium
on HVDC and FACTS, Montréal, Sep. 1995.
B. J. Baliga, “Power Semiconductor Devices for Variable Frequency
Drives,” Chapter 1, Power Electronics and Variable Frequency Drives,
B. K. Bose, ed, IEEE Press, Piscataway, NJ, 1996.
B. K. Bose, “Evaluation of Modern Power Semiconductor Devices
and Their Impact for Power Transmission,” IEEE Trans. Industry
Applications, vol. 28, no. 2, pp. 403–413, March/April 1992.
C. A. Canizares, “Analysis of SVC and TCSC in Voltage Collapse,”
in Conf. Record, IEEE PES 1998 Summer Meeting, San Diego, CA,
July 1998.
CIGRE WG 30-01, Task Force No. 2, Static Var Compensators, I.
A. Erinmez, ed., 1986.
R. Doncker, “High Power Semiconductor Development for FACTS
and Custom Power Applications,” EPRI Conf. on Future Power Delivery,
Washington, DC, April 1996.
J. B. Ekanayake and N. Jenkins, “A Three Level Advanced Static
var Compensator,” IEEE Trans. on Power Delivery, vol. 10, no. 2,
pp. 540–545, April 1996.
L. Gyugyi, R. A. Otto, T. H. Putman, “Principles and Applications
of Static, TC Shunt Compensators,” IEEE Trans. PAS, vol. PAS-97,
no. 5, pp. 1935–1945, Sept./Oct. 1978.
L. Gyugyi, C. D. Schauder, and K. K. Sen. “Static Synchronous Series
Compensator: A Solid State Approach to the Series Compensation
of Transmission Lines,” FACT Technical Papers, Westinghouse
Electric Corporation, pp. 1–8, Orlando, FL, August 1996.
L. Gyugyi, C. D. Schauder, and K. K. Sen, “Static Synchronous
Series Compensator: A Solid State Approach to the Series Compensation of the Transmission Lines,” IEEE Trans. PD, vol. 12, no. 1,
pp. 406–417, Jan. 1997.
C. J, Hatziadoniu and F. E. Chalkiadakis, “A 12-Pulse Static Synchronous Compensator for the Distribution System Employing
the Three Level GTO Inverter,” in Conf. Record, IEEE 1997 PES Meeting, Paper No. PE-542-PWRD-0-01, 1997.
N. G. Hingorani and L. Gyugyi, Understanding FACTS, IEEE Press,
New York, 2000.
POWER ELECTRONIC EQUIPMENT AND FACTS
N. G. Hingorani, “A New Scheme for Subsynchronous Resonance
Damping of Torsional Oscillations and Transient Torque, Part 1,”
IEEE Trans., vol. PAS-100, no. 4, pp. 1852–1855, April 1981.
N. G. Hingorani, “Flexible AC Transmission,” IEEE Spectrum,
pp. 40–45, April 1993.
IEEE Committee Report, “VAR Management–Problem Recognition and Control,” IEEE Trans., vol. PAS-103, pp. 2108–2116, Aug.
1984.
T. W. Kay, P. W. Sauer, R. D. Shultz, and R. A. Smith, “EHV & UHV
Line Loadability Dependence on Var Supply Capability,” IEEE Trans.,
vol. PAS-101, no. 9, pp. 3568–3575, 1982.
427
P. Kessel and H. Glavitsch, “Estimating the Voltage Stability
of a Power System,” IEEE Trans., vol. PWRD-1, no. 3, pp. 346–354,
July 1986.
T. J. E. Miller, Reactive Power Control in Electrical Power Systems,
John Wiley, 1982.
S. Mori and K. Matsuno, “Development of Large Static var Generator
Using Self Commutated Inverters for Improving Power System
Stability,” IEEE Trans. PS, vol. 8, no. 1, pp. 371–377, Feb. 1993.
K. K. Sen., “SSSC-Static Synchronous Series Compensator:
Theory, Modeling and Applications,” IEEE Trans. PD, vol. 13, no. 1,
pp. 241–246, Jan. 1998.
This page intentionally left blank
CHAPTER 16
FLICKER, BUS TRANSFER,
TORSIONAL DYNAMICS,
AND OTHER TRANSIENTS
In this chapter we will study:
■
Flicker
■
Auto bus transfer schemes
■
Cogging and crawling of induction motors
■
Tooth ripples in machines
■
Reciprocating compressors
■
Torsional vibrations
■
Out-of-phase closing and synchronizing
16-1
FLICKER
Voltage flicker occurs due to operation of rapidly varying loads,
which affect the system voltage. This can cause annoyance by causing visible light flicker on tungsten filament lamps. The human
eye is most sensitive to light variations in the frequency range of
5 to 10 Hz, and voltage variations of less than 0.5 percent in this
frequency range can cause annoying flicker on tungsten lamps.
Percentage pulsation of voltage related to frequency, at which it is
most perceptible, from various sources is shown in Fig. 16-1.1 In
this figure, solid lines are composite curves of voltage flicker by
General Electric Company (General Electric Review, August 1925);
Kansas Power and Light Company, Electrical World May 19, 1934;
T&D Committee EEI, October 14, 1934, Chicago; Detroit Edison
Company; West Pennsylvania Power Company; and Public Service Company of North Illinois. Dotted lines show voltage flicker
allowed by two utilities, reference Electrical World November 3,
1958 and June 1961.
Though Fig. 16-1 has been in use for a long time, it was superseded in IEEE Std. 1453.2 The solid-state compensators and loads
may produce modulation of the voltage magnitude that is more
complex than what was envisaged in the original flicker curves.
This standard adopts IEC standard 61000-4-153 in total. Define:
Plt = 3
12
1
× ∑ Pst 3
12 j =1 j
(16-1)
where Plt is a measure of long-term perception of flicker obtained for
a 2-h period. This is made up of 12 consecutive Pst values, where Pst
is a measure of short-term perception of flicker for 10-min interval.
This value is the standard output of IEC flicker meter. Further qualification is that IEC flicker meter is suited to events that occur once
per hour or more often. The curves in Fig. 16-1 are still useful for
infrequent events like a motor start, once per day, or even as frequent
as some residential air conditioning equipment. Figure 16-2 depicts
comparison of IEEE and IEC for flicker irritation.
For acceptance of flicker causing loads, IEC Standards (Refs. 4,
5, and 6) are recommended. The application of shape factors allows
the effect of loads with voltage fluctuations other than the rectangular to be evaluated in terms of Pst values. Further research is needed
in issues related to the effect of interharmonics on flicker and flicker
transfer coefficients from HV to LV electrical power systems.2,7
Two levels, planning level and compatibility levels, are defined.
Compatibility level is the specified disturbance level in a specified
environment for coordination in setting the emission and immunity limits. Planning level, in a particular environment, is adopted
as a reference value for limits to be set for the emissions from large
loads and installations, in order to coordinate those limits with all
the limits adopted for equipment intended to be connected to the
power supply system.
As an example, planning levels for Pst and Plt in MV (voltages
> 1 kV and < 35 kV), HV (voltages > 35 kV and < 230 kV) and EHV
(voltages > 230 kV) are shown in Table 16-1, and compatibility
levels for low voltage and medium voltage power systems are
shown in Table 16-2.
Arc furnaces cause flicker because the current drawn during
melting and refining periods is erratic and fluctuates widely, and
the power factor is low. There are other loads that can generate
429
430
CHAPTER SIXTEEN
FIGURE 16-1
Tolerable limits of flicker. Source: IEEE Standard 519.1
FIGURE 16-2
Comparison of IEC and IEEE standards with respect
to flicker tolerance. Source: IEEE Standard 1453.2
TA B L E 1 6 - 1
Planning Levels for Pst
and Plt in MV, HV, and
EHV Power Systems
PLANNING LEVELS
MV
HV-EHV
Pst
0.9
0.8
Plt
0.7
0.6
TA B L E 1 6 - 2
Compatibility Levels
for Pst and Plt in LV
and MV Systems
COMPATIBILITY LEVEL
Pst
1.0
Plt
0.8
flicker, for example, large spot welding machines often operate
close to the flicker perception limits. Industrial processes may
comprise a number of motors having rapidly varying loads or
starting at regular intervals, and even domestic appliances, such as
cookers and washing machines, can cause flicker on weak systems.
However, the harshest load for flicker is an arc furnace. During
the melting cycle of a furnace, the reactive power demand is high.
Figure 16-3 gives typical performance curves of an arc furnace,
and Fig. 16-4 is the frequency spectrums of the currents during
melting and refining. Though the signature of an arc furnace current is random and no periodicity can be assigned (thus Fourier
analysis cannot be used), some harmonic spectrums have been
established, and Table 16-3 shows typical harmonics during melting and refining stage. Note that even harmonics are produced
during melting stage. The high reactive power demand and poor
power factor causes cyclic voltage drops in the supply system.
Reactive power flow in an inductive element requires voltage differential between sending end and receiving ends and there is
reactive power loss in the element itself (Chap. 12). When the
reactive power demand is erratic, it causes corresponding swings
in the voltage dips, much depending upon the stiffness of the system behind the application of the erratic load. This voltage drop
is proportional to the short-circuit MVA of the supply system and
the arc furnace load.
For a furnace installation, the short-circuit voltage depression
(SCVD) is defined as:
SCVD =
2 MWfurnace
MVA sc
(16-2)
where MWfurnance is the installed load of furnace, and MVAsc is the
short-circuit level of the utility’s supply system. This gives an idea
whether potential problems with flicker can be expected. An SCVD
of 0.02 to 0.025 may be in the acceptable zone, between 0.03 to
0.035 in the borderline zone, and above 0.035 objectionable. When
there are multiple furnaces, these can be grouped into one equivalent MW load. The worst flicker occurs during the first 5 to 10 min
of each heating cycle and decreases as the ratio of the solid metal to
liquid metal decreases.
The significance of DV /V and number of voltage changes are
illustrated in Fig. 16-5.3 This shows a 50-Hz waveform, having a
FLICKER, BUS TRANSFER, TORSIONAL DYNAMICS, AND OTHER TRANSIENTS
FIGURE 16-3
FIGURE 16-4
Operating characteristics of an arc furnace.
Frequency spectrums of currents during (a) melting and (b) refining operation of an arc furnace.
431
432
CHAPTER SIXTEEN
TA B L E 1 6 - 3
Harmonic Content of Arc Furnace Current
HARMONIC CURRENT, % OF FUNDAMENTAL
HARMONIC ORDER
OPERATING CONDITION
2
3
4
5
7
Melting (active arc)
7.7
5.8
2.5
4.2
3.1
Refining (stable arc)
0
2.0
0
2.1
0
F I G U R E 1 6 - 5 Modulation with rectangular voltage change DV/V =
40 percent, 8.8 Hz, 17.6 changes per second.
1.0 average voltage with a relative voltage change Dv / v = 40 percent
and with 8.8-Hz rectangular modulation. It can be written as:
v(t ) = 1 × sin(2π × 50t )
40 1
× 1 +
× × signum (2π × 8 . 8 × t )
100 2
(16-3)
Each full period produces two distinct changes: one with
increasing magnitude and one with decreasing magnitude. Two
changes per period with a frequency of 8.8 Hz give rise to 17.6
changes per second.
16-1-1
Control of Flicker
During the past years, high-power thyristor valves have been used
to connect capacitors and reactors in shunt with power lines. When
it is essential to compensate load fluctuations within a few ms,
SVCs have been applied. Large TCR flicker compensators of
200 MW have been installed for arc furnace installations. Closedloop control is necessary due to randomness of load variations,
and complex circuitry is required to achieve response times less
than one cycle. Significant harmonic distortion may be generated.
Harmonic filters are required. TSCs have also been installed and
these have inherently one cycle delay as the capacitors can only be
switched when their terminal voltage matches the system voltage.
Thus, the response time is slower. SVCs employing TSCs do not
generate harmonics, but the resonance with system and transformers needs to be checked.
We discussed STATCOM in Chap. 15. It has been long recognized that reactive power can be generated without use of
bulk capacitors and reactors and STATCOM makes it possible.
As discussed in Chap. 15, it is capable of operating with leading
or lagging power factors. With design of high bandwidth control
capability, STATCOM can be used to force three-phase currents of
arbitrary waveshape through the line reactance. This means that
it can be made to supply nonsinusoidal, unbalanced, randomly
fluctuating currents demanded by the arc furnace. With a suitable
choice of dc capacitor, it can also supply the fluctuating real power
requirements, which cannot be achieved with SVCs. Harmonics are
not of concern (Fig. 15-26).
The instantaneous reactive power on the source side is the reactive power circulating between the electrical system and the device,
while reactive power on the output side is the instantaneous reactive power between the device and its load. There is no relation
between the instantaneous reactive powers on the load and source
side, and the instantaneous imaginary power on the input is not
equal to the instantaneous reactive power on the output (Chap. 15).
The STATCOM for furnace compensation may use vector control
based on the concepts of instantaneous active and reactive power, ia
and ib (Chap. 15).
Figure 16-6 shows flicker reduction factor as a function of
flicker frequency STATCOM versus SVC.8 Flicker mitigation with
a fixed reactive power compensator and an active compensator—a
hybrid solution for welding processes—is described in Ref. 9.
16-2
AUTOTRANSFER OF LOADS
Autotransfer of loads is adopted to restore power to running loads
by switching to an alternate source of power. Figure 16-7a shows
that two step-down transformers, connected to different sources of
power on the primary side, serve loads connected to a single bus.
One source is labeled as standby. On loss of the normal source,
the power is restored automatically by switching to the standby
source.
An extension of this concept is to bring the standby source of
power, say, a diesel generator, on line automatically to serve the
load. It implies that on loss of normal power, the standby generator
will be started, and the power is restored after a time delay, during
which all rotating motor loads connected to the bus will shutdown
and have to be restarted back in a certain sequence. This does not
give rise to transients and is not discussed further.
A more common configuration for load transfer is shown in
Fig. 16-7b. Here the sources are labeled 1 and 2, and the bus section
breaker is open under normal operation, when both the sources are
available. Each source supplies the loads connected to the sectionalized bus to which it is connected. On failure of any one source,
the breaker controlling that source is tripped, and the bus section
breaker is closed. Each transformer should be sized, not only for
the total bus load, but also to limit voltage drops when the connected loads accelerate.
The transients that may occur on such operation depends on
how fast the power is restored. Many fast bus transfer schemes have
been implemented, especially for generating stations, where shutdown of auxiliary station service loads will precipitate a shutdown
of the entire generating station.
FLICKER, BUS TRANSFER, TORSIONAL DYNAMICS, AND OTHER TRANSIENTS
FIGURE 16-6
433
Flicker factor R with STATCOM and SVC.
16-2-1 Induction Motor Behavior on
Loss of Power Supply
Reconnection of motors to a power supply after an interruption,
while they are still in rotation, may give rise to large transient
torques and current surges. After disconnection from the supply
lines, the motor internal voltage will decay at a rate determined by
the inertia, and motor and load characteristics. A phase difference
will therefore exist between the incoming line (alternate source
to which the motors are being switched) and the motor decaying residual voltage. Negative transient torques of seven times per
unit torque may be produced, and the maximum may not occur
exactly at 180° phase opposition of the decaying motor voltage
and the incoming supply voltage. The motor leakage reactance
and resistance will have an impact on the decay of transients, and
high damping coefficients are desirable. There are successive time
delays at which the transient torques will be zero on reconnection.
Figure 16-810 shows the transient negative torques versus reconnection time for a 2000-hp motor, open circuit time constant, 2 s, and
breakdown torque, 150 percent. The high negative torques can be
avoided with fast switching.
FIGURE 16-7
(a) Load transfer scheme without bus section breaker.
(b) Load transfer scheme with bus section breaker.
FIGURE 16-8
Negative torques on reconnection of a 2000-hp motor
to the supply system with H = 3.6 and 7.2.
434
CHAPTER SIXTEEN
This time delay is dependent upon the inertia, motor size, and
preloading. Therefore, there are three parameters to be considered:
■
Motor decaying residual voltage
■
Phase angle
■
The oscillating shaft torque and transient electrical air gap
torque
From Chap.11, for the short-circuited rotor of a squirrel cage
induction motor, vdr and vqr are zero, and when the stator is disconnected from the supply system, ids and iqs are also zero. Therefore,
we can write:
Mp
vds
=
0
vqs
0
Mp
idr
iqr
(16-4)
and
0
0
r + L r p L rω r
= r
−Lrωr rr + Lr p
Since the speed of the motor varies, Eq. (16-4) is nonlinear and
can be solved by numerical integration. It is, however, necessary to
know idr and iqr as the starting points. The stator current will fall to
zero in a very short time. As the flux in the machine cannot change
suddenly, the change in stator currents must be accompanied by
a change in the rotor currents to maintain constant flux linkages
after the motor is disconnected from the supply and before disconnection from the supply. These boundary conditions can then be
used to determine the decay of rotor currents and stator voltages
after disconnection.
For calculating the voltage decay, it is permissible to lump the
motor loads into an equivalent motor horsepower, having average
electrical characteristics and inertia constant; the slope of the decay
line is related to the X/R of the motor. Analytical expressions for
deceleration of the motor are given in Chap. 11.
Example 16-1 The residual voltage of a 6.6-kV, four-pole,
10000-hp, double-cage induction motor is simulated using
FIGURE 16-9
EMTP. The motor parameters are: load plus motor inertia
12000 lb-ft2, Ls (stator reactance) = 0.32, Rs (stator resistance) =
0.023, Rr1 (cage 1 resistance) = 0.12, Rr2 (cage 2 resistance) = 0.05,
Lr1 (cage 1 reactance) = 0.27, Lr2 (cage 2 reactance) = 0.294, all
values in ohms. The motor is running at no load when disconnected from the supply system. Figure 16-9 shows the decay in
residual voltage. Figure 16-1011 shows residual voltage and phase
shift in degrees for various motor sizes, after disconnection from
the supply system. Commonly the decays are represented in a
polar diagram (Fig. 16-11).
16-2-2
Currents and Torques on Reswitching
When the stator and rotor currents at the instant of switching are
known, the transients currents and, therefore, the transient torque
using Eq. (16-4) can be calculated.
Consider that the autotransfer occurs at a time tm, when the residual emf of the motor is Em. Then the resultant voltage vector is:
Er = Es2 + Em2 − 2Em Es cos θ
(16-5)
where Es is the supply system voltage. The voltage should be limited to a value of 1.33 puV/Hz, to prevent overfluxing and damaging the motor. Phase angle of small low-inertia motors drops
quickly and falls rapidly in and out of phase with the supply
voltage (Fig. 16-10).
16-2-3
Bus Transfer Strategies
1. Fast bus transfer
Figure 16-11 suggests that large transients can be avoided by
fast reclosing, so that the motor internal voltage is not much
displaced, and the incoming supply voltage is almost in phase
with the decaying emf.
2. Residual voltage transfer
An alternative will be to let the motor speed fall, and the internal voltage decay to a low value, say 25 percent of the supply
EMTP simulation of the decay of a 6.6-kV, 10000-hp induction motor residual voltage on disconnection from the supply system.
FLICKER, BUS TRANSFER, TORSIONAL DYNAMICS, AND OTHER TRANSIENTS
FIGURE 16-10
435
Residual voltage and phase angle of induction motors on disconnection from power supply system.11
voltage to avoid transient torques. Tests made on motors of
100 to 1500 hp establish that the critical time for maximum
inrush currents vary from 15 to 30 cycles. The voltage decay in
a group of motors will be faster than a single large motor of an
equivalent size. However, this mode of transfer defeats the
purpose of maintaining continuity of operation of connected
loads. The motors may decelerate to a level where the
reacceleration may not be possible on reconnection.
3. In-phase transfer
F I G U R E 1 6 - 1 1 Polar representation of the decay of an induction
motor on disconnection from the power supply system.
When the motor is disconnected from the supply lines, its
voltage and frequency falls, as illustrated in points 1 and 2.
The supply frequency, however, remains constant. The residual
voltage falls in and out of phase with the supply voltage, at an
increasing rate, as the motors slow down. If the alternate
supply breaker is closed exactly when the voltages are in phase,
bumpless transfer can be achieved. Care has to be exercised, as
the two sources may not be exactly in-phase when the transfer
is started, and the alternate supply phase may change further
when the normal supply breaker is opened due to changes in
the system interconnections.
436
CHAPTER SIXTEEN
F I G U R E 1 6 - 1 3 Motor voltage stresses with respect to transfer
mode: instantaneous voltages at the second breaker must be a minimum
when the breaker is closed to connect to alternate source of power.
FIGURE 16-12
To illustrate in-phase bus transfer.
The in-phase transfer must consider the circuit breaker closing
time and close the circuit breaker ahead of zero phase by breaker
closing time (Fig. 16-12). Assume that the breaker closing time is
tb seconds. Then the relay must initiate closing of the breaker
tb seconds before the phase angle reaches 360°, which means at
time ta. In order to predict when the phase angle will be zero, Taylor
series can be used.12
The phase-time curve can be estimated by Taylor series, considering the first three terms:
φ (t ) = φ (t1 ) + φ ′(t1 )(t − t1 ) +
φ ′′
(t − t1 )2
2
(16-6)
where φ (t1 ), φ ′(t1 ), and φ ′′(t1 ) are the value of phase at t1, the derivative at t1, and second derivative at t1, respectively. For φ (t ) = 0:
φ (t1 + t b ) = φ (t1 ) + φ ′(t1 )t b +
φ ′′(t1 ) 2
t
2 b
(16-7)
Equation (16-22) gives prospective phase value at tb when
φ (t1 + tb) = 0, by predetermination of φ and φ ′ and knowing the
value of tb. The in-phase transfer will be ineffective if at the time
of transfer there is not enough bus voltage to support motor
reacceleration.
A transfer logic controller is available that performs all the three
modes of transfers, user selectable. Figure 16-13 shows the three
modes of transfer with respect to the voltage difference profile across
the bus section breaker—the fast transfer and in-phase transfer are
better compared to residual voltage transfer with respect to motor
stresses. If we consider the residual voltage of the motor to completely decay to zero, the voltage across the bus section breaker is
1 pu, while for the fast bus transfer and in-phase transfer, it will be
much lower and less stressful to the motor. The motor transients
will be much reduced.
16-2-4 Momentary Paralleling
During planned load transfer, momentary paralleling of two sources
is widely used, that is, bus section breaker in Fig. 16-7b is closed
before any of the two source breakers are opened. (Synchronism
check features are incorporated.) A question arises that when the two
sources can be paralleled in the shutdown or planned load transfer
modes, why can these not continuously run in parallel? Appropriate
protective relaying schemes are available for two continuously running
parallel circuits, which will selectively trip the faulty circuit and the
loads will experience lesser transients, as compared to switching
on failure of a source. While continuous parallel operation is much
desired from the operational point of view, paralleling increases the
short-circuit duties on the circuit breakers. During momentary paralleling, a calculated risk is taken, that for the time duration involved to
transfer loads the probability of a fault is low. If a fault does occur, it
can destroy the equipment and can be hazardous to human life. This
practice should be carefully reviewed.
16-2-5 Fault Conditions
The fault conditions should be distinguished from simple loss of
source voltage, say due to inadvertent switching. The fault voltage
dips will be more severe, depending upon the location and nature of
the fault. Obviously for any fault in the bus itself or in the transformers
(Fig. 16-7), the autotransfer is blocked. A fault voltage dip will give
rise to transients in the connected motor loads, and these may not
survive operation when the alternate source of power is restored.
Sometimes simultaneous opening and closing of the breakers is
implemented. The control signals to open and close are applied at the
same time. The dead time including sensing of the sources may be
one to three cycles. There is some risk involved that a breaker may fail
to open. Alternatively, the normal breaker is first opened and interlocked, so that the standby breaker cannot be closed, unless the normal breaker has opened. The dead times may be 10 cycles or more.
The stability of loads will depend how fast the power is restored; the
stability of motors on voltage dips is discussed in Chap. 11.
16-2-6
Drop Out of Motor Contactors
Another parameter of practical consideration is that magnetic contactors for motor starting will drop out quickly—for low-voltage motor
starters, the contactors may drop out in the very first cycle of voltage
dip exceeding 30 percent. NEMA E2 starters are used for starting
and control of medium voltages (in a certain range), and these have
dc contactors, which may take a little longer to drop out, depending
upon the trapped residual magnetism in the coils. It is possible that
the motors are tripped out from service because of drop out of contactors, while these may still be able to ride through the voltage dip.
Latched type of contactors and stabilizing the contactors for
undervoltage dips for a certain time duration are possible options.
This has to be attempted carefully, as on voltage restoration all the
connected motor loads, which lost speed during the voltage dip,
will take high inrush currents to accelerate. This large current may
cause further voltage dips in the system impedance, a cumulative
effect, to precipitate a shutdown.
FLICKER, BUS TRANSFER, TORSIONAL DYNAMICS, AND OTHER TRANSIENTS
16-2-7
Autotransfer of Synchronous Motors
Autotransfer of power on synchronous motors is not attempted.
The phase angle between the motor generated voltage and supply
connection will vary from 0° to 360° per slip cycle. An autoclosing operation may produce short-circuit current equal to 2.5 times
the normal short-circuit current. This will subject the windings to
stresses approaching 6.5 times the normal short-circuit currents.
The transient torques produced by the fault currents have oscillatory
components and the peak torque may be as high as 30 to 40 times
the normal full-load torque. On a voltage dip, the excitation to the
motor may be removed and reapplied shortly thereafter, if the system
conditions are favorable. (See resynchronizing in Chap. 11.)
437
Example 16-2 The transients on reconnection of induction
motor loads are studied with EMTP modeling. Consider that five
motors of the specifications as in Example 16-1 are connected to a
6.6-kV bus, served from two alternate sources in a system configuration as in Fig. 16-7a. The normal source of power is tripped,
normal breaker is opened, and the standby breaker is closed; the
total duration of loss of power (including relaying and closing time
of breakers) is 500 ms (arbitrary here, for the example). Each of
the two transformers in Fig. 16-7a are rated at 80 MVA, transformer
impedance = 9 percent on 80-MVA base. Figure 16-14a shows that
in approximately 500 ms the bus voltage in phase a has decayed by
43 percent. The restoration of power at 500 ms does not give rise
F I G U R E 1 6 - 1 4 EMTP simulation of transients in five, 10000-hp, 6.6-kV, bus-connected motors, dead time = 500ms: (a) Bus voltage, (b) slip of a
10000-hp motor, (c) transient current in phase a, and (d) transient torque.
438
CHAPTER SIXTEEN
FIGURE 16-14
to much voltage escalation. The motors accelerate and remain stable;
the slip which had increased to approximately 13 percent rapidly
decreases (Fig.16-14b). The current in phase a and the transient electromagnetic torque (newton-meters) of one of the motors are shown
in Fig. 16-14c and d, respectively. The current on reconnection jumps
to 13800 A, approximately 15.7 times the full-load current of the
motor. The 80-MVA transformer will therefore experience a sudden
loading of 13.8 × 5 = 69 kA. The ANSI/IEEE short-time withstand
capability of the transformer for through-fault is 77.76 kA for 2 s. The
transient load for a couple of cycles can be safely allowed.
16-3 STATIC TRANSFER SWITCHES
AND SOLID-STATE BREAKERS
The static transfer switches (STS) can affect a transfer in approximately one-fourth of a cycle, depending upon the topology of the
(Continued )
circuit. STSs are commonly used in UPS systems (Chaps. 19),
and are commercially available for medium-voltage applications.
Thyristor-based STS systems have the advantage of low cost and
low conduction losses, compared to GTO- or IGBT- based technologies. The natural commutation of thyristors in a STS system is
dependent upon load power factor and depth of voltage sag, which
prolongs the transfer time to more than one-fourth of the cycle.
Figure 16-15a depicts the power circuit (only single phase
shown), with maintenance and load bypass mechanical switches.
Two sets of thyristors are connected in opposite directions to pass
ac positive and negative half-cycles. Figure 16-15b is a diagram
of transfer logic. The phase voltages Va, Vb, and Vc are transformed to Vd, Vq, and V0, using Park’s transformation. The voltage
Vp = Vd2 + Vq2 . This is compared with a reference and the error signal
is passed on to an LP filter, which attenuates voltage transients.
FLICKER, BUS TRANSFER, TORSIONAL DYNAMICS, AND OTHER TRANSIENTS
FIGURE 16-15
439
(a) Circuit of a thyristor-based static switch (only one phase shown). (b) Block circuit diagram of a transfer logic.
Filter output is compared to tolerance limit Etol, and the output of
the comparator is the transfer signal, which initiates a transfer.13
The regenerative load transfer is discussed in Ref. 14; the maximum
transfer time is determined by the zero crossing of the system voltage. The total transfer time varies from 6.5 to 10.5 ms, depending
upon the nature of the disturbance; under voltage or fault conditions.
If there is a transformer connected to the load side (Fig. 16-15a), it
can be subjected to large transients due to fast transfer.
Solid-state circuit breakers (SSBs) offer considerable advantage
over mechanical breakers. The short-circuit fault current is reduced.
The voltage dips due to three-phase fault clearance (lasting for about
100 ms or more) can be reduced to 100 µs. The impediments in the
development have been material costs and on-state losses.
At the 15-kV level, the SSBs can be built using GTOs or SCRs.
The SCRs have better blocking voltages, lesser losses, and higher
current ratings. GTOs can interrupt current with negligible delay
and can turn off the fault current during the first half cycle when
the overload condition is detected. This interruption must take
place before exceeding the current interrupting rating of GTOs.
Figure 16-16a shows a hybrid solution applied to a 15-kV breaker.
It consists of parallel branches, composed of GTOs and SCRs. The
GTO section conducts load current in the steady state. It is rated
for maximum line currents but not for fault currents. It opens rapidly when the preset level of the current is exceeded, say 3000 A.
A number of GTO switches are connected in series with snubber
circuits and metal-oxide arresters. The SCR section which incorporates pairs of antiparallel connected thyristor devices in series is
normally kept open and has no continuous current rating. It conducts fault currents (say 15 kA) for a period of 10 to 15 cycles,
so that the downstream devices on the load side may coordinate.
Further topologies of SSBs are described in Ref. 15.
Solid-state circuit breakers can be used as a bus section switch
or static transfer switches. Figure 16-16b shows the load-transfer
characteristics of two SSBs connected in a system configuration of
Fig. 16-7a, normal breakers replaced with SSBs. The load current is
basically unaffected due to transfer.
16-4 COGGING AND CRAWLING
OF INDUCTION MOTORS
Parasitic magnetic fields are produced in an induction motor due to
harmonics in the mmf originating from:
■
Windings
■
Certain combination of rotor and stator slotting
■
Saturation
■
Air gap irregularity
■
Unbalance and harmonics in the supply system voltage
IEEE standard 5191 lays down the permissible limits of harmonic current injections into the supply system. A Fourier analysis
of the waveshape of MMFs in a three-phase winding reveals that it
has a constant fundamental and harmonics of the order of 5, 7, 11,
13, . . . or 6m + 1, and 6m – 1, where m is any integer. All harmonics of the order of third and their multiples (triplen harmonics)
are absent, because a spread of 120° in windings of a three-phase
machine eliminates these, though not perfectly. The effective phase
spread for a third harmonic will be therefore 120° × 3 = 360°. The
harmonics move with a speed reciprocal to their order, either with
or against the fundamental. Harmonics of the order of 6m + 1 move
in the same direction as the fundamental field, while those of 6m – 1
move in the opposite direction.
These harmonics can be considered to produce, by an additional set of rotating poles, rotor emfs, currents, and harmonic
torques akin to the fundamental frequency, but synchronous
speeds, depending upon the order of the harmonics. The resultant
speed torque curve will then be a combination of the fundamental
and harmonic torques. This produces a saddle in the torque-speed
characteristics, and the motor can crawl at the lower speed of
one-seventh of the fundamental (Fig. 16-17).
440
CHAPTER SIXTEEN
FIGURE 16-16
(a) A hybrid static circuit breaker: GTO and SCR switches in parallel. (b) Load transfer transient with static breakers.
This harmonic torque can be augmented by stator and rotor
slotting. In n-phase winding, with g slots per pole per phase, emf
distribution factors of the harmonics are:
n = 6Ag ± 1
(16-8)
where A is any integer, 0, 1, 2, 3, . . . . The harmonics of the order
6Ag + 1 rotate in the same direction as the fundamental, while those
of order 6Ag – 1 rotate in the opposite direction.
Consider 24 slots in the stator of a 4-pole machine. Then g = 2
and 11th and 13th harmonics will be produced strongly. The
harmonic induction torque thus produced can be augmented by
the rotor slotting. Consider a rotor with 44 slots. The 11th harmonic
has 44 half-waves in the air gap each corresponding to a rotor bar.
This will accentuate 11th harmonic torque and produce strong
vibrations. If the numbers of stator slots are equal to the number
of rotor slots, the motor may not start at all, a phenomenon called
cogging.
16-4-1 Harmonic Synchronous Torques
The rotor mmf has a harmonic content and with certain combination of the stator and rotor slots, it is possible to get a stator and
rotor harmonic torque producing a harmonic synchronizing torque.
There will be a tendency to develop sharp synchronizing torque at
some subsynchronous speed (Fig. 16-17b).
The rotor slotting will produce harmonics of the order of:
n=
S2
±1
p
(16-9)
where S2 is the number of rotor slots. Here, the plus sign means
rotation with the machine. Consider a motor with S1 = 24 and
S2 = 28. The stator produces reversed 11th harmonic (reverse going)
and 13th harmonic (forward going). The rotor develops a reversed
13th and forward 15th harmonic. The 13th harmonic is produced
both by stator and rotor, but of opposite rotation. The synchronous
speed of the 13th harmonic is 1/13 of the fundamental synchronous
speed. Relative to rotor, it becomes:
−
(n s − nr )
13
(16-10)
where ns is the synchronous speed and nr is the rotor speed. The
rotor, therefore rotates its own 13th harmonic at a speed of:
(n s − nr )
+ nr
(16-11)
13
relative to the stator. The stator and the rotor 13th harmonic fall
into step when:
−
+
ns
(n − n )
= − s r + nr
13
13
(16-12)
FLICKER, BUS TRANSFER, TORSIONAL DYNAMICS, AND OTHER TRANSIENTS
FIGURE 16-17
441
(a) Harmonic induction torques in an induction motor. (b) Harmonic synchronous torques.
This gives nr = ns /7, that is, torque discontinuity is produced
not by 7th harmonic but by 13th harmonic in the stator and rotor
rotating in opposite directions.
The harmonic torques are avoided in the design of machines by
proper selection of the rotor and stator slotting.
16-4-2
Tooth Ripples
Figure 16-18 shows the tooth ripples in the air-gap flux distribution of an induction motor, somewhat exaggerated. These are produced because of variation of air-gap permeance. The frequency
of the flux pulsations corresponds to the rate at which slots cross
the pole face, given by 2gf, where g is the number of slots per
pole (as defined before) and f is the system frequency. This stationary pulsation may be considered as two waves of fundamental
space distribution rotating at angular velocity 2gw in the forward
and backward direction. The component fields will have velocities of (2 g ± 1)ω relative to armature windings and will generate
harmonic emfs of frequencies (2 g ± 1) f cycles per second. However, this is not the main source of tooth ripples. Since the ripples
are due to slotting, these do not move with respect to the stator
conductors, and these cannot generate an emf of pulsation. With
respect to rotor, the flux wave has a relative velocity of 2gw and
generates emfs of 2gf frequency. Such currents superimpose an
MMF variation of 2gf on the resultant pole MMF. These can be
again resolved into forward- and backward-moving components,
with respect to the rotor, and (2 g ± 1)ω, with respect to the stator.
FIGURE 16-18
Tooth ripples in induction motors.
Thus, stator emfs of (2 g ± 1) f are generated which are the main
tooth ripples.
16-5 SYNCHRONOUS MOTOR-DRIVEN
RECIPROCATING COMPRESSORS
Synchronous motors driving reciprocating compressors give rise to
current pulsations in the stator current due to the nature of the
442
CHAPTER SIXTEEN
F I G U R E 1 6 - 1 9 (a) Crank effort diagram for one-cylinder, double-acting compressor or two-cylinder, single-acting compressor. (b) Crank effort
diagram for two-cylinder, double-acting compressor or four-cylinders, single-acting compressor.
reciprocating compressor torque variations. Figure 16-19a shows a
crank effort diagram for a one-cylinder, double acting compressor
or a two-cylinder, single-acting compressor, and Fig. 16-19b shows
a crank effort diagram for a two-cylinder, double-acting compressor
or a four-cylinder, single-acting compressor. The torque varies per
revolution and this gives rise to variation in stator current, oscillogram in Fig.16-20. In some cases, step unloading of compressors
is used, which introduces additional irregularity in the crank effort
diagram and increases the current pulsation. Figure 16-21 shows
resolution of a compressor to equivalent rotating masses, also useful for torsional vibrations discussed in Sec. 16-6.
NEMA standards limit current pulsation to 66 percent of rated
full-load current, corresponding to an angular deviation of approximately 5 percent from the uniform speed. The required flywheel
effect to limit current pulsation is proportional to compressor factor
“X” given by:
100
WK 2 = 1 . 34 XfPr
rpm
35200
ns
Pr f
WK 2
P = V (I q cos δ + I d sin δ )
(16-15)
This can be shown to be equal to:
4
(16-13)
where X is the compressor factor, f is the frequency, Pr is the synchronizing power, and WK2 is the total inertia in lb. ft2.
A system having a mass in equilibrium, and a force tending to
return this mass to its initial position if displaced, has a natural frequency of oscillation. For a synchronous motor, it is given by:
fn =
where fn is the natural frequency of oscillation, and ns is the synchronous speed. This assumes that there is no damping and the motor
is connected to an infinite system. The forcing frequency, due to
crank effort diagram, should differ from the natural frequency by
at least 20 percent.
We defined synchronizing power for the generator in Chap. 12.
The definition for the synchronous motor is analogous. Similar
to a synchronous generator (Chap. 10), the phasor diagrams of a
synchronous motor are depicted in Fig. 16-22a, b, and c at leading
power factor, unity power factor, and lagging power factor, respectively. The resistance is ignored in these figures. The power output
can be expressed as:
(16-14)
P=
(16-16)
A disturbance, in relative position of angle d, results in a synchronizing power flow in the machine. A synchronizing torque is developed which opposes the torque angle change due to the disturbance,
that is, a load change. The final torque angle may be reached only
after a series of oscillations, which determine the transient stability
of the machine, depending upon whether these converge or diverge,
akin to stability of a synchronous generator.
The synchronizing power in per unit on a machine can be
written as:
Pr =
F I G U R E 1 6 - 2 0 Oscillogram of current input to motor, driving a
vertical two-cylinder, single-acting compressor.
V 2( x d − x q )
VEt
sin δ +
sin 2δ
xd
2xd xq
V 2( x d − x q )
dP VEt
cos δ +
cos 2δ
=
dδ
xd
xd xq
(16-17)
Figure 16-23 shows the synchronizing power with respect to torque
angle. For any change in P, we can write the equation:
D P = Pr D δ
(16-18)
FLICKER, BUS TRANSFER, TORSIONAL DYNAMICS, AND OTHER TRANSIENTS
FIGURE 16-21
FIGURE 16-22
Resolution of a compressor to equivalent rotating masses.
Phasor diagrams of a synchronous motor operating at (a) leading, (b) unity and, (c) lagging power factor.
443
444
CHAPTER SIXTEEN
FIGURE 16-23
(a) Power angle diagram of a synchronous generator/motor. (b) Synchronizing power.
The damping torque occurs due to induced currents in the damper
windings, mainly because of quadrature axis flux. The damping
power Pds at any slip s can be written as:
P
Pds = s 0
s0
(16-19)
1 dδ
ω dt
(16-20)
Then the acceleration or retardation of the rotor is given by:
a=
d 2δ
dδ
+ ρ + ν 2δ = 0
dt
dt 2
ds 1 d δ
=
dt ω dt 2
P dδ
Pds = 0
s0ω dt
(16-22)
ρ=
1
νTa
(16-27)
Example 16-3 A machine with Ta = 10 s, and synchronizing
power two times the rated power has a natural frequency of:
ν=
2π × 60 × 2
= 8.8
10
(16-23)
where Ta is the a accelerating time constant, J is the moment of
inertia, and g is the gravitational constant.
The power balance equation becomes:
Ta P0 d 2δ P0 dδ
+
+ P δ = Pa
ω dt 2 s0ω dt s
(16-26)
The oscillations in cycles per second (cps) is v/ 2π = 1 . 41 cps .
This is fairly low. Figure 16-24 shows current oscillations of a
salient-pole machine, fitted with damper cage, on sudden loading.
The solution of Eq. (16-25) is of the form:
Lastly, the power of inertia is:
Ta P0 d 2δ
ω dt 2
ωPs
Jgω02
and:
2
(16-21)
ωPs
=
Ta P0
ν=
From above relations, we can write:
Pj = Jgω02a =
(16-25)
where the natural frequency is:
where s0 is the slip, which will produce asynchronously the rated
power P0 of the machine.We can define the slip as the change in the
torque angle with time:
s=
where Pa is the net power of acceleration or retardation. This differential equation without forcing function is:
(16-24)
δ = Ae
ρ
− t
2
cos(νt + B)
(16-28)
where A and B are the constants of integration. From Eqs. (16-20)
and (16-21), the rotor slip is given by:
s=−
ν − ρ2
Ae sin(νt + B)
ω
(16-29)
FLICKER, BUS TRANSFER, TORSIONAL DYNAMICS, AND OTHER TRANSIENTS
FIGURE 16-24
16-5-1
445
Current oscillations on sudden loading a salient-pole synchronous motor.
Forced Oscillations
If the driving power is not constant and fluctuates (due to fluctuating load) and Pm is the mean, Pa is the amplitude of power oscillation at frequency l, then from Eq. (16-24)
d 2δ
dδ
+ ρ + ν 2δ = ν 2 Λ e jλt
dt
dt 2
(16-30)
where Λ is given by:
Λ=
ω Pa Pa
=
Ta P0 ν 2 Ps
(16-31)
Equation (16-46) can be solved for the forced oscillation and
gives the magnitude of the oscillatory component as:
A=
Λ
(16-32)
2 2
1 − λ + ρλ
ν ν 2
2
This is the resonance formula. Then, the forced amplitude of the
synchronous power oscillation is:
P′ = Ps A
(16-33)
FIGURE 16-25
Resonance and damping characteristics.
16
The resonance curves are shown in Fig. 16-25. The curves peak
around λ /ν = 1. Further apart is the disturbing frequency with
respect to natural frequency of the motor, lesser will be its effect.
A NEMA X-Y curve for determining compressor factor is in
Fig. 16-26. This plots compressor factor against current pulsation
for a given type of compressor. The total exchange of power with
the network is:
ρλ
1+ 2
ν
Pa = Vm Pa
2
2 2
λ
ρλ
1 − +
ν ν 2
For constant excitation, the current fluctuations are:
DI = Vm Pa
The voltage fluctuations can be calculated as:
DV = DI × Z
2
(16-34)
(16-35)
(16-36)
Consider a 900-hp synchronous motor with motor plus load
inertia = 660 kg-m2, operating at a torque angle d = 28°. Ta, the
accelerating time constant = 1.64 s. Following the above calculation method, the swing in power at the ratio u/l can be calculated. The motor compressor drive may pass through one or more
446
CHAPTER SIXTEEN
F I G U R E 1 6 - 2 7 (a) Torsional model with two shaft-coupled rotating
masses under steady-state, constant torque. (b) Free oscillations with the
torque removed.
FIGURE 16-26
NEMA compressor factor curve.
natural torsional frequencies, and amplification of these may result
(Sec.16-6).
16-5-2 Several Synchronous Motors on the Same Bus
In case several synchronous motors are connected to the same
bus and are driving oscillatory loads, the oscillating voltage drop
and input power of one machine may be superimposed on the
other machines on the same bus. A situation may arise where
the motor may alternately draw and pass energy with disturbing frequency of the mechanical load. The electric power supplied by one motor may be fed into other motors and accentuate
the oscillations. The amplitude of the oscillating load of a compressor motor is passed on to the other motors with different
proportionality ratios. The natural period of oscillations can be
changed with:
■
Changing the inertia of the drive system
■
Excitation system
■
Varying resistance of the damper windings
■
Changing the air gap
■
Varying the source reactance of the power supply system
through reactors or transformers
A large change in the flywheel will be necessary to make an
appreciable change in the natural frequency. When the reciprocating
loads are driven by induction motors, the cranks are displaced from
each other, due to different load slips of the motors so that overall
fluctuations are reduced. The induction motors require smaller flywheel effects.
16-6
TORSIONAL DYNAMICS
Torsional vibrations are responsible for failure of drive system components and can stress or shear the turbine blades in generating
units. Figure 16-27a shows a simple torsional model in steady-state
torqued condition at rest or at constant speed. The electrical torque
and the load torque are constant and in balance. There is no relative
motion between the masses, but there is a twist in the shaft, with a
spring constant of K. Note the relative positions of the angles of twist.
If the steady-state torques were removed, the two inertias would
vibrate about the zero torque axes (Fig. 16-27b). In the absence of
any damping, these vibrations will continue with peak torque and
twist equal to initial steady-state values. The resonant frequency will
be given by:
f0 =
K( J1 + J 2 )
J1 J 2
(16-37)
The stored energy in the system is converted to kinetic energy two
times per cycle, and the two inertias oscillate in opposition to each
other (Fig. 16-28). If one of the torques is removed, an oscillation
with smaller amplitude will occur.
16-6-1 Steady-State Excitation
Consider that a steady-state excitation of frequency f0 is applied
to the system shown in Figure 16-27a. A torsional vibration will
be excited, and it may continue to grow in magnitude, until the
energy loss per cycle is equal to the energy that the small disturbance adds to the system during a cycle. The amplification curves
of the resonant system are in Fig. 16-29. This can be compared
with the curves in Fig. 16-25. If the excitation frequency varies at a
certain rate, the torsional vibrations will be amplified as the system
passes through the resonant point.
The driven load may have a positive slope, that is, the load
increases with the speed. This occurs for fans and blowers. The
load may have a negative slope, that is, conveyers and crushers. If
the motor torque is removed, the negative load slope tends to give
increasing torque pulsations.
An induction motor produces transient torques during starting
(Chap. 11), however, at the instant of switching, the excitation is at
power frequency and decays fairly rapidly as the motor accelerates.
As discussed in Chap. 11, a synchronous motor, in addition to the
initial fixed frequency excitation like an induction motor, produces
a slip-frequency excitation which varies from 120 Hz at starting
to 0 Hz at synchronism. When a synchronous machine pulls out,
it will produce a sinusoidal excitation at the pull-out frequency,
till it is disconnected or resynchronized. Figure 16-30 gives basic
torque-frequency–pulsation relation of a synchronous motor. The
critical speed, with twice the slip frequency during starting, cannot
be avoided. The critical speed, with the slip frequency excitation
following pull out, can be avoided, if the machine is deenergized
in time.
16-6-2
Excitation from the Mechanical System
There can be excitations from the mechanical system too, which are
proportional to speed and may occur at a frequency of multiple of
shaft revolution or integral multiple of gear tooth passing frequency.
FLICKER, BUS TRANSFER, TORSIONAL DYNAMICS, AND OTHER TRANSIENTS
FIGURE 16-28
447
Vibrating torsional system showing shaft twist, inertia speeds, and energies versus time.
FIGURE 16-30
Torque pulsation frequency characteristics of
synchronous motor during starting and following overload (with dc field).
FIGURE 16-29
Amplification curves of the resonant system.
These are due to imperfections in the mechanical system and generally of smaller magnitude. Excitations can also occur from the load
system. A mechanical jam may produce severe dynamic torques.
It may be difficult to totally avoid some amplification of the
torques during starting, however, it should show damping as the
drive train quickly passes through the vibration mode. Figure 16-31
shows the results of a torsional analysis of a salient-pole synchronous refiner motor of 30000-hp, 13.8-kV, 1.0-pf motor during
448
CHAPTER SIXTEEN
3.0
2.0
Torque (PU)
1.0
–1.0
–2.0
–3.0
0
4
8
12
16
Time in (s)
F I G U R E 1 6 - 3 1 Torsional vibration analysis results of a 30000-hp
synchronous motor driving a pulp mill refiner.
start-up—a system model with seven inertias and six spring constants is used in the analysis. Maximum shaft torque and minimum
shaft torque during starting are 2.8 and –2.5 pu, respectively. A
fatigue analysis of the shaft can also be made.17,18,19
The torsional analysis requires a host of motor and load data,
starting characteristics, inertias, and spring constants. These are
summarized in Table 16-4. A torsional analysis may discover many
natural frequencies of the system.
16-6-3 Steam Turbines of Generating Plant
Full- or partial-load rejection or overloading of generators gives rise
to overfrequency and underfrequency operation. For example, on
clearing a system fault, the complete load may be shed, and this
will cause the turbine to overspeed and frequency to rise. Assuming
5 percent governor droop characteristics, a 50 percent load rejection will result in approximately 2.5 percent rise in the frequency.
This condition does not last long as the control action will quickly
restore speed. On the other hand, overloading can be caused due to
TA B L E 1 6 - 4
many reasons, and enough loads may not be shed, giving rise to a
prolonged operating at underfrequency.
Twofold effects occur on the generator and turbine, and turbine
is considered to be more restrictive. The rating of a generator is
reduced when operating at a lower frequency, and prolonged operation
on overload at a reduced frequency may result in generator damage
if its short-time thermal capability is exceeded.
The turbine is more restrictive because of possible mechanical
resonance that we have discussed above, due to the mechanical
resonance frequency coinciding or nearing the reduced system
frequency. These exciting frequencies may dramatically increase
the vibratory stresses, resulting in damaging or cracking of some
part of the turbine blade structure. Turbine manufacturers provide time limits for abnormal frequency operation, and Fig. 16-32
is a composite curve for five manufacturers20 for general guidelines, though specific information for a unit is readily available
with the manufacturer. The abnormal frequency operation varies
considerably with the manufacturers. The speed limits are rather
tight, and the resonant frequencies lie fairly close to the supply
system frequency. The protection is provided by coordinating settings on frequency relays with appropriate time delays to trip the
generating units.
16-6-4 Analysis
The n-spring-connected rotating masses can be described by the
equation:
J
dωm
+ Dωm + Hθ m = Tturbine − Tgenerator
dt
(16-38)
H is the tri-diagonal matrix of stiffness coefficients, θ m is the vector
of angular positions, ωm is the vector of mechanical speeds, Tturbine
is the vector of torques applied to turbine stages, and D is the tridiagonal matrix of damping coefficients. The moment of inertia
and damping coefficients are available from design data. The spring
action creates a torque proportional to the angle twist.
Figure 16-33a shows a torsional system model for the steam turbine generator. The masses will rotate at one or more of the turbine
mechanical natural frequencies called torsional mode frequencies.
When the mechanical system oscillates under such steady state at
one or more natural frequencies, the relative amplitude and phase
Data Required for Torsional Vibration Analysis
PARAMETER
DESCRIPTION
Mm (kg-m)
Maximum transient shaft torque during starting
Ms (kg-m)
Breakaway torque refiner
F1 (kg)
Transferred thrust load to motor at zero-end gap in thrust bearings, both directions
P1 (kW)
Power loss in the refiner during idling
Critical damping (%)
Critical damping in the shaft system
Fatigue analysis
Data includes shaft diameter, speed ratio, material, shear stress, and stress concentration factor due to step change
in shaft diameter
J1, J2, J3, J4 (kg-m2/lb-ft2)
Rotating inertias
K1, K2, K3 (N-m/rad/lb-in/rad)
Spring constants
Motor
Starting speed torque characteristics, average and oscillating torques, effect of variation of system voltage and
starting conditions
Load
Starting torque speed characteristics
FLICKER, BUS TRANSFER, TORSIONAL DYNAMICS, AND OTHER TRANSIENTS
FIGURE 16-32
449
Abnormal frequency tolerance limits of steam-turbine generators, consolidated curves of five manufacturers. Source: ANSI/IEEE
standard C37.106.20
of individual turbine-rotor elements are fixed and are called mode
shapes of torsional motion (Fig. 16-33b).21
Torsional mode damping quantifies the decay of torsional oscillations. The ratio of natural log of the successive peaks of oscillation
is called logarithmic decrement. The decrement factor is defined as the
time in seconds to decay from the original point to 1/e of its value.
The modal spring-mass model is a mathematical representation
of Fig. 16-33a for oscillation in mode n, given by:
K12 −K12
T1
θ1
−K12 K12 K 23 −K 23
T2
θ
2
2
+
. −K n1,n . = .
−K 23 .
.
.
.
.
Tn
θn
−K n1,n K n1,n θ n
θ1
θ
J1
J2
.
.
Jn
(16-39)
The derivation follows from eigenvectors and frequencies of
the spring-mass model. It is seen there are n second-order differential equations of motion for an n mass model and coupled to one
another by spring elements.
Diagonalization of the stiffness term would yield n decoupled
equations called the modal-spring mass models. This diagonalization
can be accomplished by coordinate transformation from a reference
frame in the rotors to a reference frame of the eigenvectors. (See
Example 15-2.)
16-7
OUT-OF-PHASE SYNCHRONIZATION
Out-of-phase synchronization can occur in power stations due to
human error and failure of autosynchronizing and synchronizing
check relays. We discussed some aspects of it in Chap. 10. Here,
it can be shown that resulting fault current due to out-of-phase
synchronization will have delayed current zeros. These should not
be confused with the delayed current zeros discussed in Chap. 10,
due to high X/R ratio of large generators and certain combination of
generator reactances and time constants.
The problem can be significant for generators with a high subtransient current component, which means high X′d /Xd and small
Td and a large dc time constant Ta. During an out-of-phase synchronizing, currents in the armature windings may exhibit delayed
zeros. The inertia constant of the generator influences these
phenomena. Whether it will lead to a problem of generator circuit
breaker operation depends upon the protective relay settings—in
some plants circuit breaker tripping may be blocked on out-ofphase synchronizing.
Example 16-4 EMTP analysis of 18-kV, 200-MVA generator
of the following specifications, on out-of-phase synchronizing is
demonstrated:
X d = 1 . 78 X ′d = 0 . 215 X ′′d = 0 . 145 Td′ = 0 . 69s Td′′ = 0 . 015
X q = 1 . 75 X ′q = 0 . 35 X ′′q = 0 . 145 Tq′ = 0 . 148s Tq′′ = 0 . 015s
ra = 0 . 0012 X a = 0 . 12 H = 5 . 62
All reactance and resistance values are in per unit. The generator
is provided with a voltage regulator, a PSS, and a governor. The
generator is connected through a step-up transformer to a 230-kV
system. The transients on out-of-phase closing of the high-side circuit breaker are depicted in Fig. 16-34, phase currents for an outof-phase closing angle of 120°. The current zero is not obtained in
phase a.
FIGURE 16-33
FIGURE 16-34
450
(a) Rotating mass model of steam turbine generator. (b) Oscillation modes.
EMTP simulation of out-of-phase closing. Current zero is not obtained in phase a current.
FLICKER, BUS TRANSFER, TORSIONAL DYNAMICS, AND OTHER TRANSIENTS
PROBLEMS
1. A 2.3-kV motor load of 5 MW is connected to 13.8-2.4 kV,
10-MVA transformer of percentage impedance of 9.5 percent
on a 10-MVA base. The cyclic starting and stopping of the
motors gives rise to unacceptable flicker. List all the means of
reducing the flicker, with their relative advantages and disadvantages and cost effectiveness. Consider that the starting current
of the composite induction motor loads is six times the full-load
current. Consider a combined operating power factor of 0.92
and motor efficiency of 94 percent.
2. Explain why a STATCOM is more effective in controlling
flicker as compared to an equivalent SVC.
3. A total furnace load of 50 MVA is connected to a system
having a short-circuit impedance of 0.01 + j0.1 pu on
100-MVA base. Can flicker be a problem.
4. Calculate the phase angle at the time of switching of an
induction motor on restoration of the supply voltage, given
that supply system voltage = 1.0 pu, the residual motor
voltage at the time of reswitching = 0.8 pu, and the resultant
voltage vector = 1.5 pu. Is the statement that an induction
motor residual voltage and fluxes decay approximately at the
same rate correct? Explain the reasons.
5. An auxiliary distribution system at medium voltage, having
two sources of power in a system configuration as shown in
Fig. 16-7a, serves generator auxiliary loads, mainly consisting
of rotating induction motors and some static loads. What is the
appropriate choice for an autobus transfer scheme?
6. Why are the torsional vibration frequencies in steam
turbines close to the 60-Hz operating frequency? Can these
frequencies be placed much away from the operating frequency
(see Fig. 16-32)?
7. Describe the forced excitation types for torsional vibrations.
Which of these modes can give rise to a greater possibility of
torsional vibration resonance?
8. An induction motor has four poles and 24 slots. Which
harmonics will predominate for harmonic induction torques?
9. Distinguish between harmonic induction torques and
harmonic synchronous torques of an induction motor.
10. The three-phase power supply to an induction motor
contains predominant fifth and seventh harmonics. What can
be expected with respect to performance and starting of the
induction motor?
11. Why it is necessary that S2, the rotor slots in an induction
motor, should not exceed approximately 50 to 60 percent of
the stator slots?
12. Consider a 1000-hp, four-pole, 4-kV synchronous motor
in which Pr = two times the motor rating. The motor and load
inertia is 5000 lb-ft2. Calculate:
■
The compressor factor X
■
The natural frequency of oscillation
■
Accelerating time constant
13. A three-phase synchronous motor of 2000 hp, 4.0 kV, and
60 Hz is connected to a stiff electrical system. It has a moment
451
of inertia of 9000 kg-m2, synchronizing coefficient of 500 kW/
electrical rad, and damping torque of 2000 N-m/electrical rad/s.
The motor is driving a reciprocating compressor, with a harmonic torque of 1500 N-m at angular frequency of 2 rad/s.
Calculate maximum deviation in load angle and pulsation of
synchronizing power.
14. Calculate the natural frequency of oscillation of a
1500-hp, six-pole, synchronous motor operating at a power
angle of 30° at full load. Total moment of inertia of rotating
parts is 2000 kg-m2.
REFERENCES
1. IEEE Std. 519, Recommended Practice and Requirements for
Harmonic Control in Electrical Systems, 1992.
2. IEEE Std. 1453, Recommended Practice for Measurements and
Limits of Voltage Fluctuations and Associated Light Flicker on
AC Power Systems, 2004.
3. IEC 61000-4-15, Electromagnetic Compatibility (EMC)—
Part 4: Testing and Measurement Techniques—Section 15:
Flicker Meter: Functional and Design Specifications, 2003.
4. IEC 61000-3-3, Electromagnetic Compatibility (EMC)—
Part 3: Limits—Section 3: Limitation of Voltage Changes,
Voltage Fluctuations and Flicker, in Public Low-Voltage Supply
Systems, for Equipment with Rated Current ≤ 16A per Phase
and Not Subject to Conditional Connection, 2008.
5. IEC-61000-3-11, Electromagnetic Compatibility (EMC)—
Part 3–11, Limits: Limitation of Voltage Fluctuations and Flicker
in Low-Voltage Power Supply Systems for Equipment with Rated
Current < = 75A, 2000.
6. IEC 61000-3-8, Electromagnetic Compatibility (EMC)—
Part 3: Limits—Section 8: Signalling on Low-Voltage
Electrical Installations—Emission Levels, Frequency Bands
and Electromechanical Disturbance Levels, 1997.
7. S. M. Halpin and V. Singhvi, “Limits for Interharmonics in the
1-100 Hz Range Based Upon Lamp Flicker Considerations,” IEEE
Trans. Power Delivery, vol. 22, no. 1, pp. 270–276, Jan. 2007.
8. C. D. Schauder and L. Gyugyi, “STATCOM for Electric Arc
Furnace Compensation,” EPRI Workshop, Palo Alto, CA, 1995.
9. M. Routimo, A. Makinen, M. Salo, R. Seesvuori, J. Kiviranta, and H.
Tuusa, “Flicker Mitigation with Hybrid Compensator,” IEEE Trans.
Industry Applications, vol. 44, no. 4, pp. 1227–1238, Jul./Aug. 2008.
10. J. C. Das, “Effects of Momentary Voltage Dips on the Operation
of Induction and Synchronous Motors,” IEEE Trans. Industry
Applications, vol. 26, no. 4, pp. 771–781, Jul./Aug. 1990.
11. Westinghouse Electrical Transmission and Distribution
Reference Book, Chapter 22: Flicker, Westinghouse Electric
Corporation, East Pittsburg, PA, 1964.
12. D. L. Hornak and D. W. Zipse, “Automated Bus Transfer
Control for Critical Industrial Processes,” IEEE Trans. Industry
Applications, vol. 27, no. 5, pp. 862–871, Sept./Oct. 1991.
13. H. Mokhtari, S. B. Dewan, and M. R. Irvani, “Performance
Evaluation of Thyristor Based Static Transfer Switch,” IEEE
Trans. Power Delivery, vol. 15, no. 3, pp. 960–966, Jul. 2000.
14. H. Mokhtari, S. B. Dewan, and M. R. Irvani, “Effect of Regenerative
Load on Static Transfer Switch Performance,” IEEE Trans. Power
Delivery, vol. 16, no. 4, pp. 619–624, Oct. 2001.
452
CHAPTER SIXTEEN
15. C. Meyer and R. W. De Doncker, “Solid-State Circuit Breaker
Based on Active Thyristor Topologies,” IEEE Trans. Power
Electron., vol. 21, no. 2, pp. 450–458, Mar. 2006.
16. J. C. Das, “Oscillations Due to Synchronous Motors Driving
Reciprocating Compressors,” Journal of Institution of Engineers,
India, vol. 63, EL 4, pp. 185–189, Feb. 1983.
17. E. L. Owen, “Torsional Coordination of High Speed Synchronous Motors, Part 1,” IEEE Trans. Industry Applications, vol. 17,
pp. 567–571, Nov./Dec. 1981.
18. E. L. Owen, H. D. Snively, and T. A. Lipo, “Torsional Coordination of High Speed Synchronous Motors, Part 2,” IEEE Trans.
Industry Applications, vol. 17, pp. 572–580, Nov./Dec. 1981.
19. C. B. Meyers, “Torsional Vibration Problems and Analysis of
Cement Industry Drives,” IEEE Trans. Industry Applications,
vol. 17, no. 1, pp. 81–89, Jan./Feb. 1981.
20. ANSI/IEEE C37.106, IEEE Guide for Abnormal Frequency
Protection for Power Generating Plants, 1987.
21. IEEE Subsynchronous Resonance WG, “Terms, Definitions and
Symbols for Subsynchronous Oscillations,” IEEE Trans. PAS,
vol. PAS-104, no. 6, pp. 1326–1334, Jun. 1985.
FURTHER READING
H. Akagi and A. Nabe, “The p-q Theory in Three-Phase Systems
Under Non-Sinusoidal Conditions,” ETEP, vol. 3, pp. 27–30, 1993.
P. Ballensperger and H. Meyer, “Overvoltages Resulting from Disconnection of High-Voltage Motors,” BBC Review, vol. 40, no. 9,
pp. 342–349, 1953.
I. M. Canay, D. Braun, and G. S. Koppl, “Delayed Current Zeros
Due to Out-of-Phase Synchronizing,” IEEE Trans. EC, vol. 13, no. 2,
pp. 124–132, Jun. 1998.
P. T. Cheng and Y. H. Chen, “Design of an Impulse Commutated
Bridge for the Solid-State Transfer Switch,” IEEE Trans. Industry
Applications, vol. 44, no. 4, pp. 1249–1258, Jul./Aug. 2008.
J. M. Daly, “Load Transfer Strategies for Machine and Other Inrush
Loads,” IEEE Trans. Industry Applications, vol. 34, no. 6, pp. 1404–1410,
Nov./Dec. 1998.
J. C. Das, “Applications of Synchronous Motors in Pulp and Paper
Industry,” TAPPI Joint Conference Process Control, Electrical and Information, pp. 165–190, Vancouver, BC, Canada, Mar. 1998.
S. Kreitzer, J. Obermeyer, and R. Mistry, “The Effects of Structural and
Localized Resonances on Induction Motor Performance,” IEEE Trans.
Industry Applications, vol. 44, no. 5, pp. 1367–1375, Sept./Oct. 2008.
D. G. Lewis and W. D. Marsh, “Transfer of Steam-Electric Generating Station Auxiliary Bus,” Trans. AIEEE, pp. 322–331, Jun. 1955.
S. R. Mendis, M. T. Bishop, and J. F. Witte, “Investigations of
Voltage Flicker in Electric Arc Furnace Systems,” IEEE Industry
Magazine, no. 2, pp. 34–38, 1986.
C. D. Schauder and L. Gyugyi, “STATCOM for Electric Arc Furnace
Compensation,” EPRI Workshop, 1995.
E. S. Thomas, “Forgoing Flicker,” IEEE Industry Magazine, vol. 13,
pp. 34–41, Jul./Aug. 2007.
W. T. Thomson, Theory of Vibration with Applications, 3rd ed.,
Prentice Hall, Englewood Cliffs, NJ, 1988.
UIE (International Union for Electricity Applications) WG Disturbances, Flicker Measurements and Evaluation, Revised, 2d ed., 1991,
www.uie.org.
K. G. Williams and A. Khayer, “Auto-Transfer of Induction Motors
in Industrial Systems,” Electrical Review, pp. 395–397, Mar. 1968.
C. C. Young and J. Dunki-Jacobs, “The Concept of In-Phase
Transfer Applied to Industrial Systems Serving Essential Service
Motors” AIEEE Trans., pp. 508–516, Jan. 1961.
CHAPTER 17
INSULATION COORDINATION
The electrical insulation is an important element of the electrical
apparatuses, and its long-term integrity is directly related to the
performance integrity. Probable life expectancy is assigned to electrical equipment, based on the deterioration and aging of the insulation and field experience. As an example, the life expectancy of
a power transformer is 20 to 25 years, though, practically much
older transformers are in service. Much has been written about the
breakdown phenomena in insulation, and the research continues as
better insulation materials are developed.
17-1
INSULATING MATERIALS
Development of solid dielectric cables up to 500 kV is discussed in
Chap. 4. The advent of thermosetting resins (which tend to set and
harden on application of heat) compared to thermoplastic resins
(which melt on application of heat and solidify on removal of heat,
e.g., polyvinyl chloride, PVC) raised the temperature of solid insulation materials in usage. Usage of epoxy resins in liquid and solid
form was a further development which revolutionized the insulation systems of the rotating machines, switchgear, and enclosed
busbars. Polytetrafluoroethelene (PTFE), commonly known as
Teflon, is chemically inert, better than gold and platinum, and can
be used at high temperature. It can be molded into various intricate
shapes as an insulating material, does not require lubrication, and
can be machined.
The types of insulation systems vary widely depending upon their
usage and application—gases dielectrics for circuit breakers, mineral oil and solid insulation systems for cables, mineral oil and less
flammable liquids for transformer insulations, porcelain and glassepoxy materials for insulators, and SF6 as an insulating medium, as
discussed in Chap. 8. Air itself is an insulating medium. The mechanisms of breakdown in each of these mediums and physical and
chemical properties vary. Two types of insulations are:
■
Self-restoring insulation. The electrical power systems which
use air as an insulating medium for external insulation are
called the self-restoring insulation systems. The breakdown
in air is strongly dependent on gap configuration, shape,
and polarity of the surge and the ambient conditions. In an
outdoor environment, the effects of rain, fog, humidity, and
pollution become important. For GIS systems, the effects
of temperature, pressure, and internal irregularities play an
important role. Failure of air insulation is self-healing, as
removal of overvoltage will restore the insulation, though
not in every case of overvoltage. It is therefore, acceptable to
tolerate a small probability of insulation failure to minimize
the cost. Probabilistic methods are, therefore, applied for this
type of insulation. We can say that the methodology tends to
optimize the cost versus failure rate, though it is not so easy
to accomplish this objective due to incomplete data of the systems and extensive modeling that may be required.
■
Non-selfrestoring insulation. An insulation failure can cause
a permanent fault and damage. This is true of solid dielectric
materials. The mechanical stresses also impact the insulation
strength. Degradation of insulation tends to increase with time.
Any flashover is undesirable and unacceptable. The insulation
characteristics must be selected with zero percent chance of
flashover with some margin of safety. Practically, the cost of
equipment and voltage is an important factor. An 800-MVA
transformer will receive a more thorough analysis compared to a
500-kVA distribution transformer in meeting these criteria.
17-2
ATMOSPHERIC EFFECTS AND POLLUTION
Pollution and atmospheric conditions have a profound impact on
external insulation.1 Rain together with pollution can drastically
reduce the insulation strength. Fog, dew formation, and light rain
with contamination are the worst conditions. The design of line or
substation insulation is based on wet conditions. For substation
insulation, BSL is defined for wet conditions, while BIL is tested
under dry conditions. It is assumed that the rain will not severely
degrade the insulation strength and wet BIL = dry BIL. This may
not be entirely true. For line insulation CFO, dry CFO is obtained
from parametric tests and wet CFO is obtained by multiplying dry
CFO with an experimentally determined correction factors.
For self-restoring insulation, the probability of flashover can be
defined by an insulation strength characteristic curve modeled by
a cumulative Gaussian distribution function (App. F), considered
valid at least four standard deviations below CFO. The statistical
BIL or BSL, defined as the 10 percent probability of flashover, is
given by equation:
σ
BIL or BSL = CFO 1 − 1 . 28
CFO
(17-1)
where σ /CFO is the coefficient of variation. The truncation point
is usually neglected. For lightning impulses, this coefficient is about
3 percent, and for switching impulses for line and tower insulation,
this is assumed to be between 6 and 7 percent.
453
454
CHAPTER SEVENTEEN
TA B L E 1 7 - 1
TA B L E 1 7 - 3
Contamination Site Severity2,3
ESSD (mg/cm2)
SITE SEVERITY
CIGRE
None
IEEE
0.015–0.03
MINIMUM SPECIFIC CREEPAGE
DISTANCE (mm/kV)
POLLUTION LEVEL
0.0075–0.015
Very light
IEC-Recommended
Creepage Distances4
I: Light
27.7
0.03
II: Medium
34.6
Light
0.03–0.06
0.03–0.06
III: Heavy
43.3
Average/moderate
0.06–0.12
0.06–0.10
IV: Very heavy
53.7
Heavy
0.12–0.24
Very heavy
0.24–0.48
Exceptional
17-2-1
>0.10
>0.48
situations like ice in heavy pollution, heavy rain, arid areas, and the
like. Table 17-34 shows the recommendations of minimum specific
creepage distance in millimeteres per kilovolt.
Methods to determine contamination are:
Contamination Severity
This is divided into two general classes:
■
English salt fog method
Industrial. The industrial contamination is caused by
particles driven by wind and deposited on insulators surfaces.
The contamination may be dust, cement, fly ash, limestone,
and the like. These materials contain salt and form a conducting
layer when wetted. The contamination is specified in terms
of milligrams per square centimeter. To standardize industrial
contamination, the equivalent salt deposit density (ESSD)
is used. The surface conductivity is defined as the ratio of
the power frequency current over a sample insulator to the
applied voltage.
The contamination and wetting are applied simultaneously
by spraying saltwater, and the degree of contamination is
defined by the salt in the sprayed solution. The insulator
surface is purely resistive during the test period of 1 hr:
LC = 2 . 34 Sa0.224 = 7 . 09 ESSD0.224
where Sa is the amount of salt in water used for test in
kilograms per cubic meter.
■
Sea. Saltwater spray driven by wind is specified in terms of
grams per liter or in kilograms per cubic meter of water.
Wet contamination test
The test may be done with “light mixture” (contaminant
defined by the amount of dry contaminant and the surface
has a resistive-capacitive impedance) or “heavy mixture” (the
contamination defined by surface conductivity).
Table 17-1 lists ESSD according to IEEE3 and CIGRE2
17-2-2 Insulation Strength of Insulators
The design of air-insulated substation insulation is universally
based on rain conditions. According to IEEE recommendations,3
the insulation strength is defined as ratio of withstand voltage and
connecting length. The withstand voltage is determined by clean
fog test method. Table 17-2 gives the standard insulators in a string
for voltages from 138 to 765 kV. The standard suspension insulator
has a leakage distance of 292 mm (11.5 in).
IEC recommendations4 describe the creepage distance for ceramic
or glass insulators for different contamination severities. The specific
leakage distance Lc is determined by different contamination test
methods. The recommendation does not cover some environmental
TA B L E 1 7 - 2
(17-2)
German Kieselghur method
LC = 1 . 42σ w0.387 = 8 . 15 ESSD0.387
(17-3)
where sw is the insulatsor surface conductivity in µs.
Clean fog test
The test uses a slow or quick wetting process, and the insulator surface changes from dry to wet. In case of slow wetting,
the surface is capacitive-resistive.
Number of Standard Insulator Units (5.75 in ë 10 in) (146 mm ë 254 mm)3
NUMBER OF STANDARD UNITS REQUIRED FOR CONTAMINATION SEVERITY I-STRINGS/V-STRINGS
SYSTEM VOLTAGE
VERY LIGHT
LIGHT
MODERATE
HEAVY
138
6/6
8/7
9/7
11/8
161
7/7
10/8
11/9
13/10
230
11/10
14/12
16/13
19/15
345
16/15
21/17
24/19
29/22
500
25/22
32/27
37/29
44/33
765
36/22
47/39
53/42
64/48
Leakage distance = 11.5 in (292 mm) for the standard insulator unit
INSULATION COORDINATION
455
Japanese fog withstand method
LC = 7 . 14 ESSD0.246
(17-4)
Some contamination countermeasures are:
■
To increase the number of insulators, as discussed above, is
the most common method.
■
To use fog-type insulators, which may have a leakage
distance equal to 150 percent of the standard insulators;
though increasing the leakage distance is not the only criterion
for satisfactory performance. Leakage distance to length in
ratios of 2.9 to 4.5 are available.
■
Nonceramic insulators have hydrophobic surfaces, which
generally improve performance. The withstand voltage per
connected length improves by 40 to 100 percent.
■
The insulator’s surface at room temperature may be coated
with vulcanized silicon rubber (RTV coatings), which produces
a hydrophobic surface and improves performance.
■
Application of silicon greases improves performance, but it
has to be removed and re-applied periodically. The technique
can be applied to sea-salt contaminations. Silicon greases,
because of their temperature stability, can be used at higher
temperatures. The greases envelope the pollution and prevent
occurrence of a discharge.
■
Washing and cleaning of deenergized insulators has been used.
Washing techniques can be applied to energized insulators too.
Monitoring contamination is not so well established. Leakage
current monitoring may be unreliable because it is dependent on
the water present and the contamination. A contamination monitor was developed, which used ellipsometry to determine optical parameters of the contamination, and its thickness. However,
without wavelength scanning, it lacked the ability to distinguish
different types of contaminations. The alternative of ESSD measurement is laborious. Spectrophotometry to measure the thickness and
refractive index has been suggested.
17-3
DIELECTRICS
The term dielectric is synonymous with insulation. A dielectric or
electrical insulation, when placed between two electrodes at different potentials, permits only a small negligible current to flow. The
electrical resistivity may be of the order of 1020 to 106 Ω-cm.
Ideally, no current should flow through a perfect dielectric, but practically, an equivalent circuit can be drawn as shown in Fig. 17-1a and
accompanying phasor diagram (Fig. 17-1b). For a perfect dielectric,
the phase angle d, called the loss angle or dissipation factor, should be
zero. As the insulation deteriorates this angle increases, and measurements of the loss angle have been used to compare the deterioration over a period of time. We can write:
δ = tan −1(2π fCs R s )
= tan −1(1/ 2π fC p R p )
when R p = 0
wheen R s = 0
(17-5)
On application of dc voltage, there is an inrush current (absorption
current) which decays, and the conduction current remains, which
will flow indefinitely. When the voltage is removed, a recovery current flows, much akin to a discharge of a capacitor. This model of a
leaky capacitor is a simplified model of a dielectric.
Practically, the insulation resistance measurement at dc voltages
of 500 to 5000 V is carried out, and the value increases as the duration
F I G U R E 1 7 - 1 (a) Equivalent circuit of a leaky dielectric. (b) Phasor
diagram. (c) Change in 1 minute and 10 minutes insulation resistance during
drying of class B insulated armature winding; initial winding temperature
25° C, and final winding temperature 75° C.
of applied voltage increases. If the insulation is dirty or moist, the
steady value will be reached quicker. The polarization index is the
ratio of the 10-min resistance value to 1-min resistance value and is
a rough indication of the condition of insulation, Fig. 17-1c.
For an insulating material, a host of mechanical, chemical, and
aging characteristics must be considered, depending upon the insulation usage. These physical parameters, like heat resistance, thermal aging, ozone and corona resistance, moisture resistance, flame
resistance and toxicity (for cable insulation systems), and surface
contamination are as important as the electrical characteristics.
Only the thermal aspect is touched upon.
17-3-1
Heat Resistance
The electrical and mechanical properties of the electrical insulating materials (EIM) are temperature dependent, thus, the standards
specify the maximum temperature rise to which a specific EIM can
be continuously subjected. The term electrical insulated systems
(EIS) denotes one or more EIMs, with conducting parts. The limiting temperatures are based on consideration of reliability and useful life in service. As an example, the permissible temperature rises,
456
CHAPTER SEVENTEEN
TA B L E 1 7 - 4
Temperature Rise Limits for Machines with a 1.0 Service Factor5
TEMPERATURE RISE (°C)*
ITEM
a
b
MACHINE PART
Insulated windings
1. All horsepower (kW) ratings
2. 1500 hp or less
3. Over 1500 hp
a. 7000 V or less
b. Over 7000 V
CLASS OF INSULATION SYSTEM
METHOD OF TEMPERATURE
DETERMINATION
A
B
F
H
Resistance
Embedded detector†
60
70
80
90
105
115
125
140
Embedded detector†
Embedded detector†
65
60
85
80
110
105
135
125
The temperature attained by cores, squirrel cage windings, collector rings, and miscellaneous parts, such as
brush holders, brushes, and the like, shall not injure the insulation in any respect.
*
For machines which operate under prevailing barometric pressure and which are designed not to exceed the specified temperature rise at
altitudes from 1000 to 4000 m, the temperature rise, as checked by tests at low altitudes, shall be less than those listed by 1 percent of the
specified temperature rise for each 100 m of altitude in excess of 1000 m.
†
Embedded detectors are located in the slots of the machines and can be resistance elements or thermocouples.
for insulation of large induction motors, from NEMA5 are shown
in Table 17-4. The temperature rises are based on 40° C ambient.
There is a certain hot-spot temperature of insulation, and the specified temperature rises in the standards are below the hottest-spot
temperature by 10° to 15° C. The allowance between the allowable
temperature rise and maximum hottest-spot temperature is determined by thermal analysis or calculations, substantiated by testing
on prototype equipment. The concept of the hottest spot temperature
is that the temperature rise throughout a machine or electrical apparatus will not be uniform, and the hottest-spot temperature may be
embedded in a certain section of insulation, for example, in the
interlayer slot windings of an induction motor or in the windings
of a transformer. The electrical and mechanical properties will be
influenced in different ways and to different degrees as a function
of temperature and thermal aging. Some mechanisms influencing
thermal aging are:
■
Oxidation that can lead to molecular cross-linking
■
Continuous molecular polymerization, which may increase
physical and electrical strength first, but may subsequently
lead to decreased flexibility, embitterment, and early failure
under mechanical stress
■
Hydrolytic degradation in which moisture reacts with
insulation under the influence of heat
■
Chemical breakdown of constituents
■
Loss of volatile constituents
It can be safely said that much analysis, industry practice, and
experience is behind the application of an insulation system to an
electrical apparatus. Yet, the electrical insulations do break down
due to electrical stresses, contamination, inappropriate application,
surface contamination, tracking, treeing, and aging. When this happens, short circuit can occur, and it may involve phases and ground;
the single-line-to-ground fault being the most common.
17-4
INSULATION BREAKDOWN
The insulation capability defines the maximum electrical stresses
that it can withstand before there is a flashover, which may be
of temporary nature, that is, overhead lines. The insulation
capabilities are defined based on rigorous testing with impulse test
waveforms. The breakdown of insulation is a function of the
nature of dielectric, for example, air, oil, SF6, and vacuums. The
breakdown phenomena in various mediums have been widely
studied, and it is not the intention to go into much details of
it. A breakdown between two electrodes in any medium will
occur if sufficiently high voltage is applied, which will result in
an avalanche of charged particles between the electrodes. The
average applied field, Ea, is simply the voltage divided by the gap
distance between the electrodes, but the electrical field is rarely
uniform. As the electrical field is increased, electrons emitted by
cathode accelerate toward anode and collide with gas molecules
to release more electrons, and the critical factor in establishing
electron avalanche is the gap distance. For practical purposes, the
developments in insulation systems are centered on decreasing
the gap for a given applied voltage for the compactness and cost
reductions of the electrical equipment.
Practically, the breakdown process is more complex. It is accelerated by formation of streamers, created by localized distortion of
electrical field by space charge. These streamers appear at a certain
number of free electrons in the cloud (108), and the increased electrical field in the space charge could cause further increase in energy
and collisions. The critical point occurs when photons are emitted
from the collisions in the steamers. The electrical resistance across
the gap is reduced, and the current through this reduced resistance
causes more heating, creating more ions. At this point an arc is formed
between the electrodes, with very high temperatures and thermal
agitation. Thus, to define insulation coordination it can be said that:
All voltages (switching, lightning, power frequency) that occur
in practice and usage of an insulation system do not initiate a gap
breakdown. The various factors impacting insulation breakdown
are:
■
Electrical field intensity and uniformity
■
Polarity of asymmetrical gaps
■
The type of insulating medium, that is, restorable gas insulation and nonrestorable gas insulation characteristics
■
The type of electrical stress, that is, the time variation and
duration of electrical field
Table 17-5 gives relative breakdown voltages of gaseous insulating mediums.
INSULATION COORDINATION
TA B L E 1 7 - 5
Relative Breakdown Voltages
for Different Gases
GAS TYPE
RELATIVE BREAKDOWN VOLTAGE
Air
1
Sulphur Hexafluoride, SF6
2.2
Freon, CCl2F2, CF3SF3
2.4–3
Carbon tetrachloride, CCl4
6
Some important factors in the insulation breakdown process
can be itemized:
Effect of Voltage Polarity The effect of polarity is that a
positive space charge is created by bombardment of molecules by
electrons, and it alters the local electrical field density. The enhancement depends upon pre-existing nonuniformities. In a point-plane
gap, the field near the plane is more uniform than near the point,
and the space charge causes a negative-point plane gap to break at
higher voltages than a positive point-plane gap; Fig. 17-2a and b
clearly illustrate this.
457
When an electrode in air is positively charged, the breakdown
voltage is lower than if the electrode is negatively charged. Practically, in the high-voltage gaps, the high-voltage conductor is more
stressed and is more irregularly shaped. For the air-porcelain insulation, for example, tower or line insulation, positively charged
impulses produce the lower insulation strength. For self-restoring
insulation, the standards specify that the polarity which gives the
lower insulation strength must be used to establish BIL and BSL.
Though not so explicitly stated, this polarity is universally positive.
Effect of Gas Density The effect of gas density is shown in
Fig. 17-3; the Paschen’s curve is obtained by varying the nitrogen
pressure at a constant temperature. As the pressure is reduced, the
breakdown voltage decreases to a minimum. This can be explained
that with decrease of pressure, the molecular separation increases
and the electrons gain more energy before collision. From the
Paschen minimum, further reduction of pressure causes an increase
in breakdown voltage, and toward the vacuum, the gas itself
becomes less important.6 This very low-pressure region may be
classified as breakdown in vacuum.
Breakdown in Vacuum Vacuum interruption is extensively
used in circuit breakers and is briefly discussed here. Pressures
bellow 10–3 mm of mercury are considered high vacuum. The charged
particles are unlikely to cause collision with a residual gas molecule,
thus ionization by collision is minimal. Electrons can, however,
FIGURE 17-2
(a) Space charge builds up in a positive point-plane gap and its electric field strength. (b) Space charge builds up in a negative pointplane gap and its electric field strength.
FIGURE 17-3
Paschens curve of pressure dependence of breakdown voltage of nitrogen.
458
CHAPTER SEVENTEEN
FIGURE 17-5
Progressive treeing phenomena in solid nonself-restoring insulation, leading to ultimate breakdown.
FIGURE 17-4
Breakdown in vacuum.
be emitted from metal surfaces by high electric field intensity, a
phenomenon called field emission:
I = Ce
−
B
E
(17-6)
where I is the emission current, E is the, the electrical field intensity, and B and C are the constants. As the contacts in vacuum
separate, initially the gap is small and electrical intensity is high
to cause electron emission, giving rise to a breakdown spark. The
voltage not changing much, the current escalates. This phenomena
is called vacuum breakdown or vacuum spark (Fig. 17-4). This shows
the characteristics for 0.5-mm rough steel gaps. The nature of this
characteristic depends upon surface conditions and material of
electrodes.
Secondary emission takes place by bombardment of high-energy
particles on surface of electrodes. The current leaves the electrodes
from a few hot spots, and the current densities are high at these
spots. The arc core temperatures are of the order of 6000 to 15000 K.
At such high temperatures, emission takes place from electrode
surfaces, and is called thermal emission. The creep of materials,
occluded gases in the material, and the vacuum chamber material
create special design problems in vacuum circuit breakers. The
vacuum gap regains its dielectric strength at a rate of approximately
5 to 10 kV/µs. An arc cannot persist in ideal vacuum, and the
separation of contacts carrying current causes vapor to be released
from the contact material giving rise to plasma. The restrikes were
common in the earlier designs of the vacuum breakers and much
development has taken place in the contact materials to limit this
phenomena.
Time Factor in Breakdown Process It is evident that the mechanism of breakdown involves movement of electrons and their
ionization to form an avalanche action. Thus, the time is an important factor. The time to begin a breakdown is called the statistical
time lag and is the time interval before the first electron becomes free
to start an avalanche. Then there is formative time lag, which is the
time taken by discharge to propagate through the gap, depending
upon the electrical field intensity. The overall time to breakdown
decreases as the voltage increases, which increases the field intensity
for a given gap. This gives rise to volt-time breakdown curve discussed
further.
Breakdown in Liquid Dielectrics The breakdown voltages in
liquid dielectrics are, generally, higher than that in gases. This is due
to the higher density of molecules in liquids. The breakdown in SF6
is a special phenomena described in Chap. 8. The impurities in liquids,
for example, dissolved gas bubbles, cause local field concentrations
and partial bridging of gaps. Therefore, there are stringent requirements for purity of insulating fluids like transformer mineral oil,
which also serves a cooling medium. In practical designs, the liquid
volume in an apparatus, say a transformer, is determined by the
cooling requirements and electrical clearances. The electrical stress
is low, 5 percent of the breakdown value.
Breakdown in Solid Dielectrics In a uniform dielectric, the
breakdown mechanism will be similar to that of a gas. The molecular spacing is much smaller, and critical level of acceleration
between collisions can occur only over a narrow range of conditions. The electrical field stress causing the breakdown is defined
as the intrinsic electrical strength. A probability of thermal runaway
occurs because of increase in dielectric losses due to temperature.
The solid dielectrics are rarely uniform and perfectly homogeneous. An important mechanism of breakdown is the partial
discharges that occur in the voids and cavities left in the dielectric
during manufacture. These voids create localized areas of higher
electrical stress. The progressive elongation of the voids, due to
enlargement of voids, is the prominent cause of breakdown in
polyethylene (PE) and cross-linked polyethylene (XLPE) cables,
a phenomena known as treeing (Fig. 17-5). This figure shows
progressive treeing, and a flashover will occur when the gap is
bridged.
Surface tracking can cause long-term degradation through
chemical changes, carbonization, and erosion. The electrical field
strength is higher than average at the electrode/dielectric interface.
The surface abrasions, contamination, and moisture can eventually
lead to a complete breakdown.
17-4-1
Consequences of Insulation Breakdown
The consequences can be evaluated depending on the type of insulation. Important criteria are whether the insulation is self-healing
or restorable or nonrestorable. A breakdown of solid dielectrics is
unlikely to be restorable, as it will do permanent damage, that is,
puncture of the insulation. Surface tracking (e.g., insulators) may
be restorable. The liquid insulation may be contaminated after an
electrical discharge (e.g., bulk oil and minimum oil-content circuit
breakers), and full dielectric strength may not be recoverable. The
number of fault current interruptions in a circuit breaker is limited,
after which the medium must be tested and replenished. In
essence, transmission line breakdowns can be qualified as restorable. All other insulations, regardless of type, are considered nonrestorable. The insulation system in an electrical apparatus may
not be exclusively restorable or nonrestorable—the bushings on
the top of a transformer tank and the transformer windings inside
the tank.
Thus, the various insulating mediums have much different
characteristics with respect to withstand characteristics of voltage
stresses. The test standards standardize the lightning, switching,
and power frequency overvoltages that the insulations need to
withstand. The designs of an electrical apparatus must cater to the
specified test requirements.
INSULATION COORDINATION
17-5 INSULATION CHARACTERISTICS—BIL
AND BSL
An impulse test wave as shown in Fig. 5-18 is supposed to mimic
the lightning impulse impinged on the electrical apparatus and is
North American practice of testing for BIL. It is extensively used
as a measure of insulation characteristics. The BIL level may be
considered equal to the peak value of 1.2/50-µs wave that will not
cause breakdown.
The BIL specified in the standards for various equipments are
arrived at by industry practices, consensus between manufacturers
and utilities, and application of surge arresters.
Data in Table 7-1 is specific to the liquid-immersed transformers. Similar data is applicable to other electrical equipment, for
example, circuit breakers, outdoor substations and bushings, and
gas-insulated substations. These BSL and BIL data are not reproduced here, but are required for practical insulation coordination
in a power system. Values similar to Table 7-1 are shown in the relevant standards. For the same rated voltage, it is possible to select
lower or upper values of BIL, which also relate to the switching
surge levels. This selection will depend upon a number of factors,
for example, the Keraunic lightning level of a place, the atmospheric
pollution, (an installation close to a sea shore with salt-laden sprays
versus a clean atmospheric conditions in a temperate climate), application of surge arresters, the overvoltage studies, and the like. As
the system voltage rises, the high cost of equipment requires more
careful evaluation of overvoltages of various origins. This requires
extensive computational requirements for overvoltage predictions
using TNAs or digital computers.
IEC7 divides the electrical systems into Range I (1 kV < Vm ≤
245 kV) and Range II (Vm > 245 kV) with respect to the standard
withstand voltages and testing procedures. IEEE draft standard
Proposal PC62.82/D2 for insulation coordination8 does the same.
The standard withstand voltages for Class I (15 kV < Vm ≤ 242 kV)
and Class II (Vm > 242 kV) are shown in Tables 17-6 and 17-7,
respectively.
Both ANSI/IEEE and IEC specify the standard values of BSL
and BIL, and generally a choice can be made out of these standard
values depending upon the availability of standard manufactured
equipment. To select an insulation level for a certain voltage without regard to the standard equipment availability is not prudent.
Equipment goes through rigorous testing according to standards to
meet the requirements of BIL and BSL.
BSL for circuit breakers is only given for voltages above 362 kV.
Also for circuit breakers, for each system voltage, two BSL values
are given. BSL for a 362-kV circuit breaker increases from 825
(closed position) to 900 kV in the open position. BSLs/BILs for GIS
are given in Table 17-8.9
Phase-to-Phase and Phase-to-Ground Withstand Internationally an extensive study has been made whether the phaseto-ground insulation levels can also be applied to phase-to-phase
conditions. The results show that the values of phase-to-ground
power frequency, temporary overvoltages, and switching overvoltages are inadequate for phase-to-phase conditions. IEC specifies
phase-to-phase BSL, as shown in Table 17-9.7 The test for phase-tophase BSL consists of applying equal positive and negative switching impulses to each electrode. The phase-to-phase BSL is 1.5 to
1.7 times the phase-to-ground BSL.
In ANSI standards, BSLs are only specified for maximum system
voltages at and above 300 kV. Phase-to-phase BSLs are not standardized in the United States.
The various combinations of the withstand voltages specified
in the standards must be selected after appropriate studies. The
equipment withstand voltages are standardized within the ratings in the standards. For example, users can lay down specifications for any of the combinations for their maximum system
operating voltage.
TA B L E 1 7 - 6
HIGHEST VOLTAGE
Vm
(PHASE-TO-PHASE)
(kV, rms)
FOR EQUIPMENT
459
Standard Withstand Voltages
for Class I8
LOW-FREQUENCY,
SHORT-DURATION
WITHSTAND (PHASETO-GROUND) (kV, rms)
LIGHTNING IMPULSE
WITHSTAND
VOLTAGE (kV) CREST
15
34
95
110
26.2
40
50
125
150
36.2
50
70
150
200
48.3
95
120
72.5
95
140
250
350
121
140
185
230
350
450
550
145
185
230
275
450
550
650
169
230
275
325
550
650
750
242
275
325
360
395
480
650
750
825
900
975
1050
TA B L E 1 7 - 7
HIGHEST VOLTAGE FOR
EQUIPMENT Vm
(PHASE-TO-PHASE) (kV, rms)
Standard Withstand Voltages
for Class II8
BIL
(PHASE-TO-GROUND)
(kV, PEAK)
BSL
(PHASE-TO-GROUND)
(kV Peak)
362
900
975
1050
1175
1300
650
750
825
900
975
1050
420
1050
1175
1300
1425
850
950
1050
550
1300
1425
1550
1675
1800
1175
1300
1425
1550
800
1800
1925
2050
1300
1425
1550
1675
1800
460
CHAPTER SEVENTEEN
TA B L E 1 7 - 8
Voltage Ratings for Gas-Insulated Substations9
SYSTEM VOLTAGE
TYPE TEST VOLTAGES
RATED MAXIMUM VOLTAGE
(PHASE-TO-PHASE) (KV, rms)
RATED BIL (KV) CREST
LOW-FREQUENCY (PHASE-TO-GROUND)
WITHSTAND (KV, rms)
SWITCHING SURGE
WITHSTAND (KV), CREST
72.5
350
160
121
550
215
145
650
310
169
750
365
242
900
425
362
1050
500
825
550
1550
740
1175
800
2100
960
1550
Note: Disconnect switch open-gap withstand shall be 10 percent higher than the substation type test values.
TA B L E 1 7 - 9
MAXIMUM SYSTEM VOLTAGE (KV)
IEC BIL and BSL7
PHASE-TO-GROUND BSLg (KV, PEAK)
RATIO BSLp /BSLg
BIL (KV, PEAK)*
300
750
850
1.5
1.5
850, 950
950, 1050
362
850
950
1.5
1.5
950, 1050
1050, 1175
420
850
950
1050
1.6
1.5
1.5
1050, 1175
1175, 1300
1300, 1425
550
950
1050
1175
1.70
1.60
1.50
1175, 1300
1300, 1425
1425, 1550
800
1300
1425
1550
1.70
1.70
1.60
1675, 1800
1800, 1950
1950, 2100
*
For each of the two BILs in this column.
17-5-1
Tail-Chopped Wave
This simulates the stresses on the system insulation, when it is subjected to a lightning impulse of 1.2/50 µs, and the voltage suddenly collapses on the tail of the wave shape due to an insulation
breakdown elsewhere in the system. The time to chop varies with
the peak voltage (Fig. 17-6).
17-5-2
Front-Chopped Wave
Flashover occurs on the rising edge of the 1.2/50-µs wave. The time
to chop tc is determined as shown in Fig. 17-7. This impulse is used
when the rate of rise of voltage is a critical parameter. It mimics the
behavior in the first few microseconds of a high-magnitude lightning surge prior to insulation flashover.
17-5-3
Standard Switching Impulse
The standard switching impulse is 100/1000-µs wave (Fig. 19-11).
Table 7-1 shows BIL levels of transformers and also switching surge
levels. While statistical methods are used for self-restoring insulation, for non-self-restoring insulation, these procedures cannot
be used. The insulation strength is specified by conventional BSL.
FIGURE 17-6
Tail-chopped 1.2/50-µs wave.
INSULATION COORDINATION
FIGURE 17-7
461
Front-chopped 1.2/50-µs wave.
The required BSL is the arrester switching impulse discharge voltage multiplied by protective ratio (Chap. 20).
The switching impulse strength is dependent upon components
of the phase-to-phase switching impulse, and both positive and
negative SOVs must be known. The collection of SOV’s may be:
■
The positive and negative polarity SOVs
■
The positive and phase-to-phase SOVs
■
The negative and phase-to-phase SOVs
In the collection of data for positive and negative SOVs, the time
constants considered are: (1) the time for which maximum positive SOV occurs and (2) the time for which the maximum phaseto-phase SOVs occur. For air clearances, in general, the maximum
positive SOV is more severe, and for non-self-restoring insulation,
the maximum phase-to-phase SOV is more severe.
17-6
VOLT-TIME CHARACTERISTICS
As the time duration of application of surge voltage to insulation
decreases, it can withstand higher stresses. This is an important factor
in the insulation coordination with surge arrester characteristics.
For restorable insulation systems, the volt-time characteristics
can be plotted by applying a series of standard test impulses with
progressively higher peak values and noting down the time to
breakdown in each case, which gives volt-time (V-t) characteristics (Fig. 17-8). The breakdown occurs in a smaller time as the
voltage peak is raised. Note that the breakdown is possible even
after the peak of the wave, as shown for time t1 in this figure.
There is a time delay between the initiation of discharge and its
breakdown. In this case, the breakdown voltage is taken as the
peak of the wave, though breakdown occurs on the tail. The time
to breakdown of insulation is an important parameter, when two
or more components are subjected simultaneously to the same
impulse stress.
FIGURE 17-8
17-7
Construction of volt-time breakdown characteristics.
NONSTANDARD WAVE FORMS
A question arises, that what is the impact of irregular wave shapes
that occur at various points in a system? These irregular wave shapes
are unidirectional or oscillatory. The insulation strength is based
on standard BIL tests. A correlation between the test wave shapes
and the irregular wave shapes is analyzed in Ref. 10. It relates a
nonstandard wave to the transformer volt-time curve as shown in
Fig. 17-9. This curve is a composite of three test points, A the standard full wave, B the chopped wave, and C the front of wave. The
equivalence considers that:
1. The nonstandard wave remains below the transformer withstand curve at all points.
462
CHAPTER SEVENTEEN
FIGURE 17-9
Voltage breakdown characteristics for nonstandard impulse wave forms.
2. The surge must not be above the line AC for longer than
half the time of AC. This second condition is imposed as the
nonstandard wave may impose more stresses on the insulation
than the standard wave shapes.
A number of graphs at various percentages of ordinates of the
volt-time curve are drawn. A percentage surge factor is assigned
to the nonstandard wave shape, and a margin of 10 percent is
required, for example, a 90 percent surge factor for nonstandard
wave is acceptable for the construction shown in Fig. 17-9.
IEEE standard3 recommends a minimum protective margin of
1.15 on BIL for non-self-restoring insulation. Industry uses higher
margins. For self-restoring insulation, the protective margin is not
recommended, and the recommended method is to raise mean time
between failures (MTBF) by increasing its value. The higher MTBF
indirectly results in the increase in the severity of incoming surge.
17-8
PROBABILISTIC CONCEPTS
Breakdown in insulations is a random phenomenon and involves
complex breakdown mechanisms. It can be said that there is no
single impulse level above which the breakdown always occurs and
below which the breakdown never occurs. Some impulse applications may produce flashover, while others with the same amplitude may be withstood by the insulation. This is particularly true
for large gaps. There is a band of impulse magnitudes over which
breakdown is likely to occur.
The probability distribution of the likelihood of breakdown
across this band of impulse waves is statistically called the normal
distribution or Gaussian distribution (App. F). Figure 17-10 shows
that the band is characterized by a mean value at which there is
a 50-50 chance of a breakdown, and a band outside at which the
breakdown has essentially 100% and 0% probability (when the
curve is extended to infinity). The mean value of the breakdown
voltage for the standard impulse voltage wave shape is also known
as the critical breakdown (flashover) voltage (CFO), which has significance in defining insulation withstand levels. The time to breakdown
at this voltage is typically 3 to 20 µs. This means that the breakdown
occurs on the tail of the test wave as shown in Fig. 17-6. The width
FIGURE 17-10
Gaussian distribution.
of the normal distribution is specified in terms of s, the standard
deviation of breakdown voltage. The distribution indicates that:
VB0 ≈ VB0.13 = VB50 − 3σ
VB100 ≈ VB99.87 = VB50 + 3σ
(17-7)
where VB0.13 is the impulse level at which breakdown occurs in
0.13 percent cases of full-impulse applications, for example, the
breakdown probability is low. VB99.87 is the impulse level at which the
breakdown occurs in 99.87 percent cases of full-wave applications, for
example, the breakdown probability is high. For a rod gap, this approximates phase-to-phase impulse behavior of overhead line insulation:
σ = 0 . 03 VB50
(17-8)
INSULATION COORDINATION
Therefore:
VB0 = 0 . 91 VB50
(17-9)
VB100 = 1 . 09 VB50
For air-insulated equipment, BIL rating is normally assigned so
that it represents a probability of breakdown of 9.7 percent or less,
typically:
BIL ≤ VB50 − 1 . 3σ = 0 . 96 VB50
As the breakdown causes permanent damage to the insulation, the volt-time characteristics cannot
be established by repeated applications of test impulse voltage. A
BIL is dictated by an appropriate standard, and testing is performed
to ensure that there is no breakdown for the specified levels. The
magnitude of various types of test impulses is determined by multiplying BIL with appropriate factors. For most oil-immersed apparatus, these factors are shown in Table 17-10.11
We can write an expression for the breakdown probability function in Gaussian distribution as:
P(V ) =
2
− 1 V − V50
exp
∫ 2 σ
σ 2π −∞
V
1
P(V ) =
1
2π
z2
∫ exp − 2
σ
V3 = CFO 1 − 3
CFO
CFO = k g
where CFO is in kilovolts. The variable kg is called the gap factor,
and at the center phase of a tower, it is given by:
where:
(17-13)
This cumulative Gaussian distribution function is shown in
Fig. 17-11a. If this function is plotted with (V − V50 )/σ as the
y axis, the breakdown function becomes a straight line (Fig. 7-11b).
We can write s as:
CFO+ = 560S
(positive polarity)
CFO− = 605S
(negative polarity)
1. Strike distance to tower side
where n is the number of tests. Table 17-11 can be constructed (also
see App. F). Extensive tables for Gaussian distribution are available
in many texts (App. F).
IMPULSE DURATION
2. Strike distance to upper truss
3. Insulator string length divided by 1.05
Factors for Estimating Withstand Voltages of
Mineral Oil–Immersed Equipment11
BIL MULTIPLIER
EQUIPMENT TYPE
Front of wave (0.5 µs)
1.30–1.50
Transformers and reactors
Chopped wave (2 µs)
Chopped wave (3 µs)
Chopped wave (3 µs)
1.29
1.10–1.15
1.15
Breakers 15.5 kV and above
Transformers and reactors
Breakers 15.5 kV and above
Full wave (1.2/50 µs)
1.00
Transformer and reactor windings
Switching surge, 250/2500 wave
Switching surge, 250/2500 wave
Switching surge, 250/2500 wave
0.83
0.63–0.69
0.63–0.69
Transformer and reactor windings
Bushings
Breakers 362–800 kV*
*
Includes air blast and SF6 breakers.
(17-17)
(17-18)
For wet conditions, multiply Eq. (17-16) by 0.96, (4 percent
decrease). As outer phase has a higher CFO, multiply Eq. (17-16)
by 1.08; V3 is increased by 10% for fronts of 1000 µs or longer. For
V-strings the insulator string length is a minimum of 1.05 times the
strike distance to structure. For I-string insulators, multiply Eq. (17-16)
by 1.10. The distance S is minimum of the following three distances:
(17-14)
TA B L E 1 7 - 1 0
(17-16)
where h is the conductor height and W is the tower width. Usually
kg = 1.20 for lattice type towers and 1.25 for steel poles where
tower width is small. For lightning impulse, the CFO may be determined from:
(17-12)
1/ 2
σ = ∑(V − V50 )2 /n
3400
1 + 8 /S
h
k g = 1 . 25 + 0 . 005 − 6 + 0 . 25(e −8W /S − 0 . 20)
S
−∞
V − V50 V − CFO
=
z=
σ
σ
(17-15)
Based on the system studies like EMTP, V3 can be substituted
with calculated maximum voltage. This leads to the deterministic
design of transmission lines provided V3 can be accurately calculated. A relation between CFO and strike distance, S, here meaning
clearances, is given by:13
(17-11)
This can be written as:
z
If the voltage is twice the standard deviation below the critical voltage (z = –2), the probability of disruptive discharge is
2.3 percent, and the probability of withstand, therefore, = (1 – P) =
0.977(97.7 percent). While s is a measure of the scatter or dispersion of observations about the mean or CFO, s/CFO is called the
coefficient of variation, as the standard deviation is normally given
in per unit or percentage of CFO. It varies with the wavefront, wet/
dry conditions.12 Therefore, the line insulation voltage denoted by
V3 can be written as:
(17-10)
Nonrestorable Insulation
463
464
CHAPTER SEVENTEEN
F I G U R E 1 7 - 1 1 (a) Breakdown probability of external insulation, linear scale Gaussian distribution (b) Breakdown probability of external insulation,
Gaussian scale, s, standard deviation.
TA B L E 1 7 - 1 1
z
–3.0
Normal (Gaussian) Distribution
–2.0 –1.28 –1.0
P (%) 0.13
2.3
10
0
15.9 50
1.0
1.28 2.0
84.1 90
3.0
97.7 99.87
An insulator has a V50 = 1000 V with s =
5 percent. A switching voltage of 900 kV is applied to the insulator.
Then:
Example 17-1
z=
900 − 1000
= −2
0 . 05 × 1000
This means –2 standard deviations below the mean, and referring to Table 17-11, P = 2.3 percent. There is a 2.3 percent chance
of flashover every time the insulator is subjected to a 900-V switching surge.
Example 17-2 Calculate the strike distance for a 400-kV line,
with standard atmospheric condition. Wet coefficient of variation =
5 percent and maximum switching surge = 2.5 pu. Width of tower
W = 1.5 m and height of tower h = 20 m. Maximum system voltage
from Table 17-7 = 420 kV. Switching surge voltage = 1050 kV. From
Eq. (17-16) CFO = 1050/0.85 = 1235 kV.
Note that S appears in both Eqs. (17-16) and (17-17). Therefore,
iteration is required to calculate S. A value of 3.1 m satisfies both
the equations by hit and trial. This gives center-phase clearance of
3.1 m. The strength of the outer phases will be greater.
Example 17-3 Calculate the recommended number of standard insulators for the line in Example 17-2. From Table 17-2,
the standard insulators are 5.75 × 10 in. Increase the calculated
3.1 m by 5 percent, say = 3.26 m, then the number of insulators
required are 24 (I-Strings). These have a leakage distance of 7008 mm.
According to Table 17-3, IEC recommendations, for lightly polluted conditions, a specific creepage of 420 × 27.7 = 11634 mm
is required for light pollution conditions. It is prudent to consider
both the clearances and the creepage, depending upon the severity
of contamination.
Nonstandard Atmospheric Conditions The following
expressions for nonstandard atmospheric conditions are from
Ref. 13
Vns = δ m H cwVs
(17-19)
INSULATION COORDINATION
where Vns is the voltage for nonstandard conditions, Vs is the voltage for standard conditions, d is the relative air density, Hc is the
humidity correction factor, and m and w are constants depending
upon G0 given by:
G0 =
CFOs
500S
(17-20)
m = 1 . 25G0 (G0 − 0 . 2)
where S is the striking distance in meters and CFOs under standard
atmospheric conditions. Further explanations of the factors are in
Ref. 3.
Flashover of Gaps in Parallel The number of insulation components in parallel between phases to ground, say in a transmission
line, may run into thousands, depending upon the station configuration. For example, in a transmission line, thousands of insulator
strings connect a phase conductor to ground. With two gaps in parallel, assume that: (1) only one of the two gaps first flashes over, (2)
a total flashover will be initiated by the gap that has shortest time to
breakdown. The probability of flashover of the first gap will be:
P1′ = P1(1 − P2 ) + (P1P2 )P1,2
(17-21)
where P1 and P2 are the probabilities of first and second gaps flashing
first, respectively, P1P2 is the probability of simultaneous flashover,
and P1,2 is the probability that first gap is faster than the second gap
2 to break. A similar expression for second gap will be:
P2′ = P2 (1 − P1 ) + (P1P2 )P2,1
(17-22)
P1,2 + P2,1 = 1
(17-23)
P1,2 and P2,1 are the functions of the probability density distributions f1(t1 ) and f2 (t 2 ). Thus:
∞ ∞
P1,2 =
The attenuation of the traveling waves should be considered in
evaluating the line’s flashover probability.
17-9
MINIMUM TIME TO BREAKDOWN
The time to breakdown (TBD) of a system of parallel gaps or insulators is also a random quantity. The distribution of TBD is important
for insulation coordination and surge protection. The probability
distribution of collective TBD is composed of TBD probability densities of individual components, each being weighted for a corresponding probability of occurrence of breakdown. Let us consider
two gaps in parallel with breakdown probabilities of P1 and P2 and
TBD distributions of f1(t) and f2(t) under a given impulse. Then the
TBD distribution of the combination is:
fc =
∞
∫ ∫ f1(t1 ) f2(t2 )dt1dt2
(17-24)
0 t
If we consider Gaussian distribution, mean values T1 and T2 and
corresponding deviations:
1 1
P1,2 = +
2
2
(T2 −T1 )/ σ 12 −σ 22
∫
0
−t 2
exp dt
2
(17-25)
φ[P1, P2 , f1(t ), f2 (t )]
∫ φ[P1, P2, f1(t ), f2 (t )]dt
(17-28)
0
where, in view of Eq. (17-21):
ϕ = P1(1 − P2 ) f1(t ) + P2 (1 − P1 ) f2 (t ) + P1P2 f12 (t )
(17-29)
and the denominator must fulfill the constraint:
∞
∫ fc (t )dt = 1
(17-30)
0
The overall distribution of TBD of a n-gap system can be shown
to be:
fc (t ) =
Also:
465
n
n!
1
P r (1 − P )n−r f(r )(t )
∑
Pc r =1 (n − r )!
(17-31)
where r considers different combinations of gaps, that is, singles,
twos, threes, and so on out of n gaps. If individual breakdown
probabilities are small, all combinational contributions to fc(t) can
be neglected and the combination probability approaches equal to
that of a single gap f(t).
17-10
WEIBULL PROBABILITY DISTRIBUTION
A fundamental problem of Gaussian distribution is the truncation value. Physically, no discharge can occur below the minimum
value of V. The function is, therefore, truncated at VB0 = VB50 – 3s.
Yet, with Gaussian distribution it is not, so IEC4 adopts Weibull
distribution. See App. F for further details and the differences of
distribution functions, Gaussian, and Weibull. Figure F-5a and b
diagrammatically represent the comparison.
The overall probability of breakdown of two gaps is:
Po = P1′ + P2′ = P1 + P2 − P1P2
(17-26)
Identical Gaps in Parallel If the probability of breakdown of a
single gap is P, then for n identical gaps in parallel, the probability
of breakdown Pn is given by:
Pn = 1 − (1 − P )n
(17-27)
If the distribution of the breakdown probability of a single gap, P, is
accepted to be cumulative Gaussian distribution, the distribution of
Pn is not Gaussian. If we consider insulators in parallel on a transmission system, the probability of withstand decreases as the numbers
of insulators in parallel increase. From Eq. (17-27), if the probability of withstand of a single insulator is considered 99 percent, and
the insulators on successive towers are considered in parallel, then
20 insulators in parallel give a withstand probability of 82 percent.
17-11
AIR CLEARANCES
In installations like electrical substations, which cannot be tested
as a whole, it is necessary to ensure that the dielectric strength is
adequate. The switching and lightning withstand voltages in air
should be greater than the withstand voltages specified in the standards at the worst atmospheric conditions, and again a choice of
the appropriate withstand levels can be made through simulations
and simplified calculations.
IEC4 provides tables for minimum clearances with a conservative approach based on BIL and different electrode configurations
(rod or conductor to structure). Also tables for minimum clearances
are provided for switching impulse withstand voltage (750 kV or
higher) for phase-to-ground and phase-to-phase. These are not
reproduced here.
The equivalent IEEE standard, Draft Guide for Recommended
Electrical Clearances and Insulation Levels in Air Insulated Electrical
Power Substations is yet in the draft form.13 NESC,14 specifies safety
466
CHAPTER SEVENTEEN
clearances, which override the calculations and all other standard
specifications.
The draft standard13 considers many factors like altitude, contamination, reduced air gaps due to corona rings, arcing due to air break
switches and expulsion fuses, and areas of high keraunic level.
17-11-1
Clearances Based on BIL
where kg is the gap factor depending upon the gap configuration.
It is one for rod-plane gap and a maximum of 1.35 for rod-rod
(horizontal ) gap. For substation air clearances, kg = 1.3 is suggested.
dm is the altitude correction factor which is 1.0 at sea level. Substituting in Eq. (17-36)
S=
Phase-to-ground clearances based upon BIL are given by the
equation:
S=
(17-32)
CFOgradient
where CFO gradient has been taken as 605 kV/m, a value found
satisfactory for typical geometry of air-insulated substations, and
S is the metal-to-metal strike distance in meters. With respect to
selection of BIL and clearances for the transformer:
1. If the time to crest tT is > 3µs, then BIL = 1.15Vt.
2. If the time to crest tT is < 3µs, and Vt /Vd ≤ 1.10 then BIL =
1.15(Vt /1.10). Vd is the calculated arrester discharge voltage
and Vt is the voltage at the transformer terminals.
3. In addition to above criteria, if the tail time constant of the
incoming surge is > 30 µs, then BSL = (1.15/0.83)Vd.
Therefore Eq. (17-32) can be written as:
1 . 15 BIL BIL
=
605
526
(17-33)
The draft standard13 postulates that at the struck point, the
phase-to-phase voltage is less than the phase-to-ground impulse
voltage, and phase-to-phase impulse voltages seldom exceed the
phase-to-ground impulse voltages. As a result, the phase-to-phase
clearances for lighting impulse can be equal to phase-to-ground
clearances.
17-11-2 Phase-to-Ground Clearances Based
on Switching Surges
The statistical probability, Gaussian distribution, reflecting 10 percent
probability of flashover is given by Eq. (17-1), repeated here:
BSL = CFO − 1 . 28σ
σ
= CFO 1 − 1 . 28
CFO
(17-34)
For self-restoring insulation, the coefficient of variation is
smaller for lightning impulses than for the switching impulses. For
lightning impulses, this coefficient is 3 percent, and for switching
impulses on line or tower insulation, it increases to an average of
5 percent. For station insulation, it is generally 0.06 or 0.07. With
a value of 0.07 (= s/CFO), Eq. (17-34) is:
BSL PH−G = 0 . 9104 CFO
(17-35)
Above 240 kV, switching surge conditions usually dominate.
The following relation holds for flashover of air gap and strike
distance for various air-gap configurations up to at least 30 m.
S=
8
(3400k g )δ m
CFO
(17-37)
The factor d, relative air density, is:
Vcrest ph-g
S=
8
8
=
(3400 × 1 . 3)
( 4024 /BSL − 1)
−1
BSL / 0 . 9104
(17-36)
−1
δ = 0 . 997 − 0 . 106 ( A )
(17-38)
where A is altitude in kilometers, and m is a constant defined by:
m = 1 . 25 G0 (G0 − 0 . 2)
(17-39)
where:
G0 =
CFO 1 . 07 BSL
BSL
=
=
500S
500S
467 S
(17-40)
This requires an iterative solution.
17-11-3 Phase-to-Phase Clearances Based
on Switching Surges
As stated before, phase-to-phase clearances are not yet established
in ANSI/IEEE. With respect to Table 17-8, which gives IEC factors of 1.5 to 1.7, Hileman found ratios as high as 1.25 to 1.40.15
Table 7 in the draft standard13 gives gap factor and coefficient of
variation for phase-to-phase switching impulses, from which S
can be calculated.
17-12
INSULATION COORDINATION
The objective of insulation coordination, a sort of overvoltage coordination, is to minimize the number of insulation failures and,
consequently, the number of interruptions. Thus, the insulation
coordination is selection of the electrical strength of the electrical
equipment and its application in relation to the overvoltages that
appear in the electrical system, taking into account the characteristics of the surge protective devices, so that an economical and
operationally acceptable level of probability is achieved.
The words “probability” and “surge arresters” are noteworthy.
The probability should be at an acceptable level to limit damage to the equipment or effect continuity of service. Also use
of surge protective devices to achieve the desired end of reducing the expense of installations by reducing the overvoltages is
an important consideration. Without surge protection devices,
an electrical system will be phenomenally expensive to design,
and proper applications of surge protection devices become of
paramount importance as the system voltage rises. A reader may
like to refer to Chap. 20 on surge arresters concurrently with this
chapter, as practically, the insulation coordination at all voltage levels
must consider the application of surge arresters. The electrical
insulation is selected to withstand dielectric stresses, classified
as follows:
■
Power-frequency voltage under normal operation. This
voltage for the purpose of insulation coordination is considered
to be the highest system voltage. The system operating voltage
is regulated by the utilities and a 5 percent overvoltage limit
seems appropriate. This may be exceeded in some cases, that
is, close to a generating station. ANSI standard C84.1-1989
specifies the nominal voltages and the operating voltage ranges
for equipment operating from 120 V to 34.5 kV in the United
States. See Chap. 7 for further discussions.
INSULATION COORDINATION
■
Temporary overvoltages. These arise from ground faults, load
rejection, and ferroresonance, and we have discussed these in
the previous chapters.
■
■
467
impedance of substation ground. Though the previous chapters provide practical data, simulations, and other considerations that are
applicable, standards need to be consulted for further guidelines.
Switching overvoltages, discussed in previous chapter.
17-12-1
Lightning overvoltages, discussed in previous chapter.
For the purpose of insulation coordination, the electrical systems can be
subdivided into four major categories: transmission lines, substations,
industrial and commercial power systems, and GIS installations.
In other words, all the transients categorized in Table 1.3 must
be considered. Figure 17-12 shows a flowchart for the selection of
the insulation characteristics. This is rather an oversimplification
of a complex process. The electrical system characteristics, calculations of overvoltages for the particular system, and application of
surge arresters are the key elements, which have varying parameters, not standardized by equations.
Experience shows that developments of generalized equations
for expected overvoltages are difficult due to the large number of
parameters affecting the results. Further, high levels of skills are
required for such calculations. Apart from calculations, experience
and practice play an important role.
In each category, the overvoltages at the equipment terminals
need to be calculated and the application of surge arresters accounted
for. Both phase-to-phase and phase-to-ground overvoltages need to
be calculated. Specific considerations apply with respect to the systems protected. As an example, all lightning events within a certain
distance from substation cause higher overvoltages at the protected
equipment than an assumed value, and all events outside the distance cause lower values. It has been documented that backflashovers do not occur at a tower close to the substation due to lower
FIGURE 17-12
Types of Electrical Systems
1. Transmission lines. We have discussed overvoltages on OH
lines in the previous chapters, particularly Chaps. 4, 5, and
7. Flashovers across insulator strings or phase conductors to
ground wires do not lead to permanent failures but transient
overvoltages. These momentary overvoltages should be
minimized at an optimum cost, and statistical procedures are
used, as stated before. The basic parameters involved are:
■
Shielding designs for direct strokes
■
Type of grounding systems; utility high voltage systems are
invariably solidly grounded (Chap. 21)
■
Estimation of the number of lightning strokes, shielding
failures, probability of backflashovers, as discussed in the
previous chapters
■
Pollution and atmospheric impacts
■
Tower footing impedance, voltage on tower top, and crossarms due to a lightning stroke
Simplified flowchart for insulation coordination.
468
CHAPTER SEVENTEEN
2. Substations. Substations contain transformers and other
valuable equipment with non-self-restoring insulation which
must be guarded against internal breakdowns. Repairs/
replacement of a large transformer will be expensive and
will result in much downtime. This cannot be tolerated for
continuity of power supply. Even a risk of flashover in air
with consequent disturbances should be kept to a minimum.
Substations are invariably shielded from atmospheric lightning by suitable arrangement of ground wires on high masts,
rising above the substation outdoor structures. These ground
wires are continuous with the incoming/outgoing transmission lines/distribution lines/sky wires, and are grounded at
each mast and also at substation outdoor structures. The
effectiveness of grounding plays an important role in surge
diversion. The equipment to be protected varies: large
transformers, circuit breakers, reactors, capacitor banks, bus
work, and the like. It is standard practice to provide surge
arresters on the primary and secondary side of each power
transformer on the incoming/outgoing lines from the substations, and at the junctions of the cables/overhead lines. The
lightning/switching overvoltages occur due to:
■
Direct lightning strokes due to shielding failures
■
Lightning/switching surges from the lines, entering and
leaving the substation
■
Backflashovers
■
Lightning strikes in the vicinity of the substation, giving rise
to induced lightning overvoltages
The rolling sphere model and other lightning protection models
for structures are discussed in Chap. 22.
The mechanism of induced voltage on the line for a nearby lightning
stroke is illustrated in Fig. 17-13, and several models are reported in
literature16,17 (see also Chap. 5). A simplified equation is:
where:
β = 0 . 004I 0.64 + 0 . 068 (first stroke)
= 0 . 004I 0.86 + 0 . 1 8 (subsequent strokes )
Z0 is the surge impedance and I is the stroke current and other
parameters are shown in Fig. 17-13.
The lighting-induced voltages in transmission lines and substations
for strokes to ground in the vicinity of the installations are generally
limited to approximately 300 kV and can be ignored for system voltages
above approximately 145 kV. Also the substations are generally considered perfectly shielded and a direct lighting stroke on the substation
structures is excluded. Therefore, the surges entering the substation
are a result of strokes on lines close to the substation, backflashover, or
shielding failure. The backflashover gives rise to overvoltages of steep
wavefront as shown in the EMTP simulation in Chap. 5.
3. Industrial systems. When the industrial systems are connected to
utility overhead systems, they will be exposed to the overvoltages
of atmospheric origin through the OH lines. The industrial systems
vary in complexity and power usage, and some large industrial
systems may receive large chunks of power, even of the order of
80 to 200 MW across high-voltage substations located within the
industrial premises. Cogeneration modes are also common, and
an industrial plant may generate excess power than what it consumes, depending upon the processes. Thus, lightning and switching surges are of consideration, the system grounding playing an
important role—most industrial systems have 22, 13.8, 4.16, or
2.4 kV as the primary distribution voltages, and these mediumvoltage distribution systems are invariably resistance grounded
(Chap. 21). Sudden load rejection, temporary overvoltages due to
faults, switching surges, impingement of lightning surges through
utility connections, and induced lightning voltages due to nearby
strokes—all enter into an informed surge protection strategy.
4. GIS. See Chap. 18.
17-12-2
1
1 + ( x + β y)
2β x + y
+ 2
2
2
2
2
y + (2β x + y)2
2 y x + 2 y + 2β xy − β y
v = Z0Ih
1 + 2β 2 x + β y − β x
+
2
2
2 2
x + 2 y + 2β xy − β y
(17-41)
FIGURE 17-13
(17-42)
Capacitance to Ground of Substation Equipment
Table 17-12 gives the stray capacitance to ground of various substation equipments. Figure 17-14 shows the circuit breaker diagrams
and minimum capacitance values used in the lightning studies. A
capacitor acts like a short circuit to a surge when uncharged and an
open circuit when it is charged. When two equipments are located
close to each other, the capacitances can be combined. Comparative simulations show that support structures do not impact the
simulation results and can be neglected. However, the capacitance
Induced voltages due to nearby lightning flash.
INSULATION COORDINATION
TA B L E 1 7 - 1 2
Capacitance to Ground Data
CAPACITANCES TO GROUND (PF)
EQUIPMENT
115 KV
400 KV
765 KV
Disconnect switch
100
200
160
Circuit breaker (dead tank, outdoor)
100
150
600
80
120
150
8000
5000
4000
Bus support insulator
CVT
Magnetic PT
500
550
600
CT
250
680
800
3500
2700
5000
Autotransformer (capacitances
depend upon MVA)
FIGURE 17-14
469
to ground of the insulators should be represented. To evaluate the
stresses on the transformer, the conservative approach is to consider that the transformer is open-circuited on the secondary with
no load connected to it.
Lumped capacitance near the substation entrance can reduce the slope
of the steep-fronted incoming wave fronts; this is akin to the phenomena
discussed in Chap. 20 for surge protection of the rotating machinery. The shapes of reflected and transmitted waves will be the same
at lossless discontinuities, and presence of capacitance or inductance
will alter this picture. A lumped shunt capacitance can be modeled by
an equivalent line stub. A capacitive voltage transformer (CVT) has a
capacitance of 2000 to 8000 pF. Suspension insulator has a capacitance
of 80 pF/unit (divide by the number of units in the string). Busbar
surge impedance can be calculated like overhead lines, and conductor
capacitances can be increased by the capacitance of insulators.
17-13 REPRESENTATION OF SLOW FRONT
OVERVOLTAGES (SFOV)
Capacitances of circuit breakers.
As an example, consider the energization and reenergization of
transmission lines, which give slow front overvoltages of transmission lines, discussed in Chap. 7. The study of Fig. 17-15 from Ref. 4
is interesting; it uses the same symbols as in Ref 4. This figure gives a
simplified overvoltage circle, given by values of phase-to-earth overvoltages and phase-to-phase overvoltages for the considered probability of 2 percent. The term “earth” in IEC standards and European
practice is synonomous with “ground” in ANSI/IEEE Standards, USA.
The area R gives the most critical stress. The symbols in this figure are defined as follows. Up is the amplitude of phase-to-phase
overvoltage, U– is the negative switching component in phase-tophase insulation test, U + is the positive switching component in
phase-to-phase insulation test, U e+ , and U e− are the positive and
negative switching component in phase-to-earth insulation test,
U c+ , and U c− are the positive and negative components defining the
center of the circle which describes phase-phase-earth slow-front
overvoltages, and U 0+ is the equivalent phase-to-earth component
used to represent most critical phase-to-phase overvoltage.
F I G U R E 1 7 - 1 5 Curve 1, simplified overvoltage circle, SFOV, phase-to-earth and phase-to-phase. Curve 2, 50 percent flashover characteristics of the
insulation, R, maximum stress.4
470
CHAPTER SEVENTEEN
IEC 71-17 defines the representative voltages between phases as
consisting of two components with equal amplitude and opposite
polarity, U +, and U – and by an equivalent positive voltage:
U 0+ = U + + βU −
(17-43)
This overvoltage is situated on line U + = U – or a = 0.5. The
most critical stress depends upon the insulation characteristics and
inclination b. The factor b depends on the electrode geometry and,
in particular on the gap spacing D between phases versus height H
between phase-to-earth.
H >> D
β →1
H << D
β →0
(17-44)
Between these two extremes, b assumes values between 0 and 1.
The center and radius of the circle in Fig. 17-15 are given by:
U c+ = U c− =
r=
U p − 2U e
2− 2
2U e − U p
(17-45)
2− 2
17-14
RISK OF FAILURE
Overvoltages that stress the system insulation can be expressed by
statistical distribution of magnitude and also time. The breakdown
probability can also be expressed as a function of the same two
quantities. Therefore, overvoltages, which fall within interval dVm
and with times to crest within dt, give risk of failure, written as:
∞ ∞
R=
∫ ∫ P(Vm , t ) f (Vm , t )dVm dt
(17-46)
0 0
It is customary to simplify Eq. (17-46) and express the risk of failure as:
∞
R=
∫ P(Vm ) f (Vm )dVm
(17-47)
0
FIGURE 17-16
Figure 17-16 shows a graphical representation of this equation
and the general method by which the probability of failure can be
assessed. It assumes that P(Vm) and f(Vm) are not correlated. The
equation applies for a single piece of insulation. If number of pieces
are connected together on the same plane and are subjected to the
same overvoltage, it may be assumed that the overall risk is equal
to that of the risk of single insulation multiplied by the number
of insulations in parallel. For a three-phase system, the risk R can
be multiplied by three or, alternatively, an overvoltages probability
density can be established by considering only the highest value of
overvoltages on the three phases. The mathematical model of R in
Eq. (17-47) is based on the following assumptions:
1. Peaks other than the highest in the wave shape of overvoltages are discarded. This gives the calculated risk of failure
lower than the actual risk.
2. The wave shape of the highest peak is assumed to be equal to
the standard switching or lightning impulse test wave shape. This
gives a calculated risk which may be higher than the actual risk.
3. The highest overvoltages peaks are assumed to be of the same
polarity. This gives a risk factor higher than the actual risk.
The overall risk factor as calculated by Eq. (17-46) is normally
conservative. The accuracy of calculation depends upon accuracy
in determination of the overvoltages in the system. A direct implication is that it is possible to coordinate the security levels of the
various parts of the system according to the consequences of a
breakdown. The insulation strength is selected to obtain a probability of failure to the required safety level. Thus, it is necessary to
define acceptable safety factors as follows:
1. Statistical withstand voltage (SWV). It is already defined in
Eq. (17-1) as the peak value of a switching or lightning impulse
test voltage at which insulation exhibits, under specified conditions, a probability of withstand equal to 90 percent. In many
cases, a larger margin between CFO and statistical withstand
voltage is adopted: z = –2 to z = –3.
2. Statistical overvoltage (SOV). The switching or lightning
overvoltages are applied to the measurement as a result of
Computation of risk of insulation failure.
INSULATION COORDINATION
an event of one specific type on the system, the peak value of
which has a probability of being exceeded by 2 percent. For
Gaussian distribution:
E2 = µ0 + 2 . 054σ 0
(17-48)
CIGRE working group18 provides some guidelines of s0. It
can be taken as 2.8 pu for high-speed reclosing without closing
resistors and 1.8 pu with closing resistors. Also see Ref. 3.
3. Statistical safety factor. A simplified procedure to evaluate
risk of failure was given in IEC 71-Insulation Coordination,
1971, now revised as Ref. 4. It designated a safety factor.
For a given type of event, it is a ratio of the appropriate statistical
impulse withstand voltage and statistical overvoltages:
SSF =
SWV
SOV
(17-49)
471
If SSF is increased, R is decreased. Sensitivity analysis and evaluations of the risk failure can be made on this basis. The complete
distribution of overvoltages and the discharge probability is defined
by one point only, that is, SWV and SOV. Figure 17-17a and b shows
frequency distributions of the overvoltages and insulation strengths,
where Vs and Vw denote SWV and SOV, respectively. In Fig. 17-17c, d,
and e, superimposition of the characteristics shows risk factors by
darkened areas: R1, R2, and R3, where R1 > R2 > R3. As SOV is increased,
the risk factor decreases. In IEC,4 the SSF factor is denoted by an
equivalent term as statistical coordination factor Kcs:
K cs =
U cw
U e2
(17-50)
The simplified statistical method for slow-front overvoltages in
Ref. 4 states that correlation between risk of failure and Kcs appears
to be only slightly effected by the parameters of overvoltage distribution. The standard describes two representations of the probability
distribution:
F I G U R E 1 7 - 1 7 Simplified statistical method for calculation and reduction of insulation failure rate. (a) Overvoltage and (b) insulation strength
probability functions. (c), (d ), and (e) Reduction of risk of failure factor by increasing insulation strength.
472
CHAPTER SEVENTEEN
Phase-Peak Method
From each switching operation, the highest peak value of overvoltage on each phase-to-earth, or between
each combination of phases, is included in the voltage probability
distribution. This distribution is then assumed to be equal for each of
the three insulations: phase-to-earth, phase-to-phase, or longitudinal.
(Longitudinal insulation is an insulation configuration between
terminals belonging to the same phase, but which are separated into
two independently energized parts, e.g., open switching device.) For
2 percent value:
Deviation σ e = 0 . 25(U e 2 − 1)
(17-51)
Truncation value U et = 1 . 25U e 2 − 0 . 25
(17-52)
Case-Peak Method From each switching operation, the highest
peak value of overvoltage of all three phase-to-earth or between all
the three phases is included in the voltage probability distribution.
One energization yields one data point, the highest peak, phaseto-earth, and phase-to-phase.
For 2 percent value:
Deviation σ e = 0 . 17(U e 2 − 1)
(17-53)
Truncation value U et = 1 . 13 U e 2 − 0 . 13
(17-54)
where Ue2 is phase-to-earth overvoltage having a 2 percent probability of being exceeded. Figure 17-18 from IEC4 depicts the risk
factors for both of these methods.
Example 17-4 Consider a 765-kV system, phase-to-earth
voltage = 625-kV peak and an SOV of 1255 kV peak = 2.0 pu. Let
SWV = 1300 kV = 2.08 pu. Then from Eq. (17-49), SSF = 1.04, and
from Figure 17-18, R = 10–2. In this case, R is the same from both
the curves in Fig. 17-18, the phase-peak and case-peak methods.
FIGURE 17-18
Example 17-5 Consider a string of 10 insulators at 500 kV.
Desired probability of 10 insulator string is 0.5 percent. A switching surge of 2.5 times the system voltage occurs. Standard mean
deviation is 6 percent for the switching surge. Calculate the required
CFO for the stated conditions.
The probability of 10 insulator gaps is given by:
P10 = 0 . 005 = 1 − (1 − P )10
Therefore:
P = 1 − (1 − 0 . 005)1/10 = 0 . 000501
This corresponds to standard deviation below mean, z = –3.29.
Therefore:
500 × 2 . 5 = CFO(1 − 3 . 29 × 0 . 06)
CFO = 1557 V
17-15
COORDINATION FOR FAST-FRONT SURGES
17-15-1
Deterministic Method
For fast-front lightning overvoltages, a deterministic coordination
factor, Kcd, of 1 is applied.4 This is because for the lightning overvoltages, probability effects are included. For fast-front switching
overvoltages, the same relations apply as for slow-front switching
overvoltages.
Figure 17-19 from this standard shows the factor Kcd as a function of ratio U ps /U e 2 . Here, U ps is the switching surge protective
level of the surge arrester. Curve (a) is applicable to phase-to-earth
overvoltages and also applies to longitudinal overvoltages. Curve (b)
is applicable to phase-to-phase overvoltages.
Risk of failure, external insulation SFOV, as a function of statistical coordination factor.4
INSULATION COORDINATION
FIGURE 17-19
17-15-2
Evaluation of deterministic coordination factor.4
Statistical Method
The Brown’s Method
The statistical method in Ref. 4 for fast-front overvoltages considers
recommended probability distributions representative of lightning
overvoltages (Chap. 5).
17-16 SWITCHING SURGE FLASHOVER RATE
(SSFOR)
For general design, it is recommended that the design value
of SSFOR is set at 0.5 flashover per 100 km-yr. Either BrownWhitehead or IEC equations can be employed for the calculations
of SSFOR.4,22 From Eq. (17-24), the incremental probability of a
flashover can be expressed as:
dP = f s (V ) f st (V )dV = pf s (V )dV
(17-55)
where function fst(V) denotes strength, and fs (V) stress, and fs(V) = p.
The strength/stress ratio and SOV profile along the line are important factors. Then:
1
SSFOR =
2
Em
∫ pfs (V )dV
(17-56)
1
∫ [1 − qn] fs (V )dV
2
If the strength is represented by a singlevalue function, CFOn, which denotes the strength of n towers
given by:
σf
CFOn = CFO 1 − z f
CFO
(17-57)
Pn = 1 − (1 − P )n = 1 − q n
This is a function of:
■
SSF
■
change of SOV along the line
■
The type of probability distribution
■
The number of towers n
(17-58)
CFOn − CFO
σf
(17-59)
Em
SSFOR =
1
∫ f (V )dV
2 CFO s
(17-60)
n
Equation (17-60) can be estimated for any SOV distribution. For
Gaussian distribution:
CFO − µ
1
n
0
SSFOR = 1 − F
2
σ0
z=
V − µ0
σ0
(17-61)
Here µ0 replaces V50 in the definition of z. The CFOn of n towers
is defined at probability of 0.5:
P = 1 − n 0. 5
(17-62)
Example 17-6 Considering a probability = 0.023 percent,
percentage deviation = 5 percent, CFO = 1000 V, Gaussian distribution, σ 0 /E2 = 0 . 12 , no arrester (from Ref. 3), and σ f /CFO = 5
percent, find SSFOR.
From Table 17-11, z = –2.0. From Eq. (17-59)
− 2. 0 =
where:
zf =
where we may call zf as the reduced variate, then SSFOR is:
0 . 5 = 1 − (1 − P )n
E
Factor 1/2 means that negative SOV distribution is neglected.
The integration in Eq. (17-56) is carried out from system lineto-neutral voltage, E, and maximum switching overvoltage, Em. By
definition, E =1.0 pu. For n-towers:
SSFOR =
473
CFOn − CFO (CFOn /CFO) − 1
=
0 . 05
σ
CFOn /CFO = 0 . 865
For Gaussian distribution, E2 = 900 kV and given that s0/E2 = 0.12,
from Eq. (17-48), µ0 = 678 kV. Then SSFOR from Eq. (17-61) is:
865 − 678 1
0 . 014
1
1 − F
= [1 − F(1 . 79)] =
1 00
2
104 2
F(Z) is obtained from the Gaussian distribution tables.The SFFOR will
vary with the type of distribution, that is, skew distribution (App. F).
474
CHAPTER SEVENTEEN
17-17
OPEN BREAKER POSITION
A breaker when opened for a long time will have its associated
disconnects also open. A lightning flash is composed of one or
more subsequent strokes, and a stroke may occur while the breaker
is open and unprotected by the surge arresters in the substation.
A remedy will be to use a surge arrester at the line side of the
breaker.
17-18
MONTE CARLO METHOD
The parameters impacting the lightning performance are subject to
large variations. The important ones are:
■
Current magnitudes of strokes to lines
■
Weather conditions and insulator swings
■
Tower footing resistance
■
Lightning strike locations
■
Shielding failures and backflashovers
d=
Values of power frequency voltages at the time of lightning
stroke
Soil resistivity
Because lightning parameters vary, the effect of lightning must be
evaluated on statistical basis. The randomly selected parameters for
each lightning incident should determine the outcome—whether a
flashover will occur. The analysis must be repeated for the number
of variants to obtain a long-term flashover rate. The numbers of
incidents normally correspond to the total number of strokes hitting the line over the period of study, 15 to 20 years.
When many statistical distributions have to be combined,
the Monte Carlo computer program, based on random selection
of relevant parameters including weathering effects, can be used.
Anderson was the first to apply this technique.19,20 Anderson and
Barthold21 refined the approach by a program, Metifor, which creates a digital model of the climate.
17-19
SIMPLIFIED APPROACH
According to IEC4, the voltage at a point in a substation can be
calculated from the following equation:
Et = Ed + 2
Sτ
n
FIGURE 17-20
S=
Kc
d + Sl
(17-64)
where Kc is the corona constant given in Ref. 15. The suggested values in kilovolts-kilometers per microsecond are 700, 1000, 1700,
and 2000 for single conductor, two conductor bundle, 3 or 4 conductor bundle, and 6 or 8 conductor bundle, respectively. Sl is the
span length in meters, and d is calculated from the equation:
■
■
where Et is the voltage at a certain equipment, Ed is the discharge
voltage of the surge arrester, which is the protection level of the
surge arrester, S is the steepness of the incoming surge, n is the
number of lines, and τ is the transit time between the arrester and
the protected equipment, considering the separation distance and
the lead length. The discharge voltage of the arrester is not a constant parameter and depends upon the current that it conducts.
The steepness of the incoming surge is given by:
(17-63)
1
n(BFR )(MTBF)
(17-65)
A substation configuration is shown in Fig. 17-20.3 n is the
number of lines terminating at the substation, for calculation of
the voltages at transformer and transformer bus, and for all other
equipment n is equal to 1, regardless of the number of lines. BFR is
the backflashover rate. It can be estimated using IEEE and CIGRE
methods (Chap. 5). BFR varies significantly with the system voltage; the BFR for 345- and 500-kV lines is 0.3 to 0.6 flashovers per
100 km-year, and for 138- to 230-kV lines, it ranges from 0.6 to 2.
The incoming surge to the station is caused by a backflash or
shielding failure and is selected for the desired reliability of the station. Typical values of MTBF range from about 50 to 200 years
for air-insulated substations and 200 to 800 years for gas-insulated
substations.
As an example, consider MTBF = 100 years, BFR = 2.0 flashovers per 100 years, then distance to flashover d = 0.5 km. VB, VJ,
and VT are the surge voltages at the breaker, at arrester connections,
and at the transformer terminals, respectively. Let the lowercase
subscripts Vb, Vj, Vt, denote the total voltages to ground, including
superimposition of power frequency voltages. TA, TT, and TB are the
travel times. Two examples in Ref. 3 compare the results of simplified calculations with actual simulations.
Example 17-7 Consider a 345-kV system, protected with a gapless surge arrester of 276-kV rated voltage. The maximum discharge voltage according to vendor’s data for 40-kA discharge
current is 808 kV. Span length = 350 m, BFR = 0.8/100 km-yr,
Simplified representation of a substation with multiple lines for calculations of insulation coordination according to IEEE method.3
INSULATION COORDINATION
MTBF = 400 years, Kc for single conductor = 675 kV-km/µs, n = 3,
and τ = 0.1 µs. Then, from Eq. (17-65)
d=
100
= 0 . 31 km
400 × 0 . 8
Steepness of incoming surge is:
S=
675
= 1022 kV/µ s
0 . 31 + 0 . 35
Therefore from Eq. (17-63)
1022
Et = 808 + 2
(0 . 1) = 876 . 1 kV
3
Larger the number of lines connected, smaller is the Et. We can
select a BIL equal to 1.2 times Et, for example, 1051 kV. Standard
BIL is 1050 kV, which is the minimum acceptable value.
17-20 SUMMARY OF STEPS IN
INSULATION COORDINATION
Primarily, the maximum voltages occurring in the system, overhead
lines, substations, or industrial systems need to be ascertained. This
is rather a complex situation due to many parameters and statistical
nature of the problem. Simplified methods are of academic interest and simulations using EMTP are popular, the results depending
upon the accuracy of the models. The steps in insulation coordination can be summarized as:
1. The surge arrester location and selection of appropriate
ratings is important (Chap. 20). To design a system without
surge arresters will be prohibitively expensive (Example 6-8 of
an EMTP simulation).
2. The incoming surge steepness and magnitude is selected.
The magnitude is approximately 1.25 times the CFO. The wavefront is calculated. Select station clearances considering weather
conditions, ground flash density, and location of the substation,
altitude above sea level and pollution level. Select preliminary
BIL and BSL levels and calculate CFO. The maximum steepness
of surge occurs for a backflashover. Standards provide guidelines
for selection of BIL and BSL for various equipments, that is,
insulators, transformers, circuit breakers, CTs, PTs, and the like.
475
3. During impulse testing of a restorable insulation, a flashover occurs on the tail of test wave, while the insulation has
successfully withstood the peak. Explain this phenomenon
with respect to breakdown mechanism in insulations.
4. As the system voltage rises, the insulation coordination with
respect to switching surges becomes important, shadowing the
insulation coordination with respect to lightning surges. Explain.
5. What is the loss angle of a dielectric? Explain its significance. Will it increase or decrease as the insulation ages?
6. The breakdown voltage for insulation will be higher for
(a) positive polarity tests, (b) negative polarity tests, (c) polarity
does not make a difference. Provide explanations for the alternative selected.
7. Why the breakdown voltage decreases from high vacuum to
mild vacuum and then again increases, Pachen’s curve?
8. Distinguish between field emission and secondary emission
in a breakdown process.
9. Calculate the leakage distance of an insulator string according to IEEE and IEC methods for a service voltage of 500 kV,
medium polluted atmosphere.
10 An insulation under test gave a flashover voltage probability of 5 percent, 150 kV. Probability was 60 percent as the voltage was increased to 180 kV. Estimate CFO and corresponding
standard deviation.
11. In Problem 10, five insulators are connected in parallel.
What is the overall probability for 150 kV?
12. Consider two dissimilar insulations:
a. Breakdown probability =10 percent and time to
flashover = 100 to 120 µs
b. Breakdown probability = 15 percent and time to
flashover = 110 to 130 µs
Estimate the overall probability of the two systems in parallel.
13. Determine the clearances and insulator length for a
500-kV line, where switching surge = 2 pu, maximum voltage =
550 kV (pu), variation = 5 percent, wet conditions, decrease
CFO by 5 percent, tower width = 2 m, and tower height = 30 m.
3. Consider that some lines may be out of service. The steepness
of the wavefront increases as the number of lines is reduced.
14. In Problem 13, calculate the probability of at least one
flashover for switching surge of 2.0 and 2.5 pu.
4. Consider appropriate safety factors on BIL, BSL, and CFO.
These are interrelated as shown in above equations. Depending
upon MTBF, the severity of incoming surge will change.
15. Calculate the steepness of an incoming surge for a 500-KV
system, where MTBF = 400 years, number of lines = 3, assume
appropriate BFR, Sl, and Kc for a single-conductor transmission
line.
5. A capacitance at the entrance of a station, for example, a
CVT, will reduce the steepness of the wavefront.
6. Simulate the system and calculate maximum voltages at the
points of interest, that is, circuit breakers, transformers, surge
arresters. Revisit the selected BIL and BSL, and apply appropriate safety factors.
16. In Figure 17-1c why does the insulation resistance dips
initially when the insulation is drying up?
17. The lightning performance can be improved by counterpoises and lowering tower footing resistance close to a
substation. Explain why. What is the surge impedance of a
counterpoise?
1. What is the difference between thermosetting thermoplastic
and epoxy resins for use as insulating materials?
18. Calculate the strike distance and insulator string length for a
400-kV tower for design of SSFOR = 1.0/100. Altitude = 1.5 km,
E2 = 690, σ 0 /E2 = 0.10, σ f /CFO = 0.05, n = 200, tower
width = 1.2 m, and conductor height = 13 m.
2. Give five reasons why standards specify different test BIL
and BSL levels for the same system voltage.
19. Estimate the BIL of a transformer and switchgear in a 230-kV
substation, given the following data: Line insulation = 15 discs
PROBLEMS
476
CHAPTER SEVENTEEN
of standard insulators, conductor diameter = 2.54 cm,
average height = 13 m, protected zone = 1.6 km, surge
impedance = 400 Ω, transformer capacitance = 1000 pF,
earthing factor = 1.35, temporary overvoltage = 1.10 pu for 1 s,
distance of surge arrester to transformer = 10 m, distance of
surge arrester to line entrance = 60 m, two lines leading in
different directions are connected to the substation. Choose
appropriate surge arrester rating. (Peruse Chap. 20, and then
attempt this problem.)
REFERENCES
15. A. R. Hileman, Insulation Coordination of Power Systems, Taylor
and Francis Group, Boca Raton, FL, 1999.
16. A. J. Eriksson, M. F. Stringefellow, and D. V. Meal, “Lightning
Induced Overvoltages on Overhead Distribution Lines,” IEEE
Trans., PAS 101, pp. 960–968, 1982.
17. P. Chowdhuri, Electromagnetic Transients in Power Systems,
John Wiley, New York, 1996.
18. CIGRE Working Group, “Switching Overvoltages in EHV and
UHV Systems with Special Reference to Closing and Reclosing
Transmission Lines,” Electra, pp. 70-122, Oct. 1973.
1. K. Feser and A. Pigini, “Influence of Atmospheric Conditions
on the Dielectric Strength of External Insulation, Electra,
no. 112, p. 83, 1987.
19. J. G. Anderson, “Monte Carlo Computer Calculation of Transmission Line Lightning Performance,” AIEEE Trans, Power
Apparatus and Systems, no. 80, pp. 414–419, 1961.
2. CIGRE Technical Bulletin 63, Guide to Procedures for Estimating the Lightning Performance of Transmission Lines, 1991.
20. M. A. Sargent, “Monte Carlo Simulation of Lightning Performance of Overhead Shielding Networks of High Voltage Stations,” IEEE Trans. PAS, Part III, no. 91, pp. 1651–1656, 1972.
3. IEEE Standard 1313.2, IEEE Guide for Application of Insulation Coordination, 1999.
4. IEC 60071-2, Insulation Coordination-Application Guide, 1996.
5. NEMA MG-1, Motors and Generators, Large Machines, Parts 20
and 21, 1987.
6. C. M. Cooke and A. H. Cookson, “The Nature and Practice of
Gases and Electrical Insulators,” IEEE Trans. EI, pp. 239–248,
1978.
7. IEC 60071-1, Insulation Coordination, Part 1: Terms, Definitions, Principles and Rules, 1993.
8. IEEE PC62.82.1/D2, Draft Standard for Insulation
Coordination—Definitions, Principles, and Rules, 2008.
9. ANSI/IEEE C37.122.1 IEEE Guide for Gas Insulated Substations, 1993(R2002).
10. G. D. Breuer, R. H. Hopkinson, I. B. Johnson, and A. J. Shultz,
“Arrester Protection of High Voltage Stations Against Lightning,”
IEEE Trans. Power Apparatus and Systems, vol. 79, pp. 414–423,
1960.
11. IEEE Standard C62.22, Guide for Application of Metal Oxide
Surge Arresters for Alternating Current Systems, 1997.
12. G. W. Alexander and H. R. Armstrong, “ Electrical Design of
345 kV Double Circuit Transmission Line, Including the Influence
of Contamination,” IEEE Trans. PAS, no. 85, pp. 656–665, 1966.
13. IEEE P1427, Draft 13, Draft Guide for Recommended Electrical Clearances and Insulation Levels in Air Insulated Electrical
Power Substations, 2004.
14. NESC, ANSI C-2, National Electric Safety Code, 1993.
(Published by IEEE).
21. J. G. Anderson and L. O. Barthold, “Metifor, a Statistical Method
of Insulation Coordination Design of EHV Lines,” IEEE Trans.
Power Apparatus and Systems, no. 83, pp. 271–280, 1964.
22. G. W. Brown, “Designing EHV Lines to A Given Outage
Rate—Simplified Techniques,” IEEE Trans. PAS, pp. 379–383,
1978.
FURTHER READING
EHV Transmission Line Reference Book, Edison Electric Institute,
New York, 1968.
G. Gallet, G. LeRoy, R. Lacey, and I. Kromel, “General Expressions
for Positive Switching Impulse Strength up to Extra Long Air Gaps,”
IEEE Trans. PAS, pp. 1989–1993, Nov./Dec. 1975.
T. Harada, Y. Aihara, and Y. Aoshima, “Influence of Humidity on
Lightning and Switching Impulse Flashover Voltages,” IEEE Trans.,
PAS-90, no. 4, pp. 1433–1442, 1971.
IEEE Standard 1243, IEEE Guide for Improving the Performance of
Transmission Lines, 1997.
IEEE Standard. 1313.1, IEEE Standard for Insulation Coordination—
Definitions, Principles, and Rules, 1996.
A. M. Mousa and R. J. Wehling, “A Survey of Industry Practices
Regarding Shielding of Substations Against Direct Lightning
Strokes,” Paper 92, WM 224-6, PWRD, 1992.
Transmission Line Reference Book, 345 kV and Above, 1st ed., EPRI,
Palo Alto, CA, 1975.
Transmission Line Reference Book, 345 kV and Above, 2d ed., EPRI,
Palo Alto, CA, 1982.
M. A. Uman, Lightning, McGraw-Hill, New York, 1969.
CHAPTER 18
GAS-INSULATED
SUBSTATIONS—VERY
FAST TRANSIENTS
GIS utilize the superior insulating properties of SF6 gas, and the assembly consists of grounded metal equipment modules, that is, circuit
breakers, current and voltage transformers, disconnects and grounding
switches, interconnecting bus, and connections to the electrical power
system. The modules are assembled together using bolted flanges with
an O-ring seal system for the enclosure and sliding plug-in contact for
the conductor. Three-bus enclosure or single-bus enclosure configuration is used, depending on the application voltage and other considerations. Figure 18-1 shows typical assembly of GIS.
The assembly can be located in enclosed buildings, and the space
requirement may be only 3 percent of a conventional outdoor airinsulated substation. Thus, the aesthetics, community considerations,
and location in crowded areas are some of the obvious advantages;
where the real estate is at a premium cost, the onsite cost of GIS may
come out to be comparative with air insulated substation.
18-1
CATEGORIZATION OF VFT
In this chapter, we will not be so much concerned about assembly
and mechanical arrangements, but the very fast transients (VTF)
that occur in GIS. These can be divided into two categories:
■
Internal transients. These produce overvoltages between the
inner conductor and the encapsulation and traveling waves
inside the enclosure. These create insulation stresses in GIS.
■
External transients. These are due to traveling waves and
radiation outside the GIS. These include transient enclosure
voltage (TEV), transient electromagnetic fields (TEMF), and
overvoltages on overhead lines and equipment. These can cause
stress on secondary and adjacent high-voltage equipment.
Internal transients are generated in GIS during normal operation
by switching of disconnects and breakers and by dielectric breakdown. The collapse of voltage across the contacts of a switching
device or to ground in case of a dielectric breakdown occurs in 3 to
5 ns. This is rapid enough to excite resonances within GIS at a frequency up to about 100 MHz. Traveling waves of very short rise time
occur which propagate in either direction from the breakdown location.
The propagation throughout the substation can be analyzed by representing GIS sections as low-loss distributed parameter transmission line, each section having a certain characteristic impedance
and transit time. Akin to transmission line traveling wave theory
(Chap. 4), the traveling waves are reflected and refracted at every
point where these meet an impedance discontinuity. The generated
transients depend on the GIS configuration, and superimposition of
reflected and refracted waves at discontinuities like “T” junctions,
bushings, or breakers. Thus, transient voltages can increase above
the original values and very high-frequency oscillations can occur.
18-2
DISCONNECTOR-INDUCED TRANSIENTS
Isolators (also called disconnects/disconnectors) are installed in
several locations in a GIS and are referred to as busbar isolators
or line isolators. Two situations can be examined during switching
action of an isolator.
1. Two networks are to be isolated, for example, on the right
and left of the GIS; each network has its distributed inductance
and capacitance. Under unfavorable conditions, there can be
a phase shift between the voltage of the two networks, and a
voltage of twice the system voltage can arise across the poles of
the isolator (Fig. 18-2).
2. The second more frequent use is to connect or disconnect
unloaded portions of the GIS. The second network on the right
in Fig. 18-2, system 2, is absent and the isolator disconnects a
part of GIS or overhead line from the source.
Disconnector operation typically involves slow-moving contacts
that result in numerous discharges during operation. A restrike
occurs every time the voltage between contacts exceeds the dielectric strength of the gaseous medium. Each restrike generates a
spark, which equalizes the potential between the contacts. Following spark extinction, the source and load-side voltages again deviate and another spark occurs when the voltage across the contacts
reaches new dielectric strength. Now consider the opening of disconnect with flashover. Assume that the load side of the interrupter
477
478
CHAPTER EIGHTEEN
FIGURE 18-1
FIGURE 18-2
Cross section through a section of GIS assembly.
A disconnector in GIS, interconnecting two systems, possible switching in phase opposition.
GAS-INSULATED SUBSTATIONS—VERY FAST TRANSIENTS
has trapped charge V1 and surge impedance Z1, and the source side
has a trapped charge Vs and surge impedance Zs. At the time of
breakdown (sparking occurs as soon as the voltage between the
source and load exceeds the dielectric strength across the contacts),
the voltage on the load side goes from V1 to:
V1 + (Vs − V1 )
Z1
Z1 + Z s
(18-1)
And the voltage on the source side goes from Vs to:
Vs − (Vs − V1 )
Zs
Z1 + Z s
(18-2)
After restrike, a high-frequency current will flow through the
spark and equalize the capacitive load voltage to the source voltage. The potential difference across the contacts will fall and the
spark will extinguish. A subsequent restrike occurs when the
voltage between the contacts reaches the new dielectric strength
level, determined by the speed of the parting of contacts and the
disconnect characteristics.
In the simplest case, consider Zs = Z1, Vs = 1 pu, and V1 = 0, that is,
a disconnector connecting a previously grounded load and the first
prestrike occurring at peak of the ac source voltage. Vs and V1 go to
0.5 pu in about 3 to 5 ns. For a GIS operating at 420 kV, this implies
a change of 210 kV in, say, 4 ns or rate of change of approximately
50 MV/µs. In terms of direction of propagation, the voltage changes
by 210 kV over a distance of 130 cm or a change of 1.6 kV/cm.
The transient magnitude of the voltage on one side of disconnect
can exceed if the surge impedances differ on the two sides of the
disconnector, that is, if the disconnector is near a “T” or a capacitive
voltage transformer is located close to the disconnector.
Figure 18-3 illustrates these phenomena. If we assume that the
breakdown voltage of the gap increases with increasing separation
of the contacts as they part, then at the start of the contact separation, voltages on V1 and V2 are equal. As the voltage V2 – V1 across
the gap changes and exceeds the dielectric strength of the gap, a
breakdown occurs and first restrike occurs. Both poles of the disconnecting switch are electrically connected by the conducting
spark, and V2 is rapidly changed to V1. At this instant, the transient current through the gap interrupts. As the supply-side voltage
changes, the second restrike occurs with an increased breakdown
voltage, VB, due to larger gap. The voltage V2 follows voltage V1 in
steps until at the end of the switching process, the gap can no longer
be broken down due to increased spacing.
FIGURE 18-3
479
The discharge during each individual restrike begins as the voltage across the contacts collapses, and in SF6, it occurs in 10–2 µs and
is directly related to the formation of spark channel. With a typical
voltage decrease of 10 kV in 1 ns, it gives rise to a traveling wave,
which propagates away from the gap into the installation. After a
certain travel time, the wave reaches the open end of the GIS, is
reflected back, and crosses the gap, which may be still bridged by
the arc. At a further discontinuity, for example, connection to an
OH line, it is split into reflected and transmitted components. The
reflected wave travels a second time toward the open end of GIS and
is again reflected. Thus, the discharge transient shows a double periodicity of the traveling wave. If the circuit has T-connections, then
the discharge transient will have components of different frequency.
Very different magnitudes can occur, depending on the installation.
Example 18-1 An open-ended GIS has Zg = 75 Ω, which is to be
disconnected from an OH line of Z1 = 320 Ω. A restrike occurs at
Vb = 500 kV, at a contact gap of 3 cm. Find the initial amplitude of
the voltage and current entering into GIS and how it ends.
The initial amplitude Ving entering GIS can be easily calculated
as no reflection is present yet, and the breakdown voltage Vb distributes itself corresponding to surge impedances of the lines. The
voltage wave entering the GIS is:
Vb Z g
Ving =
Z g + Z1 + R s
(18-3)
where Rs is the spark resistance and is neglected, initially. This gives
95 kV. Thus, the voltage wave into the transmission line is 405 kV
and into GIS 95 kV. The initial value of current wave is given by:
I in =
Ving
Zg
= 1 . 26 kA
(18-4)
The spark resistance, which was neglected earlier, can be found
from Toepler equation:
Rs =
KTl
t
∫ idt
(18-5)
0
where Rs is spark resistance in ohms, KT is Toepler coefficient =
(0.4 – 0.8)10–4 Vs/cm for SF6 at 1 to 20 bar, and l is spark length in
cm. This shows that the resistance falls below 10 Ω in 20 ns.
Voltage on the open-ended GIS side of the disconnector without loss of charge.
480
CHAPTER EIGHTEEN
The power carried by the wave into the transmission line is:
P=
V 2inl
Zl
(18-6)
where Vinl voltage entering transmission line =405 kV.
This gives a power of 512 MW into the line. In comparison, the
power loss in the spark resistance and GIS, for practical purposes,
is so small that it can be ignored. Thus, the transient discharge
oscillations in GIS are mainly damped by wave transmitted into the
transmission line; in other words, in a loss-free GIS open at both
ends, if a surge voltage Vo enters GIS, the discharge oscillation will
continue indefinitely. Considering reflection now, the reflection factor is (Chap. 4):
ρ=
Z1 − Z g
Z1 + Z g
(18-7)
The transmitted wave of (1+ P )Vo runs into the line. At the end
of reflection process, the voltage on line 2 is reduced by reflection
constant and the energy stored in the wave in GIS goes down by r.2
Though the waves may be more complex, the fundamental concept
that the wave energy is removed by transmitted waves holds. In
isolator models, the arc extinction takes place when the current
has fallen to 1 to 5 A. Though this current to be interrupted is
small, high di/dt values occur due to high frequency. As the current
reduces, it can be interrupted at a high-frequency zero crossing.
The total duration of transients has been estimated from optical observations of the spark, with the use of so-called streak photographs on a high-speed moving film. The duration of luminous
period is determined by smearing of the spark picture. These pictures
can also show sequential restrike with time interval between them.
The behavior on a closing operation is similar and the load-side
voltage will follow the supply-side voltages until the contacts are
made.
18-3
BREAKDOWN IN GIS—FREE PARTICLES
If a breakdown occurs within GIS, the transient magnitude is generally much greater than for a switching operation. The voltage goes
from initial value of V (1 per unit) to zero, again in 3 to 5 ns. Though
the in-service breakdowns are rare, and when these occur, they are
induced by switching-related transient or by areas of high-voltage
stress within GIS. The electrical field in a GIS is approximately uniform due to circular enclosures. During manufacture, extreme care
is taken to eliminate any irregularities and free particles, which can
be a potential problem in breakdown in SF6. This becomes important as the operating voltage is raised. Extreme care is required in
handling and field assembly to eliminate free conducting particles.
Most dielectric failures will generate a transient larger at least by
a factor of two than the switching transient. During testing, the
voltage is raised to 2.5 times the normal operating voltage, and a
breakdown under such a condition will generate transients three to
four times greater.
The VHF transients thus generated due to breakdown or across
switch contacts propagate away from their source, reflecting and
refracting at impedance mismatches. This results in a complex pattern
of traveling waves within the substation that may superimpose to
generate greater voltages in some locations as compared to the others. The switching overvoltages to which a substation is subjected
is a function of station configuration and the characteristics of the
switching devices.
hours to days, as a result of leakage through spacers. Large trapped
charges are undesirable because they will not only result in overvoltages, but may also levitate particles. These particles may be scattered
across the insulating surfaces, reducing their breakdown strength. A
trapped charge of 1pu implies that the first breakdown on closing the
disconnector will occur at 2 pu across the switch contacts and may
lead to conductor-to-ground overvoltage up to 2.5 pu.
The disconnector operation with +1 pu voltage on one side and
–1 pu voltage on the other side is the worst-case scenario. In theory, this
can give rise to peak waveform amplitude of 3 pu. Numerous studies
indicate theoretical worst-case transient-induced overvoltages in the
range of 2.8 pu relative to power frequency peak voltage. Typically, a
magnitude little over 2 pu is more practical. The probability density
of trapped charges is discussed in (Ref. 1), which shows that only
5.9 percent trapped charges in pu, normalized by the peak voltage
of the applied ac voltage, are of 1.0 per unit. 65.3 percent are below
0.5 per unit. The probability density of trapped charge left on a capacitive load during opening of a disconnector with arcing time of 0.6 s
and 0, 15, 30 percent and contact breakdown asymmetry as a result
of 1000 Monte Carlo simulations is shown in (Ref. 2). This shows that
the trapped charge left on the load side is less than 0.3 pu.
18-3-2 Speed of Operation
Overvoltages are dependent on the speed of the operation of the
disconnector. The voltage drop at the disconnector before striking
and the trapped charge that remains on the load side are of concern. For a slow-speed interrupter, the maximum trapped charge
reaches 0.5 pu and a voltage collapse of 1.5 pu. For these cases, the
overvoltages may reach up to 2 pu. The trapped charge increases
with a high-speed interrupter, and can be a maximum of 1 pu.
The highest overvoltages reach 2.5 pu. The frequencies depend on
the length of the GIS section and are in the range of 1 to 50 MHz.
Larger disconnector-induced transients occur during opening as a
result of the statistical variation in nature of disconnector operation,
documented in (Ref. 3). In case of a high-speed disconnector, the
probability of an occurrence of prestrike by interpolar breakdown
voltage of 1.8 to 2.0 per unit is less than 1 percent.1
During closing, a reversal of the previous description takes place.
The first strike invariably occurs at the peak of the power frequency
voltage. When the GIS is fed through a transformer, oscillations of
the whole system can occur. The high-frequency transients may
couple through PTs and CTs, interfere with the secondary equipment, and cause electromagnetic coupling problems.
18-3-3 Operating Voltage of GIS
The magnitude of switching-induced transients is proportional
to the operating voltage, while the dimensioning of GIS say up to
550 kV, is proportional to the basic impulse levels impulse (BIL).
Thus, the severity of the switching-induced transients increases
with the increasing voltage class. Consider a BIL of 1550 kV for
550-kV GIS and a BIL of 1050 kV for 230-kV GIS. The ratio of the
BIL with respect to operating voltage is 3.45 for 550-kV GIS and
5.6 for 230-kV GIS.
In the past, 25 percent failures in 550-kV GIS occurred due
to switching-induced transients, though the transients should not
have produced a voltage of 3.45 pu, IEEE Std. C37.122.1.4 (This
standard contains a bibliography of 1518 technical papers and
references on GIS.) When a defect is present in the conductor inside
GIS, the withstand voltage can decrease by a factor of 2 or more,
and a decrease in the surge waveform rise time is from 100 to 10 µs.4
This points to the necessity of appropriate field testing.
18-3-1 Trapped Charges
When a disconnector operates on a floating section of switchgear, a
trapped charge may be left on the floating section due to capacitance.
Left to themselves, these trapped charges will decay very slowly, from
18-3-4
Maximum VFT Stresses
The maximum VFT stresses under normal operating conditions
occur due to disconnector operation. The maximum voltage is a
GAS-INSULATED SUBSTATIONS—VERY FAST TRANSIENTS
function of the trapped charge on the load side, the geometry of GIS,
and the disconnect voltage at the time of breakdown. The following
conclusions can be drawn based on the published literature:
■
The trapped charge is mainly dependent on disconnector
characteristics. The faster the switch, the greater is the mean
value of the voltage.
■
The capacitive-graded GIS-air or GIS-oil bushings impact
the rise time of the transient, which is further discussed in
Sec. 18-8-2.
■
For slow switches, the probability of restrikes and prestrikes in the voltage range of 1.8 to 2 per unit is small, though
it cannot always be ignored.
■
The breakdown voltage of the disconnector gap may vary for
positive and negative values, which effects the trapped charge
distribution.
18-4
Internally generated transients propagate throughout GIS to reach
external connections and bushings, where they cause transient
enclosure voltages (TEV) and traveling waves that propagate along
overhead transmission lines.
18-4-1
Transient Enclosure Voltages
Transient enclosure voltages are also called transient ground potential
rises (TGPR). These are short-duration high-voltage transients that
appear on the enclosure of GIS because internal transients couple
to the enclosure at its discontinuities. Figure 18-4 illustrates this.
FIGURE 18-4
The propagation of an internally generated transient to an air termination and its refraction to outside transmission line/cable is the
dominant mechanism for damping out the switching transient. At
the air termination, we can decipher three transmission lines as
follows:
1. The GIS enclosure is at ground for the GIS conductor, but
it acts as a conductor with respect to the station ground and
ground mat. At higher frequencies, GIS enclosure, generally
about 4 ft from the ground, is really two distinct conducting surfaces, interior and exterior.5 Thus, part of the energy couples to
the transmission line formed by outside of the GIS enclosure
relative to earth and station ground.
2. The GIS conductor to GIS enclosure.
3. Overhead line to ground.
The reflection coefficient at the transition:
ρtr =
EXTERNAL TRANSIENTS
481
( Zenc + Zoh )Z gis
Zenc + Zoh + Z gis
(18-8)
Then, refraction coefficient is 1 + rtr.
The peak transient ground wave into outside enclosure is:
(1+ ρtr )
−Zenc
Zenc + Zoh
(18-9)
This simplifies to:
Zenc
Vgr = − 2Vi
Zenc + Zoh + Z gis
Voltage transmission on an insulation breakdown within GIS.
(18-10)
482
CHAPTER EIGHTEEN
where Vi is the voltage within GIS incident on termination; Zgis is
the GIS bus duct impedance, typically 60 Ω; Zoh is the overhead line
surge impedance, typically 300 to 400 Ω; and Zenc is the impedance
of the GIS enclosure relative to station ground, typically 150 Ω.
The negative sign in Eq. (18-10) implies reversal of the waveform
with respect to the internal transient. This assumes perfect junction
between the lines. The effect of vertical bushings is ignored. The real
SF6 systems are not so simple as a configuration of a central conductor, enclosure, and ground plane, yet the magnitude of the initial
step transient that is coupled to the enclosure-to-ground plane can
be estimated with reasonable accuracy from Eq. (18-10). The surge
impedance Zenc can be calculated from the following equation:
Zenc ≈ 60 cos h −1(h /r )
(18-11)
where r is the radius of the enclosure and h is the height. For a
500-kV GIS, consider r of the order of 25 to 30 cm, and height 1.5 m.
This gives a surge impedance of approximately 150 Ω.
Although the initial TGPR response may be like a step function,
reflections from external ground leads and internal discontinuities
will cause overall response to be oscillatory. These oscillations are
largely dependent on the physical length of the bus and are in the
range of 5 to 50 MHz.
18-4-2 Effect of the Ground Straps
In Fig. 18-4, one way to reduce TGPR is to reduce Zenc and add
ground straps from the enclosure to the ground plane. The ground
straps have significant effect on the waveshape that propagates away
from the terminations, though most ground straps may be too long
and too inductive for effective grounding of TGPR. The ground lead
can be considered as a vertical transmission line with surge impedance that varies with the height. The attachment of the ground strap
to the enclosure constitutes a T-connection. When the transient
reaches a ground strap, a division takes place, which reduces the
magnitude of the transmitted wave. This can be expressed by the
coupling coefficient, as follows:
k=
2 Z strap
2 Z strap + Zenc
(18-12)
where Zstrap is the surge impedance of the ground strap. This is normally > Zenc, the attenuation is normally small, k = 0.8. Practically,
the surge impedance of the ground strap varies along its length, but
may be considered constant for simplification.
Now consider the effect of the grounding grid. The wave traveling down the ground strap meets the low resistance of the grounding grid. At this point, the wave is reflected back and reduced along
the grounding lead to the enclosure, where it will tend to cancel the
original waveform, the phenomenon similar to the one illustrated
in Example 5-3, in connection with a lattice diagram of a struck
tower. The traveling wave from the air/SF6 bushing will be altered
by the reflected ground wave after a time interval equal to twice the
transit time along the ground strap. Depending on this time, the
incident wave may be reduced in magnitude or attain its peak before
the reflected wave from the ground reduces its magnitude. The end
result may be a peaked wave, as shown in Fig. 18-5.
The maximum TGPR will be approximately 60 percent of the
voltage incident on GIS-to-air termination and of opposite polarity. The
maximum transient likely to be incident on the air termination is 1.3 pu
which will generate 0.8 pu on the enclosure at the base of the termination. This voltage will last only for nanoseconds. TGPR due to dielectric
breakdown of GIS, especially during testing, is of much larger magnitude than that caused by switching. Note the following points:
■
The ground connection has no effect on the transient generated by the breakdown, the transient magnitude of GIS-to-air
FIGURE 18-5
TGPR with and without ground straps.
termination, or transient ground rise. It will have only an effect
when the transient ground rise reaches the ground connections
many nanoseconds later.
■
The rise time of the wave which emerges from GIS-to-air
termination will be of the order of 10 ns.
■
The wave takes about 4 ns to propagate from GIS enclosure to ground where it gets inverted and reflected back to the
enclosure, canceling the voltage on the enclosure.
■
Transient ground rise can cause sparks across electrical discontinuities in the electrical enclosure and can induce
transients on poorly configured control cables that may cause
incorrect operation of electrical and electronic equipment.
■
Transient ground rise in indoor GIS is reduced through the
use of a metal building with a coaxial connection between the
metal wall and the enclosure. The interior of the building acts
like a Faraday cage and reflects transients that propagate from
external GIS to air terminations back toward the building.
■
When a GIS is connected to a high-pressure fluid-filled
cable, the enclosures of two systems are isolated and bypassed
with a polarization cell to apply cathodic protection to the
cable pipe.6 The transient can cause a failure of the insulation
between the cable pipe and GIS. The problem can be eliminated by extending the insulator to the point so that it does not
flash over.
18-5 EFFECT OF LUMPED CAPACITANCE
AT ENTRANCE TO GIS
When a capacitance, for example, a CVT is installed at the entrance
of a GIS, under fault conditions the capacitor will discharge, the
frequency determined by inductance and capacitance of the discharge loop (Fig. 18-6). For a loop inductance of 20 µH and capacitance of 1000 pF, the discharge frequency will be about 1 MHz and,
therefore, skin effect considerations apply. The refracted waveforms
of higher frequency are superimposed upon the lower-frequency
waveform due to discharge loop. Induced potentials may be generated in the nearby metallic loops. A discharge waveform is shown
in the EMTP simulation in an example later.
The waveform can be approximated by the following expression:7
V = Vle −αlt cos ωlt + Vhe −αht sin ωht
(18-13)
where Vl is peak value of low-frequency component of enclosure
transient voltage; Vh is high-frequency component of enclosure
GAS-INSULATED SUBSTATIONS—VERY FAST TRANSIENTS
FIGURE 18-6
Impact of external capacitance discharge on TGPR.
transient voltage; al and ah are attenuation factors of low-frequency
and high-frequency components, respectively; and ωl and ωh are
angular frequency of low-frequency and high-frequency components, respectively.
For shock hazard considerations, the body energy can be calculated from the following equation:
E=
1 Vl2 Vh2
+
4 R B αl αh
(18-14)
where the body resistance RB varies from 50 Ω for good contact to
100000 Ω for dry contact, typical value being 500 Ω.
18-6
TRANSIENT ELECTROMAGNETIC FIELDS
The electromagnetic fields are radiated from the enclosure and will
stress the secondary equipment, especially the electronic controls and
the computer equipment. Measurements of these fields have been
made on GIS.8 At a distance of 9 cm, an electrical field of 60 kV/m
with main oscillating frequency of 10 MHz was observed, and at a
distance of 5 m from the enclosure, an electrical field of 5 kV/m but
higher frequency was observed in an 800-kV GIS. While the electrical
field strength rapidly reduces with distance, its frequency increases.
Reflections and refractions from internal structures are observed.
18-7
483
BREAKDOWN IN SF6
We discussed some superior insulating properties of SF6 as an electronegative gas and breakdown mechanism in Chap. 8. With respect
to insulation coordination in GIS, it is an important criterion. Here,
the insulation has to be considered nonrestoring, and in the event
of a fault, long downtimes have to be accepted. To ensure reliability,
this failure rate should be kept low. Due to almost perfect metal
casing, atmospheric and environmental effects are minimum, yet
for the steep-fronted waves, the insulation properties are quite different. Due to small gap and high field strengths, the voltage-time
characteristics of SF6 are comparatively flatter as compared to that
of air insulation, and this is of much importance. It becomes all the
more necessary that the overvoltages are limited by surge arresters.
We will not go into the breakdown theories in detail, except
to show breakdown time lags in SF6 on the application of a surge
voltage, (Fig. 18-7).
The two criteria for breakdown are that:
1. There must be enough electrical fields of sufficient strength
and adequate distribution to produce avalanches according to
streamer criteria. For a given electrode configuration, this
condition is met by voltage U0 at time t0.
2. There must be one primary electron in a suitable location
to initiate first avalanche. Such electrons are produced due to
cosmic, ultraviolet, and radioactive radiations. Electrons are
emitted at the cathode by electrical and thermal excitations and
photon emissions. As these occur randomly, the time lag ts
(statistical time lag) indicates availability of an initiatory electron.
According to streamer criteria a first avalanche occurs followed
by condensing avalanches bridging the gap.
There is a third time delay tf (formative time lag) which is the
sum of two time delays—one time lag for the formation of streamer
(negligible) and second for the formation of spark.
The total time lag after the application of voltage impulse is tc,
which is calculated as follows:
tc = t0 + t s + t f
(18-15)
Figure 18-7 shows the difference between a step voltage and
lightning impulse.9
18-7-1
Voltage-Time Characteristics
Figure 18-8a shows the VI characteristics when U0 is exceeded.
For zero-percent probability, only tf is considered. Then ts is added
later on for 95 percent probability. The voltage-time characteristics
obtained by this method are shown in Fig. 18-8b. Further research
shows that the breakdown voltages are higher if the impulse is
chopped, of the order of 10 percent or more, and the influence of
the wavefront is much smaller as compared to the wave-tail on the
breakdown voltage and the breakdown probability.10
The SF6 pressure, stressed electrode area, impurities, and electrode surface roughness are some factors that influence the breakdown on switching and lightning surges.
When applied to actual assembly of GIS, the field strength is
approximately uniform and BIL is approximately equal to chopped
wave test. Table 18-1 shows the BIL and BSL levels of GIS from
IEEE Std. C37.122.11 The importance of BSL under disconnector
operation has been highlighted earlier. It may be prudent to raise
the BSL level when specifying GIS over the values specified in the
standards for better security. The safety margins considered are normally 20 percent above the maximum crest of the voltage calculated,
in GIS.
484
CHAPTER EIGHTEEN
FIGURE 18-7
Breakdown time lags in SF6 for step voltage change and lightning impulse.
18-8
MODELING OF TRANSIENTS IN GIS
The modeling of transients in GIS is not straightforward. The internal damping is determined by a number of factors, including spark
resistance, and refraction to lines and cables connected to the substation. The accurate modeling of these components and the relationship
between the enclosure and ground are necessary.3,12 The computing of
an accurate waveform at an interval of a meter in the substation would
be impractical. For a rise time of the order of 10 ns, any connection larger than 1 ft should be thought of as a transmission line with
surge impedance and a propagation time. An approximate approach is
acceptable so long as it is verified against measurements.
IEEE reports in (Refs. 13 and 14) provide modeling guidelines
for VFT. The modeling can be single-phase or three-phase, depending on the study to be performed. An electrical equivalent circuit
composed of lumped elements and distributed parameter line
models is used. The skin effect at high frequencies can produce
appreciable attenuation; however, often this effect is ignored for
conservatism. The calculations of internal transients may be performed using distributed parameter models for which conductor
enclosure is taken into account, assuming that external enclosure is
perfectly grounded. For TEV, a second mode of enclosure to ground
is also considered.
18-8-1 Bus Work, Conductors, and Cables
For frequencies up to 100 MHz, the bus duct can be represented
as a lossless transmission line. The inductance and capacitance of
a coaxial single-phase cylindrical configuration with conductor
radius of r and internal enclosure radius of R is given by:
L=
µ0 R
ln
r
2π
(18-16)
2πε
C=
ln(R /r )
Therefore, the surge impedance is:
Z = L /C =
FIGURE 18-8
(a) Application of volume-time and voltage-time
criteria for development of voltage-time characteristics of SF6. (b) Calculated
voltage-time characteristics of SF6, based on (a).
µ0ε
2π
ln
R
R
≈ 60 ln
r
r
(ε = ε 0 )
(18-17)
Experimental results show that propagation velocity in GIS
ducts is approximately 0.95 to 0.96 of the speed of light.
The bus work and conductors between discontinuity points and
connections between substation equipments can be represented
by line sections, which can be modeled by untransposed distributed parameter sections with surge impedances. The minimum
GAS-INSULATED SUBSTATIONS—VERY FAST TRANSIENTS
TA B L E 1 8 - 1
485
BIL and BSL of GIS
SYSTEM VOLTAGE
TYPE TEST VOLTAGES
RATED MAXIMUM VOLTAGE
PHASE-TO-PHASE
RATED BIL,
KV CREST
LOW-FREQUENCY PHASE-TO-GROUND
WITHSTAND KV, RMS
SWITCHING IMPULSE WITHSTAND
KV CREST
72.5
350
160
121
550
215
145
650
310
169
750
365
242
900
425
362
1050
500
825
550
1550
740
1175
800
2100
960
1550
4
ANSI/IEEE Std. C37.122.1, IEEE Guide for Gas Insulated Substations, 1993 (R2002).
conductor length with distributed parameter representation dictates the simulation step in EMTP which may become of the order
of 1 ns (typically 5 ns). The surge impedance of GIS (60 to 75 Ω)
is considerably smaller than that of air-insulated line or bus work
(300 to 400 Ω), and considerable overvoltages can develop at open
disconnect positions. The surge impedance of cables is between 30
and 60 Ω and velocity of propagation 1/3 to 1/2 of speed of light.
is represented with single-surge impedance, and dotted lines are
the response with lumped capacitance. The response is for a step
input in all the cases.15
18-8-2
18-8-4 Surge Arresters
Bushings
A detailed model consists of several sections of transmission lines
in a series that can be used, as the bushing gradually changes the
surge impedance of the GIS to that of the line. Rigorously, the
graded bushings are modeled with a group of coaxial transmission
line sections created by concentric grading foils. A further detailed
model considers the coupling between the conductors and shielding electrodes. The incident wave divides between the concentric
coaxial transmission lines formed by the foils. On a simplified basis,
the bushing can be represented by equivalent single-section surge
impedance and an equivalent surge capacitance. A lumped resistor
represents the losses.15 Figure 18-9 shows the simulation results with
these models. The solid line indicates the response with concentric
transmission lines, the dashed line is the response when the bushing
FIGURE 18-9
18-8-3
Power Transformer
At high frequencies, the transformer behaves like a series and shunt
capacitance network. See Chap. 14.
Surge arrester models are discussed in Chap. 20. If the switching
operations do not produce voltages high enough for the metaloxide arresters to conduct, these can be modeled as capacitance to
ground. A detailed model represents each internal shield and block
individually, and includes travel times along shield sections, and
capacitance between these sections, capacitance between blocks
and shields, and the blocks (Chap. 20). Because the GIS conductors are inside a grounded metal enclosure, the lightning impulses
can only enter through the connection of GIS to the rest of the system. Cables and direct transformer connections are not subject to
lightning strikes; therefore, only air-to-SF6 bushing connections are
a lightning concern. The conventional metal-oxide arresters may
not be effective on high-rise switching surges.
Response of bushing models—solid line represents a number of transmission line elements; dashed line, bushing represented by a
single transmission line; dotted line, bushing represented by equivalent lumped capacitance.15
486
CHAPTER EIGHTEEN
18-8-5 Circuit Breakers
A closed circuit breaker can be represented by a lossless line, length
equal to the physical length of the breaker, with propagation velocity reduced to 95 percent that of light. An open-circuit breaker is
not so simple to model. Circuit breakers with several chambers may
contain grading capacitors, which are not arranged symmetrically.
The accuracy of simulation depends on the details of the modeling of each GIS component. To achieve reasonable results, highly
FIGURE 18-10
accurate models are required. The arrangement of spacers, shielding electrodes, and varying diameters can be accurately simulated
from physical parameters derived from manufacturer’s drawings.
Figure 18-10, adapted from (Ref. 14), shows a detailed model of
a line feeder connected to an overhead line with length of each section in meter, surge impedance, and capacitances. It shows 420-kV
GIS model with duplicate busbars, disconnectors, circuit breaker,
current, and potential transformers. Note each small section is
Detailed model of a feeder, based on Ref. 14.
GAS-INSULATED SUBSTATIONS—VERY FAST TRANSIENTS
FIGURE 18-11
Simulated versus actual response based on model, Fig. 18-10.14
modeled with a line length and its surge impedance. Figure 18-11
shows comparison of computer simulation and actual measurements of disconnector-induced overvoltages in a 420-kV GIS. The
effect of spacers, elbows, corona shields, and other hardware is considered, and the simulation closely follows the actual results.
18-9
INSULATION COORDINATION
The configurations of GIS vary. In fact, all the bus arrangements
popular in outdoor air-insulted substations can be implemented in
GIS, for example: (1) single-bus arrangement, (2) main and transfer
FIGURE 18-12
487
bus, (3) ring bus, (4) double-bus single breaker, (5) double-bus
double breaker, and (6) breaker and one-half schemes. These are
not shown here. One difference is the use of maintenance ground
switches; Fig. 18-12 shows 500-kV GIS single-line diagram of connections, with two incoming circuits, two outgoing circuits, and a
bus section circuit-breaker for coupling the duplicate busbars. The
assembly, thus, consists of disconnect switches, circuit breakers,
surge arresters, voltage and current transformers, gas–oil bushings,
air bushings, and gas barriers. Note the use of grounding switches
with fault closing capability for maintenance. The power transformers (not shown in Fig. 18-12) may be throat-connected to GIS bus,
Implementation of a double bus bar with bus section power system configuration in GIS; disconnectors and grounding switches are shown.
488
CHAPTER EIGHTEEN
or the transformers may be connected through an open air bus. The
surge arresters may be connected at each line entrance and exit,
and they can be conventional air-insulated arresters outside the GIS
enclosure; alternatively, gas-insulated arresters may be accommodated inside the GIS enclosure. The latter have an advantage that
the surge arrestee lead lengths will be short.
Thus, the modeling of transients in GIS on EMTP with all the
connections, terminations, surge arresters, potential transformers,
taps, and bushings becomes rather complex. On a simplistic basis,
assuming a certain incoming surge and modeling the entire GIS as
a bus of certain surge impedance, a hand calculation of the voltage,
say at the end of an open GIS terminal can be made based on the
lattice diagrams discussed in Chap. 4.
The considerations for the insulation coordination are similar as discussed in Chap. 17, for air-insulated substations, modified by the short
transit time of the incoming surges in the GIS.
Again we consider:
■
Back flashovers and shielding failures
■
Switching and lightning overvoltages
■
Application of surge arresters and their locations
■
Tower-footing resistance, especially close to GIS
18-10
■
Presence of capacitive voltage transformer (outside GIS) at
the entrance of GIS
■
Impact of bushing capacitance, entrance, and outgoing
■
Influence of T-connections and branched connections
It is noted that the high overvoltages in GIS are caused by back
flashovers, especially if these occur close to GIS, which may result in
insulation failure. For simulation, only a few spans of overhead line
close to GIS need to be considered. The tower footing resistance plays
an important role. The greater the tower footing resistance, the greater
the distance from GIS that should be considered. Back flashovers generate overvoltages of high rate of rise at the point of flashover. Thus,
a back flashover close to the GIS means overvoltages of high rise time
and magnitude.
FIGURE 18-13
Only the lightning strokes close to GIS contribute to the risk of
insulation failure. Voltage within GIS will depend on the steepness
of the incoming voltage, the relative surge impedance of GIS and
overhead line/cable, and the length of the GIS, as it determines the
wave travel time. Initially, the overvoltages will increase with the
length of GIS bus; however, when the 2T, where T is the travel
time in the GIS, reaches the duration of the entering voltage, the
superimposition of the reflected waves is less pronounced and the
overvoltages decrease.
When a coupling capacitor is connected (say a CVT outside the
GIS) at the entrance, it reduces the overvoltages in GIS as the steepness of the incoming voltage is reduced. This will delay the travel
time of the surge, say to an open disconnector, and there will be short
delay in voltage built up on GIS. The capacitor decreases the MTBF.
Shielding failures, when the lightning stroke lands on the phase
conductor rather than on ground wire, should not normally cause
flashover in a well-designed overhead line. Even with flashovers,
the overvoltages entering the substation are unlikely to have a front
time <1 µs.
SURGE ARRESTERS FOR GIS
As discussed in an earlier section, the voltage-time characteristics
of breakdown in SF6 are flatter compared to that of air insulation. It
means that an incoming surge is likely to cause breakdown in the
GIS before breakdown occurs in air. A high incoming overvoltage
tends to increase the rate of voltage buildup in the entire GIS with
the same arrester characteristics. The arrester will conduct earlier,
but the reflection time of the negative wave from the arrester to
reach any point in the GIS remains the same. Increasing the protective level for fast front transients, as compared to air-insulated
substations, is one option, and a higher margin of 20 percent can be
applied. An arrester on the incoming, which may be located outside
GIS, is normally provided and its insulation level should be chosen
consistent with GIS (Fig. 18-13). A CVT on the incoming junction of OH line and GIS will slow down the fast front of incoming
surges. For large substations, an arrester inside GIS at location 2 on
the source side of the first disconnector can be provided, though it
has been debated whether such a location is helpful at all for the
VFT generated by the disconnector operation. Though metal-oxide
arresters have been demonstrated to respond to VFT, it is doubtful
Location of surge arresters in GIS and external to GIS.
GAS-INSULATED SUBSTATIONS—VERY FAST TRANSIENTS
whether the dimensions involved will allow control of VFT surges
of nanoseconds. An arrester at location 4, on the primary side of the
transformer, is invariably provided. Again, the transformer windings
will be subjected to high frequencies. With one arrester only at the
incoming, the maximum overvoltage will occur at the far end of
GIS at transformer connection. With two arresters, it will occur
somewhere in the middle of GIS.16,17
When a GIS has direct connection to a transformer, much impedance discontinuities are avoided and only degradation is caused by
the slight delay in the rise time due to bushings. At the transformer
terminals, the surge will appear with no reduction in magnitude and
slight degradation in the rise time until it is attenuated by reflections
and surge arresters. The surge capacitance of the power transformer
has rather a small impact on the overvoltages within GIS.
The influence of a number of connected branches on maximum
overvoltages is shown in Fig. 18-14. In this figure, Vd is the discharge voltage of the arrester. The figure represents equal length of
branches and is drawn for a system voltage of 420 kV and arrester
discharge voltage of 830 kV. The ratio of the line-to-GIS surge
impedances is 5 and L is the distance to the disconnector.
Special arresters, indoor or outdoor types, for use with GIS have
been developed. These have high energy absorbing capability. The
active part is installed in metal enclosure filled with SF6 gas under
pressure and forms an impervious pressure system according to
IEC Std. 60694,18 Chap. 20.
Example18-2 A system configuration of 750-kV GIS section is
shown in Fig. 18-15. The bushing 1 is connected to a short spur
of 750-kV line, and bushing 2 is connected to a power transformer, the secondary of the transformer is open circuited. The
length of the three sections and bushings in GIS are modeled with
surge impedances, bushing capacitances, and so on. A lightning
stroke, 200 kA, 3/100 µs wave front, occurs on the top of tower,
which results in a backflashover of phase c. The resulting voltage
transients at points VT, Vm, and Va in Fig. 18-15 are shown in
Figure 18-16a to c, respectively. These show similar patterns. The
phase c voltage rises to approximately 1750 kV peak (= 2.86 times
the normal) at the transformer terminals. The surge arrester currents SA1 and SA2 are depicted in Figure 18-17a and b, respectively. The discharge current through phase c, arrester SA1, has a
peak of 6000 A.
FIGURE 18-15
FIGURE 18-14
489
Influence of parallel connected branches of equal
length in a 420-kV GIS.
Example 18-3
Now consider that phase c flashes over to
ground at 1000 kV. The resulting voltage transient patterns at
VT, Va, and Vm are simulated in Fig. 18-18. Figure 18-19a and b
illustrates the flashover voltage and current transients to ground,
respectively.
A GIS interconnected with a spur of 750-kV transmission line for study of transients on backflash, phase c ; Examples 18-1 and 18-2.
490
CHAPTER EIGHTEEN
FIGURE 18-16
a, b, c, Voltages VT, Vm, and Va, respectively, on backflash conductor phase c ; see text.
GAS-INSULATED SUBSTATIONS—VERY FAST TRANSIENTS
FIGURE 18-17
a and b, Surge arrester currents, SA1 and SA2, respectively.
491
492
CHAPTER EIGHTEEN
FIGURE 18-18
FIGURE 18-19
Voltages VT, Va, and Vm on ground flash at 1000 kV in phase c; Example 18-2.
a and b, Voltage and current, flashover to ground, phase c ; Example 18-2.
GAS-INSULATED SUBSTATIONS—VERY FAST TRANSIENTS
FIGURE 18-19
PROBLEMS
1. During operation of a disconnector, the voltage on the
source side is 1.2 per unit, and the load side is 0.5 per unit.
Source side Z = 100 Ω, the load side Z = 75 Ω. Assuming that
a sparkover takes place at the peak of the voltage, calculate the
source and load-side voltages after sparkover.
2. A breakdown occurs at 750 kV in the middle of a 20-m
section of GIS, connected to an OH line of Z = 400 Ω, and
open at the other end. Considering a surge impedance of 75
Ω at either end of GIS, and a velocity of propagation of 3E08
(m/s), calculate (a) voltage at open end at breakdown and after
first reflection and (b) voltage at junction of OH line and GIS
on breakdown and after first reflection. How will these voltages
behave in subsequent reflections? Will they increase or decrease?
3. A GIS is connected to a transmission line at one end and
terminated in a transformer at the other end. A surge arrester is
installed at the transformer end only. Discuss the limitations of
this scheme. At what point in the GIS will the transient voltage
peak? If a surge arrester is installed on the incoming line, how
will the location of maximum surge voltage in GIS change?
4. Draw a freehand sketch of the waveshape of a disconnectorinduced transient on opening the disconnector, superimposed
upon the system voltage.
5. A GIS is connected to an OH line of surge impedance =
400 Ω. Consider a surge impedance of 100 Ω between the GIS
and its enclosure, and a surge impedance of 75 Ω for the GIS,
open at the other end. Calculate the peak transient voltage on
the enclosure in per unit. Also calculate the voltage at the open
end of the GIS and junction of OH line and GIS. Explain the
polarity of the enclosure voltage.
493
(Continued )
6. Calculate surge impedance of a bus, with enclosure
diameter 30 cm and conductor diameter 4 in. What is the
estimated capacitance?
7. How does the insulation coordination of GIS differ from an
air-insulated substation?
8. Write a half-page note on the voltage-time characteristics of
SF6, without any mathematical equations.
REFERENCES
1. S. Yanabu, H. Murase, H. Aoyagi, H. Okubo, and Y. Kawaguchi,
“Estimation of Fast Transient Overvoltages in Gas Insulated
Substations,” IEEE Trans. PD, vol. 5, no. 4, pp. 1875–1882,
Nov. 1990.
2. S. A. Boggs, A. Krenicky, A. Plisse, and D. Schlicht, “Disconnect
Switch Induced Transients and Trapped Charges in Gas-Insulated
Substations,” IEEE Trans. PAS, vol. 101, no. 10, pp. 3593–3602,
Oct. 1982.
3. S. A. Boggs, N. Fujimoto, M. Collod, and E. Thuries, “The
Modeling of Statistical Operating Parameters and the Computation of Operation Induced Waveforms for GIS Disconnectors,”
CIGRE Paper 13-15, 1984.
4. IEEE Std. C37.122.1, IEEE Guide for Gas Insulated Substations, 1993. (This standard contains a bibliography of 1518
technical papers and references on GIS.)
5. N. Fujimoto, E. P. Dick, S. A. Boggs, and G. L. Ford, “Transient
Ground Potential Rise in Gas Insulated Substation: Experimental Studies,” IEEE Trans. PAS, vol. 101, pp. 3603–3619,
Oct. 1982.
494
CHAPTER EIGHTEEN
6. N. Fujimoto, S. J. Croall, and S. M. Forty, “Techniques for the
Protection of Gas-Insulated Substation to Cable Interface,” IEEE
Trans. PD, vol. 3, no. 4, pp. 1650–1655, Oct. 1988.
7. G. L. Ford and L. A. Geddes, “Transient Ground Potential Rise
in Gas Insulted Substations—Assessment of Shock Hazard,”
IEEE Trans. PAS, vol. 101, no. 10, pp. 3620–3629, Oct. 1982.
8. J. Meppelink, K. Diederich, K. Feser, and W. Pfaff, “Very Fast
Transients in GIS,” IEEE Trans. PD, vol. 4, pp. 223–233, Jan. 1989.
9. I. M. Bortnik, C. M. Cooke, “Electrical Breakdown and Similarity
Low in SF6 at Extra High Voltages,” IEEE Trans. PAS, vol. 91,
no. 5, pp. 2196–2203, 1972.
10. T. H. Teich and W. S. Zaengi, Dielectric Strength of an SF6 Gap,
In Current Interruption in High-Voltage Network, K. Ragaller, ed.,
Plenum Press, New York, 1978.
11. IEEE Std. C37.122, IEEE Standard for Gas Insulated Substations,
1993.
12. N. Fujimoto, H. A. Stuckless, and S. A. Boggs, Calculation of
Disconnector Induced Overvoltages in GIS, In Gaseous Dielectrics, vol. IV, L. Christophorou, ed., p. 473, Pergamon Press,
New York, 1984.
13. IEEE Report, “Modeling Guidelines for Fast Front Transients,”
IEEE Trans. PD, vol. 11, no. 1., pp. 493–506, Jan. 1996.
14. IEEE Report, “Modeling and Analysis Guidelines for Very Fast
Transients,” IEEE Trans. PD, vol. 11, no. 4, pp. 2029–2035,
Oct. 1996.
15. N. Fujimoto and S. A. Boggs, “Characteristics of DisconnectorInduced Short Rise Time Transients Incident on Externally
Connected Power System Components,” IEEE Trans. PD, vol. 3,
no. 3, pp. 961–970, Jul. 1988.
16. M. E. Potter and T. O. Sokoly, “Development of Metal-Oxide
Varistors for Gas Insulated Surge Arresters,” IEEE Trans. PAS,
vol. PAS-101, no. 7, pp. 2217–2220, July 1982.
17. M. Mitani, “Analysis of Lightning Surge Phenomena and
Examination of Insulation Coordination in a Three-Core Type
Gas Insulated Bus,” In Conference Proceedings, IEEE PES Summer
Meeting, Paper A 79 401-1, 8 pages, July 1979.
18. IEC Std. 60099—Part 4, Metal Oxide Surge Arresters Without
Gaps for AC Systems, 2009.
FURTHER READING
H. W. Anderi, C. L. Wagner, and T. H. Dodds, “Insulation Coordination for Gas Insulated Substations,” IEEE Trans. PAS, vol. 92,
no. 5, pp. 1922–1930, Sept./Oct. 1973.
W. Boeck and K. Pettereson, “Fundamentals and Specific Data
of Metal-Enclosed Substations for the Insulation Coordination,”
CIGRE Paper 23-03, 14 pages, Aug. 1978.
P. F. Coventry and A. Wilson, “Fast Transients in Gas Insulated
Substations—An Experimental and Theoretical Investigation,”
Gaseous Dielectrics, vol. VI, pp. 503–508, 1991.
R. Erikson and H. Holmborn, “Insulation Coordination of GasInsulted Substations,” Proceedings of the International Symposium on
Gaseous Dielectrics, Knoxville, TN, March 6–8, 1978.
IEC 60071-2, Insulation Coordination, Part 2: Application Guide,
1996.
T. Kobayashi, S. Mori, H. Koshiishi, K. Niromija, M. Mitsuki,
H. Yokoyama, T. Hara, “Development of Compact 500 kV,
8000 A Gas Insulated Transmission Line—Study on Insulation
Design,” IEEE Trans. PAS, vol. 103, no. 11, pp. 3154–3164,
Nov. 1984.
J. M. Meek and J. G. Craggs, Electrical Breakdown of Gases, John
Wiley and Sons, New York, 1978.
D. B. Miller and P. M. Harrison, “Measurements and Modeling
of Switching Transients in Gas-Insulated Transmission Lines,”
Conference Proceedings, IEEE SOUTHEASCON’ 87, Tampa, FL,
vol. 2, pp. 456–460, Apr. 1987.
H. Raether, Electron Avalanches and Breakdown, Butterworth, London,
1964.
Klaus Ragller, ed., Surges in High-Voltage Networks, Plenum Press,
London, 1980.
T. H. Teich and W. S. Zanegi, The Dielectric Strength of an SF6 Gap,
In Current Interruptions in High Voltage Networks, K. Ragaller ed.,
pp. 269–297, Plenum Press, New York, 1978.
B. Wahlstron, H. Holmborn, and A. Schei. “Overvoltage Protection
of Metal Enclosed SF6 Substations: Insulation Coordination Philosophy and Surge Arrester Characteristics,” CIGRE Paper 33–03,
15 pages, Aug. 1976.
J. M. Wetzer, M. A. Van Houten, and P. C. T. Ven der Laan, “Prevention of Breakdown Due to Overvoltages Across Interruptions of GIS
Enclosure,” Gaseous Dielectrics, vol. VI, pp. 531–536, 1991.
CHAPTER 19
TRANSIENTS AND SURGE
PROTECTION IN
LOW-VOLTAGE SYSTEMS
The mechanism of generation of surge voltages on low-voltage
power systems is somewhat akin to the switching transients and
direct or indirect effects of lightning in the high-voltage systems.
In low-voltage systems, the surges may appear in any combination
of line, neutral, or grounding conductors. These may be of sufficient
magnitude, duration, rate of change, periodic or random in nature
to cause damage or operational upset. The effectiveness of grounding plays a significant role. Telephone and data/communication lines
also provide a means of conducting surges into a facility, and need
to be protected. Electrical line noise generally implies any voltage less
than two times the nominal peak voltage of the system, and it can
cause malfunctions in computer software. To distinguish between
the electrical noise and transient voltage surges, the latter generally
implies transient voltage amplitude which exceeds two times the
nominal peak voltage of the electrical system.
19-1
MODES OF PROTECTION
Figure 19-1 shows seven modes of protection in three-phase, wyegrounded systems. These are phase to ground (L-G, three modes),
phase to neutral (L-N, three modes), and, finally, line to ground
(L-G mode). The L-L and L-N modes are called normal modes, while
L-G and N-G are called common modes; the term “common” comes
from an old term used in the telecommunication industry meaning
from ground.
Most commercial facilities are fed from a utility transformer
that transforms the utility primary distribution voltage, normally
12.47 kV to a common voltage of 480 or 208 V. Three-phase conductors and the neutral conductor feed the loads, while the fifth
ground wire provides the ground reference. When an external disturbance enters the building, it is coupled between one or more
phase wires and ground or neutral. Most transient phenomena,
that is, switching of capacitors, utility load shedding, accidents
involving power loss, and transfer switches (which transfer power
form one source to another) may produce a transient at the service
entrance. Thus, all modes shown in the Fig. 19-1 should be protected. The ground conductor is grounded at the distribution pole,
and even if a ground grid is utilized to provide a zero reference
point, there will be transient voltage differential developed when
the ground current is shunted to ground.
19-2 MULTIPLE-GROUNDED
DISTRIBUTION SYSTEMS
Figure 19-2 shows typical grounding practice for wye service
entrance served by a wye multiple-grounded medium voltage system in North America. Note the multiple grounds of the neutral
conductor protected neutral (PEN). The practice of grounding of
commercial and residential facilities in the United States requires
that the neutral conductor is bonded to the ground conductor at
the service entrance, and both are bonded to the building ground.
There cannot be N-G surge at the service entrance. However L-N
surges within the building can produce N-G surges at the end of a
branch circuit.
Further implications of multiple-grounded distribution systems
are shown in Fig. 19-3. National Electric Safety Code (NESC)1
requires that the neutral on multiple-grounded wye distribution
systems have a minimum of four earth connections per mile. This
also applies to direct buried underground cables. The voltage
between neutral and earth can originate from a variety of sources. A
60-Hz voltage can exist between objects connected to neutral and
earth. A short-duration transient can exist, when the lightning current is dissipated into the earth. A differential voltage between the
neutral and ground is more likely to occur when the same service
transformer feeds two or more consumers.
Figure 19-4 shows the grounding practice for industrial establishments. Here the neutral is grounded only at one point, at the
source. This figure shows that the neutral from the utility transformer is not required to be run for industrial plant mediumvoltage, three-phase loads. In case the industrial plant needs some
loads like lighting and controls to be served from low-voltage
grounded systems, these lower voltages are served from a separate
transformer with artificially derived neutral. In case the service is
at low voltage, a neutral may be run to supply phase-to-neutral
495
496
CHAPTER NINETEEN
FIGURE 19-1
FIGURE 19-2
FIGURE 19-3
Seven modes of protection, common and normal modes, in a three-phase, four-wire, wye-connected, low-voltage system.
Typical grounding practice for wye-service entrance served by multiple-grounded, medium-voltage system in North American systems.
Distribution of load currents in phase and neutral/ground conductor in a multiple-grounded system; the neutral/ground conductor
develops differential voltages.
TRANSIENTS AND SURGE PROTECTION IN LOW-VOLTAGE SYSTEMS
FIGURE 19-4
497
Typical grounding practice for industrial distribution systems, the transformer neutral is grounded only at the source in North American
systems.
loads, but it is not grounded anywhere in the plant except at the
service transformer. There is no bonding of neutral conductor with
the ground at the service entrance, a practice which is invariably
followed for industrial medium- or high-voltage grounded systems
or separately derived industrial systems.
19-2-1
Equivalent Circuit of Multiple-Grounded Systems
Figure 19-3 of a multiple-grounded system shows that the grounds
at various points cannot be at the same potential. This figure shows
the current flow in the multiple-grounded neutral under normal
operation. The load current flows through line to neutral, but as
the neutral is grounded at the consumer premises (ground CG) and
also at multiple points, the neutral current returns to the utility
transformer through multiple paths; the sharing of current depends
upon the relative impedances of the grounding circuit. An equivalent impedance diagram is shown in Fig. 19-5. The system may
be analyzed using symmetrical components or equivalent circuit
concepts. The line may pass through a region of high soil resistivity;
FIGURE 19-5
each grounding point can be modeled individually along with the
section of the feeder separating it from the adjacent grounds.
National Electric Code (NEC)2 article 250.106 requires that
lightning protection system ground terminals shall be bonded to
the building or structure electrode system (so that the potential
differential between these is minimized). Further NEC articles
mandate that electrical equipment is bonded and connected in a
manner to establish a path of sufficiently low impedance. Where
the ground resistance of a single ground electrode exceeds 25 Ω,
additional ground rods are mandated to lower the resistance to 25 Ω.
This value of 25 Ω in NEC is too high; an ideal ground should
provide a near-zero resistance between bonded components and
the ground electrode of the facility to limit ground potential rise on
a surge current. With the grounding resistance of 25 Ω allowed by
NEC, high surge currents will produce high ground potential rise
(GPR), which can damage the surge protection devices.
Consider the dissipation of a lightning surge near the distribution system (Fig. 19-6). If the lightning current is not effectively
dissipated through the arrester, the result can be flashover of the
An equivalent circuit diagram of a multiple-grounded system for a line-to-ground fault at a remote node.
498
CHAPTER NINETEEN
FIGURE 19-6
Distribution of lightning stroke current in a pole-mounted transformer service to a premises.
insulation and impingement of the surge on the consumer apparatus.
This figure shows a surge arrester mounted on the transformer tank
and the surge current will pass through the tank to the neutral
that acts as ground conductor. The division of the surge current is
shown in thick arrows. A surge voltage will appear on the neutral
conductor and the consumer premises as the neutral is bonded to
the consumer ground. This surge voltage will depend upon a number
of factors—the downward lead length, the resistance of the grounding
electrodes, and the surge impedances of the various paths. Generally,
it may not be detrimental to the premises, especially when the recommendations of surge protection of low-voltage systems and the category of installations are followed, however, a possibility of flashover
cannot be ruled out. The grounding of underground cable distribution
system is more important, in the sense that lightning surges and wave
fronts may double on cables. The voltage is reduced by close connection of the surge arrester to the cable terminations. The parameters of
surge performance of grounding systems under high impulse currents
of short rise time have been discussed earlier in Chap. 5, and will be
further discussed in Chap. 22. It may be necessary to state here the
grounding and bonding requirements laid down in NESC1 and NEC.2
■
NESC requires grounded items on joint poles (e.g., for
power and communication) to be bonded together using either
single grounding conductor or bonding the supply grounding
conductor to the communication grounding conductor, except
where a certain separation is maintained (Rule 97A), in which
case there should be insulation between the grounding conductors. A hazardous potential difference can exist between the
two conductors. The Rule 215C3 requires bonding between
messengers at typically four times per mile.
■
It is required that a common ground electrode system
should be created by the two utilities for the communication
and power supply systems. If separate electrode systems are
used, these should be bonded together with a minimum #6
AWG conductor. This is to ensure that dangerous potentials do
not exist between the two grounding systems. A user of
computer modems, fax machines, answering machines, and
other communication equipment could be exposed to an
electrical shock apart from damage to the equipment.
■ NEC (250.24(A)(5)) prohibits bonding of the equipment
grounding conductor and neutral inside the premises. Note that
the neutral will carry a current, and a difference of potential exists
between the neutral and the ground conductor. Again, bonding
is required to metal water pipes, which limits the possibility of a
potential difference between the water system and other
noncurrent-carrying parts within the building. [A coupling can
occur through soil resistivity (Chap. 22)]. It is prohibited using
interior metal water piping system located more than 5 ft from the
entrance to the building from being used to interconnect
grounding electrodes within the building.
19-3
HIGH-FREQUENCY CROSS INTERFERENCE
Consider electronic devices that are connected together through a
data cable. The digital equipment radiates high-frequency energy
back on to the power line and must meet FCC specifications. Every
device containing any digital clock frequencies above 10 kHz has to
be registered and approved to meet FCC specifications. In a building hundreds of such devices may be housed throughout, and electrical noise can sum up to major pulses, causing errors or upsets.
Every computer or electronics circuit board contains ground paths,
which are eventually connected to the building ground. This ground
path passes over all the sensitive chips, CPUs, controllers memories,
and the like. One input goes to ground and a voltage comparison of
data to ground is made. Data signals are very small. In Fig. 19-7, the
devices are connected through a data cable and are possibly served
from different ac sources. The grounds are not uniformly the same at
two locations, especially at high frequencies, and even a few feet of
distance can create a voltage difference. Because of higher resistance
of the computer circuit boards, the difference in ground voltages
tend to concentrate at logic chips, which can cause errors.
Strategic installations of proper power-conditioning equipment
can mitigate potential cross-reference hazards, though improper
use of surge suppressor can worsen the problem by diverting a significant amount of energy into the ground circuit near the computer or its terminals. Consider a 5000-V surge and an impedance of
1 Ω between ground connections. This will generate a potential rise
of 5000 V. Lowering of grounding resistance becomes important and
TRANSIENTS AND SURGE PROTECTION IN LOW-VOLTAGE SYSTEMS
FIGURE 19-7
To illustrate ground differential voltage on two computer systems connected through a data cable.
larger size ground conductors can be run to the source or entrance
ground. All data communication equipment should be referenced to
a single ground network, properly designed to eliminate differential
voltages. Embedding of ground mats under the electronic equipment, which are then connected to the main grounding system to
establish an equipotential surface, are common means. TVSS should
not randomly shunt surge impulses to ground. Further discussions
and designs of grounding systems for electronic and data processing
equipment are not the scope of this book. To quote from NEC:
“To protect the sensitive electronic equipment, knowledge of
transient voltages and their waveforms, frequency of occurrence,
energy levels, and failure threshold of the protected equipment is
required.” An interested reader may see Refs. 3, 4, and 5. IEEE
standard3 has 603 pages and provides extensive bibliography.
19-4
SURGE VOLTAGES
We have amply discussed the lighting and switching overvoltages
in previous chapters. In low-voltage systems there are more coupling modes for these overvoltages.
19-4-1
499
Lightning
The coupling methods are: (1) direct coupling, associated with
lightning energy in the incoming conductors, (2) inductive couplings produced by magnetic fields during a lightning strike, and
(3) capacitive couplings derived from the charged ions passing over
conductors. Shielding is often used to bleed off these charges to
negate capacitive coupling effects. The lightning produces overvoltages through the following coupling mechanisms:
1. A direct stroke on primary circuits, that is, on a phase
conductor, will inject high currents into primary circuits; the
coupling mode can be through the phase and ground conductors and transformers. A direct stroke can also occur on the
secondary conductors.
2. A nearby stroke that sets up electromagnetic fields, which
in turn gives rise to overvoltages.
3. Surge transference through the transformers (Chap. 14).
4. Couplings through the common ground impedance paths
when a large amount of ground current flows, say due to cloudto-ground discharges. This couples through the common
grounding impedance paths and gives rise to transient voltage
differentials.
19-4-2
Switching
The switching transients originate due to normal and abnormal
conditions, as discussed earlier:
1. Capacitor switching, and fault clearing (Chaps. 6 and 8)
2. Load switching and load turn-off (Chap. 5)
3. Operation of current limiting fuses (Chap. 8)
4. Multiple reignitions or restrikes within the switching
devices themselves (Chap. 8)
5. Resonating circuits associated with switching devices
(Chaps. 2 and 6)
6. Commutation notches in electronic power converters
(Chap. 15)
19-5
EXPOSURE LEVELS
The rate of occurrence of surges varies over large limits and is not
easily predictable in a particular power system. IEEE6 classifies the
exposure levels as shown in Fig. 19-8:
Low exposure. Low exposure occurs in systems in geographical
areas known for low lightning activity, with little load or
capacitor switching activity.
Medium exposure. Medium exposure occurs in systems in
geographical areas known for medium to high lightning
activity, or with significant switching transients. Both or only
one of these causes may be present.
High exposure. The more severe conditions result from extensive exposure to lightning or unusually severe switching
surges.
Figure 19-8 shows that the surges can be the result of original
surge or the remnant resulting from the sparkover of the clearances.
500
CHAPTER NINETEEN
sections. A total of five test waveforms are specified, which are discussed in the following sections.
19-6-1
Combination Wave
The lightning-impulse (1.2/50 µs and discharge-current 8/20 µs)
wave shapes are shown in Chap. 5. The 1.2/50-µs and 8/20-µs
waves taken together are called combination waves; open circuit voltage and short-circuit current, respectively. The terminology according to IEC is “impulse” waves. See Chap. 5, Eq. (5-13) through
Eq. (5-18) for these wave shapes.
19-6-2
100-kHz Ring Wave
The 0.5/100-kHz ring wave shape, shown in Fig. 19-9,6 is a reasonable representation of surge voltages in 120- and 240-V ac systems.
A surge, even if originally unidirectional, excites natural oscillation
frequencies,7 and the oscillatory surge may have different frequencies. The wave shape is characterized by:
Rise time = 0 . 5 µ s ± 0 . 15 µ s
ringing frequency = 100 kHz ± 20 kHz
and
(19-1)
The amplitude decays, so that the amplitude ratio of the second
peak to first peak is between 40 and 110 percent. The ratio of the
third peak to the second peak and of the fourth peak to third peak
is between 40 to 80 percent. The equations are:
FIGURE 19-8
Rate of surge occurrence versus voltage level at
unprotected locations. Source: ANSI/IEEE Standard C62.41.6
For outdoors, the clearances will be higher, a sparkover of 10 kV
(1.2/50-µs wave) is typical, though 20 kV is possible. For indoor
wiring devices used in 120-, 240-, or 480-V distributions, a sparkover of 6 kV is adequate between the phase and the ground.
19-6
TEST WAVE SHAPES
This section should be read in conjunction with Sec. 19-7 on location categories as there are cross-references between these two
FIGURE 19-9
V (t ) = AVP (1 − e −t / τ1 )e (t /τ 2 )cos ω t
(19-2)
where t1 = 0.533 µs, t2 = 9.788 µs, A = 1.59, and w = 2p105 rad-s–1. The
rise time is defined as the time between the 10 and 90 percent
amplitude points on the leading edge of waveform. The frequency
is calculated from the first and third zero crossing after the initial
peak.
The nominal amplitude of the first peak of either open-circuit
voltage Vp or the short-circuit current Ip is selected according to the severity involved. The ratio Vp/Ip is specified as 12 Ω ± 3 Ω for category
B requirements and 30 Ω ± 8 Ω for category A requirements. No
short-circuit waveform is specified for 100-kHz ring wave.
100-kHz ring wave. Source: ANSI/IEEE Standard C62.41.6
TRANSIENTS AND SURGE PROTECTION IN LOW-VOLTAGE SYSTEMS
FIGURE 19-10
19-6-3
Wave form of 5-kHz ring wave. Source: ANSI/IEEE Standard C62.41.6
5-kHz Ring Wave
The waveform is shown in Fig. 19-106 and is defined by its opencircuit voltage parameters:
Rise time: 1 . 5 µ s + 0 . 5 µ s
and
ringing frequency: 5 kHz ± 1 kHz
Ratio of adjacent peaks of opposite
polarity = 60 to 80 percent
(19-3)
τ 1 = 0 . 7356 µ s, τ 2 = 280 . 4 µ s, A = 1 . 027, ω = π10 4 rad-s−1
(19-4)
The location categories in Figure 19-13 are based on the limiting
effects of inductance of the branch circuits at frequencies associated
with two standard test waves, which cause amplitude of current to
decrease as distance from the source of surge increases. The 5-kHz
ring wave is applicable to all categories of location.
10/1000-ls Wave
This waveform is shown in Fig. 19-11. The characteristics are:
Open circuit voltage:
Front time: 10 µ s(+ 0, − 5) µ s
Duration: 1000 µ s(+ 1000, − 0) µ s
(19-5)
Electrical Fast Transient
Circuit opening by air-gap switches has been recognized as producing a succession of clearing and reignitions, which generate bursts
of fast ringing surges. The transients have been associated with arcing phenomena under the label, “showering arc”.3 IEC8 requires a
test involving bursts of surges of 5-ns rise time and 50-ns duration.
IEEE C37.90.19 intended for protective relays and relay systems
also includes a fast transient specification of rise time 10 ns and
duration of 150 ns. The individual EFT in a burst is defined as:
Rise time: 5 ns ± 1 . 5 ns
Duration: 50 ns ± 1 . 5 ns
(19-8)
The duration is defined as the full width at half-maximum
(FWHM), that is, the time difference between the 50 percent amplitude points at the leading edge and trailing edge of each pulse.
Individual pulses occur in bursts with duration of 15 ms ± 3ms.
Within each burst the repetition rate is specified as a function of
peak open-circuit voltage.
For peaks ≤ 2kV: 5 kHz ± 1 kHz
For peaks > 2kV: 2 . 5 kHz ± 0 . 5 kHz
Short-circuit current:
Front time: 10 µ s(+ 0, − 5) µ s
Duration: 1000 µ s(+ 1000, − 0) µ s
where: τ 1 = 3 . 827 µ s, τ 2 = 1404 µ s, A = 1 . 019. The long-term waveform reduces the effect of inductance and is applicable to all location
categories.
19-6-5
The equation is same as for 100-kHz ring wave with the following constants:
19-6-4
501
(19-9)
The equation is:
(19-6)
V (t ) = AVP (1 − e −t / τ1 )e (t / τ 2 )
(19-10)
The equation is:
I(t ) = AI p (1 − e −t / τ1 )e −t / τ 2
(19-7)
where τ 1 = 3 . 5 ns, τ 2 = 55 . 6 ns, and A = 1 . 270. Figure 19-12 shows
the waveform.
502
CHAPTER NINETEEN
FIGURE 19-11
FIGURE 19-12
19-7
Waveform of 10/1000-µs current surge. Source: ANSI/IEEE Standard C62.41.6
(a) Waveform of EFT pulse. (b) Pattern of EFT bursts. Source: ANSI/IEEE Standard C62.41.6
LOCATION CATEGORIES
6
IEEE C62.41 divides locations into three broad categories, as
shown in Fig. 19-13a. The range of possible surge impedances and
difficulty of selecting a specific value is addressed in these categories. Location category C is likely to be exposed to substantially
higher voltages than the location category B, and higher exposure
rates of Fig. 19-8 could apply with open-circuit voltages of 10 kV
and discharge currents of 10 kA or more. The demarcation between
category B and C is taken at the meter or at the main disconnect of
the utility service. If the service is at high voltage, the demarcation
is at the secondary of the supply service transformer. For surges
originating in the utility supply, the source impedance may be considered constant, while the series impedance of the mains increases from
outside the location to within the building. Open-circuit voltages for
TRANSIENTS AND SURGE PROTECTION IN LOW-VOLTAGE SYSTEMS
FIGURE 19-13
C62.41.6
503
(a) Location categories. (b) Voltage staircases and current down-slopes according to location categories. Source: ANSI/IEEE Standard
504
CHAPTER NINETEEN
surges other than the fast transients show little attenuation within
the building.7 Secondary arresters having 10-kA, 4/10-µs ratings
have been successfully employed, effectively diverting associated
surge currents. Direct lightning strikes will produce higher currents.10 A location-C category surge protection device could be
used in locations A and B, but this is not necessary or economical.
The location categories are described in qualitative terms, as an
attempt to describe the scenarios of surges impinging at the service
entrance or those generated inside the building. The propagation of
surges is a phenomenon that does not recognize arbitrary boundaries, but is influenced by the components inside the installation. As an
example, a surge protection device on the primary of a transformer
does impact the secondary distribution. The concept resets on the
propagation and dispersion of surge currents. The surge currents at
the service meet the high surge impedance of the wiring system, and
with or without flashovers, reduce the surge current diverted into
the branch circuits. In contrast, a voltage surge below the point of
flashover of clearances will run unimpeded into the subcircuit wiring.
This concept based on IEEE Std11 is shown in Fig. 19-13b.
Consider now a direct flash to the structure. The current will
seek dispersion into local and remote earth electrodes and in the
neutral conductor in multiple grounded systems. IEEE Std11 recognizes that coupling of surge voltages will occur within the building
power system:
1. Shift in the potential of conductors by rise of ground potential due to flow of surge current may be represented by a unidirectional pulse.
2. Induction of voltage or current in the circuit loops by the
electromagnetic field of the lightning may be a ring-shape
wave.
These two types of surges involve less energy-delivery capability
than those associated with direct dispersion of the lightning current.
In the absence of published measurements made during these rare
TA B L E 1 9 - 1
LOCATION CATEGORY
occurrences, it is difficult to assign quantitative recommendations.11
The application of test waveforms in categories A, B, and C is
summarized in Table 19-1.
A reference to IEC12 can be made which is more specific with
respect to cloud-to-ground lightning strike on a facilitie’s electrical service. It discusses the effect of direct stroke current (practically a rare occurrence on low-voltage incoming service because
the conductors are strung at a much lower level from the ground)
and assumes that 50 percent of the total lightning energy enters
the earth grounding conductors, and the remaining 50 percent is
divided by the numbers of conductors effected. It defines a worst
peak current of 200 kA with a 10 × 350 µs waveform. After 50 percent
of the current enters the grounding system, the remaining current is
divided into two paths (L and N) giving 25 kA per conductor entering a facility (Fig. 19-14). A structure as defined in this standard
can be anything from a high-rise building to an outdoor shelter
containing SCADA or telecommunication equipment. Similar to
ANSI/IEEE, lightning protection zones (LPZ) are introduced, see
Chap. 22 for further discussions.
Example 19-1 We have simulated capacitor switching and resonant circuits in Chaps. 2 and 6, and these clearly show the nature of
the transients. This example shows an EMTP simulation of propagation of transients in a commercial 480-V wiring system. The simplified system configuration is in Fig. 19-15. This shows a 600-kVA,
12.47- to 0.48-kV, three-phase transformer, with multiple grounded
service connection to premises. (Practically, one service transformer
may serve a number of residential/small consumer loads.) Consider
that the service is overhead, 1-m long, 4/0 Penguin (211.6 KCMIL,
6 strand) with a neutral/ground conductor of 115.6 KCMIL
(7 strands, #8). The neutral is multiple grounded at four points,
equal distance from the service transformer.
A lightning stroke of 1.2/50-µs wave and 10-kV peak occurs at
1
/4 of a mile from the service transformer on phase a to ground at
0.02 ms. The three-phase bus serves mixed loads, a 100-hp induction motor, a 208-V load of 150 kVA through a 200-kVA transformer,
Summary of Test Requirements for Location Categories
A
B
C
100-kHz ring wave
All coupling modes except N-G:
A1—low, 2 kV, 0.07 kA
A2—medium, 4kV, 0.13 kA
A3—high, 6kV, 0.2 kA
Effective impedance = 30 Ω in all cases
All coupling modes except N-G:
B1—low, 2 kV, 0.17 kA
B2—medium, 4 kV, 0.33 kA
B3—high, 6 kV, 0.5 kA
Effective impedance = 12 Ω*
No requirement
Combination wave,
1.2/50 µs and
8/20 µs
No provision
All coupling modes except N-G:
B1—low, 2 kV, 1.0 kA
B2—medium, 4 kV, 2.0 kA
B3—high, 6 kV, 3.0 kA
Effective impedance = 2 Ω*
All coupling modes except N-G:
C1—low, 6 kV, 3.0 kA
C2—medium, 10 kV, 5.0 kA
C3—high, 20 kV, 10 kA
Effective impedance = 2 Ω*
5/50-ns bust
Test severity 1, 1 kV
Test severity II, 2 kV
Test severity III, 4 kV
Test severity 1, 1 kV
Test severity II, 2 kV
Test severity III, 4 kV
No provisions
10/1000 µs
Low (residential): none
Medium (commercial)—1.0 Upk,† source Z = 1.0 Ω
High (Industrial)—1.3 Upk,† source Z = 0.25 Ω
As for category A
As for category A
5-kHz ring wave
Low—(far from switched capacitor banks) = none
Medium—1.0 Upk,† Z = 1–5 Ω
High—(near large switched banks)
1.8 Upk,† source impedance = 0.5 to 1 Ω
As for category A
As for category A
*
The effective impedance of surge source, emulated by surge generator is defined as the ratio of peak voltage to peak current, but it is not pure resistance.
Upk to be added to the mains voltage for the phase angle at which the surge is applied.
†
TRANSIENTS AND SURGE PROTECTION IN LOW-VOLTAGE SYSTEMS
FIGURE 19-14
FIGURE 19-15
505
Distribution of direct lightning stroke current, IEC.12
A typical commercial distribution system with incoming utility service connections for EMTP simulation of surges in the wiring system.
a single-phase load, and also a two-phase load of 100 kVA between
phases a and b. Except for the two-phase load all other loads are
switched off.
The voltages at the metering points m1 through m8 are shown
in Fig. 19-16a and b. This shows oscillatory nature of response. The
voltage couples to other phases, and high-frequency superimposed
oscillations can be observed on the input voltage to the 600-kVA
transformer. The neutral-to-ground voltage (m6) shows oscillations
of small magnitude. There is voltage escalation in phase a (m2) at
the service bus for a short duration. If we assume that the dielectric
strength and clearances would limit the voltage at the service bus
to 6 kV, the amplitudes throughout the distribution system would
be reduced.
19-8
SURGE PROTECTION DEVICES
We may define SPDs (surge protection devices) as an assembly of
one or more components intended to limit or divert surges. The
device contains at least one nonlinear component. For applications
to low-voltage systems, we may subdivide SPDs into two distinct
categories:
506
CHAPTER NINETEEN
FIGURES 19-16
1. Secondary surge arresters. Secondary surge arresters are
rarely exposed to direct lightning strikes and are rated
1000 V or less. These meet the category C test requirements
and are, therefore, installed between the transformer and
the service entrance main overcurrent protective device.
It appears that the application of secondary surge arresters directly across the transformer LV terminals can greatly
reduce the possibility of transformer failures. In Fig. 19-6, if
the lightning strikes the primary line, the current is not only
discharged through the primary arrester to the pole-ground
lead, but also through the consumer-load ground. Besides,
Simulated surge patterns.
the surges can couple to the primary side and vice versa,
through the common ground. Some utilities that did not use
secondary surge protection on their transformers are reconsidering this practice. The voltage ratings are 175 and 650 V
for metal-oxide and valve-type arresters. As yet, no MCOV
ratings have been assigned for metal-oxide arresters. Duty
cycle discharge current is 1.5 kA, with 8 × 20-µs impulses
and 22 discharges; high-current short duration test is 10 kA,
4 × 10 µs, and two discharges. The performance characteristics of metal-oxide and valve-type arresters are shown in
Tables 19-2 and 19-3, respectively.
TRANSIENTS AND SURGE PROTECTION IN LOW-VOLTAGE SYSTEMS
TA B L E 1 9 - 2
ARRESTER RATING
(V)
507
Performance Characteristics of Secondary Metal-Oxide Surge Arresters
EQUIVALENT FOW
PROTECTIVE LEVEL (KV)
DISCHARGE VOLTAGE FOR 8 ë 20 lS CURRENT WAVE
AT 1.5 KA (KV)
AT 5 KA (KV)
AT 10 KA (KV)
DISCHARGE CAPABILITY FOR
8 ë 20 lS CURRENT WAVE (KA)
AT 20 KA (KV)
175
1.2
0.78
0.94
1.1
1.4
20
650
5.0
2.2
2.6
2.9
3.5
20
FOW: Front-of-wave.
TA B L E 1 9 - 3
Performance Characteristics of Secondary Valve-Type Surge Arresters
IMPULSE SPARKOVER VOLTAGES
DISCHARGE VOLTAGE FOR
8 ë 20 lS CURRENT WAVE
FRONT OF WAVE
ARRESTER RATING (V)
RATE OF RISE (KV/lS)
SPARKOVER LEVEL (KV)
1.2 ë 50 lS SPARKOVER LEVEL (KV)
AT 5 KA (KV)
AT 10 KA (KV)
175
10
2.5–3.0
2.1–2.5
1.0–1.5
1.4–1.8
650
10
2.9–3.8
2.5–3.5
2.2–3.8
2.9–5.0
■
SPDs must be rated for the short-circuit currents at the
point of application
2. Transient voltage surge suppressors. The term TVSS is unique
to UL 1449 standard.13 TVSS is installed on the load side of
a service entrance and provides protection of the equipment
against transient surge voltages. These are rated 600 V or less
and are required to have category B surge ratings.
■
The SPDs may consist of a combination of individual components; however, it is important to consider ratings as applied
to the power system to be protected.
■
19-8-1
The system grounding is an important consideration; the
NEC limit of 25 Ω grounding resistance is too high for
practical purposes.
Application of SPDs
There are many considerations for the proper application of SPDs.
The effect of lead length becomes important when SPDs are separately mounted, away from the equipment that they protect. UL test
data for integral panel board devices shows that 1ft of #8 stranded
connecting wire adds 165 V. An externally mounted device will
require several feet of connections, adding hundreds of volts to the
suppressor let-through performance. Thus, better surge protection
is achieved by integrating the SPDs within panel boards, switchgear, load centers, that is, within the equipment these SPDs devices
protect. Table 19-4 shows the effect of cable connections versus
surge current and increased system voltage level. We will revert to
the separation distance in Chap. 20, however, the effect on surge
protection is much pronounced in low-voltage systems. Some other
considerations for the application are:
■
Application of SPDs for electronic, data processing, and
communication circuits requires special considerations. The
restrikes, current chopping, and lightning surges originating in
the power systems can be detrimental to these circuits.3,4,14
■
Environmental constraints, that is, ambient temperature,
humidity, and altitude, are a consideration, and an appropriate
enclosure type should be selected.
19-8-2
1. Surge current capability. It is defined as the maximum level
of surge current that an SPD can withstand for a single surge
event. An SPD in a geographical location like Florida will be
highly susceptible to lightning. A high level of surge current
capability is desirable in such areas. Note that C62.416 does
not recommend maximum peak ampere ratings when defining location categories A to C. The manufacturers specify the
peak ampere rating based on the summation of capabilities of
individual suppression components associated with particular
suppression mode.
■
SPDs should have required protection modes at the point of
connection to the power system.
■
SPD should be selected for the appropriate location category
and should have been tested for that category.
■
The lead lengths for connections to the required modes of
suppression should be the shortest possible. Integrated surge
protection devices should be considered.
TA B L E 1 9 - 4
Characteristics of SPDs
Some characteristics of SPDs are:
Effect of Cable Connections on Suppressor Voltage Rating
DESCRIPTION
Suppressor voltage rating (V)
10 ft of open conductor voltage
SURGE CURRENT 3 KA
500
500
500
1650
5-ft twisted and 10-ft total conductor voltage
650
650
500
1500
200
2170
650
5010
1-ft twisted and 2-ft total conductor voltage
Increased system voltage, suppressor voltage plus conductor voltage
SURGE CURRENT 10 KA
1000
700
600
5660
2150
1250
508
CHAPTER NINETEEN
TA B L E 1 9 - 5
UL 1449 Suppression Voltage Rating for TVSS*
L-N
L-G
N-G
L-L
MCOV
120/240 V, single phase
SERVICE VOLTAGE
330
330
330
700
150
208 Y/120 V, three phase, four wire
330
330
330
700
150
700/330
330
330
1200/700
275/150
240/120 V, three phase, high leg delta
480Y/277 V, three phase , four wire
600
600
600
1200
320
600Y/347 V, three phase, four wire
1000
1000
900
1800
420
Note: All values are shown in volts
*Input surge voltage is 1.2 × 50 µs at 6 kV, and current is 8 × 20 µs at 500 to 3000 A. These are high exposure ratings.
■
Service entrance equipment. Surge current capability
100 to 250 kA
■
Downstream distribution. Surge current capability 80 to
150 kA
2. Clamping voltage. It is the measure of the SPD to limit the
voltage a surge suppressor will pass to the load that it protects.
It is the performance measure of a surge arrester to attenuate
a transient. The UL suppression voltage ratings of TVSS are
shown in Table 19-5.
3. Response time. TVSS response time is measured in ns. The
response time of 1 ns is common for TVSS in the industry,
while some manufacturers are claiming response time of even
1 ps. The speed of light is 0.3 mm/ps and electrical signals
through conductors travel at a smaller speed. The measurements of response time in picoseconds are much dependent
upon the test setup.
4. Sparkover voltage. This voltage for the low-voltage systems
is defined as 6 kV. Surge voltage in the low-voltage systems is
limited by the circuit’s dielectric strength. The decrease in the
peak surge current between category C and category A is a
direct correlation of various influencing factors such as circuit
impedance and current capability.
5. Joule ratings or energy delivery capability. An SPD may contain many components, like silicon avalanche diodes (SAD),
metal-oxide varistors (MOVs), and gas tubes. MOVs and SADs
typically fail due to excessive energy, and these components
are rated in terms of joules, which these are capable of handling. The energy absorption will vary with the type of pulse.
The significant parameter is not “the energy contained in the
surge,” but the actual energy that can be deposited in a surgeabsorbing device.15 In a purely resistive load, the surge energy
can be expressed as V 2 /R, however, for a nonlinear surge
protection device this relation is not so simple. Thus, the
energy-delivery capability of a surge is difficult to calculate when
surge is diverted or shunted by a nonlinear device. A surge of
high amplitude and short duration has the potential of upsetting
the equipment operation but has little energy. A surge of high
amplitude and long duration has the potential of high energy
deposition.6 It appears that the maximum surge current and
clamping voltage seem to be reliable parameters for comparison
between the SPDs performance, rather than the joules.
In Chap. 20, the energy-handling capability of the surge arresters applied at medium and high voltages is an important parameter
of selection of the arrester. However, the arrester resistance and the
surge voltage at the application of the surge arrester are calculated
using the published data of the arrester for the switching surge test
wave shapes. For SPDs at low voltage, there is no such test standard
for specifying the switching surge tests, Some attempts have been
made to specify in terms of specific energy as ∫ (V 2 /R )dt, where R is
arbitrarily taken as 50 Ω. However, varistor impedance is not constant
and varies with the current and voltage in a nonlinear manner, and
the energy deposited in the varistor varies with the source impedance,
amplitude, and waveform.15
It is important that SPDs are capable of suppressing shortduration surges resembling and including that of lightning activity;
it is also equally important that SPDs suppress long-duration surges.
Suppressors intended to protect branch panels or outlets will be
required to suppress long-duration surges more frequently than the
surges induced by lightning activity.
19-9
SPD COMPONENTS
The component surge protection devices may be defined as a discrete SPD involving a specific technology and installed as a component within a surge protector, for example gas tubes, MOVs, and
avalanche junction semiconductor devices. Rarely, are these used in
isolation as examined below.
SPDs can be categorized as voltage-limiting type and voltageswitching type. The voltage-limiting types have high impedance when
no surge is present and limit voltage progressively and smoothly by
reducing its impedance. On the other hand, a voltage-switching
device (“crowbar”) can have a sudden voltage collapse to a low
impedance state, that is, air gaps and gas tubes. These create short
circuit in the system in response to a surge. The power-flow current
is a concern, and the surge energy has to be dissipated elsewhere
in the circuit. These do not provide an interruption-free service,
unless used in conjunction with other components to avoid short
circuit being applied to the line. The published impulse breakdown
voltage is defined for specific rate of voltage rise.
The component varistors and avalanche junction semiconductors are voltage-limiting SPDs that behave like nonlinear impedances, and no short circuit occurs when responding to a surge.
These are available in a variety of rated parameter values. A comparison of the parameters is shown in Table 19-6.
19-9-1
Gas Tubes
Gas tubes are cold cathode discharge tubes. There are two, sometimes
three, electrodes sealed inside an enclosure that is filled with gas.
As the gap is subjected to increasing field intensity due to a voltage
surge, it breaks down at some voltage determined by the rate of rise
of the surge and the design of the gas tube. The dc breakdown potential for a certain gas or gas mixture follows Paschen’s law (Chap. 17).
The line is, therefore, crowbarred or shorted until the voltage across
the tube drops below its extinguishing level. One common method
to interrupt the follow-current is to install a fuse ahead of the gas tube.
TRANSIENTS AND SURGE PROTECTION IN LOW-VOLTAGE SYSTEMS
TA B L E 1 9 - 6
RATED DEVICE PARAMETER
DC breakdown voltage
Nominal varistor voltage, Vn
Breakdown voltage, VBR
Comparison of Different Device Parameters for SPDs
GAS TUBES/AIR GAPS
MOVS
AVALANCHE JUNCTION SEMICONDUCTORS
75 to >1200 V
3.5 to >1200 V
3 to > 850 V
Capacitance
0.5–5 pF
Maximum single-impulse discharge current
5000–100000 A (8/20)
10–2000 A (10/1000)
3–30000 pF
5–10000 pF
8–80000 A (8/20)
Rated single-pulse transient current, Itm
Rated peak impulse current, IPPM
Impulse breakdown voltage
Clamping voltage
509
2.5–40 A (10/1000)
250 to > 1500 V (100 V/µs)
17–4000 V (8/20)
Rated RMS voltage, Vm
Rated stand-off voltage, Vwm
3–1500 V
DC standby current, Id
Insulation resistance
0.5–200 µA
7–540 V (10/1000)
3–700 V
0.01–1000 µA
1–10 GΩ
Another method is to use a varistor in series with a spark gap. A finite
time is needed to start the electron avalanche action and breakdown;
therefore, the gas tubes are slow to operate. Also the faster the rate of
rise, the higher the overvoltage required to operate the tube. Damage
to the protected equipment can occur on fast rising surges.
Telephone companies, usually, install a gas tube across the telephone wiring at the point of entry to a home or commercial facility.
Communication interfaces RS-422 and signal circuits are similarly
protected. The grounding and mounting is governed by provisions
of NEC2 or ANSI C2.1
FIGURE 19-17
The three-electrode tube provides both normal- and commonmode protection in a single device. The two outer electrodes are
connected to the signal lines being protected, and the center electrode is connected to the ground (Fig. 19-17a and b).
19-9-2
Metal Oxide Varistors
Figure 19-18 shows the volt-ampere characteristics of a metal-oxide
varistor, a contraction of variable resistor. This shows three regions:
(1) leakage region, (2) normal varistor operation, (3) upturn region.
(a) A three-electrode gas tube. (b) Operating characteristics of the gas tube.
510
CHAPTER NINETEEN
FIGURE 19-18
The metal-oxide particles are compressed under very high pressure
to form various size discs, electrical leads are bonded to the discs,
and the finished component is covered with an insulating material.
The conduction mechanism of MOVs results from semiconductor
junctions at the boundary of zinc-oxide grains formed during sintering process. A varistor may be considered a multijunction device
with many grains in series parallel combination. The equivalent
circuit model is shown in Fig. 19-19. When exposed to surges, large
amount of currents are conducted, and there will be energy deposited in the varistor during its surge diversion function. At low levels
of current, ROFF, which is of high value, is the prevailing component.
In the conduction region, resistor Rx takes progressively decreasing values. At large currents in the upturn region, RON becomes
a significant part of the total device resistance, causing an upturn
with value of RON as asymptote. Parallel capacitor can pass a current
V-I characteristics of a MOV.
which may be higher than the dc leakage current. Lead reactance
significantly affects the behavior of the varistor. Considerations are
applied in the thermal design of an application, considering ambient temperature and temperature rise when passing a surge.
Clamping voltage has been defined previously. The maximum
surge current Itm is the current 8/20-µs waveshape, which a varistor
is rated to withstand for a single surge. Rated rms voltage is the maximum voltage that can be applied continuously. The dc standby current
is the current conducted by the varistor from a power source. The selfheating of the varistor should not be significant compared to its rated
transient average power dissipation. Rated recurrent peak voltage is
the maximum designated value of a repetitive nonsinusoidal power
source of specified wave shape that can be applied continuously
between terminals of the device. The nonlinear exponent a shown
in Fig. 19-18 is the measure of varistor nonlinearity according to
I = kV α
(19-11)
where k is a device constant.
FIGURE 19-19
Equivalent circuit of a MOV.
The voltage overshoot shown in Fig. 19-20 occurs due to lead
inductance. The following definitions are applicable: Vc is the clamp
voltage for 8/20-µs wave, V2 is equal to (V1 +V2)/2, Vos = V1 – Vc is
the voltage overshoot, t2 – tc is the overshoot duration, tc is the time
for the device to reach its clamp voltage, t2 is the time for device to
decay to 50 percent of its overshoot voltage, t1 is the time for device
to reach its peak value, and t1 – tc is the response time.
Measurements of the clamping voltage across a lead-mounted
varistor can indicate values exceeding levels observed with standard
8 × 20 µs waveform. This higher voltage is referred as voltage
overshoot, Vos. For fast response solid-state devices, the voltage
overshoot, response time, and overshoot duration are the phenomena
primarily caused by the lead inductance.
A procedure for evaluating the cumulative effect of surges on
varistors has been devised.16 The method constructs a model of the
surge environment and derives a set of surges of specific magnitude. This enables calculation of an annual rate of consumption of
the rated pulse life of varistors, which can then be selected so that
TRANSIENTS AND SURGE PROTECTION IN LOW-VOLTAGE SYSTEMS
FIGURE 19-20
To illustrate voltage overshoot, response time, and voltage overshoot duration of a MOV.
the rated life will not be consumed within some the time duration,
chosen as the design goal.
The response time of a leadless MOV can be less than 0.5 ns.
Practically, with attached leads it is much higher. Figure 19-21
shows the derating curves for 40-mm diameter MOVs. The numbers
FIGURE 19-21
reserved.
511
across the curve can be taken as the relative value of the varistor
in service for the specified surge environment. A MOV subjected
to low-duration, low-current surges can last for a very long time,
while it can fail quickly if subjected to high-current, long-duration
surges.
Derating curves of 40-mm diameter MOVs. Reproduced with permission from Phoenix Contact (www. phoenixcontact.com). All rights
512
CHAPTER NINETEEN
NEC2 requires category 3 or category 5 cables for modern data
circuits. The specifications for these cables call for a very low capacitance because adding capacitance to the data signal can attenuate
the normal data flow. Installing parallel MOVs on a data circuit has
the same parasitic capacitance effects. Combined with the inductance
of the cables, a low-pass filter is created that result in considerable
signal attenuation in circuits with frequencies above 30 kHz. Therefore, MOVs are not well suited for high-frequency applications.
To summarize the advantages and disadvantages, MOVs can
handle relatively large current levels, very specific turn-on time, a
wide range of protection levels, but the performance decays with
time, as the crystalline structure is etched away every time a surge
passes through it. Also, they are not suitable for high-frequency
applications.
19-9-3
Avalanche Junction Semiconductors
Silicon avalanche diodes (SADs) are two-terminal devices having
symmetrical or asymmetrical characteristics, and their series and
parallel combinations are used to enhance the voltage and powerhandling capability. Figure 19-22 shows avalanche diode V-I
characteristics for a P-N junction.
Clamping voltage Vc is the crest (peak) voltage across the device,
assuming that external leads do not adversely add to this voltage.
A waveform of 10/1000 µs is used as the standard test current
impulse. The clamping voltage varies as a function of the applied
peak impulse current. Rated peak impulse current IPPM is the maximum value of peak impulse current for a minimum of 10 pulses,
using 10/1000-µs waveform and maximum duty cycle of 0.01 percent
without causing device failure. Rated stand-off or working rms
voltage VWM is assigned by the manufacturers, and is the maximum continuous operating voltage of the avalanche diode that is
determined by multiplying the minimum breakdown voltage by 0.9
or 0.95. These voltage ratings are considered the maximum circuit,
system, or line voltage when operating on device full temperature
range. Rated peak surge current IPP is the same as defined for MOVs.
The breakdown voltage VBR is measured at 1 mA, which may be stated
as a minimum or nominal value and is a characteristic of the avalanche
point for a P-N junction. In Fig. 19-22, VFS is the forward voltage and
IFS is the forward current; IFSM is the maximum forward current.
Silicon avalanche suppressor diodes were developed to protect
sensitive electronics in aerospace industry. They exhibit a response
time of less than 5 ns and limit transients to a low voltage level,
FIGURE 19-22
Bipolar characteristics of a SAD.
typically less than 300 V (for a 120-V ac system). These have small
leakage current. The disadvantages are low energy-handling capability and capacitance concerns for high-frequency applications.
Diodes used in the reverse breakdown region are called zener
diodes. Strictly only devices of breakdown voltage less than 5 V use
zener mechanism, and it is not a bipolar device. SADs for transient
voltage suppression are manufactured as bipolar devices. The zener
diode is designed primarily for voltage regulation and is slower to
respond than SADs.
19-9-4
Failure Modes of SPD Components
Gas tube arresters may fail because of mechanical shock, corrosion, hermetic seal failure, or operation on excessive large surges.
They may or may not interfere with the system operation. Failure
due to short circuits, low breakdown voltage, and low insulation
resistance can be detected by the user of the protected equipment
and are preferable where protection of property, people, or terminal equipment is of importance. The high breakdown failure mode
is not normally noticeable, and may be used where uninterrupted
system operation is more important.
MOVs can fail in the short-circuit mode with violent rupture
and shattering of the material, which may pose a danger of the flying
debris. This can be mitigated by use of overcurrent protection devices,
generally, current-limiting fuses, which can isolate the faulty MOV or the
entire circuit depending upon the location, as shown in Figure 19-23a
and b. The varistor can have suitable packaging to contain overheating and shattering. Encapsulation may not be the answer to
this problem. Initially, the encapsulating material acts as a barrier
to expansion, but it has limited effectiveness in terms of confining
explosion and may increase the magnitude and violence of an event.
On the other hand, nonencapsulated devices will fail in a graceful,
noneventful manner. The MOVs exhibit thermal runaway when the
limiting voltage is set too close to the peak of the sine wave. Higher
leakage current passing through the device leads to overheating.
An avalanche diode can fail due to short circuit, which has two
modes. In a shorted junction, the surface or bulk material has failed,
evidenced by melting of silicon material. The second failure mode
is melting of internal materials due to arc across semiconductor
material caused by a long-duration surge. The device can fail in
open-circuit mode when breakdown voltage exceeds 150 percent
of the pretested value at a value used to obtain VBR or lower current.
A device is considered a failure when the clamping voltage exceeds
120 percent of the pretested voltage.
MOVs have some disadvantages with respect to silicon avalanche diodes. A MOV cannot maintain a stable protection level
VPL as the current conducted increases (Fig. 19-18). A MOV
may be considered failed if its initial VPL has shifted by more than
± 10 percent from the original value. Degradation with use is another
consideration. With repeated conduction paths, the zinc-oxide
particles do not perform consistently. There is evidence that once
the degradation starts, it will continue in that direction. A comparison of the characteristics of single-SPD devices is shown in
Table 19-7. This shows that all the desirable features cannot be
obtained with one technology.
19-10
CONNECTION OF SPD DEVICES
19-10-1
Single-stage Parallel Connection
This connection is shown in Fig. 19-24 and is the most popular. The
devices may consist of high-energy, tight-clamping, and fast-response
characteristics. This configuration has two limitations, namely, the
clamping level is a function of transient rise time, and the lead length
is a consideration when installing parallel units. The limitation occurs
because of use of one protective component, which may have high
surge capability, but slow response, that is, gas tubes.
TRANSIENTS AND SURGE PROTECTION IN LOW-VOLTAGE SYSTEMS
FIGURE 19-23
Alternative methods of protection of MOVs through current-limiting fuses.
TA B L E 1 9 - 7
TYPE OF SPD
Characteristics of SPDs
RESPONSE TIME < 5 ns SURGE CURRENT CAPABILITY HIGH-ENERGY CAPABILITY SAFE CLAMP VOLTAGE
LONG LIFE
CONNECTION METHOD
Gas tube
No
High
High
No
Yes
Only L-G
MOV
Yes
Medium
Medium
Yes
Limitations*
L-L, L-N, L-G**
L-L, L-N, L-G**
L-L, L-N
Avalanche diode
Yes
Low
Low
Yes
*
Selenium rectifiers
No
Medium
Medium
No
Medium
Note: Service interruption occurs with gas tubes.
*
May fail explosively under category C surge conditions.
**
For L-G connection, life expectancy will be short.
FIGURE 19-24
Shunt connections of a single SPD.
513
514
CHAPTER NINETEEN
FIGURE 19-25
Multistage parallel connection of SPDs.
19-10-2 Multistage Parallel Connections
19-10-4
Parallel protectors can be improved by adding more stages of the
different types of protective components. This enhances reliability
and response for both common-mode and normal-mode protection. The primary surge suppression component provides a path
for the surge current, while the secondary surge suppression component provides tight clamping (Fig. 19-25).
Figure 19-28 shows a lattice circuit using SADs. The first stage
responds in 5 ns, and if the transient is of high magnitude, the first
stage triggers the second stage to provide additional dissipation
capability. The SCR2 acts merely as a switch to trigger the stage
on. The clamping voltage V2 is lower than V1. When the first stage
is turned off, the equipment downstream is protected at a lower
clamp voltage of V2.
19-10-3
Lattice Circuit
Series Hybrid Design
A series inductor or control element provides protection by delaying the rapidly rising waveform and protecting the secondary
components. The series element with parallel capacitance attenuates electrical noise. The primary surge component is connected in
common mode and diverts a larger amount of energy, simultaneously protecting the secondary surge components which may be
MOVs or avalanche diodes. These components are usually installed
line-to-neutral or line-to-line. These respond within 5 ns. Unlike
parallel units, series hybrid systems maintain uniform lead-length
distances between protection modules and phase conductors.
Figure 19-26 shows a three-stage protection solution and corresponding attenuation of the voltage surge. Each component shares
in the overall reduction of the transient and is applied within its
surge-handling capability. Some problems identified with series
hybrid circuits are:
■
19-10-5
Snubber Circuits
A sudden reverse voltage is applied to semiconductors in many
applications after it has been turned off. With high inductive loads
it can be a problem, and the high dv/dt may turn on the device or
even result in its failure. A snubber circuit consists of a capacitor
and resistor in series which is connected across the semiconducting
device. Consider that a SCR is connected to a source impedance of
Rs and Ls. Let R and C be the values of resistance and capacitance in
the snubber circuit that need to be determined. When the circuit
is energized and assuming that the capacitor is initially uncharged,
the maximum dv/dt across SCR is:
dv ER
=
dt L s
(19-12)
R + R s = 2 Ls /C
In case of bidirectional transients, the power dissipation
through primary and secondary devices is of consideration.
The circuit is designed for transients from source to load side.
The minimum capacitance required is given by the expression:
■
C=
In case of harmonics and load regulation, there is load-dependent
voltage drop across the inductor. Possibility of resonances with
inductor and capacitances exist.
Figure 19-27 shows a circuit accommodating filters for higherfrequency noise attenuation. Digital equipment radiates energy
back into the power system. Any device containing any digital
clock frequencies or pulses above 10 kHz must be registered and
approved by FCC specifications. This limits the radiation from a
single device. However, in a single facility, hundreds of such devices
may contribute to sum up the noise in major pulses, which can
cause system errors. Strategic installations of power-conditioning
equipment with high-frequency filtering can obviate this crossreference hazard. The filtering must be capable of broad range filtering,
for example, from 100 kHz to 100 MHz.
1 0 . 564 Em
2 L s dv /dt
2
(19-13)
where Em is the rms applied voltage to the circuit and dv/dt is the
maximum safe tolerable value for the SCR. The resistance can be
calculated from:
R = 2σ L s /C
(19-14)
where s, the damping factor, may be taken approximately as 0.65.
Table 3-1 in Ref. 3 defines surge parameters affecting equipment
failure modes. For example, for semiconductors, peak amplitude,
maximum rate of rise, and I2t (energy let through) in the devices are
surge parameters of concern. In addition, for triacs, source impedance is of concern.
TRANSIENTS AND SURGE PROTECTION IN LOW-VOLTAGE SYSTEMS
F I G U R E 1 9 - 2 6 Three-stage surge protection with coupling inductors. Reproduced with permission from Phoenix Contact (www. phoenixcontact.
com). All rights reserved.
FIGURE 19-27
A hybrid connection of SPDs with filters.
515
516
CHAPTER NINETEEN
FIGURE 19-28
19-11
A lattice circuit for surge protection using SADs.
POWER QUALITY PROBLEMS
Transients and noise are two important concerns of power quality.
Voltage sag is reduction of nominal system voltage for more than
0.01s and less than 2.5 s. A swell is increase in the nominal voltage over the same time limits. Low and high voltages are increases
or decreases in voltages for more than 2.5 s. There can be outright interruptions, frequency variations, transients caused by load
interruption, and harmonic pollution, as shown in Fig. 19-29. Frequency variations are more of a concern for engine-generator-based
distribution systems. Voltage waveform distortions (harmonics)
occur due to nonlinear loads and dissymmetry, that is, unbalanced
loads cause voltage unbalance. Power quality problems cost the
U.S. industry some billions of dollars per year, though these can be
effectively mitigated in a system with proper designs and selection
of equipment
The nonlinear loads are increasing at a fast rate, and the power
quality problems in the distribution systems are compounding.
The nonlinear loads degrade the power quality, and these loads are
much sensitive to the pollution they produce. We discussed these
in Chap. 16. Here, another example of switch mode power supplies (SMPs) can be stated, which creates severe line pollution. The
switch-mode power supplies have replaced the conventional power
supplies for computers, copiers, TV sets, and other household
appliances. These have some advantages, for example, greater tolerance to rms voltage fluctuations, fundamental frequency variations,
smaller compact size, greater efficiency, and lower manufacturing
costs, yet these create new power quality problems.
Figure 19-30a and b show conventional- and switch-mode power
supply systems, respectively. The conventional power supply has a
main input transformer, a full-wave bridge rectifier, and the main
ripple frequency is at 120 Hz. The current drawn from the supply
system is relatively linear; capacitors C1 and C2 and inductor act as
a passive filter. In SMP, the incoming voltage is rectified at line voltage
and high dc voltage is stored in capacitor C1. The switcher and controls
switch dc from C1 at high rate (10 to 100 kHz). These high-frequency
pulses are stepped-down in a transformer and rectified. The switcher
eliminates series regulator and losses in conventional supplies, and
the end product is more efficient with lighter components. Four
common configurations used with the SMPs are: flyback, pushpull, half bridge, and full bridge.
The current drawn from the supply system is discontinuous and
flows in pulses (Fig. 19-31). This current spectrum has high harmonic
content. The third harmonic is 81.0 percent, fifth harmonic is
60.6 percent, and seventh is 37 percent. There are considerable
percentages of higher harmonics. In a three-phase, four-wire system,
if the loads are not fairly balanced, the neutral can be overloaded with
third harmonics and a neutral conductor size equal to phase conductors
may be necessary.2 Third harmonic traps and filters can be provided.
Harmonic filters, active or passive, are the most effective in mitigating
the harmonic problems (Chap. 6).
Switch-mode power supplies produce 180- to 100-kHz impulses
through the rectification process. Due to lack of main input transformer mass and greater internal capacitive coupling, SMPs have
much greater susceptibility to transient surge voltages. The fast-rise,
high-frequency transients enter the SMPs through the low-impedance
paths and are dissipated within the SMPs or logic circuits and hardware. A failure can occur.
Figure 19-29 shows the interaction of various technologies
and their effectiveness for a particular power supply problem. It
is not the intention to discuss the various mitigation technologies
shown in Fig. 19-29. Let us consider, as an example, uninterruptible
power supply (UPS) systems.5 A conceptual circuit is shown in Fig.
19-32a. The ac power is rectified, a battery system floated on the
dc output, and the dc voltage is reconverted to ac. A static bypass
switch can reduce the mean time between failures (MTBF) and
switches over the load to another standby ac source in case of a
component failure in the main rectifier-battery-inverter lineup. The
static switch transfers fast, practically, in-phase transfer, with little
voltage drop on transfer. In Fig.19-32b, the interruption in the voltage is hardly noticeable. Two lineups of rectifiers, battery systems,
and inverters can be connected in redundant or load-sharing mode,
again with a bypass, depending upon the required service reliability
of the load.
TRANSIENTS AND SURGE PROTECTION IN LOW-VOLTAGE SYSTEMS
FIGURE 19-29
517
Power quality conditions and conditioning technologies to overcome power quality problems.
The first step in identifying the power quality problems and
their impact on the processes is to distinguish which operating
characteristics of the concerned equipment is likely to cause an
equipment malfunction or shutdown. Methods of characterizing
rms disturbances for calculations of performance indices have been
developed. An important parameter is low-voltage sag and its time
duration. A recommended method of summarizing expected voltage
sag is shown in Fig. 19-33, which presents performance as constant
supply sag contours, similar to a topographical contour map. This
can be directly compared with the equipment sensitivity. The problem
lies in forming the voltage contour map at a location. The equipment
sensitivity is sometimes specified by the manufacturers.
19-12
SURGE PROTECTION OF COMPUTERS
With respect to protection of computers and electronics, over the
course of years, the component density on an IC has increased (it is
now possible to accommodate more than couple of million transistors on a chip the size of a postage stamp). This has increased the
vulnerability to transients. The memory circuit of a chip can be
upset with as little as 10–9 J of energy (Fig. 19-34), and the chip
can be destroyed by 10–5 J. The higher energy enters through
(1) customers ac/dc power supply systems and (2) data lines. Both
must have surge protection. It is estimated that 88.5 percent of
power-line disturbances are of transient type:
518
CHAPTER NINETEEN
FIGURE 19-30
(a) A conventional power supply, no longer in use. (b) Switch-mode power supply circuit diagram.
Damage. There can be immediate component damage. If the
transient is of large magnitude/time duration, a burnout can
occur.
Erosion—long-term failure. The effect may not become
apparent for sometime, but the component erodes and
degrades, which may result in failure in days or weeks.
19-12-1
Causes of Semiconductor Failure
The causes of semiconductor failure are:
F I G U R E 1 9 - 3 1 Discontinuous line-current input demanded by a
SMP, containing high percentage of harmonics.
■
Oscillatory decaying transients: 49 percent
■
Voltage impulse transients: 39.5 percent
■
Undervoltage and overvoltages: 11.0 percent
■
Voltage outages: 0.5 percent
■
Total is 100 percent
A voltage transient creates the following types of stresses on
sensitive electronic equipment:
Upset errors. There can be a data error or an altered memory.
This upset is caused by a low-level transient of voltage
amplitude sufficiently intense to cause a component to
change state.
1. Overstress due to transients, lightning, and electrostatic
discharge (ESD).17 ESD phenomena generate electromagnetic
fields from dc to low gigahertz. The ESD event includes not
only the discharge current, but also the electromagnetic fields
and corona effects before and during discharge. Sudden transfer of charge between bodies of differing electrostatic potentials
occurs. Electrostatic induction is defined as a means by which
portions of humans (hands, fingers, or hips) or other items
can become differentially charged. Physical charge transfer
occurs when charged particles are physically transferred to
an object that is itself not creating the charge. Most common
methods of charging is the act of walking. The human body
in the process of walking builds up electrical charge with
respect to its surroundings. Walking on a floor with foot
wear of an insulating material leads to charge buildup on
the underside of shoe sole by triboelectrification (involves
electron or ion transfer upon contact due to frictional localized
heating of microscopic contact areas on solid surfaces). A
transient voltage of 35 kV can occur to microprocessor-based
equipment from a simple walk across a synthetic carpet
(Table 19-8). (It is common experience that on a dry winter
day, one can get a mild shock by touching the metal door
knob of a door or see blue sparks on friction of nylon
garments in the dark.) The voltage levels caused by ESD can
TRANSIENTS AND SURGE PROTECTION IN LOW-VOLTAGE SYSTEMS
FIGURE 19-32
FIGURE 19-33
519
(a) Circuit diagram of an UPS system. (b) Critical load transfer waveforms through a static switch.
Topographical concepts applied to voltage sags and equipment susceptibility to ride through voltage sags.
be quite high. This type of overstresses account for 65 percent
of the failures.
3. Five percent of the failures occur due to defects in the manufacturing, usually within 39 days of operation.
2. Thirty percent of the failures occur because of environmental
conditions, that is, high temperature, high moisture, and high
humidity.
This shows that transients and ESD account for the bulk of the
failures.
520
CHAPTER NINETEEN
FIGURE 19-34
TA B L E 1 9 - 8
Upset and damage energy levels of digital ICs.
Typical Generated Static Voltages
STATIC VOLTAGE DEVELOPED (KV)
NO.
19-13
EVENT
HIGH HUMIDITY (80%)
1
Walking across synthetic carpet
35
1.5
2
Handling polyethylene bag
20
0.6
3
Sitting on foam cushion
18
1.5
4
Sliding plastic box on carpet
18
1.5
5
Heat shrinkable film on PC board
16
3
6
Pulling Mylar tape from PC board
12
1.5
7
Walking across vinyl floor
12
0.25
POWER QUALITY FOR COMPUTERS
Table 19-9 shows typical range of power quality and load parameters of a major computer manufacturer.5 Computer manufacturers
specify maximum momentary voltage deviations for their equipment to operate without errors and without sustaining damage.
Transient conditions are specified in terms of amplitude and time.
Some manufacturers may specify total loss of power from 1 ms to
1 cycle. A figure of 8.3 ms was common for the older equipment.
Impulse tolerances are of much shorter duration.
19-13-1
LOW HUMIDITY (20%)
CBEMA Curves
Figure 19-35a shows an envelope of voltage tolerances that was
put forward by Computer and Business Equipment Manufacturer’s
Association (CBEMA) working group and included in IEEE
standard. 5 This has been superseded with a new curve in
Fig. 19-35b in 2000 and is called, “New Information Technology
Industry Council (ITI, formerly, CBEMA) curve (2000).” It attempts
to define everything from specification criteria for electronic equipment to the basis of power quality performance contracts between
electrical utilities and large industrial consumers. Yet it is a partial
picture of the immunity limits in modern office electronic equipment.
CBEMA curve does not address noise immunity. This criterion
is addressed as energy delivery criterion. The operation of data
links, which should operate successfully without noise-related
interference, is a data-transfer criterion. Also reference grounds
should operate at equal potentials and free of transient voltage
shifts, as discussed in Sec. 19-3.
Another industry standard that defines voltage sag ride-through
capability for semiconductor processing, and automated test
equipment is SEMI F47-0200-2000 (Semiconductor Equipment
and Materials International, Inc.).18 The tolerable limits defined
in this curve are: 50 percent of nominal voltage for a time period
of 0.05 to ≤ 0.2 s; 70 percent for 0.2 to ≤ 0.5 s; and 80 percent for
0.5 to ≤ 1.0 s.
19-14
TYPICAL APPLICATION OF SPDs
Figure 19-36 shows application of SPDs in a typical distribution
system. The characteristics and selection of the SPD at each location
follows the guidelines discussed above.
TRANSIENTS AND SURGE PROTECTION IN LOW-VOLTAGE SYSTEMS
TA B L E 1 9 - 9
Typical Range of Input Power Quality and Load
Parameters of a Major Computer Manufacturer
PARAMETER
RANGE
*
Voltage limit, steady-state all phases
Voltage disturbances, all phases
*
Harmonic content†
+6%, –13%
Surge +15% for 0.5 s maximum
Sag –18% for 0.5 s maximum
Transient voltage 150-200% for 0.2 ms
5% maximum with equipment operating
Electromagnetic compatibility
†
1 V/m maximum
60 Hz ± 0.5
Frequency limits*
Frequency rate of change*
1 Hz/s (slew rate)
†
Three-phase voltage unbalance
‡
2.5% of arithmetic average
Three-phase load unbalance
5-20% maximum for any one phase
Power factor‡
0.8-0.9
Load demand
‡
0.75-0.85
*
These parameters depend on power source.
These parameters are a function of interaction of the source and the equipment load.
‡
These parameters are a function of the equipment. The harmonic content of the voltage is computed as the
sum of all harmonic voltages added vectorially.
†
FIGURE 19-35
(a) CBEMA curve (old), now superseded by (b) new ITI (CBEMA) curve.
521
522
CHAPTER NINETEEN
FIGURE 19-35
FIGURE 19-36
(Continued )
Typical applications of SPDs in a distribution system.
TRANSIENTS AND SURGE PROTECTION IN LOW-VOLTAGE SYSTEMS
PROBLEMS
523
19. What is the major cause of failure of semiconductors?
1. Distinguish between electrical noise and transients. Draw a
freehand sketch illustrating the two.
20. Write the category classification (A, B, or C) on each of the
surge protective devices shown in Fig. 19-36.
2. Describe normal mode and common mode of surge protection for a three-phase, four-wire, low-voltage system.
21. Based on this chapter and a manufacturer’s catalogue,
write down specifications of all SPDs shown in Fig. 19-36.
3. The multiple-grounding systems of utility services to commercial and residential buildings give rise to differential voltages
between neutral and ground. What are the relative advantages
and disadvantages? Why is this not applied to industrial and
HV systems? Comment on the statement: “A person taking a
shower in his home gets an electrical shock.” Can it be true?
22. A ring test wave is specified in the standards. What type of
switching surge can produce a ring wave in a low-voltage system?
4. How are the lightning surges coupled to low-voltage systems?
5. Explain why standards specify that the maximum lightning
surge voltage will get limited to 6 kV in locations of medium
exposures.
6. Compare ANSI/IEEE location categories with IEC. What are
the major conceptual differences?
7. Recommend a SPD specification for application in category C
location, without any rigorous study.
8. Distinguish between transient voltage surge suppressors
(TVSS), surge protection devices (SPDs), and SSAs (secondary
surge arresters). Can a TVSS device be used in category C location?
9. Write eight considerations that are applicable when selecting a SPD for the low-voltage systems.
10. Write a note on the controversy surrounding surge-current
capability versus energy-handling capability of a TVSS device.
How can data on surge-handling energy capability be misleading?
11. What are the UL limits of clamp voltages for 120-V, 240-V,
and 480-V, low-voltage systems?
12. What are major differences between gas tube, MOV, and
selenium rectifiers with respect to speed of response to a surge?
Which of these devices has the highest life?
13. MOVs have been shattered on handling surges in some
installations. What are the common remedial measures to
mitigate this problem?
14. Compare varistors with selenium rectifiers. Write a note
on the failure mode of these two devices.
15. Describe the effect of lead length on the operation of an
MOV. An MOV is connected with a lead length of 10 ft. By
what percentage will its clamp voltage change?
16. The overshoot of voltage in a varistor occurs because of
(1) high surge voltage, (2) varistor characteristics,(3) rate of
rise of surge voltage, (4) lead length, (5) all of these. Which is
correct?
17. Give reasons why multistage parallel designs of TVSS are
necessary. What is the limitation of a single-stage shunt device?
What are some objections to the use of series devices in multistage parallel arrangements?
18. A 120-V, single-phase ac power supply has a voltage swell
of 10 percent for 3 s for a computer application. Is it acceptable?
What is the maximum time duration for safe tolerance of the
overvoltage, keeping the same magnitude?
23. Design a snubber circuit for an SCR; its maximum dv/dt =
100 V/µs, source inductance = 0.2 mH, applied voltage =
480 V rms.
24. In Example 19-1 (Fig. 19-15), single-phase loads and
loads served by 200 kVA are shown disconnected in the simulation results obtained in Fig. 19-16a and b. What will be
the effect of connecting these loads in service on the nature
of transients? Will the amplitudes and decay rate increase or
decrease? Consider that the 100-hp motor in Fig. 19-15 is
operating at steady state when the system is impacted with the
surge. What can be expected in the current, terminal voltage,
direct axis, and quadrature axis transients of the motor?
REFERENCES
1. ANSI C2, Electric Safety Code, 2002.
2. NFPA70, National Electric Code, 2008.
3. IEEE Std. 1100, IEEE Recommended Practice for Powering and
Grounding Electronic Equipment (Emerald Book), 1999.
4. IEEE Std. 518, IEEE Guide for Installation of Electrical Equipment
to Minimize Noise Inputs to Controllers from External Sources,
1982.
5. IEEE Std. 446, IEEE Recommended Practice for Emergency
and Standby Power Systems for Industrial and Commercial
Applications, 1995.
6. ANSI/IEEE Std. C62.41, IEEE Recommended Practice on Surge
Voltages in Low Voltage AC Power Circuits, 1991.
7. F. D. Martzloff, “Coupling, Propagation and Side Effects of
Surges in an Industrial Building Wiring System,” IEEE Trans.,
IA-26, no. 2, pp. 193–203, Mar./Apr. 1990.
8. IEC 62305-1, Protection Against Lightning, Part-1, General
Principles, 2010.
9. IEEE Std. C37.90.1, Surge Withstand Capability (SWC) Tests
for Protection Relays and Relay Systems, 1989.
10. P. Chowdhri, “Estimation of Flashover Rates of Overhead Power
Distribution Lines by Lightning Strokes to Nearby Ground,”
IEEE Trans., PWRD-4, no. 3, pp. 1982–1987, Jul. 1989.
11. IEEE Std. C62.41.1, IEEE Guide on Surge Environment in
Low-Voltage (1000 V or Less) AC Power Circuits, 2002.
12. IEC 62305-4, Protection Against Lightning, Part 4, Failure of
Electrical and Electronic Systems Within Structures, 2006.
(This is a Revision of Earlier IEC 61312-1, Protection Against
LEMP, 1995, Now Withdrawn).
13. UL 1449, 2nd ed., Standard for Transient Voltage Surge
Suppressors, July 1987.
14. IEEE Std. C62.36, IEEE Standard Test Methods for Surge
Protectors Used in Low Voltage Data, Communication, and
Signaling Circuits, 1994.
524
CHAPTER NINETEEN
15. T. Key, A. Mansoor and F. Martzloff, “No Joules for Surges:
Relevant and Realistic Assessment of Surge Stress Threats,”
International Conference on Harmonics and Quality of Power,
Las Vegas, Sep. 1996.
16. F. D. Martzloff, “Matching Surge Protective Devices to Their
Environment,” IEEE Trans. IA, vol. IA-21, no. 1, Jan. /Feb. 1985.
17. IEEE Std. C62.47, IEEE Guide on Electrostatic Discharge:
Characteristics of the ESD Environment, 1997. (This standard
was archived in 2003).
18. SEMI F47-0200, Specifications for Semiconductor Processing
Equipment Voltage Sag Immunity, 2000.
FURTHER READING
ANSI/IEEE Std. C62.11, IEEE Standard for Metal Oxide Surge
Arresters for AC Power Circuits (> 1 kV), 1999.
IEC 60664, Insulation Coordination for Equipment Within Low
Voltage Systems, Part 1, 1980.
IEEE Std. C62.33, IEEE Standard Test Specifications for Varistor
Surge-Protective Devices, 1982.
IEEE Std. C62.35, IEEE Standard for Test Specifications for
Avalanche Junction Semiconductor Surge Protective Devices, 1987.
IEEE Std. C62.42, IEEE Guide for the Application of Component
Surge Protection Devices for Use in Low-Voltage (Equal to or Less
than 1000V AC or 1200 V DC) Circuits, 2005.
IEEE Std. C62.45, Guide on Surge Testing for Equipment
Connected to Low-Voltage AC Power Circuits, 2002.
IEEE Std. C62.1 IEEE Standard for Gapped Silicon Carbide Surge
Arresters for AC Power Circuits, 1989.
NEMA LS-1, Low Voltage Surge Protection Devices, 1992.
F. D. Martzloff and T. F. Leedy, “Electrical Fast Transients: Application
and Limitations,” IEEE Trans., IA-26, no. 1, pp. 151–159, Jan./Feb. 1990.
C. R. Paul and K. B. Hardin, “Diagnosis and Reduction of Conducted
Noise Emissions,” IEEE Trans. EMC, pp. 553–560, Nov. 1988.
R. B. Standler, “Protection of Small Computers from Disturbances on the Mains,” in Conf. Record, IEEE IAS, Annual Meeting,
pp. 1482–1487, Oct. 1988.
E. S. Thomas, J. B. Dagenhart, R. A. Barber, and A. L. Clapp,
“Distribution System Grounding Fundamentals,” IEEE Industry
Applications Magazine, vol. 11, no. 5, Sept./Oct. 2005.
CHAPTER 20
SURGE ARRESTERS
Previous chapters have examples of applications of surge arresters.
The applications of surge arresters are based on interrelated aspects,
like (1) knowledge of system temporary overvoltages, switching,
and lightning surges, (2) system grounding and ground resistance
of the grid to which the arrester is connected, Chap. 21, (3) equipment being protected, and (4) characteristics of the surge arresters.
The surge arresters may be applied at:
■
Transmission line terminations and origins
■
OH line supports—transmission and distribution line towers
and poles—at certain intervals, for insulation protection
■
An open circuit breaker
■
Protection of substation (transmission, distribution, industrial, or generation)
■
Junctions of overhead lines and cables, in OH distribution
■
Shunt and series capacitor banks
■
Circuit breakers—TRV control and medium-voltage vacuum contactors
■
Rotating machinery, motors, and generators
■
Gas-insulated substations
■
Power transformers of all types—generating, step-up,
step-down, distribution, pad mounted, substation, and a variety
of winding connections; auto-transformers, step voltage
regulators, Chap. 14
■
Series reactors, Chap. 15
■
Protection of drive systems, Chap. 6
■
Protection of low-voltage systems, Chap. 19
Each of these applications has some generalities and some specifics. General concepts are discussed and applied to some situations,
without an attempt to be comprehensive about all applications of
surge arresters.
20-1
IDEAL SURGE ARRESTER
An ideal surge protection device should clamp the system voltage
to its normal value, when an overvoltage condition arises. Normally
it should have an infinite resistance, which should change precisely
under an overvoltage condition so that enough current is conducted
to clamp the voltage. This transition should occur instantaneously
without causing disturbance to the power system, and the device itself
should be immune to failure, including overloading and high-current
conduction. Further, the performance should be consistent with any
type of surge or applied voltage—of different wave shapes, rise times,
and frequencies. A surge outside the protected zone should not cause
a flashover inside the protected zone, and strokes within a protected
zone should not cause flashovers inside or outside the protected zone.
The practical surge protection tends to simulate this ideal. Thus,
the basic function of the arrester is to limit transient voltage to some
lower level, depending on the arrester characteristics. This level
may be called the protective level. It will be somewhat higher than
the system voltage and become important in insulation coordination. During operation, the arresters dissipate energy and should
not be damaged on this transient energy surge through them.
20-2
ROD GAPS
Rod gaps or air gap devices were the earliest and are no longer in
popular use. Rod gaps were installed across transformer bushings and
insulators. Once the air gap breaks down under an overvoltage condition, that is, the lightning surge, it draws the arc away from the equipment being protected but will maintain the arc even after the lightning
surge has been discharged. The arc may extinguish at a current zero;
however, due to prolonged time of arcing, the system ground fault
relays may operate, resulting in interruption of service and the very
reliability of the service may be jeopardized. The electrodes, which
may be rounded or pointed, across which the arc is drawn will rapidly
deteriorate. Though simple and rugged, the rod gaps have serious
limitation of application as surge protective devices.
The rod gaps are designed to withstand 150 percent of system
voltage under the worst atmospheric conditions, humidity, and
relative air density. The 60-Hz withstand voltage of the gap, VW,60:
VW ,60 = 2 × 1 . 5 × VTOV
(20-1)
where VTOV is the temporary overvoltage in kV rms.
VB, the mean breakdown voltage of the gap, is related to 60-Hz
breakdown voltage:
VB = VW ,60 + 3σ
= 1 . 06 VW ,60
(20-2)
525
526
CHAPTER TWENTY
20-3
EXPULSION-TYPE ARRESTERS
Expulsion-type arresters are stated here as of historical interest.
These were the next development in the surge protection and were
intended to break up the follow current, so that the continuity of
services could be maintained without operation of ground fault
protective devices. Two air gaps, one upper and one lower, were
provided in series. The breakdown of the upper gap led to the
breakdown of the lower gap, which had a plug of fibrous material
to cool the arc, so that the current was interrupted at a current zero.
These arresters had limited useful life because the fibrous material
was consumed and had different operating characteristics, depending on the voltage wave shape. These are no longer in use.
20-4
FIGURE 20-1
Standard mean breakdown voltage for rod gaps, 60 Hz.
where s is the standard deviation of the breakdown voltage, taken
as 2 percent for 60-Hz voltage VW, 60. This voltage can be corrected
for atmospheric conditions:
VM = VB
Kh
R ad
(20-3)
where VM is the maximum system voltage, and Kh and Rad are the
humidity and relative air density correction factors, respectively.
Figure 20-1 illustrates the gap spacing in centimeters with respect
to 60-Hz standard mean breakdown voltage.
FIGURE 20-2
VALVE-TYPE SILICON CARBIDE ARRESTERS
Valve-type arresters are basically an air gap in series with a nonlinear resistor of the silicon carbide type. Though replaced with metaloxide gapless arresters, these are still in wide use.
The breakdown characteristic of the air gap in the arrester governs the initial voltage at which surge-limiting action begins. The
silicon carbide blocks have a nonlinear characteristic, so that their
resistance decreases as the current increases. Figure 20-2a shows
a schematic representation of the arrester and Fig. 20-2b shows a
cross section through the arrester, functional only.
The silicon carbide crystals are bonded with an inert material by
sintering in a kiln at 1000°C. The outer surface of a valve block has
an epoxy or ceramic collar to prevent flashovers when conducting
high currents. The VI characteristics of silicon carbide valve block
is controlled by grains of silicon carbide within the block. The heating
(a) Circuit representation of a valve-type surge arrester. (b) Cross-sectional view.
SURGE ARRESTERS
FIGURE 20-3
VI characteristics of a distribution class surge arrester.
occurs due to contact points within the block, and thus, there is a
distinct relationship between the current magnitude, wave shape,
and the temperature at the point of contact. The silicon carbide has
a negative coefficient of resistance, which decreases with increasing
temperature and increasing current. The characteristics are tailored
to provide voltage limiting with lightning discharge current wave
shapes, keeping the power flow currents low, which are interrupted
by the air gap.
The blocks have little overload capability and can be destroyed
if subjected to energy discharge beyond their design capabilities.
The VI characteristics are measured using standard 8/20 µs test
wave shape for peak magnitudes of 1.5, 3, 5, 10, and 20 kA. A VI
characteristic of distribution class surge arrester is shown in Fig. 20-3.
The silicon elements are chosen to give a certain protective level at
a specified lightning discharge current, 20 kA in this figure. The
power flow current after discharge of a surge is interrupted by air
gap at a current zero.
There are a number of series gaps, each rated at 1 to 1.5 kV. Each
gap may consist of a contoured brass, copper, or stainless steel plate
separated from the adjacent plate by a ceramic spacer. The use of
modular gaps makes it feasible to have different ratings by assembling varying number of gaps, so that
■
Ability to interrupt power flow current is increased.
■
Increase in total arc voltage drop is obtained, thus enhancing power flow current-interrupting capability of the arrester.
■
527
Response to steep-fronted waves is improved.
■
Response to different voltage wave shapes can be modified by
control of voltage between individual gaps.
As the heating is dictated by current, short-duration surges create higher voltage drops than the long-duration surges. Figure 20-4
shows the discharge voltage as a function of rise time of the
impulse current. Manufacturers publish data for the switching
surge capabilities.
Surge protection levels are not standardized and the manufacturers are required to publish maximum values for each design;
these data are required for proper application.
The arrester continues to conduct until the arc in the air gap
is extinguished at current zero. Due to nonlinearity, the current
through the surge arrester is nonsinusoidal. Practically, the gap
design is more complex than what has been described earlier.
Preinsertion Gap For the purpose of surge protection, it is
desirable to have gap breakdown at a fixed voltage level regardless
of the voltage wave shape. However, the gap reacts to instantaneous
voltage and voltage rises at different rates, depending on the maximum surge level and its rate of rise. The statistical time lag, which is
the time taken by the initial electrons to start the avalanche process,
can be minimized by incorporating a pre-ionization gap in addition
to the main arc gap. A smaller gap is placed into the circuit and
coupled into it by large capacitive or resistive impedance.
Grading Components In case of even slight nonuniform distribution of voltage across the gaps, the gaps with higher voltage
applied across it will break down first and the breakdown will cascade throughout the assembly. Consequently, the arresters are fitted
with some form of intentional grading components, that is, grading
resistors. This provides a brief description of the constructional features; the characteristics for surge suppression are of more interest.
20-4-1
Arrester Ratings
Arrester Class The arresters’ ratings depend on the class of the
arresters, which are as follows:
■
Station class arresters, voltage ratings 3 to 682 kV
■
Intermediate class arresters, voltage ratings 3 to 120 kV
■
Distribution class arresters, voltage ratings 1 to 30 kV
The distribution class arresters are further divided into heavy-duty
distribution class arresters and normal-duty distribution class arresters.
528
CHAPTER TWENTY
FIGURE 20-4
Correction factors for nonstandard current impulses.
Voltage Rating
A valve-type arrester must be able to withstand
rated voltage for 24 min, while discharging 5 to 10 kA of standard
lightning currents at 1-min interval. Successful operation means that
the power flow current after each discharge should be interrupted.
This rated voltage is, therefore, defined by the duty cycle tests. The
standards publish the rated voltages. An arrester will not be able to
continuously withstand its rated voltage. The selection of the rated
voltage of the arrester for a particular application is described further.
Overvoltage Rating The valve-type arresters are applied so that
their rated voltage is greater than the system overvoltage produced
by single line-to-ground faults. The definition of COG and its
calculations have been described in Chap. 9. Considerations should
also be applied to the overvoltages and their duration, which may
be generated at the location of the arrester due to contingency
operations, that is, severe load dropping (Chap. 7). Overvoltage
characteristics of arresters are an important parameter.
The ability to withstand overvoltage demands that the arrester gaps
should not spark over when nonconducting. When conducting, the
arrester should be able to withstand increased stresses and have the
capability to interrupt higher power follow currents. The distribution
class surge arresters do not have a well-defined overvoltage capability,
while intermediate class and station class surge arresters have better
overvoltage withstand capabilities. The performance of distribution
class arresters can, therefore, only be expressed in terms of increasing
probability of failure with higher overvoltages.
Manufacturers publish the overvoltage capability curve of the
arresters. Figure 20-5 shows such a curve for station and intermediate class arresters.
60-Hz Sparkover Voltage The 60-Hz sparkover voltage level is
specified by the manufacturers. This does not mean that the arrester
can withstand this voltage continuously. The limiting factor is probability of the failure of grading resistors in the arrester assembly.
Lightning Impulse Sparkover Voltage The front of wave sparkover is tested with 1.2 × 50-µs standard wave, with a peak magnitude
selected to give a rise time of 25 kV/µs for each 3 kV of arrester rating; that
is, an arrester of 24 kV should be tested for 200 kV/µs, with a test impulse
peak of 225 kV. Ten impulses, five of each polarity, are applied, and
maximum sparkover voltage is taken as the published value.
FIGURE 20-5
Overvoltage operating capability of a station class
and intermediate class surge arresters.
A 1.2 × 50-µs impulse sparkover test determines the highest
1.2 × 50-µs impulse for which there is a 50 percent probability of
sparkover occurring within 3 µs. A series of impulses is applied
for the test calculations. The published value is the mean of all the
applied impulses.
Lightning Surge Discharge Performance A lightning discharge interacts with the system, and the magnitude and shape of
the discharge current can vary. The tests determine the capability of
the arrester to discharge standard current surges and to interrupt the
succeeding power flow current. Lightning current test wave shape
SURGE ARRESTERS
is 8 × 20 µs. Discharge voltage current characteristics are obtained
for currents of 1.5-, 3.0-, 5.0-, 10.0-, 20-, and 40-kA crest.
High Current Short-Duration Test Two current impulses are
applied to an arrester or an arrester-prorated section. The magnitude of the impulse is 10 kA for distribution class arresters, and
65 kA for intermediate and station class arresters, using 4/10-µs
wave, with a tolerance of –0 percent to 50 percent to accommodate the characteristics of the test equipment. The test specimen should withstand these impulses without damage and major
deterioration.
Switching Surge Discharge Performance Switching surges
are of longer duration and, therefore, may contain more energy
than lightning surges. Distribution class surge arresters will not
be normally subjected to switching surges and, therefore, their
switching surge capabilities are not specified. Also, switching surge
sparkover voltage is not specified for intermediate and station class
surge arresters of voltage rating less than 60 kV. The switching surge
sparkover test includes three sequences, each identical, except that
a different standard test wave is used:
■
30/60 µs
■
150/300 µs
■
1000/2000 µs
Transmission Line Discharge Test (TLD) The test standards
also specify that station and intermediate class surge arresters be
subjected to current discharges generated by a test circuit that
approximates an OH line.1,2 This is called a TLD. The parameters of
TLD test are specified in Refs. 1 and 2.
In addition, high current short-duration tests are conducted
(HCSD, 4/10-µs wave). The nonstandard tests indicate that 90 percent
of randomly selected arresters will survive one 20-kA discharge and
70 percent will survive one HCSD discharge.
Table 20-1 shows protective characteristics of valve-type station
class arresters.3 Similar characteristics for distribution class arresters and intermediate class arresters are available in Ref. 3. Switching
surge absorption capabilities of valve-type arresters are specified in
Table 20-2, which seems to be conservative. The ability of a surge
arrester of a given rating to absorb energy depends on the shape of
the switching surge.
20-5
METAL-OXIDE SURGE ARRESTERS
20-5-1
Construction and Operation
A metal-oxide gapless arrester consists of several metal-oxide elements
connected line to ground. The resistance of the zinc oxide changes
with voltage, but the change is more dramatic as compared to that
of silicon carbide. Figure 20-6 shows a cross section through a typical arrester, and Fig. 20-7 shows the VI characteristics of the zinc elements (the material consists of approximately 90 percent of zinc oxide;
10 percent are oxides of other metals, like aluminum, antimony, barium,
bismuth, cobalt, and so on) versus that of silicon carbide. The extreme
nonlinearity allows zinc-oxide arrester to be designed so that these conduct only a small current under normal system voltage conditions, and
a much larger current at slightly higher voltage. Figure 20-7 shows that
low-current zone is affected by temperature and frequency. For 100°C,
three curves are shown: dc VI, ac resistance VI, and ac total VI. For currents above 1 A, the VI characteristic is highly nonlinear, and the voltage
drop remains constant over a wide range of currents. In high-currentdensity region, the device loses its nonlinearity due to the linear resistance of the zinc-oxide grains.
Considerable power dissipation occurs due to passage of leakage current. Metal-oxide surge arresters are susceptible to thermal
runaway.
529
The construction of the assembly is very similar to silicon carbide gap-type arresters, except the gap. There are gapped metaloxide surge arresters, which are not discussed.
20-5-2
Equivalent Circuit
An equivalent circuit of the metal-oxide surge arrester is shown in
Fig. 20-8.4 The leakage current is mostly capacitive, and the capacitance
of the arrester Cp varies with its class, from 400 to 2000 pF. The inductance LE is 10 to 20 nH and can be ignored at 60 Hz. C1 and C2 are constants and I is the arrester current. The capacitance of metal-oxide surge
arresters is important in modeling and is shown in Table 20-3.
With normal voltage applied, the current is, therefore, mostly
leading and has a resistive component, which is distorted. As the
nonlinearity increases, the distortion in the resistive component of
the current is increased. This change in current at different voltage
levels means that there is no constant relation between the voltage,
current, and power dissipation. An equation that models the VI
characteristics has been developed,4 and is given by:
C1
+ RI
C2 − ln I
V=
(20-4)
where V is resistive voltage drop, C1 and C2 are constants, I is the
arrester current, and R is the equivalent valve element resistance.
Constants C1 and C2 vary somewhat with the manufacturers and
the dimensions of the arrester.
A so-called “alpha equation” to model the VI characteristics is
much in use and is given by:
V = K I1/α
(20-5)
where V is resistive voltage drop, I is arrester current, K is proportionality constant, and a is nonlinearity constant. The alpha equation
is less accurate compared to Eq. (20-4).
The nonlinearity constants K and a can be determined from
solutions of two simultaneous nonlinear equations, using high and
low levels of arrester voltages and currents. Alternatively, it can be
assumed 4.5 for valve-type and 25 for metal-oxide arresters. K is
given by the following equation:
K = 0.96 Vds for intermediate or station class arresters
= 1.73 Vow for riser pole-type units
= 1.96 Vow for distribution class arresters
(20-6)
Vds, VOW are defined in the following section.
20-5-3
Energy Absorption Capability
An advantage of metal-oxide arresters is that they can absorb more
energy compared to gapped surge arresters. The energy handling
capability is published by the manufacturers and is dependent on
thermal stability limit and thermal shock limit of the arrester. The
following list shows the typical range (manufacturer’s literature
should be consulted for accuracy):
■
Distribution class:
1 to 1.9 kJ/kV (MCOV)
■
Intermediate class:
2.7 to 3.4 kJ/kV (MCOV)
■
Station class (2.7 to 48 kV):
5 kJ/kV (MCOV)
■
Station class (54 to 36 kV):
9 kJ/kV (MCOV)
The kV here pertains to the arrester MCOV rating, discussed
further in Sec. 20-5-4.
Pressure Relief Current A criterion in the selection of the
arrester class is pressure relief current limits, which should not be
exceeded at the arrester location above the system short-circuit currents
530
TA B L E 2 0 - 1
Protective Characteristics of Gapped Silicon-Carbide Station Arresters
IMPULSE SPARKOVER VOLTAGE
VOLTAGE RANGE
ARRESTER
(KV rms)
OF THE
FRONT-OF-WAVE RATE OF RISE
OF TEST VOLTAGE
(KV/l S)
KV
CREST (RANGE
OF MAXIMA)
1.2/50-l S KV
CREST (RANGE OF
MAXIMA)
SWITCHING SURGE
SPARKOVER VOLTAGE
KV
CREST (RANGE OF
MAXIMA)
DISCHARGE VOLTAGE FOR 8/20-l S DISCHARGE CURRENT WAVE
KV CREST FOR
1500 A (RANGE
OF MAXIMA)
KV CREST FOR
3000 A (RANGE
OF MAXIMA)
KV CREST FOR
5000 A (RANGE
OF MAXIMA)
KV CREST FOR
20000 A (RANGE
OF MAXIMA)
KV CREST FOR
40000 A (RANGE
OF MAXIMA)
6.7–7.5
7.7–8.3
–9.2
22.9–24.3
–28
38.2–40
–46
3
25
10–18
10–14
—
4.7–6
5.3–6.5
9
75
28.5–38
24–32
—
13.9–17
16–18
17.8–19
15
125
45–47
40–51
—
23.1–27.5
26.6–30
29.5–32
33.4–36
24
200
71–86
62–77
—
36.9–44
42.5–48
47–51
53.4–57
61–63.5
36
300
107–118
92–108
—
55.3–66
63.7–72
70.5–76
80–85
91.5–94.5
–111
48
400
143–148
122–132
—
73.8–88
84.9–96
94–102
106–114
122–126
–148
72
600
204–226
169–190
163–178
114–131
130–144
141–155
159–170
180–189
–222
96
800
270–295
218–245
218–225
151–174
173–192
188–218
212–227
240–253
–296
120
1000
338–360
272–300
272–275
188–218
216–240
235–272
265–285
300–319
–370
168
1400
460–525
380–404
380–381
263–305
303–336
329–362
371–399
420–442
–517
192
1600
520–600
427–460
426–435
300–348
346–384
376–414
424–455
480–505
–591
258
2000
760–790
575–620
573–585
402–438
465–474
505–515
569–575
650–666
–795
294
2000
875–885
653–675
653–675
458–472
528–532
576–595
635–653
735–758
–906
372
2000
1078–1100
870–890
790–830
562–610
655–680
726–738
809–826
932–955
1136–1145
420
2000
1200–1250
980–1005
890–940
634–713
739–770
819–830
913–930
1050–1070
1176–1294
468
2000
1326–1390
1090–1110
992–1045
707–794
823–860
913–930
1018–1040
1170–1200
1310–1441
540
2000
1515–1555
1274–1280
1145–1200
814–890
949–990
1052–1070
1173–1195
1350–1390
1646–1663
612
2000
1700–1765
1440–1480
1300–1370
924–1010
1076–1130
1193–1220
1330–1360
1531–1580
1865–1885
684
2000
1880–1960
1610–1680
1455–1525
1031–1130
1153–1260
1331–1360
1489–1520
1709–1765
2063–2107
All the standard voltage ranges are not shown in this table. See Ref. 3 for further details.
6–7
KV CREST FOR
10000 A (RANGE
OF MAXIMA)
20–21.5
–74
SURGE ARRESTERS
TA B L E 2 0 - 2
ARRESTER CLASS
Switching Surge Absorption
Capability of Typical ValveType Arresters
NOMINAL ENERGY
CAPABILITY PER KV
OF ARRESTER RATING
(J/KV)
ESTIMATED ONE-SHOT
ENERGY CAPABILITY,
PER KV OF ARRESTER
RATING (J/KV)
Station
2000
3000
Intermediate
1000
1500
Distribution
500
750
FIGURE 20-8
TA B L E 2 0 - 3
ARRESTER CLASS
Cross section through a gapless metal-oxide surge
arrester.
Equivalent circuit of a metal-oxide element.
Capacitance of Metal-Oxide
Surge Arresters
SUBCLASS
CAPACITANCE (PF)
Distribution
Normal
Heavy duty
Riser pole
400
700
1200
Intermediate
—
1200
Station
FIGURE 20-6
531
2000
and duration. The pressure relief currents are specified in Ref. 5 and
vary from 40 to 80 kA rms symmetrical. If the pressure relief capability of a surge arrester is exceeded, the discs may crack or rupture.
This will reduce the arrester internal discharge resistance. It may
not jeopardize the insulation protection characteristics. In case of
complete failure, line-to-ground arc will develop and pressure will
build inside the arrester. The pressure will be safely vented to the
outside atmosphere and an external arc will be established, provided the fault current is within the pressure relief capability of the
arrester. Standards specify 65 kA rms symmetrical (169-kA peak,
first crest), though arresters with higher pressure relief capability
are available. Many applications require high energy handling capability; for example, for the application of surge arresters to capacitor
banks, energy capability becomes an important consideration.
Metal-oxide gapless arresters change smoothly from conducting a
small leakage current to kiloamperes of surge current as the voltage
is increased. Manufacturers do not specify a conduction threshold
above which the dissipation of switching surge energy may be of concern. The conduction threshold voltage is taken as the instantaneous
terminal voltage or discharge voltage at which the surge arrester current is 10 A. The operation on switching surge is not of concern if:
Vds ≥ 1 . 25Vs
(20-7)
and
Vow ≥
Vs
1.1 2
(20-8)
where Vs is switching surge overvoltage in peak, Vow is power frequency
voltage withstand capability of the surge arrester for 10 s in kV rms,
and Vds is maximum switching surge discharge voltage in kV peak at
500 A for intermediate class and 1000 A for station class arresters.
Equation (20-7) is used for station class and intermediate class surge
arresters, while Eq. (20-8) is for distribution class surge arresters.
20-5-4 Maximum Continuous Operating Voltage (MCOV)
FIGURE 20-7
arrester.
VI characteristics of a station class metal-oxide surge
The MCOV is defined as the maximum continuous operating voltage to which the unit may be subjected continuously, and remain
532
CHAPTER TWENTY
thermally stable after being subjected to standard impulse duty
tests. It is implied that the arrester is not capable of withstanding
voltages above its MCOV rating on a continuous basis. It is the maximum voltage at which the arrester can be permanently energized;
MCOV ≥ K T Vln g , where Vln g is the line-to-ground voltage and KT is
voltage tolerance factor, which considers allowances for variations
due to voltage regulation. It may be typically taken as 1.05, but it
can be higher as well. The arresters are normally connected from
phase to ground. An arrester on a corner-grounded system or a
delta-connected system with fault on one phase will be exposed to
phase-to-phase voltage and must withstand phase-to-phase voltages. Therefore, the circuit connections, for example, delta, singlephase wye, as well as arrester connections, must be considered.
System grounding is another consideration. In high-resistance
grounded systems, especially for industrial process plants, an
immediate shutdown is avoided on occurrence of first line-toground fault, and the fault may be allowed to persist for hours. In
such applications, the arrester MCOV must be chosen to withstand
the higher phase-to-ground voltages that may even exceed line-toline voltages, continuously.
20-5-5 Duty Cycle Voltage Rating
The duty cycle voltage is defined as the maximum permissible voltage
between its terminals at which the arrester is designed to perform
its duty cycle. Duty cycle voltage rating is above MCOV. The arrester
will operate at duty cycle voltage rating for a limited duration. Test
procedures are described in Ref. 1.
20-5-6 Temporary Overvoltage (TOV)
Figure 20-9 shows TOV capability of station class TranquellTM surge
arresters of General Electric Company. Low-magnitude TOVs are
those that cause a rise in the element temperature, and the largest surge voltages will cause a surge arrester to reach its thermal
stability limit of 200°C in 1 to 200 s. The high-magnitude TOVs
are those that cause leakage currents in excess of 1 A, so that the
system voltage waveform begins to distort due to voltage drop in
the system impedance. It is, therefore, not possible to generalize
the overvoltage capabilities of the surge arresters. An EMTP program can be used for case-by-case studies. Failure can occur due
to rise in temperature caused by TOV, which may drive the arrester
beyond its thermal stability limit.
FIGURE 20-9
All rights reserved.
The TOV is also a function of the arrester type (Fig. 20-10).
This figure shows that the distribution class surge arresters have a
higher TOV. The stability limit voltage also depends on the arrester
design. This figure also depicts that the stability limit voltage for
intermediate and distribution class arresters is above the duty cycle
voltage. Generally, for distribution class arresters, TOV is not of
major concern.
We discussed TOV in Chap. 7. A TOV can be defined as a voltage condition that lasts at least for a cycle and is limited in duration.
Figure 20-11 provides a prospective of voltages across the arrester
and their time duration with reference to TOV, switching, and
lightning surges based on MCOV rating of the arrester. If a rigorous study is not available, the overvoltage on single line-to-ground
fault can be considered (Chap. 9). The TOV capability must exceed
the magnitude and duration of expected temporary overvoltages,
considering operating time of the primary and backup protective
devices. The curves in Fig. 20-9 illustrate the duration and magnitude of the TOV that can be applied to the arrester before the
arrester voltage is reduced to MCOV. Also, the permissible durations are a function of the energy that may have been discharged
through the arrester just prior to the application of TOV. This prior
energy is mostly the result of discharge of a switching surge.
Manufacturers sometimes publish curves of prospective switching surge versus arrester discharge energy applicable to their arresters that can be applied for a general estimate of the TOV capability.
Figure 20-12 shows such a curve for 336-kV and 300-kV metaloxide arrester for 400-kV system for Tranquell station class arresters.
If the switching surge is 2.5 per unit, [400 × ( 2 / 3 ) × 2 . 5 kV] and
arrester rating is 336 kV, then, for a 100-mi-long line, the energy
read from this figure is 1.1 kJ/kV. If the station class arrester has an
energy capability of 7.2 kJ/kV, six surges can be discharged within 1
min period. After 1 min rest period, the discharge can be repeated.
Note that the energy-handling capability of arresters is specified for
a certain magnitude of switching current and surge impedances.
Some other system considerations and connections of equipment being protected must be considered. A delta-wye step-down
transformer that has its only source of ground at the substation
may become ungrounded on operation of line breaker and back fed
from the wye-side, exposing the surge arrester connected line-toground to line-to-line voltage.
For line-to-ground–connected surge arresters, we may summarize that:
Overvoltage capability of station class, General Electric Company Tranquell™ station class surge arresters. Reproduced with permission.
SURGE ARRESTERS
FIGURE 20-10
533
Relationship between four operating regions, different classes of surge arresters.
FIGURE 20-12
Prospective switching surge versus arrester discharge energy, 400-kV system, General Electric Company Tranquell™ station
class surge arresters; 300 kV and 326 kV rated voltages. Reproduced with
permission. All rights reserved.
F I G U R E 2 0 - 1 1 Voltage across surge arrester, generalization, for
various overvoltage conditions.
■
For solidly grounded systems, an arrester rating of 80 percent
of maximum phase-to-phase voltage with no fault on the system
can be used.
■
For multigrounded wye open-wire circuits in distribution
systems, the nominal phase-to-ground operating voltage is
multiplied by 1.25 and for cable spacer circuits by 1.50.
■
For ungrounded and impedance grounded systems, MCOV
is selected equal to line-to-line voltage, or more, where the
faults can be removed in a few seconds.
■
Ungrounded or resistance-grounded systems may require
MCOV = 1.25 times or higher than line-to-line voltage.
Table 20-4 shows the typical arrester-rated voltages for grounded
neutral circuits and for high-impedance grounded, ungrounded, or temporarily ungrounded systems. High-voltage systems are not impedance
grounded. The surge arrester data shown for high-voltage impedance
grounded/ungrounded system may be applicable for special situations.
20-5-7 Lightning and Switching Surge
Discharge Currents
The tests determine the ability of arrester to operate successfully
under application of sequence of current impulses while energized
at MCOV.
534
CHAPTER TWENTY
TA B L E 2 0 - 4
NOMINAL SYSTEM VOLTAGE
Selection of Arrester-Rated Voltage With
Respect to System Grounding
GROUNDED NEUTRALS
4.16
HIGH IMPEDANCE-GROUNDED, UNGROUNDED,
OR TEMPORARILY UNGROUNDED SYSTEMS
3.0
4.5
13.8
4.5
5.1
10
12
15
18
34.5
27
30
36
39
138
108
120
132
144
230
172
180
182
400
300
312
336
360
Table 20-5 shows lightning impulse classifying currents 8 / 20-µs
wave shape for discharge voltage characteristics,1 and Table 20-6
shows switching surge classifying currents to obtain the discharge
voltage characteristics with a time to crest of 45 to 60 µs. We will
further discuss these lightning and switching currents in Sec. 20-6.
Table 20-7 shows the characteristics of Tranquill metal-oxide
station class arresters of General Electric Company, reproduced
with permission. Tables 20-8 and 20-9 depict the VI characteristics
of arresters for front of wave (FOW), 8 / 20 µs, 36 / 90 µs, and also
for 1-ms wavefront, courtesy of General Electric Company. The
data shown in these tables may not be readily available from a manufacturer. The data shown in these tables are used throughout the
following examples.
Table 20-10 provides the arrester discharge voltage data for various arrester classes. The factors shown are generalized and are not
of a particular manufacturer.
TA B L E 2 0 - 5
Lightning Impulse Classifying
Currents
CLASSIFICATION OF THE ARRESTER
Station (800 kV, maximum system voltage)
Station (550 kV, maximum system voltage)
Station (below 550 kV, maximum system voltage)
Intermediate
Distribution, heavy duty
Distribution, normal duty
Distribution, light duty
IMPULSE VALUE
(PEAK A)
20000
15000
10000
5000
10000
5000
5000
228
240
At such high voltages, there are no
impedance-grounded or ungrounded
systems
TA B L E 2 0 - 6
SYSTEM VOLTAGE,
MAXIMUM
Switching Surge Classifying
Current
STATION CLASS
(CREST A)
INTERMEDIATE
CLASS
3–150
500
500
151–325
1000
—
326–900
2000
—
20-6
RESPONSE TO LIGHTNING SURGES
The steepness of the lightning surge voltage varies from the standard
wave shape and so does the discharge voltage. Statistical data may
be available for a certain location of rate of rise of the surge voltages at
arrester locations, which will differ for direct strokes and induced
voltages. The system configuration also plays a role. A surge will be
reflected at any impedance discontinuity, such as line end, fault, line
tap, or junction between OH and underground systems. A metaloxide surge arrester will begin conducting a lightning surge current
when the voltage reaches approximately 80 percent of the FOW
peak discharge voltage. The test procedure for FOW sparkover
results in a wave front which is determined by the test apparatus
and not by the surge arrester. Thus, practically the FOW response is
determined more by the system and characteristics of the originating surge rather than the surge arrester.
The voltage response of the arrester to a lightning surge after it
begins its surge-limiting action is termed voltage response. This depends
on the peak current discharged, which is termed coordinating current. The coordinating current is one key parameter in the insulation
TA B L E 2 0 - 7
ARRESTER
RATING
(KV rms)
MCOV
(KV rms)
Gapless Metal-Oxide Surge Arrester Data
MAX. SWITCHING PROTECTIVE LEVEL
(KV CREST) AT INDICATED CURRENT
MAXIMUM DISCHARGE VOLTAGE (KV CREST) AT INDICATED CURRENT FOR 8/20-l S CURRENT WAVE
TOV
(1S, KV rms)
FOW
(KV CREST)
1.5 KA
3.0 KA
5.0 KA
10 KA
15 KA
20 KA
40 KA
KV
KA
2.7
2.2
3.1
7.8
5.9
6.2
6.5
6.9
7.4
7.8
8.9
5.4
0.5
5.1
4.2
6.0
14.8
11.2
11.8
12.3
13.1
14.0
14.7
16.9
10.3
0.5
7.5
6.1
8.8
21.4
16.2
17.0
17.7
18.9
20.2
21.2
24.3
14.8
0.5
9.0
7.65
11.0
26.6
20.2
21.1
22.0
23.5
25.1
26.4
30.2
18.4
0.5
15.0
12.7
18.3
44.2
33.5
35.1
36.6
39.1
41.8
43.9
50.3
30.6
0.5
18.0
15.3
22.0
53.3
40.4
42.3
44.1
47.1
50.3
52.8
60.6
36.8
0.5
27
22.0
31.7
76.5
58.0
60.8
63.3
67.7
72.3
75.9
87.0
52.9
0.5
30
24.4
35.2
84.9
64.3
67.4
70.3
75.1
80.2
84.2
96.5
58.7
0.5
45
36.5
52.6
128
88.3
0.5
54
44
63
144
72
58
85
191
96.8
102
106
113
121
127
146
111
116
120
127
135
141
159
102
0.5
148
154
160
169
179
188
212
136
0.5
96
78
113
255
197
206
213
225
239
250
282
181
0.5
108
87
127
287
222
232
240
254
270
282
318
204
0.5
120
98
142
321
249
259
269
284
301
315
355
235
1.0
144
117
170
382
296
309
320
338
359
375
423
280
1.0
168
136
198
446
345
360
373
394
418
437
493
326
1.0
192
156
226
509
394
411
426
450
477
499
563
372
1.0
240
194
283
635
491
513
531
562
596
623
703
465
1.0
258
209
304
683
528
551
571
604
641
670
755
518
2.0
276
224
325
730
565
589
611
646
685
716
808
554
2.0
294
238
347
778
602
628
650
688
730
763
860
590
2.0
300
243
354
795
615
641
665
703
745
779
879
603
2.0
360
292
424
953
737
769
797
843
894
934
1054
723
2.0
(All standard arrester ratings are not shown.)
Courtesy of General Electric Company; reproduced with permission. All rights reserved.
535
536
CHAPTER TWENTY
TA B L E 2 0 - 8
Arrester VI Characteristics for Ratings 2.7 to 48 kV
ARRESTER VOLTAGE IN PER UNIT OF THE 10 KA, 8/20-lS DISCHARGE VOLTAGE
TEST WAVE
8/20 lS
FOW
MAX
1-MS WAVEFRONT
MIN
MAX
MIN
MAX
MIN
MAX
1
10
0.608
0.645
0.663
0.696
0.599
0.635
0.653
0.686
0.596
0.631
0.650
0.681
100
500
0.695
0.754
0.743
0.794
0.685
0.743
0.732
0.782
0.676
0.738
0.722
0.777
0.776
0.817
0.812
0.850
0.769
0.807
0.805
0.841
CURRENT (A)
MIN
36/90 lS
1000
2000
0.891
0.939
0.933
0.977
0.787
0.829
0.824
0.863
5000
10000
1.013
1.110
1.061
1.132
0.895
0.981
0.937
1.000
15000
20000
40000
1.168
1.210
1.329
1.210
1.271
1.458
1.031
1.069
1.174
1.069
1.123
1.288
Courtesy of General Electric Company; reproduced with permission. All rights reserved.
TA B L E 2 0 - 9
Arrester VI characteristics for Ratings 54 to 360 kV
ARRESTER VOLTAGE IN PER UNIT OF THE 10-KA, 8/20-lS DISCHARGE VOLTAGE
TEST WAVE
8/20 lS
FOW
MAX
1-MS WAVEFRONT
MIN
MAX
MIN
MAX
MIN
MAX
1
10
0.647
0.682
0.691
0.725
0.645
0.674
0.689
0.717
0.640
0.671
0.684
0.713
100
500
0.734
0.790
0.769
0.819
0.722
0.775
0.756
0.803
0.716
0.762
0.750
0.790
0.802
0.839
0.828
0.859
0.787
0.839
0.813
0.859
CURRENT (A)
MIN
36/90 lS
1000
2000
0.927
0.972
0.958
0.996
0.820
0.860
0.847
0.881
5000
10000
1.044
1.117
1.070
1.131
0.923
0.988
0.946
1.000
15000
20000
40000
1.167
1.209
1.318
1.200
1.254
1.414
1.032
1.069
1.166
1.061
1.109
1.251
Courtesy of General Electric Company; reproduced with permission. All rights reserved.
TA B L E 2 0 - 1 0
ARRESTER CLASS
Arrester Discharge Voltage
With Respect to Its Class at
20-kA Coordinating Current
DISCHARGE VOLTAGE IN pu BASED ON
DISTRIBUTION CLASS NORMAL DUTY
ARRESTER AS 1 pu
Distribution—normal duty
Distribution—heavy duty
Distribution—riser pole
1.0
0.87
0.78
Intermediate
0.71
Station
0.68
coordination. The appropriate coordinating current for lightning surges
depends on the effectiveness of shielding. Table 20-11 contains coordinating currents that are found satisfactory in most situations.5
Manufacturers publish data of the discharge voltage of the surge
arresters for 8 / 20 µs current surges (Table 20-7). As the discharge
voltage will depend on the wave shape and duration of associated
discharge current, it may be necessary to correct the published data
to account for wave shapes encountered in the actual surge applications, using data from Tables 20-8 and 20-9.
For insulation coordination and application of surge arresters,
it may be necessary to reduce the discharge voltage for a better
protective margin.
Increasing the arrester class is one way to reduce the discharge
voltage, as shown in Table 20-10. The other advantages of choosing
a higher arrester classification are:
SURGE ARRESTERS
TA B L E 2 0 - 1 1
537
Currents for Determining
Discharge Voltages in
Shielded Substations with
Shielded Incoming Lines
MAXIMUM SYSTEM VOLTAGE
DISCHARGE CURRENT (A)
*
15
36.5
72.5
121
145
242
362
550
800
*
5000
5000
5000
10000
10000
15000
20000
*
Generally unshielded lines.
■
Failures are less likely.
■
Higher energy-handling capability.
■
Discharge voltage does not increase rapidly with discharge
current.
Metal-Oxide Surge Arresters in Parallel
Another alternative to cater for higher discharge currents is to connect metal-oxide
gapless arresters in parallel. The discharge current for each arrester
is reduced and, therefore, the discharge voltage is reduced. This
option can be exercised with metal-oxide arresters only as exact
matching of discharge characteristics is required. The valve-type
arresters with air gap have a broad tolerance of characteristics, and
the current sharing between parallel units will be unpredictable.
The gapped-type surge arresters should, therefore, never be paralleled. Table 20-12 shows the effect of parallel connection of distribution class arresters. Most beneficial improvement is obtained
with two arresters in parallel.
A configuration that can be used for resistance-grounded mediumvoltage systems is shown in Fig. 20-13b. Again, only metal-oxide
surge arresters should be used in this configuration. This is the
application of surge protection to a 13.8-kV, impedance-grounded
system. Normally, say, 18-kV arresters are required for phase-toground connection, as shown in Fig. 20-13a. If the system was
solidly grounded, 12-kV arresters would be adequate for phase-toground connection, as the TOV is limited. For configuration shown
in Fig. 20-13b, 12-kV arresters are chosen for connection from phase
to a common wye point, which is then connected to ground through
TA B L E 2 0 - 1 2
Effect of Parallel Distribution
Class Arresters on Discharge
Voltage
DISCHARGE VOLTAGE REDUCTION
NUMBER OF
UNITS
COORDINATING CURRENT
IN EACH UNIT
NORMAL DUTY
ARRESTER PU
HEAVY DUTY
ARRESTER PU
1
20
1.00
1.00
2
10
0.87
0.86
3
6.7
0.83
0.82
4
5
0.80
0.80
F I G U R E 2 0 - 1 3 (a) Conventional phase-to-ground connection of
three surge arresters, rated voltage 18 kV, for 13.8-kV resistance-grounded
system. (b) Configuration with four arresters of 12 kV and 6 kV for better
control of phase-to-phase surges; see text.
a 6-kV arrester. This behaves like a 18-kV arrester for phase-toground surges, same as in Fig. 20-13a; however, for phase-to-phase
overvoltages, the effective rating of surge arresters in Fig. 20-13b is
24 kV versus 36 kV in Fig. 20-13a.
20-7
SWITCHING SURGE DURABILITY
For insulation coordination, an estimate of the energy through the
arrester for a switching surge is required. The energy dissipated is
related to prospective switching surge magnitude, its wave shape,
and system impedance. This can be best determined through detailed
system studies with TNA or EMTP. In the absence of this analysis, the
energy absorbed can be estimated from the following equations:5
J = D L E AI A /v
I A = (Es − E A )/Z
(20-9)
where J is the discharge energy in kJ, EA is the arrester discharge
voltage for the switching current IA in kA, DL is line length in km, v
is speed of light, Es is prospective switching surge voltage in kV, and
Z is single-phase surge impedance of the line in ohms.
Manufacturer’s data are required for the discharge energy capability, generally expressed as kJ/kV of rating voltage rating or kJ/MCOV.
Example 20-1 A surge arrester of 258 kV rating has a maximum switching protective level of 518-kV, 2-kA switching impulse
538
CHAPTER TWENTY
current—data taken from Table 20-7. The line length is 300 km of
surge impedance 350 Ω and the switching surge level is 900 kV.
Then from Eq. (20-9), IA is 1.09 kA. However, from Eq. (20-9), we
cannot calculate the discharge current correctly as the discharge voltage of the arrester is not constant and varies with the current. The internal resistance of the arrester should be calculated which can be taken
as a straight line with constant slope. Table 20-9 shows the arrester
voltage for a surge of 36 / 90 µs and 2000 A discharge current is 0.859
(maximum value) of the arrester voltage for 10-kA, 8 / 20-µs wave.
From Table 20-7, the arrester discharge voltage for 10-kA, 8 / 20-µs
wave is 604 kV. Therefore, 604 × 0.859 = 518 kV, which is the same
as shown under maximum switching protection level for 2 kA current
in Table 20-7. If the first estimate of discharge current of 1.09 kA is
FIGURE 20-14
used, then again referring to Table 20-9, this scaling factor is reduced
to 0.828, which gives a discharge voltage of 604 × 0.828 = 500 kV.
Now, recalculate the discharge current, which increases to 1.148 kA.
From Eq. (20-9), the energy is 1033 kJ or 4.0 kJ/kV. This is well within
the capability of the station class surge arrester.
Approximately, the energy can be calculated from J = 0 . 5CE2,
where C is the total capacitance of the line. This gives 1157 kJ.
Example 20-2 In Example 5-6, a metal-oxide surge arrester of
258 kV is applied on the transformer primary; see also Fig. 5-32.
The EMTP simulation of power through the arrester is shown in
Fig. 20-14a and its histogram in Fig. 20-14b. The arrester has an
energy-handling capability of 7.2 kJ/kV, a total of 1857.6 kJ. The
(a) Power through the surge arrester, Example 20-2. (b) Histogram of the power through the arrester.
SURGE ARRESTERS
539
note that two surge arresters have been used in parallel. The surge
arresters for GIS are special, high-energy arresters (Chap. 19).
20-8 ARRESTER LEAD LENGTH AND
SEPARATION DISTANCE
F I G U R E 2 0 - 1 5 Reduction of secondary voltage magnitude and
oscillation frequency, Example 20-3. Compare this with Fig. 6-28; see text.
calculated energy absorbed by the arrester is 210.8 kJ, which is
a safe application. The arrester can discharge approximately six
surges of this nature.
Example 20-3 This is a continuation of Example 6-8. Figure 6-28
shows the high-frequency oscillations of secondary voltage of transformer T2, and furthermore this voltage is 7.65 times the rated
secondary voltage of 480 V. A secondary surge arrester in conjunction
with a 2-µF surge capacitor reduces this voltage magnitude to
1.71 per unit. Comparing Fig. 6-28 with Fig. 20-15, the oscillation
frequency is also reduced.
Example 20-4 In Example 18-1, the study of transients in a GIS,
the surge arrester currents SA1 and SA2 are shown in Fig. 18-17a
and 18-17b, respectively. The power through the surge arrester is
depicted in Fig. 20-16. It hits an instantaneous peak of 1.9 GW, and
FIGURE 20-16
The surge arresters are mostly connected line to ground. The lead
length is totaled on both sides of the arrester. The lead length may
be defined as the conductor length totaled on both sides of the
arrester housing and the ends of the leads of the protected equipment. This must be considered with respect to the point of surge
impact (Fig. 20-17). This figure clearly shows how the separation distance becomes lead length and vice a versa with respect to the point of
surge impact. In Fig. 20-17a, the separation distance is c and the lead
length is a + b. In Fig. 20-17b, the lead length is a + b + c. Note that the
dimensions (length of the arrester itself) are not included in the lead
length. Even a minor amount of stray inductance in the lead length
can create a significant voltage drop in the lead length due to rapid
rise in increase of current. The bends in the lead length add to this
inductance, and therefore, the leads to the arrester on the equipment
side and on ground side are run as straight and direct as possible. This
voltage drop affects the protection level provided by the surge arrester.
The voltage drop in the lead length is given by:
Vle = L le Sld
(20-10)
where Vle is the voltage drop across the lead in kV, Lle is the inductance of the lead length in µH, and Sld is the slope of the rise of
discharge current in kA/µs. Adding the voltage drop across the lead
length to ascertain a protective level with the arrester as installed
should modify the surge arrester discharge voltage.
20-8-1
Separation Distance
The separation distance is the length of connection separating the line
terminal of the arrester from the line terminal of the protected equipment. It should not be confused with the lead length (Fig. 20-17).
Transient power through the arrester, Example 20-4.
540
CHAPTER TWENTY
FIGURE 20-17
(a) and (b) To explain arrester lead length and separation distance with respect to the point of impact of the surge.
Separation distance becomes important when it is not possible to
locate the surge arrester directly at the terminals of the protected
equipment. It typically occurs in the substations and at transition
points between the OH and underground distribution.
On a lightning surge, the surge arresters operate in a few microseconds or less to affect voltage changes. These changes propagate
approximately at the speed of light, and the separation creates a
delay of some microseconds. The instantaneous surge voltage at
equipment terminals will therefore be different from that at the
arrester terminals. Therefore, the surge arrester effectiveness is
reduced with increasing separation.
If the separation distance exceeds a certain critical distance, its
effect on the equipment protective level must be investigated and
accounted for.
Example 20-5 The protective level of an arrester is 160 kV, and
separation plus lead length is 60 m from the equipment. Considering a propagation velocity of 300 m/µs, the travel time of the surge
for a distance of 60 m is 0.2 µs. Incident surge wave is of 200 kV/
µs. The incident wave will travel past the arrester unchanged, as it
is below the conduction threshold of the arrester. At t = 0.2 µs, it
arrives at the equipment, which can be considered an open circuit of
line for illustrative purposes, and is reflected back positively toward
the arrester. The rate of rise of voltage at the equipment is effectively
doubled. At t = 0.4 µs, the voltage wave arrives at the arrester terminals and the rate of rise is doubled. At t = 0.6 µs, the voltage reaches
conduction level of the arrester and a negative wave of 400 kV/µs
rate of rise is reflected toward the equipment. The negative wave
arrived at t = 0.8 µs is doubled and reflected back toward the
arrester. Because of negative polarity, the voltage at the equipment
terminals starts decreasing. Further reflections may cause a positive
sawtooth voltage, but the highest voltage at the equipment occurs
at 0.8 µs. Construction of a lattice diagram will facilitate the construction of sawtooth waveform shown in Fig. 20-18.
For a simple configuration, as shown in Fig. 20-19, with arrester
ahead of the equipment to be protected, the voltage at the equipment terminals can be determined from the following equation:
Vpe = Vpa + 2S f
d es + d a
λ
(20-11)
where Vpe is the voltage at the protected equipment in kV, Vpa is the
initial protective level of the surge arrester in kV, Sf is the rate of rise
of the front in kV/µs, des is the separation distance in m, da is the
lead length in m, and l is the propagation velocity in m/µs.
20-8-2 Reflections from Other Equipment
Reflections from other equipment can be accounted for by IEEE
method.5 This is particularly suitable for analyzing the effect of separation in transformer substations. The following explanations specify how
a two-transformer and three-line system configuration, Fig. 20-20a
and b, can be reduced to the simple equivalent circuit shown in
Fig. 20-19. The separation distance and the lead length should be
properly calculated. Refer to Fig. 20-20b for the following steps:
1. Remove the transformer that is not being considered for
surge protection. Assuming that surge protection of transformer T1 is of interest, transformer T2 is removed.
2. Identify junction between des, separation distance, and da,
the lead length, and the line that has an incoming surge. This
junction is “c” in Fig. 20-20.
3. Remove all lines connected to the lead length da, between
junction c and the arrester terminal. Thus, line 3 is removed.
4. Multiply rate of rise of incoming surge by 3/(n + 2), where
n is the number of lines remaining in service after the lines in
rule 3 are removed. Referring to Fig. 20-20b, n = 2.
SURGE ARRESTERS
FIGURE 20-18
541
Sawtooth voltage at the protected equipment, surge arrester located some distance away from the protected equipment, Example 20-5.
where Vt is the maximum stress allowed at the transformer and Vsa
is the voltage at the surge arrester from function point c to ground.
For calculation of inductance of lead length, a value of 4 µH/ft is
assumed. The separation distance is calculated from the curve in
Ref. 5 which gives 32.5 ft. This curve is approximated by the following analytical equation:
0 . 385(vV ) 0 . 957 BIL − V
sa
sa
D =
×
d
V
7
BIL
2
.
92
−
0
.
95
sa
sa
20-9
FIGURE 20-19
Example of surge protection with line terminated
at a single transformer (protected equipment), surge arrester located some
distance away from the protected equipment.
To calculate the maximum permissible separation, follow the
procedure shown in Example 20-6.
Example 20-6 In Fig. 20-20, lead length da is 71 ft and separation distance des is 29 ft. Arrester has a protective level of 254 kV at
a rate of rise of 900 kV/µs. Following rules 1, 2, and 3, transformer
T2 in Fig. 20-20 is removed, line L3 is removed, and according to
rule 4, the modified rate of rise is:
S f = 900 ×
The separation distance within which the equipment is protected
can be said to be dependent on the steepness of the incoming wave.
Let the surge impedance be 450 Ω, velocity of propagation v be
984 ft/µs, and BIL be 450 kV. Then calculate chopped-wave withstand (CWW) by using the following equation:
CWW = 1 . 1 BIL = 495 kV
di /dt = 2S f /Z = 3 . 0 kA/µs
L = d a × 0 . 4 = 28 µH
Vt = CWW/1 . 15 = 430 kV
Vt /Vsa = 1 . 27
APPLICATION CONSIDERATIONS
Figure 20-21 shows a general flowchart for application of surge
arresters. The importance of correct system data, study results of
overvoltages, equipment to be protected, and location of surge
arrester are the starting points. Tables 20-1 and 20-7 show that all
the characteristics of the arrester are based on the rated voltage of
the arrester. The flowchart in Fig. 20-21 shows the interrelatedness
of the activities and arrester parameters. The objective is to select
an arrester which will:
■
Provide required protective levels in the standards with
respect to the insulation strength.
■
Not be damaged when discharging the surges at the
required location.
3
3
= 900 × = 675 kV/µs
n+2
4
Vsa = Vpa + L(di /dt ) = 254 + 28 × 3 = 338 kV
(20-13)
(20-12)
■
Not operate under normal system operations. As discussed
earlier, the basic considerations are selection of MCOV, TOV,
switching surge energy discharged, the pressure relief current,
and effects of ambient temperature and altitudes.
■
Apply special considerations for use with capacitor banks,
GIS, electronic equipment, rotating machines, and even transformers; that is, dry-type transformers may require closer coordination of the surge protection devices due to, generally, lower
winding surge withstand capabilities.
20-9-1
Protective Levels
The protective level is the maximum crest voltage that appears across
arrester terminals under specified conditions. For gapless arresters,
542
CHAPTER TWENTY
FIGURE 20-20
(a) and (b) Two-transformer and three-line substation surge protection, calculation of maximum separation.
it is the arrester discharge voltage for a specified discharge current.
For gapped arresters, the protective level is the higher of the gap
sparkover voltage or discharge voltage. The following protective
levels are specified in ANSI/IEEE standards.3,5
FOW (Front-of-Wave Protective Level) This level is defined
as the higher of the FOW sparkover voltage for specified wave
shapes or arrester discharge voltage resulting with the application
of lightning impulse classifying current magnitude cresting in 0.5 µs.
The lightning impulse classifying currents are given in Table 20-11.
The currents are dependent on shielding. The table is for completely
shielded lines for some distance from the substations, which means
that predominant mechanism will be backflashovers. The arrester
current can be calculated from the following equation:
I = Ic =
3 . 84(ECFO − Ec )
Z0
(20-14)
where I is arrester discharge current in kA, Ic is arrester coordinating current in kA, ECFO is the positive CFO of insulation in kV, Ec is
arrester discharge voltage in kV, Z0 is single-phase surge impedance
of line, and factor 3.84 is the correction factor based on studies.5
The discharge currents in stations with nonshielded lines should
not be less than 20 kA. In severe thunderstorm areas, keraunic level
of 40 or more, higher levels may be desirable.
LPL (Lightning Impulse Protective Level) The higher value
of the lightning impulse sparkover for 1 . 2 / 50-µs lightning impulse
or arrester discharge voltage that results from an 8 / 20-µs wave.
The selection of the discharge current depends on the following:
■
The importance of the installation
■
The line insulation and grounding effects
■
The probability of occurrence of higher currents
SPL (Switching Impulse Protective Level)
The higher value
of the switching impulse sparkover or arrester discharge voltage
that results from a current wave with a time to crest of 45 to 60 µs or
gap sparkover from similar waves. The arrester coordinating current
for the switching surges is a complex function of the surge arrester
characteristics and the details of the system. The effective impedance
seen by the arrester during a switching surge can vary from several
hundreds ohms for arresters connected to OH lines to tens of ohms
for arresters connected near cables and capacitor banks.
20-9-2 Insulation Withstand
BIL, BSL, and CWW values are required for the insulation coordination. These may be taken from the relevant equipment standards.
Transmission and distribution line strength is described by CFO,
and a standard deviation of 5 percent of CFO. The BIL and BSL
may be conventional or statistical, CFO – 1.28 s (Chap. 17). Factors for estimating the withstand voltage of mineral-oil-immersed
equipment are provided in Ref. 5. The negative polarity lightning
impulse CFO is approximately 600 kV/m, and for the positive polarity it is 560 kV/m. Bus and line support insulators’ breakdown voltage
is about 1.3 to 1.4 times CFO.
20-9-3
Insulation Coordination with Surge Arresters
Two methods of insulation coordination are described:3,5
1. Tabulation of protective ratios (PRs) or margins (PMs)
2. Graphical representation
Three-Point Method
In this method, CWW, BIL, and switching surge withstand (BSL) are compared with the corresponding
defined protective levels. The basic assumption is made that the
SURGE ARRESTERS
FIGURE 20-21
Flowchart for application of surge arresters.
insulation will be protected over the entire range of lightning and
switching impulses, provided that the margin is adequate. Allowances for separation effects are included.
The following PRs are defined
PR L1S =
CWW
= PML1S = [PR L1S − 1] 100
FOW
PR L 2 S =
BIL
= PML 2 S = [PR L 2 S − 1] 100
LPL
PR s =
(20-15)
impulse, PRs is same,
are:
BSL
SPL
BIL
VT
≥ 1 . 15 . For switching
≥ 1 . 15 . The PM limits for coordination
PML1 ≥ 20
PML1S ≥ 15
PML 2 ≥ 20
PML 2 S ≥ 15
PM s ≥ 15
PM s ≥ 15
CWW
− 1 100
PM(1) =
(FOW + Ldi /dt )
The PR limits for coordination are:
PR L1 ≥ 1 . 2 PR L1S ≥ 1 . 15
(20-16)
PR s ≥ 1 . 15 PR s ≥ 1 . 15
PRL1S refers when there is significant separation. If time to crest is
equal to 2µs or less, PRWL1S = CWW ≥ 1 . 15where
VT is determined
,
VT
as in Example 20-6; otherwise, PR L2s =
(20-17)
For distribution system insulation coordination, the following
PMs are acceptable:
BSL
= PM s = [PR s − 1] 100
SPL
PR L 2 ≥ 1 . 2 PR L 2 S ≥ 1 . 15
543
(20-18)
PM(2) = (BIL/LPL − 1) 100
where di/dt is calculated by dividing the crest current by the time to
crest. Inductive voltage drop varies as a function of the magnitude
of the current impulse as well as its rate of rise. A 10 kA current
with rise time of 8 µs gives a voltage drop of 0.5 kV/ft, but with 1 µs
rise time, it becomes 4 kV/ft.
544
CHAPTER TWENTY
FIGURE 20-22
Typical volt-time curves for coordination of surge arrester protective levels with insulation withstand strength of liquid-filled
transformers.
In general, PM(1) and PM(2) should both be at least 20 percent.
For oil-filled, solid, or inorganic insulation, CWW can be assumed
1.15 times BIL, and for dry-type organic insulation, CWW can be
assumed equal to BIL.
The discharge voltage of an arrester is greater for less frequent high
crest lightning discharge surges and increases with higher rates of rise
of lightning current. Currents higher than 20 kA can be considered.
Graphical Coordination Curve Another method of insulation coordination is the graphical coordination curve comparison
method. Plot three points for the published voltages for the specific
arrester under consideration: (1) FOW, (2) LPL at the coordinating
current, and (3) switching surge protective level as a straight line. Connect the points with a curve of approximately the shape in Fig. 20-22,
for oil-filled transformers.5 If a manufacturer voltage-time sparkover
curve is available, it can be used instead of approximation. Draw a ladder of lines each extending from 5 to 10 µs at levels corresponding to
5, 10, and 20 kA. At 8 / 20-µs test wave, plot CWW, BIL, and SPL
curves. This is illustrated in the following example.
Example 20-7 For a 345-kV system nominal voltage, the data
for application are: maximum voltage = 362 kV, rated switching
impulse voltage = 2.5 per unit peak, temporary overvoltage =
1.5 per unit for 1.4 s, line length = 300 km, surge impedance = 350 Ω,
available short-circuit current = 40 kA rms symmetrical. The power
transformer to be protected has a BIL = 1050 kV, CWW = 1155 kV,
and BSL = 870 kV. Average ambient temperature = 40°C.
As the system is solidly grounded, an 80 percent arrester is selected.
This gives an arrester rated voltage of 276 kV. From Table 20-7, following are the arrester parameters:
MCOV = 224 kV rms
TOV = 325 kV rms
FOW = 730 kV crest
Switching surge protective level = 554 kV at 2-kA switching discharge current. To ascertain LPL, read from this table, the discharge
voltage kV crest for 8/20 µs wave at the qualifying current of 10 kA
for 345 kV voltage. This gives 646 kV.
Also, the arrester has an energy-handling capability of 8.9 kJ/kV,
pressure relief capability of 65 kA rms symmetrical, and can be located
in an average ambient temperature of 45°C without any derating.
Establish the base voltage in terms of arrester rated voltage =
(362 × 2 )/ 3 = 295 kV crest. Then, the switching surge is 740 kV
and temporary overvoltage is 0.96 per unit. Referring to Fig. 20-9,
the temporary overvoltage can be withstood for 9, 6, and 0.9 s with
no prior energy, 0.5 per unit prior energy, and 1.0 per unit prior
energy, respectively. This application is acceptable. Now, calculate
the switching energy for a surge of 745 kV, similar to Example 20-1.
This gives a switching current of 0.67 kA, and J = 1.80 kJ/kV. The
arrester has a capability of 8.9 kJ/kV.
The PRs can now be calculated:
PR(1) = 1155 / 730 = 1 . 58
PR(2) = 1050 / 646 = 1 . 62
PR(3) = 870 / 554 = 1 . 57
These exceed the minimum required values, and the application
is safe.
20-10
SURGE ARRESTER MODELS
Silicon carbide, gapless metal-oxide, and gapped metal-oxide models
are supported in EMTP type 99; pseudo-nonlinear resistance and type
92 piecewise linear resistance models can be used; however, type 92
ZnO model allows single or multiple exponential segments, gapped or
gapless arresters and is the preferred model for all arresters. Nonlinear
resistance segments can be modeled by the following equation:
V
i = p
Vref
q
(20-19)
where p and q are the characteristics of the arrester and Vref is arbitrary. It can be rated voltage, or maximum switching surge protective level (for switching surge model of the arrester). This is
depicted in Fig. 20-23.
Station Class Silicon-Carbide Arresters Switching surges
can be modeled with single exponential as follows:
Vref = 2Vrated
q = 14
p = 500[Vrated /Vsparkover ]14
p = 3000[Vrated /Vsparkover ]14
Vrated < 48 kV
Vrated > 48 kV
(20-20)
SURGE ARRESTERS
FIGURE 20-23
Modeling of metal-oxide surge arrester with discrete segments of different slopes.
Lightning surges can be modeled as follows:
Constants c, q, and a for
Metal-Oxide Surge Arrester
Models, EMTP Empirical
Parameters
TA B L E 2 0 - 1 3
Vref = 2Vrated
q = 14
(20-21)
p = 1000[0 . 7962 /S 0.1]14
ARRESTER-RATED
VOLTAGE (KV)
where S is steepness of the discharge current in kA/ms.
Station Class Metal-Oxide Arresters
Vref = 2Vrated
p = 1000[1 . 0 /c]q
q = 17 . 2, c = 1 . 292
q = 21, c = 1 . 306
Vrated = 5 4 to 360 kV
(20.23)
where c, q, and b are shown in Table 20-13.
Use of supporting program called ARRDAT from known VI
characteristics is the most popular model.
Lightning Surge Models Double exponential model is given by
the following equation:
f (t ) = Vm[e αt − e βt ]
(20-24)
The analytical equations for standard test wave shapes are given
in Chap. 5 and 19. Some disadvantages of the double exponential
model are that (1) it is only an approximation of measured lightning currents, (2) amplitude does not correspond to peak value of
the impulse, and (3) numerical problems, that is, subtraction of
two exponentials.
A single exponential model is given by:
i(t ) =
I 0 K n −t / τ
e
n 1+ Kn
K=
t
τ1
C
Q
a
60–360
3–10
10–40
1.454
1.182
31.1
8.2
17.7
17.7
396–588
3–10
10–40
1.500
1.350
52.0
16.9
17.3
17.3
stroke duration, time interval between t = 0 and point on tail where
amplitude falls to 50 percent of the peak value; I0 is the peak value;
and n is factor influencing rate of rise, typically n = 5 to 10.
For a 8/20-µs current wave, amplitude 10 kA:
Lightning surges can be modeled as follows:
p = 1000[1 . 0 /cS1/ β ]q
DISCHARGE CURRENT�
RANGE (KA)
(20.22)
Vrated = 396 to 444 kV
Vref = 2Vrated
545
(20-25)
where t1 is the wavefront time constant proportional to front duration, time interval between t =0 and wave peak; t is proportional to
I 0 = 10 kA
τ 1 = 8E6
τ = 20E6
(20-26)
Any lightning, switching or test wave shape, and ramp or
impulse can be modeled using analytical or graphical models, for
example, point-to-point wave model.
A more accurate model of metal-oxide surge arrester can be
generated for switching or lightning surges, using the manufacturer’s VI characteristics from the data in Tables 20-8 and 20-9.
As an example of generating this model for a 90-kV metal-oxide
surge arrester for the lightning impulses, scaling factors for
8/20-µs wave are specified in Table 20-9, from 1 to 40 kA, for the
voltage based on coordinating current of 10 kA. Two columns,
giving maximum and minimum scaling factors, are provided.
For conservatism, the maximum values are used. The result of
EMTP simulation of exponents and various segments is shown
in Fig. 20-24. For switching surge model, 36/90-µs data are
used. Therefore, an appropriate surge arrester model for the
type of surge involved should be applied. For fast transients,6,7
the model may consist of parallel capacitance and series inductance shunted by a resistor.
20-11
SURGE PROTECTION OF AC MOTORS
The surge withstand capability of motors is not so well defined. A
reasonable value of the impulse strength can be 125 percent of the
crest value of the factory high potential test.8 As the high voltage
546
CHAPTER TWENTY
FIGURE 20-24
An EMTP model derived based on 90-kV station class surge arrester, data as shown in Tables 20-7 and 20-9.
test is conducted for 1 min with a voltage equal to twice the rated
voltage of the machine + 1000 V, the BIL of motor windings is:
BIL = 1 . 25 2[Vnameplate + 1000]V
(20-27)
Now compare the BIL of a 4000-V rated motor with that of a
transformer and enclosed switchgear:
■
Motor BIL = 15.9 kV
■
Oil-filled transformer = 75 kV
■
Enclosed switchgear = 60 kV
This shows that compared to other electrical apparatus, the
motor BIL is low, and furthermore, the motor windings have a complex structure. Another factor that needs to be considered is that
medium-and-high voltage motors are normally controlled through
vacuum contactors, which may restrike.
20-11-1 Surge Protection of Vacuum Contactors
In Chap. 8, it was mentioned that the chopping current of vacuum
circuit breakers had been reduced, and the restrikes, common in
the initial development of vacuum technology, were prevented
by using better contact materials. However, we must distinguish
between the vacuum circuit breakers and contactors, as the latter
are more prone to restrikes. An area of possible multiple ignitions
is shown in Fig. 20-25 with respect to locked rotor current of the
motor (for application of motors up to 6.6 kV).9 The frequency
shown in this figure is given by:
fn =
1
2π LC
FIGURE 20-25
(20-28)
where L is ungrounded motor inductance at locked rotor condition, l is length of the cable connection from the contactor to the
motor, and Cv is capacitance of the cable per unit length (C = lCv).
Essentially Eq. (20-28) is a resonance formula of cable capacitance
with motor locked rotor reactance. Therefore, a certain length of
cable, if exceeded, can lead to reignition. This shows that (1) motor
insulation is more vulnerable to stresses on account of lower BIL
and (2) there is a possibility of restrikes in the switching devices. As
an example, for a 500-hp motor, overvoltage protection device is
needed if #4 shielded cable length, used to connect the motor to the
switching vacuum contactor, exceeds approximately 470 ft. This is
based on the cable data.
20-11-2
Motor Insulation
The motor insulation has two different functions: (1) there is insulation between turns, and then (2) a group of turns comprise a coil,
which has to be insulated from ground. It is impractical to employ
the same insulation between turns as the ground insulation of a
coil. The windings present a complex system of distributed inductance and capacitance. The response is entirely different to impulse
surges at high frequency, as compared to 60-Hz response. The surge
phenomenon can be viewed as a circuit problem based on transmission line theory. The propagation rate is much lower through
closely coupled winding in the slots of the magnetic material.
Akin to transformers, the voltage across the windings will not
be uniformly distributed and the first few turns will be severely
stressed. With respect to propagation velocity in the turns embedded in the slots (magnetic material), the propagation velocity is of
the order of 10 to 20 m/µs, and the velocity in the end windings
that overhangs in air can be ignored. This brings about the concept
of electrical length of a winding expressed as the time required for
the wave to transit from one end to another end of the windings.
Zone of probable restrikes in vacuum contactors, based on the motor locked rotor current and frequency of oscillation; see text.
SURGE ARRESTERS
547
The effectiveness of a capacitor connected at a point other than
the motor terminals will not be optimum. An incoming surge, before
the capacitor becomes effective, will be reflected back from the
motor terminals and will produce almost twice the rate of rise. The
following design basis parameters for the surges can be adopted:10
1. 10 kA, 4/10 µs current wave to simulate direct lightning stroke
2. 60 kV, 1.2/50 µs voltage wave to simulate indirect lightning
or induced lightning stroke
3. 1.5 kA, 8/20 µs current wave to simulate switching surge
F I G U R E 2 0 - 2 6 Effect of rise of surge voltage on the inter-turn voltage stress in motor windings versus motor core length.
Assume that a medium voltage motor has a core length of 0.5 m
and a propagation velocity of 10 m/µs. A crest of approximately twice
the rated motor voltage from line to ground, say 6800 V for a motor
of 4.16 kV, with a rise time to crest of 1 µs impacts the motor. Then,
the surge voltage between the first and second turn of the line terminal is 680 V. The steep-fronted waves concentrate on the first few
turns, and will be attenuated as they progress through the winding.
If the rise time of the wave is reduced, so does the voltage stresses on
the turn insulation (Fig. 20-26). The standard practice has been to
slope the impulse wave so that the time to reach the maximum voltage is 10 µs. The desired limitation is achieved by the application
of a surge capacitor at the motor terminals. A surge capacitor of size
0.5 µF has been commonly applied (Fig. 20-27).
Example 20-8 A 0.5-µF capacitor is applied at the motor terminals and incoming surge is 6800 V, with rise time 1 µs. Most
connections between the motor starter and motor will have surge
impedance of the order of 20 to 50 Ω. Considering a surge impedance of 50 Ω, the voltage builds up according to the following
equation:
Em = Es (1 − e −t / t′ )
(20-29)
where t′ is the time constant = RC = 25(10–6) s.
At t = t0, when the surge arrives at the capacitor terminals, the
voltage Em is zero and the current through the capacitor is 6800/50 =
136 A peak. Therefore, the rate of change, dEm/dt (maximum) =
136/(0.5 × 10–6) = 272 V/µs.
For surge duration of 5 µs, and from Eq. (20-29), the voltage
across the capacitor is 1233 V peak.
FIGURE 20-27
The capacitors will impact the initial rate of rise, while the surge
arresters do not. These are provided in parallel with capacitors to
limit the surge magnitude. A LC filter is suggested in Ref. 10. With
appropriate choice of components, the output from the filter, for
any of three types of surges, is reduced below the motor BIL for
motors of 480 to 5000 V. The inductor rating is of the order of 0.5
to 1 mH, and capacitor rating is 0.5 to 1 µF.
20-11-3
Machines Directly Connected to OH Lines
Figure 20-28 shows a protection scheme for the rotating machines
directly connected to the OH lines. The surge protection capacitors
and surge arresters are shown, both for the line and neutral side of
the motor. The neutral-side surge arrester and capacitor connected
between the common wye-connected neutral point of the motor to
ground may be required in some cases. In addition, a surge arrester
is shown on the line side. The arrester AL, along with arrester AM at
machine terminals and capacitor CS, reduces the voltage rate of rise
at machine terminals to a value so that the machine turn insulation
is protected. The arrester AL discharges much of surge current and
limits the voltage that is applied to the transmission line inductance.
The separation distance D is of consideration, and is a function of the
machine voltage class, system grounding, and ground resistance.
20-12
SURGE PROTECTION OF GENERATORS
Generators operating in synchronism with utility sources may
island due to a fault or disconnection, giving rise to overvoltages.
Conventionally, surge arresters paralleled with surge capacitors
are provided for the surge protection of the generators, located in
the generator line terminal compartment itself. A generator, whether
connected in a step-up transformer configuration, or bus connected
and operated in synchronism with the utility, can be subjected to
the following possible overvoltages:11
■
Power frequency overvoltages. Load rejection may leave the
generator connected to an OH line, cable, or capacitor, and this
situation can lead to self-excitation (due to energy absorbed in
Surge protection of a motor with a surge capacitor alone.
548
CHAPTER TWENTY
FIGURE 20-28
Surge protection of motors directly connected to an overhead line.
the system capacitance) and harmonic resonance may occur.
The overvoltage will depend on the exciter response and operating reactive power. Modern exciters may limit the voltage
to 1.05 per unit; however, the arrester on the high side of the
transformer will operate on these overvoltages, which may
reach two times or more.
If the time to half value is 400 µs, CFO is 2500 kV for 500-kV system, and surge impedance is 350 Ω, then surge current is 7.14 kA,
and the energy in the surge is:
■
A capacitor bank reduces the transient voltage caused by a lightning surge. An ungrounded bank ties the three phases together,
reducing the equivalent surge impedance and transient voltage
caused by the surge. A grounded wye-bank provides low impedance path, slowing the surge considerably. The energy dissipated in
the arrester can be estimated from:
A neutral resistor left out of service can result in ferroresonance overvoltages, involving the capacitance of generators
and potential transformers. These overvoltages may reach
2.4 per unit.
■
An HV to LV fault in the step-up transformer can present
large stresses in the generator.
E=
∫ vidt
(20-31)
(20-32)
If the discharge voltage of the arrester is assumed constant with
current, then approximately:
20-13 SURGE PROTECTION OF
CAPACITOR BANKS
Certain considerations for application of surge arresters to capacitor banks are enumerated in Chaps. 6 and 8. Surge arresters can
be used to provide protection for lightning transients, switching
transients, interruption of capacitor currents, recovery voltages,
restrikes, and capacitor switching.
Lightning surges Capacitor banks with neutrals grounded will
be charged by the lightning stroke current, and when protected by
a metal-oxide surge arrester, the arrester will limit this voltage to
its protective level. At the termination of stroke, the surge arrester
will cease to conduct, leaving some charge on the capacitor. The
discharge energy is of consideration. For an ungrounded capacitor
bank, relatively little energy is added to the capacitors and highdischarge energy surge arresters are not required.
Depending on the capacitor bank size and location, these may
be self-protecting, especially if surge arresters for lightning protection are provided to protect other equipment close to the capacitor
banks, and substation shielding is in place. In any case, a simulation is required considering substation layout, bus connections,
transformers, surge arresters, and capacitor banks. The energy on
backflashovers and shielding failures and its impact on overvoltages on capacitors can be estimated by detailed simulation.
An important factor is the origin of surge on the transmission
lines. Capacitor banks located in shielded substations will see a
surge propagated from a remote location, and the surge energy will
be small. The limiting magnitude of the surge current is:
CFO
I=
Z
Q = Iτ / 2 = 1 . 47C
(20-30)
E = v ∫ idt = vQ
(20-33)
For 1.47 C, as calculated in Eq. (20-31), and a surge arrester of,
say 276 kV, discharge voltage at 10 kA = 646 kV crest, the energy
in kJ/kV is 3.44, which is well within the capability of the arrester.
The arrester has a rating of 7 kJ/kV and is safely applied for a surge
having a charge of 3.5 C. The charge in a direct lightning stroke on
the conductor close to the location of capacitor bank can be higher.
Ungrounded wye-connected capacitor banks have very little effect
on the surge arrester.
Switching Surges In Chap. 6, some switching transients and
the overvoltages produced due to connection and disconnection of
the capacitor banks were discussed. In Chap. 8, current interruption, recovery voltages, and overvoltages due to breaker operation
in presence of a ground fault were discussed. The location of arresters to control these transients were also covered in these chapters.
Here, it is highlighted that for switching transients, irrespective of
neutral grounding and circuit configuration, the energy requirements of the arrester must be checked for proper application with
proper system modeling. The following equation may be used for
estimate purposes:
1
E = C(Vs2 − Vp2 ) J
2
(20-34)
where Vs is the surge voltage and Vp is the protective level of the
arrester. There may be a need for multiple-column arresters in certain applications.
SURGE ARRESTERS
549
With some reiteration of the discussions in earlier chapters, the
following areas indicate specific considerations:
4. To control overvoltage on inductively coupled lower voltage
systems, surge arresters are required; see Chaps. 6 and 14.
1. The capability of primary and backup switchgear to limit
TRV and possibility of restrikes. The breaker technology has
come a long way to produce restrike-free breakers, but this
possibility of a restrike cannot be entirely eliminated. Switching transient of various origins can occur, but restrikes result
in the highest arrester duty. The arresters minimize the risk of
restrikes and are an insurance against unforeseen resonant conditions. The worst-case scenario is a two-phase restrike, with
full charge on the capacitors due to a previous operation.
The transient voltage on capacitor bank and the recovery voltage across the switching device can be reduced during a restrike by
installing arresters on the capacitor side of the switching device. The
two-phase restrike can be considered as a conservative approach.
Connecting arresters line to ground on ungrounded capacitor banks
may not limit the overvoltages. Figure 20-29 shows that the arresters may be connected phase to ground, phase to neutral, or phase to
phase. For a particular application, in each of these cases, the arrester
characteristics, protective level, and durability on switching surges
can be calculated. In this figure, Vg is the phase-to-neutral voltage of
the system, Zg can be zero to infinity, Zs is the source impedance, the
switches show two-phase restrike, L is the series inductance, and C is
the capacitor bank, which in all three cases is shown ungrounded.
Figure 20-29a depicts arresters connected phase to ground, and
these do not limit the trapped charges on the capacitors, which
can be higher than 2.0 per unit. Figure 20-29b illustrates arresters
connected phase to neutral, and these can reduce the trapped charge
2. Higher phase-to-phase voltages on transformer windings
can occur when a capacitor is energized, and a transformer
remains connected to the capacitor on a radial line.12
3. To control voltages due to resonance when switching capacitors in series or parallel with transformers or other capacitors
at lower voltages, surge arresters are required; see Chap. 6.
F I G U R E 2 0 - 2 9 Surge protection of ungrounded wye-connected capacitor banks. (a) Surge arresters connected phase to ground. (b) Surge arresters
connected to an ungrounded neutral point and a surge arrester connected neutral to ground across neutral potential device. (c) Delta-connected surge arresters
for protection of phase-to-phase surges.
550
CHAPTER TWENTY
to a lower value, but the connection does not limit the neutral highfrequency overvoltages. A potential device is normally connected to
monitor the fuse failure or phase unbalance in capacitor banks, and a
surge arrester connected neutral to ground can be added (Fig. 20-29b).
This will reduce the recovery voltage across the switching device and
the possibility of a restrike. Figure 20-29c shows delta-connected
surge arresters. When a series reactor is provided, either to limit
inrush current or to form a single-tuned filter at some harmonic of
interest, location of the surge arrester at source side of the reactor,
point A in Fig. 20-29a, will not protect the capacitors. The voltage
may be as high as two times of that at the reactor.
The MCOV selection should be based on rms voltage in the presence of harmonics. Also on switching of capacitors, the overvoltages
can reach even 10 percent above system voltage for short duration.
Example 20-9 13.8 kV, 12 Mvar three-phase ungrounded wye,
capacitor bank, short-circuit level at 13.8 kV = 40 kA symmetrical
is simulated with two-pole restrikes of the switching device using
EMTP. Figure 20-30a shows phase-to-phase voltages, which escalate to 2.97 per unit, and the neutral voltage in Fig. 20-30b rises to
a peak of approximately 8 kV.
With 12.0-kV-rated metal-oxide surge arresters connected phase
to neutral and a 6-kV arrester between neutral and ground, as in
Fig. 20-29b, phase-to-phase voltages are reduced to maximum of
1.84 per unit (Fig. 20-31a). The power through the 12-kV surge
arrester in phase c is shown in Fig. 20-31b. The energy handled
is 5.04 kJ/kV. This exceeds the energy-handling capability of the
arrester which is 4 kJ/kV.
F I G U R E 2 0 - 3 0 (a) Two-phase restrike (without arcing), phase-to-phase overvoltages; wye-connected ungrounded capacitor banks, Example 20-9.
(b) Neutral-to-ground overvoltage.
SURGE ARRESTERS
551
F I G U R E 2 0 - 3 1 (a) Two-phase restrike (without arcing), phase-to-phase overvoltages; wye-connected ungrounded capacitor banks, with surge arresters,
Example 20-9. (b) Power through 12-kV arresters.
20-14
CURRENT-LIMITING FUSES
A current-limiting fuse (CLF) is designed to reduce equipment damage by interrupting the rising fault current before it reaches its peak
value. Within its current-limiting range, the fuse operates within
1/4 to 1/2 cycle. The total interrupting time consists of melting time
(sometimes called the prearcing time) and the arcing time. The letthrough current can be lower than the prospective fault current and
rms symmetrical available current can be lower than the let-through
peak current. Figure 20-32 shows the let-through characteristics of
CLFs. Note that the threshold current, or the critical current at which
the current-limiting action starts, point A in Fig. 20-32, depends on
the current rating of the fuse. A noteworthy feature is that the
let-through energy is much reduced, because of current limitation
and fast operating time of 1/4 to 1/2 cycle.
When a CLF operates in the current-limiting range, it abruptly
introduces a high resistance to reduce the fault current magnitude and duration. An arc voltage, much higher than the system
voltage, is generated, which forces the current to zero. The fusible
552
CHAPTER TWENTY
FIGURE 20-32
Let-through characteristics of current-limiting fuses.
element of nonhomogeneous cross section may be perforated or
notched and while operating, it first melts at the notches, because
of reduced cross-sectional area at the notch. Each melted notch
forms an arc, which lengthens and disperses the element material
into the surrounding medium. Controlling the size and shape of
notches controls the arcs in series, and hence the rate of rise of
the arc voltage and its magnitude. The voltage crests in a few hundred microseconds. The peak voltage occurs approximately at the
peak let-through current. This is illustrated in Fig. 20-33. This letthrough peak voltage must be limited in the design of the CLF to
meet ANSI/IEEE standard requirements13 (Table 20-14). For example,
for a 15-5 kV maximum rated voltage, the voltage peak should not
exceed 70 kV for CLF of rating less than or equal to 12 A, and
49 kV for CLF ≥ 12 A.
20-14-1 CLFs with Surge Arresters
Typically, for primary protection of substation transformers in industrial environment up to a certain kVA rating, CLFs are used. The UL
listing of less inflammable liquid-immersed transformers for indoor
installations is based on limiting the let-through energy that will be
released into a fault in the transformer. This limitation of energy
prevents explosion and damage to personnel and property.
At the same time, in these applications of CLFs, a surge arrester
may be present upstream of the transformer for protection of transformer feeder or close to the transformer. It is possible that the surge
arrester may be damaged due to operation of the fuse, because of
the high arc voltage that is generated. Figure 20-34 is an equivalent
circuit diagram for calculation of switching surge generated by the
operation of a CLF and energy diverted to surge arrester.
F I G U R E 2 0 - 3 3 Arc voltage generated on operation of a currentlimiting fuse. Curve (a) surge voltage, (b) peak surge current, (c) circuit
voltage, (d) short-circuit current.
To calculate the energy absorbed by the surge arrester, a difficulty arises as both the CLFs and the surge arrester have nonlinear voltage-current characteristics. Two solutions are possible,
graphical approach and EMTP simulation. For illustrative purposes,
a graphical method of calculation, followed by EMTP simulation
results, is illustrated.
SURGE ARRESTERS
TA B L E 2 0 - 1 4
Maximum Permissible Arc
Voltage of Current Limiting
Fuses
MAXIMUM PEAK ARC VOLTAGE (KV)
RATED MAXIMUM VOLTAGE
THROUGH 12 A
2.8
5.5
8.3
15.5
22.0
27.0
>12 A
13
25
38
70
117
123
9
18
26
49
70
84
553
where Es is energy stored in the system inductance in J, Ls is system
reactance in H, and Ilt is peak let-through current of CLF in A for
the available short-circuit current.
The system impedance can be approximately calculated from
the following equation:
Zs =
K 0Vlg
If
(20-37)
where K0 is overvoltage factor, Vlg is line-to-neutral voltage in kV
rms, If is fault current in kA, and Zs is system impedance.
The nonlinear characteristics of the fuse can be represented by:
1 . 75
I clf = K F Vclf
(20-38)
where Iclf is instantaneous fuse current in A, Vclf is instantaneous
fuse arc voltage in kV, and KF is fuse arc voltage constant. This constant
is given by:
KF =
I lt
V 1fa.75
(20-39)
where Vfa and Ilt have been defined earlier.
The current division between the surge arrester and fuse is
calculated by establishing the operating point on their VI curves.
Then, the arrester current is given by:
F I G U R E 2 0 - 3 4 Circuit configuration of a surge arrester due to
operation of a current-limiting fuse.
The peak arc voltage generated by a fuse should be corrected for
system operating voltage and short-circuit current.14 It is given by
the following expression:
Vfa = K v .K i .Vfm
(20-35)
where Vfa is actual fuse arc voltage in crest; Vfm is maximum fuse
arc voltage, from Table 20-14; Kv is voltage adjustment factor due
to nonhomogeneous nature of CLF; and Ki is current adjustment
factor based on the ratio of short-circuit current and critical current
of the fuse.
The maximum energy will be stored in the system inductance
at the instant the CLF begins to interrupt the fault current. When
the arc voltage and the system voltage are coincidental, the current
begins to be limited. This energy is given by:
Es =
1 2
LI
2 s lt
TA B L E 2 0 - 1 5
VOLTAGE
0
5
10
20
25
30
35.28
(20-36)
Division of Current Between
Surge Arrester and
Current-Limiting Fuse
Iclf
0
1113
3744
12591
18607
25600
34000
Ia
34000
32887
30256
21409
15393
8400
0
I a = I lt − I clf = I lt − K F V 1clf.75
(20-40)
A 200E CLF, rated voltage = 15.5 kV, is applied
for the primary (13.8 kV) protection of a 2500 kVA, 13.8 to 2.4-kV
transformer, and the 13.8-kV system is low resistance-grounded.
Overvoltage factor = 1.06, maximum arc voltage = 49 kV peak, as
per ANSI/IEEE standards, critical current from the fuse let-through
characteristics =6.5 kA rms (Fig. 20-32), and maximum system lineto-ground voltage Vlg = 8.45 kV. The available short-circuit current
at 13.8-kV system is 40 kA rms. The adjusted arc voltage Vfa =
35.28 crest, according to Eq. (20-35), all adjustment factors not
shown.
As the 13.8-kV system is resistance grounded, an arrester of
rated voltage of 15 kV is selected, characteristics as in Table 20-7.
The let-through current for a fault of 40 kA sym is 34 kA peak
(Fig. 20-32). From Eq. (20-36), the energy stored in the system
is 305 kJ. The 15-kV station class surge arrester has a single-shot
energy capability of 60 kJ. As the energy stored in the system is
greater than the energy-handling capability of the arrester, the division of energy should be calculated.15
From Eq. (20-39), KF = 34000/(35.28)1.75 = 66.57. The division
of current is shown in Table 20-15. Now, the VI characteristics of
the surge arrester based on data in Table 20-7 and arc voltage versus
Iclf of the fuse calculated in Table 20-15 can be plotted together, and
the crossing of these two characteristics gives the operating point.
This gives a voltage of 30 kV and current of 6 kA. Voltage in terms
of fuse arc generated voltage = 31/35.28 = 0.88, and current in
terms of fuse let-through = 6/34 = 0.176.
Another graph is needed to calculate the energy through the
arrester. This is plotted in Fig. 20-35. Enter the curve on the x-axis
at calculated value of 0.176, go to peak source voltage curve (per
unit of operating point voltage, maximum curve is for 0.7, while
the calculated value here is 0.88), and read off from the vertical
axis the arrester energy as a percentage of the total energy. Approximately 20 percent of the energy passes through the arrester, that
is 61 kJ, which is close to its maximum single-shot capability. An
EMTP simulation using Fig. 20-34 gives 66 kJ.
Example 20-10
554
CHAPTER TWENTY
FIGURE 20-35
Arrester energy versus initial current for metal-oxide surge arresters.
PROBLEMS
1. How does the surge protection of motors connected to OH
lines differ from those connected through small cable lengths?
2. Explain the limitations of gap-type arresters for protection
of capacitor banks.
3. Draw a freehand sketch of the waveform through a metaloxide surge arrester in (1) low-current region, less than 1 A
and (2) high-current region.
4. A gapless arrester is selected for a certain application. It
meets all the requirements of insulation coordination and PR
ratios, except the energy-handling capability. What can be
done? Discuss all the possible alternatives and their ramifications, say, Examples 20-9 and 20-10.
5. The following system data are provided for selection of a
surge arrester for a 138-kV system:
■
The system is solidly grounded.
■
The temporary overvoltages are 1.2 times lasting for 10 s.
■
The COG is 1.1 on a phase-to-ground fault, ground fault
clearance time = 1 s.
■
On load rejection, a temporary overvoltage of 120 percent
occurs for 5 s.
■
For selection of TOV, the prior energy is 0.5 per unit.
Using the tables in this chapter, select rated voltage, MCOV,
and TOV of a gapless metal-oxide arrester.
6. How is the maximum stability voltage related to TOV?
Which class of arrester, distribution, intermediate, or station is
better?
7. To obtain a better PM, the discharge voltage of a gapless
metal-oxide arrester is required to be reduced. What can be
done?
8. In Fig. 20-20, da = 40 m, des = 100 m, switching surge1000 kV/µs. Surge arrester discharge voltage at 10 kA = 284 kV
crest, line length = 300 km. What is the voltage at the
protected equipment (transformer T1)?
9. In Prob. 8, BIL of power transformer is 550 kV, system
voltage is 138 kV. Using the tables in this chapter, find CWW
and the gapless arrester-rated voltage, MCOV, TOV, FOW, and
calculate the three PRs. Are these within the acceptable limits
specified in IEEE standards?
10. In Prob. 9, plot the values similar to Fig. 20-22.
11. What is the limitation of a two-exponential model of a
surge arrester in EMTP?
12. Select a station class, gapless zinc-oxide surge arrester for
a 400-kV system based on the following data:
System solidly grounded, power frequency overvoltages =
1.07 per unit, TOV with 0.5 per unit prior energy, and a temporary overvoltage of 1.4 per unit for 1s. Maximum switching
surge level = 2 per unit, line length = 600 km, surge impedance = 400 Ω. Use the tables and figures in this chapter.
13. How do the phase-to-phase overvoltages at a remote location, connected through a transmission line, arise in capacitor
bank switching? What is the nature of phase-to-ground overvoltages? Will the voltages be higher or lower in a system with
high short-circuit power?
14. A single-tuned capacitor filter bank, wye-connected, has
ungrounded neutral. Draw a sketch showing the optimum
locations of the surge arresters. What is the purpose of a surge
arrester connected from the capacitor bank neutral to ground?
SURGE ARRESTERS
15. Plot the CLF and surge arrester VI curve in Example 20-10
and verify the operating point calculated in this example.
16. In Example 20-9, the size of the capacitor bank is increased
to 20 Mvar. Will it impact the phase-to-phase voltage profiles?
REFERENCES
1. ANSI/IEEE Standard C62.11, IEEE Standard for Metal Oxide
Surge Arresters for AC Power Circuits >1 kV, 2005 (IEEE
Standard C62.11a, 2008).
2. ANSI/IEEE Standard C62.1, Standard for Gapped Silicon
Carbide Arresters for AC Power Systems, 1989.
3. ANSI/IEEE Standard C62.2, Guide for the Application of
Gapped Silicon-Carbide Surge Arresters for Alternating Current
Systems, 1997.
4. M. V. Lat, “A Method for Performance Prediction of Metal Oxide
Arresters,” IEEE Trans. PAS, vol. 104, no. 10, pp. 2665–2675,
Oct. 1985.
5. IEEE Standard C62.22, Guide for Application of Metal Oxide
Surge Arresters for Alternating Current Systems, 1997.
6. D. W. Durbak, “Zinc Oxide Arrester Model for Fast Front
Surges,” EMTP Newsletter, vol. 5, no. 1, Jan. 1985.
7. W. Schmidt, J. Meppelink, B. Richter, K. Feser, L. E. Kehl, and
D. Qiu, “Behavior of Metal Oxide Surge Arrester Blocks to Fast
Transients,” IEEE Trans. PD, pp. 292–300, Jan. 1989.
8. IEEE Committee Report, “Impulse Voltage Strength of Rotating
Machines,” IEEE Trans. PAS, vol. 100, no. 8, pp. 4041–4053,
Aug. 1981.
9. S. F. Frag and R. G. Bartheld, “Guidelines for Application of
Vacuum Contactors,” IEEE Trans. IA, vol. 22, no. 1, pp. 102–108,
Jan./Feb. 1986.
10. S. M. Dillard and T. D. Greiner, “Transient Voltage Protection
for Induction Motors Including Electrical Submersible Pumps,”
IEEE Trans. IA, vol. IA-23, no. 2, pp. 365–370, Mar./Apr. 1987.
11. E. P. Dick, B. K. Gupta, J. W. Porter, and A. Greenwood,
“Practical Design of Generator Surge Protection,” IEEE Trans.
PD, vol. 6, no. 2, pp. 736–743, Apr. 1991.
12. P. Kirby, C. C. Erven, and O. Nigol, “Discharge Capacity of Metal
Oxide Valve Elements,” IEEE Trans. PD, pp. 1656–1665, Oct. 1988.
13. ANSI Standard C37.46, ANSI Specifications for Power Fuses
and Disconnect Switches, 1981.
555
14. M. V. Lat, Application Guide for Surge Arresters on Distribution
Systems, Research Report H3Z 2p9, Canadian Electrical Association, 1988.
15. J. C. Das, “Coordination of Lightning Arresters and Current
Limiting Fuses,” IEEE Trans. IA, vol. 38, no. 3, pp. 744–751,
May/Jun. 2002.
FURTHER READING
J. E. Harder, A. E. Hughes, and J. Vosicky, “Analytical Method for
Coordination of Surge Arresters with Current Limiting Fuses,” IEEE
Trans. IA, vol. IA-17, no. 5, pp. 445–453, Sep./Oct. 1981.
A. R. Hileman and K. H. Weck, “Protection Performance of Metal
Oxide Surge Arresters,” Electra, pp. 133–146, Dec. 1990.
IEC Standard 60099, Part 4, Metal Oxide Surge Arresters Without
Gaps for AC Systems, 2006–07.
IEC Standard 60099, Part 5, Selection and Application Recommendations, 2000–03.
IEEE Switchgear Committee and Surge Protective Devices Working Group, IEEE Trans. PAS, vol. PAS-91, pp. 1075–1078, May/Jun.
1972.
IEEE Standard C62.23, IEEE Application Guide for Surge Protection of Electric Generating Plants, 1995.
IEEE Standard 1299/C62.22.1, IEEE Guide for the Connections of
Surge Arresters to Protect Insulated Shielded Electrical Power Cable
Systems, R2003.
IEEE Working Group 3.4.11, “Modeling of Metal Oxide Surge
Arrester,” IEEE Trans. PD, pp. 302–309, Jan. 1992.
IEEE Working Group 3.4.17, “Impact of Shunt Capacitor Banks on
Substation Surge Environment, and Surge Arrester Applications,”
IEEE Trans. PD, vol. 11, no. 4, pp. 1798–1807, Oct. 1996.
D. W. Jackson, “Analysis of Surge Capacitor Lead Connections
for the Protection of Motors,” IEEE Trans. PAS, vol. 103, no. 9,
pp. 2605–2611, 1984.
R. A. Jones and H. S. Fortson, Jr., “Considerations of Phase-to-Phase
Surges in the Application of Capacitor Banks,” IEEE Trans. PD, vol. 1,
no. 3, pp. 240–245, Jul. 1986.
M. P. McGranaghan, W. E. Reid, S. W. Law, and D. W. Gresham,
“Overvoltage Protection of Capacitor Banks,” IEEE Trans. PAS,
vol. 103, no. 8, pp. 2326–2336, Aug. 1984.
NEMA LA-1, Surge Arresters, 1999.
J. Osterhout, “Comparison of IEC and U.S. Standards for Metal Oxide
Surge Arresters,” IEEE Trans. PD, pp. 2002–2006, Oct. 1992.
This page intentionally left blank
CHAPTER 21
TRANSIENTS IN
GROUNDING SYSTEMS
The grounding systems can be studied under two classifications:
(1) system grounding and (2) equipment grounding. System grounding refers to the electrical connection between the phase conductors and
ground and dictates the manner in which the neutral points of wyeconnected transformers and generators or of artificially derived neutral systems through delta-wye or zig-zag transformers are grounded.
The equipment grounding refers to the grounding of the exposed
metallic parts of the electrical equipment, which can become energized and create a potential to ground—say due to a breakdown of
insulation or fault—and can be a potential safety hazard. The safety
of the personnel and human life is of importance. Also in the previous chapters we noted that the grounding of lightning arresters,
low-voltage surge protection devices, and tower footing resistance
impact the performance, backflashovers, and control of overvoltages.
Thus, low resistance of grounding systems is important on both the
counts—personal safety and system considerations. Ninety percent of
the soil in the United States has a resistivity of approximately 90 Ω-m
. Low resistance in soils of high resistivity can be achieved by special
devices and soil treatment, as is demonstrated in Example 21-3. The
methods of system grounding are:
■
Solidly grounded systems
■
Low-resistance grounded systems
■
High-resistance grounded systems
■
Reactance grounded systems
■
Ungrounded systems
We can add resonant grounding systems (reactance fault neutralizers) to this categorization, and we will briefly study the characteristics of
each of these grounding systems. Figure 21-1 shows basic connections
of various grounding methods. Table 21-1 summarizes the grounding
methods with respect to system voltage levels, though variations do exist.
The system grounding also varies in various parts of the world, according
to the established engineering practices in a country.
21-1
SOLID GROUNDING
In a solidly grounded system, there is no intentional impedance
between the system neutral and ground. A power system is solidly
grounded when the generator, power transformer, or grounding
transformer neutral is directly connected to the ground. Note that a
solidly grounded system is not a zero impedance circuit due to the
sequence impedances of the grounded equipment itself. These systems, in general, meet the requirements of an “effectively grounded”
system in which ratio X0 /X1 is positive and less than 3.0 and ratio
R0 /X0 is less than 1, where X1, X0, and R0 are the positive-sequence
reactance, zero-sequence reactance, and zero-sequence resistance,
respectively. The coefficient of grounding was defined in Chap. 9.
To recapitulate, COG is the ratio of ELg /ELL in percentage, where
ELg is the highest rms voltage on an unfaulted phase, at a selected
location, during a fault effecting one or more phases to ground and
ELL is the rms phase-to-phase power frequency voltage obtained at
that location with the fault removed. These systems are, generally,
characterized by COG of 80 percent. Approximately, a surge arrester
with its rated voltage calculated on the basis of the system voltage
multiplied by 0.8 can be applied. We will consider solidly grounded
systems in two distinct situations in the following sections.
21-1-1 Grounding of Utility EHV, HV, and
Distribution Systems
The utility systems at transmission, subtransmission, and distribution levels are solidly grounded. The main reason for this is that on
occurrence of a ground fault, enough ground fault current should
be available to selectively trip the faulty circuit. The utility generators, connected in step-up configuration to a generator transformer,
are invariably high resistance grounded (Fig. 21-1). If a generator
neutral is left ungrounded, there is a possibility of generating high
voltages through inductive-capacitive couplings (see Sec. 21-3).
Ferroresonance can also occur due to the presence of generator PTs.
The utility substations serving large chunks of power at high
voltages for industrial plants through delta-wye transformers have
wye windings low-resistance grounded. The most common secondary voltages of distributions for the industrial plants are 13.8 kV,
4.16 kV, and 2.4 kV.
21-1-2
Low-Voltage Industrial Distribution Systems
The low-voltage systems in industrial power distribution systems
used to be solidly grounded. However, this trend is changing and
high resistance grounding is being adopted. The solidly grounded
557
558
CHAPTER TWENTY-ONE
model because of spasmodic nature of the arc fault. This is due to
elongation and blowout effects and arc reignition. Arc travels from
point to point and physical flexing of cables and structures can
occur. Arcing faults can exhibit low levels because of the impedance of the arc fault circuit itself. Arcing faults can be discontinuous
requiring a certain minimum voltage for reignition. The limits of
the acceptable damage to material for arc fault currents of 3000 to
26000 A in 480-V systems have been established by testing1,2 and
are given by the following equation:
Fault damage ∝ (I )1.5 t
(21-1)
where I is the arc fault current and t is the duration is seconds.
VD = K s (I )1.5 t(in )3
(21-2)
where Ks is the burning rate of material in in3 /As1.5, VD is acceptable
damage to material in in3, I is the arc fault current, t is the duration
of flow of fault current, and Ks depends upon type of material and
is given by:
Ks = 0.72 × 10–6 for copper
= 1.52 × 10–6 for aluminum
= 0.66 × 10–6 for steel
(21-3)
1
NEMA assumes a practical limit for the ground fault protective
devices, so that:
(I )1.5 t 250I r
(21-4)
Ir is the rated current of the conductor, bus, disconnect, or circuit breaker to be protected.
Combining these equations, we can write:
VD = 250K sI r
FIGURE 21-1
Methods of system grounding.
systems have an advantage of providing effective control of overvoltages, which become impressed or are self-generated in the
power system by insulation breakdowns and restriking faults. Yet,
these give the highest arc fault current and consequent damage
and require immediate isolation of the faulty section. Single-lineto-ground fault currents can be higher than the three-phase fault
currents. These high magnitudes of fault currents have twofold effect:
■
Higher burning or equipment damage
■
Interruption of the processes, as the faulty section must be
selectively isolated without escalation of the fault to unfaulted
sections
The arcing faults are caused by insulation failure, loose connections, or accidents. The arc behavior is difficult to predict and
(21-5)
As an example, consider a circuit of 4000 A. Then the NEMA
practical limit is 1.0 × 106 (A)1.5 s and the permissible damage to
copper, from Eq. (21-5) is 0.72 in3. To limit the arc fault damage
to this value, the maximum fault clearing time can be calculated.
Consider that the arc fault current is 20 kA. Then, the maximum
fault clearing time, including the relay operating time and breaker
interrupting time, is 0.35 s. It is obvious that vaporizing 0.72 in3 of
copper on a ground fault, which is cleared according to established
standards, is still determinant to the operation of the equipment.
Shutdown and repairs will be needed after the fault incidence.
The arc fault current is not of the same magnitude as the threephase fault current, due to voltage drop in the arc. In the low-voltage
480-V systems, it may be 50 to 60 percent of the bolted three-phase
current, while for medium-voltage systems it will approach threephase bolted fault current, but somewhat lower. An arcing fault
releases incident energy measured in cal/cm2, and this can cause
fatal body burns to a worker who may happen to be maintaining the electrical apparatus. In recent times, there has been much
emphasis on limiting the arc flash hazard, calculating it precisely,
and using appropriate personal protective equipment (PPE) for
personal safety and avoiding fatal arc-flash burns. This subject
is not discussed here and an interested reader may see Refs. 3
and 4.
Due to high arc fault damage and interruption of processes, the
solidly grounded systems are not in much use in the industrial distribution systems.
However, ac circuits of less than 50 V, circuits of 50 to 1000 V
for supplying premises wiring systems, and single-phase 120/240-V
control circuits must be solidly grounded according to NEC.5
Figure 21-2 shows a sustained arc fault current in a 3/16-in gap
in a 480-V three phase system.2 Experimentally, an arc is established
TRANSIENTS IN GROUNDING SYSTEMS
TA B L E 2 1 - 1
System Grounding with Respect to Voltage Levels
SYSTEM GROUNDING METHODS
IMPEDANCE
SYSTEM VOLTAGE
SOLID
Extra high voltage, > 345 kV
LOW R
HIGH R
REACTANCE
RESONANT
X
High voltage, 115 to 230 kV
X
Medium voltage, 2.4 to 69 kV, utility systems
X
Medium voltages, 2.4, 4.16, 13.8, 23.0 kV,
industrial systems
X*
X
Medium voltages, 2.4, 4.16 kV, industrial systems
X
Low voltages < 1000 V
X
Circuits < 50 V, control circuits 120/240 V
(single phase) and circuits of 50–1000 V for
premises wiring, as per NEC
X
X
Utility generators connected through
step-up transformers
Industrial bus-connected generators
X
X†
X‡
X‡
*
X§
Not in common use in the United States; some European countries and Russia use this method. Generally applied at 15 kV and above for
distribution systems.
†
For small single-phase machines and three-phase machines on low-voltage and medium-voltage systems, say up to 1000 kVA.
‡
Grounding of bus-connected industrial generators through low resistance typically to limit the ground current to 200 or 400 A has been a
common practice. Recent trends are toward hybrid grounding—a combination of HR and low-resistance grounding.
§
Not in common use in the United States.
The ungrounded systems are not shown in this Table, as these are not in use. In a power system, tripping of a grounded source may result
in a section of the system becoming ungrounded. Appropriate protective measures are required, for example, protection through neutral
displacement tuned voltage relays to 60 Hz. Possibility of ferroresonance exists in this scenario.
FIGURE 21-2
Arc fault in a 3/16-in gap, 480-V system.
559
560
CHAPTER TWENTY-ONE
between phase c of the bus and ground, and a current of 1100 A flows.
After three-cycle, phase a is involved and the arc current for two-line
to enclosure is 18,000 A. Arc energy equals 7790 kW-cycles.
21-2
RESISTANCE GROUNDING
An impedance grounded system has a resistance or reactance connected in the neutral circuit to ground, as shown in Fig. 21-1. In
a low-resistance grounded system, the resistance in the neutral circuit is so chosen that the ground fault is limited to approximately
full-load current or even lower, typically 200 to 400 A. The arc fault
damage is reduced, and these systems provide effective control of
the overvoltages generated in the system by resonant capacitiveinductive couplings and restriking ground faults (see Sec. 21-3).
Though the ground fault current is much reduced, it cannot be
allowed to be sustained, and selective tripping must be provided to
isolate the faulty section. For a ground fault current limited to 400 A,
the pickup sensitivity of modern ground fault devices can be even
lower than 5 A. Considering an available fault current of 400 A
and the relay pickup of 5 A, approximately 98.75 percent of the
transformer or generator windings from the line terminal to neutral
are protected. This assumes a linear distribution of voltage across
the winding. (Practically, the pickup will be higher than the low set
point of 5 A.) The incidence of ground fault occurrence toward the
neutral decreases as square of the winding turns. Medium-voltage
distribution systems in industrial distributions are commonly lowresistance grounded.
The low-resistance grounded systems are adopted at medium
voltages, 13.8 kV, 4.16 kV, and 2.4 kV for industrial distribution
systems. Also industrial bus-connected generators are commonly
low-resistance grounded. An industry practice has been, generally, to limit the fault current to 400 A, or lower in some cases. A
recent trend in industrial bus-connected medium-voltage generator
grounding is hybrid grounding system.6
21-2-1 High-Resistance Grounded Systems
High-resistance grounded systems limit the ground fault current to
a low value, so that an immediate disconnection on occurrence of
a ground fault is not required. It is well documented that to control
over voltages in the high-resistance grounded systems, the grounding resistor should be so chosen that
Rn =
Vln
3I c
(21-6)
where Vln is the line-to-neutral voltage and Ic is the stray capacitance
current of each phase conductor. Figure 21-3 shows transient voltage in percent of normal line-to-ground crest voltage versus the
resistor kW/charging capacitive kVA. The transients are a minimum
when this ratio is unity. This leads to the requirement of accurately
calculating the stray capacitance currents in the system.7 Cables,
motors, transformers, surge arresters generators all contribute to
the stray capacitance current. Surge capacitors connected line to
ground must be considered in the calculations. Once the system
stray capacitance is determined, then, the charging current per
phase, Ic, is given by:
V
I c = ln
X c0
(21-7)
where Xc0 is the capacitive reactance of each phase, stray capacitance considered lumped together.
This can be illustrated with an example. A high-resistance
grounding system for a wye-connected neutral of a 13.8–0.48
kV transformer is shown in Fig. 21-4a. This shows that the stray
capacitance current of all the distribution system connected to the
secondary of the transformer is 0.21 A per phase, assumed to be
FIGURE 21-3
Overvoltages versus ratio of resistor kW/charging kVA.
balanced in each phase. Generally, for the low-voltage distribution systems, a stray capacitance current of 0.1 A per MVA of
transformer load can be taken, though this rule of thumb is no
substitute for accurate calculations of stray capacitance currents.
Figure 21-4a shows that under no fault condition, the vector sum
of three capacitance currents is zero, as these are 90° displaced with
respect to each voltage vector, and therefore, 120° displaced with
respect to each other. Thus, the grounded neutral does not carry
any current and the neutral of the system is held at the ground
potential, Fig. 21-4b. As:
I c1 + I c2 + I c 3 = 0
(21-8)
no capacitance current flows into the ground. On occurrence of a ground
fault, say in phase a, the situation is depicted in Fig. 21-4c and d.
The capacitance of faulted phase a is short-circuited to ground. The
faulted phase, assuming zero fault resistance is at the ground potential (Fig. 21-4d), and the other two phases have line-to-line voltages
with respect to the ground. Therefore, the capacitance current of
the unfaulted phases b and c increases proportional to the voltage increase, that is, 3 × 0 . 21 = 0 . 365 A. Moreover, this current in
phases b and c reverses and flows through the transformer windings
and sums up in the transformer winding of phase a. Figure 21-4e
shows that this vector sum = 0.63 A.
Now consider that the ground current through the grounding
resistor is limited to 1 A only. This is acceptable according to Eq. (21-6)
as the stray capacitance current is 0.63 A. This resistor ground current also flows through transformer phase winding a to the fault
and the total ground fault current is I g = 12 + 0 . 632 = 1 . 182 A
(Fig. 21-4e).
The above analysis assumes a full neutral shift, ignores the fault
impedance itself, and assumes that the ground grid resistance and
the system zero-sequence impedances are zero. Practically, the neutral shift will vary (Fig. 21-5).
Fault Detection, Alarms, and Isolation As the ground fault
currents are low, special means of fault detection and isolation are
required. Figure 21-6a and b show this. In Fig. 21-6a, alarm/trip
can be provided through neutral-connected voltage relays, device
59, connected across a part of the neutral grounding resistor.
TRANSIENTS IN GROUNDING SYSTEMS
561
FIGURE 21-4
(a) and (b). The stray capacitance currents and voltages in a low-voltage wye-connected high-resistance grounding system under
no-fault conditions. (c) The flow of capacitance and ground currents, phase a faulted to ground. (d ) Voltages to ground for phase a grounded. (e) Phasor
diagram of summation of capacitance and resistor currents.
capacitive current. The sensitive ammeter can monitor the capacitive current in each feeder and indicate the state of the system by
monitoring the capacitance current.
Figure 21-6b shows a ground fault localization scheme, popular
in the industry and called a “pulsing-type high-resistance grounding system.” The pulses are created by a current sensing relay and
cyclic timer, 62, at a frequency of approximately 20/min by alternatively shorting and opening a part of the grounding resistor through
a contactor. These can be traced to the faulty circuit with a clip-on
ammeter.
Advantages of HR Systems Some obvious advantages are:
■
The resistance limits the ground fault current and, therefore,
reduces burning and arcing effects in switchgear, transformers,
cables, and rotating equipment.
FIGURE 21-5
Phase-to-phase and phase-to-ground voltages on a
line-to-ground fault, with varying degree of neutral shifts.
This relay should preferably be a rectifier type of relay to sense harmonic currents that may flow through the ground resistor. Consider
a feeder ground fault; the flow of capacitive and resistive components of the current are shown in Fig. 21-6a. The sensitive ground
fault sensor and relay on each unfaulted feeder see the capacitive
current related to that feeder only, but the sensor and relay on the
faulted circuit see total ground fault current less the feeder’s own
■
It reduces mechanical stresses in circuits and apparatus carrying fault current.
■
Reduces arc blast or flash hazard to personnel who happen
to be in close proximity of ground fault.
■
Reduces line-to-line voltage dips due to ground fault and
three-phase loads can be served.
■
Control of transient overvoltages is secured by proper selection
of the resistor.
562
CHAPTER TWENTY-ONE
FIGURE 21-6
(a) Alarm and fault detection system in a high-resistance grounded system. (b) Pulsing-type high-resistance grounding system and fault
detection.
Limitation of HR Systems The limitation of the system is that
the capacitance current should not exceed approximately 10 A to
prevent immediate shutdowns. As the system voltage increases, so
does the capacitance currents. This limits the applications of HR
system to systems of rated voltages of 4.16 kV and below.
Though immediate shutdown is prevented, the fault situation should not be prolonged, the fault should be localized and
removed. There are three reasons for this:
1. Figure 21-4d shows that the unfaulted phases have voltage
rise by a factor of 3 to ground. This increases the normal
insulation stresses between phase-to-ground. This may be of
special concern for low-voltage cables. If the time required
to deenergize the system is indefinite, 173 percent insulation
level for the cables must be selected.8 However, NEC does not
specify 173 percent insulation level, and for 600-V cables,
insulation levels correspond to 100 and 133 percent. Also
Ref. 8 specifies that the actual operating voltage on cables
should not exceed 5 percent during continuous operation and
10 percent during emergencies. This is of importance when
600-V nominal three-phase systems are used for power
distributions. The dc loads served through six-pulse converter
TRANSIENTS IN GROUNDING SYSTEMS
systems will have a dc voltage of 648 and 810 V, respectively,
for 480 and 600-V rms ac systems.
2. Low levels of fault currents if sustained for long time may
cause irreparable damage. Though the burning rate is slow,
the heat energy released over the course of time can damage
cores and windings of rotating machines even for ground currents as low as 3 to 4 A. This has been demonstrated in test
conditions.9
3. A first ground fault left in the system increases the probability of a second ground fault on other phase. If this happens,
then it amounts to a two-phase-to-ground fault with some
interconnecting impedance, depending upon the fault location.
The potentiality of equipment damage and burnout increases.
21-3
UNGROUNDED SYSTEMS
In an ungrounded system, there is no intentional connection to
ground except through potential transformers or metering devices
of high impedance. In reality, an ungrounded system is coupled
to ground through distributed phase capacitances. It is difficult to
assign X0 /X1 and R0 /X0 values for ungrounded systems. The ratio
X0 /X1 is negative and may vary from low to high values and COG
may approach 120 percent. These systems provide no effective control of transient and steady-state voltages above ground. A possibility
of resonance with high-voltage generation, approaching 5 times or
more of the system voltage exists for values of X0 /X1 between 0 and
–40. For the first phase-to-ground fault, the continuity of operations
can be sustained, though unfaulted phases have 3 times the normal
line-to-ground voltage. All unremoved faults, thus, put greater than
normal voltage on system insulation and increased level of conductor
and motor insulation may be required. The grounding practices in
the industry are withdrawing from this method of grounding.
If an inductor of certain size gets connected to ground, then
the possibility of high voltages exist, as the overvoltage is given by:
Vov =
XL
V
X co / 3 − X L t
(21-9)
FIGURE 21-7
563
where Vt is the applied terminal voltage, XL is the inductance of
the grounded inductor. Figure 21-7 shows three possible cases of a
high inductance that may get connected to a phase and give rise to
resonant voltages.
1. The coil of a motor starter may be inadvertently connected
between phase and ground due to a ground fault.
2. A fuse can operate in one phase due to a ground fault, this
connects the reactances of the other two phases in parallel
between phases and ground.
3. A broken grounded conductor on the load side of the transformer connects reactances of two phases in parallel between
phase and ground.
The phenomena of arcing grounds and resulting overvoltages
which may escalate to 5 to 6 times the normal rated voltage can
be explained with reference to Fig. 21-8. It is somewhat similar to
restrikes discussed in Chap. 8. Intermittent ground faults can give
rise to these phenomena.
Figure 21-8a shows normal voltage vectors rotating counterclockwise. Consider that phase a is grounded, as shown in
Figure 21-8b. The current in a capacitor is zero when the voltage is at
its peak, and therefore at the instant shown in Fig. 21-8b the capacitance is charged to the line voltage and the current is zero, thus the
arc tends to extinguish. During the next half cycle, as the voltage
vectors rotate, the phase a voltage changes from zero to twice the
line voltage, dotted lines. This value of line-to-ground potential of
phase a may be sufficient to break down the gap in the ground fault
circuit, which got extinguished half cycle before. Thus, a pulse current flows and the phase a voltage may swing between plus and
minus 2 times the rated voltage at a frequency of 20 to 100 times
the fundamental, due to presence of reactance in the circuit. If it
was a solid metallic connection between phase a and ground, it
would leave the phase a conductor at ground potential. Associated
with the transitory oscillation of the voltage, there will be a corresponding oscillatory charge current. This transient charging current
or restrike current will again reach zero when the system voltage
triangle is at its maximum excursion in the negative direction (lower
Connections of an inductance to ground for faults in ungrounded systems.
564
CHAPTER TWENTY-ONE
FIGURE 21-8
(a), (b), and (c). Illustration of arcing grounds in ungrounded systems and consequent development of high voltages.
part of Fig. 21-8c). In the next half cycle as the voltage vectors
rotate further, the phase a voltage will escalate from –2 to –4, as
indicated in lower part of Fig. 21-8c. This increases voltage across
the gap, which may again result in a restrike. Also see capacitor
restrikes discussed in Chap. 8.
establishments. A disadvantage of the system is that the resonant
tuning can change due to switching conditions, that is, when a part
of the system may be out of service or when the system expansion
takes place. This grounding method is not common in the United
States, though sometimes used in Europe (Sweden) and Russia.
21-4
21-4-2 Artificially Derived Neutrals
REACTANCE GROUNDING
In reactance grounding, a reactor is connected between the system
neutral and ground, the magnitude of the ground fault current that
will flow depends upon the size of the reactor. The ground fault
current should be at least 25 percent and preferably 60 percent of
the three-phase fault current to prevent serious transient overvoltages (X0 < or equal to 1.0X1). This current is considerably higher
than in a resistance grounded system, and the reactance grounding
is not an alternative to resistance grounding. The system is generally used for grounding of small generators, so that the generator
ground fault current does not exceed three-phase fault current and
three-phase four-wire loads could be served. Reactance grounded
systems are not common in the United States.
21-4-1
Resonant Grounding
Figure 21-1 also shows a resonant grounding system, ground-fault
neutralizer. A reactor can be connected between the neutral of a
system and ground and tuned to the system charging current so that
the resulting current is resistive and of low magnitude. This current
is in phase with the line-to-neutral voltage, so that the current and
voltage zeros occur simultaneously. The system is used for voltages
above 15 kV, consisting of overhead transmission or distribution
lines. The system is rarely used for industrial and commercial
Many times it is required to ground delta-connected transformer
windings and other ungrounded separately derived systems. A neutral can be artificially derived in a delta-connected system with zigzag transformer or a wye-delta-connected grounding transformer.
Figure 21-9a shows a zigzag transformer. Windings a1 and a2 are
on the same limb and have the same number of turns, but are
wound in opposite directions. The zero-sequence currents in the two
windings on the same limb have, therefore, canceling ampere turn
effect. The impedance to the zero sequence currents is that due to
leakage flux of the windings. For the positive and negative sequence
currents, neglecting magnetizing currents, the connection has infinite impedance. Figure 21-9b shows distribution of zero-sequence
currents on a ground fault ahead of a zigzag transformer. A wye-delta
grounding transformer circuit can be similarly drawn. The neutrals
of large utility generators directly connected to the step-up transformers (GSUs) are not directly connected to ground through a high
resistance but through a distribution transformer which is loaded
on the secondary windings with a grounding resistor. An example
will clarify the calculations.
Example 21-1 The example illustrates deriving an artificial neutral through a wye-delta grounding transformer in a delta-connected
system. Figure 21-10a shows a 5-MVA, 34.5 to 2.4-kV, delta-delta
TRANSIENTS IN GROUNDING SYSTEMS
565
FIGURE 21-9
(a) Flow of ground fault currents in the windings of a zig-zag transformer. (b) Application of a zig-zag transformer to derive an artificial
neutral and current flows for a downstream ground fault.
transformer serving industrial motor loads. The wye-delta distribution grounding transformer is loaded with a secondary resistor.
Given that the capacitance charging current of the system is
8 A, and the system and equipment data is as shown in Table 21-2,
it is required to calculate the value of the resistor to limit the ground
fault current to 10 A. Neglect transformer resistance and source
resistance. The ground current has to be higher than the capacitance current Eq. (21-6).
The connection of sequence networks is shown in Fig. 21-10b
and the given impedance data is reduced to a common 100-MVA
base, as shown in Table 21-2. Note that the zero sequence impedance of the motors is infinite as the motor wye-connected neutrals
are left ungrounded. This is the common practice in the United
States. (This contrasts with grounding practices in some European
countries, where the motor neutrals are grounded.) The source
zero-sequence impedance can be calculated based on the assumption of equal positive and negative sequence reactances. The motor
voltage is 2.3 kV, and therefore its per unit reactance on 100-MVA
base in per unit is given by:
16 . 7
1 . 64
2.3
= 9 . 35
2.4
2
Similarly, the grounding transformer per unit calculations
should be adjusted for correct voltages:
1. 5 2. 4
X0 =
= 75
0 . 06 2 . 4 / 3
2
The equivalent positive and negative sequence reactances
are: 1.41 per unit (pu) each. The zero-sequence impedance of
the grounding transformer is 50 + j75 per unit. The total fault current should be limited to 10 – j8 = 12.80 A. Thus, the required
impedance is:
2400 / 3
= 324 . 8 Ω
Zt =
12 . 8 / 3
The base ohms (100-MVA base) = 0.0576. The required Zt =
324.8/ base ohms = 5638.9 per unit. This shows that the system
positive and negative sequence impedances are low compared
to the desired total impedance in the neutral circuit. The system
positive and negative sequence impedances can, therefore, be
neglected.
566
CHAPTER TWENTY-ONE
G
(a)
3.1 Ω
FIGURE 21-10
(b)
(a) System configuration for Example 21-1, derivation of an artificial neutral through wye-delta transformer. (b) Connection of
sequence networks.
TA B L E 2 1 - 2
EQUIPMENT DESIGNATION
System Data for Example 21-1
GIVEN DATA
PER UNIT SEQUENCE IMPEDANCE ON A 100-MVA BASE
34.5-kV source
Three-phase fault level = 25.1 kA, single line-to-ground
fault 20 kA (symmetrical values)
Xs 1 = Xs 2 = 0.067
Xs 0 = 0.116
34.5-kV, 5-MVA transformer,
delta-delta connected
X1 = X2 = X0 = 8% on 5-MVA base
Xt 1 = Xt 2 = Xt 0 = 1.60
2.3-kV 1800-hp (1640-kVA)
motor load
Locked rotor reactance = 16.7%
Xm 1 = Xm 2 = 9.35
(Note 1)
Xm 0 = infinite
Grounding transformer, 60-kVA,
wye-delta connected 2400:120V
X0 = 1.5%
R0 = 1.0%
X0 = 75
R0 = 50
Note: Negative sequence impedance of a rotating machine is not the same as positive sequence impedance. Here an assumption is made for simplicity of calculations;
subscripts 1, 2, 0 refer to positive, negative, and zero sequence impedances.
IR0 = 10/3 =3.33 A. Therefore, ZR0 = (2400/ 3)/3.33 = 416.09
Ω = 416.09/ base Ω = 7223.9 per unit. The additional resistor to
be inserted is:
2
− R tG0
R R 0 = Z R2 0 − X tG0
= 7223 . 92 − 752 − 50
= 7173 . 5 pu
where R R0 is added resistor, Z R0 is total impedance in ground circuit,
X tG0 and R tG0 are reactance and resistance of the grounding transformer, Fig. 21–10b.
Multiplying by base ohms, the required resistance = 413.2 Ω.
These values are in symmetrical component equivalents. In actual
values, referred to 120-V secondary, the resistance value is:
120
RR =
413 . 2 × 3 = 3 . 1 Ω
2400
2
TRANSIENTS IN GROUNDING SYSTEMS
If we had ignored all the sequence impedances, including that
of the grounding transformer, the calculated value is 3.12 Ω. This
is often done in the calculations for grounding resistance for highresistance grounded systems, and all impedances, including that of
the grounding transformer, can be ignored without appreciable error
in the final results. The grounding transformer should be rated to permit continuous operation, with a ground fault on the system. The
per phase grounding transformer requirement is 2.4 (kV) × 3.33 (A) =
7.92 kVA, that is, a total of 7.92 × 3 = 23.76 kVA. The grounding
transformer of the example is therefore adequately rated.
21-5 GROUNDING OF VARIABLE-SPEED
DRIVE SYSTEMS
A brief reference can be made to the grounding of variable-speed
drive systems (VSD) systems, where special considerations apply.
Consider a three-phase, six-pulse bridge rectifier circuit (Fig. 21-11).
Only two phases conduct at a time, and the dc plus and negative
voltages to mid-point are shown. These voltages do not add to
zero and the mid-point oscillates at thrice the ac supply system
FIGURE 21-11
567
frequency. The dc positive and negative buses have common mode
voltages and its magnitude changes with the firing angle. The peak
of the voltage is approximately 0.5 Vln, where Vln is the peak line-toneutral point input voltage.
Figure 21-12 shows common mode voltages on the motor isolated neutral-to-ground of a 4160-V drive system GTO inverter.
The peak line-to-ground Vl-g voltage is 4100 V and the waveform
has a frequency of 60-Hz. The peak neutral-to-ground voltage is
2500 V and has a frequency of 180 Hz. The operation of the output
bridge creates a common mode voltage by exactly the same mechanism as the input bridge does, where the back emf of the motor is
analogous to the line voltage.
Thus, the worst-case condition for the common mode voltage is
no-load, full speed operation, as the phase-back angle is 90° for both
the converters, and the motor voltage is essentially equal to the line
voltage. The sum of both common mode voltages is approximately Vln
at six times the input frequency. Since the input and output frequencies
are generally different, the motor experiences a waveform with beat
frequencies of both input and output frequencies, and there will be
instances when twice the rated voltage is experienced, (Fig. 21-12).10
Generation of common mode voltage in a six-pulse converter.
568
CHAPTER TWENTY-ONE
FIGURE 21-12
Common mode neutral-to-ground and line-to-ground voltages in a CSI for a drive system.10
The grounding must ensure that the motor insulation system is
not stressed beyond its design level. Figure 21-13 shows three possible methods. In Fig. 21-13a output drive isolation transformer is
provided with its secondary grounded. The transformer primary
winding insulation can tolerate the common mode voltage swings
better than the motor insulation. This option is tricky as the drive
isolation transformer is subjected to residual dc offset in the drive
and high harmonic content passing through the transformer windings. A better location for the drive isolation transformer would
be at the input line end (Fig. 21-13b), and the secondary winding
TRANSIENTS IN GROUNDING SYSTEMS
569
F I G U R E 2 1 - 1 3 (a) Isolation transformer with grounded secondary to withstand common mode voltage. (b) Drive isolation transformer at input,
common mode voltage across transformer secondary. (c) Input line reactor, common mode voltage across drive motor windings.
is left ungrounded. The neutral of the filter capacitors on the output
of the inverter provides a convenient place to ground the load side
of the inverter and a small resistor rated 1 A or so is enough to do it.
The line-to-neutral voltages must, then, be taken into account for the
insulation of the secondary of the transformer. Also the cables from
the transformer secondary to the input rectifier bridge must be rated
for higher voltage to ground; for example, for a 4.16-kV drive system,
cables with 173 percent insulation level will be required; alternatively, 8-kV cables can be used.
An input or output drive transformer increases the cost and
reduces the efficiency of the drive system. In a transformer-less
GTO drive system, a line reactor may be used on the input side to
affect commutation notches, but the motor insulation must withstand twice the normal voltage stress to ground (Fig. 21-13c).
21-6
GROUNDING FOR ELECTRICAL SAFETY
One of the major objectives of grounding is the safety of the personnel and to ensure freedom from dangerous electrical shock voltage
exposure. This becomes of greater importance in utility high-voltage
substations, as the high-voltage systems are solidly grounded and
the fault currents are high. We can categorize as follows:
1. Utility substations in isolation, that is, located far away from
the loads served
2. Utility substations located within the premises of industrial
distribution systems
3. Industrial systems in isolation, that is, located away from
the utility substations
Let us first concentrate on Situation 1 above. IEEE Standard
80-2000, “Guide for Safety in AC Substation Grounding”11 is the main
document addressing this subject and the methodology described in
this standard is widely used in the United States; though it has some
limitations which we will discuss in the sections to follow. Due to
complex and iterative nature of the grounding system design, the
computer programs are invariably used for calculations using IEEE
method and other methods like finite element methods. The criteria
for safety are described in the following section.
21-6-1
Criteria for Safety
The shock situation is illustrated in Fig. 21-14. On occurrence of
a ground fault, the potential of the local earth rises with respect to
the remote earth. This is shown as ground potential rise (GPR) in
Figure 21-14, and is simply given by GPR = IG RG, where IG is the
current returning through grid to earth and RG is the grid resistance.
The calculation of IG is not so simple. It is not the bolted fault current at the location. All the available ground fault current does not
give rise to GPR, and a split factor is applicable depending upon the
number of sky wires, tower footing resistance, soil resistivity, connections to grounding conductors, and remote and local grounds,
which is discussed further in Section 21-6-2.
Figure 21-14 shows that the safety criteria are to establish safe step
and touch voltages in the grounding grid area during a fault, when
someone may be walking in the substation or touching a grounded
metallic frame or structure. Also transferred voltage must be considered. (Note the profile of the potential with respect to grounding grid
conductors buried at a certain depth below the soil.) All these voltages are shown in this figure and are defined as step voltage, touch
voltage, mesh voltage, and transfer voltage. These are discussed in
the following sections.
Step Voltage The step voltage is defined as the difference in surface potential experienced by a person bridging a distance of 1m
with his feet, without contacting any other grounded object. This
is given by:
Estep,50 = (1000 + 6Cs (hs , K )ρ s ) 0 . 116 / t s
Estep,70 = (10 0 0 + 6Cs (hs , K )ρ s ) 0 . 157 / t s
(21-10)
570
CHAPTER TWENTY-ONE
FIGURE 21-14
Shock hazard situation, step, touch, mesh, and transfer voltages, and GPR. The figure is adapted from ANSI/IEEE Std. 80.11
where Estep,50 and Estep,70 signify the tolerable limits for a body weight
of 50 and 70 kg, respectively.
Touch Voltage The touch potential is defined as the potential
difference between the ground potential rise and the surface potential at the point where a person is standing while at the same time
having a hand in contact with a grounded structure. This is shown
as Et in Fig. 21-14 and is given by:
Etouch,50 = (1000 + 1 . 5 Cs (hs , K )ρ s ) 0 . 116 / t s
Etouch,70 = (1000 + 1 . 5 Cs (hs , K )ρ s ) 0 . 157 / t s
(21-11)
where Etouch,50 and Etouch,70 signify the tolerable limits for a body
weight of 50 and 70 kg, respectively. An explanation of Eqs. (21-10)
and (21-11) follows.
These equations are derived from the tolerable limits of shock hazard current that can pass through the human body without a shock
hazard. (The threshold of fibrillation is 107 mA rms for a body weight
of 70 kg, and the equations use a lower value of 91 mA rms.)
The surface resistivity of the soil, denoted by rs, is an important parameter in the equations. The higher the surface resistivity,
the greater will be the tolerable step and touch potentials and
more economical the grounding grid design. In all grounding grid
designs, it is a standard practice to increase the surface resistivity
by installing crushed rock to a depth of 4 to 6 in (hs = depth of
the crushed rock) throughout the substation area. Table 21-3 gives
the resitivity of some materials used in the substations. Consider,
for example, that the natural soil has a resistivity of 90 Ω-m. If the
surface material #3 in Table 21-3 is used, the surface resistivity
improves to 3000 Ω-m. Therefore, we observe that:
■
To have low ground grid resistance, a lower soil resistivity is
desirable.
■
To have increased step and touch voltages for personal
safety, a higher surface soil resistivity is desirable.
■
Crushed rock treatment of higher soil resistivity on top of lowresistivity soil meets these two conflicting requirements.
Factor Cs =1 for no protective surface layer. When a surface layer
of crushed rock of higher resistivity is installed compared to the bare
soil, then Cs < 1. The factor Cs considers derating the nominal value of
the surface resistivity material, based upon thickness of the rock layer
that is laid in the substation. An expression for Cs from Ref. 11 is:
Cs =
n =∞
Kn
1
1+ 2 ∑
2
0 . 96
n =1 1 + (2nh s / 0 . 08)
(21-12)
where K, the reflection factor is given by:
K=
ρ − ρs
ρ + ρs
(21-13)
where ρ is the resistivity of natural soil, without surface treatment.
Values of Cs are plotted in a graph form in Ref. 11, not reproduced
here.
The Shock Duration The higher the time for which the ground
fault is sustained, the lower will be the tolerable step and touch
potentials and more difficult the grid design. Thus, high-speed fault
clearance is an important factor. In Eqs. (21-10) and (21-11), ts is the
shock duration in s. The shock duration is conservatively chosen
considering the ground fault clearance time (relay operating time
plus breaker interrupting time). For safety and conservatism, it is
assumed that the primary ground fault protection fails to operate
and the fault is cleared in backup protection zone with additional
time delay. Fault clearance times used in the calculations generally
TRANSIENTS IN GROUNDING SYSTEMS
TA B L E 2 1 - 3
571
Resistivity of Substation Surface Materials
RESISTIVITY (W-m)
NO.
SURFACE MATERIAL
WET
1
Crusher run granite with fines
140 × 10
1300
2
#57 washed granite similar to 3/4 in gravel
190 × 106
8000
Clean limestone slightly coarser than #2
7 × 10
2000–3000
Washed granite similar to 3/4 in gravel
2 × 10
5
Washed granite similar to pea granite
40 × 10
5000
6
Crushed aggregate base granite (with fines)
Varies
500–1000
7
Concrete
2000–10000
50–100
8
Concrete
1200–280000
21–63
9
Asphalt
Varies
10000
10
Asphalt
2 × 106–30 × 106
10000–6 × 106
3
4
vary from 0.25 to 0.5 s. As stated in Ref. 11 this time may be much
higher for smaller substation and may approach 3 s. This defines all
the terms in Eqs. (21-10) and (21-11).
Mesh Voltage Again referring to Fig. 21-14, the mesh voltage Em
is defined as the maximum touch voltage to be found within a mesh
of the grounding system. The maximum touch voltage is equal to the
mesh voltage.
Transfer Voltage The transferred voltage Etrrd is a special case
of the touch voltage, where a voltage is transferred into or out of
the substation due to metallic connections. These include buried
pipe lines close to the substation, cable racks, grounded shields of
cables, and cable trays, entering and leaving the substation. On a
first thought, isolation of local and remote grounds seems to be an
alternative to prevent problems of transferred potentials. Practically,
this is not attempted. Sometimes, insulting barriers are installed in
the substation fences, but to isolate all metallic connections coming
in and getting out of a substation is not practical. The couplings can
take place through the soil also, as discussed in Section 21-9.
Again, referring to Fig. 21-14, consider that the module of
placement of grid conductors is reduced by installing another grid
conductor in between the existing two grid conductors. Then the
consequent change in the surface potential profile is as shown in
the dotted lines. Obviously the step, touch, and mesh potentials are
all reduced. Thus, on a simplistic basis, an effective grounding grid
design optimizes the grid conductors and their placement modules.
21-6-2
DRY
Design Parameters of Grounding Grids
Soil Resistivity Measurements The soil resistivity at the
site of location is an important criterion for design of the grounding grid. The GPR is given by the ground fault current that flows
through the earth and the resistance of the grounding grid plays an
important role. Depending upon the soil resistivity, special electrodes
and soil treatment may become necessary to have an acceptable grid
resistance. The soil resistivity over a given area will be rarely uniform
and will vary with the depth, moisture content, type of earth, that is,
bedrock, wet organic soil, sandy loom, etc. The soil resistivity is measured using Wenner’s Four-Pin method or by laboratory testing of soil
borings at different depth; the former method is commonly used.
These measurements at different depths will form a sort of scatter
plot and a least square line can be fitted by computer programs (App.
F). A two-layer soil model results, which breaks soil resistivity into
two numbers, with respect to the depth of the soil. Figure 21-15a
and b shows the equivalent soil resistivity for two-layer soil models,
6
6
6
10000
3
commonly used for substation designs. Note that the IEEE calculations are based on a single-layer model.
The Worst Ground Fault Current The maximum of the singleline-to-ground or double-line-to-ground fault bolted current and
their X/R ratios are required. In Chap. 9 we studied the calculations
of unsymmetrical fault currents. The available ground fault current
in a system depends upon the method of system neutral grounding.
In the calculations of worst ground fault currents, the resistance of
the ground grid is often ignored. A single line-to-ground fault is
given by the expression:
I=
3E
(R1 + R 2 + R 0 + 3R f + 3R g )2 + ( X1 + X 2 + X 0 )2
(21-14)
where Rg is the ground grid resistance and Rf is the fault resistance.
The expressions for double line-to-ground fault are in Chap. 9. A
worst grounding fault is that which gives the maximum flow of
zero-sequence current. This depends upon the relative values of the
sequence impedances. For Z0 Z1 > Z22, the single line-to-ground fault
current will be higher, for Z0 Z1 < Z22, double line-to-ground fault
will be the worst type of fault, Figure 9-1.
The ground grid resistance and fault resistances are ignored in
the fault calculations for the grounding grid designs.
The Split Factor Consider the following scenarios:
1. There is no ground connection of the neutral at the local
substation (e.g., a delta transformer high-voltage primary
windings). For a ground fault on the high-voltage side, all the
ground fault current must flow to the remote-grounded neutral.
2. There is no remote ground, and the high-voltage primary
winding neutral is grounded locally only. The entire fault current will circulate locally and none flows to the remote ground.
3. For a situation where both the neutrals at local and remote
substations are grounded, the fault current will split, partly
flowing through the local ground and partly returning to the
remote ground, the split factor depending upon the relative
ground resistances.
Practically, the situation with respect to split factor is more complex. The ground wires of the transmission lines are normally connected to station ground and these divert a considerable amount
FIGURE 21-15
than the top layer r1.
572
(a) Resistivity of two-layer soil model, lower layer r2 of higher resistivity than the top layer r1. (b) Lower layer r2 of lower resistivity
TRANSIENTS IN GROUNDING SYSTEMS
FIGURE 21-16
Flow of earth current through an earth wire.
of current from the ground. A similar effect occurs when pipes
and cables are buried and their sheaths and armor are in effective contact with the ground. Figure 21-16 shows flow of current
through a ground wire and this forms a sort of ladder network.
If the line is sufficiently long it behaves with the source like an
equivalent impedance independent of length. Also see the distribution of ground current in multiple grounded distribution
systems, (Chap. 19).
Endrenyi12 reduces the tower impedances and ground wires
in identical spans to an equivalent impedance. In the matrix
method,13 an impedance matrix is derived for each span of the
line. Dawalibi14 provides algorithms for deriving simple equations to solve for current in each tower. Meliopoulos15 introduces an equivalent conductor to represent effect of earth using
Carson’s formula (App. D). Thus, the techniques that model the
phase conductors, ground wires, tower footing resistance in detail
will give the best determination of the split factor Sf. Apart from
EMTP, other computer programs are available for the calculation
of the split factor. These are, for example, SMECC (EPRI report
EL-2682/216 developed by EPRI and PATHS, developed for EPRI).
PATHS was developed to simulate faults on the transmission lines,
but has been used to find the grounding grid current for simple
substations. The IEEE Std. 8011 includes simplified curves for calculating the split factor, based on the calculated grid resistance,
number of transmission and distribution lines with ground wires,
and whether the current is contributed solely from the remote
sources or local/remote sources and also tower footing resistance.
These curves are not reproduced here.
Sizing the Grid Conductor and Connectors The short-time
temperature rise of the conductor can be obtained from the following equation by Sverak:17
TCAP K + T
I = 5 . 0671 . 10−6 A
ln 0 m
t cαr ρr K 0 + Ta
573
1/ 2
(21-15)
where I is the rms current in kA, A is the conductor cross section in
circular mils, Tm is the maximum allowable conductor temperature
in °C, Ta is the ambient temperature in °C, Tr is the reference temperature of material constants in °C, α0 is the thermal coefficient
of resistivity at 0°C, αr is the thermal coefficient of resistivity
at reference temperature—ar = 0.00393 for annealed soft copper
wire, conductivity 100 percent, ρr is the resitivity of the ground
conductor at reference temperature Ta in µΩ-cm = 1.7241 at 20° C
for annealed soft copper wire, K 0 = 1/α0 = 234 for soft annealed
copper wire at 0° C, tc = time of current flow in s, TCAP = thermal
capacity factor = 3.422 J/cm 3 /°C for soft annealed copper.
TCAP for various description of grounding conductors is given
in Ref. 18.
For mechanical reasons, a conductor size less than 2/0 AWG
is not used, and generally the minimum size of conductor in
high-voltage substations is 4/0 AWG. The connectors must meet
the same criteria as the conductors, that is, corrosion resistance,
electrical conductivity, current-carrying capability, and mechanical strength. Standards define the test performance requirements. Connectors may be brazed type, using a brazing method,
the filler material melts above 450°C; exothermic welded type;
and pressure type. The maximum temperature rise limit Tm
is 450°C for brazed connections and 350 to 250°C for bolted
connectors.
The Grid Resistance The grid resistance is given by:
Rg =
ρ
4
π ρ
+
A L
(21-16)
where L is the total length of the buried conductor and A is the area
of the grid in square meters.
This shows that there is an upper limit to the reduction of the
grid resistance in a certain given area by increasing the length of
the buried conductor. For grid depths between 0.25 and 2.5 m, the
following expression can be used:
1
1
Rg = ρ +
L
20 A
1
1 +
1 + h 20/A
(21-17)
574
CHAPTER TWENTY-ONE
Total resistance of the grid with conductors and ground rods is
given by:
Rg =
Maximum Step and Touch Potentials The mesh and step
voltages are given by:
Em = ρ K m K i IG / L
2
R1R 2 − R12
R1 + R 2 − 2R12
(21-18)
(21-25)
The geometric factor Km is given by:
where R1 is the resistance of grid conductors,
R1 = (ρ1 /π l1 )[ln(2l1 /h′ + K1(l1 / A ) − K 2]
Es = ρ K s K i IG / L
(21-19)
Km =
1 D 2 ( D + 2h )2 h K ii
8
ln
+
− +
ln
2π 16hd
8 Dd
4d K h π (2n − 1)
(21-26)
R2 is the resistance of ground rods,
R 2 = (ρa / 2nπ l2 )[ln(8l2 /d 2 ) − 1 + 2K1(l2 / A )( n − 1)2]
(21-20)
R12 is the mutual resistance between the group of grid conductors
and group of ground rods,
R12 = (ρa /π l1 )(ln(2l1 /l2 + K1(l1 / A ) − K 2 + 1)
(21-21)
The terms used in the above equations are defined below:
r1 is the soil resistivity encountered by grid conductors buried
at depth h Ω-m, ra is the apparent soil resistivity seen by ground
rod in Ω-m, H is the thickness of upper soil layer in m, r2 is the soil
resistivity from depth h downward in Ω-m, l1 is the length of grid
conductors in m, l2 is the length of ground rods in m, h is the depth
of grid burial in m, h′ = d1h for conductors buried at depth h, or
0.5d1 for conductors at earth surface, A is the area of grid in m2, n is
the number of ground rods, K1 and K2 are the constants related to
the geometry of the system,11 d1 is the diameter of grid conductor
in m, d2 is the diameter of ground rods in m, a is the short-side of
grid in m, and b is the long side of grid in m.
When the tops of the rods are at the same depth as the grid
conductors
ρa = l2 (ρ1ρ2 )/ρ2 (H − h ) + ρ1(l2 + h − H )
The Maximum Grid Current
(21-22)
The maximum grid current is
given by:
IG = C p D f S f I g
(21-23)
Kii = 1 for grids with ground rods along the perimeter, or for grids
with ground rods in the corners, as well as both along the perimeter
and throughout the grid area.
K ii =
1
(2n )2 / n
for grids with no ground rods or for grids with only a few ground
rods, none located in the corners or on the perimeter.
K h = 1 + h / h0
(21-28)
where h0 is the 1-m, reference depth of the grid, D is the spacing
between parallel conductors in m, h is the depth of burial of the
grid conductors in m, n is the number of parallel conductors in one
direction, and d is the diameter of the grid conductor in m.
Ki is the corrective factor for the mathematical grid model:
K i = 0 . 656 + 0 . 172n
(21-29)
For grids with ground rods, Em can be written as:
Em =
ρI G K m K i
Lc + 1 . 15Lr
(21-30)
where Lc is the total length of the conductor and Lr is the total
length of the ground rods. For grids with only a few ground rods,
change the denominator to Lc +Lr.
Step Voltage In Eq. (21-25) the L = Lc + 1.15 Lr or L = Lc + L r.
Similar qualifications apply for Emesh. For burial depths 0.25 m <
h < 2.5 m:
Ks =
11
1
1
+ (1 − 0 . 5n−2 )
+
π 2h D + h D
(21-31)
The step voltage can now be calculated by Eq. (21-25).
21-6-3
where Df is the decrement factor for the entire duration of the fault
current, to account for the asymmetry in the ground fault current:
(21-27)
Limitations of the Simplified Equations
There are certain assumptions in deriving the above equations as
discussed in Ref. 11. For square or rectangular grids:
n ≤ 25
T
− 2t / T
D f = 1 + a (1 − e f a )
t
f
1/ 2
(21-24)
where Ta is the effective X/R ratio of the system subtransient impedance, tf is duration of fault, sf is the split factor, Ig is the ground fault
current.
The factor Cp considers the future changes in the system, which
may give rise to higher ground fault currents. The split factor can
be defined as the ratio of grid current divided by 3I0
0 . 25 m ≤ h ≤ 2 . 5 m
d < 0 . 25 h
(21-32)
D > 2. 5 m
For equally spaced rectangular grids, the value of n for determining factor Ki and Km for mesh voltage Em should be:
n = na nb
(21-33)
TRANSIENTS IN GROUNDING SYSTEMS
where na and nb are the number of conductors in each direction.
For calculating the step voltage, the value of n for Ki and Ks is the
maximum of na and nb.
Example 21-2 This example is a hand calculation of a grid
design to illustrate the iterative process and complexity of these
calculations. Consider the design with the following given
parameters:
2. Calculate tolerable step and touch potentials.
The touch and step potentials can be calculated based on
the soil resistivity r =270 Ω/m , top layer of limestone rs =
3000 Ω/m:
K=
Area of the rectangular grid = 84 × 57 m.
Soil resistivity = 270 Ω-m. (Practically, it will rarely be
uniform and the two-layer soil model is derived from the
measurements.) Here we will consider a uniform soil resistivity.
This can be an arithmetic average of the measurements for
illustrative purposes.
Surface material is clean limestone with, resistivity =
3000 Ω-m.
Depth of the surface layer = 0.152 m (approximately 6 in).
Estep50 = (1000 + 6Cs (hs , K )ρ s )0 . 116 / t s
= (1000 + 6 × 0 . 79 0 × 3000)0 . 116 / 0 . 5 = 1275 . 0 V
The touch potential is:
Etouch 50 = (1000 + 1 . 5Cs (hs , K )ρ s ) 0 . 116 / t s
= (1000 + 1 . 5 × 0 . 790 × 3000) 0 . 116 / 0 . 5 = 747 . 2 V
3. Estimate the length of required buried conductor.
Next estimate the length of the buried conductor. The following expression can be used:
Depth of grid conductor below natural soil h = 0.5m.
K m K i ρI G
< [1000 + 1 . 5Cs (hs , K )ρ s] 0 . 116/ t s
L
Ambient temperature Ta = 40°C.
Duration of current flow tf = 0.5 s.
Duration of current flow for sizing grid conductor = 0.5 s.
The substation has a transformer with high-voltage, delta primary, and wye-connected secondary, solidly grounded. The remote
source is solidly grounded, 100 mi away. The substation has two
incoming lines with ground wires and two outgoing lines with
ground wires.
1. Calculate the conductor size from Eq. (21-15).
K + T
I = 5 . 671 × 10−6 A TCAP ln 0 m
t cαr ρr K 0 + Ta
Tm is the maximum allowable temperature that varies depending on the type of connections. For brazed joints (thermo weld),
it is considered 450°C, but for pressure-type connections, the
limit is 250 to 350°C.
Consider the lower limit of 250°C and soft annealed copper
conductors, the constants of which are given in Eq. (21-15).
Though the current giving rise to GPR will be lower, the conductors are sized for the maximum fault current available. The factor
Cp considers future increase in the system short-circuit level. For
this example, let us consider Cp = 1.
Substituting these values:
23 4 + 250
3 . 422
1 = 5 . 0671 × 10− 6 A
ln
0 . 5 × 0 . 00393 × 1 . 7241 234 + 40
This gives an area A in circular mils of 99089. Thus, a conductor size of 2/0 AWG (133100 CM) is acceptable. However, we use 4/0 AWG (211600 CM) based on mechanical
considerations. Welded-type connections can be used at the
perimeter conductors and every forth module lengthwise and
breadth wise, while compression-type connectors can be used
elsewhere for ease of installation. The diameter of 4/0 conductor is 1.167 cm.
ρ − ρs
= − 0 . 834
ρ + ρs
Then from Ref. 11, Cs = 0.790
Consider a body weight of 50 kg. The step potential is:
Total single line-to-ground fault current 3I0 = 12 kA.
X/R = 15.
575
(21-34)
Equation (21-34) signifies that Em (calculated) is less than Etouch (tolerable).
We calculated the RHS of the above equation as 742.2 V. We do
not know Km, K i, and Sf to calculate the grid current, and as a
first step, some assumptions can be made on the values of these
parameters (based upon experience). Consider arbitrarily, Km =
0.7, Ki = 0 6, split factor of the current cannot be found unless
the grid resistance is known and that cannot be calculated unless
the length of the buried conductor and ground rods to be provided are known. Assume a split factor of 0.7, which gives grid
current of IG = 8.4 kA. Ignoring Df for this preliminary calculation
and substituting these values gives an initial estimate of conductor
length = 1275 m. Consider 40 10 ft long copper ground rods of
1 in diameter provided at the perimeter of the grid.
Proceed with the preliminary design on the basis of the assumption. Calculate grid resistance. Estimate split factor from the graphs
in Ref. 11, calculate Df of current and the maximum IG giving rise
to GPR according to Eq. (21-23). Calculate the maximum step and
touch potentials according to equations previously described.
4. Check and reiterate the calculations.
These calculations reveal that the calculated touch voltage
exceeds the permissible safe touch voltage of 747.2 V, while
the step voltage is within the safe limits. Thus, the design should
be modified by manual iteration of the involved parameters,
until the desired results are obtained.
All these iterative calculation steps are not shown. The design
satisfying the requirements is described as follows:
■
The grid consists of 20 conductors lengthwise, that is, parallel
to x axis and 29 conductors parallel to y axis. This gives a uniform
spacing of conductors throughout the rectangular grid area of
87 × 60 m, giving total length of conductors equal to 3723 m.
■
Note that according to IEEE 80 calculation procedures, the
unequal spacing of the conductors is not permissible, and these
should be spaced at uniform interval, here 3 m. The minimum
spacing is limited to no less than 2.5 m.
■
Retain 40 ground rods of 1 in diameter, and 10 ft long at the
grid perimeter.
576
CHAPTER TWENTY-ONE
5. Run final calculations.
Calculate the grid resistance:
And:
1
1
R g = 270
+
3843
20 × 84 × 57
K ii = 0 . 656 + 20 × 0 . 172 = 4 . 096
1
1 +
1 + 0 . 5 20 / 84 × 57
Therefore from Eq. (21-25):
Es =
= 1 . 716 Ω
Note that the length of the ground rods is added in the length
of the total grid conductors. This resistance value agrees closely
with the computer-based calculations, using finite element
method (see further discussions below), which gives 1.649 Ω
versus 1.716 Ω with hand calculations.
Calculate the Df from Eq. (21-24):
D f = 1+
15
(1 − e −2×0.5×2 π f /15 ) = 1 . 039
2π f × 0 . 5
Estimate current split factor. Consider 100 percent remote
contribution, that is, all the current must return to remote
grounded source as the incoming lines from remote are connected to a step-down transformer with delta primary windings,
which block the flow of zero-sequence currents for a high-voltage
side fault. Consider two transmission lines and two feeder lines
entering and leaving the substation, and a tower footing resistance for transmission lines of 100 Ω and that of feeder lines equal
to 200 Ω. This gives a split factor of 0.5, graphically determined
from IEEE 80.11
Thus, the current giving rise to GPR:
I g = (3I 0 )S f D f C p = 12 × 0 . 5 × 1 . 039 × 1 = 6 . 234 kA
Therefore, the GPR = 10,700 V.
Calculate Km from Eq. (21-24)
(3 + 2 × 0 . 5)2
32
0.5
ln
+
−
.
.
.
×
×
×
×
×
16
0
5
0
01167
8
3
0
5
4
0
01167
.
1
Km =
2π
K ii
8
+ K ln π (2n − 1)
h
In the above equation, for calculation of mesh voltage factor
Km, irregularity factor Ki is calculated as follows:
n = 29 × 20 = 24
for
Em
K ii = 1
K h = 1 + 0 . 5 / 1 = 1 . 2247
Substituting these values:
Km = 0.30
Also:
K i = 0 . 656 + 0 . 172 × 24 = 4 . 784
Thus, Em is calculated from Eq. (21-25)
Em =
ρI G K m K i
270 × 6234 × 0 . 32 × 4 . 784
=
= 667 V
Lc + 1 . 15Lr
3723 + 1 . 1 5 × 120
This is acceptable.
Calculate the factors for the step voltage from Eq. (21-31):
Ks =
1 1
1
1
+
+ (1 − 0 . 518 ) = 0 . 515
π 2 × 0 . 5 3 + 0 . 5 3 .
270 × 6234 × 4 . 096 × 0 . 515
= 919 . 50 V
3723 + 1 . 15 × 120
6. Is the calculated design safe?
Note that the maximum touch voltage cannot be greater than
Em. Thus, we have completed a design with step and touch
voltages below the safe limits. The calculated touch and step
potentials are approximately 89 and 72 percent, respectively,
of the safe tolerable limits.
Based on these calculation results, should we conclude that
the grid design is safe?
This cannot be said with certainty because of the limitations of
IEEE method applied in the above calculations. The calculation
procedure does not account for the areas of high risk near the
corners of the grid.
7. Check with computer based calculations.
The computer based calculations of exactly the same system
give the following results:
■
Maximum touch potential = 698.07 V versus 667 V calculated above by hand calculations.
■
Maximum GPR = 9856 V versus 10700 V by hand calculation.
While these numbers are comparable, the profile of voltages
through a cross section of the grid based on computer calculations can reveal areas of high touch and step voltages. This cannot
be easily hand calculated, pointing to limitation of such calculation. Though, such calculations are academically instructive.
With computer-based calculations the voltage at any point in the
grid can be calculated, and it is not the same in every mesh. It
tends to rise toward the periphery and in the grid corners.
Figure 21-17 shows a profile of the touch potential through
the middle of the grid. It is seen that touch potential everywhere is
acceptable. Figure 21-18 shows a similar profile at the outermost
conductor. This shows that the touch potential exceeds the tolerable limits by 143 V, approximately 2 m from the grid parameter.
It is necessary to provide another run of grid conductor or add
more ground rods around the periphery of the grid at 2 m level.
Generally, the grid conductor module is reduced to 50 percent at
the corners.
Figure 21-19 shows a three-dimensional sketch of the touch
voltage contours. Note that the potential tends to rise toward the
corners, though the actual values cannot be read.
The calculation procedure in ANSI/IEEE standard does not permit modeling of grid conductors at unequal spacing and gives no
idea with respect to the voltage contours in the grid. Some qualifications are:
1. The geometric parameters should not exceed the limits
specified in Eq. (21-32). However, in the foregoing example,
these did not, yet we have areas of high potential risk.
2. A two-layer model is not supported. In the foregoing
example, we considered only a single-layer model. A model
with a top-layer resistivity to a certain depth and lower-layer
resistivity below that depth, based on test measurements, can
be derived by currently available computer programs.
3. An unsymmetrical grid, that is, L-shaped with projections,
cannot be analyzed with respect to danger points in the
TRANSIENTS IN GROUNDING SYSTEMS
FIGURE 21-17
577
Profile of touch voltage through the middle cross section of the grid. This shows touch voltage below maximum safe touch voltage
of 698.07 V.
FIGURE 21-18
Profile of touch voltage at the periphery conductor of the grid. This shows higher than the safe touch voltage at the corners.
corners and bends. It is difficult to control the potentials at the
corners in such a grid shape.
4. Some utilities adopt a grid design where the ground conductors are buried at two levels. The lower depth has conductors of larger size, while the top conductors are of smaller cross
section, connected to the lower grid conductors at certain
intervals. Though the design is not so common and somewhat
controversial, an economy in conductor material is an advantage. Such a design cannot be analyzed using IEEE methods.
5. EPRI has developed grounding grid analytical programs,
which calculate the split factors and can handle unequal spacing of conductors, two-layer designs with unequal conductor
spacing, and flexibility in determining local danger points.
21-7
FINITE ELEMENT METHODS
Most computer algorithms use finite element methods18 in addition to the IEEE method and have the graphical capabilities to plot
three-dimensional profiles as well as surface potentials through
any cross section of the grid. An effective design using unequal
spacing and economizing the cost of the materials can be implemented. In the finite element methods, the current density need
not be uniform.
The current flux at any point A, with respect to an elemental
section of the grid conductor, as shown in Fig. 21-20, is:
y2
ξ=
σ dy
∫ 4π1 R 2 r
y1
(21-35)
578
CHAPTER TWENTY-ONE
FIGURE 21-19
A three-dimensional plot of the touch voltages.
where, from Fig. 21-20, x is the current per unit area at any point,
s1 is the current flowing to ground per unit length of conductor
(current density) and:
R = (i − x1 )2 + ( j − y1 )2 + (k − z1 )2
r=
(i − x1 )i + (i − y1 ) j + (i − z1 )k
R
(21-36)
The electrical field at any point is then:
E = ρξ
(21-37)
where r is the soil resistivity. Then the voltage at point a is:
v=
FIGURE 21-20
Illustration of the concept of finite element method
for grounding grid design.
∫ E. dl
(21-38)
The conductor length can be divided into small finite elements.
The current density will not be uniform. In practice, variation of the
current density along the length of an element will have little effect
TRANSIENTS IN GROUNDING SYSTEMS
FIGURE 21-21
579
A section of a computer printout showing the finite element approach in dimensioning the grounding electrodes.
upon the calculated voltages. The variation between elements will
be significant. The variation in current density can be accounted
for by modeling the elements in sections. Then the total voltage at a
point is the summation of all the elemental sections in the grid.
Figure 21-21 shows a section of the computer printout. Note
the difference in current in the elements. A user can increase the
number of sections of a conductor for analysis for greater accuracy.
As an extension, multiple images of each conductor are used to
perform analysis in two-layer soil models. The advantage is that the
technique accounts for the finite length of the element and can handle grid designs with large asymmetry. Special danger points, that is,
exterior to the fence along the perimeter, and the grid corners can be
ascertained and the grid design modified for the optimum results.
Figure 21-22 shows the special areas in L-shaped grid where the
hazards potentials should be investigated.
It is practical to extend crushed rock layer some distance outside the fence, while the fence itself is included in the grid area,
about 1 to 1.5 m inside the grid conductors. A grid conductor run
about 0.8 m away outside the fence will help to reduce the shock
hazard. Note the high resistivity of asphalt shown in Table 21-3.
Outside the grid, from the grid conductors on the boundary, the
voltage will fall gradually over a distance.
Example 21-3 This example is a computer simulation of a relatively difficult grid design as the soil resistivity measurements are
762 Ω-m. The grid is 242 × 121 m, rectangular. The computer calculations optimize the design with unequal conductor spacing, 26
conductors along x-axis, and 72 conductors along y axis, shown in
the grid layout in Fig. 21-23. Note the closer spacing of the conductors toward the perimeter. The calculated GPR is 12556 V, with a
grid current of 6.77 kA. The grid resistance is 1.8531 Ω. The tolerable step and touch voltages are 550.45 Ω and 1709 V, respectively.
Due to rocky soil, Chemrods® are used,19 and each ground
rod is installed horizontally at a shallow depth of 0.5 m due to the
rocky nature of the soil and difficulty in drilling. Each horizontally
installed rod of 8 ft length in artificial soil fill is treated like a 40 ft 1.5
in rod driven vertically in the soil. The three-dimensional conductor profile of the grid is shown in Fig. 21-24. A three-dimensional
profile of voltages is shown in Fig. 21-25. Compare the voltage
counter profile with Fig. 21-19. By closer spacing of the ground
grid conductors toward the periphery, the touch voltages are even
lower compared to the voltages in the middle grid meshes.
21-8
GROUNDING AND BONDING
Consider the following scenarios:
F I G U R E 2 1 - 2 2 Danger points, where the voltages can be high, at
the corners of an L-shaped grid.
1. The lightning currents that are to be conducted to ground
can be very large. Low-impedance grounding is required to
dissipate the electrostatic charge and prevent a strike and to
provide a path for lightning surge currents. The efficacy of
lightning protection system can be marred by an ineffective
grounding system. In the lightning protection system of structures, the metallic portions of windows and frames, are bonded
to the down conductors to prevent side flashes.
580
CHAPTER TWENTY-ONE
FIGURE 21-23
FIGURE 21-24
Plan view of grounding conductors and rods, unequal spacing.
A three-dimensional view of the grounding grid electrodes with simulated ground rods 40 ft deep.
2. Potential hazards can occur if the tanks and vessels
and floating roof tanks storing inflammable liquids are not
grounded according to appropriate standard requirements.
4. The electrical noise and shielding can pose problems in
data processing and control systems in case of ineffective or
inappropriate grounding.
3. The data control and computer system grounding has
special requirements.
5. The protection of human life and risk of fire hazard and explosion is directly related to proper system and equipment grounding.
TRANSIENTS IN GROUNDING SYSTEMS
FIGURE 21-25
581
A three-dimensional plot of the touch voltage profile of the grid.
Lack of bonding can give rise to differential voltages with respect
to the grounded equipment and pose shock hazards. In an industrial plant, the plant grid is essentially composed of steel reinforcing
bars in the concrete footings, foundations, and floor slabs. These
electrodes are supplemented at each building and structure by bare
copper conductors connecting together individual footings, foundations, water pipes, and driven rods. At each building or structure,
the grounding system is bonded to structural steel, large metallic
tanks, and the frames of process and electrical equipment. Metallic
pipes and conduits are bonded to the grounding electrode system by
virtue of being supported on or from structural steel. The neutrals
of separately derived systems or their secondary side neutral impedances are also bonded to the building grounding electrode system.
This creates an equipotential surface and provides the required
safety for personnel and operation of the protective relays.
Let us consider the grounding grid designs in a situation where
a high voltage utility substation is located next to or in the same
premises as a large industrial facility. It is not uncommon to see
230-kV high voltage step-down substations consisting of a number of transformers and industrial plant loads of the order of 150
to 200 MW. The distribution voltage may be at multivoltage level,
say, at 13.8, 4.16, 2.4, and low voltage. These distribution systems
will, invariably be high resistance or low resistance grounded; thus
limiting the magnitude of ground fault currents. The maximum
ground fault current giving rise to GPR will, therefore, occur for
a high-voltage fault in the utility substation. As discussed earlier,
there is no effective way to isolate all the metallic connections,
cable shields, cable racks, and ground connections between the
utility substation and the industrial distribution systems. In fact,
an industrial plant grid will have much lower ground resistance as
compared to the utility substation grid. With all the ground systems bonded together, the transfer potentials (Fig. 21-14) should
not be a problem. Here the ground current will split between (1)
the remote source, and (2) industrial distribution grounding system
and utility grounding grids. This leads to fairly complex calculations to analytically calculate the split factor.
21-9
FALL OF POTENTIAL OUTSIDE THE GRID
Figure 21-2620 shows that the potential will fall gradually outside
the grid area. The earth potential distribution from the edge of a
power station grid with respect to remote earth point is shown for
various grid sizes.
First consider an analytical calculation of the fall of grid potential. Consider a grid of area 31416 m2, 2000 m of buried ground
conductor, and a soil resistivity of 200 Ω-m (sand and clay). This
gives a grid resistance of 0.6 Ω; the current flowing in the earth is
11.25 kA. Applying split factor and decrement factor, the calculated
GPR = 6.75 kV.
The voltage at a distance x from the grid can be calculated from
the following equation:
0 . 64
V( x )
=
sin −1(r /x ) rad
GPR (1 + 4r /L )
(21-39)
where V(x) is the voltage at distance x measured from the center of
the grid, and r is the radius of a circle with an area equal to the grid
area. This is independent of the soil resistivity and is merely a function of grid geometry, and distance x should be ≥ 3r.
582
CHAPTER TWENTY-ONE
Fall of potential outside a grid. (1) A small grid area 1600 ft2 (150 m2), (2) a medium-small grid area, approximately 35000 ft2 (3350 m2),
(3) a medium-large grid area, approximately 290000 ft2 (27000 m2), (4) a large grid area, approximately 935000 ft2 (87000 m2). Source: ANSI/IEEE Std. 367.20
FIGURE 21-26
Assuming a totally isolated grid, the voltage at 300 m from the
grid will be 1.19 kV. Thus, the zone of the fall of potential outside
the grid extends over a considerable distance. These calculations
can be correlated with Fig. 21-26. A large separation distance is
required to reduce the coupled voltage to 100 V. The impact of GPR
and its zone of influence can be summarized as follows:
■
The potential can couple to other nearby grids. Isolation of
two grids in close proximity is not possible and these should
be interconnected.
FIGURE 21-27
■
The potential can be transferred to a metal part in the
ground in the vicinity of the grid. Consider a buried telecommunication cable. The potential can enter the telecommunication circuits through cable sheath or telecommunication
grounding electrodes.
■
Figure 21-27 shows that the contours of potential around a
grid area are not uniform and get distorted due to presence of
buried pipes and metal objects. In this figure, A is the area of
the power station grid. Bs are points of equal values of ground
Zone of influence of fall of potential outside a power station grid to safe levels.
TRANSIENTS IN GROUNDING SYSTEMS
resistance from station ground grid where the GPR is reduced to
an acceptable level. Note the departure from ideal circular locus.
Area C is the zone of influence of GPR.
21-10
INFLUENCE ON BURIED PIPELINES
From the above discussions, it is amply clear that soil itself acts like
a coupling medium for a potential generated somewhere else in the
power system, and the effect of resultant GPR is present at a considerable distance from the original site of GPR. Often pipe lines and power
lines run in parallel (at least for some distance), and due to the high cost
of acquiring land and right-of-way, it is not practical to avoid such parallelism. In the pipeline work, the following equation is used to ascertain
the distance at which the effect of parallelism is considered negligible:
d ≈ 100 ρ
(21-40)
This means that for a high soil resistivity say 500 Ω-m, a separation of 2.24 km is required. High voltages can be induced in the
pipelines and currents can flow due to such parallelism. These voltages and currents can have the following effects:
■
Damage the pipeline insulation and cause flashovers.
■
Swap the normal cathodic protection currents provided for
the pipelines and render the cathodic protection inoperative.
■
These can be a source of danger and shock hazard to operating
personnel.
The two conditions to be studied are (1) ground faults, which will
raise the tower footing and surrounding ground voltage, as discussed
in earlier chapters, and (2) voltages induced under normal operating
conditions. This occurs because the magnetic flux around the conductors and supports is not perfectly balanced. Mutual inductances exist
between the overhead line and the pipeline, which can be estimated
using Carson’s equations, (App. D). The pipeline acts like a parallel
transmission line of certain characteristics’ impedance. The voltage
and current induced in the pipeline is given by the expressions:
Vs =
− jMω J −γ p ( L− x ) −γ p x
−e ]
[e
2γ p
− jMω J
−γ ( L − x )
−γ x
Is =
[2 − e p
−e p ]
2Z
FIGURE 21-28
(21-41)
583
where Vs and Is are the current and voltages at any distance x, respectively, L is the length of parallelism, g p = propagation constant, Z is
the characteristic impedance, M is the mutual inductance, and J is
the current in the power line. Figure 21-28 shows the current and
voltage profiles. Equation (21-41) is applicable when pipe line is
terminated in its characteristics impedance.
Table 21-4 is an actual calculation of the induced voltages
on a 30-in pipeline sections paralleled with 400-kV line carrying a current of 100 A (line configuration not described here).
The induced voltage is a function of line-coating resistance
(screening effects not shown). The remedial measures to reduce
induced voltages on parallelism include lowering tower footing
resistance, earth wires on towers, metallic screen (buried metallic
conductor), and increasing spacing between the power line and
pipeline.21
21-11 BEHAVIOR UNDER LIGHTNING
IMPULSE CURRENT
In Chap. 5, there is a brief discussion of the tower footing resistance under lightning impulse currents. The lightning current is at
high frequencies, from some hundreds of kHz to 1 MHz, and the
soil resitivity also varies over a wide range. The transient behavior
of the ground electrode system is determined more by inductive
phenomena than the resistive effects. The rate of rise of the front of
current impulse is of major importance, as it increases the inductive
voltage drop.22,23,24
The high values of lightning currents, with very short front
durations, can result in high current density in the layers of
soil, adjacent to the grounding conductors and electrodes. IEEE
standard25 has a table which provides mathematical expressions for
calculating the ground resistance of grounding electrodes of various
shapes. For a single ground rod of length L and radius r, the ground
resistance is given by:
R=
ρ 4L
− 1
ln
2π L r
(21-42)
The current density J at a distance a from the rod for an injected
current I, is J = I /2π aL and the voltage gradient E is rJ.
For high currents, when the gradient E exceeds a certain level,
soil moisture is evaporated, and arcs are produced within the soil
around the electrode in a certain area surrounded by streamers. The
streamers and arc zones can be modeled as an area of zero resistivity.
Voltage and currents induced in a pipeline in parallel with a power line; the pipeline terminated in its characteristic impedance.
584
CHAPTER TWENTY-ONE
TA B L E 2 1 - 4
Induced Voltages in a 30 in Pipeline Paralleled
Sections with a 400-kV Line
SOIL RESISTIVITY (W-m)
SEPARATION (m)
LENGTH OF PARALLELISM (km)
10
160
16.7
INDUCED VOLTAGE (KV)
20
25
150
30.7
25
22
100
27.4
23
60
460
2.4
13.3
Note: The transmission line carries a current of 100 A. The pipeline has a coating resistance of 10 Ω/km,
linear resistance of 0.2 Ω/km, and linear inductance of 0.5 Ω/km.
Thus, for certain critical field strength, the diameter of the grounding rod is artificially increased. This means that a ground rod can be
modeled as hemisphere electrode.
For a hemisphere of radius r11:
ρ
R=
2π r
E0 ρ
Ri =
2π I
2 π a 2 E0
1 ρ E0
=
2π R 2
ρ
(21-45)
Here, we have set a = r. Then in terms of Ig and from Eq. (21-44)
Ig
(21-46)
I
FIGURE 21-29
R
1 + (I /I g )
(21-47)
We applied this equation in Chap. 5. An equation to estimate
the tower footing inductance is:23
L f = 60Tt ln
(21-44)
where E0 is the critical gradient. A critical gradient of 1000 kV/m is
suggested in Ref. 22, though 400 kV/m is more common. There has
to be a sufficient current Ig to produce the critical gradient. Then,
from the current density and voltage gradient for the hemisphere
electrode:
Ri = R
Ri =
(21-43)
Similar expressions for J and E are: J = I /2π ra 2 and E = rJ. Now
expand the radius r to → a new radius = a, and eliminating a from
the above relations, the impulse resistance is:
Ig =
It can be shown that Ri is a function of log of I and a further
modification to this equation for ground rods is:
tf
Tt
(21-48)
where Tt is the tower travel time, and t f is the time to crest of the
stroke current.
21-11-1
Impulse Response of Grounding Grids
When analyzing a grid system for impulse currents, consider
Fig. 21-29a, where the impulse current is injected into a certain point
in the system. An elemental section can be considered as shown in
Fig. 21-29b and it acts like a distributed parameter transmission line.
Based on the current theoretical studies and experimental work, the
following conclusions are summarized:
1. The impulse current dispersion is dependent upon the electrode length, soil resisitvity, peak value of the surge current,
and the time to crest.
(a) Injection of impulse current in a grounding grid. (b) Simulation like a traveling wave circuit.
TRANSIENTS IN GROUNDING SYSTEMS
2. An analytical expression to calculate the effective length of
earth electrode is:
le = K 0 ρ τ
(21-49)
where le is the effective length in m, and t is the time to crest in
µs, and r is the resistivity in Ω-m. The factor K0 depends upon
the geometric construction. It can be taken as 1.40 for the single
conductor energized at one end, 1.55 for the single conductor
energized in the middle, and 1.65 for conductors arranged in
mesh formation, energized at the center. The effective length
signifies the distance at which the conventional ground resistance does not undergo any significant reduction.
3. The localized earth electrodes will present lower resistance
if lightning impulse current is sufficiently high to cause soil
ionization.
10. Consult IEEE Std. 80 to find out the split factor of the
ground fault current given that:
Single line-to-ground fault current = 20 kA
Ground mat resistance = 1 Ω
Tower footing resistance = 20 Ω
Number of transmission lines leaving/entering the
substation = 4
Number of sky wires = 4
Remote and local contribution are 25% and 75%, respectively.
Calculate the split factor based on the calculation procedure
given in this standard.
11. Design a grounding grid, given the following parameters:
Ground fault current = 11 kA rms symmetrical, X/R = 10
Selection and applications of grounding systems for low-voltage
to high-voltage levels and their behavior under power frequency
and surge currents is rather an extensive field. The chapter provides
an overview of the system and equipment grounding and points to
further investigations and reading.
Split factor = 0.6
PROBLEMS
Maximum allowable temperature for compression joints:
350°C
1. A 480-V system is solidly grounded. Calculate the permissible damage in cubic inches to copper, steel, and aluminum
for a rated current of 2000 A.
585
Capacity factor = 1.1
Ambient temperature = 40°C
Grid area = 70 m × 80 m rectangular
Soil resistivity = 200 Ω-m
2. In Prob. 1, calculate the maximum fault clearing time of
a ground fault relay to limit the damage to the permissible
NEMA limits. The arcing current is 30 kA, and the operating
time of the circuit breaker is half a cycle.
Grid conductor buried to a depth of 0.6 m
3. Comment on the statement that arcing ground phenomena
occurs only in the ungrounded systems.
Number of ground rods = 30, along the periphery and grid
corners. Each rod is 3/4 in diameter and 10 ft long.
4. What are the typical X0 /X1, R0 /X0 ratios for an effectively
grounded system? What is typical COG for solidly grounded
systems?
5. The utilities solidly ground their transmission systems and
also distribution and subdistribution systems, except the generators, which are high resistance grounded. Why? If a generator neutral is left ungrounded, what harmful effects can occur?
6. An 18-kV, three-phase generator is to be high resistance
grounded through a distribution transformer of 240-V secondary windings. The calculated capacitance current of the
generator circuit is 8 A. Calculate (1) voltage ratio and kVA
rating of the transformer, and (2) the secondary loading resistor value across 240-V secondary windings of the distribution
transformer and its current rating. What should be the primary
voltage rating of the distribution transformer? Could there be
a problem if 18/ 3 kV is selected, as the generator windings
are wye-connected and rated for 18 kV?
7. Why are 13.8-kV industrial distribution systems not high
resistance grounded? State two technical reasons.
8. Comment on the statement: “On a cloudy rainy day, a deer
was grazing outside the fence of a high-voltage substation.
Suddenly it fell unconscious to ground, as if subjected to an
electrical shock. Then it got on its feet and fled.”
9. Describe the importance of providing crushed rock in the
design of substation grounding grids, especially in areas of low
soil resistivity.
Crushed rock laid to a depth of 0.1 m, resistivity = 3000 Ω-m
Fault duration = 0.5 s = shock duration.
Calculate:
■
Size of grid conductor
■
Tolerable step and touch potentials
■
Decrement factor
■
Grid resistance
■
GPR
■
Factors K, Km, Ki, Em etc.
Iterate and finalize the grid design. Prepare a layout of the final
design. Does the design need to be modified? Where will the
additional conductors/ground rods be added without a rigorous
calculation to ascertain local danger points? Modify the calculated design and prepare a final sketch of the layout.
12. Calculate the fall of potential outside the grid area at a distance of 100 and 200 m in Prob. 11. At what distance will the
voltage fall to 100 V?
REFERENCES
1. NEMA PB1-2, Application Guide for Ground Fault Protective
Devices for Equipment, 1977.
2. H. L. Stanback, “Predicting Damage from 277 Volt SinglePhase-to-Ground Arcing Faults,” IEEE Trans. IA, vol. 13, no. 4,
pp. 307–314, Jul./Aug. 1977.
586
CHAPTER TWENTY-ONE
3. NFPA 70E, Electrical Safety Requirements for Employee Workplaces, 2004.
4. IEEE Std. 1584, IEEE Guide for Performing Arc-Flash Calculations, 2002.
20. ANSI/IEEE Std. 367, IEEE Recommended Practice for Determining the Electrical Power Station Ground Potential Rise and
Induced Voltages from a Power Fault, 1996.
5. ANSI/NFPA 70, National Electric Code, 2008.
21. J. C. Das, “Influence of HV Line Parallelism on Buried Pipe
Lines,” Electrical India, vol. XX, no. 1, pp. 27–35, Jan. 1980.
6. J. C. Das, “Ground Fault Protection of Bus-connected Generators in an Interconnected 13.8 kV System,” IEEE Trans. IA,
vol. 43, no. 2, pp. 453–461, Mar./Apr. 2007.
22. E. E. Oette, “A New General Estimation for Predicting the
Impulse Resistance of Concentrated Earth Electrodes,” IEEE Trans.
PD, vol. 4, no. 2, pp. 1329–1337, 1989.
7. D. S. Baker, “Charging Current Data for Guess Work-free
Design of High Resistance Grounded Sytems,” IEEE Trans. IA,
vol. IA-15, no. 2, pp. 136–140, Mar./Apr. 1979.
23. W. A. Chisholm and E. Janischewskyj, “Lightning Surge
Response of Grounding Electrodes,” IEEE Trans. PD, vol. 4, no. 1,
pp. 1329–1337, Apr. 1989.
8. ICEA Pub. S-61-40, NEMA WCS, Thermoplastic Insulated
Wire for Transmission and Distribution of Electrical Energy,
1979.
24. CIGRE Working Group 33.01, Guide to Procedures for
Estimating the Lightning Performance of Transmission Lines,
Brochure 63, Oct. 1991.
9. J. R. Dunki-Jacobs, “The Reality of High Resistance Grounding,”
IEEE Trans. IA, vol. IA-13, pp. 469–475, Sept./Oct. 1977.
25. IEEE Std. 142, IEEE Recommended Practice for Grounding of
Industrial and Commercial Power Systems, 1991.
10. J. C. Das and H. Osman, “Grounding of AC and DC Low-Voltage
and Medium-Voltage Drive Systems,” IEEE Trans. IA, vol. 34,
no. 1., pp. 205–216, Jan./Feb. 1998.
11. ANSI/IEEE Std. 80, IEEE Guide for Safety in Substation
Grounding, 2000.
12. J. Endrenyi, “Analysis of Transmission Tower Potentials During
Ground Faults,” IEEE Trans. PAS, vol. 86, pp. 1274–1283, Oct.
1967.
13. S. A. Sebo, “Zero Sequence Current Distribution Along Transmission Lines,” IEEE Trans. PAS, vol. 88, pp. 910–919, Jun. 1969.
14. F. Dawalibi, “Ground Fault Distribution Between Soil and
Neutral Conductors,” IEEE Trans. PAS, vol. 99, no. 2, pp. 452–461,
Mar./Apr. 1980.
15. A. P. Meliopoulos, A. Papalexopoulos, and R. P. Webb,
“Current Division in Substation Grounding System,” Proc. of the
1982 Protective Relaying Conf., Georgia Institute of Technology,
Atlanta, GA, 1982.
16. EPRI Final Report, EL-2682, Vol. 1, “Analysis Techniques for
Power Substation Grounding Systems,” Oct. 1982.
17. J. G. Sverak, “Sizing of Ground Conductors Against Fusing,”
IEEE Trans. PAS, vol. 100, no. 1, pp. 51–59, Jan. 1981.
18. P. P. Silvester and R. L. Ferrari, Finite Elements for Electrical
Engineers, 3rd ed., Cambridge University Press, New York,
1996.
19. Lightning Eliminators and Consultants, Chem Rod and GAF
(Ground Augmentation Fill) Product Data, www.lecglobal.com.
FURTHER READING
R. R. Conrad and D. Dalasta, “A New Ground Fault Protective
System for Electrical Distribution Circuits,” IEEE Trans., vol. IGA-3,
no. 3, May/Jun. 1967.
F. Dawalibi and D. Mukhedkar, “Parametric Analysis of Grounding
Grids,” IEEE PES Winter Meeting, Paper No. F79243-7, 1979.
M. J. Frazier and J. Dabkowski, “Magnetic Coupled Longitudinal
Electrical Filed Measurements on Two Transmission Lines,” IEEE
Trans. PAS, vol. 104, no. 4, pp. 933–940, Apr. 1985.
General Electric Industrial Power System Data Book, 1954.
IEEE Std. 399, Brown Book, Power System Analysis, 1997.
E. B. Joy, A. P. Meliopoulos, and R. P. Webb, “Touch and Step Calculation for Substation Systems,” IEEE PES Winter Meeting, Paper
No. A79052-2, 1979.
R. H. Kaufman and J. C. Page, “Arcing Fault Protection for Low
Voltage Power Distribution Systems—Nature of the Problem,” IEEE
Trans. IA, vol. 79, pp. 160–167, Jun. 1960.
R. C. Quist, “Voltages to Ground in Load Commutated Inverters,”
IEEE Trans. IA, vol. 24, pp. 526–530, May/Jun. 1988.
W. F. Robertson and J. C. Das, “Grounding Medium Voltage Mobile
or Portable Equipment,” Industry Applications Magazine, vol. 6, no. 3,
pp. 33–42, May/Jun. 2000.
R. Ruenburg, Transient Performance of Electrical Power Systems,
McGraw Hill, New York, 1954.
R. Verma and D. Mukhedkar, “Ground Fault Current Distribution
in Substation Towers and Ground Wires,” IEEE Trans. PAS, vol. 98,
pp. 724–730, 1979.
CHAPTER 22
LIGHTNING PROTECTION
OF STRUCTURES
Surge protection of the incoming services, electrical supply lines,
and communication lines was discussed in the previous chapters.
In a likewise manner, the direct and nearby cloud-to-ground
discharges can be hazardous to the structures, human life, and
the contents in the structures. To safeguard against lightning
hazards, risk management approach is adopted. In this approach,
the lightning risks are identified, frequencies of events and their
consequences estimated, and if these are above a tolerable limit,
lightning protection is provided. The protection provided should
reduce the risk below an acceptable level. In this approach, a comparison can be drawn with the statistical methods used for insulation
coordination. The type of structure, its occupancy, risk of lightning
damage, and cost are simultaneously considered in arriving at an
engineered solution.
Variations exist with respect to practices in Europe according to IEC standards and NFPA 780 (National Fire Protection
Association) used in the United States. Both these practices are
briefly discussed.
22-1
PARAMETERS OF LIGHTNING CURRENT
The lightning parameters considered for the protection in IEC
standards1–4 are:
■
Peak value of the first stroke. The lowest value of the downward flashes is important for the choice of air terminal systems
to prevent direct flashes to the structures and has the highest
statistical values for protection against electrodynamic effects.
■
Maximum rate of rise. This is important for inductive effects
and overvoltages.
■
Flash duration and total charge in the flash. The highest statistical values are important for limiting the thermal effect at the
impact point of lightning flash.
■
Specific energy in flash. The highest value of statistical distribution
is important for selection of conductor sizes to prevent damage due
to thermal effects and implementing suitable grounding systems.
22-2
TYPES OF STRUCTURES
The structures according to IEC 62305-33 are classified as:
1. Common structures.
2. Structures with risks of explosion; that is, zone 0 as classified in IEC 60079-105 for storing solid explosive materials.
IEC does not consider hazardous zones types 1 and 2 at risk of
explosion due to low probability of simultaneous presence of
lightning and inflammable vapors.
3. Structures with electronic systems in which a large amount
of electronic installations exist, including telecommunication
equipment.
4. Structures dangerous to environment, which may cause
biological, chemical, or radioactive emissions and hazard as a
consequence of lightning; for example, chemical, petrochemical,
and nuclear plants.
22-2-1
Risk of Fire
For risk of fire, the structures are classified into three categories
based on the specific fire load of the structure, which is calculated
as the ratio of the total amount of combustible material in the
structure divided by the overall surface area of the structure. It is
specified in kg/m2.
1. Structures with high risk of fire. Structures that are constructed
of combustible materials or have roofs of combustible materials,
and structures with a specific fire load of 45 kg/m2.
2. Structures with ordinary risk of fire. Structures with specific
fire load of 20 to 45 kg/m2.
3. Structures with low risk of fire. Structures with a specific fire
load of <20 kg/m2 and structures that contain combustible
materials occasionally.
587
588
CHAPTER TWENTY-TWO
22-3
RISK ASSESSMENT ACCORDING TO IEC
The following risks are to be taken into account according to the
type of loss:
Figure 22-1, based on IEC 62305-3,3 shows these risks from different types of damages. Risk components are specified.
1. Lightning flashes direct to the structure may generate:
R1—loss of human life
RA—risk of shock due to touch and step potentials
R2—loss of service to public
R3—loss of cultural heritage
RB—risk component due to fire, explosion, mechanical, and
chemical effects inside the structure
R4—economic loss—loss of structural value, contents, and
normal activity in the structure
RC—risk component due to failure of electrical and
electronic systems
FIGURE 22-1
Risk categories, type of loss, and type of damage according to IEC.
LIGHTNING PROTECTION OF STRUCTURES
2. Lightning flashes to ground near the structure generate:
RM—risk due to failure of electrical and electronic components inside the structure due to overvoltages
3. Lightning flashes direct to incoming lines generate:
TA B L E 2 2 - 1
589
Typical Values of Tolerable
Risk Factor RT (IEC Standards)
TYPE OF LOSS
RT
Loss of human life
10–5
RU—risk due to shock of living beings
Loss of service to public
10–3
RV—risk related to fire, mechanical, and chemical effects
Loss of cultural heritage
10–3
RW—component due to failure of electrical and electronic
equipment
4. Lightning flashes to ground near the incoming line will have:
RZ—risk due to failure of electrical and electronic equipment
Note that the type of damage may be ultimately the same, but
the various components are labeled with respect to the type of
lightning activity and loss.
IEC 62305-11 and 62305-22 define the risk as probable annual loss
in a structure due to lightning and suggests the following expression:
R = NPL
(22-1)
where N is the number of flashes, P is the probability of damage,
and L is the value of consequent loss. The probability P is not so
simple to calculate. The probability that a spark could trigger a fire
is given by:
P = ps p f
(22-2)
where ps is the probability of a spark and pf is the probability of a
fire. The probability of failure of electronic system due to overvoltages caused by a direct flash to structure is given by:
P = [1 − (1 − pr )(1 − pi )]
(22-3)
where pr is failure due to overvolatge by resistive coupling and pi is
the failure due to inductive coupling.
The factor L is dependent on the use of the structure, the attendance time of the personnel in the structure, the type of service
provided, and the value of goods affected by the damage. The factor
R consists of the sum of its components, with reference to point of
strike, as follows:
R = R D + RI
(22-4)
where RD is the risk due to direct flashes to the structure and RI is
the risk due to indirect flashes to the structure. These are given by:
R D = R A + R B + RC
(22-5)
R I = R M + RU + R V + R W + R Z
(22-6)
For various types of damages:
R = R s + R F + RO
(22-7)
where risk of shock to living beings is:
R s = R A + RU
(22-8)
The risk related to physical damage is:
R F = R B + RV
(22-9)
The risk related to failure of electrical and electronic systems is:
RO = RC + R M + R W + R Z
(22-10)
IEC 62305-22 provides details of the calculations of risk factors.
Table 22-1 shows typical values of tolerable risk factors. The objective
is to reduce R to a maximum level RT. If R ≤ RT, lightning protection
is not necessary; if R > RT, protection measures shall be adopted to
reduce R ≤ RT.
22-4
CRITERIA FOR PROTECTION
According to IEC 62305-1,1 the lightning protection system (LPS)
consists of both the external lightning protection system and the
internal lightning protection system inside the structure. The external LPS should be designed to achieve the following:
1. Intercept a direct lightning strike to the structure
2. Conduct the lightning current safely to ground
3. Disperse it into the earth
Protection measures are required to avoid hazard of touch-andstep potential for persons outside the structure or in the vicinity of
down conductor system. This can also be achieved by increasing
the surface resistivity of the soil outside the structure and of the
floors inside the structure; see Table 21-3.
Four sets of LPS, types I, II, III, and IV, are defined, based on the
corresponding lightning protection level. For each lightning protection level, a set of maximum and minimum current parameters
have been stipulated in IEC 62305-11. These values are shown in
Table 22-2. These four levels may be considered construction rules
for external LPS. For each level, the maximum and minimum lightning current parameters are fixed.
As an example, for protection level 1, the specified fixed maximum values do not exceed with a probability of 99 percent. Ten
percent positive and 90 percent negative flashes are considered.
Values taken from positive flashes must have probabilities below
10 percent and those from negative flashes below 1 percent. The
minimum values of the lightning current amplitude influence the
positioning of air termination system of an LPS in order to intercept
the lightning flashes direct to the structure.
The minimum values of the lightning current parameters fixed
in IEC 62305-11 and the rolling sphere radius, according to protection level, are shown in Table 22-3. Flashes with peak values less
than the specified minimum value of current may still strike the
structure. An explanation is provided in the next section.
22-4-1
Lightning Flashes to Earth
IEC standards consider two basic types of lightning flashes:
(1) downward flashes initiated by a downward leader from cloud
to earth and (2) upward flashes initiated by an upward leader from
an earthed structure to cloud. In a flat territory, mostly downward flashes occur (Fig. 22-2). For exposed and higher structures,
upward flashes become dominant (Fig. 22-3).
The profiles of short strokes and long strokes according to
IEC 62305-11 and 62305-44 are shown in Fig. 22-4a and b, respectively.
Short strokes are typically below 2 ms, and long stroke typically
2 ms < Tlong < 1 s. The components in the upward stroke are the first
590
CHAPTER TWENTY-TWO
TA B L E 2 2 - 2
Lightning Current Parameters
PROTECTION LEVEL
OCCURRENCE
First short stroke
Subsequent
short stroke
Long stroke
Flash
PARAMETER
SYMBOL
UNIT
I
II
III–IV
Peak current
I
kA
200
150
100
Short-stroke charge
Qshort
C
100
75
50
Specific energy
W/R
MJ/Ω
10
5.6
Time parameters
T1/T2
µs/µs
Peak current
I
kA
Average steepness
di/dt
kA/µs
Time parameters
T1/T2
µs/µs
Long-stroke charge
Qlong
C
Time parameter
Tlong
s
Flash charge
Qflash
1
C
2.5
10/350
50
200
37.5
25
150
100
0.25/100
200
150
100
0.5
300
225
150
3
Source: From IEC 62305-1, 2006 , and IEC 62305-3, 2006.
TA B L E 2 2 - 3
PROTECTION LEVEL
Minimum Value of Lightning
Current and Related Rolling
Sphere Radius
ROLLING SPHERE
RADIUS, R (m)
MINIMUM PEAK
CURRENT, I (KA)
I
20
3
II
30
5
III
45
10
IV
60
16
For dimensioning of the LPS, and with reference to Table 22-2,
consider the following parameters:
1. Effects of lightning are related to peak value of the current
and specific energy, W/R.
2. The thermal effects are related to specific energy, W/R, when
resistive coupling is involved and to charge Q when arc develops
to the installations.
3. The sparking caused by inductive coupling is related to di/dt
of the lightning current front.
4. Values I, Q, and W/R related to mechanical effects are determined from the positive flashes.
Source: From IEC 62305-3, 2006.3
long stroke without or with up to 10 superimposed short strokes.
All short stroke parameters of the upward strokes are less than
that of downward flashes. For lightning protection, the lightning
parameters for upward strokes are considered to be taken care of by
maximum values of the downward flashes.
FIGURE 22-2
22-4-2 Dimensioning LPS
Based on the probability concepts and analyses of the lightning surges, a weighted probability can be determined. The lightning current falls between the minimum and maximum values, as
defined in Table 22-4.
Components of downward flashes typical in flat territory and to lower structures, IEC.
LIGHTNING PROTECTION OF STRUCTURES
FIGURE 22-3
FIGURE 22-4
Components of upward flashes typical to higher structures, IEC.
(a) Short-stroke parameters, IEC. (b) Long-stroke parameters, IEC.
591
592
CHAPTER TWENTY-TWO
TA B L E 2 2 - 4
having a definite charge is captured by the structure itself, may be
evaluated as a function of the downward leader charge. The impact
of the lightning to structure is only possible when the tip of the
downward leader reaches the volume above the structure defined
by the attractive radius, given by:
Probability for the Limits
of the Lightning Current
Parameters
PROBABILITY
LIGHTNING PROTECTION LEVEL
PROBABILITY VALUES ↓
I
II
III
IV
Higher than minimum,
Table 22-2
0.99
0.97
0.91
0.84
Lower than maximum,
Table 22-3
0.99
0.98
0.97
0.97
Source: From IEC 62305-3, 2006.3
R = Iα 0 . 84h 0.6
(22-12)
where:
α = 0 . 7h 0.02
(22-13)
where h is the height of the structure in m. For structures ranging
from 10 to 100 m, and the average amplitude current of 35 kA, the
simplified formula is:
R = 14h 0.6
22-5
PROTECTION MEASURES
The protection measures based on the contents of Tables 22-2,
22-3, and 22-4 are shown in Table 22-5.
22-5-1 Positioning of Air Terminals
Three methods are suggested in IEC 62305-3,3 and, as shown in
Table 22-5, they are as follows:
1. The protection angle method
2. The rolling sphere method
3. The mesh method or the Faraday cage Method
The rolling sphere method is based on electrogeometric model.
It was first proposed by Lee.6 The position of the downward leader
approaching the grounded structure defines a distance from the top
of the structure called the striking distance. It is related to the charge
in the downward leader and the peak value of the lightning current.
Different relations have been proposed between the striking distance and the peak value of lightning current (also see Chap. 5).
IEEE Working Group’s7 proposal is accepted by IEC, and the
relation is (also see Chap. 5):
D s = 10I 0.65
(22-14)
Another formula9 for a free-standing structure of up to 60 m and
lightning current of 31 kA is:
R = 24 . 6h 0.4
(22-15)
Figure 22-5 shows that as the height of the structure increases,
the number of strokes per annum increases. Empire Estate Building
in Manhattan, New York, is struck by lightning on an average of
20 times per year.
Without sifting through various expressions, the IEC 62305-33
makes the applications easy by specifying the rolling sphere radius
for various lightning protection levels, as shown in Table 22-5. The
protection with rolling sphere method is shown in Fig. 22-6. The
air terminal system is adequate if no point of the structure to be
protected comes in contact with a sphere with radius R, as shown
in Table 22-5, rolling around and on top of the structure in all possible positions. IEC recognizes that with structure heights greater
than the radius of rolling sphere, side flashes may occur, though
the probability is small.
Figure 22-7 shows the protection angle method. Note how the
angle varies with the height of the structure. The termination point
of the curve, in black dots, shows the height limit of the protection angle method on the abscissa. Only mesh methods or rolling
(22-11)
where Ds is the striking distance and I is the surge current. This
does not consider the height of the structure. The model in Ref. 8
provides a rational basis for taking account of the structure height.
According to this model, the attractive radius, defined as the maximum distance from the structure for which a downward leader
TA B L E 2 2 - 5
Minimum Values of Rolling
Sphere Radius, Mesh Size, and
Protection Angle Corresponding
to Lightning Protection Levels
PROTECTION METHOD
LPL
ROLLING SPHERE
RADIUS, R (m)
FARADAY CAGE,
MESH, m ë m
PROTECTION ANGLE
I
20
5×5
See Fig. 22-7
II
30
10 × 10
III
45
15 × 15
IV
60
20 × 20
Source: From IEC 62305-3, 2006.3
(m)
FIGURE 22-5
height.
Increase in incidence of lightning with the structure
LIGHTNING PROTECTION OF STRUCTURES
FIGURE 22-6
593
Design of LPS air termination system according to rolling sphere radius, IEC.
sphere method apply for greater heights. The height h is the height
of the air terminal above the area to be protected; this means add
height of the highest point of the structure to the length of the air
terminal. This is illustrated in Fig. 22-8. The angle α1 corresponds
to the height of the air terminal h1, while the angle α2 corresponds
to the height h2 above ground = h1 + h. The angle does not change
for heights below 2 m.
The following types of air terminations are recognized:
1. Rods
2. Catenary wires
3. Meshed conductors
FIGURE 22-7
Lightning protection by protection angle method.
Termination in black dots shows the maximum height on x-axis to which
protection angle method can be applied.
FIGURE 22-8
The radioactive terminals or terminals (see section 22-12-2)
with intensified ionization, if used, are to be positioned only as
conventional terminals.
Structure volume protected by a vertical air termination system, IEC concept.
594
CHAPTER TWENTY-TWO
22-5-2 The Step-and-Touch Voltages
IEC 62305-33 specifies that risk for persons for the step-and-touch
voltages is negligible if one of the following conditions is fulfilled:
1. The probability of persons approaching or the time of their
presence outside the structures and close to down conductors
is very low.
2. Insulation over the exposed conductor is provided to withstand
100 kV, 1.2/50-µs BIL, which requires at least 3-mm cross-linked
polyethylene. (The insulation thickness varies according to the
conductor size and voltage rating. According to NEC, the insulation thickness for 601-2000 V nonshielded types RHH and RHW
cables conductor size 501-1000 KCMIL is 3.05 mm. Cables rated
for higher voltages and of smaller conductor size are required.)
3. The resistivity of surface layer of the soil for a distance of
3 m from the conductor is no less than 5000 Ω/m. Asphalt in a
layer of 5 cm thick will meet this requirement.
4. The natural down conductors consist of several columns of
extensive metalwork of the structure, or several pillars of interconnected steel, electrically continuous.
5. Equipotential surface by means of meshed grounding system is provided for controlling the step voltage; see Chap. 21.
22-6 TRANSIENT BEHAVIOR OF
GROUNDING SYSTEM
The behavior of grounding electrode systems under impulse currents is discussed in Sec. 21-11. Equation (21-48) is repeated here:
Le = K 0 (ρT1 )1/ 2
(22-16)
To disperse the lightning current into the soil through the ground
electrodes, the maximum energy that a human body can tolerate in
transient conditions and the risks involved if this level is exceeded
are considered in IEC 62305-3.3 The maximum energy is 20 W-s.
The standard lays down the minimum dimensions of the ground
electrode system based on the probabilistic lightning parameters,
the earth resistivity, and the LPS level. There are two basic types of
earth electrode arrangements that need to be considered.
■
Type A comprises horizontal and vertical ground electrodes
(i.e., conductors and ground rods) connected to each down
conductor.
■
Type B comprises a ring conductor external to the structure
and is in contact with soil for at least 80 percent of its total length
or foundation electrodes, that is, interconnected reinforcing steel
of the foundations or other suitable metal structures.
For type B electrode system, the mean radius r of the area
enclosed by the ring earth electrode or foundation earth electrode
shall not be less than l1 from Fig. 22-9.3
r > l1
(22-17)
where l1 is greater than r, additional radial or vertical or inclined
electrodes shall be added whose individual lengths, lr horizontal
and lv vertical, are given by:
lr = l1 − r
lv = (l1 − r )/ 2
(22-18)
The number of additional electrodes shall not be less than the
number of down conductors with a minimum of two and will be
connected to the ring bus with equal spacing, as far as practical.
F I G U R E 2 2 - 9 Minimum length l1 versus soil resistivity required
according to LPS system type, IEC classifications. Types III and IV are
independent of soil resistivity.
22-7 INTERNAL LPS SYSTEMS
ACCORDING TO IEC
We discussed categories A, B, and C for the lightning protection
according to ANSI/IEEE standards in Chap. 19. Figure 22-10 from
IEC 62305-44 defines the zones of lightning electromagnetic impulse
(LEMP) severity. Each individual zone is characterized by different changes in electromagnetic conditions at its boundaries. The
protection should be completed with proper shielding, bonding,
and grounding. Services entering the structure should avoid overhead connections to avoid flashes occurring directly on overhead
services, reduce level of overvoltages by shielding, divert lightning
current, and consider increased BILs where needed. Figure 22-10
shows the following locations of SPDs according to IEC standards:
1. At the boundary LPZ 0/X, SPDs should meet class I requirements, test impulse current = 10/350 µs.
2. At the boundary LPZ X/Y (X>0, Y>1), SPDs should meet
class II requirements, test impulse current = 8/20 µs.
See IEC 62305-44 for further discussions and applications.
22-8 LIGHTNING PROTECTION ACCORDING
TO NFPA STANDARD 780
NFPA 78010 is the guiding document for the lightning protection
of structures in the United States. There are more high-rise structures in the United States than in the rest of the world. NFPA first
adopted specifications for protection of buildings against lightning
in 1904, and subsequently, these specifications have been revised
at least 24 times, and 2008 is the current edition. This standard has
specific requirements for lightning protection of:
■
Ordinary structures
■
Special occupancies
■
Fixed and floating roof tanks
■
Heavy-duty stacks
■
Structures containing flammable vapors
■
Watercraft
LIGHTNING PROTECTION OF STRUCTURES
595
ds
FIGURE 22-10
■
Wind-turbines
■
Protection of livestock in fields
■
Protection of trees
LEMP zones according to IEC; see text.
■
Picnic grounds, playgrounds, ball parks, and other open
spaces
■
Parked aircraft, and so on
These specifics are not discussed. The standard excludes protection of electrical generating, transmission and distribution systems,
and also explosive manufacturing buildings and magazines. The basic
tenats of this standard and lightning protection philosophy are based
on Faraday cage, also called integral system or Franklin system.
22-9 LIGHTNING RISK ASSESSMENT ACCORDING
TO NFPA 780
In addition to direct losses, such as destruction of the building, fire,
and killing of livestock, indirect losses arise due to loss of business
and essential properties. A whole community may depend on the
integrity of a single structure for their safety and comfort and the
examples cited are a police station, a fire station, water-pumping plant,
telecommunication facility, and so on. The damage to museums
and cultural sites will be an irreplaceable loss of cultural heritage.
In most cases, the need for lightning protection may be obvious,
for example:
■
Large crowds
■
Service continuity
■
Very high lightning flash frequency
■
Tall isolated structures
■
Buildings containing explosives or flammable materials
■
Buildings containing irreplaceable cultural heritage
Apart from lightning flash density, the risk assessment accounts
for the following factors:
1. Building environment
2. Type of construction
596
CHAPTER TWENTY-TWO
FIGURE 22-11
Calculation of equivalent collective area for a rectangular structure according to NFPA 780.
When a LPS is installed, the following additional measures
should be considered:
3. Structure occupancy
4. Lightning stroke consequences
The following expression for the yearly lightning strike
frequency is specified:
N d = N g × Ae × C1 × 10−6
(22-19)
where Nd is yearly stroke frequency, and Ng is the yearly flash density in the region where the structure is located. Reference 10 provides a map of the United States, data collected by U.S. National
Lightning Detection Network (NLDN), showing the contours of Ng.
Ae is equivalent collective area of the structure, and C1 is environmental coefficient.
The equivalent collective area of a structure is defined as the area
obtained by extending a line with a slope of 1 to 3 from the top of
the structure to ground, completely around the structure. The calculation of equivalent area for various structure shapes is explained
with accompanying figures. Figure 22-11, for example, shows this
calculation for a rectangular structure of length L, width W, and
height H. The equivalent area in m2 is:
Ae = LW + 6H( L + W ) + π 9H 2
(22-20)
The environmental coefficient accounts for the topography of
site of the structure and any objects located within a distance of 3H
from the structure that can effect the collective area. These factors
are tabulated in the standard. As an example, for a structure located
within a space containing structures or trees of the same height or
taller within a distance 3H, C1 = 0.25.
The tolerable lightning frequency, Nc, is considered as:
1 . 5 × 10−3
C
(22-21)
C = C2 × C 3 × C 4 × C 5
(22-22)
Nc =
where:
where the coefficients C2, C3, C4, and C5 take into consideration the
construction, occupancy, contents, and so on. Briefly, these constants are tabulated in Table 22-6.
If Nd > Nc, the LPS should be installed. If Nd ≤ Nc, the LPS is optional.
Note that the standard does not use the words “not required.”
■
Limiting step-and-touch potentials
■
Restricting fire propagation
■
Limiting induced overvoltages
■
Reduceing effects of lightning-induced voltages to sensitive
electronic equipment
Compare these requirements with IEC standards discussed
earlier.
Example 22-1 A rectangular structure, L = 30 m, W = 20 m, H =
20 m, is considered. The structure is located in Texas with Ng = 3.
The structure is surrounded by smaller structures within a distance
3H, has metal construction with metal roof, stores irreplaceable cultural items of exceptional value, is normally occupied, continuity
of services is required, and there are no environmental effects. The
risk assessment is as follows:
From Eq. (22-20), calculate the equivalent collective area, for
the given dimensions. This gives Ae = 17909.9 m2.
Calculate expected lightning strike frequency to the structure from
Eq. (22-21). Here Ng = 3, and from the Table in this standard with
respect to location topology, C1 = 0.5. Substituting in Eq. (22-19),
Nd = 0.026—yearly lightning strike frequency to the structure.
Read factors C2, C3, C4, and C5 from Table 22-6, based on the
given conditions. These factors are C2 = 0.5, C3 = 4.0, C4 =1.0, C5 =
5.0, C =10.
Calculate tolerable lightning frequency to the structure, from
Eq. (22-21). This gives Nc = 0.15 × 10–3 yearly lightning strike frequency to the structure.
As Nd > Nc, the lightning protection is required. Now consider
that the same structure, exactly under the same physical environment, construction, occupancy, and usage, is located in Florida,
with Ng = 12. Then the yearly frequency Nd becomes 0.104, and
more care must be taken in designing the lightning protection for
such a structure.
22-10
PROTECTION OF ORDINARY STRUCTURES
An ordinary structure is defined as any structure that is used for
ordinary purposes, whether commercial, industrial, farm, institutional, or residential.
LIGHTNING PROTECTION OF STRUCTURES
TA B L E 2 2 - 6
597
Risk Assessment According to NFPA 78010 (Determination of Coefficients C 1, C 2, C 3, C 4, C 5)
ENVIRONMENTAL COEFFICIENT C1
C1
Relative structure location
Structure located within a space containing structures or trees of the same height or taller within a distance of 3H
0.25
Structure surrounded by smaller structures within a distance 3H
0.5
Isolated structure, no other structure located within 3H
1
Isolated structure on a hilltop
2
STRUCTURE COEFFICIENT C2
Structure
Metal Roof
Nonmetallic Roof
Flammable Roof
Metal
0.5
1.0
2.0
Nonmetallic
1.0
1.0
2.5
Flammable
2.0
1.0
3.0
STRUCTURE CONTENTS COEFFICIENT C3
Structure contents
C3
Low value and inflammable
0.5
Standard value and nonflammable
1.0
High value, moderate flammability
2.0
Exceptional value, flammable, computer and electronics
3.0
Exceptional value, irreplaceable cultural items
4.0
STRUCTURE OCCUPANCY COEFFICIENT C4
Structure occupancy
C4
Unoccupied
0.5
Normally occupied
1.0
Difficult to evacuate or risk of panic
3.0
LIGHTNING CONSEQUENCE COEFFICIENT C5
Lightning consequence
C5
Continuity of facility services, not required, no environmental effect
1.0
Continuity of facility services required, no environmental effect
5.0
Consequences to the environment
10.0
The construction materials used for lightning protection are
divided into two classifications:
1. Class I materials, consisting of lightning conductors,
air terminals, ground terminals, and associated fittings, are
required for lightning protection of structures not exceeding
75 ft (23 m).
2. Class II materials, of similar nature as class I materials, are
used for structures exceeding 75 ft (23 m).
The Tables in NFPA 78010 provide specifications and sizing of
air terminals, main conductor, bonding conductor, and so on. Class II
materials are of heavier size and cross-sectional area.
Roof types of structures with respect to shape, (e.g., flat, mansard, hip, gable, and so on), construction materials, slope, multilevels,
conductor placements, air terminal height, and support systems are
specified. The zone of protection is dependent on the geometry of
the structure. Here we limit our discussions to the rolling sphere
method and strike termination devices on a flat roof.
22-11
NFPA ROLLING SPHERE MODEL
The zone of protection depicting rolling sphere model is shown in
Fig. 22-12. It has a radius of 46 m (150 ft). The zone of protection
includes the space not intruded by a rolling sphere.
■
Where the sphere is tangent to the earth and resting against
the strike termination device, all space in the vertical plane
between the two points of contact and under the sphere is considered to be in the zone of protection.
■
A zone of protection is also formed when such a sphere is resting on two or more strike termination devices and includes the
space in the vertical plane under the sphere and between those
devices, Fig. 22-13. Note that the zone of protection is limited to
the space above the horizontal plane of the lowest structure. For
structures exceeding 46 m height above earth or “above a lower
strike termination device,” the protection zone is the vertical
plane between the points of contact and also the point where the
sphere is resting against a vertical surface of the structure and the
lower termination device to earth.
598
CHAPTER TWENTY-TWO
FIGURE 22-12
Protection by rolling sphere method, NFPA 780.
Equation (22-23) is based on a striking distance of 46 m. For
Eq. (22-23) to be valid, the sphere shall be tangent to lower roof or
in contact with the earth, and in contact with vertical portion of the
higher portion of the structure.
Figure 22-13 shows the principle applied to structures above
150 ft height. The shaded area shows the protection zone. The difference in heights between the upper and lower roofs and earth
shall be 46 m or less.
Figure 22-15 shows a conduction LPS for flat roof, with their
major components and spacing.
Example 22-2 Design an air termination system according to
NFPA 780 for a rectangular flat roof, with dimensions 100 × 80 m.
Based on Fig. 22-15, the system requires:
■
94 air terminals
■
7 longitudinal conductors, spaced approximately 13.33 m
apart
■
7 cross conductors
■
10 down conductors to grounding grid at the base of the
structure
FIGURE 22-13
Rolling sphere method applied to structures higher
Material specifications are not discussed.
than 150 ft.
22-12 ALTERNATE LIGHTNING
PROTECTION TECHNOLOGIES
Figure 22-14 depicts 46-m geometric model for structures up
to height of 46 m. Based on the height of the strike termination
device for the protected structure (7.6, 15, 23, 30, and 46 m) above
ground, reference to the appropriate curve shows anticipated zone
of protection for objects and roofs at lower elevations. The horizontal protective distance found from the curve can also be calculated
from:
d = h1(300 − h1 ) − h2 (300 − h2 )
(22-23)
where d is horizontal distance in ft, h1 is height of the higher roof,
and h2 is height of the lower roof.
This section discusses some alternate lightning protection technologies. The research continues in this important field. However, it is
important to state that the manufacturers presented their cases for
incorporation of alternate lightning protection technologies while
the technical committee of NFPA 780 was considering the 2004
revision. The committee did not accept incorporation of any of
these technologies in the standard. Also, the 2008 revision does not
incorporate any of these technologies.
22-12-1 Franklin Rods—Sharp versus Blunt Tips
There is some controversy ranging with respect to sharp versus
blunt Franklin rods. The air terminal is meant to attract and direct
the stroke leader, and its effectiveness is assessed on the basis of
LIGHTNING PROTECTION OF STRUCTURES
FIGURE 22-14
FIGURE 22-15
Zone of protection utilizing rolling sphere method.
Air terminals on a flat or gently sloping roof, NFPA 780.
599
600
CHAPTER TWENTY-TWO
probability of capture of charged particles for a given configuration. Langmuir researchers (Langmuir Labs, New Mexico, United
States11), experimented with sharp-pointed lightning rods on the
top of a mountain that did not work, and the lightning instead
struck the nearby trees because of the buildup of corona discharge
around the rod’s tip. This shifted the positive charged wave away
from the rod, seeking a lesser disruptive path. Further research is
reported in Ref. 12, and the following relations are presented.
High probability of lightning striking the Franklin rod:
H + D > DL + D
H > DL
(22-24)
22-12-3 Laser Beam Systems
High probability of lightning striking the ground:
H + D < DL + D
H < DL
(22-25)
Equal probability of lightning striking the ground and rod:
H + D = DL + D
H = DL
discharge currents were measured before and during the thunderstorm. Figure 22-16 shows that when the field strength exceeded
1000 V/m, both the radioactive terminal and the sharp-pointed rod
emitted the same ionization current. Average DL for enhanced air
terminals (radioactive terminals) under thunderstorm conditions is
longer than DL for Franklin rod12. But under fair weather conditions, with low absolute humidity, reverse is true. The authors conclude that sharp air terminals are more efficient than blunt ones in
attracting flashovers, and that ionized terminals are more efficient
than nonionized terminals.
(22-26)
where DL is gain in the length H as an upward connecting leader
is formed by the approaching downward leader, and D is an
empirical relation between the leader current and striking distance
(Whitehead’s relation).
22-12-2 Ionizing Terminals (Radioactive
Lightning Terminals)
These are not so new in the market and have been available for
quite some time. These are based on the use of radio isotopes in
the metal of the air terminal. It is usually of the pointed design,
and the number of elements are supposed to control the reach of
the collector. However, a controversy has prevailed. Figure 22-16
shows the results of two test programs conducted by independent
researchers in Sweden and Switzerland. A radioactive terminal
and a sharp Franklin rod were installed at the same height and
The laser beam system was developed by Leonard Ball.13 The
laser was termed “mode-locked” system that produced large-scale
multiphoton ionization (MPI) in the right place at the right time.
It claims to divert the downward leader and the resulting channel
from distances of several kilometers. The major considerations are
cost, state of development, and the problem of diverting the stroke
energy to earth without damaging the laser itself.
22-12-4 Lightning Prevention (Dissipation Systems)
The dissipation array system (DAS, U.S. Patent No. 4180698) is supposed to prevent a lightning stroke to both the protected area and the
array itself. Figure 22-17 shows the component parts—an ionizer, a
ground current collector, and interconnections to ground grid. The
ionizer consists of an array of multiple sharp points, designed for the
specific applications. It provides ionization to transfer the collected
charge through it and the surrounding air molecules. The earth charge
collector (ECC) are the conventional grounding systems. These are
augmented, so that the grounding resistance is lowered. It collects
the charge induced in the area and equipment to be protected. And
finally, the charge conducting system provides a low impedance path
between EEC and ionizer. It claims to:
■
Prevent direct stroke to the protected facility
■
Reduce electrostatic field within the sphere of influence
■
Provide an area free of lightning-related electromagnetic
phenomena
F I G U R E 2 2 - 1 6 Conventional rod versus radioactive terminals,
discharge patterns; two test results by independent authorities.
A lightning stroke neutralizes the charge differential between
the base of a storm cloud and its image charge on the earth below.
By making the intervening air space a leaky dielectric, the same
function can be achieved slowly. DAS encourages the trickle charge
concept through the use of point discharge.
An electrostatic field near a pointed conductor tends to concentrate on the point, enhancing the electrical field. Under fair weather
conditions, an electrical field exists at the ground. At an altitude
increase, the air has high conductivity, and the surface of earth,
which is also a good conductor, constitutes a sort of capacitor, two
plates charged to different potentials. The positive field at ground
is about 130 V/m.
The point discharge current will start to flow from the tip of an
earthed vertical conductor as soon as the electrical field exceeds
a critical value, which is required to initiate ionization by collision.
Under a thunderstorm, the base of the cloud has mostly negative charge, and upper part of cloud is positively charged (Chap. 5).
The negatively charged base will attract positive charges from the
ground. Thus, under fair weather conditions, while the cloud is
negatively charged, it becomes positively charged under a thunderstorm. The point discharge current, from the array of thousands of
sharpened points, will carry away positively charged ions. These
will move away from the array, and depending on the wind velocity,
these will form a space charge that reduces electrical field around the
points, since lines of force will terminate on these ions rather than
LIGHTNING PROTECTION OF STRUCTURES
FIGURE 22-17
Principals of DAS. (Copyright Lightning Eliminators and Consultants, Inc. Reproduced with permission.)
on the sharpened points. This will progress till the electrical field is
reduced below corona level. As the space charge is carried away by
the wind, the electrical fields near the points increase again, and the
new corona discharge starts. Thus, point discharge currents have a
pulsed nature at some interval of time. As a result, the initiation of
the upward leader would not take place, and the lightning strike
will be eliminated.
Figure 22-18 shows a hemispherical array, consisting of multiple
sharp points—this array is called an ionizer. Depending on the
structure to be protected, the arrays of different configurations,
dimensions, and shapes have been fabricated.
Two extensive investigations of the system were conducted.
J. Hughes organized the first investigation, “Review of Lightning
Protection Technology for Tall Structures,” Lyndon B. Johnson
Space Center, Clear Lake City, Houston, Texas. Twelve analysts
FIGURE 22-18
601
presented different views about the efficacy of multipoint systems.14
The conclusions drawn were:
■
Single point corona currents exceeded multipoint corona
currents.
■
A single point at a height of 50 ft always gave more corona
than DAS at the same height.
■
The DAS did not eliminate lightning.
■
The lightning stroke is photographed, striking an array many
times with measured currents of the order of 30 to 50 kA.
In another investigation, the DAS was installed on an air traffic
control tower. Examination of the multipoint array after lightning
A hemisphere multipoint array, typical DAS system. (Copyright Lightning Eliminators and Consultants, Inc. Reproduced with permission.)
602
CHAPTER TWENTY-TWO
stroke showed missing spikes and mechanical expansion, and bulging of down conductors was noted, showing that these passed large
amounts of lightning current.
Yet, in many practical installations covering substations, tall
structures, communication facilities, power stations, and the petroleum and paper industries, the system is reported to be effective.15
Thus, it may be inferred that the system does not entirely eliminate
lighting strikes, but is still effective in most applications.
22-12-5 Coaxial Cable as a Down Conductor
A low impedance path from the terminals to ground is imperative. Tests demonstrate that with a steep voltage, wave front, such
as created by lightning surge impedance of conventional conductors, increases to a point where side flashes can occur. Specially
manufactured large bare copper conductors have been used, and
bonding to metallic parts of the structures is a common practice
while the conductors are run as straight as possible, without kinks
and bends to the ground terminations. A coaxial cable is a recent
development and has a surge impedance of 16 to 126 Ω versus 500
to 5000 Ω for conventional open wire conductors.
22-13
IS EMF HARMFUL TO HUMANS?
Associations have been made between various cancers and leukemia and electromagnetic fields in some epidemiological studies,
which attracted a lot of public concern and exposure in the media.
However, these studies cannot be called conclusive. Some studies
were based on indirect assessment of exposure, in geographical
areas close to the power lines, rather than actual measurement of
flux density. Some studies, which suggested associations between
health and magnetic fields, indicated exposures that are less than
the theoretical threshold level for creation of an electrical current
density in head or trunk, comparable in magnitude to the current
density levels that occur in normal body processes. Other studies
indicated that weak magnetic fields are associated with an adverse
response while strong ones are not. Data on some other studies will
even suggest a potential beneficial effect. In June 2001, an expert
scientific group of IARC (International Agency for Research on
Cancer) reviewed studies and extremely low magnetic fields (ELFs)
were classified as “possibly carcinogenic.” To put this classification
in proper prospective, note that “coffee” and “gasoline engines” are
also classified as possibly carcinogenic.
22-13-1 EMF Sources
ELFs occur in every office environment and wherever electricity
is used. Electrical fields arise from electrical charges, measured in
V/m, and magnetic fields arise from motion of electrical charges,
that is, current, and expressed in Telsa (T) or sometimes Gauss
(10000 G = IT). These fields are not shielded by most common
materials. Their frequencies are 50 or 60 Hz, with higher harmonics up to 300 Hz and lower harmonics up to 5 Hz. The magnetic
field values in homes in North America average 0.11 µT, and electrical fields average tens of V/m. Readings in the field taken under
a 380-kV line at the point of greatest sag showed a magnetic flux
density of 15 to 20 µT, and electrical field can be several hundred
V/m. Close to appliances, the magnetic fields may be much higher.
22-13-2
Levels
According to a study by WHO, interaction between current and
muscle cells occurs above a body current density of 1000 mA/m2.
The lowest level for detection of biological effects is 10 mA/m2.
Below 1 mA/m2, there are no biological effects. A current density of
1.2 mA/m2 corresponds to 5 kV/m for the electric field, and 100 µT
for the magnetic field. These are the values adopted in some European
countries with short-term higher values.
22-13-3 Monitoring and Survey
Monitoring can be performed using sensitive and accurate gauss
meters. The meter should be able to measure a flux of 0.01 µT. A
large number of readings may be taken over a course of time. Evaluating a personal exposure involves determining weighted average
and mean density at waist level.
22-13-4 Screening
If the levels are found to be high, possibly close to load centers,
switchgear, cables, and metal trays, low content carbon steel or
nickel content alloys are used for shielding. A magnetic shield
should have low reluctance and remain unsaturated.
WHO published a new monograph reviewing the scientific literature on health effects of ELF in 2007.16 This evaluated all the
available evidence accumulated over three decades of research. A
technical guide for measurements of low-frequency electrical and
magnetic fields near overhead power lines is discussed in Ref. 17.
Characteristics of ELF magnetic fields are discussed in Ref. 18.
This chapter provides a glimpse into the fascinating art and
science of protection of structures against lightning. Research
continues in this field. Approximately 1000 persons are hit with
lightning every year in the United States. EPRI organized a mock
power distribution system in the state of Florida, the area of highest
lightning activity in the United States, and with RTL studies investigated the effect of lightning on buried cables. It was found that the
ground flashes of lightning created channels of intense heat, which
fused the sand and clay together into molten glass-like crystals, and
these channels ran across the concrete walls of the trenches to seek
the buried cables.19
PROBLEMS
1. Calculate the equivalent length of the grounding conductor
for a lightning surge of rise time = 200 kA/µs, surge current =
100 kA, soil resistivity = 500 Ω-m. Consider that the point of
impact is the center of a mesh-grounding electrode system.
2. A building has a ground conductor run along its parameter,
total length = 400 m. Considering a soil resistivity of 500 Ω-m,
and according to IEC standards, is it adequate to prevent shock
hazard?
3. What is the recommended value of the resistivity of soil
around a structure within a range of 3 m from the conductor
according to IEC to prevent hazard due to step-and-touch
potential? How can this resistivity be obtained in a soil of natural resistivity of 100 Ω-m?
4. Compare IEC LEMP zones of protection with ANSI/IEEE
categories in Chap. 19.
5. Describe the differences between NFPA 780 and IEC rolling
sphere methods of lightning protection. IEC standard does not
recommend any intermediate lightning termination system for
structures higher than 60 m, and accepts the risk of side flashes.
NFPA rolling sphere method requires a radius of 46 m (150 ft)
tangent to earth of lower level of the structure. Comment.
6. A structure is 95 m tall. How will the lightning protection
be approached with respect to IEC and NFPA standards?
7. Write an expression for (1) fire risk and (2) shock hazard
risk based on the component risk factors according to IEC
discussed in this chapter.
8. Conduct a risk analysis, according to NFPA 780, to ascertain
if a LPS is required for the following building installation:
LIGHTNING PROTECTION OF STRUCTURES
Building dimensions = 80 × 100 m, 60 m high factor, C1 =
0.25, Ng = 4, nonmetal construction with nonmetallic roof,
high value and moderate flammability, normally occupied,
continuity of service required, with no environmental effects.
9. In Prob. 8, design a roof lightning termination system
according to NFPA 780. Calculate the number of roof conductors, spacing of roof conductors, number of air terminals, and
number of down conductors.
REFERENCES
1. IEC 62305-1, Protection Against Lightning, Part 1—General
Principles, 2006.
2. IEC 62305-2, Protection Against Lightning, Part 2—Risk
Management, 2006.
3. IEC 62305-3, Protection Against lightning, Part 3—Physical
Damage to Structures and Life Hazard, 2006.
4. IEC 62305-4, Protection Against Lightning, Part 4—Electrical
and Electronic Systems Within Structures, 2006.
5. IEC 60079-10, ed. 4.0, Electrical Apparatus for Explosive Gas
Atmospheres, Part 10—Classification of Hazardous Areas, 2009.
6. R. H. Lee, “Lightning Protection of Buildings,” IEEE Trans. IA,
vol. 15, pp. 237–240, 1979.
7. IEEE Working Group Report, “A Simplified Method of Estimating
Lightning Performance of Transmission Lines,” IEEE Trans. PAS,
vol. PAS 104, no. 4, pp. 912–932, 1985.
8. A. J. Eriksson, “The Incident of Lightning Strikes to Power
Lines,” IEEE Trans. Power Delivery, PWRD-2, pp. 859–870, 1987.
9. F. A. M. Rizk, “Modeling of Transmission Line Exposure to
Direct Lightning Strokes,” IEEE Trans. Power Delivery, vol. 5,
no. 4, pp. 2009–2029, 1990.
10. NFPA 780, Standard for Installation of Lightning Protection
Systems, 2008.
11. D. Eskow, “Striking Back at Lightning,” Popular Mechanics,
Aug. 1983.
12. K. P. Heary, A. Z. Chaberski, S. Gumley, J. R. Gumley, F. R. Richens,
and J. H. Moran, “An Experimental Study of Ionization Air
Terminal Performance,” in Conf. Record, IEEE Power Engineering
Society Summer Meeting, Portland, Oregon, July 1998.
603
13. L. M. Ball, “The Laser Lightning Rod System: Thunderstorm
Domestication,” Applied Optics, vol. 13, pp. 2292–2295, Oct. 1974.
14. R. M. Bent and S. K. Llewellyn, “An Investigation of the Lightning Elimination and Strike Reduction Properties of Dissipation
Arrays,” in Conf. Record, Review of Lightning Protection Technology
for Tall Structures, Lyndon B. Johnson Space Flight Center, Clear
Lake City, Houston, TX, Nov. 1976.
15. R. B. Carpenter, Jr. and M. M. Drabkin, Lightning Strike
Protection, LEC, Inc. Colorado, March 2005. Available at:
http://www.lightningeliminators.com
16. WHO Environmental Health Criteria No. 238, Geneva 2007.
Available at: http:/www.who.int/peh-emf/publications/elf_ehc/
en/index.html
17. CIGRE Work Group, GT C4.203, “Technical Guide for
Measurement of Low Frequency Electrical and Magnetic Fields
Near Overhead Power Lines,” Electra, no. 243, pp. 32–39,
April 2009.
18. CIGRE Work Group, TF C4.205, “Characteristics of ELF
Magnetic Fields,” Electra, no. 231, pp. 62–69, April 2007.
19. NOVA-Lightning, Videocassette, WGBH, P.O. Box 2284,
S. Burlington, VT 05407-2284, USA.
FURTHER READING
I. Cotton and N. Jenkins, “Lightning Protection of Wind Turbines,”
International Conference and Exhibition on Lightening protection, Paper
No. 6.1, Solihull, West Midlands, UK, 1998.
J. C. Das, “Lightning Protection of Industrial and Commercial
Facilities—What is New?” Construction Journal of India, vol. II, Issue 1,
pp. 32–38, Jan./Feb. 1999.
IEEE Std. C95.6, IEEE Standard for Safety Levels with Respect to
Human Exposure to Electromagnetic Fields, 0–3 kHz, 2002.
M. E. Morris, R. J. Fisher, G. H. Schnetzer, K. E. Merewether, and
R. E. Jorgenson, “Rocket Triggered Lightning Studies for Protection
of Critical Assets,” in Conf. Record, IEEE Ind. and Commercial Power
System Conference, 1993, St. Petersburg, Florida.
NFPA 115, Standard for Laser Fire protection, 2003.
B. Richardson, “Lightning Protection of Hi-Tech Buildings,” EC&M,
Aug. 1989.
WHO Media Center. Fact Sheet No. 322, June 2007.
This page intentionally left blank
CHAPTER 23
DC SYSTEMS, SHORT
CIRCUITS, DISTRIBUTIONS,
AND HVDC
AC and dc systems are generally interconnected at some interface
and the transient behavior of one impacts the other, though there
can be stand-alone dc systems. The short-circuit transients, dc
current interruption, trends in residential and commercial dc distributions, and HVDC transmission systems are discussed in this
chapter. From the transient analysis point of view HVDC systems
provide considerable challenges.
23-1
SHORT-CIRCUIT TRANSIENTS
IEC standard1 is a comprehensive document on the subject; though
the dc short-circuits currents are covered in some other publications too, which are referred in proper context in this chapter. This
IEC standard addresses calculation of short-circuit currents in dc
auxiliary installations in power plants and substations and does
not include other dc systems, for example, electric railway traction
and transit systems.
The dc sources analyzed for the short-circuit transients are:
■
Lead acid batteries
■
DC motors and generators
■
Converters in three-phase bridge configuration
■
Smoothing capacitors.
1 − e − t /τ1
1− e
− t p /τ1
i2 (t ) = i p [(1 − α )e −( t −t p)/ τ 2 + α] t ≥ t p
α=
Ik
ip
23-1-1
Short Circuit of a Lead Acid Battery
We studied the transient in an RL circuit in Chap. 2. The short
circuit of a battery is analogous:
i=
EB
(1 − e −( R /L )t )
R
(23-1)
(23-2)
(23-3)
(23-4)
where EB is internal battery voltage, R is the total resistance in the
circuit, which is given by:
R = R B + RC + R L
Figure 23-1 shows typical time current profiles of these sources
and Fig. 23-2 shows approximation function assumed in Ref. 1. The
function is described by:
i1 (t ) = i p
where Ik is the quasi-steady-state short-circuit current, Ip is the peak
short-circuit current, tp is the time to peak, t1 is the rise time constant, and t2 is the decay time constant.
The quasi-steady-state current Ik is conveniently assumed as the
value at 1 s after beginning of the short circuit. If no definite maximum is present, as shown in Fig. 23-1a for the converter current,
then the function is given by Eq. (23-1).
(23-5)
where RB is the internal cell resistance, RC is the resistance
of cell interconnections, and RL is the lead resistance. These
resistances must be accurately calculated. Similarly the inductance L is:
L = LCC + L BC + L L
(23-6)
where LCC is the inductance of the cell structure, LBC is the inductance of the battery cells considered as bus bars, and LL is the
inductance of the battery leads. The internal inductance of the cells
can be considered to be zero. Again these inductances are small and
should be accurately calculated.
605
606
CHAPTER TWENTY-THREE
F I G U R E 2 3 - 1 Short-circuit current profiles of dc sources. (a) Rectifier with and without smoothing reactor. (b) Lead acid battery. (c) Capacitor. (d) Dc
motor with and without additional inertia mass.1
From Eq. (23-4) the maximum battery short-circuit current is:
I Bsc =
EB
R
(23-7)
R B = R cell N =
and the initial rate of rise is:
diB EB
=
dt
L
The battery internal resistance is normally specified by the battery manufacturer. An expression from Ref. 2 is:
(23-8)
Rp
Np
(23-9)
where Rcell is the resistance in ohms per cell, N is the number of
cells, Rp is the resistance in ohms per positive plate, and Np is the
number of positive plates in a cell. Rp is given by:
Rp =
V1 − V2
Ω/positive plate
I 2 − I1
(23-10)
where V1 is the cell voltage and I1 is the corresponding rated discharge current per plate. Similarly, V2 is the cell voltage and I2 is the
discharge current at V2. Another expression from Ref. 3 is:
RB =
FIGURE 23-2
Standard approximation of short-circuit function.1
EB
Ω
100 × I 8hr
(23-11)
where I8hr is the 8-h ampere rating of the battery to 1.75 V per cell at
25°C. RB is not a constant quantity and depends on the charge state of
the battery. A discharged battery has a much higher cell resistance.
Example 23-1 Consider a 120-V battery of 200 A-h rating,
8-hr rate of discharge to 1.75 V, each cell having dimensions of
height 7.9 in, length is 10.7 in, width is 6.8 in. The battery is rack
mounted, 30 cells per row as shown in Fig. 23-3; cell connectors
are 250 KCMIL, diameter is 0.575 in. The battery is connected
through a cable of approximately 100 ft, cable resistance 5 mΩ, and
inductance 14 µH to a circuit breaker.
DC SYSTEMS, SHORT CIRCUITS, DISTRIBUTIONS, AND HVDC
FIGURE 23-3
Lead acid battery system layout for calculation of battery short-circuit current.
Calculations According to IEEE Equations The equation for
the battery short-circuit current can be written based on Eq. (23-4)
by calculating all the resistance and inductance in the circuit.
The manufacturer specifies the following expression for internal
resistance of this battery:
RB =
31EB
mΩ
I 8hr
The inductance of two round conductors of radius r, spaced at
distance d is given by:
(23-12)
where L is in henry per meter, m0 is the permeability in vacuum =
4π × 10−7 H/m. From Fig. 23-3, the distance d = 24 in., and
r, the radius of 250 KCMIL conductor, is 0.2875 in. Substituting
these values gives LCC = 1.87 µH/m. For an 18-ft loop length,
LCC = 10.25 µH
The inductance of the battery cells can be determined by considering each row of cells like a bus bar at spacing d = 24 in, height
of bus bar h = height of cell = 7.95 in, width of bus bar w = width
of cell = 6.8 in. The inductance is given by:
L BC =
µ0 3
d
+ ln
H/m
h + w
π 2
120
= 4 . 19 × 106 A /s
28 . 61 × 10−6
28 . 61 × 10−6
= 1 . 14 ms
25 . 089 × 10−3
The current, therefore, reaches 0.63 × 4781 = 3012 A in 1.14 ms,
and in 2.28 ms it will be 0.87 × 4781 = 4159 A.
Calculations as per IEC Standards In the IEC method of calculation1 the battery resistance RB is multiplied by a factor of 0.9, while
all other resistances remain unchanged. Also, if the open-circuit voltage of the battery is not known, then use EB = 1.05UnB, where UnB =
2.0 V/cell for the lead acid battery. The peak current is given by:
ipB =
120
× 103 = 4781 A
25 . 1
µ0
d
0 . 25 + ln
r
π
Substituting the values gives: LBC = 4.36 µH. The total inductance
in the system = 10.25 + 4.36 + 14 = 28.61 µH. The initial rate of
rise of current is:
and the time constant is:
Substituting the values, this gives a battery resistance of 18.6 mΩ.
If Eq. (23-11) is used, then RB = 6 mΩ. To use Eqs. (23-9) and
(23-10), a battery discharge curve published by the manufacturer
is required. This shows initial cell voltage versus the amperes per
plate and also the various discharge rate curves.
For purpose of this example, let us consider RB = 18.6 mΩ.
From Fig. 23-3, the total length of battery connectors is 28 ft. The
resistance at 25°C can be read from appropriate tables in electrical
handbooks or analytically calculated; it is equal to 1.498 mΩ. Thus,
the total resistance in the battery circuit including lead length is
25.1 mΩ. The maximum short-circuit current is therefore:
L=
607
(23-13)
EB
R BBr
(23-14)
where ipB is the peak current and RBBr is the total equivalent resistance.
The time to peak and the rise time are read from the curves in IEC,1
which are not reproduced, based on 1/d, which is defined as follows:
1
2
=
δ (R BBr / L BBr ) + (1/TB )
(23-15)
The time constant TB = 30 ms and LBBr is the total equivalent
inductance to the fault point. The decay time constant τ 2B = 100 ms.
The quasi-steady-state current is given by:
I kB =
0 . 95EB
R BBr + 0 . 1R B
(23-16)
This considers that battery voltage falls and the internal cell resistance increases after a short circuit. All equations in IEC are in MKS
units. The curves in IEC for calculations of short-circuit currents in
this example and other examples to follow are not reproduced. An
interested reader may like to get a copy of this standard.4
608
CHAPTER TWENTY-THREE
Example 23-2 Example 23-1 is repeated with IEC method of calculation. The total resistance and inductance in the battery circuit are:
R BBr = 0 . 9 × 18 . 6 + 1 . 498 + 5 = 23 . 238 mΩ
L BBr = 28 . 61 µH
H
Therefore, the maximum short-circuit current is:
ipB =
1 . 05 × 120
= 5 . 42 kA
23 . 238 × 10−3
Calculate 1/d from Eq. (23-15)
1
2
= 2 . 37 ms
=
δ 23 . 238 × 10−3
1
+
28 . 61 × 10−6
30 × 10−3
Then from the curve in Ref. 1, time to peak is approximately
5.4 ms, and the rise time is 1.2 ms. The quasi-steady-state current is:
I kB =
0 . 95 × 1 . 05 × 120
= 4 . 77 kA
23 . 238 + 0 . 1(18 . 6)
Short-circuit current plots according to this calculation are shown
in Fig. 23-4(a).
23-1-2 Short Circuit of DC Motors and Generators
ANSI/IEEE Method of Calculation
An expression for the shortcircuit currents of dc motors and generators is:3
ia =
e
e
e0
−σ t
(1 − e −σ at ) − 0 − 0 (1 − e f )
r
r
rd′
′
d
d
(23-17)
where ia is the per unit current, e0 is the internal emf prior to short
circuit in per unit, rd is the steady-state effective resistance of the
machine in per unit, r′d is the transient effective resistance of the
machine in per unit, sa is the armature circuit decrement factor,
and sf is the field circuit decrement factor.
The first part of the equation has armature time constant, which
is relatively short and controls the buildup and peak of the short
circuit current, the second part is determined by the shunt field
excitation and it controls the decay of the peak value. The problem with
the calculation is that the time constants in this equation are not
time-invariant. Saturation causes the armature circuit decrement
factor to increase as the motor saturates. Approximate values suggested for saturated conditions are 1.5 to 3.0 times the unsaturated
value and conservatively a value of 3.0 can be used. The unsaturated value is applicable at the start of the short-circuit current
and the saturated value at the maximum current. Between these
two extreme values, the decrement is changing from one value to
another. Figure 23-5 shows the approximate curve of the shortcircuit current and its equivalent circuit. For the first two-thirds of
the curve, the circuit is represented by machine unsaturated inductance La′ , and for last one-third part of the short-circuit curve La′ is
reduced to 1/3 with series transient resistance. The peaks shortcircuit current in per unit is given by:
ia′ =
e0
rd′
(23-18)
The transient resistance rd′ in per unit requires some explanation. It is the effective internal resistance:
rd′ = rw + rb′ + rx′
FIGURE 23-4
(23-19)
Calculated short-circuit current-time plots. (a) Lead
acid battery. (b) DC motor. (c) Rectifier. (d) Capacitor.
DC SYSTEMS, SHORT CIRCUITS, DISTRIBUTIONS, AND HVDC
609
The armature circuit decrement factor is:
σa =
rd′2π f
Cx
(23-24)
The maximum rate of rise of current in amperes per second is
given by:
dia V1e 0
=
dt
La′
(23-25)
Rate of rise of current can also be expressed in terms of per unit
rated current:
dia
PN1e 0
=
dt 19 . 1C x
FIGURE 23-5
Short-circuit time curve for a dc motor or generator,
showing two distinct time constants.
where rw is the total resistance of the windings in the armature circuit, rx′ is equivalent to flux reduction in per unit, and rb′ is the
transient resistance equal to reactance voltage and brush contact
resistance in per unit. The flux reduction and distortion are treated
as ohmic resistance. The values of transient resistance rd′ in per unit
are given graphically in the AIEE Committee report5 of vintage
1950, depending on the machine rating, voltage, and speed. The
transient resistance is not constant and there is a variation band.
The machine load may also affect the transient resistance.6 Similarly, the steady-state resistance is defined as:
rd = rw + rb + rx
(23-20)
(23-26)
In Eqs. (23-25) and (23-26), e0 can be taken equal to unity without
appreciable error. More accurately e0 can be taken as 0.97 per unit for
motors and 1.03 for generators. The inductance La′ is given in tabular
and graphical forms in an AIEE publication.7 Figure 23-6 shows La′
values in mH for certain motor sizes, without pole face windings. The
recent IEEE standard8 reiterates this calculation method.
Example 23-3 Calculate the terminal short-circuit current of a
230-V, 150-hp, 1150-rpm motor. The motor armature current is
541 A.
From graphical data in Ref. 3, the transient resistance =
0.068 per unit. The inductance La′ from graphical data in Fig. 23-6
is 1.0 mH. Then, the peak short-circuit current is:
I a′ =
Ia
541
=
= 7956 A
rd′ 0 . 068
where rb is the steady-state resistance equivalent to reactance voltage and brush contact in per unit, and rx is steady-state resistance
equivalent to flux reduction in per unit. The maximum rate of rise
of the current is dependent on armature unsaturated inductance.
The unit inductance is defined as:
L a1 =
V1 2 × 60
I a 2π PN1
(23-21)
Per unit inductance is the machine inductance La′ divided by the
unit inductance:
Cx =
La′ PN1 La′ I a
=
19 . 1 V1
L a1
(23-22)
This can be written as:
La′ =
19 . 1C x V1
PN1I a
(23-23)
where P is the number of poles, N1 is the base speed, V1 is the rated
voltage, Ia is the rated machine current, and Cx varies with the type of
machine. Charts of initial inductance plotted against unit inductance
show a linear relation for a certain group of machines. For this purpose, the machines are divided into four broad categories as follows:
Motors: Cx = 0.4 for motors without pole face windings.
Motors: Cx = 0.1 for motors with pole face windings.
Generators: Cx = 0.6 for generators without pole face windings.
Generators: Cx = 0.2 for generators with pole face windings.
FIGURE 23-6
Inductance of dc motors in mH versus motor hp.
610
CHAPTER TWENTY-THREE
FIGURE 23-7
Equivalent circuit: short circuit of a dc motor. Total short circuit current-summation of partial short-circuit currents from battery, rectifier,
and capacitor.
At normal speed or decreasing speed with τ mec ≥ 10τ F, the factor
κ M = 1, where τ mec is mechanical time constant given by:
and the initial rate of rise of the current is:
dia V1
230
=
=
= 230 kA /s
dt La′ 1 × 10 −3
τ mec =
As shown in Fig. 23-5, time constant changes at point b.
(23-31)
where J is the moment of inertia and Mr is the rated torque of the
motor.
The field time constant is given by:
La′
3rd′
The base ohms are Va /Ia = 230/541 = 0.425. Therefore, rd′ =
(0.425) (0.068) = 0.0289 Ω. This gives a time constant of 11.52 ms.
IEC Method of Calculation The resistance and inductance network for short circuit of a dc machine with a separately excited field
is shown in Fig. 23-7. The equivalent resistance and inductance are:
R MB = R M + R ML + R y
(23-27)
L MB = L M + L ML + L y
where RM and LM are the resistance of the armature circuit, including brushes, RML and LML are the resistance and inductance of the
conductor in the motor circuit, respectively, and Ry and Ly are the
resistance and inductance of the common branch, respectively, if
present. The time constant of the armature circuit to the point of
short circuit is given by:
τM =
L MB
R MB
(23-28)
The quasi-steady-state short-circuit current is given by:
I KM =
L F U rM − I rM R M
L0 F
R MB
I KM = 0
when n → 0 (23-29)
where LF is the equivalent saturated inductance of the field circuit
on short circuit, L0F is the equivalent unsaturated inductance of the
field circuit at no load, UrM is the rated voltage of the motor, IrM is
the rated current of the motor, n is the motor speed, and nn is the
rated motor speed.
The peak short-circuit current of the motor is given by:
ipM
2π Jn0 R MBI rM
M rU rM
U −I R
= κ M rM rM M
R MB
τF =
LF
RF
for τ mec ≥ 10τ F the time to peak and time constant are given by:
t pM = κ 1Mτ M
(23-33)
τ 1 M = κ 2 Mτ M
The factors k1M,k2M are taken from the curves in IEC1 and are dependent on tF /tM and LF /L 0F . For decreasing speed with tmec < 10tF,
the factor kM is dependent upon 1/d = 2tM and w 0.
ω0 =
1 I rM R M
1−
U rM
τ mecτ M
(23-34)
where w0 is undamped natural angular velocity and d is the decay
coefficient; kM is derived from the curves in the IEC standard.1
For decreasing speed with τ mec < 10τ F, the time to peak τ M is
read from the curve in IEC standard, and the rise time constant is
given by:
τ 1M = κ 3 Mτ M
(23-35)
where κ 3M is read from the curves in Ref. 1, which are not reproduced here.
The decay time constant τ 2M for nominal speed or decreasing
speed with τ mec ≥ 10τ F is given by:
τ 2M = τ F
τ 2M =
(23-30)
(23-32)
L0 F
κ τ
L F 4 M mec
when n = n n = const
when n → 0 with τ mec ≥ 10τ F
(23-36)
DC SYSTEMS, SHORT CIRCUITS, DISTRIBUTIONS, AND HVDC
For decreasing speed with τ mec < 10τ F :
τ 2 M = κ 4 Mτ mec
(23-37)
where κ 4M is again read from curve in Ref. 1, not reproduced here.
Thus, IEC calculations require extensive motor data and application of number of graphical data in the standard.
Example 23-4 Calculate the short-circuit current of a 15-hp,
1150-rpm, six-pole, 115-V, dc motor for a terminal fault. The armature current = 106 A, the armature and brush circuit resistance =
0.1 Ω, and inductance in the motor circuit = 8 mH; τ F = 0.8 s,
τ mec > 10τ F , L0 F /L F = 0 . 5, and τ mec = 20 s.
There is no external resistance or inductance in the motor circuit, therefore R MBr = R M = 0 . 10 Ω . IEC is not specific about calculation of motor circuit resistance. The time constant is:
τM =
L M 8 × 10−3
=
= 80 ms
0 . 10
LR
The quasi-steady-state current from Eq. (23-29) is:
115 − (0 . 10)(106)
0.5
= 522 A
0 . 10
From Eq. (23-30), the peak current = 1044 A, because for
τ mec > 10τ F , factor κ M in Eq. (23-30) is equal to 1. The time to peak
and time constant are given by Eq. (23-33). From Curve in IEC1
and τ F /τ M = 10 and L F /L0 F = 0 . 5, factor κ 1M = 8 . 3 and κ 2 M = 3 . 7.
Therefore, time to peak = 640 ms and time constant τ 1M = 296 ms.
The short-circuit profile is plotted in Fig. 23-4b.
23-1-3
Short-Circuit Current of a Rectifier
ANSI/IEEE Method
The typical current-time curve for short circuit of a rectifier is shown in Fig. 23-8. The maximum current is
reached at half cycle after the fault occurs. The peak at half cycle is
caused by the same phenomena that creates dc offset in ac shortcircuit calculations. The magnitude of this peak is dependent upon
X/R ratio, the ac system source reactance, rectifier transformer
impedance, and also the resistance and reactance through which
the current flows in the dc system. The addition of resistance
or inductance in the dc system reduces this peak and, depending
upon the magnitude of these components, the peak may be entirely
611
eliminated, with smoothing dc reactor as shown in Fig. 23-1.
Figure 23-8 shows three regions of the rectifier short-circuit current. The region A covers the initial rise of current, the peak current
occurs in region B, and region C covers the time after one cycle till
the current is interrupted.
The initial rate of rise of dc short-circuit current for bolted fault
varies with the magnitude of the sustained short-circuit current.
The addition of inductance in the dc circuit tends to decrease the
rate of rise.
An equivalent circuit of the rectifier short-circuit current is
developed with a voltage source and equivalent resistance and
inductance. The equivalent resistance varies with rectifier terminal voltage, which is a function of the short-circuit current. The
equivalent resistance is determined from rectifier regulation curve
by an iterative process, which can admirably lend itself to iterative
computer solution. The equivalent inductance is determined from
sustained short-circuit current for a bolted fault and rated system
voltage. The magnitude of the peak current is determined from ac
and dc system impedance characteristics.3
The following step-by-step procedure can be used:
1. Calculate total ac system impedance ZC = RC + XC in ohms.
Convert to per unit impedance zC, which may be called the
commutating impedance in per unit on rectifier transformer
kVA base. This is dependent on the type of rectifier circuit.
For double-wye, six-phase circuit, the conversion is given by:
ZC = z C × 0 . 6 ×
ED
Ω
ID
(23-38)
where ED and ID are rectifier rated dc voltage and current.
2. Assume a value of rectifier terminal voltage eda under
faulted condition and obtain factor K2 from Fig. 23-9. Then
the preliminary calculated value of the sustained short-circuit
current is given by:
I da =
K2
I
zC D
(23-39)
The equivalent rectifier resistance is then given by:
RR =
(ED − Eda )
Ω
I da
(23-40)
Eda is the assumed rectifier terminal voltage in pu under fault
conditions.
Eda = eda × ED
3. The sustained value of the fault current is:
I dc =
ED
RR + RD
(23-41)
where RD is the resistance external to the rectifier. The rectifier
terminal voltage in volts is:
Edc = ED − I dc R R
FIGURE 23-8
Short-circuit current profile of a rectifier.
(23-42)
4. The value of Eda = eda × ED should be within 10 percent of
the calculated value Edc, the rectifier terminal voltage under
sustained short-circuit current. The iterative process is repeated
until the desired tolerance is achieved.
612
CHAPTER TWENTY-THREE
Now, Eda = 0.392 × 125 V = 49 V which is acceptable. To calculate rate of rise of the current, the rectifier inductance LR is required.
This is calculated based upon terminal short-circuit of the rectifier.
On a terminal short-circuit, voltage is zero and from Fig. 23-9,
K2 = 1.02. This gives a terminal short-circuit current of 16320 A.
Then from Ref. 3, rectifier inductance is given by:
LR =
FIGURE 23-9
Sustained fault current factor versus rectifier terminal
voltage.
Example 23-5 Consider a 100-kW source at 125 V dc. The dc
resistance of the feeder cable is 0.004 Ω. Let the ac source and rectifier transformer impedance zC = 0.05 pu and ID = 800 A. Calculate
the rectifier resistance for a fault at the end of the cable. Assume
eda = 0.5 per unit, that is, Eda = 62.5 V. K2 from Fig. 23-9 = 0.70.
Therefore:
K
0 . 70
× 800 = 11200 A
I da = 2 I D =
zC
0 . 05
ED
125
= 13048 A
=
I dc =
R R + R D 0 . 00558 + 0 . 004
Edc = 125 − (13048)(0 . 00558) = 7 2 . 18 V
This does not satisfy Eda = eda × ED We can iterate once more for
closer estimate of RR:
FIGURE 23-10
ZQ min =
cU n
3IkQ
′′ max
(23-43)
The minimum short-circuit current is given by:
cU n
3IkQ
′′ min
(23-44)
The resistance and inductance on the ac side are:
ED − Eda
62 . 5
=
= 0 . 00558 Ω
11200
I da
Edc = 72.18 V
eda = 49 V (0.392 pu)
K = 0.77
Ida = 12320 A
RR = 0.006169 Ω
Idc = 12292.5 A
Edc = 49.17 V
This gives 0.0213 mH. Considering that the cable has an inductive
reactance of 0.003 Ω, (= 0.00796 mH), the rate of rise of current
is (125)/(0.00796 + 0.0213) = 4.27 kA/s. The peak current can be
1.4 to 1.6 times the sustained current depending upon ac and dc
system parameters.3
Thus the short-circuit currents of converters are high and the
semiconductor devices are protected with fast-acting, current-limiting
fuses, specially designed to reduce fuse let-through energy.
IEC Method of Calculation The equivalent circuit diagram of
the short-circuit of a rectifier is shown in Fig. 23-10. The maximum
short-circuit current is given by minimum impedance ZQmin, which
is obtained from the maximum short-circuit current IkQ
′′ max of the
ac system:
ZQ max =
Then RR is:
RR =
ED
360 × I da
R N = RQ + R P + RT + R R
X N = XQ + X P + XT + X R
(23-45)
where RQ and XQ are the short-circuit resistance and reactance of the ac
source referred to the secondary of the rectifier transformer, RP and XP
are the short-circuit resistance and reactance of the power supply cable
referred to the secondary side of the transformer, RT and XT are the
short-circuit resistance and reactance of the transformer referred to
the secondary side of the transformer, and RR and XR are the shortcircuit resistance and reactance of the commutating reactor if present.
Similarly on the dc side:
R DBr = R S + R DL + R y
LDBr = L S + LDL + L y
Equivalent circuit for calculation of short-circuit current at dc terminals of a rectifier.
(23-46)
DC SYSTEMS, SHORT CIRCUITS, DISTRIBUTIONS, AND HVDC
where RS, RDL, and Ry are the resistances of dc saturated smoothing reactor, the conductor in the rectifier circuit, and the common
branch, respectively, and LS, LDL, and Ly are the corresponding
inductances. The quasi-short-circuit current is given by:
ikD = λ D
3 2 cU n U rTLV
π
3 Z n U rTHV
(23-47)
where Zn is the impedance on the ac side. The factor lD as a function of RN /XN and RDBr /RN is estimated from the curves in Ref. 1.
Analytically, it is given by:
1 + (R N /X N )2
λD =
1 + (R N /X N )2[1 + 0 . 667(R DBr /R N )]2
(23-48)
The peak short-circuit current is given by:
i pD = κ D IkD
(23-49)
where the factor κ D is dependent on:
R N 2R DBr
1 +
3R N
XN
and
LDBr
LN
(23-50)
It can be estimated from the curves in Ref. 1 or analytically:
κD =
ipD
I kD
π
=1+
2 − 3
e
π
+ φD cot φD
π
L
sin φD − arrctan DBr
LN
2
(23-51)
where
RN
XN
2 R DBr
1 + 3 R
N
t pD = (3κ D + 6) ms
(23-52)
when
1
t
3 pD
(23-55)
The decay time constant τ 2D for 50 Hz is given by:
τ 2D =
2
ms
RN
R DBr
+
0
6
0
9
.
.
X N
R N
(23-56)
The time constants for 60-Hz systems are not given in Ref. 1.
Example 23-6 A three-phase rectifier is connected to a threephase 480-V system through a 100-kVA transformer, 480 to 120 V,
of 3 percent impedance, transformer X/R = 4. The available short
circuit on 480-V side is 36 kA, and the fault point X/R = 6. The dc
smoothing reactor has an inductance of 5 µH and the resistance
of the cable connection is 0.002 Ω. It is required to calculate the
short-circuit current and plot its profile.
The ac side source impedance and transformer impedance
reflected on the secondary side are:
R Q + jX Q = 0 . 00008 + j0 . 00048 Ω
R T + jX T = 0 . 001 + j0 . 004 1 9 Ω
Therefore:
R N + jX N = 0 . 0011 + j0 . 004671 Ω
On the dc side:
R DBr = 0 . 002 Ω
and
LDBr = 5 µH
RN
= 0 . 24
XN
λD =
when
and
R DBr
=2
RN
Then from Eq. (23-48)
LDBr
≤1
LN
L
t pD = (3κ D + 6) = 4 DBr − 1 ms
L
N
LDBr
>1
LN
(23-53)
If κ D < 1 . 05, the maximum current, compared with the quasi-steadystate short-circuit current, is neglected, and t pD = Tk is used. The rise
time constant for 50 Hz given by:
τ 1D
τ1D =
1
Time to peak t pD, when κ D ≥ 1 . 05 is given by:
τ 1D
For simplification:
Therefore:
φD = arctan
L
= 2 + (κ D − 0 . 9)2 . 5 + 9 DBr ms
n κ D ≥ 1 . 05
when
L N
R 2 LDBr
= 0 . 7 + 7 − N 1 +
X N 3 L N
L
× 0 . 1 + 0 . 2 DBr ms
when κ D < 1 . 0 5
L N
(23-54)
613
1 + (0 . 24 )2
= 0 . 897
1 + (0 . 24 )2 (1 + 0 . 667 )(2 . 0)2
The quasi-steady-state current from Eq. (23-47) is:
3 2 1 . 05 × 480 1 2 0
IkD = (0 . 897 )
= 18 . 36 kA
π 3 × 0 . 0048 480
To calculate the peak current, calculate the ratios:
RN
XN
2 R DBr
1 + 3 R = (0 . 24 )(1 + 0 . 667 × 2) = 0 . 56
N
LDBr
5 × 10−6
= 0 . 392
=
LN
0 . 0128 × 10−3
Thus from Eq. (23-52):
1
= 60 . 75 °
φD = tan −1
1 + 0 . 667(2)
614
CHAPTER TWENTY-THREE
From Eq. (23-51), κ D = 1 . 204. Therefore, the peak short-circuit
current is:
ipD = κ DI kD = 1 . 204 × 18 . 36 = 22 . 10 kA
The time to peak is given by Eq. (23-53)
t pD = (3κ D + 6) ms = (3 × 1 . 204 + 6) = 9 . 62 ms
23-1-5
The rise time is given by Eq. (23-54) and is equal to 3.83 ms, and
the decay time constant from Eq. (23-56) is 4.58 ms.
The short-circuit current is plotted in Fig. 23-4c. The intermediate values can be plotted using Eqs. (23-1) and (23-2). The calculations are for a 50-Hz system. For a 60-Hz system the peak will
occur in approximately 8.3 ms.
23-1-4 Short Circuit of a Charged Capacitor
IEC Method of Calculation
The resistances and inductances in
the capacitor circuit are:
(23-57)
LCBr = LCL + L y
where RC is the equivalent dc resistance of the capacitor, and RCL
and LCL are the resistances and inductances of the conductor in the
capacitor circuit, respectively. The steady short-circuit current of
the capacitor is zero, and the peak current is given by:
EC
RCBr
(23-58)
where EC is the capacitor voltage before the short circuit, and κ C is
read from the curves in Ref. 1 based on:
1 2 LCBr
=
δ
RCBr
ω0 =
Total Short-Circuit Current
In Fig. 23-7 the total short-circuit current at the fault point F1 is
the sum of partial short-circuit currents from various sources. For
a fault at F2, the total short-circuit current is calculated by adding
resistance and reactance of the common branch to all the partial
current calculations, and then a correction factor is applied.
For a short circuit at F2, after the common branch (Fig. 23-7),
the partial short-circuit currents are calculated by adding the resistance and inductance of the common branch to the equivalent
circuit. A correction factor is then applied. These correction factors from every source are obtained from following equations (as
described in Ref. 1):
ipcorj = σ jipj
RCBr = R C + RCL + R y
ipC = κ C
From curves in Ref. 1, κ C = 0 . 92. The peak current from Eq. (23-58)
is (0.92) × (120/0.05) = 2208 A. The time to peak from curves in
Ref. 1 = 0.75 ms and κ 1C = 0 . 58. From Eq. (23-60) the rise time
constant is 0.58 × 0.75 = 0.4335 ms. Also κ 2C = 1 and from Eq. (23-61)
the decay time constant is 5 µs. The short-circuit current profile is
plotted in Fig. 23-4d.
ikcorj = σ jikj
(23-62)
Example 23-8 The total short-circuit current profile at F1 is plotted. From the previous examples, the time to peak, the magnitude,
and the decay time are different for the partial short-circuit currents
as plotted in Fig. 23-4. Thus, a graphical approach is taken to summate the currents, as shown in Fig. 23-11. The maximum peak is
approximately 27.3 kA and it occurs at 9 ms after the fault.
The short-circuit current from the rectifier predominates. The
short-circuit current from the capacitor is a high-rise pulse which
quickly decays to zero. The dc motor short-circuit current rises
slowly. Smaller dc motors have high armature inductance (Fig. 23-6).
The relative magnitudes of the short-circuit currents contributed by
(23-59)
1
LCBrC
If LCBr = 0, then κ C = 1.
The time to peak is read from curves in Ref. 1. If LCBr = 0, then
the time to peak tPC = 0. The rise time constant is:
τ 1C = κ 1Ct pC
(23-60)
where κ 1C is read from the curves in Ref. 1. The decay time constant is:
τ 2C = κ 2C RCBrC
(23-61)
where κ 2C is again read from the curves in Ref. 1. These curves are
not reproduced.
Example 23-7 A 120-V, 100-µF capacitor has RCBr = 0.05 Ω and
LCBr = 10 mH. The terminal short-circuit profile is required to be
calculated.
1 2 × 10 × 10−3
=
= 0.4
δ
0 . 05
Also:
ω0 =
1
10 × 10−3 × 100 × 10−6
= 1000
FIGURE 23-11
short-circuit currents.
Total short-circuit current—summation of partial
DC SYSTEMS, SHORT CIRCUITS, DISTRIBUTIONS, AND HVDC
615
the sources can vary depending on the ratings: this and connections
can give varying profiles of the total short-circuit current and time to
peak. The total profile is important for properly applying dc circuit
breakers.
23-1-6
Matrix Methods
The above calculations are based on the theorem of superimposition. Matrix techniques, as for ac systems, are equally applicable to
dc systems too. In an example,3 three sources of current, a generator,
a rectifier, and a battery, are considered in parallel. The resistances
and inductances of the system components are calculated, and
separate resistance and reactance networks are constructed, much
akin to ac short-circuit calculation. These networks are reduced to
a single resistance and reactance. Then the maximum short-circuit
current is simply given by the source voltage divided by the resistance and its rate of rise by equivalent time constant. This is rather
an oversimplification and assumes that all sources have the same
voltage. When voltages differ, then the partial short-circuit calculations
as described above can be made. For calculations of current from a
rectifier, an iterative procedure has been demonstrated.
23-2
CURRENT INTERRUPTION IN DC CIRCUITS
Current interruption in ac circuits (Chap. 8) concentrates on the
circuit breakers operating when the current is passing through zero.
We alluded to high-resistance current interruption or rheostatic
breaker. There are no current zeros in dc circuits. Thus, a current
zero must be forced. There are two methods—the current can be
forced to zero by increasing the arc voltage to a level that is higher
than the system voltage (rheostatic breaker) or by injecting into the
circuit a voltage which is of opposite polarity to that of driving voltage. This means that a reverse current flows into the source.
23-2-1
Rheostatic Breaker
An ideal rheostatic circuit breaker inserts a constantly increasing
resistance in the circuit until the current to be interrupted drops to
zero. The arc gets extinguished when the system voltage can no longer maintain the arc because of high voltage drops. The arc length
is increased and the arc resistance acquires high value. The energy
stored in the system is gradually dissipated in the arc. The voltampere characteristic of a steady arc is given by:
Varc = anode voltage + cathode voltage
+ voltage drop across the arc
A+
C
D
+ B+
d
I arc
I arc
(23-63)
where Iarc is the arc current, Varc is the voltage across the arc, d is the
length of the arc, and A, B, C, and D are constants. For small arc
lengths, the voltage across arc length can be neglected:
Varc = A +
C
I arc
(23-64)
Voltage across the arc reduces as the current increases. Energy dissipated in the arc is:
t
Earc = ∫ ivdt
(23-65)
0
Equation (23-65) can be written in the general form as:
t
Earc = ∫ im2 r(sin ωt )2 dt
0
(23-66)
F I G U R E 2 3 - 1 2 A rheostatic breaker, lengthening of arc. Splitter
plates schematically shown.
For a steady arc, that is, current not varying (dc arc), we can write:
Earc = Varc I arct
(23-67)
The approximate variation of arc resistance r with time t is obtained
for different parameters of the arc by experimentation and theoretical analysis.
In a rheostatic breaker, if the arc current is assumed constant,
the arc resistance can be increased by increasing the arc voltage.
Therefore, the arc voltage and the arc resistance can be increased
by increasing the arc length. The arc voltage increases until it is
greater than the voltage across the contacts. At this point, the arc is
extinguished. If arc voltage remains lower, the arc will continue to
burn until the contacts are destroyed.
Figure 23-12 shows a practical design of the arc lengthening
principle. The arc originates at the bottom of the arc chutes and
is blown upward by the magnetic force. It is split by arc splitters,
which may consist of resin-bonded plates of high-temperature fiber
glass, placed perpendicular to the arc path. Blow-out coils, in some
breaker designs, subject the arc to a strong magnetic field forcing it
upward in the arc chutes.
Figure 23-13 shows the dc arc characteristics for different arc
lengths. The resistance characteristic is shown by a straight line.
For arc length given by curve a, the arc resistance characteristics
shown by straight line intersects at point A. The arc voltage is less
than the supply voltage and the arc will continue to burn. As the
arc length is increased, the arc voltage increases above the supply
voltage and the arc is extinguished. During the arcing time, the
supply source continues to give up energy (energy stored in the
inductance of the system); the longer the arc burns the greater is
the energy. Thus, the entire interruption process is a question of
energy balance.
This principle has been successfully employed in some commercial designs of medium-voltage ac breakers also. In these
breaker designs, the current can be easily extinguished at current
zero, there is practically no current chopping, and the breaker
mechanism is very light, except for a large arc chute with splitters.
In the case of dc, some chopping can be expected as there is no
current zero.
Consider a dc current flowing in a parallel LC circuit. If this current is suddenly interrupted (instantaneously), the recovery voltage
situation can be simulated by forcing an equal and opposite current
616
CHAPTER TWENTY-THREE
FIGURE 23-13
Relation of arc and system voltage during dc current
interruption.
through the interrupting breaker. Referring to Chap. 2, the recovery
voltage in this case will be:
1
i
Vr (s) =
C 2 1
s +
LC
(23-68)
and its solution is:
Vr (t ) = i
L
t
sin
C
LC
(23-69)
where i is the current to be interrupted. In case a ramp is used, that
is, the current is gradually brought to zero, the rate of rise of the
recovery voltage can be slowed, that is, the slower the chopping rate,
the slower will be the recovery voltage. A ramp signal in Laplace
transform can be written as:
a a
i = − 2 − 2 e − tc s
s
s
(23-70)
i
where a = 0 = slope of the ramp, and the solution with this signal is:
tc
t − tc
− iL
t
Vr (t ) =
t − cos
u(t − t c )
− 1 − cos
t c
LC
LC
(23-71)
23-2-2
HVDC Breakers
A reader may pursue this section after Sec. 23-4, HVDC Transmission. HVDC circuit breakers are not necessary and are not used.
Thyristor control takes care of the overcurrent, short circuits, and
abnormal conditions in HVDC converters, a metallic return transfer
breaker (MRTB) is, however, required.
In high-voltage dc circuit breakers, the energy stored in the system can be high 0.5 LI d2 = 10 to 25 MJ. Artificial current zeros are
F I G U R E 2 3 - 1 4 Interruption of high-energy dc currents, commutating circuit, parallel surge arrester and current zeros brought by reverse
current flow.
produced by a reverse flow of current. Figure 23-14 shows main
breaker contacts in parallel with a charged capacitor, reactor, and
vacuum gap. This circuit is called a commutating circuit. When the
main breaker contacts open, the vacuum gap is triggered at t0. The
precharged capacitor discharges violently through main circuit causing discharge current to flow in opposition to the main current. The
main current drops down and oscillates with current zeros. The current is interrupted by the main circuit breaker at one of the current
zeros. Vacuum gap seals in and the commutating circuit is opened.
The energy in the main dc pole is partly absorbed by the commutating circuit and partly by the zinc-oxide surge arrester which
can absorb up to 20 kJ/kV. The arc in the main circuit is quenched
by interrupting medium, air, or SF6. The stresses are much higher
because of higher energy associated with dc current interruption
and higher TRV appears across the breaker pole.
The commutation circuits can vary. In the passive commutating
circuit, a parallel LC resonant circuit is used. For HVDC application, the main pole breakers are not used; however, MRTB is used
in bipolar HVDC transmission, and the bipolar mode is changed to
monopolar mode during a fault on one of the poles.9,10
The HVDC breaker types identified by CIGRE working group
are classified on the following basis:
■
Switching time
■
Current to be interrupted
■
TRV
■
Switching energy
The current to be interrupted is a function of switching time,
converter control, and short-circuit ratio of HVDC system with
respect to the ac system. The short circuit rises to a maximum value
within 30 to 50 ms; thereafter, converter control brings it down to
5 percent of full-load current in 120 ms:
At t = 0, Is = Id
At t = 15 ms, Is = 1.25 Id
At t = 30 ms, Is = 3 Id
At t = 150 ms, Is < 0.25 Id
DC SYSTEMS, SHORT CIRCUITS, DISTRIBUTIONS, AND HVDC
TA B L E 2 3 - 1
TYPE
COMPLEXITY
Classification of HVDC Breakers
TIME
DEPENDENCE UPON
CONVERTER CONTROL
CURRENT
CAPABILITY
TRV
A
Most complex
< 15 ms
No
Up to 1.25 Id
Highest
B1
Less complex
60–90 ms
Yes
Low
High
B2
Least complex
90–120 ms
Yes
Low
Low
The classification according to CIGRE is:
■
Type A: It is fast breaker, less than 15 ms, and does not wait
for converter action to reduce dc voltage.
■
Type B: It is slow and waits for converter action to reduce
dc line current to low value. It is classified into two types
B1 and B2. Table 23-1 shows the characteristics of these
breaker types.
FIGURE 23-15
617
23-3 DC INDUSTRIAL AND COMMERCIAL
DISTRIBUTION SYSTEMS
The dc distribution systems are being considered for commercial
facilities. A greater percentage of office and commercial building
loads are electronic in nature, which have dc as the internal operating
voltage. Fuel and solar cells and batteries can be directly connected
to a dc system, and the double conversion of power, first from dc to
ac and then from ac to dc, can be avoided. Figure 23-15 shows the
Ac versus dc distribution systems for commercial facilities.
618
CHAPTER TWENTY-THREE
FIGURE 23-16
A dc distribution system for U.S. Navy, based on Ref. 13.
conceptual base. A case study is presented in Ref. 11 which compares reliability, voltage drops, cable sizing, grounding, and safety,
ac versus dc distribution system, which is a part of Department of
Electrical Power Engineering, Chalmers University of Technology,
Gothenburg, Sweden.
For high reliability UPS systems are used for computers and
other sensitive loads. Distributed generation units, like solar cells
and fuel cells, generate power at dc, and natural gas microturbines,
which generate power at high frequency, need double conversion
of power (Fig. 23-15).
With dc distribution, the electronic loads can be supplied more
effectively, and by choosing a proper voltage level, one conversion
stage is avoided. This results in savings of energy and equipment
costs, and so dc distribution becomes attractive. Solar and fuel cells
can be directly connected to the dc bus, while for microturbines, a
rectifier is needed. A battery block can be directly connected.
The prospective dc distribution opens up an entirely new set
of issues—system studies, short-circuit calculations, application
of circuit breakers, load flow, contingency analysis, voltage levels,
starting impact of loads, and conversion technologies. The transient response of many household appliances, incandescent and
fluorescent lamps, coffee makers, computers, and monitors are
shown in Ref. 12.
An example of industrial distribution is shown in Fig. 23-16, dc
shipboard distribution system,13 envisaged by U.S. Navy. Two steam
turbine generators are connected through rectifiers to a 7000-V dc
bus. The dc loads in a zone are served through dc-dc converters and
the ac loads through an inverter. The dc-dc converters isolate the loads
from the rest of the system, and any fault in that zone does not escalate to other areas. Similarly, the rectifiers isolate the generators and
synchronizing and frequency control requirements of the generators
are relaxed. The dc bus becomes immune to ground faults through
proper system grounding. Thus, ease of maintenance, reliability, and
confinement of a system to a limited area are the obvious advantages.
More power can be handled on a cable circuit with dc than with ac.
Simulation transients with PSCAD/EMTD are shown in Ref. 14. The
rectifiers, inverters, and converters use 18-kHz PWM schemes for
switching and have controllers to regulate the output voltages.
23-4
HVDC TRANSMISSION
The cumulative megawatts of HVDC systems around the world
approach 100 GW. HVDC has a long history, but a transition point
occurred when thyristor valves took over mercury arc rectifiers in the
late 1970s. The major technology leap was in Brazil with the 3150
MW ± 600 kV Itaipu project commissioned from 1984 to 1987. The
overhead line is 800 km long and each 12-pulse converter is rated
790 MW, 300 kV. HVDC is finding major applications in countries
like India and China, and a large number of thyristor valve–based
systems are planned—the power levels and distances are such that
± 800 kV may be needed. An HVDC technology review paper is
at weblink.15 Another Web site of interest is that of CIGRE Study
Committee B4, HVDC, and Power Electronic Equipment.16
HVDC Light The IGBTs for motor drives have begun to find
applications in HVDC systems at the lower-end of power usage.
These operate using PWM techniques; there is little or no need for
reactive power compensation as the converters can generate active
and reactive power. The systems have found applications in offshore wind farms and short-distance XLPE-type cable systems. The
largest system to date is the 330-MW cross-sound dc link between
Connecticut and Long Island.
23-4-1
HVDC Advantages
An HVDC interconnection properly planned and designed may
achieve the following advantages:
1. An interlinking of two ac systems through interconnections
which may have become overloaded during load development poses problems of trip out, system separation, and load/
frequency management. There are limitations of load transfer
with respect to deviations of frequency in the interconnected
systems. A dc link on the other hand is immune to such fluctuations and power transfer remains steady.
2. It is possible to improve the stability of the network as a
whole by introducing control parameters from the ac network,
and the disturbances in the ac network can be damped out by
modulating power flow through the dc link.
3. An ac interconnection is a synchronous link, and with
increased generating capability, it requires equipment of
increasing short-circuit ratings. HVDC link is an asynchronous
connection, and the short-circuit levels of interconnected systems remain unchanged. Also frequency disturbances in one
system do not impact the interconnected system. HVDC links
are in operation, interconnecting 40- or 50-Hz systems with
60-Hz systems.
4. A synchronous HVDC link is a combination of HVDC link in
parallel with ac tie lines. Power transfer through parallel dc line
can be controlled to have a stabilizing effect on parallel ac tie
line. The stabilizing controls are initiated after first opening the
ac line, continue during the dead time and subsequent return
of the ac system to the equilibrium point.
DC SYSTEMS, SHORT CIRCUITS, DISTRIBUTIONS, AND HVDC
5. The power through an HVDC link can be regulated more
precisely and rapidly, change of the order of 30 MW/min or
more. The limitations are imposed by the ac system reserve
capacity and generation.
6. An HVDC link does not transmit reactive power (though
converters require reactive power to operate). Thus, there is no
loss of reactive power in the HVDC line itself. Continuous charging currents are absent. Thus, transmission losses are reduced.
7. The skin effect is absent in dc currents, and the conductors
can have a uniform current density through their cross section.
8. The phase-to-phase clearances and, phase-to-ground clearances are smaller for dc transmission. HVDC towers are physically smaller for the same ac voltage level, and right of way
(ROW) is reduced.
9. With respect to line loading, the ac line remains loaded
below its thermal limit due to limits of transient stability, and
conductors are not fully utilized. The voltage across the line
varies due to absorption of reactive power, which is load power
factor dependent. The voltage fluctuates with the load. An
ac line cannot be loaded more than approximately 0.8 times
the surge impedance loading. Such limitations do not exist in
HVDC transmission. Line can be loaded up to the thermal limits of line or thyristor valves.
FIGURE 23-17
619
10. Intermediate substations are generally required in ac
transmission for compensation located approximately 300 km
apart—no such substations are required for HVDC transmission. It is point-to-point long-distance transmission, though
multi-terminal operation is possible.
11. Ac transmission requires several three-phase conductors, while HVDC transmission requires two-pole conductors.
Therefore, HVDC becomes more economical over ac transmission due to reduced tower size, conductor cost, reduced ROW,
and reduced transmission losses. HVDC can utilize even earth
return and may not need a double circuit.
12. An HVDC line can be operated with constant current or
voltage regulation by suitable control of the thyristor valves
and tap changer control.
23-4-2
HVDC Configurations and Operating Modes
Figure 23-17 shows common system configurations:
1. Monopolar systems are the simplest and most economical for moderate power transfer. Only two converters and one
high-voltage connection is required. These have been used
with low-voltage electrode lines and sea electrodes to carry
return currents (Fig. 23-17a).
HVDC system configurations.
620
CHAPTER TWENTY-THREE
2. In congested areas, or soils of high resistivity, conditions
may not be conducive to monopolar systems. In such cases,
a low-voltage cable is used for the return path, and the dc
circuit uses local ground connection for potential reference
(Fig. 23-17b).
few kilometers away from the shore, while the shore electrode is
buried on the seashore near the sea. The cathodic protection of
buried metallic objects is one way of preventing corrosion.17
3. An alternative of monopolar systems with metallic return
is that the midpoint of a 12-pulse converter can be connected
to earth and two half voltage cables or line conductors can be
used. The converter is operated only in 12-pulse mode, so that
there are no stray currents (Fig. 23-17c).
Figure 23-18 shows a practical layout of a terminal. While reactive power compensation and harmonic filters have been previously discussed, dc filters are required to limit interference with
communication circuits, which may be inductively coupled to the
dc line. The parameters to be considered are separation between
the dc and communication lines, their shielding, the presence of
ground wires, and the soil resistivity. This criterion is expressed
as equivalent disturbing current. Disturbance effects are lower in
bipolar designs. The filter design must account for all operating
modes and harmonic sources. In Chap. 15 we noted that while the
converter throws odd harmonics on to the ac supply system, the
even harmonics of input frequency are transmitted to the load. A
Fourier expression for the output voltage is:
4. Back-to-back systems are used for interconnection of synchronous networks and use ac lines to connect on either side.
The power transfer characteristics are limited by the relative
capabilities of adjacent ac systems. There are no dc lines. The
purpose is to provide bidirectional exchange of power, easily
and quickly. An ac link will have limitations in control over
direction and amount of power flow. Twelve-pulse bridges are
used. It is preferable to connect two back-to-back systems in
parallel between the same ac buses (Fig. 23-17d).
5. The most common configuration is 12-pulse bipolar converter for each pole at the terminal. This gives two independent
circuits each of 50 percent capacity. For normal balanced operation, there is no earth current. Monopolar earth return operation
can be used during outage of the opposite pole (Fig. 23-17e).
6. The earth return option can be minimized during monopolar operation by using opposite pole line for metallic return
through pole/converter bypass switches at each end. This
requires a metallic return transfer breaker in the ground electrode line at one of the dc terminals to commutate the current from relatively low resistance of earth into that of dc line
conductor. This metallic return facility is provided for most dc
transmission systems (Fig. 23-17f).
For voltages above ± 500 kV, series-connected converters are
used to reduce energy unavailability for individual converter outage
or partial line insulation failure. By using two-series-connected converters per pole in a bipolar system, only 25 percent of the line capability is lost for a converter outage or if the line insulation is degraded
and it can support only 50 percent of the rated line voltage.
23-4-3
Earth Return
The flow of direct current through earth can give rise to the following problems:
■
Corrosion of buried metallic pipes, cable sheaths, and
fences due to electrolytic action
■
Disturbance in communication signals through metallic
rails in the path of earth current
■
Rapid consumption of electrode material
■
Shocks to fish, sea life, and shore swimmers
The earth electrodes are installed far away from the main terminal
substation earth of HVDC system; the location is selected such that
there are no buried pipe lines, cables, and structure foundations. This
may be at a distance of 5 to 10 km, and the electrodes are connected
to the neutral point of the converter through an electrode line lightly
insulated. The touch and step potentials, (Chap. 21) should be within
prescribed limits.
For submarine cable HVDC transmission, the earth electrodes
are in the form of sea electrode or shore electrode. The sea electrode is held in the sea water close to the shore and is installed a
23-4-4
Terminal Layout
e 0 = e d + e 2 sin 2ωt + e 2′ cos 2ωt + e 4 sin 4ωt + e ′4 cos 4ωt + ⋅⋅
(23-72)
where em and e m′ (m = 2, 4, 6,...) are given by:
em =
2Em sin(m + 1)α sin(m − 1)α
−
π
m +1
m − 1
e m′ =
2Em cos(m + 1)α cos(m − 1)α
−
m +1
m − 1
π
(23-73)
Generally 12th harmonic band pass filter with active filtering of
higher order harmonics are provided.
23-4-5 Line-Commutated Current Source Converters
Line-commutated current source converters form the basis of highpower and high-voltage HVDC transmission. We discussed the control of dc voltage output of the current source converters, delay and
commutation angle, harmonic generation, and mitigation through
phase multiplication and the waveforms in Chap. 15. A fully controlled six-pulse converter will act as an inverter, if the firing angle
is adjusted above 90°. At a = 90° the output voltage is zero, and
the positive half and negative half waves are equal. As the angle is
increased above 90°, inverter action is obtained. The firing angle is,
however, limited and cannot be 180°, as explained further.
Figure 23-19 shows waveforms for rectifier and inverter operation. For inverter operation the output power factor is leading. The
reactive power increases as a approaches 90° (Chap. 15).
For a six-pulse bridge, internal no-load voltage is:
Vdo =
3 3 Em
cos α
π
(23-74)
Then, considering the dc voltage drop in the source inductance
(commutating inductance):
3 3 Em
3ω L sI d
cos α −
π
π
3 3 Em
3ω L sI d
cos(α + µ ) +
=
π
π
Vd =
(23-75)
We can write:
3
X I = R cI d
π cd
(23-76)
FIGURE 23-18
Details of dc terminal setup: bipolar HVDC system.
621
622
CHAPTER TWENTY-THREE
FIGURE 23-19
Effect of delay angle on voltage waveform—rectifier and inverter operation modes of a six-pulse converter.
where Rc is the equivalent commutating resistance, which does not
represent a real resistance and does not consume any real power.
For rectifier or inverter operation a thyristor experiences a
reverse voltage for (π − α − µ ) after the commutation has taken
place. However, for inverter operation, angle a > 90°. This means
that for inverter operation the thyristors are reverse biased for a
shorter duration as compared to the rectifier operation. Therefore,
the firing angle should be limited so that angle g = (π − α − µ ) is
enough for proper commutation. Angle (π − γ ) is called the extinction angle.
Figure 23-20 shows the operating modes of converter as a
rectifier and inverter. The angle a can be varied so that Id is constant; this may be called mode 1 of operation. As source voltage Vs
increases, the internal voltage Vdo also increases so that difference
between these two is a constant value. To increase Vd, the firing
angle is advanced. The duration for which the SCR is reversed
biased will reach a minimum value required at some level of internal voltage. Any further increase in a for increasing Id will result
in failure of commutation. This sets the limit for constant current mode. Any further increase in Id is possible only by reducing a, so that margin g remains constant; this is the other mode
of operation. Here the dc voltage will decrease with an increase
in current.
Figure 23-21 shows the inverter waveforms for a = 5π /6. The
voltage across one of the thyristors is also shown. Unless proper
control is exercised to maintain margin angle, commutation failure
can occur. Equation (23-75) can also be written as:
3ω L s
π
Vd + π I d = Em cos α
3 3
To determine the instant of firing, replace α with wt and (a + m)
with (π − γ min ):
2ω L s
3
I d − Em cos γ min = Em cos ωt
FIGURE 23-21
FIGURE 23-20
Rectifier/inverter characteristics of a converter.
(23-77)
and voltage waveforms.
(23-78)
A six-pulse inverter: circuit diagram and current
DC SYSTEMS, SHORT CIRCUITS, DISTRIBUTIONS, AND HVDC
623
where g min is a constant. Therefore, the left side of Eq. (23-78)
depends upon Id. The right-hand side is the negative value of ac
phase c voltage for firing thyristor 2. Whereas the right side is the
same for all thyristors, the control voltage will be different for each
thyristor and separate firing circuits are required.
Example 23-9 A six-pulse circuit operates in inverting mode with
constant margin angle g min = 20°. Input voltage is 440-V dc, source
resistance = 1 Ω, input current = 20 A. The ac voltage is 480 V, 60 Hz.
Calculate source inductance. What is the output power factor?
Converter dc voltage is given by:
Vdo = 440 + I d rs = 460 V
Therefore:
3ω L s
× 20 = − 460 + 3 3 cos γ min = 70 V
π
Then:
FIGURE 23-22
70 × π
Ls =
× 1000 = 9 . 70 mH/phase
20 × 3 × 377
From Eq. (23-77):
3 3 Em
cos α = − 460 + 70 = − 390
π
390 × π
3 3
×
3
2 × 480
■
b = π − a is the ignition advance angle.
■
g = π − a is the extinction advance angle.
■
m = d − a = b − g is the overlap angle.
More completely, the Vd equations for rectifier and inverter mode
are written as:
Therefore:
cos α = −
= 0 . 60 leading
cos γ min = 0 . 98 leading
The output power factor = (0.60 + 0.98)/2 = 0.79 leading
approximately.
Figure 23-22 shows definitions of the angles related to rectifier
and inverter operation.
Vd = Vdo cos α − R cI d − R eq I d − Vdrop
rectifier
Vd = Vdo co s γ − R cI d + R eq I d + Vdrop
Inverter
a is the ignition delay angle.
■
m is the overlap angle.
■
d is the extinction delay angle = a + m.
FIGURE 23-23
(23-79)
where Req is the equivalent resistance representing losses in valves
and auxiliaries, and Vdrop is the voltage drop in the valve itself. The
equivalent circuits of rectifier and inverter reduce to the simple circuits shown in Fig. 23-23.
The current flowing in the link between rectifier and inverter is:
Id =
■
Various angles in rectifier and inverter operation.
Vdor cos α − Vdoi cos γ
R cr + R L + R ci
(23-80)
where RL is the dc line resistance, and the commutating resistances
are as defined in Eq. (23-76).
Equivalent circuits of (a) rectifier and (b) inverter.
624
CHAPTER TWENTY-THREE
FIGURE 23-24
Control circuit diagram of a pole control, HVDC, LCC source converters.16
23-4-6 Control and Operation of HVDC
A load commutated converter (LCC) HVDC system is operated
so as to maintain constant dc current and voltage. The control circuit of a phase is shown in block circuit diagram of Fig. 23-24.16
This produces the operating characteristics shown in Fig. 23-25 by
selecting the values amongst the outputs of constant current (CC),
constant voltage (CV), and constant extinction angle (CEA). Extinction angle control is needed to avoid commutation failures. The
two characteristics of the inverter and rectifier are symmetrical with
respect to horizontal axis of the dc current. The interaction indicates
an operating point in the steady state, points A or B. Usually the
FIGURE 23-25
HVDC operation with each converter having rectifier
and inverter characteristics.
rectifier sets the dc current and the inverter the dc voltage. The actual
operating points of the converters differ because of the voltage drop
in the dc line. Current control gives fast response, while voltage control is comparatively slow to avoid unstable control action.
The dc voltage can be controlled by varying the delay angle,
which has a faster response, or by controlling the converter ac
voltage by load tap changers on transformers, which gives a slow
response. Load tap changing (LTC) is used to keep angles a and g
within a desired range. Also by increasing the angle a, the reactive
power requirements increase.
At any time, only one terminal can control the dc power in a
two-terminal system. The power control is integrated in parallel
with the dc control loop and corrects the current order setting so as
to adjust the actual dc power to the setting value.
Power inversion or an interchange of rectifier and converter operation can be done by changing the converter that subtracts the current
margin Im in Fig. 23-25. A new operating point B with reversed dc
power is the intersection of two dotted lines. The power reversal action
changes the dc polarity and the current direction remains as before.
There are ac/dc system interactions which must be considered.
The protection and control functions of dc system can normally prevent spread of disturbances, but an improperly controlled terminal
can even accentuate the disturbances. Trip of generator can bring
about a block of HVDC, resulting in possible power flow, voltage,
instability, operating reserve, and frequency response issues.
Consider a synchronous dc link. Figure 23-26 shows the powerangle characteristics and the impact of critical damping control on the
stability. Curve A is for ac lines tripping, curve B for a parallel dc link,
but with Pd control only and curves 3 and 4 with damping controls.
HVDC offers the flexibility of adding auxiliary controls to stabilize the system for transient and dynamic stability swings. An
example for improving transient stability is to block HVDC and
then slowly ramp it up to full output. Dynamic loops can be added
to provide damping of oscillatory response. Other slower-acting
controls can utilize an HVDC to share operating reserves across
synchronous systems through frequency response loops.18,19,20
DC SYSTEMS, SHORT CIRCUITS, DISTRIBUTIONS, AND HVDC
625
how strong the ac system is with respect to the HVDC link. It is
defined as:
SCR =
SMVA,min
Pd,max
(23-85)
where SMVA,min is the minimum short-circuit MVA of the ac bus at
the HVDC link, and Pd,max is the maximum rated bipolar power of
the HVDC link. The minimum short-circuit level can be calculated
based on the minimum three-phase short-circuit current of the ac
system at the point of interconnection (Chap. 9).
The equivalent SCR (ESCR) considers the reactive power of
shunt capacitor filters and other shunt capacitors if any.
ESCR =
FIGURE 23-26
Torque angle stability characteristics, with and
without HVDC synchronous link. Curve A for ac line tripping. Curve B—with
parallel HVDC link and only Pd control. Curves C and D—with damping
HVDC control.
23-4-7
Reactive Power Requirements
The converters consume reactive power both in the rectifier and
inverter mode (Fig. 15-7). The reactive power demand is usually
50 to 60 percent of the active power demand.
Equation (23-76) can be written as:
Vd = Vdo cos α − D Vd = Vdo
cos α + cos δ
2
(23-81)
The power factor is given by:
cosφ = 0 . 5(cos α + cos(α + µ )) rectifier
cosφ = 0 . 5(cos γ + co
o s(γ + µ )) inverter
(23-82)
To achieve high power, factor a and g should be kept low. From
Eq. (23-82)
cos φ ≈
Vd
Vdo
(23-83)
The reactive power can be calculated from the following
expressions:
Q = Vd I d
(23-84)
As an example, if Vdo = 280 kV, Vd = 250 kV, Id = 2 kA, the reactive
power requirement is 252 Mvar. At inverter end, the inverter feeds
the ac load, therefore, the reactive power requirements of the ac
load must be added.
The reactive power sources are discussed in Chap. 15. The
reactive power can be supplied by SVC’s, rotating condensers, and
shunt capacitors. The shunt capacitors will supply a fixed amount
of reactive power and will overcompensate at light loads.21 The
ac filters can serve the dual purpose of supplying reactive power
requirements as well as mitigating harmonics (Chap. 6).
23-4-8 Short-Circuit Ratio
The definition of SCR here should not be confused with SCR for
synchronous generators described in Chap. 10. Here SCR signifies
Pd ,max
(23-86)
An ac system with SCR < 2 is considered weak, 2 to 4 as intermediate, and > 4 as strong. The impacts of low SCR (weak electrical
system) are:22
■
High dynamic overvoltages
■
Voltage instability
■
Harmonic resonance and objectionable flicker
With low SCR, the Pd /Id curve has a stability limit above which
increase in Id causes a decrease in Pd. Control of voltage and recovery from disturbances becomes difficult. The dc system response
may contribute to the collapse of the ac system. Synchronous condensers can be installed to increase SCR, as these contribute to the
short-circuit currents.
The ac bus voltage depends on SCR, active power, and reactive
power supplied by the ac filters. For a given power flow, ac bus
voltage can be raised by increasing the shunt compensation.
On sudden load rejection, there will be transient rise in ac voltage, which should be limited to 1.1 pu. This is controlled by rapidly
reducing reactive power provided by shunt capacitors. SVCs have
an obvious advantage (Chap. 15).
The harmonic resonance problems are due to parallel resonance
between ac capacitors, filters, and ac system at lower harmonics
(Chap. 6).
The problems of flicker can arise as the switching of shunt
capacitors and reactors may cause a large voltage swing in the vicinity of compensating equipment due to frequently switched compensating devices.
23-4-9
2
Vd 0
V −1
d
SMVA,min − Qc
Typical Thyristor Current and Voltage Waveforms
Figure 23-27 shows typical waveforms of a thyristor voltage and
current, under normal operation. The system represented is 230-kV
dc link, 12-pulse converters, one converter served from wye-wye
transformer, and the other through delta-wye transformer. This
figure depicts the waveforms of one of the thyristors in six-pulse
bridge connected to wye-wye transformer. Figure 23-28 shows the
impact of a dc pole-to-ground fault on one of the lines that occurs
at 200 ms and is cleared in 100 ms EMTP simulations.
23-4-10
VSC-Based HVDC: HVDC-Light
Voltage converter-based HVDC, also called HVDC-light, consists of
a bipolar two-wire HVDC system with converters connected poleto-pole (Fig. 23-29). DC capacitors are used to provide a stiff dc
voltage source. There is no earth return operation. The converters
are coupled to the ac system through ac phase reactors and converter
transformers. Harmonic filters are located between the phase reactors and converter transformers. This avoids the harmonic loading
626
CHAPTER TWENTY-THREE
FIGURE 23-27
Typical waveforms, normal operation, voltage, and current in one of the thyristors of a six-pulse converter, 230-kV HVDC transmission.
FIGURE 23-28
As in Fig. 23-27, but a dc line-to-ground fault occurs at 200 ms, cleared in 100 ms. Fault resistance = 0.1 Ω.
DC SYSTEMS, SHORT CIRCUITS, DISTRIBUTIONS, AND HVDC
FIGURE 23-30
627
P-Q characteristics, VSC-based HVDC, and practical
operating range.
and dc stresses on the converter transformers. The harmonic filters
are much smaller due to PWM modulation (Chap. 15).23,24
The IGBT valves comprise series-connected IGBT positions. An
IGBT exhibits low forward voltage drop and has a voltage-controlled
capacitive gate. The complete IGBT position consists of an IGBT, an
antiparallel diode, a voltage divider, and a water-cooled heat sink.
IGBTs may be connected in series to switch higher voltages, much
alike thyristors in conventional HVDC.
Active power can be controlled by changing the phase angle of
the converter ac voltage with respect to filter bus voltage, whereas
the reactive power can be controlled by changing the magnitude
of the phase voltage with respect to filter bus voltage (Chap. 15). This
allows separate active and reactive power control loops for HVDC
system regulation. The active power loop can be set to control the dc
voltage or the active power. In a dc link, one terminal may be set to
control the active power, while the other terminal to control the dc
side voltage. Either of these two modes can be selected independently.
The operating range of VSC converter is shown in Fig. 23-30.
PROBLEMS
1. Plot the short-circuit profile of a lead acid battery: 240 V,
120 cells, 500 A-h at 8-hour rate of 1.75 V per cell at 25°C.
Each cell is 15 in long, 7 in wide, and 10 in high. The cells
are arranged in two-tier configuration, 30 cells per row, total
4 rows. Intercell connectors are 1 in × 1/2 in cross section,
resistance 0.0321 m Ω/ft. Battery is connected through a cable
of 0.002-Ω resistance and 15-µH inductance. The fault occurs
at the end of the battery cable.
FIGURE 23-29
VSC-based HVDC.
2. Calculate and plot short-circuit current profile of a dc
motor of 100 hp, 230 V, 690 rpm, armature current = 256 A,
and transient resistance = 0.12 Ω.
3. Calculate and plot the short-circuit current profile for a
fault on the dc side of a rectifier, 480-V, three-phase ac power
628
CHAPTER TWENTY-THREE
supply system, short-circuit level of the ac system = 30 kA rms
symmetrical, X/R = 7.0. The rectifier is supplied through a
three-phase transformer of 400 kVA of percentage impedance =
4 percent, X/R = 4, the dc side equivalent resistance and
reactance are 0.001 Ω and 4 µH. (The IEC methods of calculation illustrated in the text will require a copy of IEC standard.1
However, methodology other than IEC procedures can be used
for the solution of above problems.)
4. Based on the partial currents calculated in Probs. 1, 2, and
3, plot the total current. What is its peak value and time to
peak? Select a suitable circuit breaker with respect to the shortcircuit ratings.
5. A six-pulse converter is fed from a transformer of 230–110 kV
9% impedance. Determine dc voltage for a = 25° and m = 15°.
If the dc current is 2000 A, what is the effective commutating
reactance, rms fundamental component of ac current, power
factor, and the reactive power requirement?
6. Repeat Prob. 5 for a 12-pulse converter.
7. A six-pulse converter is connected to a 480-V, 60-Hz, threephase power source and operates at a = 30°. The load current
is maintained constant at 100 A, and load voltage = 360 V.
What is the load resistance, source inductance, and angle m?
8. Explain the impact of extinction angle on commutation failures. Describe all modes of operation of an HVDC link.
9. The ideal no load dc voltage of one pole at the rectifier
end of dc link is 550 kV. The direct current = 1000 A and
Vd = 500 kV. Calculate the reactive power requirements.
Explain why the reactive power requirements at inverter
end are higher.
Characteristics of DC Motors and Generators,” AIEEE Trans.,
vol. 68, pp. 1100–1106, 1949.
7. A. G. Darling and T. M. Linville, “Rate of Rise of Short-Circuit
Current of DC Motors and Generators,” AIEE Trans., vol. 71,
pp. 314–325, 1952.
8. IEEE Standard 399, Power System Analysis, 1997.
9. J. J. Vithayathil, A. L. Courts, W. G. Peterson, N. G. Hingorani,
S. Nilsson, and J. W. Porter, “HVDC Circuit Breaker Development and Field Tests,” IEEE Trans., vol. PAS-104, pp. 2693–2705,
Oct. 1985.
10. CIGRE Joint Working Group 13/14-08, “Circuit Breakers for
Meshed Multi-terminal HVDC Systems, Part 1: DC Side Substation Switching Under Normal and Fault Conditions,” Electra,
no. 163, pp. 98–122, Dec. 1995.
11. A. Sannino, G. Postiglione, and M. H. J. Bollen, “Feasibility of a DC Network for Commercial Facilities,” IEEE
Trans. Industry Applications, vol. 39, no. 5, pp. 1499–1507,
Sep. /Oct. 2003.
12. D. Nilsson and A. Sannino, “Load Modeling for Steady-State
and Transient Analysis of Low-Voltage DC Systems,” In Conference Record, IEEE I&CPS, Paper 0-7803-3/04, 2004.
13. M. E. Baran and N. R. Mahajan, “DC Distribution for Industrial
Systems: Opportunities and Challenges,” IEEE Trans. Industry
Applications, vol. 39, no. 6, pp. 1596–1601, Nov./Dec. 2003.
14. J. G. Ciezki and R. W. Ashton, “Selection and Stability Issues
Associated with a Navy Shipboard DC Zonal Electrical Distribution System,” IEEE Trans. Power Delivery, vol. 15, pp. 665–669,
Apr. 2000.
10. Explain impact of short-circuit ratio on the stability limit.
15. http://www.internetcad.com/pub/energy/technology_abb.pdf
11. A dc line-to-ground fault occurs on a 500-kV line, fault
resistance = 5 Ω. Reactance of the smoothing reactor in series
with rectifier = 0.5 H. What is the energy requirement of a dc
circuit breaker?
16. www.cigre-b4.org: CIGRE Study Committee B4, HVDC, and
Power Electronic Equipment.
12. Study an ac distribution system of a commercial facility
and convert it into a dc distribution system. Include all singleline diagrams of distribution main switchboard and panels.
Show details of all converters and cables, and calculate dc voltage drops in all main and subcircuits and make a comparative
analysis.
REFERENCES
1. IEC Standard 61660-1, Short-Circuit Currents in DC Auxiliary
Installations in Power Plants and Substations, 1997.
2. IEEE Standard 946, DC Auxiliary Power Systems for Generating Stations, 1992.
3. General Electric Company, GE Industrial System Data Book,
Schenectady, New York, 1978.
4. www.iec.ch, IEC Standards on line.
5. AIEEE Committee Report. “Maximum Short-Circuit Current
of DC Motors and Generators, Transient Characteristics of DC
Motors and Generators,” AIEEE Trans., vol. 69, pp. 146–149,
1950.
6. A. T. McClinton, E. L. Brancato, and R. Panoff, “Maximum
Short-Circuit Currents of DC Motors and Generators, Transient
17. M. Parker and E. G. Peattie, Pipe Line Corrosion and Cathodic
Protection, 3rd ed., Gulf Professional Publishing, Houston, TX.
1995.
18. V. K. Sood, HVDC and FACTS Controllers, Kulwer, Norwell, MA,
2004.
19. A. Ekstrom and G. Liss, “A Refined HVDC Control System,”
IEEE Trans. PS, vol. PAS 89, pp. 723–732, May-Jun. 1970.
20. IEEE Committee Report, “HVDC Controls for System Dynamic
Performance,” IEEE Trans., vol. PWRS-6, no. 2, pp. 743–752,
May 1991.
21. IEEE Standard 1031, IEEE Guide for the Functional Specifications of Transmission Line Static VAR Compensators, 2000.
22. CIGRE and IEEE Joint Task Force Report, “Guide for Planning
DC Links Terminating at AC Locations having Low ShortCircuit Capabilities, Part 1: AC/DC Interaction Phenomena,”
CIGRE Publication 68, Jun. 1992.
23. B. Jacobson, Y. Jiang-Hafner, P. Rey, and G. Asplund, “HVDC
with Voltage Source Converters, and Extruded Cables for up
to ±300 kV and 1000 MW,” In Proc., CIGRE, pp. 84–105,
2006.
24. G. Asplund, K. Eriksson, H. Jiang, J. Lindberg, R. Palsson, and
K. Stevenson, “DC Transmission Based on Voltage Source
Converters,” in Proceedings CIGRE, Paris, 1998.
DC SYSTEMS, SHORT CIRCUITS, DISTRIBUTIONS, AND HVDC
FURTHER READING
J. Arrillaga, High Voltage Direct Current Transmission, 2d. ed. IEEE
Press, Piscataway, NJ, 1998.
EPRI HVDC Electrode Design, EPRI Research Project 1467-1,
Report, Palo Alto, EL-2020.
EPRI HVDC Transmission Line Reference Book, EPRI Report TR-102764,
1993.
A. Greenwood, Electrical Transients in Power Systems, John Wiley
and Sons, New York, 1991.
629
E. W. Kimbark, Direct Current Transmission, Vol. 1, Wiley Interscience,
New York, 1971.
N. Knudsen and F. Iliceto, “Contributions to the Electrical Design
of HVDC Overhead Lines,” IEEE Trans., vol. PAS93, no. 1,
pp. 233–239, 1974.
P. Kundur, Power System Stability and Control, Chapter 10: HVDC
Transmission, EPRI, Palo Alto, 1993.
K. R. Padiyar, Power Transmission Systems, John Wiley, New York,
1990.
This page intentionally left blank
CHAPTER 24
SMART GRIDS AND WIND
POWER GENERATION
In the years to come, the power generation, transmission, and
distribution will undergo profound changes like improved environmental compatibility, reliability, and operational efficiency, integration of renewable energy technologies like wind, solar power,
and distributed generation. The modern grid systems are being
controlled and will be controlled and operated so that the dynamic
state of the grid is known in the terms of:
1. Rotor angle stability and voltage stability
2. Increase/decrease in transmission capability that can take
place in real-time over transmission systems
3. Control and regulation of power flow to maintain grid
parameters
4. Remedial action schemes (RAS) and system integrated
protection systems (SIPS)
5. Identification of the remedial measures that should be
taken to avoid an extreme contingency, that is, cascading and
blackouts
6. Physical implementation of corrective actions
The technologies driving the self-healing smart grid are: widearea measurement systems (WAMSs), system integrity protection schemes (SIPSs), phasor measurement units (PMUs), energy
management systems (EMSs), flexible AC transmission (FACTS)
(Chap. 16), and communication systems, dynamic contingency
analysis (DCA); all somewhat related.
It is amply clear from Chap. 12 that stability of a system is not
a fixed identity and varies with the operating and switching conditions. Some not so common contingencies in a system can cascade
and bring about a shutdown of a vital section. Historically, the great
Northeast Blackout of November 9–10, 1965, and more recently
the 2003 East Coast Blackout can be mentioned.
24-1 WAMS AND PHASOR MEASUREMENT
DEVICES
Wide area network measurements have been around for the last
60 years and have been used in economic dispatch, generation
control, and real-time measurements of power flows. Supervisory
control and data acquisition systems (SCADAs) are of late-1960s
origin and provided real-time state estimates of power systems.
The measurement comprised a data window of several seconds,
without regard to the instant at which the precise measurement
was made, while the system may have drifted meanwhile from the
instant of measurement. Developments in microprocessor-based
relays got an impetus in 1970s, based on the requirements that
symmetrical components of currents and voltages at relay locations
be estimated from synchronized sampled data on a system-wide basis.
In the 1980s global positioning systems (GPSs) were deployed
and the prospect of synchronizing sampled data on a system-wide
basis became a reality.
This requirement led to the concept of phasor measurement
unit. The concept is simple; a sinusoidal waveform can be represented by a magnitude and phase angle (Fig. 24-1). The magnitude
is the peak or rms value of the sinusoid. The phase angle is given by
the frequency and the time reference. The synchrophasor representation X of a signal x(t) is the complex value given by:
X = X r + jX i
= ( X m / 2 )e jφ
=
Xm
2
(24-1)
(cos φ + j sin φ )
where X m / 2 is the rms value of signal x(t) and φ is the phase
angle relative to cosine function at normal system frequency synchronized to universal time coordinated (UTC). This angle is 0°
when maximum of x(t) occurs at the UTC second rollover [1 pulse
per second (PPS) time signal] and −90° when the positive zero
crossing occurs at the UTC second rollover. Synchrophasors are,
thus, phasor values that represent power system sinusoidal waveforms referenced to nominal system frequency and coordinated
with universal time. The phase angle is uniquely determined by
the time of measurement, waveform, and system frequency. If a
sinusoid is observed at intervals (0, T0 , 2T0 , . . . , nT0 , . . .) leading
to phasor representations ( X 0 , X1 , X 2 , . . .) and observation time
interval T0 is an integer multiple of sinusoid T = 1/f, then a constant
phasor is obtained at each observation. If observation time T0 is
not an integer multiple of T, the observed phasor has a constant
631
632
CHAPTER TWENTY-FOUR
FIGURE 24-1
Concept of phasor representation of a sinusoidal waveform.
magnitude, but angles of the phasors ( X 0 , X1 , X 2 , . . .) will change
uniformly at a rate 2π ( f − f0 )T0 , where f0 = 1/T0.
System frequencies are not rock steady and can vary. An interconnected system runs at the same frequency and all phase angles
rotate together, one way or the other. Because of this rotation, the
phase angle measurements should be made exactly at the same
rate. As an example, state estimators run at intervals ranging from
a few seconds to 10s to minutes, and a phasor system running at
6+ samples/s cannot directly feed into the slower system. A solution
would be to use synchronized samples drawn (periodically) from the
full data set. This led to the development of IEEE standard C37.1181
revised in 2005. The basic measurement requirements, including
angle-time relationship, are detailed in this standard. The accuracy of
phasor estimate is compared with a mathematically predicted value
using a total vector error (TVE). This can be defined as root square
difference of the values, and compliance with the standard1 requires
a difference within 1 percent under various conditions:
TVE =
( X r (n ) − X r )2 + ( X i (n ) − X i )2
X i2 + X i2
(24-2)
where Xr(n) and Xi(n) are the measured values and Xr and Xi are
the theoretical values of the input signal at instant of time of
measurement.
Obtaining a phasor equivalent of an arbitrary sinusoidal signal
requires a sample of waveform taken at appropriate frequency—
the quality of phase estimate has to be ensured. Discrete Fourier
transform (DFT) is the most commonly used method of phase estimation. This technique uses the standard Fourier estimate applied
over one or more cycles at nominal system frequency. At a sufficient
sample rate and accurate synchronization with UTC, it produces
an accurate and usable phasor value for most system conditions.
Problems with DFT response like roll-off can occur with varying
frequency and must be corrected, for example, by centering the
measurement window. GPS is universally used for the UTC time
reference. Other PMUs may rely on time signal, such as IRIG-B
from an external GPS receiver.
The PMU functions are built into microprocessor-based multifunction relays (MMPR) and digital fault recorders (DFRs). These
may have variable capabilities. Based on analogue inputs; threephase quantities; and positive, negative, and zero sequence phasors
can be outputted. The sensing elements, that is, the accuracy of
potential and current transformers, become a question mark, and
so far ANSI/IEEE relaying class accuracies are found to be adequate.
Further work is being done by the North American Synchrophasor
Initiative (NASPI) project.
Figure 24-2 shows a typical hierarchal system; the PMUs feed
into the phasor data concentration (PDC) at a control center.
PDCs are produced which interface with other products, such as
monitor/control platforms and a data historian. PDCs connect to
multiple PMUs and receive, parse, and sort incoming data. Due to
sheer amount of data, it is an overwhelming computer processing task. IEEE standard1 establishes PMU data protocols. Over the
course of years, CPU processing power has increased. The number
of incoming PDC devices that may be deployed is limited by CPU
processing power.
Originally WAMSs were limited to single utilities. The interutility data exchange enables wide-area visibility. When interfacing with SCADA, the data must be reduced to match SCADA data
rates and interface with protocols used by SCADA. (Most estimators draw data from SCADA). The widely used IEEE common
format for transient data exchange (COMTRADE), IEEE Standard
C37.1112 developed for time sequence data, supports binary and
floating points formats. Most control center applications use a data
historian for analysis and trending. And generally, these will accept
data at full rate.
The phasor estimation, primarily developed for steady-state
signals, will be applied to system dynamics as the next step. Most
power system dynamics are slower compared with the speed
of phasor systems. An IEEE working group is formed to revise
C37.118 to include dynamic performance requirements. DCA
will make stability assessment and issue real-time control signals. The stability functional requirements will dictate the system
performance.
24-2 SYSTEM INTEGRITY PROTECTION
SCHEMES
System integrity protection schemes are automated systems that protect
the grid against system contingencies and minimize the potential for
wide outages. Without SIPS it may not be possible to provide for
many contingencies, address transmission paths, alternate routes,
corrective measures, and take prior warnings. A SIPS design is
based on system studies of predefined contingencies for a variety of
conditions. According to the IEEE Power System Relaying Committee
(PSRC), the following is the list of SIPS measures:
■
Generator and load rejection
■
Underfrequency and undervoltage load shedding
■
Adaptive load mitigation
■
Out-of-step tripping
■
Voltage and angular instability and advance warning
schemes
■
Overload and congestion mitigation
SMART GRIDS AND WIND POWER GENERATION
FIGURE 24-2
633
Typical star hierarchal system of PMUs feeding into PDCs that feed local and remote applications. These can extend to share data
between utilities.
■
System separation
■
Shunt capacitor switching
■
Tap changer control
■
SVC/STATCOM control
■
Turbine valve control
■
HVDC controls
■
Power system stabilizer control
■
Discrete excitation
■
Dynamic breaking
■
Generator runback
■
Bypassing series capacitor
■
Black-start or gas turbine start-up
■
ASGC actions
■
Bus bar splitting
We have discussed the basic concepts of many of these items
in this book. Applied to complex grid systems, SIPS is the last line
of defense to protect the integrity of the power system and propagation of disturbances for severe system emergencies caused by
unplanned operating conditions.
24-3
ADAPTIVE PROTECTION
The objective of adaptive relaying is to adjust relay performance or
settings as per changing system conditions. It can be defined as, a
protection philosophy which permits and seeks to make adjustments
automatically in various protection functions in order to make
them more attuned to prevailing system conditions. This is being
achieved by phenomenal advancements in the microprocessor-based
technology applied to protective relaying. For example, current differential schemes with high-speed communications can be applied to
transmission lines.
Dependability and security are measures of reliability, which
mutually oppose.3 To be dependable, the protection must always
trip, even if there are nuisance trips. Consider that a system is
robust and a dependable protection is applied to it—if the system changes, whether due to planned or unplanned outages,
the strength of the system to withstand same amount of trips
becomes questionable. With WAMS and digital devices, it is
possible to reorganize so as to reorient the relay performance
from dependable to secure. Figure 24-3 shows a scheme,
where three protective schemes can trip independently, without supervision to security, while tripping decisions are connected so that out of three at least two schemes should operate
correctly. After the 2003 East Coast Blackout, National Electric
Reliability Council (NERC) recommended removing all unnecessary zone 3 distance tripping to avoid, “over-tripping” by
these elements.
Other smart grid issues can be itemized as follows:
■
Requirements for renewable portfolio standards (RPS), limits on greenhouse gases (GHS), and demand response (DR).
■
■
Advanced metering structures at consumer loads.
Integration of solar, wind, nuclear, and geothermal facilities
which pose their own challenges. For example, the large-scale
solar plants or wind generation may be located in areas distant from existing transmission facilities. New protection and
control strategies, interconnection standards—for example,
low-voltage ride-through (LVRT) capabilities—forecasting, and
scheduling are required.
634
CHAPTER TWENTY-FOUR
FIGURE 24-3
Schematic adaptive protection and redundancy.
■
Managing circuit congestion, managing distribution system
overloads.
■
Role of information and automation technologies.
Figure 24-4 shows a wide-area control framework. Although it may
not be entirely possible to avoid multiple blackouts, the probability,
size, and impact of widespread outages can be reduced.
24-4
WIND-POWER STATIONS
A synopsis of wind-power generation is included. This is an important subject in view of rising energy costs and growing concerns
of global climate changes and environmental effects. With respect
to transient and stability analyses, interconnections of wind-power
FIGURE 24-4
stations with grid systems pose even larger problems, and require
more thorough analysis of the stability of the interconnection and
system isolation under disturbances.
More than 75000 MW of wind-power generation has been added
worldwide, out of which over 12000 MW is in the United States.
Looking at energy penetration levels (ratio of wind power delivered by
total energy delivered), Denmark leads, reaching a level of 20 percent
or more, followed by Germany. Sometiimes the wind energy penetration exceeds 100 percent, with excess sold to Germany and NordPool.
Nineteen off-shore projects operate in Europe producing 900 MW.
United States off-shore wind energy resources are abundant.
In the United States, wind-power generation accounts for
approximately 0.6 percent of the total, and Renewable Energy
Laboratory (DOE/NREL) did an investigation of what 20 percent
Wide-area control framework.
SMART GRIDS AND WIND POWER GENERATION
FIGURE 24-5
Twenty percent penetration of installed wind-power capacity: land-based and off-shore.
of energy from wind would look like in 2030 (Fig. 24-5). American Electric Power (AEP) produced a white paper that included
a 765-kV network overlay for a U.S. power system that would
increase reliability and allow for 400-GW of wind or other generation to be added. The political climate change in Washington can
impact these decisions and accelerate exploitation of wind power.
The modern wind-power plants can be as large as 300-MW and are
often located within a short distance of each other.
24-5
635
WIND-ENERGY CONVERSION
Today’s wind turbines all over the world have three-blade rotors, diameters ranging from 70 to 80 m and mounted atop 60 to 80 m or higher
towers. The tower heights up to 160 m are a technical feasibility. The
typical turbine installed in the United States in 2006 can produce about
1.5 MW of power. Higher-rated units and off-shore wind base plants
may see a unit size of 5 MW or more by 2010. Figure 24-6 shows the
developments of single-unit wind-power turbines in the United States.
Figure 24-7 is a schematic representation of electrical and
mechanical features of a wind converter unit, with upwind rotor.
FIGURE 24-6
The rotor speed which is of the order of 8 to 22 rpm is the input to
gear box, and on the output side the speed is 1500 to 1800 rpm. The
drive train dimensions are large, increasing the horizontal dimension of nacelle.
24-5-1
Drive Train
Several designs are under development to reduce the drive train weight
and cost. One approach is to build direct drive permanent magnet generators that eliminate the complexity of the gear box. The slowly rotating generator will be larger in diameter, 4 to 10 m, and quite heavy. The
decrease in cost and availability of rare-earth permanent magnets is
expected to significantly affect size and weight. The generator designs
tend to be compact and lightweight and reduce electrical loses in windings, as compared to wound rotor machines. Prototypes have been
built—a 1.5-MW design with 56 poles is only 4 m in diameter versus
10 m for a wound rotor design. It is undergoing testing at the National
Wind Technology Center.
A hybrid of direct drive approach uses a low-speed generator. The
WindPACT drive train project has developed a single-stage planetary
Development of single-unit wind turbines in the United States.
636
CHAPTER TWENTY-FOUR
weight growth much lower than the geometric escalation of blade
lengths. Work continues in the application of lighter and stronger carbon fiber in highly stressed areas to stiffen the blades, improve fatigue
resistance, and simultaneously reduce the weight. Research continues in
the development of lighter blades, such as carbon fiber and fiberglass.
24-6
THE CUBE LAW
Wind originates from a difference in temperature and pressure in
air mass. A change in these parameters alters the air density r. The
force exerted on volume of air V is given by:
F = Vg D ρ
(24-3)
where g is the gravitational constant. This produces kinetic energy:
E=
1 2
mv
2
(24-4)
where m is the mass of the air, v is the velocity which is assumed
constant, and E is the wind power. This is rather an oversimplification. If we consider an air volume of a certain cross section and a
swirl-free speed, upstream of the turbine and downstream of the
turbine, it will result in a reduction in speed, with a corresponding
broadening of the cross sectional area (wake decay). Thus, practically v is not constant. However, with this simplification of constant
speed, the basic tenets of turbine output are still valid.
The following equation can be written for the air mass:
m = ρ Av
(24-5)
where A is the rotor area. Substituting Eq. (24-5) in Eq. (24-4), the
theoretical power output is:
FIGURE 24-7
A schematic of a wind-power conversion unit,
showing major mechanical and electrical components.
drive operating at a gear box ratio of 9.16:1. The gear box drives a
72-pole permanent magnet (PM) generator, and reduces the diameter
of a 1.5-MW generator to 2 m.4 Another development is the distributed drive train.
24-5-2
Towers
Depending upon the nacelle weight, the towers are constructed
from steel or steel/concrete. The tower heights are up to 100 m.
Wind speeds are height dependent, and lattice towers of up to
160 m height can be constructed. A relationship between tower
mass and tower height shows sharp increase in the tower mass
per meter height as turbine output increases, approximately
2000 kg/m for turbines in the output range of 1.5 MW. Large
plants tend to have significantly greater mass per meter as the
mast height increases. There is an ongoing effort to develop
advanced tower designs that are easily transported and installed
and are cost effective.
The wind speeds are not uniform over the area of the rotor. The
rotor profiles result in different wind speeds at the blades nearest to the
ground level compared to the top of the blade travel. Gusts and changes
in wind speed impact the rotor unequally. Influences due to tower
shadow or windbreak effects cause fluctuations in power or torque.
24-5-3
The Rotor Blades
As the wind turbines increase in output so do their blades. During
the 1980’s, the blade length was only 8 m. It has increased to 70 m
for many land-based wind units. Improved blade designs have kept
P=
1
ρ Av 3c p
2
(24-6)
where the wind-speed-dependent coefficient cp describes the
amount of energy converted by the wind turbine. It is in the range
of 0.4 to 0.5.
All the energy in a moving stream of air cannot be captured. A
block wall cannot be constructed because some air must remain
in motion after extraction. On the other hand, a device which
does not slow the air will not extract any energy. The optimal
blockage is called Betz limit, which is around 59 percent. The
aerodynamic performance of blades has improved dramatically,
and it is possible to capture about 80 percent of the theoretical
limit. The new aerodynamic designs also minimize fouling due
to dirt and bugs that accumulate at the leading edge and can
reduce efficiency.
According to Betz, the maximum wind power turbine output is:
P=
16
ρ 3
A
v
27 R 2 1
(24-7)
where AR is the air flow in the rotor area and v1 is the wind velocity
far upstream of the turbine. The maximum is obtained when:
v2 =
2
v
3 1
and
v3 =
1
v
3 1
(24-8)
where v3 is the reduced velocity after broadening of the air stream
past the rotor, and v2 is the velocity in the rotor area. The ratio of the
power absorbed by turbine to that of moving air mass is:
P0 = A R
ρ 3
v
2 1
(24-9)
SMART GRIDS AND WIND POWER GENERATION
FIGURE 24-8
Rotor power of a wind generating unit, based on rotor speed and wind velocity.
where vTS is the blade tip speed and vRP is the speed of the rotor
plane, and vTS can be written as:
and
cp =
P
P0
(24-10)
Another way of defining cp is with respect to l, which is defined as:
λ=
637
vTS 2π nr
=
vRP
vRP
(24-11)
FIGURE 24-9
vTS = 2π nr
(24-12)
where r is the rotor radius, m, and n is the speed, s−1. Typical values
of l are 8 to 10, and the tip-speed ratio influences the power coefficient cp. Also cp is dependent on wind speed. Combining these
relations, Fig. 24-8 shows power or torque versus the wind speed.
(Torque is simply power divided by angular velocity w.) Figure 24-9
cp-l characteristics of a wind turbine unit with blade pitch angle.
638
CHAPTER TWENTY-FOUR
shows performance coefficient as a function of tip-speed ratio with
blade pitch angle as a parameter (see Sec. 24-7).
24-7
OPERATION
Figure 24-10 shows power curves for typical modern turbine. The
turbine output is controlled by rotating the blades about their long
axis to change angle of attack; this process is called “controlling the
blade pitch.” The turbine is pointed into the wind by rotating the
nacelle about the tower, which is called the “yaw control.” Modern
turbines operate with rotor positioned on the windward side of tower,
which is referred as an “upward rotor.” A turbine generally starts producing in winds of about 12 mph, reach a maximum power at about
28 to 30 mph and shutdown, or “feather the blades,” at about 50 mph.
The amount of energy in the wind available for extraction by turbine
increases with cube of speed, thus a 10 percent increase in speed
means a 33 percent increase in energy. While the output increases
proportional to rotor-swept area, the volume of material, and thus the
cost, increases as cube of the diameter. Controllers integrate signals
from dozens of sensors to control rotor speed, blade pitch angle, generator torque, power conversion voltage, and phase angle.
Wind-speed changes may occur over long periods of time or
suddenly within a matter of seconds. The system has to be protected
from the sudden gusts of wind. The mechanical loads are determined by dynamic forces, and knowledge of dynamic wind behavior at a location is necessary for proper component ratings, and the
mechanical power acting on the turbine should be limited.
There are three methods to achieve it:
1. Stall
2. Active stall
3. Pitch-control
FIGURE 24-10
The stall control exercises adjustable clutches on rotating blade tips
to shut down. Under normal conditions, laminar air flow occurs on
the blades. The lift values corresponding to angle of attack are achieved
at low drag components. With wind speeds exceeding nominal values
at which the generator-rated output occurs, higher angles of attack
and stalling occurs. This is achived by properly profiling the blades.
The lift forces and lift coefficient are reduced and the drag forces and
coefficients increased (Fig. 24-11a). Stall-regulated machines are often
designed with asynchronous generators of higher nominal output,
and rigid coupling with the grid is obtained. An active stall control is
achived with turnable rotor blades (Fig. 24-11b).
Variable blade pitch allows direct control of turbine. By varying the
blade pitch it is possible to control the torque of the turbine and by
further adjustments bring about a stall condition (Fig. 24-11c). The
control and regulation system is complex. In high power applications,
pitch control is used. For the design and control of pitch adjustments,
a host of mechanical moments and forces must be considered. These
inclule forces and moments due to blade deflection, lift on blades,
moments on propeller due to teetering, and frictional moments.5
24-7-1 Speed Control
The curves of fixed- and variable-speed generators are marked in
Fig. 24-12. This shows that when the turbine is driven by a synchronous generator, varying the generator frequency at a certain
wind speed will give operation at n/n1 = 1, where n corresponds
to the grid frequency. The turbine is constrained to follow the grid
frequency. Sufficient turbine torque to drive the generator is available for wind speeds above approximately 3.6 m/s for synchronous
generators to about 3.8 m/s for asynchronous generators. Under
variable-frequency generator operation, the speed of rotation can
be freely set within the given limits. The turbine utilization of the
available wind power is optimized. A ramp control of the active
power output is possible.
Typical wind generating unit operating curve, power verses wind speed.
SMART GRIDS AND WIND POWER GENERATION
FIGURE 24-11
Limiting the mechanical power in a wind turbine. (a) Stall control. (b) Active stall control. (c) Pitch control.
24-7-2 Behavior Under Faults and Low-Voltage
Ride-Through
Figure 24-13 shows the recommendation of Western Electricity
Coordinating Council (WECC) wind generation task force (WGTF)
with respect to proposed voltage ride-through requirements for
all wind generators. A three-phase fault is cleared in 9 cycles, and
the post-fault voltage recovery dictates whether the wind-powergenerating plant can remain online. The requirement does not
apply to faults that will occur between the wind generator terminals
and the high side of GSU (generator step-up unit transformer), and
the wind plants connected to transmission network via a radial line
will not be required to ride-through the fault on that line.
Figure 24-13 also addresses the high and low voltage profile that
must be maintained. Thus, the voltage should remain within a certain operating region defined in Fig. 24-13. Induction generators,
FIGURE 24-12
639
degrade power system voltage performance as these require excitation reactive power. The Federal Energy Regulatory Commission
(FERC) orders 661 and 661A require new wind generators to have
capability to control their reactive power within 0.95 leading to 0.95
lagging range. As this requirement can be expensive to comply, FERC
requires it only if the interconnection study shows that it is needed.
Modern wind generators provide this capability from power electronics that control the real power operation of the machine.
24-8
WIND GENERATORS
Induction generators are either squirrel-cage or wound-rotor
induction types, and their operation, circuit diagrams, and modeling
is discussed in Chap. 11. For wind-power generation, the generators
are rotating-field-type. The coupling with the grid, directly or through
inverters, is of significance. Mostly induction generators are used.
Wind turbine torque-speed characteristics by variation of generator frequency, superimposed on wind-power curves.
640
CHAPTER TWENTY-FOUR
FIGURE 24-13
Proposed WECC voltage ride-through requirements of wind generators.
The induction generator must draw its reactive power requirement from the grid source. When capacitors, SVCs, and rotary
phase shifters are connected, the operational capabilities can be
equivalent with synchronous machines, though resonance with
grid inductance is a possibility. Induction generators produce
harmonic and synchronous pulsating torques, akin to induction
motors (Chap. 11). A synchronous machine provides control of
operating conditions, leading or lagging by excitation control. With
respect to interconnection with the grid, the schemes exist that are
discussed in Secs. 24-8-1 through 24-8-3.
24-8-1
Direct Coupled Induction Generator
The direct coupled induction machine is generally of four-pole type;
a gear box transforms the rotor speed to a higher speed for generator operation above synchronous speed. It requires reactive power
from grid or ancillary sources, and starting after a blackout may be
a problem. Wind dependent power surges produce voltage drops
and flicker. The connection to the grid is made through thyristor
switches which are bypassed after start. A wound-rotor machine
has the capability of adjusting the slip and torque characteristics by
inserting resistors in the rotor circuit, and the slip can be increased
at an expense of more losses and heavier weight (Fig. 24-14a). The
system will not meet the current regulations of connection to grid
and may be acceptable for isolated systems.
24-8-2 Induction Generator Connected to Grid
through Full-Size Converter
The induction generator is connected to the grid through two back-toback voltage source converters. Because of the full-power rating of the
inverter, the cost of electronics is high. The wind-dependent power
spikes are damped by the dc link. The grid-side inverter need not be
switched in and out so frequently and harmonic pollution occurs.
24-8-3
Doubly Fed Induction Machine (DFIM)
The stator of the induction machine is directly connected to the
grid, while the rotor is connected through voltage source converter
(Fig. 24-14b). The energy flow over the converter in the rotor circuit is bidirectional. In subsynchronous mode, the energy flows to
the rotor, and in supersynchronous mode, it flows from rotor to
the grid. The ratings of the converter are much reduced, generally
one-third of the full power, and depend on the speed range of the
turbine. The power rating is:
P = Ps ± Pr
(24-13)
where Ps and Pr are the stator and rotor powers. But the rotor has only
the slip frequency induced in its windings, therefore, we can write:
Pr = Pa × s
(24-14)
where s is the slip and Pa is rotor air gap power. For a speed range
of ± 30 percent, the slip is ± 0.3, and a third of converter power is
required. Also we can write:
ns =
fr ± f
120
p
(24-15)
where p is the number of pairs of poles.
Synchronous generators can be brush type or brushless type of
permanent magnet excitation systems. These are also connected to
the grid much like asynchronous machines. The excitation power
has to be drawn from the source, unless the generator is of permanent magnet type. Figures 24-14c and d show typical connections.
24-9
POWER ELECTRONICS
The entire output of variable voltage, variable frequency output of a
wind generator, sometimes called the wild ac, is converted to direct
current, which is then converted to utility quality ac power. The
frequency converters condition the electrical energy from the wind
generators and dampen the influence on the grid connections. With
respect to the topology of the electronic devices, we have:
■
Current-controlled rectifier
■
Voltage source rectifier
■
Voltage source inverters
■
Current source inverters
The rectifiers may be (1) uncontrolled, (2) bridges with dc/dc
regulators, and (3) controlled rectifiers. Again, pulse-controlled
SMART GRIDS AND WIND POWER GENERATION
641
F I G U R E 2 4 - 1 4 Grid connections of wind generators. (a) Direct connection of an induction generator, stall regulated. (b) Connections of a DFIG,
variable-speed generator with pitch regulation. (c) Synchronous generator, brush-type or brushless with voltage source converters, pitch regulated.
(d ) Gearless connection of a low-speed permanent magnet generator.
IGBT topology with phase multiplication to reduce harmonic generation is the preferred choice, as active and reactive control of
power can be exercised (Chap. 15).
Consider a synchronous generator grid connection. The constant voltage dc link is supplied by a controlled rectifier bridge, and
the rectifier is current controlled so that magnitude and phase angle
of the generator current is controlled by triggering of the rectifier.
By phase shifting the generator current in underexcited and overexcited regions, the generator voltage can be controlled and matched
to the dc link.
Short-circuit current calculations according to machines integrated
in industrial systems may not always be valid. For example, in a DFIM,
the stator current for a nearby fault may be limited to nearly rated current if rotor power converter remains active. It may, however, be disabled by crowbar circuit for protection during fault, in which case the
fault current will be several times the rated currernt for a few cycles.
Switching of devices in converters gives rise to interference
emission over a wide spectrum. The electromagnetic compatibility
should be ensured according to relevant standards.
24-9-1
Reactive Power Control
Apart from the reactive power need of the induction machine itself,
the passive connecting element consumes reactive power. These
elements are transformers and cable connections to the point of
grid. Then the reactive power is required by loads. Problems of
transient low voltages can occur when the wind power generation
is connected to relatively weak grid systems.
Some wind-generating plants have added SVCs, DSTATCOMs,
and STATCOMs (Chap. 15), which control the power factor to
unity at the point of interconnection. The Argonne Mesa wind plant
in New Mexico has a DSTATCOM, which controls the power factor
to utility at the point of interconnection at Guadalupe 345-kV station bus. Four mechanically switched capacitor banks are located
in the collector substation some 2 mi away from the interconnect
substation. The DSTATCOM controls determine the required reactive power output based on voltage and current measurements at
345-kV collector bus.
Figure 24-15 shows the impact of high winds on the 1.5-MW
generators, connected to a 230-kV transmission line. Line-drop
compensation algorithms are utilized to synthesize voltage at the
point of interconnection, located approximately 75 km from the
wind plant. The flicker index of the voltage is less than 2 percent
at the point of interconnection. In spite of considerable variation in
the wind speed, the plant output is relatively stable.
Figure 24-16 shows field tests results on an active power
regulator and power rate limiter on an operating 30-MW wind
plant. Initially, the output is curtailed to 10 MW, and during the
tests the active power command is raised in four 5-MW increments. The transition between each step ramp-rate is controlled
to 2 MW/min.
642
CHAPTER TWENTY-FOUR
FIGURE 24-15
24-9-2
Wind-plant voltage response and regulation at the point of interconnection.
Harmonics
Generation of harmonics and mitigation is discussed in Chaps. 6
and 15. Even harmonics in wind generation can arise due to unsymmetrical half waves and may appear at fast load changes. Subharmonics can be produced due to periodical switching with variable
frequency. Interharmonics can be generated when the frequency is
not synchronized to the fundamental frequency, which may happen
at low- and high-frequency switching.
The interharmonics due to back-to-back configuration of two
converters can be calculated according to IEC.6
f n,m = [( p1k1 ) ± 1] f1 ± ( p2k2 )F
(24-16)
where fn,m is the interharmonics frequency, f1 input frequency, F
is output frequency, p1 and p2 are pulse numbers of the two converters, respectively. Interharmonics are also generated due to
speed-dependent frequency conversion between rotor and stator
of DFIM and as side bands of characteristic harmonics of PWM
FIGURE 24-16
converters. Noncharacteristic harmonics can be generated due to
grid unbalance.
24-10
COMPUTER MODELING
Modeling is required in the planning stage to conduct interconnection
studies, to establish grid reliability, and to simulate energy capture
for hybrid plants. A forecast is required for the wind power generation energy capability. This requires wind density probability curves
and history of wind samples at the location of wind generation. Also
simulation is required for aerodynamics, mechanical dynamics,
and structures—this gives ideas of static and dynamic loads, predicted power curves, vibration modes, and control system response.
Electrical transients in generators and power electronics need to be
simulated. Excess starting currents, behavior under short-circuit and
under voltage transients, and isolation from grid can be studied in a
time frame varying from a few microseconds to several seconds. GE
PSLF/PSDS and Siemens PTI/PSSE programs are designed for study
of large-scale interconnected systems, yet there is not much sharing
Active power response of a wind plant with ramp control.
SMART GRIDS AND WIND POWER GENERATION
FIGURE 24-17
FIGURE 24-18
643
Simplified block circuit diagram of aerodynamic and mechanical systems for modeling.
Output generated voltage of a 2-MW wind-generating DFIG unit, three-phase fault at 50 ms, cleared in 6 cycles, EMTP simulation.
644
CHAPTER TWENTY-FOUR
FIGURE 24-19
Voltages at the point of interconnection.
of the data between consultants, utilities, and power planners. Engineering design models are implemented in three-phase simulation
programs like EMTP and PSCAD. A simplification of turbine aerodynamic and mechanical systems models is depicted in Fig. 24-17.
Example 24-1 This example is a simulation of transients using
EMTP for a wind-generation plant of 22 MW, 2-MW DFIM units,
FIGURE 24-20
connected to utility system at 69 kV, through a GSU of 26 MVA.
A three-phase fault occurs on the 69-KV side of the GSU transformer
at 50 ms, and cleared at 51 ms, fault duration 1 ms ( = 6 cycles).
Figure 24-18 shows the generated voltage. Figure 24-19 depicts
voltage at the point of interconnection. Figure 24-20 shows the
stator and rotor currents in a DFIM, and also electrical power.
DFIG stator and rotor currents and electrical power output.
SMART GRIDS AND WIND POWER GENERATION
FIGURE 24-21
Real wind speed function, 2000 points, 200 intervals.
Figure 24-21 illustrates representation of wind speed function,
2000 sample points, interval 0 to 200.
24-11
645
FLOATING WIND TURBINES
The wind patterns change with height above ground. At a height of
approximately 1000 ft above ground, the winds are comparatively
steady and power can be produced 24 hours a day. It is not practical
to construct 1000-ft high towers. A video of an innovative idea of
helium-filled, lighter-than-air, floating wind turbines and development of a successful prototype is at Ref. 7. The construction of a
successful prototype describes a number of hurdles, such as design
of blades, testing in wind tunnels, stability as the turbine climbs
through the wind turbulence around 300-ft above ground, the
innovations in design of a tether with copper-core cable to transmit
generated power to ground, the strength of tether to support tons
of weight to withstand forces which the floating turbine will experience during the climb-up. Some millions of floating turbines can
meet all the energy requirements of the world, and set back the
clock on global warming. It may not be a commercial viability, but
is indicative of necessity-based ingenuity in the process of development of new technologies for better life on earth.
REFERENCES
1. IEEE Std. C37.118, IEEE Standard for Synchrophasors for
Power Systems, 2005.
2. IEEE Std. C37.111, IEEE Standard for Common Format for
Transient Data Exchange (COMTRADE) for Power Systems,
1999.
3. J. C. Das, “Power System Relaying” in Wiley Encyclopedia of
Electrical and Electronic Engineers, vol. 17, pp. 71–86, 2002.
4. The following reports can be found at: www.nrel.gov/publications/
D. A. Griffen, WindPACT Turbine Design Scaling Studies
Technical Area 1—Composite Blades for 80–120 m Rotor,
21 Mar. 2000–15 Mar. 2001; NREL Rep. SR-500-29492;
G. Bywaters, V. John, J. Lynch, P. Mattila, G. Norton, J. Stowell,
M. Salata, O. Labath, A. Chertok, and D. Hablanian, Northern
Power Systems WindPact Drive Train Alternative Design Study
Report: Period of Performance, Apr. 12, 2001–Jan. 31, 2005;
NREL Rep. SR-500-35524, 2004; M. W. LaNier, LWST
Phase 1 Conceptual Design Study: Evaluation of Design
and Construction Approaches for Economical Hybrid Steel/
Concrete Wind Turbine Towers, Jun. 28, 2002–Jul. 31,
2004; NREL Rep. SR-500-36777.
5. Dynamic Models for Wind Farms for Power System Studies,
http://www.energy.sintef.no/wind/IEA.asp.
6. IEC 61000-2-4, Electromagnetic Compatibility, Part 2. Environmental Section 4: Compatibility Levels in Industrial Plants for
Low-Frequency Conducted Disturbances.
7. Discovery Broadcast Channel—Green Earth-Infinite Winds,
www.discovery.com.
FURTHER READING
E. A. DeMeo, W. Grant, M. R. Milligan, and M. J. Schuerger,
“Wind Power Integration,” IEEE Power Energy Magazine, vol. 3,
no. 6, pp. 38–46, 2005.
EPA, Renewable Portfolio Standards Fact Sheet, http://www.epa.
gov/chp/state-policy/renewable_fs.html.
GE Energy and AWS Truewind, Ontario Wind Integration Study,
http://www.ieso.ca/imoweb/pubs/marketreports/OPA-Report200610-1.pdf.
S. Heier, Grid Integration of Wind Energy Conversion Systems, 2d ed.,
John Wiley, New York, 2009.
IEC-61400-21, Wind Turbine Generator Systems. Part 21: Measurement and Assessment of Power Quality Characteristics of Grid
Connected Wind Turbines, 2001.
646
CHAPTER TWENTY-FOUR
IEEE Std. 1001-1988, Guide for Interfacing Dispersed Storage and
Generation Facilities with Electric Facility Systems, 1988.
North American SynchroPhasors Initiative (NASPI), http://www.
naspi.org.
A. G. Phadke, J. S. Throp, and M. G Adamiak, “A New Measurement
Technique of Tracking Voltage Phasors, Local System Frequency,
and Rate of Change of Frequency,” IEEE Trans. PAS, vol. 102, no. 5,
pp. 1025–1038, May 1983.
R. Strzelecki and G. Benysek, eds., Power Electronics in Smart Electrical Energy Networks, Springer-verlag, London, 2008.
UWIG Modeling User Group, Dynamic Model Validation for the
GE Wind Turbine, www.uwig.org.
Western Electricity Coordinating Council Disturbance Monitoring
Reports, www.wecc.biz.
APPENDIX A
DIFFERENTIAL EQUATIONS
Differential equations form a powerful analytical tool in electrical
engineering. A fundamental knowledge of differential equations is
a prerequisite for understanding transients. This appendix provides
an overview.
An equation involving differential coefficients is called a differential equation. An example is:
L
d 2q
dq q
+ R + = E sin ω t
dt c
dt 2
(A-1)
This is an equation of the second order and first degree. The
order of the differential equation is the same as the order of the
highest differential coefficient present in the equation. The degree
pertains to the exponential of the highest differential. For example,
the following equation has an order of two and a degree of three:
4
d 2 y
dy
2 + y + y4 = 0
dx
dx
3
n
n+1
dv
+ + a n−1 + a n v = y(t )
dt
y = A cos x + B sin x
d2 y
= − ( A cos x + B sin x )
dx 2
dy h( x, y)
=
dx f ( x, y)
(A-7)
is a homogeneous equation if h(x, y) and f(x, y) are of the same degree.
Therefore, the following equation is a homogeneous equation:
( y2 − xy) dx + x 2dy = 0
(A-8)
dy xy − y2
=
dx
x2
(A-9)
The criterion in Eq. (A-7) is satisfied. Its solution can be found by
substituting as follows:
y = vx
dv
dy
= v+ x
dx
dx
(A-10)
By equating and simplifying, the original equation becomes:
x
dv
= −v 2
dx
(A-11)
−
dv dx
=
x
v2
(A-12)
or
(A-5)
Integrating and reverse substituting, the solution is:
Thus:
2
HOMOGENEOUS DIFFERENTIAL EQUATIONS
A differential equation of the form:
(A-4)
dy
= − A sin x + B cos x
dx
or
A-1
(A-3)
Differentiating it twice gives:
d y
= −y
dx 2
It can be generalized that the order of the differential equation
obtained will be equal to the constants in the original equation.
Because, by rearranging, Eq. (A-8) can be written as
is an equation of the nth order and nth degree. Note that the exponential of the lower derivative can be higher than the exponential
of the nth derivative.
In this equation a0 , a1, . . . , an are the constants, v(t) is the dependent variable, t is the time and is an independent variable, and y(t) is
the forcing function, sometimes called the excitation. Differentiating
the ordinary equations and eliminating the arbitrary constants can
form the differential equation. Consider an equation of the form:
2
■
(A-2)
In general, the following equation:
d n−1v
d n v
a 0 n + a1 n−1
dt
dt
This is a second-order equation obtained by eliminating the two
constants A and B in the original equation.The original equation
forms a solution of the differential equation arrived in Eq. (A-6).
d y
+y=0
dx 2
(A-6)
x
= log x + C
y
(A-13)
where C is a constant.
647
648
APPENDIX A
A-2
With this transformation Eq. (A-18) becomes:
LINEAR DIFFERENTIAL EQUATIONS
dz
+ P(1 − n )z = Q(1 − n )
dy
Consider a nonhomogeneous equation written as:
dy
+ Py = Q
dx
(A-14)
where P and Q are functions of x or are constants. P and Q cannot
be the functions of y. The Eq. (A-14) is called a linear differential
equation. Its solution can be found by multiplying both sides by:
e∫
Pdx
(A-15)
This is a linear equation and can be solved as before.
Example A-2 Solve:
tan y
dy
+ tan x = cos y cos 2 x
dx
The equation can be written as:
Thus, Eq. (A-14) becomes:
sec y tan y
Pdx dy
Pdx
e ∫ + Py = Qe ∫
dx
dy
dz
= sec y tan y
dx
dx
d ∫ Pdx
∫ Pdx
ye
= Qe
dx
Thus, the original equation reduces to:
Integrating both sides
= ∫ (Qe ∫
Pdx
Pdx
)dx + C
(A-16)
Pdx
This is the required solution. The factor e ∫ in Eq. (A-16)
is called the integrating factor, abbreviated as IF. The solution can
therefore be written in the following form:
yIF =
∫ Q IF dx + C
(A-17)
[( 4 x /x 2 +5 ) dx]
= e 2 log( x
2 +5 )
=
A-3
= e log( x
2 +5 )2
(A-20)
(A-21)
∂N
∂x
BERNOULLI’S EQUATION
Sometimes it is possible to reduce a differential equation to the
form in Eq. (A-14) by simple substitution. Consider the equation
of the form:
(A-18)
where P and Q are constants or function of x, but not of y as before.
This can be reduced to linear form by dividing by yn and then substituting the following expression:
1− n dy dz
=
yn dx dx
An equation of the form:
is the partial differential coefficient of M with respect to y, keeping
x constant; similarly:
x 4 5x 2
+
+C
4
2
Therefore:
EXACT DIFFERENTIAL EQUATIONS
∂M
∂y
x
1
=z
yn−1
A-4
where:
= ( x 2 + 5)2
∫ x 2 + 5 ( x 2 + 5)2dx + C
dy
+ Py + Qyn
dx
sec y = (sin x + C)cos x
∂M ∂N
=
∂y ∂x
Thus, the solution can be written as:
y( x 2 + 5)2 =
Its solution is:
is said to be an exact differential equation, if:
dy
+ 4 xy = x
dx
Here IF is:
e∫
dz
+ z tan x = cos 2 x
dx
Mdx + Ndy = 0
Example A-1 Solve the following equation:
( x 2 + 5)
dy
+ sec y tan y = cos 2 x
dx
By substituting z = sec y, and differentiating:
Therefore:
ye ∫
(A-19)
is the partial differential coefficient of N with respect to x keeping
y constant. The exact differential equations can be solved in the
following three steps:
1. Integrate M with respect to x keeping y constant.
2. Integrate with respect to y, only the terms in N which are
devoid of x.
3. The solution is given by the sum of the results of Steps 1 and 2.
Example A-3 Test for exactness and solve the following equation:
( x 4 − 2 xy2 + y 4 )dx − (2 x 2 y − 4 xy3 + cos y)dy = 0
Here:
M = ( x 4 − 2 xy2 + y 4 )
N = (2 x 2 y − 4 xy3 + cos y)
DIFFERENTIAL EQUATIONS
This satisfies the criteria in Eq. (A-21) and is therefore an exact
equation. The solution is given by:
This shows that y = Cu is the solution of:
dy
+ Py = Q
dx
∫ ( x 4 − 2 xy2 + y4 )dx + ∫ − cos ydy = C
In general, the complementary function is the solution of
the differential equation with Q set to zero. The solution will
have constants which are equal to the degree of the equation,
and these constants are evaluated from the initial conditions.
The solution presents a steady state when the transients have
decayed to zero. This conclusion will be amplified with
examples to follow.
5
x
− x 2 y2 + xy 4 − sin y = C
5
CLAIRAUT’S EQUATION
The equation:
y = px + f ( p )
(A-22)
Differentiate:
where:
− Pdx
dx
v = e ∫ ∫ (Qe ∫ )dx
dy
p=
dx
is called the Clairaut’s equation. Differentiating with respect to x:
with respect to x:
dv
− Pdx
Pdx
− Pdx
Pdx
= −Pe ∫ ∫ (Qe ∫ ) dx + e ∫ Qe ∫
dx
dp
dp
dy
= p + x + f (p)
dx
dx
dx
or:
However, dy/dx = p. Substituting and rearranging:
[x + f ′( p)]
dp
=0
dx
or
dp
=0
dx
Thus, p = a
Then:
y = ax + f (a )
(A-23)
is the required solution.
A-6 COMPLEMENTARY FUNCTION AND
PARTICULAR INTEGRAL
The solution of the differential equation in Eq. (A-14) can be written as summation of complementary function and particular integral. Let us revisit the solution of Eq. (A-14) derived in Eq. (A-16).
Equation (A-14) can be written as:
ye ∫
Pdx
= ∫ (Qe ∫
Pdx
) dx + C
or:
− Pdx
− Pdx
Pdx
y = Ce ∫ + e ∫ ∫ (Qe ∫ ) dx
y = Cu + v
− Pdx
u=e ∫
dv
= −Pv + Q
dx
and
Differentiate:
− P dx
u=e ∫
with respect to x. Then:
du
− Pdx
= −Pe ∫ = −Pu
dx
du
+ Pu = 0
dx
or
d(Cu )
+ P(Cu ) = 0
dx
− Pdx
Pdx
v = e ∫ ∫ Qe ∫ dx
(A-25)
dv
+ Pv = Q
dx
This shows that y = v is the solution of the original differential
equation [Eq. (A-14)].
■ In general, the particular integral does not contain a
constant and represents the transient response of the system
represented by the differential equation. The complete
solution is the sum of complementary function and particular
integral. We will apply these concepts to the solution of
second-order differential equations, which occur very
frequently in electrical systems.
A-7
FORCED AND FREE RESPONSE
Let us introduce here the ideas of free and forced response. Consider
a differential equation of the form:
n
where:
(A-24)
■
Thus, the solution is:
A-5
649
m
di y
diu
∑ ai dt i = ∑ bi dt i
i=0
(A-26)
i=0
where u = u(t) is the known input and y = y(t) the unknown output.
The free response of a differential equation is the solution of the differential equation when the input u(t) is identically zero. Then the
differential equation reduces to:
n
di y
∑ ai dt i
=0
(A-27)
i=0
The forced response of a differential equation is the solution of the
differential equation when all the initial conditions are identically
zero; that is:
y(o),
dy
dt
,...,
t =0
d n−1 y
dt n−1
t =0
(A-28)
650
APPENDIX A
This means that the forced response depends only on the input
u(t). For a constant coefficient ordinary differential equation the
forced response can be written in terms of a convolution integral:
t
yb (t ) =
m
∫ w(t − τ )∑ bi
i=0
0
d i u(τ )
dτ
dτ i
■
The total response is the sum of the free response and forced
response. We also use the terms steady-state response and transient response. The steady-state response is that part of the total
response which does not approach zero as the time approaches
infinity. The transient response is that part of the total response
which approaches zero as the time approaches infinity.
A-8 LINEAR DIFFERENTIAL EQUATIONS OF THE
SECOND ORDER (WITH CONSTANT COEFFICIENTS)
The general form of the equation is:
(A-30)
where P and Q are constants and R is a function of x or constant.
Define a differential operator D, so that:
dy
Dy =
dx
d2 y
D2 y =
dx
( D − m) y = v
then:
(A-29)
here w(t –t) is the weighting function, also called the Kernel of the
differential equation. This form of convolution integral describes a
casual system. Note that w(t) is a free response of the differential
equation and therefore requires n initial conditions for complete
specifications. These initial conditions fix the values of the constants C1, C2 . . . , Cn.
d2 y
dy
+ P + Qy = R
dx
dx 2
Substitute:
(A-31)
Then the complementary function is found by putting R = 0 in
Eq. (A-25):
( D − m)v = 0
v = C1e mx
or
Therefore, we can write:
( D − m) y = C1e mx
This can be written as:
dy
− my = C1e mx
dx
The solution is:
ye −mx = ∫ (C1e mx )e −mx dx + C2
= C1 x + C2
Thus, the complementary function is:
y = (C1 + C2 x )e mx
(A-35)
Case 3: The equation has imaginary roots. Let the roots be
a± ib. Then the solution will be:
y = C1e (α+iβ )x + C2e (α −iβ )x
= e α x[C1e iβ x + C2e −iβ x ]
= e α x[C1(cos β x + i sin β x ) + C2 (cos β x − i sin β x )]
(A-36)
= e α x[(C1 + C2 ) cos β x + i(C1 − C2 )sin β x]
Equation (A-36) can be written as:
y = e α x[A cos β x + B sin β x]
D 2 y + PDy + Qy = 0
(A-34)
(A-37)
Example A-4 Solve the differential equation:
Assume that:
d2 y
dy
− 6 + 9y = 0
dx
dx 2
y = C1e mx
is the complementary function of Eq. (A-25). Then:
The auxiliary equation is:
C1e mx (m2 + Pm + Q ) = 0
D 2 y − 6 Dy + 9 = 0
The equation:
m2 + Pm + Q = 0
(A-32)
y = (C1 + C2 x )e 3 x
is called the auxiliary equation.
Let us solve the Eq. (A-32). Three distinct cases arise:
C1 = 0 and
Case 1: The equation has real and different roots. The complementary function is:
(A-33)
Case 2: The equation has real and equal roots. In this case, we
can write:
(D – m)(D – m) y =0
(A-38)
The constants C1 and C2 can be found from the initial conditions. If the given initial conditions are:y(0) = 0 and y′(0) = 3, then
substituting y = 0 and x = 0 in Eq. (A-38):
A-9 CALCULATION OF COMPLEMENTARY
FUNCTION
y = C1e m1x + C2e m2 x
The roots are real and equal to 3,3. Therefore, the solution is:
y = C2 xe 3 x
On differentiating:
y′ = C2e 3 x + 3C2 xe 3 x
Substituting x = 0 and y′ = 3 in the above equation, C2 = 3. Therefore,
the solution satisfying the given conditions is:
y = 3 xe 3 x
DIFFERENTIAL EQUATIONS
A. Prove that:
Example A-5 Solve the differential equation:
d2 y
+ 6 y + 10 = 0
dx 2
for
y(0) = 2
1 ax
1 ax
e =
e
f (D)
f (a )
and
(A-41)
We know that:
y′(0) = y′′(0)
De ax = ae ax
The roots of the auxiliary equation are 3 ±i, therefore, the complementary function is:
D 2e ax = a 2e ax
y = e −3 x ( A cos x + B sin x )
−−−−−−−−−
y = 2, at x = 0, therefore, substituting, A = 2
651
D ne ax = a ne ax
y = e −3 x (2 cos x + B sin x )
if
f ( D )e ax = ( D n + C1D n−1 + + Cn−1D + Cn )e ax
Differentiating:
Then
dy
= e −3 x[− (3B + 2)sin x + (B − 6)cos x]
dx
f ( D )e ax = (a n + C1a n−1 + + Cn−1a + Cn )e ax
Differentiating again:
or
d2 y
= e −3 x[(− 6B + 16)cos x + (8B + 12)sin x]
dx 2
1 ax
e
f (D)
e ax = f (a )
Equating y′ = y″ at x = 0, we get B = 3.33. Thus, the solution is:
1 ax
1 ax
e =
e
f (D)
f (a )
y = e −3 x (2 cos x + 3 . 33 sin x )
If f (a) is zero, then this rule fails. In this case:
A-10
HIGHER-ORDER EQUATIONS
The complementary function of higher-order equations can be similarly found. Consider nth-order auxiliary equation:
a 0 D n + a1D n−1 + + a n−1D + a n = 0
1 ax
1
e = x2
e ax
f (D)
f "(a )
sin ax = f (−a 2 )
D(sin ax ) = a cos ax
3
D 4 (sin ax ) = D 2 D 2 sin(ax ) = D 2 (−a 2 sin ax ) = (−a 2 )2 sin ax
In general:
( D 2 )n sin ax = (−a 2 )n sin ax
2
sin ax
1
sin ax =
f (D2 )
f (−a 2 )
This can be factored as follows:
( D 2 + 4 D + 4 )( D 2 + 4 D + 5) = ( D + 2)( D + 2)( D 2 + 4 D + 5)
Thus, we can write:
f ( D 2 )sin ax = f (−a 2 )sin ax
Thus, the roots are 2, 2, –2 ± i. The solution is:
y = e 2 x (C1 + C2 x ) + e −2 x (C3 cos x + C 4 sin x )
A-11 CALCULATIONS OF PARTICULAR
INTEGRALS
The expressions for the calculation of particular integrals are shown
in Table A-1. We will prove some of these expressions.
D 2 (sin ax ) = D(a cos ax ) = −a 2 sin ax
D + 8 D + 25D + 36 D + 20 = 0
4
1
sin ax
f (D2 )
Proceed as follows:
d4 y
d3 y
d2 y
dy
+ 8 3 + 25 2 + 36 + 20 = 0
4
dx
dx
dx
dx
The auxiliary equation is:
(A-43)
B. Prove that:
(A-40)
Then, its complementary function can be written based on the relations already derived.
Example A-6 Find the solution of the differential equation:
(A-42)
If f ′(a) is also zero, then:
(A-39)
It has n roots, namely m1, m2, m3 . . ., mn; some of them can be equal,
imaginary, or real:
a 0 ( D − m1 )( D − m2 )( D − mn ) = 0
1 ax
1
1 ax
e =x
e ax = x
e
f (D)
f ′( D )
f ′(a )
1
1
f ( D 2 )sin ax =
f (−a 2 )sin ax
f (D2 )
f (D2 )
or
sin ax = f (−a 2 )
1
sin ax
f (D2 )
This proves the identity.
(A-44)
652
APPENDIX A
TA B L E A - 1
Rules for Finding Particular Integrals
in Differential Equations
1 ax
1 ax
e =
e
f (D )
f (a )
A.
if f ( a ) = 0
1 ax
1 ax
e =x
e
f (D )
f ′( a )
ifff ′( a ) = 0
1 ax
1 ax
e =x2
e
f (D )
f ′′( a )
B.
1 n
x = [f ( D )]−1 x n
f (D )
C.
sinax
1
sinax =
f (D 2 )
f ( −a 2 )
and
cosax
1
cosax =
f (D 2 )
f ( −a 2 )
D.
1 ax
1
φ( x )
e φ ( x ) = e ax
f (D )
f (D +a )
E.
1 n
1
x sinax = Im e iax
x n
f (D )
f
(
D
+
ia
)
and
1 n
1
x n
x co sax = Ir e iax
f (D )
f ( D + ia )
Im stands for the imaginary part and Ir for the real part.
F.
The general equation for finding the particular integral of
any function f (x):
1
φ ( x ) = e ax ∫ e −ax φ ( x )dx
D −a
C. Prove that:
Substitute:
1 ax
1
φ( x )
e φ( x ) = e ax
f (D)
f (D + a )
This equation is sometimes called heavyside shifting theorem.
D[e φ( x )] = e Dφ( x ) + ae φ( x ) = e ( D + a )φ( x )
D 2[e ax φ( x )] = D[e ax ( D + a )φ( x )]
= e ax ( D 2 + aD )φ( x ) + ae ax ( D + a )φ( x )
= e ax ( D + a )2 φ( x )
ax
ax
ax
ax
1
1
X=
[e ax X]
f (D + a )
f (D)
1
1
φ( x )
[e ax φ( x )] = e ax
f (D)
f (D + a )
D n[e ax φ( x )] = e ax ( D + a )n φ( x )
f ( D )[e φ( x )] = [e f ( D + a )φ( x )]
1
e axφ( x ) =
[e ax f ( D + a )φ( x )]
f (D)
e ax
or:
In general:
ax
f ( D + a )φ( x ) = X
(A-45)
D. Prove the following general equation in Table A-1:
ax
(A-46)
1
φ( x ) = e ax ∫ e −ax φ( x )dx
D−a
(A-47)
DIFFERENTIAL EQUATIONS
The complete solution is:
Assume that the particular integral is:
1
φ( x ) = y
D−a
(C1 + C2 x + x 3 )e 2 x +
Then:
ExampleA-8
1
(D − a )
φ( x ) = ( D − a ) y
(D − a )
5 −2 x 1
e + log 3
16
4
Solve:
d2 y
dy
+ 4 + 4 = x3
dx
dx 2
or:
φ( x ) = Dy − ay
The roots of the auxiliary equation are –2, –2 and therefore the
complementary function is:
This is a linear differential equation. Its solution is:
− adx
ye ∫ =
653
(C1 + C2 x ) e −2 x
∫ e − ∫ adx φ( x )dx
The particular integral is:
or:
ye −ax =
∫ e −axφ( x )
−2
1
1 D
x 3 = 1 + x 3
2
4 2
( D + 2)
Which proves Eq. (A-47).
E. General solution with multiple roots:
PI =
Expand by binomial theorem; particular integral is:
1
x
( D − s1 )( D − s2 )
(A-48)
Consider that s1 and s2 are the roots of the characteristic equation.
Thenthe particular integral can be found by successive integrations
D (− 2)(− 3) D 2 (− 2)(− 3)(− 4 ) D 3
1
+
+ x 3
1 − 2 +
4
2
2!
4
3!
8
1 1
PI =
x
D − s1 D − s2
but:
1
x = e s2 x ∫ e −s2 x x dx
D − s2
=e
∫e
( s2 −s1 )x
∫e
− s2 x
e
∫e
( s2 −s1 )x
∫e
( s3 −s2 )x
9
1 3
2
x − 3 x + x − 3
2
4
Example A-9
2
x(dx )
∫ ∫ e
( sn −sn −1 )x
∫e
− sn
x(dx ) (A-49)
n
A-12 SOLVED EXAMPLES
Example A-7 Solve:
2
d y
dy
− 4 = 4 y = 6 xe 2 x + 5e −2 x + log 3
dt
dt 2
d y
dy
+ 2 + 5 y = 2 sin 3 x
dx
dx 2
The roots of the auxiliary equation are 1 ± 2i. Thus, the complementary function is:
( A cos 2 x + B sin 2 x ) e − x
The particular integral is:
1
1
2 sin 3 x = 2
sin 3 x
D2 + 2D + 5
(− 32 ) + 2 D + 5
=
The roots of the auxiliary equation are 2, 2, and therefore the complementary function is:
The particular integral is:
1
1
1
log 3
6 xe 2 x + 2
5e −2 x + 2
D − 4D + 4
D − 4D + 4
D − 4D + 4
1
1
1
+ log 3 2
e0x
= 6e 2 x 2 x + 5e −2 x
4+8+ 4
D − 4D + 4
D
5
1
= x 3e 2 x + e −2 x + log 3
4
16
2 2 D + 4
4D + 8
sin 3 x
sin 3 x =
2 D − 4 2 D + 4
4 D 2 − 16
1
1
= − ( D + 2)sin 3 x = − (3 cos 3 x + 2 sin 3 x )
13
13
(C1 + C2 x )e 2 x
2
Solve:
2
In general if s1, s2, s3, . . . , sn are the roots of the auxiliary equation,
the particular integral is:
s1 x
=
9
1
(C1 + C2 x ) e −2 x + x 3 − 3 x 2 + x − 3
2
4
1
[e s2 x ∫ e −s2 x x dx]
D − s1
s1 x
1 3
3 2 3 1 3 3
3
x − Dx + D x − D x
4
4
2
Thus, the complete solution is:
Substituting:
PI =
=
The complete general solution is:
y = ( A cos 2 x + B sin 2 x ) e − x −
Example A-10
1
(3 cos 3 x − 2 sin 3 x )
13
Solve:
d2 y
dy
− 3 + 2 = 3 xe 2 x + 2e x cos x
dx
dx 2
654
APPENDIX A
The roots of the auxiliary equation are 1 and 2. Therefore, the complementary function is:
Now:
1
sec 2 x = e 2ix ∫ e −2ix sec 2 xdx
D − 2i
C1e 2 x + C2e x
The particular integral is:
= e 2ix
1
1
3 xe 2 x + 2
2e x cos x
D 2 − 3D + 2
D − 3D + 2
1
1
= 3e 2 x
x + 2e x
cos x
( D + 2)2 − 3( D + 2) + 2
( D + 1)2 − 3( D + 1) + 2
1
1
cos x
x + 2e x 2
D(1 + D )
D −D
1
1
= 3e 2 x (1 + D )− 1 x + 2e x
cos x
−1 − D
D
(1 − D )
1
cos x
= 3e 2 x [1 − D + D 2 + ]x − 2e x
(1 + D )(1 − D )
D
1
= 3e 2 x − 1 + D + x − e x (1 − D )cos x
D
= 3e 2 x
Also:
i
1
sec 2 x = e −2ix x − log cos 2 x
D + 2i
2
The particular integral is therefore:
i
i
1 ix
e x + log cos 2 x − e −2ix x − log cos 2 x
4i 2
2
This can be further simplified to:
d2 y
+ y = x 2 sin x
dx 2
x
1
sin 2 x + cos 2 x log cos 2 x
4
2
The particular integral is given by:
Example A-13 Find the particular integral of:
1
1
x 2 sin x = Im 2
x 2e ix
2
D +1
D +1
d3 y
d2 y
dy
+4
+6 = x
2
dx
dx
dx
The roots of the auxiliary equation are 0, (s1), (2 – 2i) (s2), and
–(2 + 2i) (s3). The particular integral is:
−1
1 D
= Im e ix
1 + x 2
2iD 2i
PI =
=
The solution is given by:
e ix
2i
x 3 ix 2 x
−
+
2 2
3
an x n
d2 y
+ 4 y = sec 2 x
dx 2
C1 cos 2 x + C2 sin 2 x
dn y
d n−1 y
+ a n−1 x n−1 n−1 + + a 0 y = φ( x )
n
dx
dx
x = ez
The particular integral is:
(A-50)
z = log e Z
d
=D
dz
The equation is reduced to a differential equation with constant
coefficients:
1
1
sec 2 x =
sec 2 x
( D + 2i)( D − 2i)
D2 + 4
1 1
1 1
sec 2 x −
sec 2 x
4i D − 2i
4i D + 2i
where a0, a1, a2, . . . , an are constants is called a homogeneous linear
differential equation. By substituting:
The complementary function is:
=
∫ e −(2+2i)x ∫ e 4ix ∫ e(2−2i)x x(dx )3
An equation of the form:
Example A-12 Solve:
1 1
1
=
−
sec 2 x
4i D − 2i D + 2i
1
x
D( D + 2 + 2i)( D + 2 − 2i)
A-13 HOMOGENEOUS LINEAR DIFFERENTIAL
EQUATIONS
1 x 3
x
x2
PI = − cos x − cos x −
sin x
2 3
2
2
i
= e 2ix x + log cos 2 x
2
Example A-11 Find particular integral of:
= Im
cos 2 x − i sin 2 x
dx
coss 2 x
= e 2ix ∫ (1 − i tan 2 x )dx
x2
= 3e 2 x − x + 1 − e x (cos x + si n x )
2
1
x 2
= Im e ix
2
( D + i) + 1
∫
dy dy dz 1 dy
=
=
dx dz dx x dz
or:
x
dy
= Dy
dx
(A-51)
DIFFERENTIAL EQUATIONS
Similarly, it can be proved that:
x2
d2 y
= D( D − 1) y
dx 2
d3 y
x
= D( D − 1)( D − 2) y
dx 3
From these equations x can be eliminated by multiplying the first
equation by 4 and the second equation by (D + 3) and then subtracting. This gives:
(A-52)
3
y = C1e −2t + C2e t
Dy = − 2C1e −2t + C2e t
Using Eq. (A-51) the equation is reduced to:
D( D − 1) y − 2 Dy = e + 8
( D − 3D ) y = e + 8
z
3
x = − C2e t
4
The roots of the auxiliary equation are 0 and 3. Therefore the complementary function is:
C1 + C2e 3z
The particular integral is:
1
1
8
ez + 2
e 0z
(e z + 8) = 2
D 2 − 3D
D − 3D
D − 3D
e z 8z
1 z
1
=
e + 8z
e 0z = − −
2
3
1− 3
2D − 3
The complete solution is:
e z 8z
−
2
3
PARTIAL DIFFERENTIAL EQUATIONS
Partial differential equations are encountered in transmission line
models, wave equations, heat flow, and other engineering applications. A brief description and methods of solution are provided.
The equations contain partial differential coefficients, independent
variables, and dependent variables. Let us denote the independent
variables with x and y and the dependent variable by z; then the
partial differential coefficients are:
∂z
=q
∂y
∂z
=p
∂x
∂2 z
=s
∂ x∂ y
(A-54)
The selection of p, q, r, and s is arbitrary. Consider an equation:
Pp + Qq = R
SIMULTANEOUS DIFFERENTIAL EQUATIONS
When two or more dependent variables are functions of a single
independent variable, the equations involving their derivates form
simultaneous differential equations. In the transient solutions of
electrical networks, many simultaneous differential equations are
required to be solved.Consider the equations:
dx
+ ay = t
dy
A-15
∂2 z
=r
∂x 2
x 8
= C1 + C2 x 3 − − log x
3 3
A-14
Substituting the solution thus found and solving for x, we get:
z
y = C1 + C2e 3z −
This can be solved for y, roots are 1 and –2, and thus the solution is:
d2 y
dy
− 2x
= x +8
dx
dt 2
2
( D + 2)( D + 3) y − 4( D + 2) y = 0
( D 2 + D − 2) y = 0
Example A-14 Solve:
x2
(A-55)
This is called Lagrange’s linear equation, where P, Q, and R are functions
of x, y, and z. Such an equation can be solved by following steps:
■
Step 1: Write the auxiliary equation:
dx dy dz
=
=
P
Q
R
(A-56)
(The proof of this relation is not provided.)
(A-53)
dy
+ bx = sin t
dt
Here x and y are both functions of t. The procedure of solving simultaneous differential equations is somewhat similar to solution of
simultaneous algebraic equations. Matrix techniques are shown in
Chap. 2. Here we will illustrate the concept with a simple example.
Example A-15 Solve the following simultaneous equations:
dx dy
+ + 3x + 2 y = 0
dt dt
Step 2: Let u = c1 and v = c2 be the solutions.
■
Step 3: Then f (u,v) = 0 or u = f (v) is the solution. (A-58)
Example A-16
p=
∂z
∂x
q=
Solvexp + yq = z, where
∂z
∂y
The auxiliary equation is:
Thus, from first two equations
We can write the equations as:
( D + 3)x + ( D + 2) y = 0
■
dx dy ∂ z
=
=
x
y
z
dy
+ 4x + 2y = 0
dt
4 x + ( D + 2) y = 0
655
log x = log y + log c1
and from the last two equations
log y = log z + log c2
y /z = c2 , x /y = c1
(A-57)
656
APPENDIX A
and the solution is:
Nonhomogeneous Linear Differential Equations
the equation of the form:
p − mq = az
x y
f , =0
y z
A-15-1
N th-Order Linear Partial Differential Equations
(A-59)
is a homogeneous linear partial differential equation of nth order.
It is homogeneous because all the terms contain derivatives of the
same order. The solution is somewhat akin to ordinary differential
equations, complementary functions, and particular integrals.
a0
y + mx = c
and from first and third relation:
1
log z + c
a
ax = log z + ac
x=
Therefore:
∂z
∂z
∂z
+a
+a
=0
∂ x 2 1 ∂ x∂ y 2 ∂ y2
2
(A-64)
z = e ax −ac = c2e ax
Complementary Function
Consider an equation:
2
dx dy dz
=
=
1 −m az
Thus, from first two relations:
∂n z
∂n z
∂n z
+ a1 n−1 + + a n n = F( x, y)
n
∂x
∂x ∂y
∂y
A-15-2
(A-63)
The Lagrange equation is:
An equation of the type,
a0
Consider
2
(A-60)
Z = e ax f ( y + mx )
A-15-3
Write this equation as:
(A-65)
Particular Integrals
The rules for finding particular integrals in partial differential equation are tabulated in Table A-2.
(a 0 D 2 + a1DD′ + a 2 D′2 ) = 0
Case 1:
Put D = m, D′ = 1, then the equation reduces to:
PI
a 0 m + a1m + a 2 = 0
2
e ax+by
1
e ax+by =
f (a, b)
f ( D, D′)
(A-66)
(Put D = a, D′ = b)
If the roots are real and unequal, then:
CF = f1( y + m1 x ) + f2 ( y + m2 x )
(A-61)
Case 2:
PI
If the roots are real and equal, then:
CF = f1( y + mx ) + xf2 ( y + mx )
(A-62)
TA B L E A - 2
sin(ax + by)
1
sin(ax + by) =
(A-67)
f ( D 2 , DD′, D′2 )
f (−a 2 , −ab, −b 2 )
D 2 = −a 2
DD′ = −ab
D′2 = −b2
Rules for Finding Particular Integrals in
Partial Differential Equations
A.
PI
1
1 ax +by
e ax +by =
e
f ( D ,D ′ )
f ( a ,b )
B.
PI
sin( ax + by )
1
sin( ax + by ) =
f ( D 2 , DD ′, D ′2 )
f ( −a 2 − ab − b 2 )
C.
PI
cos( ax + by )
1
cos( ax + by ) =
f ( D 2 , DD ′, D ′2 )
f ( −a 2 − ab − b 2 )
D.
PI
1
x m y m = [f ( D ,D ′ )]−1 x m y m
f ( D ,D ′ )
E.
PI
1
φ ( x ,y )
f ( D ,D ′ )
Resolve
1
in partial fracti ons, considering f ( D ,D ′ ) as
f ( D ,D ′ )
function of D only.
PI =
1
φ ( x ,y ) = ∫ φ( x ,c − mx )dx
D − mD ′
DIFFERENTIAL EQUATIONS
Case 3:
PI
cos(ax + by)
1
cos(ax + by) =
(A-68)
f ( D 2 , DD′, D′2 )
f (−a 2 , −ab, −b 2 )
657
Let y = XT, where X is a function of x only and T is a function of t
only. Then we can write:
∂y
dT
=X
∂t
dt
∂2 y
d 2T
=X 2
2
∂t
dt
Case 4:
Note that T and X are functions of a single variable only. Similarly
1
PI
x m yn = [ f ( D, D′)]−1 x m yn
f ( D, D′)
(A-69)
Expand f[(D, D′)]–1 in ascending powers of D or D′ and operate on x m yn term by term.
Substituting these results in the original equation:
Case 5:
X
Any function, F(x, y)
PI
1
F( x, y)
f ( D, D′)
1
F( x, y) =
D − mD′
d 2T
2
dt
C 2T
∫ F( x, c − mx )dx
Example A-17 Solve:
d2 X
− kX = 0
dx 2
The auxiliary equation is:
m2 − kC 2 = 0
m=±C k
m2 − k = 0
m=± k
Three cases arise:
Case 1: ki > 0
T = C1e C
Therefore, the complimentary function is:
CF = f1( y) + xf2 ( y) + f 3 ( y + 2 x )
PI =
The auxiliary equations are:
∂3 z
∂3 z
= 2x 2 y
−2
3
∂ x∂ y
∂x
m 2 ( m − 2) = 0
d 2 X
2
dx
= k(say)
X
and
d 2T
− kC 2T = 0
dt 2
(A-70)
where c is replaced with y + mx after integration.
( D 3 − 2 D 2 D′) = 0
d 2T
d2 X
= C 2T 2
2
dt
dx
Thus by separating the variables, we have:
Resolve 1/f(D, D′) into partial fractions. Considering that f(D,
D′) is a function of D alone:
PI =
∂2 y
d2 X
=T 2
∂x 2
dt
dX
∂y
=T
dt
∂x
kt
+ C 2 e −C
kt
X = C 3e
kx
+ C4e −
kx
(A-71)
Thus the solution is:
y = (C1e C
1
2x 2 y
D − 2D2 D′
kt
+ C 2 e −C
kt
) × (C3e
kx
+ C4e −
kx
)
3
=2
1
2D′
D 3 1 −
D
Case 2: k < 0 (wave motion)
x2 y
y = (C5 cos C kt + C6 sin C kt ) × (C7 cos k x + C8 sin k x )
(A-72)
−1
2 2D′ 2
2 2D′ 2
x y
= 3 1 −
x y = 3 1 +
D
D
D
D
=
2
2 2
2 2
x y + x 2 = 3 x 2 y + x 3
3
3
D
D
D
4x6
x5
= 2y
+
3× 4 × 5 3× 4 × 5× 6
Thus, the complete solution is CF + PI.
Example A-18 Solve the wave equation:
∂2 y 2 ∂2 y
=c
∂t2
∂x 2
Case 3: k = 0
y = (C9t + C10 ) × (C11 x + C12 )
(A-73)
The constants can be evaluated from the boundary conditions, as
illustrated before.
Partial differential equations appear in the wave propagation on
transmission lines (Chap. 4). The nonlinear differential equations
and their solutions are discussed in App. G. A nonlinear differential equation is nonhomogeneous and has variable coefficients.
An important nonlinear differential equation in electrical engineering is the swing equation of a synchronous machine (Chap. 12).
Numerical methods are used for solution of nonlinear differential
equations (App. G).
658
APPENDIX A
FURTHER READING
R. Bronson and G. Costa, Differential Equations, 3d ed., Schaum’s
Outline Series, McGraw Hill,New York, 2006.
J. Cronin, Ordinary Differential Equations: Introduction to Qualitative
Theory, Chapman and Hall/CRC, Boca Raton, FL, 2008.
P. DuChateau and D. W. Zachmann, Partial Differential Equations,
Schaum’s Outline Series, McGraw Hill, New York, 1986.
H. Edwards and D. Penny, Differential Equations and Boundary Value
Problems—Computing and Modeling, Pearson Education, Upper Saddle
River, NJ, 2004.
S. J. Farlow, Partial Differential Equations for Scientists and Engineers,
Dover Publications, New York, 1993.
E. D. Rainville and P. E. Bedient, Short Course in Differential Equations,
4th ed., Macmillan, New York, 1969.
R. G. Watts, Essentials of Applied Mathematics for Scientists and
Engineers, Morgan and Claypool Publishers, San Rafael, CA, 2007.
APPENDIX B
LAPLACE TRANSFORM
The classical approach to the solution of differential equations is
described in App. A, and the methodology can be used for a variety of excitation functions. Laplace transformation transforms the
exponential and transcendental functions and their combinations
into algebraic equations. Differentiation and integration are transformed into multiplication and division. Effective use of step and
impulse responses is made. The boundary values are considered in
the formation of the transform. After a solution of these geometric equations is found, the inverse Laplace transform is applied to
obtain the solution in the time domain. This three-step process of
solving the differential equations may simplify the calculations.
If f(t) is a function defined for all positive values of t, then,
∞
F(s) =
∫ e −st f (t )dt
(B-1)
0
is called the Laplace transform of f(t), provided the integral exists.
We write it in the form:
[ f (t )] = F(s)
Some properties of the transform are:
(a) [af1(t ) + bf2 (t )] = a [ f1(t )]+ b[ f2 (t )]
where a and b are not functions of t.
(b) [e at f (t )] = F(s − a )
e iat − e −iat
(t sin at ) = t
2i
If F(s) is the Laplace transform of f(t) and denoted by above equation,
then,
(t n ) =
=
1
[ (te iat ) − (te −iat )]
2i
=
1 1
1
−
2
2i (s − ia ) (s + ia )2
=
2as
(s2 + a 2 )
(B-3)
is called the inverse Laplace transform of F(s).
Tables B-1 and B-2 provide Laplace transforms of some functions
and their inverses. We will prove one result shown in Table B-1.
Example B-1 Prove that:
n!
s n+!
(B-4)
By definition:
(B-6)
This is called first shifting theorem. Proofs of Eqs. (B-5) and (B-6)
are not provided.
Example B-2 Find the Laplace transform of t sin at
(B-2)
f (t ) = −1F(s)
(B-5)
B-1
METHOD OF PARTIAL FRACTIONS
The resolution of the transformed geometric equations into partial
fractions is key to the solution of differential equations using Laplace
transform. A function can be converted into its partial fractions:
∞
(t n ) =
∫ e −stt n dt
0
Substitute x = st
∞
n
x dx
(t ) = ∫ e
s s
0
−x
n
=
1
s n+1
n!
= n+1
s
∞
∫ e − x x n dx
0
N( x )
N( x )
A( x ) B( x ) C( x )
=
=
+
+
D( x ) G( x )H( x )L( x ) G( x ) H( x ) L( x )
(B-7)
The numerator N(x) must be of lower order than the denominator D(x). Mathematical texts describe the resolution of a
function into partial fractions—here an overview is provided
through examples.
Example B-3 Find inverse Laplace transform of:
2s + 1
s(s + 1)(s + 2)
659
660
APPENDIX B
TA B L E B - 1
Some Important Laplace
Transform Pairs
Some Important Inverse Laplace
Transform Pairs
1
s
1.
1
− 1 = 1
s
n!
n = 0,12
, ,3,...
s n +1
2.
1 t n −1
− 1 n =
s ( n − 1)!
1
s >a
s −a
3.
a
s 2 +a 2
1 at
− 1
=e
s − a
4.
a
−1 2 2 = sin at
s + a
5.
s
−1 2 2 = cos at
s + a
6.
a
−1 2 2 = sinh at
s − a
7.
s
−1 2 2 = cosh at
s − a
s +a
( s + a )2 + ω 2
8.
1 at
1
= e sin bt
− 1
2
2 b
−
+
s
a
b
(
)
s sin θ + ω cos θ
s 2 +ω 2
9.
s − a at
− 1
= e cos bt
( s − a )2 + b 2
s cos θ − ω sin θ
s 2 +ω 2
10.
1 at
1
− 1
= e sinh bt
( s − a )2 − b 2 b
1.
u (t ) =
2.
(t n ) =
3.
(e at ) =
4.
(sin at ) =
(cos at ) =
5.
TA B L E B - 2
s
s 2 +a 2
s
s 2 −a 2
6.
(co sh at ) =
7.
a
(sinh at ) = 2 2
s −a
8.
(e −at sin ωt ) =
9.
(e −at cos ωt ) =
10.
(sin ωt +θ ) =
11.
(cos ωt +θ ) =
12.
(te at ) =
1
( s − a )2
11.
13.
t n −1 1
n = int eger
=
( n − 1)! s n
s − a at
− 1
= e cosh bt
( s − a )2 − b 2
12.
14.
1 n −1 at
1
t e =
( n − 1)!
( s − a )n
s 2 −a 2
−1 2 2 2 = t cos at
( s + a )
ω
( s + a )2 + ω 2
Therefore, the inverse Laplace transform is:
1
3
(1)+ e −t − e −2t
2
2
This can be written as:
B-1-1
2s + 1
A
B
C
= +
+
s(s + 1)(s + 2) s s + 1 s + 2
2s + 1 = A(s + 1)(s + 2) + Bs(s + 2) + Cs(s + 1)
B=
C=
2s + 1
s(s + 2)
2s + 1
s(s + 1)
1
=
2
s=0
=1
A
A
A
N( x )
F( x )
= 0 + 1 + + m−1 +
X
G( x )
X mG( x ) X m X m−1
F( x ) = f0 + f1 x + f2 x 2 +
( s = 0)
s=−2
−3
2
(B-9)
G( x ) = g 0 + g1 x + g 2 x 2 +
N( x ) = n0 + n1 x + n2 x 2 +
(s = − 1)
This gives the following relations:
s=−1
=
(B-8)
where
A, B, and C can be evaluated by:
2s + 1
A=
(s + 1)(s + 2)
Repeated Linear Factors
A general equation for resolution into partial fractions is of the form:
( s = − 2)
A0 =
n0
g0
A1 =
n1 − A0 g1
g0
A2 =
n2 − A0 g 2 − A1g1
g0
(B-10)
LAPLACE TRANSFORM
In general:
Ak =
Therefore, the inverse transform is:
k−1
1
nk − ∑ Ai gk − 1
g 0
i=0
(B-11)
The method of application of these equations to obtain partial fractions is illustrated in the following example.
Example B-4 Resolve into partial fractions:
s +2
s 3 ( s 2 + 2s − 4 )
1
[a sin at − b sin bt]
a 2 − b2
B-2 LAPLACE TRANSFORM OF
A DERIVATIVE OF f (t )
[ f ′(t )] = s[ f (t ) − f (0)]
2
A
A A
Ds + E
s2 + 2
= 0+ 1+ 2+ 2
3 2
s s + 2s − 4
s ( s + 2s − 4 ) s 3 s 2
We could write A0 = A, A1 = B, A2 = C. Then
n0
2
1
=
=−
g0 − 4
2
1
n1 − A0 g1 0 + 2 (2)
1
A1 =
=
=−
g0
−4
4
1
1
1 − − (1) − − (2)
n − A0 g 2 − A1g1
1
4
2
A2 = 2
=
=−
g0
−4
2
0
∞
− ∫ (−se st ) f (t )dt
0
0
= − f (0 ) + sf (t )
+
= sf (t ) − f (0+ )
(B-12)
■
The Laplace transform of a derivative of f(t) corresponds approximately to the multiplication of Laplace transform of f(t) by s.
f n (t ) = s n [ f (t ) − s n−1 f (0+ ) − s n−2 f ′(0+ ) − − f n−1]
(B-13)
B-3
LAPLACE TRANSFORM OF AN INTEGRAL
The Laplace transform of integral of f(t) is given by:
t
∫ f (t )dt =
0
1
F(s)
s
(B-14)
We can also write:
1
t
∫ f (t )dt = −1 s F(s)
(B-15)
0
Calculate D and E as follows:
■
D = n 3 − A0 g 4 − A1g 3 − A2 g 2 =
1
2
E = n 3 − A0 g 3 − A1g 2 − A2 g1 =
5
4
The partial fractions are:
The Laplace transform of an integral of f(t) corresponds to
the division of Laplace transform of f(t) by s.
Example B-6 Find inverse Laplace transform of:
1
s(s2 + 1)
Inverse Laplace transform of:
11
1 1
2s + 5
− 3+ 2+ −
2 s 2s s 2(s2 + 2s − 4 )
Example B-5 Find inverse Laplace transform of:
s2
(s2 + a 2 )(s2 + b 2 )
1
−1 2 = sin t
s + 1
Therefore:
1
−1 2
=
s(s + 1)
Example B-7
Resolve into partial fractions:
s2
a2
b2
1
1
= 2 2 2 2− 2 2 2 2
2
2
2
2
(s + a )(s + b ) a − b s + a
a −b s +b
1
= 2 2
a −b
∫ e −st f ′(t )dt = e −st f (t )
In general:
n0 is the numerator with s = 0, and g0 is the denominator with
s = 0. n1 = 0 because the numerator does not have an s term, g1 is 2,
as the denominator has 2s term. n2 = 1 as numerator has s2 term,
etc. Substituting these values:
a2
b2
2 2 − 2 2
s
a
s
+
+b
Thus, we can write:
1
1 2 1
a sin at − b 2 sin bt
2
a
b
a −b
2
∞
∞
f ′(t ) =
We can write the following fractions:
A0 =
661
t
∫ sin t dt = [− cos t]0 = − cos t + 1
t
0
Find inverse Laplace transform of:
8
s 4 − 4 s2
−1
8
= 4 sinh 2t
(s2 − 4 )
−1
t
8
= 4 ∫ sinh 2t dt = 2[cosh 2t]0 = 2(cosh 2t − 1)
s(s2 − 4 )
0
t
−1
8
s2 (s2 − 4 )
t
=
∫ 2(cosh 2t − 1)dt = sinh 2t − 2t
0
662
APPENDIX B
Write the function as:
LAPLACE TRANSFORM OF tf (t )
B-4
If:
2a 2
s2
2a 2a 2
+ 2
1 −
s
s
2a −
[ f (t )] = F(s)
then:
[t n f (t )] = (− 1)n−1
dn
[F(s)]
ds n
(B-16)
Therefore the value at t = 0 is 2a.
B-7
The proof is not provided.
Example B-8 Find the Laplace transform of:
FINAL-VALUE THEOREM
When the Laplace transform is known, the corresponding function
can be found at t = ∝, by the final-value theorem:
te t sin 3t
f (∞) = lim s→ 0 sF(s)
(B-19)
We know that:
Example B-11 The final value of the function in Example B-10
2
is –1, because as s →0, function = − 2a2 = − 1.
2a
3
sin 3t = 2
s +9
[e t sin 3t] =
B-8
3
(s − 1)2 + 9
Then from Eq. (B-16):
(te t sin 3t ) =
B-5
d
3
3(2s − 2)
=
ds s2 − 2s + 10 (s2 − 2s + 10)2
d2 y
dy
− 4 + 4 y = 64 sin 2t
dt
dt 2
LAPLACE TRANSFORM OF (1/t ) f (t )
The initial conditions are Y(0) = 0, Y ′(0) = 1.
If:
[ f (t )] = F(s)
Step 1. Taking Laplace transform of both sides and considering the boundary conditions specified, we can write:
then:
∞
1
f (t ) =
t
∫ F(s)ds
(B-17)
s
(s − 2)2 y(s) = 1 +
sin 2t
t
sin 2t
=
t
=
∞
y(s) =
1
s
∫ s2 + 4 ds = 2 × 2 tan −1 2
2
s
∞
128
s2 + 4
128
s2 + 4
8
17
8s
+
+ 2
y(t ) = −1 −
2
s − 2 ( s − 2) s + 4
π
s
s
− tan −1 = cot −1
2
2
2
= − 8e 2t + 17te 2t + 8 cos 2t
When the Laplace transform is known, the corresponding time
function can be evaluated at t = 0, by the initial-value theorem:
f (0+ ) = lim s→ ∞ sF(s)
(B-18)
Example B-10 Find the value of function below at t = 0
2a(s2 − a )
(s − 2as + 2a 2 )
1
8
16
8s
−
+
+
(s − 2)2 s − 2 (s − 2)2 s2 + 4
Step 3. Apply inverse transform:
s
INITIAL-VALUE THEOREM
2
128
s2 + 4
Step 2. Resolving into partial fractions:
2
sin 2t = 2
s +4
B-6
[s2 y(s) − 4 sy(0) − Y ′(0)] − 4[sy(s) − Y (0)]+ 4 y(s) =
s2 y(s) − 1 − 4 sy(s) + 4 y(s) =
A proof is not provided.
Example B-9 Find the Laplace transform of:
SOLUTION OF DIFFERENTIAL EQUATIONS
Ordinary linear differential equations with constant coefficients can
be easily solved by the Laplace transform method, without finding
the general solution.
Example B-12 Solve the following differential equation with
Laplace transform:
This example illustrates the general method of solution of differential equations using Laplace transform.
B-9 SOLUTION OF SIMULTANEOUS
DIFFERENTIAL EQUATIONS
Solutions of two simultaneous differential equations can be obtained
using Laplace transform. We take the transform of the differential
equations, solve them like algebraic equations, eliminate variables
by substitution, and take inverse transform.
LAPLACE TRANSFORM
Example B-13 Solve the following differential equations:
dx
+ 4y = 0
dt
The value of the function becomes infinite as ε→0, that is, the area
of the rectangle shown in Fig. B-1b is unity. The unit impulse function is, therefore, defined as:
δ (t − a ) = ∞
dy
− 9x = 0
dt
and
For X(0) = 2 and Y(0) = 1. Taking Laplace transform:
∫
∞
t≠a
(B-23)
d (t – a)dt = 1
0
Laplace transform of unit-step function is given by:
∞
a +ε
sy(s) − Y (0) − 9 x(s) = 0
0
a
∫ f (t )δ (t − a )dt = ∫
1
f (t ) dt
ε
= (a + ε − a ) f (λ )
Substituting the values:
sx(s) − 2 + 4 y(s) = 0
1
ε
= f (λ )
sy(s) − 1 − 9 x(s) = 0
where:
λ >a
Therefore:
s + 18
s2 + 36
δ (t − a ) = 0
t=a
sx(s) − X(0) + 4 y(s) = 0
y(s) =
663
x( s ) =
2s − 4
s2 + 36
and
< a +ε
(B-24)
∞
∫ f (t )δ (t − a )dt = f (a ) as ε → 0
(B-25)
0
Taking inverse Laplace transforms:
B-12
2
x = − sin 6t + 2 cos 6t
3
y = cos 6t + 3 sin t
B-10
gt (T ) = u(t − t 0 ) − u(t − t 0 − T )
UNIT-STEP FUNCTION
The unit-step function is defined as:
u(t − a ) = 0
t<0
u(t − a ) = 1
t≥a
(B-20)
a≥0
∞
∫ e −st u(t − a )dt =
0
B-11
The function is shown in Fig. B-1c. It is rectangular pulse starting
at t0 and lasting for T. The function is useful in finding Laplace
transform of other functions.
B-13
See Fig. B-1a. Laplace transform of the unit function is given by:
[u(t − a )] =
GATE FUNCTION
A gate function can be created by two unit-step functions (Chap. 2)
and written as:
e −as
s
(B-21)
SECOND SHIFTING THEOREM
If:
[ f (t )] = F(s)
then:
[ f (t − a )u(t − a )] = e −as F(s)
IMPULSE FUNCTION
An impulse function is shown in Fig. B-1b. A large force acts for a short
time duration. The unit impulse function is the limiting function:
Consider the following functions:
f (t − t 0 )
1
δ (t − 1) =
a < t < a +ε
ε
= 0 otherwise
(B-22)
FIGURE B-1
(B-26)
f (t − t 0 )u(t )
f (t )u(t − t 0 )
f (t − t 0 )u(t − t 0 )
These are all different and the second shifting theorem applies only
to the last function.
(a) Step function, (b) impulse function, (c) gate function.
664
APPENDIX B
FIGURE B-2
Four different functions as marked as (a), (b), (c), and (d ).
Example B-14 Find the Laplace transform of the following
functions:
1. f (t − t 0 ) = sin ω (t − t 0 )
2. f (t − t 0 )u(t ) = sin ω (t − t 0 )u(t )
3. f (t )u(t − t 0 ) = sin ω t u(t − t 0 )
4. f (t − t 0 )u(t − t 0 ) = sin ω (t − t 0 ) u(t − t 0 )
These four functions are shown graphically in Fig. B-2a, b, c, and
d, respectively. The first and the second functions are different but
these have the same Laplace transform. A reader may decipher why
it is so. The Laplace transform is given by:
[sin ω (t − t 0 )] = [sin ω t cos ω t 0 − cos ω t sin ω t 0]
=
ω cos ω t 0 − s sin ω t 0
s2 + ω 2
The Laplace transform of (c) is:
∞
[sin ω t u(t − t 0 )] = ∫ (sin ω t )e −st dt
t0
ω cos ω t − s sin ω t
0
0
= e −t 0 s
s2 + ω 2
∞
=
1
∫ [e(−s+ jω )t − e(−s− jω )t ]dt
2j t
0
To find Laplace transform of the fourth function shown in Fig. B-2d,
apply second shifting theorem:
[sin ω (t − t 0 )u(t − t 0 )] = e −t0s (sin ω t )
ω
= e −t 0 s 2
s + ω2
Example B-15 Find the inverse transform of:
e −2 s
s2
This can be solved by second shifting theorem:
1
−1 2 = t
s
e −2s
−1 2 = (t − 2)u(t − 2)
s
This is zero for 0 < t < 2 and is t – 2 for t > 2, a step function.
A theorem of importance, which can be helpful in transient
solution when the excitation is a step function, is:
f (t )u(t − a ) = e −as [ f (t + a )]
(B-27)
The proof of this theorem is not provided. Its application is illustrated in the following example.
Example B-16 Consider that an LC circuit is excited by a step
voltage given by:
v(t ) = 1
0 < t <1
= 0 otherwise
It is required to find the current in the circuit. The differential
equation is:
d 2q q
+ = v(t )
dt 2 c
Consider = 1 H and C = 1F, then taking Laplace transform:
∞
s2q(s) − sQ(0) − Q′(0) + q(s) =
∫ v(t )e −st dt
0
Consider the initial conditions that Q(0) = Q′(0) = 0, We can write:
∞
1
q(s)(s2 + 1) =
∫ te −st dt + ∫ 0e −st dt
0
1
e −st
= t
−
−s 0
1
1
∫
0
e −st
dt
−s
LAPLACE TRANSFORM
This gives:
q(s) =
665
From Fig. B-3, we can write:
1 e −s e −s 1
− 2 + 2
−
s +1 s
s
s
2
Taking inverse Laplace transforms:
−e −s
e −s
1
q(t ) = −1 2
− −1 2 2
+ −1 2 2
+
1
1
s
s
s
s
(
)
(
)
+
+
s
(
s
1
)
From Table B-2, we can write:
1
2
=
s(s + 1)
−1
f1(t ) =
e
f 3 (t ) = − (t − T )u(t − T )
T
Thus, the Laplace transform is:
F(s) = F1(s) + F2 (s) + F3 (s)
=
∫ sin t dt = 1 − cos t
1
−1 2 2
= ∫ (1 − cos t )dt = t − sin t
s (s + 1) 0
t
Now from Eq. (B-27)
−e −s
−1 2
= −[1 − cos(t − 1)]u(t − 1)
s(s + 1)
e −s
−1 2 2
= [(t − 1) − sin(t − 1)]u(t − 1)
s (s + 1)
Thus, q(t) is given by:
e
[1 − (Ts + 1)e −Ts]
Ts2
We could arrive at the same result by using the function in Fig. B-1c.
The multiplication of a function with a gate function means that it will
have nonzero values only in the duration of the gate. Thus for the ramp,
we can write:
f (t ) =
e
e
tg(t ) = t[u(t ) − u(t − T )]
T
T
F(s) =
e
[ (tu(t )) − ((tu(t − T ))]
T
This gives the same result as before.
B-14
PERIODIC FUNCTIONS
If f (t) is a periodic function with period T, then the Laplace transform of f(t) is given by:
q = −[1 − cos(t − 1)]u(t − 1) −[(t − 1) − sin(t − 1)]u(t − 1)
Example B-17 Write the Laplace transform of the ramp function
shown in Fig. B-3a.
The function can be considered to consist of three components,
as shown in Fig. B-3b, c, and d. Then:
f (t ) = f1(t ) + f2 (t ) + f 3 (t )
e
Ts2
e
F2 (s) = − e −Ts
s
e
F3 (s) = − 2 e −Ts
Ts
F1(s) =
f2 (t ) = −eu(t − T )
t
0
e
tu(t )
T
T
[ f (t )] =
∫ e −st f (t )dt
0
(B-28)
1 − e −sT
The proof of Eq. (B-28) is not provided. We can also postulate
that:
■
The Laplace transform of a periodic function with period T is
equal to 1/(1 – e–Ts) times the Laplace transform of the first cycle.
Example B-18
Find the Laplace transform of the waveform
given by:
f (t ) = 2t
[ f (t )] =
0≤t ≤3
1
1 − e − 3s
3
∫ e −stt dt
0
=
te −st
e − st
1
− (1) 2
2
− 3 s −s
s 0
1− e
=
2 3e −st 1 − e −3s
+
s2
1 − e − 3 s −s
3
Periodicity occurs in dc rectifier circuits.
Example B-19 Find the Laplace transform of rectifier half-wave
shape, given by:
FIGURE B-3
(a) Ramp function. (b), (c), and (d ) Ramp function
decomposed into three functions.
f (t ) = sin ω t
=0
0 < t < π /ω
π / ω < t < 2π / ω
666
APPENDIX B
From Eq. (B-28)
[ f (t )] =
=
Then:
t
∫ f1( x ) f2 (t − x )dx = F1(s)F2 (S )
0
2 π /ω
∫
1
1 − e −2 π s /ω
e −st f (t )dt
0
2 π /ω
π /ω
− st
sin
dt
e −st × 0 dt
+
e
∫
−2 π s /ω ∫
1− e
0
π /ω
1
Integral eax sin bx is given by:
∫ e ax sin bx dx = e ax
or:
t
F1(s)F2 (s) = −1 ∫ f1( x ) f2 (t − x )dx
0
This can be proved as follows:
(a sin bx − b cos bx )
a 2 + b2
t
∫ f1( x ) f2 (t − x )dx
0
Therefore:
[ f (t )] =
π /ω
e −st (−s sin ω t − ω cos ω t )
−2 π s /ω
s2 + ω 2
1− e
0
1
=
∞
t
0
0
∫ e −st ∫ f1( x ) f2 (t − x )dx dt
∞ ∞
∞ t
=
Simplification of these yields:
∫ ∫ e −st f1( x ) f2(t − x )dx dt = ∫ ∫ e −st f1( x ) f2 (t − x )dt dx
0 0
ω
[ f (t )] = 2
(s + ω 2 )[1 − e −π s /ω ]
We could arrive the same result by using gate function. The Laplace
transform of the single half-sine cycle is first found.
f (t ) = (sin ω t )G(π /ω ) = (sin ω t )[u(t ) − u(t − π /ω )]
Therefore:
[ f (t )] = [sin ω tu(t )] − [sin ω t u(t − π /ω]
= F1(s) + F2 (s)
∞
0
x
∫ e −sx f1( x )dx ∫ e −s(t−x ) f2 (t − x )dt
∞
=
∫ e −sx f1( x )F2 (s)dx
0
∞
= ∫ e −sx f1( x )dx F2 (s) = F1(s)F2 (s)
0
Example B-20 Find the inverse Laplace transform of:
[cos at] =
ω
(1 + e −π s /ω )
s2 + ω 2
1
2
t
t
∫ cos[(a − b)x + bt] dx + 2 ∫ cos[(a + b)x − bt]dx
1
0
0
sin[(a − b) + bt] sin[(a + b)x − bt]
=
+
2(a − b) 0
2(a + b)
0
t
ω
1
1 − e − π s /ω s2 + ω 2
CONVOLUTION THEOREM
Let:
and
∫ cos ax cos b(t − x )dx
0
=
1 + e −π s /ω
ω
1 − e − 2 π s /ω s2 + ω 2
[ f1(t )] = F1(s)
s
s2 + b 2
t
=
The same result as arrived at before.
B-15
[cos bt] =
s2
−1 2 2 2 2
(s + a )(s + b )
Then from Eq. (B-28) Laplace transform of periodic half-wave
rectifier is:
=
s
s2 + a 2
Therefore from convolution theorem:
Combining for the half cycle, we can write:
F(s) =
a≠b
We know that:
ω
s2 + ω 2
ω
F2 (s) = 2
e − π s /ω
s + ω2
F(s) =
=
0 x
∞
s2
−1 2 2 2 2
(s + a )(s + b )
Solving, this gives:
F1(s) =
(B-29)
[ f2 (t )] = F2 (s)
=
t
a sin at − b sin bt
a 2 − b2
B-16 INVERSE LAPLACE TRANSFORM BY
RESIDUE METHOD
f(x) is the sum of residues of esxF(s) at poles of F(s). This will be
illustrated with an example:
LAPLACE TRANSFORM
667
If a factor e–s l, which may be called a convergence factor, is applied
to unilateral Fourier transform, we have:
Example B-21 Find the inverse Laplace transform of:
1
(s + 1)(s2 + 1)
∞
∞
∞
0
0
0
X(ω ) = ∫ [e −σ t f (t )]e − jω t dt =
We can write:
1
st
−1
= sum of residues of e F(s) at the poles
(s + 1)(s2 + 1)
∫ f (t )e −(σ + jω )t dt = ∫ f (t )e −st dt
(B-31)
where s = σ + jω . Then we can write Eq. (B-32) as:
∞
The poles are s = –1, s = + i, s = – i. Residue of estF(s) at s = –1
F(s) =
∫ f (t )e −st dt = f (t )
(B-32)
0
lim s→−1(s + 1)
e st
e −t
=
2
(s + 1)(s + 1) 2
Again by definition, the inverse Fourier transform of Eq. (B-31) is:
Similarly, residue of estF(s) at s = i:
lim s→i (s − i)
e −σ t f (t ) =
e st
e st
e it (1 + i)
= lim s→i
=−
(s + 1)(s + i)
4
(s + 1)(s2 + 1)
1
2π
∞
∫ X(ω )e jω t dω
(B-33)
−∞
or:
σ + jω
f (t ) =
and
lim s→−i (s + i)
e st
e −it (i − 1)
=
2
4
(s + 1)(s + 1)
Therefore, the required inverse is:
e −t e it (1 + i) e −it (i − 1) e −t e it + e −it i(e it − e −it )
−
+
=
−
−
2
4
4
2
4
4
=
e −t 1
1
− cos t + sin t
2 2
2
We could have obtained the same results by partial fraction method,
as before.
B-17 CORRESPONDENCE WITH
FOURIER TRANSFORM
We can arrive at some correspondence between Fourier transform
and Laplace transform. Many texts will show the Fourier transform
pair as:
−∞
X(ω ) =
∫ x(t )e − jω t dt
∞
1
x(t ) =
2π
(B-30)
∞
∫ X(ω )e
−∞
jω t
dω
1
∫ F(s)e st ds
2π j σ − j ω
(B-34)
The real part s should be large enough to make the integral converge. When the integral exists we say that the function is Laplace
transformable.
The Laplace transform method is extensively covered in the
mathematical texts and its applications to the electrical engineering transients. Yet, the limitations are that it is not suitable for computer-based applications of analysis of large power systems. Also,
nonlinearity and saturation cannot be taken into account; see App. G
for further discussions.
FURTHER READING
D. K. Cheng, Analysis of Linear Systems, Addison-Wesley Publishing
Company, Reading, MA, 1959.
R. A. DeCarlo and P. M Lin, Linear Circuit Analysis-Time Domain,
Phasor and Laplace Transform Approaches, 2d ed., Oxford University
Press, New York, 2001.
S. Goldman, Laplace Transform Theory and Electrical Transients,
Dover Publications, New York, 1966.
P. K. F. Kuhjittig, Introduction to Laplace Transform, Plenum Press,
New York, 1978.
M. B. Reed and G. B. Reed, Electrical Network Theory, Laplace Transform Technique, Scranton International Textbook Company, 1968.
M. G. Smith, Laplace Transform Theory, Van Nostrand, London/
New York, 1966.
This page intentionally left blank
APPENDIX C
Z-TRANSFORM
The role of z-transform in discrete system analysis is the same as that of
Laplace and Fourier transforms in continuous systems. Difference equations are based on discrete systems (Chaps. 2 and 3), and their analysis
is carried out by using z-transform. A signal in continuous-time system
can be sampled at small intervals (Fig. C-1). Then we can write:
f *(t ) = f (t )δT (t )
(C-1)
where the superscript * means that f(t) is a sampled discrete function. We can write it as f(k) and δT (t ) represents a periodic train of
unit impulses spaced T seconds apart. Thus for f(t) = 0, t < 0,
∞
f (k ) = ∑ f (nT )δ (t − nT )
(C-2)
n=0
(C-3)
Write:
(C-7)
The inverse Laplace transform:
{ f (k)} = Z −1[F(z )]
(C-8)
f (k ) = 0
=a
k<0
k
(C-9)
k≥0
Then from the definition of z-transform in Eq. (C-5):
z = e Ts
(C-4)
Then z-transform of a sequence {f(k)} is defined as:
Z[{f(k)}] = F(z) =
k=∞
∑
f (k)z −k
∞
F(z ) = ∑ a k z −k
(C-5)
F(z) is a polynomial in z. The z-transform exists only if the sum
given in Eq. (C-5) converges. z is an operator of z-transform, z is
a complex variable defined by m + ju (where m and u are real variables) and F(z) is the z-transform of {f(k)}. Consider a sequence:
f (k ) = {10, 7, 4, 1, − 1, 0, 3}
then
This converges only if:
az −1 < 1
F(z ) =
1
1 − az −1
1
3
F(z ) = 10z + 7 z + 4 z + 1 − + 0 + 3
z
z
(The as superscript of 1 denotes zero of the sequence.) Often, {f(k)}
2
is defined over equally spaced intervals of time 0, T, 2T, . . . , kT. The
dependence on T is usually suppressed and the variable arguments
T and kT are used interchangeably where there is no ambiguity.
z-transform is sometimes defined as the transformation:
(C-6)
| z | > |a |
| z | >| a |
(C-11)
The region of convergence in the complex plane is shown in Fig. C-2a.
Now consider the sequence:
f (k ) = −bk
3
(C-10)
k=0
k=−∞
z ≡ e sT
{ f (k)} = {..., f (− 2), f (− 1), f (0), f (1), f (2),...}
Now, consider the single-sided geometric sequence, denoted by its
k-th term as:
If we take the Laplace transform of Eq. (C-2):
∞
∞
[ f (k )] = ∑ f (nT )δ (t − nT ) = ∑ f (nT )e −nTs
n=0
n=0
which amounts to exponential change of variables between the
complex variable z = m + ju and the complex variable s = s + jw
in the Laplace transform domain, where T is the sample period of
the discrete-time system. This definition implies a sequence {f(k)}
or {f(kT)}, obtained by ideal sampling of a continuous signal f(t) at
uniformly spaced times kT, where k = 1, 2, . . . The z-transform of
a two-sided noncasual sequence is:
=0
k<0
k≥0
Then:
F(z ) =
k=−1
∞
k=−∞
k=1
∑ −bk z −k = ∑ −bk z −k
1
=
1 − bz −1
(C-12)
| z | < |b|
669
670
APPENDIX C
FIGURE C-1
(a) Function in time domain. (b) Function considered as sequence of impulses at sampled rate.
FIGURE C-2
Region of convergences and z-transforms.
This is shown in Fig. C-2b. If b = a, the two sequences have the
same z-transform, that is, these are not unique. It follows that if we
are dealing with single-sided sequences k ≥ 0, their z-transforms
are unique.
Consider now a two-sided sequence, if we consider that
| a| < | z | < | b|, then the region of convergence is shown in Fig. C-2c.
This region exists only if | b | > | a |. The transform does not exist if
| b| = | a | .
Discrete unit impulse. Consider a discrete unit impulse:
δ (k ) = 1
k=0
=0
k≠0
(C-13)
Z[u(k )]=
C-1
C-1-1
1
1 − z −1
(C-16)
PROPERTIES OF z-TRANSFORM
Linearity
If f(k) and g(k) can be added and a and b are constants, then:
Z {af (k ) + bg(k )} = aZ[{ f (k )}]+ bZ[{ f ( g )}]
Example C-1 The z-transform of the {f(k)} where:
Then:
Z[δ(k )] =
Then:
∞
∑ δ (k)z −k = 1
(C-14)
k=−∞
Discrete unit step.
u(k ) = 0
k<0
=1
k≥0
f (k ) =
4k
k<0
2k
k≥0
can be written as:
(C-15)
Z[{ f (k )}]=
k=− 1
k=∞
k=−∞
k=0
∑ 4 k z −k + ∑ 2 k z − k
(C-17)
Z-TRANSFORM
This is applicable to two-sided sequence. The proof is not provided.
For one-sided sequences:
Example C-2 Find z-transform of:
sin(k +1)
f (k + n )u(k ) ↔ z n[F(z ) − f (0) − z −1 f (1) − z −( n−1) f (n − 1)]
k=∞
k=∞
k=0
k=0
F(z ) = ∑ sin(k + 1)z −k = ∑
e
i(k+1)
−e
2i
−(k+1)
f (k − n )u(k − n ) ↔ z −n F(z )
z −k
k=∞
Z[{ f (k − 1)}] = z −1F(z )
as
f (− 1) = 0
Z[{ f (k + 1)}] = zF(z ) − zf (0)
Z[{ f (k + 2)}] = z 2 F(z ) − z 2 f (0) − zf (1)
k=∞
1 i
1
e ∑ (e i z −1 )k − e −i ∑ (e −i z −1 )k
2i k=0
2i k=0
C-1-5
1
= e i[1 + (e i z −1 ) + (e i z −1 )2 + ]
2i
−
=
then:
Z[{kf (k)}] = −z
1
1
e −i
ei
−
i
−
1
2i 1 − e z
2i 1 − e −i z −1
d
Z[{k n f (k )}] = −z F(z )
dz
Z[{1}] =
d
(1 − z −1 )−1
dz
1
= z(1 − z −1 )2 2 = z −1(1 − z −1 )−2
z
Z[{k}] = −z
Change of Scale
If Z[{f(k)}] = F(z) then:
C-1-6
(C-19)
z
f (k )
Z
= − ∫ z −1F(z )dz
k
k≥0
C-2
z sin b
Z(sin bk ) = 2
z − 2z cos b + 1
(C-26)
INITIAL-VALUE THEOREM
For one-sided sequences, if:
Z[{ f (k )}] = F(z )
Then, from Eq. (C-19)
k≥0
then:
f (0) = Limz →∞ F(z )
( Z /a ) sin b
(z /a )2 −[2(z /a )]cos b + 1
The proof of Eq. (C-27) is not provided.
The z- transform of
az sin b
z 2 − 2az cos a + a 2
Example C-4
k
z
1
=
z
−
2
1/ 2
Shifting Property
If:
Z[{ f (k )}] = F(z ),
Then from the initial value theorem in Eq. (C-27)
then:
Z[{ f (k ± n )}] = Z ±n F(z )
Division by k
If:
then:
We know that:
C-1-4
(C-25)
Z[{ f (k )}] = F(z )
Proof of Eq. (C-19) is not provided.
Example C-3 Find z- transform of:
=
1
1 − z −1
From Eq. (C-23):
(C-18)
The proof is not provided.
Z[a k sin bk] =
(C-24)
Thus, if f(k) = 1 then we know that:
If {f(k)} = F(z) and {g(k)} = G(z) and a and b are constants then:
a k sin bk
(C-23)
n
Theorem
z
Z[{a k f (k )}]= F
a
d
F(z )
dz
In general:
z 2 sin 1 − z sin 2
F(z ) = 2
z − 2z cos1 + 1
C-1-3
Multiplication by k
Z[{ f (k )}] = F(z )
1 −i
e [1 + (e −i z −1 ) + (e −i z −1 )2 + ]
2i
Z −1[aF(z ) + bG(z )] = aZ −1[F(z )]+ bZ −1[G(z )]
(C-22)
If:
This on further simplification gives:
C-1-2
(C-21)
It follows that for the casual sequence:
k=∞
k=∞
1
1
= ∑ e i(k+1)z −k − ∑ e −i(k+1)z −k
2i k=0
2i k=0
=
671
(C-20)
z
lim z →∞
=1
z − 1/ 2
(C-27)
672
C-3
APPENDIX C
We know that:
FINAL-VALUE THEOREM
The final-value theorem is given by:
lim k→∞ f (k ) = lim z →1(z − 1)F(z )
Z[{3k}] = [1 + 3z −1 + 32 z −2 + 33 z −3 + ] =
(C-28)
Provided the limit exits; that is, the sequence has a final value. For
the final value theorem to be applicable F(z) should not have poles
outside the unit circle. The proof of Eq. (C-28) is not provided.
Example C-5 Find the final value of the sequence:
[1 − (1/ 4 )k ]
The z-transform of the sequence is:
Z [{ f (k )}] = Z [{3k}{4k}] =
= lim z →1
z(z − 1)
4 z 2 − 5z + 1
= lim z →1
z(z − 1)
= 4/3
(z − 1)(z − 1/ 4 )
■
Direct division
■
Binomial expansion and partial fractions
■
Residue method
Example C-7 Find inverse z-transform of:
2z
z −a
Z[{ f (k )}] = F(z ),
then:
(C-29)
The proof of Eq. (C-29) is not provided.
2z
2z
=
z −a z
If there are two sequences,
{ f (k )} and {g(k )},
a
= 2 1 −
a
z
1−
z
1
−1
= 2 + 2az −1 + 2a 2 z −2 + + 2a k z −k
then their convolution:
= {2a k}z −k
{h(k )} = { f (k )} {g(k )}
*
(C-30)
Consider casual sequences:
F(z ) = { f (0) + f (1)z + f (2)z
−2
+ }
= g(2)z
−2
+ }
−1
−1
then:
F(z )G(z ) = f (0)g(0) + { f (1)g(0) + f (0)g(1)}z −1
+ { f (0)g(2) + f (1)g(1) + f (2)g(0)}z −2 +
= h(0) + h(1)z −1 + h(2)z −2 +
= Z{h(k )} = z{ f (k )}*{g(k )}
Example C-6 Find the z-transform of the sequence:
k=0
| z | <| a |
and
a a2
= 2 1 + + 2 +
z z
CONVOLUTION
k=0
| z | >| a |
We will use binomial expansion:
k
F(z )
Z ∑ f (n ) =
−1
n→−∞
1 − z
k=∞
(C-31)
The inverse z-transform can only be settled if the region of convergence is given. The inverse transform can be found by:
If:
k=∞
INVERSE z-TRANSFORM
Z −1F(z ) = { f (k )}
PARTIAL SUM
{ f (k)} = ∑ 3k ∑ 4k
1
(1 − 3z −1 )(1 − 4 z −1 )
The sequence {f(k)} can be found from F(z) and is defined as the
inverse z-transform:
k
(1/ 4 )z
1
lim z →∞ 1 − = lim z →1(z − 1) 2
4
z − (5z / 4 ) + (1/ 4 )
G(z ) = {g(0) + g(1)z
1
1 − 4 Z −1
Then from Eq. (C-30):
C-6
Thus, from Eq. (C-28):
C-5
Z[{4k}] = [1 + 4 z −1 + 4 2 z −2 + 4 3 z −3 + ] =
Table C-1 provides z transforms of some important sequences.
(1/ 4 )z
z 2 − (5z / 4 ) + (1/ 4 )
C-4
1
1 − 3Z − 1
Thus:
2z
Z −1
= [2a k ]
z − a
For | z | < | a | :
− 2z
2z
2z
1
2z
[1 − (z /a )]−1
=−
=−
=
z −a
a−z
a [1 − (z /a )]
a
=−
2z z z 2
1 + + 2 +
a a a
=−
2z 2z 2 2z 3
− 2 − 3 −
a
a
a
Therefore:
1
1 1
{ f (k )} = , − 3 , − 2 , −
a
a
a
Z-TRANSFORM
TA B L E C - 1
z-Transform of Some Important Sequences
SEQUENCE K ê 0
Z-TRANSFORM
[f ( k )]
F (z )
δ(k )
1
u (k) or 1
( 1 − z − 1 )− 1
k
−z
d
( 1 − z − 1 )− 1
dz
|z | >1
kn
d
−z ( 1 − z −1 )−1
dz
|z | >1
ak
( 1 − az −1 )−1
|z | > |a |
( k + 1)( k + 2 )( k + n − 1) k
a
( n − 1)!
zn
( z − a )n
|z | > a , k ≥ 0, n ≥ 2
k
z −n ( 1 − z −1 )−( n +1)
|z | >1
( 1 − az −1 )−( n +1)
|z | > |z |
Ck
( 1 − z −1 )n
0 ≤ k ≤ n , |z | > 0
n k
k a
d
−z ( 1 − az −1 )−1
dz
|z | < |a |
ak
( 1 − a 2 )( 1 − az )( 1 − az −1 )−1
|a | < |z | <
sin αk
z sin α
z 2 − 2z cos α + 1
k ≥0
c k sin αk
cz sin α
z 2 − 2cz cos α + c 2
k ≥0
cosαk
z 2 − z cosα
z 2 − 2z cosα + 1
k ≥0
c k cos αk
z 2 − cz cos α
z − 2cz cos α + c 2
k ≥0
cosh αk
z 2 − z cosh α
z 2 − 2z cosh α + 1
k ≥0
c k cosh αk
z 2 − cz cosh α
z − 2cz cosh α + c 2
k ≥0
sinh αk
z sinh α
z 2 − 2z cosh α + 1
k ≥0
c k sinh αk
cz sinh α
z 2 − 2cz cosh α + c
k ≥0
CONDITIONS
n
Cn
k +n
n
C na k
n
2
2
1
|a |
673
674
APPENDIX C
C-7
INVERSION BY PARTIAL FRACTIONS
Assuming that F(z) is a rational function in z:
F(z ) =
bm z m + bm−1z m−1 + + b0
z n + a n−1z n−1 + + a 0
m≤n
(C-32)
The inverse z-transformer can be obtained by partial fractions.
For m = n, divide numerator by denominator to separate out the
constant term:
F(z ) = a +
N(z )
D(z )
(C-33)
Now, the polynomial N(z) is one order less than D(z). Thus, for m < n
N(z )
F(z ) =
(z − p1 )(z − p2 )(z − p n )
(C-34)
Cn
C1
C2
=
+
++
z − p1 z − p2
z − pn
Mz 2 + Nz Mz(z − c cos α ) +[(Mc cos α + N )/(c sin α )](cz sin α )
=
z 2 + pz + q
z 2 − 2cz cos α + c2
(C-42)
Mz 2 + Nz
Mc cos α + N k
Z −1 2
= M[ck cos α]+
[c sin αk]
c sin α
z + pz + q
(C-43)
Similarly for
Example C-8 Find inverse z-transform of:
z
1
Z −1
= {a k}
= Z −1
1 − az −1
z − a
z
z /a
Z −1
= {−a k}
= −Z −1
1 − z /a
z − a
| z | > |a |
z 2 + 3z
z + z + 1/ 9
(C-35)
| z | < |a |
(C-36)
2
1
9
c = ± 1/ 3
p =1
For c = –1/3:
|z | > b
p
= 3/ 2 > 1
2c
z
zr
Z −1
= Z − 1 z −(r −1)
−
z
b
r
(
)
− b)r
z
(
1 = 2c cosh α
(k + 2 − r )(k + 3 − r )ku(k − r + 1)b(k−r+1)
(r − 1)!
cosh α = 3 / 2
r ≥ 2 | z | >|b |
sinh α = 5 / 2
(C-37)
z
(k + 2 − r )(k + 3 − r )kb(k−r+1)
Z−1
u(−k − r − 1)
=−
(r − 1)!
(z − b)r
| z | <|b |
(C-38)
3. Quadratic nonrepeated factor. Let the factor be:
Mz + N
z 2 + pz + q
(∴ cosh 2 α − sinh 2 α = 1)
From Eq. (C-42):
z 2 + 3z
z(z − c cosh α ) +[(c cosh α + 3)/(c sinh α )](cz sinh α )
=
z + z + 1/ 9
z 2 − 2cz cosh α + c2
2
Substituting the numerical values and simplifying:
(C-39)
Compare Eq. (C-39) with:
Z[(ck cos αk )] =
z > 1/ 3
Here:
q = c2 =
2. Linear repeated factor. Let the repeated factor be:
=
p
= cosh α > 1
2c
p = 2c cosh α
c2 = q
1. Linear nonrepeated factor.
r≥2
p
> 1:
2c
Mz 2 + Nz
Mc cosh α + N k
Z −1 2
= M[ck cosh α]+
[c sinh αk]
z
pz
q
+
+
c sinh α
(C-44)
where:
where p1, p2,. . . , pn are the poles of F(z).
z
(z − b)r
p
< 1:
2c
For
z 2 + 3z
z(z − c cosh α )
15
cz sinh α
= 2
−
2
2
z + z + 1/ 9 z − 2cz cosh α + c
5 z − 2cz cosh α + c
2
Therefore:
z 2 − cz cos α
z 2 − 2cz cos α + c2
(C-40)
1
z 2 + 3z
15 1
= − cosh αk −
− sinh α
z + z + 1/ 9 3
5 3
k
Z −1
k
2
k≥0
Or compare with:
Z[(ck cosh αk )] =
z 2 − cz cosh α
z 2 − 2cz cosh α + c2
(C-41)
where:
c2 = q
p = − 2c cos α
p
= cos α
− 2c
p
=< 1
− 2c
or
or
= 2c cosh α
>1
C-8
INVERSION BY RESIDUE METHOD
The residue theorem states that:
f (k ) = ∑ residues of z k−1F(z )
at its poles
(C-45)
where the residue of a simple pole zi is:
[(z − z i )z k−1F(z )]z =z
i
(C-46)
Z-TRANSFORM
TA B L E C - 2
675
Inverse z-Transforms
INVERSE Z-TRANSFORM
Ãz à > ÃaÃ, k > 0
Ãz à < ÃaÃ, k < 0
z
z −a
a ku(k )
−a k u ( k )
z2
( z − a )2
( k +1)a k
−( k + 1)a k
z3
( z − a )3
1
( k + 1)( k + 2 )a k u ( k )
2!
1
( k + 1)( k + 2 )a k u ( k )( −k + 2 )
2!
zn
( z − a )n
1
( k + 1)....( k + n − 1)a k u ( k )
( n − 1)!
−
1
z −a
a k −1u ( k − 1)
−a k −1u ( −k )
1
( z − a )3
1
( k − 2 )( k − 1)a k −3u ( k − 3 )
2
1
− ( k − 2 )( k − 1)a k −3u ( −k + 2 )
2
PARTIAL FRACTION
The residue of a pole is its coefficient in the partial fraction expansion. For repeated poles, order r, at pole z = zi is:
1
d r −1
(z − z i )r z k−1F(z )
−
r
1
(r − 1)! dz
z =z
(C-47)
1
( k + 1)....( k + n − 1)a k
( n − 1)!
Coefficients, which may be negative are assumed to be constants. The
functions may be defined only at t = nT, where n = 0, 1, 2, . . . . It is of
second-order as it contains an ordinate x(t +2T) and is linear as it does
not contain powers, except first powers. If T = 1, the equation becomes:
x(n + 2) + a1 x(n + 1) + a 0 x(n ) = e(n )
i
Example C-9 Find inverse z-transform of:
(C-49)
The classical method of solving difference equations is akin to
differential equations, the complementary function, and particular
integral.
In Chap. 1, we stated that the origin of electromagnetic transient
analysis program (EMTP), which has become the most important analytical tool for simulation of electrical system transients all over the
world, started with a paper by H.W. Dommel published in 1969.1
The paper proposed digital solution of electromagnetic transients
based on difference equations.
Example C-10 Solve the difference equation:
z
Z
(z − 2)(z − 3)
−1
Residue at z = 2 is given by:
z
k−1
k
(z − 2)z
= −2
(z − 2)(z − 3) z =2
Residue at z = 3:
z
k−1
k
(z − 3)z
=3
(z − 2)(z − 3) z =3
yk+3 − 3 yk+2 + 3 yk+1 − yk = u(k )
Take z-transform of both the sides:
Thus, the required inverse is sum of the residues:
Z[ yk+3] − 3Z[ yk+2]+ 3Z[ yk+1] − Z[ yk ] = Z[u(k )] = [z 3Y (z ) − z 3Y (0)
3k − 2k
Table C-2 provide inverse z-transforms.
− z 2Y (1) − zY (2)] − 3[z 2Y (z ) − z 2Y (0) − zY (1)]+ 3[3Y (z )
C-9
− zY (0)] − Y (z ) =
SOLUTION OF DIFFERENCE EQUATIONS
Difference equations arise in electrical engineering when there is a
recurrence in system configurations. As an example, an electrical
network consisting of a chain of identical components—a combination of series and shunt impedances as in transmission lines—is
best analyzed by difference equations. While the differential equations contain derivatives of the dependent variable, difference equations contain differences of values of the dependent variables at
discrete equally spaced values of the independent variable. Following is an example of second-order linear difference equation:
x(t + 2T ) + a1 x(t + T ) + a 0 x(t ) = e(t )
(C-48)
1
1 − z −1
Consider the initial conditions that Y(0) = Y(1) = Y(2) = 0. Then
substituting and simplifying:
[z 3 − 3z 2 + 3z − 1]Y (z ) =
1
1 − z −1
(z − 1)3 Y (z ) =
1
1 − z −1
Y (z ) = z −3 (1 − z −1 )4
676
APPENDIX C
Therefore:
Here, we have:
yk = Coefficient of z
−k
in z
(k − 2)(k − 1)k
6
= z (1 − z )
−3
−1 −4
A=
in z −k−3 = (1 − z −1 )−4
= Coefficient of z −k
yk =
−3
0
1
6
−
1
5
6
B= 0
1
−
x(k ) =
x1(k )
x 2 (k )
x(0) = 0
1
(C-59)
k≥3
Therefore:
C-10
STATE VARIABLE FORM
Akin to differential equations, it is often desirable to describe a system with a set of first-order difference equations, rather than by
one or more nth-order difference equations. Consider an nth-order,
single-input, linear, and constant-coefficient difference equation:
z
zI − A = 1
6
n
∑ ai y(k + i) = u(k)
(C-50)
i=0
(zI − A )−1 =
This can be replaced with:
x1(k + 1) = x 2 (k )
1
5
1
z2 + z +
6
6
5
6
1
−
6
z+
(C-60)
1
z
This gives:
x 2 (k + 1) = x 3 (k )
(C-51)
x n (k + 1) = −
−1
5
z+
6
n−1
1
1
∑ a i x i+1(k ) + u(k )
a n i=0
a n
or in the matrix form:
x1(k + 1)
0
1
x 2 (k + 1)
0
0
=
.
.
.
x n (k + 1)
−a 0 /a n −a1 /a n
0
1
.
.
x1(k )
0
0
.
x 2 (k )
0
0
.
+
u
.
.
1
.
. −a n−1 /a n x n (k ) 1/a n
z
z
2 5
1
5
1
(z − 1)z + z +
z2 + z +
6
6
6
6 +
X(z ) =
2
z
z
2 5
5
1
1
2
z + z+
(z − 1)z + z +
6
6
6
6
The first term is the free response and the second term is the forced
response:
x(k ) =
x(k + 1) = Ax(k ) = b u
(C-53)
1
3 1
1
− 2 − + −
2 3
2
2
k
1
1
3 1
− 2 − + −
2
2 3
2
k
k
(C-52)
or:
(C-61)
k
k = 0, 1, 2,...
(C-62)
Consider the solution of the difference equation:
x(k + 2) +
5
1
x(k + 1) + x(k ) = u(k )
6
6
(C-54)
In the state variable form, the equation can be written as:
x1(k + 1) = x 2 (k )
5
1
x 2 (k + 1) = − x 2 (k ) − x1(k ) + u(k )
6
6
(C-55)
Consider the state form of the difference equation for multi-input,
multi-output systems, a modification of Eq. (C-53). See also Chap. 2.
x(k + 1) = Ax(k ) + Br(k )
(state equation )
(C-56)
Consider r(k) = 1. The z-transform of the vector-matrix form of the
equation is:
z X(z ) − z x(0) = AX(z ) +
z
B
z −1
(C-57)
X(z ) = z(zI − A )−1 x(0) +
z
(zI − A )−1 B
z −1
(C-58)
or:
REFERENCES
J. A. Cadzow and H. R. Martens, Discrete Time Control Systems,
Prentice Hall, Englewood Cliffs, NJ, 1970.
H. W. Dommel, “Digital Computer Solution of Electromagnetic
Transients in Single- and Multiphase Networks,” IEEE Trans. PAS,
vol. PAS-88, no. 4, pp. 388–399, Apr. 1969.
S. Goldberg, Difference Equations, Wiley, New York, 1958.
W. D. Humpage, z-Transform Electromagnetic Transient Analysis in
High Voltage Networks, Peter Peregrinus (IEE-UK), 1982.
E. I. Jury, Theory and Application of z-transform Method, Wiley, New
York, 1964.
B. C. Kuo, Discrete Data Control Systems, Science Tech., Champaign,
IL, 1974.
E. J. Muth, Transform Methods with Applications to Engineering and
Operations Research, Prentice Hall, Englewood Cliffs, NJ, 1977.
I. J. Nagrath and M. Gopal, Systems Modeling and Analysis, Tata
McGraw Hill, New Delhi.
R. Vich, z-Transform Theory and Application, Kluwar Academic,
New York, 1987.
APPENDIX D
SEQUENCE IMPEDANCES
OF TRANSMISSION LINES
AND CABLES
The concept of symmetrical components is basic to the understanding of transformation of sequence impedances. It is assumed that a
reader has some knowledge of this subject, which is covered in many
texts.1–4 Also, a fair knowledge of matrix manipulation is assumed.
Practically, the transmission or cable systems constants will be
calculated using computer-based subroutines in EMTP-like programs which provide evaluation routines for low-to-high frequency
models. Some data is available in tabular form in the texts.5–8 The
basis of these calculations and required transformations is of interest for system modeling, fault studies, and transients analyses, and
to formulate a theoretical base.
D-1
AC RESISTANCE OF CONDUCTORS
The conductor ac resistance is dependent on frequency and proximity effects, temperature, and bundle conductor effects. Spiraling
of conductors with a certain pitch increases the length of wound
conductor. The resistance increases linearly with temperature and
is given by the following equation:
T + t
2
R 2 = R1
T + t1
(D-1)
where R2 is the resistance at temperature t2 and R1 is the resistance
at temperature t1. T is the temperature coefficient which depends
on the conductor material. It is 234.5 for annealed copper, 241.5
for hard drawn copper, and 228.1 for aluminum. The resistance is
read from manufacturer’s data, databases in computer programs, or
generalized tables.
The skin effect considers that as the frequency increases, the
current distribution in the cross section of the conductor will not
be uniform. The current tends to flow more densely near the outer
surface of the conductor than toward the center. This is because an
ac flux results in induced emfs which are greater at the center than
at the circumference, so that potential difference tends to establish
currents that oppose the main current at the center and assist the
current at the circumference. The result is that the current is forced
to the outside, reducing the effective area of the conductor. The
effect is utilized in high-ampacity hollow conductors and tubular
bus bars, to save material costs. The skin effect is given by:
Ycs = F( x s )
(D-2)
where Ycs are the skin effect losses in the conductor and F(xs) is a
skin effect function:
x s = 0 . 875 f
ks
R dc
(D-3)
where ks depends on conductor construction, and f is the frequency.
Proximity effect is also considered in cables. This occurs because
of distortion of current between two conductors in close proximity.
The concentration of current occurs in parts of bus bars or conductors
closest to each other (currents flowing in forward and return paths).
The expressions and graphs for calculating proximity effect are given
in Ref. 9.
Thus, we can write the following equation describing the ac and
dc resistance of the conductor, considering both—the skin effect as
well as proximity effect.
R ac /R dc = 1 + Ycs + Ycp
(D-4)
The internal inductance and resistance ac to dc ratios using Bessel’s functions is provided in Ref. 10. The internal impedance of conductors is comparatively small. Its frequency-dependent behavior
can be simulated by dividing the conductor into n hollow cylinders
with an internal reactance L and conductivity Gr = 1/Rr. This model
can be replicated by an equivalent circuit consisting of a series of connections of hollow cylinders (Fig. D-1).11 The values of Lr and Gr for
each cylinder can be calculated, depending upon radius rr .
r
rr = rn
n
m
(D-5)
A good approximation of real R(f) and X(f) curves can be achieved
by varying the exponent m. For example, with n = 5 and m = 0.15,
677
678
APPENDIX D
where D is any point at a distance D from the surface of the conductor and r is the conductor radius. In most inductance tables, D = 1 ft
and adjustment factors are tabulated for higher conductor spacing.
The total reactance is:
L=
µ 0 1
D µ0
D µ0
D
+ ln =
ln
H/m
ln
=
r 2π e −1/ 4r 2π GMR
2π 4
(D-9)
where GMR is called the geometric mean radius and is equal to
0.7788r. It can be defined as the radius of a tubular conductor with
an infinitesimally thin wall that has the same external flux out to a
radius of 1 ft as the external and internal flux of a solid conductor
to the same distance.
D-2-1
Inductance of a Three-Phase Line
We can write the inductance matrix of a three-phase line in terms
of flux linkages l a, l b, and l c:
Laa
λa
λb = Lba
λc
Lca
Lab
Lbb
Lcb
Lac
Lbc
Lcc
Ia
Ib
Ic
(D-10)
The flux linkages l a, l b, and l c are given by:
F I G U R E D - 1 (a) Conductor divided into concentric cylinders.
(b) Equivalent circuit. (c) Simulation results of internal resistance and
reactance, actual versus equivalent circuit.
a good agreement of the equivalent circuit with real performance of
conductor up to 100 kHz is achieved.
R = R int =
ρl
π rn2
X = 2π f L int = 2π f
R = R int
f
fx
X = 2π f L int
µl
8π
f
fx
(henry per meter)
µ0 D
ln H/m
2π r
1
1
1
I a ln
+ I c ln
+ I b ln
Dbc
Dba
GMR b
λc =
µ0
2π
1
1
1
I a ln
+ I b ln + I c ln
GMR c
Dca
Dcb
(D-11)
where Dab, Dac, . . . are the distances between conductor of a phase
with respect to conductors of b and c phases. Laa, Lbb, and Lcc are the
self-inductance of the conductors and Lab, Lac, . . . are the mutual
inductances. If we assume a symmetrical line, that is, GMR of all
three conductors is equal and also the spacing between the conductors is equal, the equivalent inductance per phase is:
L=
µ0 D
ln
H/m
2π GMR
(D-12)
D-3
(D-7)
where m0 is the permeability = 4p10–7(H/m). Its external inductance
is due to flux outside the conductor and is given by:
Lext =
µ0
2π
for f >> f x
INDUCTANCE OF TRANSMISSION LINES
µ0
H/m
8π
λb =
The phase-to-neutral inductance of a tree-phase symmetrical line is
the same as the inductance/conductor of a two-phase line.
The internal inductance of a solid, smooth, round metallic cylinder
of infinite length is due to its internal magnetic field when carrying
an alternating current and is given by:
L int =
1
1
1
µ0
I a ln
+ I c ln
+ I b ln
2π
GMR a
Dac
Dab
for f << f x
(D-6)
D-2
λa =
(D-8)
TRANSPOSED LINE
A transposed line is shown in Fig. D-2. Each phase conductor occupies the position of other two phase conductors for one-third length
of the length. The purpose is to equalize the phase inductances and
reduce unbalance. The inductance derived for symmetrical line is
still valid and the distance D in Eq. (D-8) is substituted by the geometric mean distance (GMD). It is given by:
GMD = ( Dab Dbc Dca )1/ 3
(D-13)
For a mathematical relation, consider a rotation matrix R, given by:
0 0 1
R= 1 0 0
0 1 0
(D-14)
It can be demonstrated that premultiplying by R will move the
third row in a 3 × 3 impedance matrix to row 1; postmultiplying
SEQUENCE IMPEDANCES OF TRANSMISSION LINES AND CABLES
FIGURE D-2
Transposed transmission line.
by R −1 will move the third column to position 1; premultiplying by
R −1 = R 2 will move the first row to the position of the third row;
postmultiplying by R will move the first column to position 3. These
manipulations can be used to compute the overall impedance of a
transposed line. Figure D-2 shows a transposed line in three sections. In the first section, we can write:
Va1
Z11−1
Vb1 = Z21−1
Z 31−1
Vc1
Z12−1
Z22−1
Z 32−2
Z13−1
Z23−1
Z 33−1
I a1
I b1
I c1
(D-15)
(D-16)
In the second section, phases c-a-b correspond to positions a-b-c
of the first section. Therefore, the following transformation applies:
R −1V123 = R −1Z123−1R R −1I123
which is the same as:
V231 = Z231−2I 231
(D-17)
In the third section, phases b-c-a, correspond to the phases a-b-c
in the first section. Thus, the following transformation applies:
R V123 = R Z123−1R −1 R I123
(D-18)
V312 = Z 312−3I 312
Then the overall impedance matrix of the line is:
( Z11−1 + Z22−2 + Z 33−3 ) ( Z12−1 + Z23−2 + Z 31−3 ) ( Z13−1 + Z21−2 + Z 32−3 )
Z = ( Z21−1 + Z 32−2 + Z13−3 ) ( Z22−1 + Z 33−2 + Z11−3 ) ( Z23−1 + Z 31−2 + Z12−3 )
( Z 31−1 + Z12−2 + Z23−3 ) ( Z 32−1 + Z13−2 + Z21−3 ) ( Z 33−1 + Z11−2 + Z22−3 )
(D-19)
Example D-1 Consider a transposed line with three equal sections,
though practically, it will not be possible to transpose exactly in three
sections. Moreover, the utilities are getting away from transposition of
the high-voltage lines.
Consider:
Z12 = Z21 = Z23 = Z 32 = 0 . 1 + j1 . 0
Z13 = Z 31 = 0 . 1 + j1 . 2
0 . 2 + j2 . 0 0 . 1 + j1 . 0 0 . 1 + j1 . 2
Z123 = 0 . 1 + j1 . 0 0 . 2 + j2 . 0 0 .1
1 + j1 . 0
0 . 1 + j1 . 2 0 . 1 + j1 . 0 0 . 2 + j2 . 0
Then, for the second section,
0 . 2 + j2 . 0 0 . 1 + j1 . 0 0 . 1 + j1 . 0
Z231 = R −1Z123R = 0 . 1 + j1 . 0 0 . 2 + j2 . 0 0 . 1 + j1 . 2
0 . 1 + j1 . 0 0 . 1 + j1 . 2 0 . 2 + j1 . 2
0 . 2 + j2 . 0 0 . 1 + j1 . 2 0 . 1 + j1 . 0
Z 312 = R Z123R −1 = 0 . 1 + j1 . 2 0 . 2 + j2 . 0 0 . 1 + j1 . 0
0 . 1 + j1 . 0 0 . 1 + j1 . 0 0 . 2 + j2 . 0
The sum of the three sections [Eq. (D.19)] is:
0 . 6 + j6 . 0 0 . 3 + j3 . 2 0 . 3 + j3 . 2
Z = 0 . 3 + j3 . 2 0 . 6 + j6 . 0 0 . 3 + j3 . 2
0 . 3 + j3 . 2 0 . 3 + j3 . 2 0 . 6 + j6 . 0
All the mutual impedances are exactly balanced. This can be decoupled
to a diagonal matrix with symmetrical component transformation.
D-4
COMPOSITE CONDUCTORS
A transmission line with composite conductors is shown in Fig. D-3.
Consider that group X is composed of n conductors in parallel, each
of which carries 1/n of the line current, and the group Y is composed
of m parallel conductors, each of which carries –1/m of the return
current. Then Lx, the inductance of conductor group X is:
which is the same as:
Z11 = Z22 = Z 33 = 0 . 2 + j2 . 0
Then for the first section:
Similarly,
or in compact form:
Vabc−1 = Z123−1 Iabc−1
679
L x = 2 × 10−7 ln
nm ( D
n2
aa
Dab Dac ... Dam ),...,( Dna Dnb Dnc ... D n m )
( Daa Dab Dac ... Dan ),...,( D na D nb Dnc ... Dnn )
(D-20)
We write Eq. (D-20) as:
D
L x = 2 × 10−7 ln m H/m
D sx
(D-21)
The term Dm abbreviated for numerator of Eq. (D-20) can be called
mutual GMD and denominator GMR.
Similarly:
D
L y = 2 × 10−7 ln m H/m
Dsy
(D-22)
680
APPENDIX D
Generally, for transmission lines, the off-diagonal elements of the
sequence impedance matrix are zero. In high-voltage transmission
lines which are transposed, this is generally true and the mutual couplings between phases are almost equal. However, the same cannot
be said of distribution lines, and these may have unequal off-diagonal
terms. In many cases the off-diagonal terms are smaller than the diagonal terms, and the errors introduced in ignoring these will be small.
Sometimes equivalence can be drawn by the equations:
Zaa + Zbb + Zcc
3
Zab + Zbc + Zca
Zm =
3
Zs =
(D-28)
that is, an average of the self-and mutual impedances can be taken.
The sequence impedance matrix then has only diagonal terms. See
Example D-2.
D-6 THREE-PHASE LINE WITH
GROUND CONDUCTORS
FIGURE D-3
Inductance of composite conductors.
The total inductance is:
L = ( L x + L y ) H/m
D-5
(D-23)
Consider a symmetrical three-phase line with 3 × 3 matrix having
equal self-impedances and mutual impedances:
Z M M
Zabc = M Z M
M M Z
(D-24)
It can be diagonalized (decoupled) with symmetrical components:
Z012 = Ts−1ZabcTs
1
1 1
a a 2 Zabc 1
1
a2 a
1
a2
a
Va = R a I a + jω La I a + jω LabI b + jω LacI c + jω LawI w + jω LavI v
− jω LanI n + Va′ + R nI n + jω L nI n − jω LanI a − jω LbnI b
IMPEDANCE MATRIX
1 1
=
1
3
1
A three-phase transmission line has couplings between phase-tophase conductors and also between phase-to-ground conductors.
Consider a three-phase line with two ground conductors, as shown
in Fig. D-4. The voltage Va can be written as:
1
a
a2
− jω LcnI c − jω L wnI w − jω L vnI v
(D-29)
where Ra, Rb, . . . , Rn are the resistances of phases a, b, . . . ,n, respectively, La, Lb, . . . , Ln are the self-inductances, and Lab, Lac, . . . , Lan are
the mutual inductances.
This can be written as:
Va = (R a + R n )Ia + R n Ib + R n Ic + jω ( La + L n − 2 Lan )Ia
+ jω ( Lab + L n − Lan − Lbn )Ib + jω ( Lac + L n − Lan − Lcn )Ic + R n I w
+ jω ( Law + L n − Lan − L wn )I w + R n I v + jω ( Lav + L n − Lan − L vn )I v + Va′
(D-25)
0
0
1 Z + 2M
=
0
0
Z−M
3
0
0
Z−M
= Zaa −g Ia + Zab−g Ib + Zac−g Ic + Zaw−g I w + Zav−g I v
(D-30)
But if we start with an original three-phase system, not completely balanced, we will have different results. Ignoring mutual impedances, let:
Zabc =
Z1
0
0
0
Z2
0
0
0
Z3
(D-26)
Then attempting to decouple it will give:
Z1 + Z2 + Z 3 Z1 + a 2 Z2 + aZ 3 Z1 + aZ2 + aZ 3
1
Z012 =
Z + aZ + aZ 3
Z1 + Z2 + Z 3 Z1 + a 2 Z2 + Z 3
3 1 2 2
Z1 + a Z2 + aZ 3 Z1 + aZ2 + aZ 3 Z1 + Z2 + Z 3
(D-27)
If we start with equal self-impedances and unequal mutual impedances, the results will be the same. The resulting matrix is nonsymmetrical. In the application of symmetrical component theory, it is
assumed that the system is perfectly balanced before an unbalance
condition occurs, for example, the study of a line-to-ground fault.
FIGURE D-4
Transmission line section with two ground conductors.
SEQUENCE IMPEDANCES OF TRANSMISSION LINES AND CABLES
where Zaa-g and Zbb-g are the self-impedance of a conductor with
ground return, Zab-g and Zac-g are the mutual impedances between
two conductors with common earth return.
Similar equations apply to voltages of other phases and ground
wires. Then the following matrix holds for the voltage differentials
between terminals marked w, v, a, b, c and w′, v′, a′, b′ and c′:
D Va
Zaa−g Zab−g Zac−g Zaw−g Zav−g
Ia
D Vb
Zba−g Zbb−g Zbc−g Zbw−g Zbv−g
Ib
D Vc
D Vw
D Vv
= Zca−g Zcb−g Zcc−g Zcw−g Zcv−g I c
Z wa−g Z wb−g Z wc−g Z ww−g Z wv−g I w
Z va−g Z vb−g Z vc−g Z vw−g Z vv−g I v
(D-31)
ZB
ZD
Iabc
Iwv
(D-32)
Zaa
Va
Vb
Zba
Vc
Zca
−− = −
Va′
Za′a
Vb′
Zb′a
Vc′
Zc′a
Zab
Zbb
Zcb
−
Za′b
Zb′b
Zc′b
Zac
Z bc
Zcc
−
Za′c
Zb′c
Zc′c
|
|
|
−
|
|
|
Zaa′
Zba′
Zca′
−
Za′a′
Zb′a′
Zc′a′
Zab′
Zbb′
Zcb′
−
Za′b′
Zb′b′
Zc′b′
Zac′ I a
Zbc′ I b
Zcc′ I c
− −−
Za′c′ I′a
Zb′c′ I′b
Zc′c′ I′c
(D-36)
Vabc
Z
= 1
Va′b′c′
Z3
Z2
Z4
Iabc
Ia′b′c′
(D-37)
For symmetrical arrangement of bundle conductors Z1 = Z 4 . Modify so that lower portion of the vector goes to zero. Assume that:
Considering that the ground wire voltages are zero:
Va = Va′ = Va′′
DVabc = Z A Iabc + Z B Ivw
(D-33)
0 = Zc Iabc + Z D Ivw
Vb = Vb′ = Vb′′
(D-38)
Vc = Vc′ = Vc′′
Thus:
Then upper part of the matrix can be subtracted from the lower part:
Ivw = −Z −D1ZC Iabc
(D-34)
D Vabc = (Z A − Z B Z −D1ZC) Iabc
This can be written as:
DVabc = Zabc Iabc
Zaa′−g Zab′−g Zac′−g
Zabc = Z A − Z B Z −D1ZC = Zba′−g Zbb′−g Zbc′−g
Zca′−g Zcb′−g Zcc′−g
(D-35)
The five-conductor circuit is reduced to an-equivalent threeconductor circuit. The technique is applicable to circuits with any
number of ground wires provided the voltages are zero in the lower
portion of the voltage vector.
D-7
Each conductor in the bundle carries a different current and has
different self-and mutual impedance because of its specific location.
Let the currents in the conductors be Ia, Ib, Ic, and I′a , I′b, and I′c, respectively. The following primitive matrix equation can be written as:
This can be partitioned so that:
In the partitioned form this matrix can be written as:
D Vabc
Z
= A
D Vwv
ZC
681
|
Zaa′
Zab′
Zac′
|
Zbb′
Zbc′
Z ba ′
|
Zca′
Zcb′
Zcc′
−−
−−
−−
|
| Za′a′ − Zaa′ Za′b′ − Zab′ Za′c′ − Zac′
| Zb′a′ − Zba′ Zb′b′ − Zbb′ Zb′c′ − Zbc′
| Zc′a′ − Zca′ Zc′b′ − Zcb′ Zc′c′ − Zcc′
(D-39)
We can write it in the partitioned form as:
I
Z
Z2
Vabc
= t 1
= abc
Ia′b′c′
0
Z2 − Z1 Z 4 − Z2
(D-40)
Write:
I′′a = I a + I′a
BUNDLE CONDUCTORS
Consider bundle conductors, consisting of two conductors per phase
(Fig. D-5). The original circuit of conductors a, b, c, and a′, b′, c′ can
be transformed into an equivalent conductor system of a″, b″, and c″.
FIGURE D-5
Va
Zaa
Zab
Zac
Vb
Zba
Zbb
Zbc
Vc
Zca
Zcb
Zcc
−− =
−−
−−
−−
0
Za′a − Zaa Za′b − Zab Za′c − Zac
0
Zb′a − Zba Zb′b − Zbb Zb′c − Zbc
0
Zc′a − Zca Zc′b − Zcb Zc′c − Zcc
I′′b = I b + I′b
I′′c = I c + I′c
Transformation of bundle conductors to equivalent single-conductor system.
(D-41)
Ia
Ib
Ic
−−
I′a
I′b
I′c
682
APPENDIX D
We can write the following matrix in the partitioned form:
Z
Z2 − Z1
Vabc
I ′′
= t 1
= abc
0
Z2 − Z1 ( Z 4 − Z2 ) − ( Z2t − Z1 )
Ia′b′c′
(D-42)
This can now be reduced to the following 3 × 3 matrix as before:
Z′′aa
Va′′
Vb′′ = Z′′ba
Vc′′
Z′′caa
Z′′ab
Z′′bb
Z′′cb
Z′′ac
Z′′bc
Z′′cc
I′′a
I′′b
I′′c
(D-43)
P=
See Example D-3 for an application.
D-8
where Zii is the self-impedance of conductor i with earth return,
Ω/mi, Zij is the mutual impedance between conductors i and j, Ω/mi,
Ri is the resistance of conductor, Ω/mi, Sii is the conductor to image
distance of the ith conductor to its own image, Dij is the distance
between conductors i and j, ri is the radius of conductor, ft, Sij is
the conductor-to-image distance of the ith conductor to the image
of jth conductor, w is the angular frequency, G is 0.1609347 ×
10–7 Ω-cm/abohm-mi, GMRi equal to geometric mean radius of
conductor i, r is the soil resistivity, and qij is the angle as shown
in Fig. D-6.
Expressions for P and Q are:
CARSON’S FORMULA
+
The theoretical value of Z abc-g can be calculated by Carson’s formula
(circa 1926). This is of importance even today in calculations of line
constants. For an n-conductor configuration, the earth is assumed an
infinite uniform solid with a constant resistivity. Figure D-6 shows
image conductors in the ground at a distance equal to the height of
the conductors above ground and exactly in the same formation, with
same spacing between the conductors. A flat conductor formation is
shown in Fig. D-6.
S
Zii = R i + 4ω PiiG + j X i + 2ω G ln ii + 4ω QiiG Ω /mi
ri
Sij
+ 4ω QijG Ω /mi
Zij = 4ω PiiG + j 2ω G ln
Dij
k2
2
1
π
k cos θ + cos 2θ 0 . 6728 + ln
−
k
8 3 2
16
(D-44)
k2
k 3 cos 3θ π k 4 cos 4θ
−
θ siin θ +
16
1536
45 2
k 2 cos 2θ k 3 cos 3θ
1 2
1
cos θ −
+
Q = − 0 . 0386 + ln +
2 k 3 2
64
45 2
−
k 4 sin 4θ k 4 cos 4θ 2
−
ln + 1 . 0895
384
384 k
(D-45)
where k = 8 . 565 × 10 4 Sij f /ρ , Sij is in feet, r is soil resistivity in
ohms-meter, and f is the system frequency. This shows dependence
on frequency as well as soil resistivity.
D-8-1
Approximations to Carson’s Equations
These approximations involve P and Q and the expressions are
given by:
Pij =
π
8
1
2
Qij = − 0 . 03860 + ln
2 kij
(D-46)
Using these assumptions, f = 60 Hz and soil resistivity =100 Ω-m,
the equations reduce to:
1
Zii = R i + 0 . 0953 + j0 . 12134 ln
+ 7 . 93402 Ω /mi
GMR
i
1
+ 7 . 93402 Ω /mi
Zij = 0 . 0953 + j0 . 12134 ln
Dij
FIGURE D-6
Line conductors and their images at equal depth in the
ground, Carson’s formula.
(D-47)
Equation (D-47) is of practical significance for calculations of
line impedances.
Example D-2 Consider an unsymmetrical overhead line configuration, as shown in Fig. D-7. The phase conductors consist of
556.5 KCMIL (556500 circular mils) of ACSR conductor consisting of
26 strands of aluminum, 2 layers, and 7 strands of steel. From the
properties of ACSR conductor tables, the conductor has a resistance
of 0.1807 Ω at 60 Hz and its GMR = 0.0313 ft at 60 Hz. Conductor
diameter = 0.927 in.
SEQUENCE IMPEDANCES OF TRANSMISSION LINES AND CABLES
683
Eliminate the last row and column:
0 . 1846 + j0 . 9825 0 . 0949 + j0 . 4439 0 . 0921 + j0 . 3334
Zabc = 0 . 0949 + j0 . 4439 0 . 1864 + j0 . 9683 0 . 0929 + j0 . 3709
0 . 09 2 1 + j0 . 3334 0 . 0929 + j0 . 3709 0 . 1809 + j1 . 0135
Convert to Z012 by using symmetrical component transformation
Z012 = Ts−1ZabcTs
0 . 3705 + j1 . 7536 0 . 0194 + j0 . 0007 − 0 . 0183 + j0 . 005 5
Z012 = − 0 . 0183 + j0 . 0055 0 . 0907 + j0 . 6054 − 0 . 0769 − j0 . 0146 Ω /mi
0 . 0194 + j0 . 0007 0 . 0767 + j0 . 0147 0 . 0907 + j0 . 6054
This shows mutual coupling between sequence impedances. We could
average out the self and mutual impedances according to Eq. (D-28):
Zs =
Zaa + Zbb + Zcc
= 0 . 184 + j0 . 9973
3
Zm =
Zab + Zbc + Zca
= 0 .0
0 933 + j0 . 38271
3
Then the matrix Zabc becomes:
Z012 =
FIGURE D-7
Line configuration for calculations of line constants.
The neutral consists of 336.4 KCMIL, ACSR conductor
resistance = 0.259 Ω/mi at 60 Hz and 50°C and GMR = 0.0278 ft,
and conductor diameter is 0.806 in.
Using Eq. (D-47) (all in ohms):
Zaa = Zbb = Zcc = 0 . 1859 + j1 . 3831
which is a decoupled diagonal matrix.
Example D-3 Figure D-8 shows a high-voltage line with bundle
ACSR conductors. Each conductor has a cross sectional area of
636000 (3 layers of 54 strands of aluminium, 0.1085 inch diameter
and 7 strands of steel, 0.1085 inch diameter) circular mils. Conductor
GMR = 0.0329 ft, resistance = 0.1688 Ω/mi, diameter = 0.977 in,
and the spacings are as shown in Fig. D-8. Calculate the primitive
impedance matrix and reduce it to 3 × 3 matrix, Then convert it
to sequence component matrix. From Eq. (D-47) and the specified
spacings in Fig. D-8, matrix Z1 is:
Z nn = 0 . 3543 + j1 . 3974
0 . 164 + j1 . 3770 0 . 0953 + j0 . 5500 0 . 0953 + j0 . 4659
Z1 = 0 . 9 5 3 + j0 . 5500 0 . 164 + j1 . 3770 0 . 0953 + j0 . 5500
0 . 0953 + j0 . 4659 0 . 0953 + j0 . 5500 0 . 164 + j1 . 3770
Zab = Zba = 0 . 0953 + j0 . 8515
Zbc = Zcb = 0 . 0953 + j0 . 7674
Zca = Zac = 0 . 0953 + j0 . 7182
This is also equal to Z4, as the bundle conductors are identical and
symmetrically spaced. Matrix Z2 is:
0 . 0953 + j0 . 8786 0 . 0953 + j0 . 5348 0 . 0953 + j0 . 4581
Z2 = 0 .0
0 953 + j0 . 5674 0 . 0953 + j0 . 8786 0 . 0953 + j0 . 5348
0 . 0953 + j0 . 4743 0 . 0953 + j0 . 08786 0 . 0953 + j0 . 8786
Zan = Z na = 0 . 0953 + j0 . 7539
Zbn = Z nb = 0 . 0953 + j0 . 7674
Zcn = Z nc = 0 . 0953 + j0 . 7237
The primitive matrix is 6 × 6 given by Eq. (D-39) formed by partitioned matrices according to Eq. (D-40). From these two matrices,
we will calculate matrix equation [Eq. (D-42)].
It is required to form a primitive Z matrix, convert it to 3 × 3 Zabc
matrix and then to develop sequence impedance matrix Z012.
Therefore the primitive impedance matrix is:
Z prim
0 . 3706 + j1 . 7627
0
0
0
0 . 0907 + j0 . 6146
0
0
0
0 . 0907 + j0 . 6146
0 . 1859 + j1 . 3831 0 . 0953 + j0 . 08515
0 . 0953 + j0 . 08515 0 . 1859 + j1 . 3831
=
0 . 0953 + j0 . 7182 0 . 095 3 + j0 . 7624
0 . 0953 + j0 . 7539 0 . 0953 + j0 . 7674
Z1 − Z2 =
0 . 069 + j0 . 498
j0 . 0150
j0 . 0079
j0 . 0150
0 . 069 + j0 . 498
− j0 . 0171
− j0 . 00841
− j0 . 0170
0 . 069 + j0 . 498
0 . 0953 + j0 . 71 8 2
0 . 0953 + j0 . 7624
0 . 1859 + j1 . 3831
0 . 0953 + j0 . 7237
0 . 0953 + j0 . 7539
0 . 0953 + j0 . 7674
0 . 0953 + j0 . 7237
0 . 3543 + j1 . 397 4
684
APPENDIX D
FIGURE D-8
Bundle conductors matrix transformation.
and
Zk = (Z1 − Z2) − (Z2t − Z1) =
0 . 138 + j0 . 997 − j0 . 0022
− j0 . 000 5
− j0 . 0022 0 . 138 + j0 . 997 − j0 . 0022
− j0 . 0005
− j0 . 0022 0 . 138 + j0 . 997
The inverse is:
Zk−1 =
0 . 136 − j0 . 984
0 . 000589 − j0 . 002092 0 . 0001357 − j0 . 0004797
0 . 0005891 − j0 . 002092
0 . 136 − j0 . 981
0 . 00058 9 1 − j0 . 002092
0 . 136 − j0 . 981
0 . 0001357 − j0 . 0004797 0 . 0005891 − j0 . 0 0 2092
Then, the matrix (Z2 − Z1) Zk−1 (Z2t − Z1) is:
0 . 034 + j0 . 2500
− 0 . 000018 − j0 . 000419 0 . 0000363 − j0 . 00 0 3871
− 0 . 000018 − j0 . 000419
0 . 034 + j0 . 2500
− 0 . 000018 − j0 . 000419
0 . 034 + j0 . 2500
0 . 0000363 − j0 . 000387 − 0 . 000018 − j0 . 0004 1 9
Note that the off-diagonal elements are comparatively smaller as
compared to the diagonal elements. The required 3 × 3 transformed
matrix is then Z1 minus above matrix:
0 . 13 + j1 . 127 0 . 095 + j0 . 55 0 . 095 + j0 . 466
Ztransformed = 0 . 095 + j0 . 55 0 . 13 + j1 . 127 0 . 095 + j0 . 55 Ω /mi
0 . 095 + j0 . 466 0 . 095 + j0 . 55 0 . 13 + j1 . 127
Cn =
The sequence impedance matrix is (Z012 = Ts−1ZabcTs):
0 . 32 + j2 . 171 0 . 024 − j0 . 014 − 0 . 024 − j0 . 014
Z012 = − 0 . 024 − j0 . 014 0 . 035 + j0 . 605 − 0 . 048 + j0 . 028 Ω /mi
0 48 + j0 . 028 0 . 035 + j0 . 605
0 . 024 − j0 . 014 0 .0
D-9
πε 0
F/m(farads per meter)
ln( D /r )
(D-48)
where ε 0 is the permittivity of free space = 8.854 × 10–12 and other
symbols are as defined before. For a three-phase line with equilaterally spaced conductors, the line to neutral capacitance is:
C=
2πε 0
F/m
ln( D /r )
(D-49)
ln(GMD/r ) − ln
(
2πε 0
3
Sab′Sbc′Sca′ / 3 Saa′Sbb′Scc′
)
(D-50)
Using the notations in Eqs. (D-21) and (D-22), this can be written as:
Cn =
CAPACITANCE OF LINES
The shunt capacitance per unit length of a two-wire, single-phase
transmission line is:
C=
For unequal spacing, D is replaced with GMD from Eq. (D-8). The
capacitance is affected by ground and the effect is simulated by a
mirror image of the conductors exactly at the same depth as the
height above the ground. These mirror-image conductors carry
charges which are of opposite polarity to those of above ground conductors (Fig. D-9). From this figure, the capacitance to ground is:
D-9-1
2πε 0
10−9
=
ln( Dm /Ds ) 18 ln( Dm /Ds )
(D-51)
Capacitance Matrix
The capacitance matrix of a three-phase line is:
Caa
Cabc = −Cba
−Cca
−Cab
Cbb
−Ccb
−Cac
−Cbc
Ccc
(D-52)
This is diagrammatically shown in Fig. D-10a.The capacitance
between the phase conductor a and b is Cab and capacitance between
phase- a conductor and ground is: Caa – Cab – Cac . If the line is perfectly
SEQUENCE IMPEDANCES OF TRANSMISSION LINES AND CABLES
685
where
Pii =
S
S
1
ln ii = 11 . 17689 ln ii
2πε 0
ri
ri
(D-57)
Sij
Sij
1
Pij =
ln
= 11 . 17689 ln
Dij
2πε 0 Dij
where Sij is the conductor to image distance below ground, ft, Dij is
the conductor-to-conductor distance, ft, ri is the radius of the conductor, ft, and ε 0 is the permitivity of the medium surrounding the
conductor = 1.424 × 10–8 F/mi for air.
For sine wave voltage and charge, the equation can be expressed
as:
Caa −Cab −Cac
Ia
I b = jω −Cba Cbb −Cbc
Ic
−Cca −Ccb Ccc
(D-58)
Capacitance of three-phase lines with ground wires and with bundle
conductors can be addressed as in the calculations of inductances. The
primitive P matrix can be partitioned and reduces to 3 × 3 matrix.
Example D-4 Calculate the matrix P and C for the Example D-2.
Neutral is 30 ft above ground and configuration of Fig. D-7 is
applicable.
The mirror images of the conductors are drawn in Fig. D-7.
This facilitates calculation of spacings required in Eq. (D-57) for P
matrix. Based on the geometric distances and conductor diameter
the primitive P matrix is:
FIGURE D-9
Mirror-image conductors for calculation of line capacitances, conductors, spacing, mirror images, and electrical charges.
symmetrical, all diagonal elements are the same and all off-diagonal
elements of the capacitance matrix are identical:
C −C′ −C′
Cabc = −C′ C −C′
−C′ −C′ C
(D-53)
Symmetrical component transformation is used to diagonalize the
matrix:
C012 = Ts−1CabcTs =
0
C − 2C′ 0
0
C + C′ 0
0
0 C + C′
(D-54)
The zero, positive, and negative sequence networks of capacitance of a symmetrical transmission line are shown in Fig. D-10b.
The eigenvalues are C – 2C′, C +C′, and C +C ′, and. C +C′ can be
written as 3C′ – C – 2C′; that is, it is equivalent to line capacitance of
a three-phase system minus line-to-ground capacitance of a threeconductor system.
In a capacitor V = Q/C. The capacitance matrix can be written as:
−1
Vabc = PabcQabc = Cabc
Qabc
(D-55)
where P is called the potential coefficient matrix; that is,
Paa Pab Pac
Va
Vb = Pba Pbb Pbc
Vc
Pca Pcb Pcc
(D-56)
Paa
P
P = ba
Pca
Pna
Pab
Pbb
Pcb
Pnb
80 . 0922
= 33 . 5387
21 . 4230
23 . 3 2 28
Pac
Pbc
Pcc
Pnc
Pan
Pbn
Pcn
Pnn
33 . 5387
80 . 0922
25 . 7913
24 . 5581
21 . 4230
2 5 . 7913
80 . 0922
20 . 7547
23 . 3288
24 . 5581
20 . 7547
79 . 1615
This is reduced to 3 × 3 matrix:
73 . 2172 26 . 3015 15 . 3066
P = 26 . 3015 72 . 4736 19 . 3526
15 .3
3 066 19 . 3526 74 . 6507
Therefore, the required C matrix is inverse of P and Yabc is:
j6 . 0141 − j1 . 9911 − j0 . 7170
Yabc = jωP −1 = − j1 . 9911 j6 . 24 7 9 − j1 . 2114 µS/mi
− j0 . 7170 − j1 . 2114 j5 . 5111
D-10
CABLE CONSTANTS
Construction of cables varies widely, mainly a function of insulation
type, method of laying and voltage of application. For high-voltage
applications above 230 kV or 325 kV, oil-filled, paper-insulated
cables are used, though recent trends see development of solid
dielectric cables. A three-phase solid dialectic cable has three conductors enclosed within a sheath and because the conductors are
much closer to each other than those in an overhead line and permittivity of insulating medium is much higher than that of air, the shunt
capacitive reactance is much smaller as compared to a overhead line.
Thus, use of a T or P model is required even for shorter cable
lengths, see Chap. 4.
686
APPENDIX D
FIGURE D-10
(a) Capacitance of a three-phase line. (b) Equivalent positive, negative, and zero sequence network of capacitances.
The inductance per unit length of a single conductor cable is
given by:
µ
r
L = 0 ln 1
2π r2
(D-59)
where r1 is the radius of the conductor and r2 is the radius of the
sheath; that is, cable outside diameter divided by 2.
When single-conductor cables are installed in magnetic conduits,
the reactance may increase by a factor of 1.5. Reactance is also dependent on conductor shape; that is, circular or sector-shaped, and on
magnetic binders in three-conductor cables. Manufacturers’ data
is normally used. The flow of currents in the magnetic grounded
sheaths increases the effective conductor resistance.
D-10-1
Shunt Admittance of Cables
In a single-conductor cable, the capacitance per unit length is given
by:
C=
2πεε 0
F/m
ln(r1 /r2 )
(D-60)
By change of units, this can be written as:
C=
7 . 35ε
pF/ft
log(r1 /r2 )
Note that e is the permittivity of the dielectric medium and
not free space. The capacitances in a three-conductor cable are
shown in Fig. D-11. This assumes a symmetrical construction and
the capacitances between conductors and from conductors to the
sheath are equal. The circuit of Fig. D-11a is successively transformed and Fig. D-11d, which shows that the net capacitance per
phase = C1 + 3 C2. Table D-1 gives typical values of the dielectric
constants of the cables.
D-10-2 Zero-Sequence Impedance
of the OH Lines and Cables
The zero-sequence impedance of the lines and cables is dependent
on the current flow through a conductor and return through the
ground or sheaths, and encounters the impedance of these paths.
The zero-sequence current flowing in one phase also encounters
SEQUENCE IMPEDANCES OF TRANSMISSION LINES AND CABLES
FIGURE D-11
TA B L E D - 1
(a) Capacitances in a three-phase cable. (b) and (c) Equivalent circuits. (d ) Final capacitance circuit.
Relative Permittivity of
Insulating Materials
TYPE OF INSULATION
Polyvinyl chloride (PVC)
687
provided in Ref. 7. As an example, the zero-sequence impedance of
a three-conductor cable with a solidly bonded and grounded sheath
is given by:
PERMITTIVITY (d )
3.5–8.0
Ethylene-propylene insulation
2.8–3.5
Polyethylene insulation
2.3
Cross-linked polyethylene (XLPE)
2.3–6.0
Impregnated paper
3.3–3.7
Mass-impregnated
4.2
Fluid filled
3.5
z 0 = rc + re + j0 . 8382
(D-61)
where rc is the ac resistance of one conductor Ω/mi, re is the ac
resistance of earth return (depending on equivalent depth of earth
return, soil resistivity, taken as 0.286 Ω/mi), De is the distance to
equivalent earth path (see Ref. 7), and GMR3c is the geometric mean
radius of conducting path made up of three actual conductors taken
as a group:
GMR 3c = 3 GMR1c S 2
the currents arising out of that from conductor self-inductance, from
mutual inductance to other two phase conductors, from the mutual
inductance to the ground and sheath return paths, and from the self
inductance of the return paths. Tables and analytical expressions are
De
f
log10
60
GMR 3c
(D-62)
where GMR1c is the geometric mean radius of individual conductor
and S = (d + 2t), where d = diameter of the conductor and t is the
thickness of the insulation.
688
APPENDIX D
D-10-3
Cable Constant Calculation Routines
Cable constant calculation routines are included in EMTP-type programs. The electrical representation is a series impedance matrix Z
and a shunt matrix Y. The basic inputs required for these cable constant routines (See Chap. 7 for a calculation) require material properties apart from the cable construction, cable geometry, method of
laying, burial depth, and the like.12,13 These routines take account
of skin effect and can include proximity effects.14,15 Tables D-2 and
D-3 show the resistivity of conductive materials and parameters of
semiconductive layers, respectively.
The resistivity of the surrounding medium depends strongly on
soil characteristics. Submarine cables are designed with a magnetic
steel armor and the permeability depends on wire diameter, laying
angle, and intensity of circumferential magnetic field. Curves for
the permeability of round steel wire armor due to magnetic field in
circumferential direction is included in Ref. 15.
Most extruded insulations, including XLPE and PE, are practically
lossless up to 1 MHz, whereas paper insulation exhibits significant
losses at lower frequencies.
The losses are associated with complex frequency dependant
permittivity.
ε r = ε r′ (ω ) − jε r′′(ω )
tan δ(ω ) =
(D-63)
ε r′′
ε r′
(D-64)
Brenien and Johansen fitted a Debye model to measured frequency
response of insulation samples of low-pressure, fluid-filled cable, in the
frequency range of 10 to 100 MHz.16 The permittivity is given by:
εr = 2. 5 +
0 . 94
1 + ( jω. 6 . 10−9 )0. 315
(D.65)
High-frequency transients in cable systems essentially propagate as
decoupled coaxial waves between cores and sheath and transient
behavior is sensitive to modeling of cable parameters:
1. Increasing core resistivity increases attenuation and slightly
decreases propagation velocity.
2. Increasing sheath resistivity or decreasing sheath thickness
increases attenuation.
3. Increasing insulation permittivity increases cable capacitance. This decreases velocity and surge impedance.
TA B L E D - 2
MATERIAL
Resistivity of Conductive Materials
RESISTIVITY (q), W-m
Copper
1.728E-8
Aluminum
2.83E-8
Lead
22E-8
Steel
18E-8
TA B L E D - 3
F I G U R E D - 1 2 Variation of transmission line parameters due to skin
effects. Conductors in flat formation, spacing 2 m apart, height above
ground = 12 m, ground resistivity = 100 Ω-m.
Parameters of Semiconductive
Layers (Extruded Insulation)
Resistivity (Ω-m)
< 1E-3
Permittivity
> 1000
4. With fixed insulation thickness, adding semiconducting
screens increases inductance of the core-sheath loop without
changing the capacitance. This decreases velocity and surge
impedance.17
D-11 FREQUENCY-DEPENDENT TRANSMISSION
LINE MODELS
The transmission line models for transient studies should be appropriate for the involved frequency range (Chap. 4). The parameters
vary with frequency depending on:
■
Soil resistivity
■
Skin effect
■
Conductor height
■
Proximity effects
Some curves of variations with frequency are provided in Ref. 18.
Figure D-12 shows variations of positive- and zero-sequence
resistances and inductances due to skin effects.
REFERENCES
1. J. L. Blackburn, Symmetrical Components for Power System
Engineering, Marcel Dekker, New York, 1993.
2. L. J. Myatt, Symmetrical Components, Pergamon Press, Oxford,
UK, 1968.
3. C. F. Wagner and R. D. Evans, Symmetrical Components,
McGraw Hill, New York, 1933.
4. P. M. Anderson, Analysis of Faulted Systems. Iowa State University
Press, Ames, IA, 1973.
5. D. G. Fink, Ed. Standard Handbook for Electrical Engineers,
10th ed., McGraw Hill, New York, 1969.
6. T. Croft, W. Summers, F. Hastwells, American Electrician’s
Handbook, 15th ed., McGraw Hill, New York, 1970.
SEQUENCE IMPEDANCES OF TRANSMISSION LINES AND CABLES
689
7. Central Station Engineers. Electrical Transmission and Distribution
Reference Book, 4th ed., East Pittsburg, PA, Westinghouse Corp,
1964.
13. A. Amentani, “A General Formation of Impedance and Admittance of Cables,” IEEE Trans. PAS, vol. 99, no. 3, pp. 902–909,
May/Jun. 1980.
8. The Aluminum Association. Aluminum Conductor Handbook,
2nd ed., Washington, DC, 1982.
14. Y. Yin and H. W. Dommel, “Calculations of Frequency
Dependent Impedances of Underground Power Cables with
Finite Element Method,” IEEE Trans. On Magnetics, vol. 25,
no. 4, pp. 3025–3027, Jul. 1989.
9. J. H. Neher and M. H. McGrath, “The Calculation of the
Temperature Rise and Load Capability of Cable Systems,”
AIEEE Trans., Part III, vol. 76, Oct. 1957.
10. W. D. Stevenson, Elements of Power System Analysis, 2d ed.,
McGraw Hill, New York. 1962.
15. G. Bianchi and G. Luoni, “Induced Current Losses in Single
Core Submarine Cables,” IEEE Trans. PAS, vol. 95, pp. 49–58,
Jan./Feb. 1976.
11. CIGRE, Working Group 33.02 (Internal Voltages), Guidelines
for Representation of Network Elements When Calculating
Transients, Paris.
16. O. Brenien and I. Johansen, “Attenuation of Traveling Waves in
Single-Phase High Voltage Cables,” Proc. IEE, vol. 118, no. 6,
pp. 787–793, Jun. 1971.
12. L. M. Wedephol and D. J. Wilcox, “Transient Analysis of
Underground Power-Transmission Systems. System-Model and
Wave-Propagation Characteristics,” Proc. IEE, vol. 120, no. 2,
pp. 253–260, Feb. 1973.
17. IEEE PES TF, Parameter Determination for Modeling System
Transients, Part II: Insulated Cables, IEEE WG.
18. IEEE PES TF, Parameter Determination for Modeling System
Transients, Part I: Overhead Lines, IEEE WG.
This page intentionally left blank
APPENDIX E
ENERGY FUNCTIONS
AND STABILITY
Generally, we seek explicit solutions to circuit problems, and circuit
analysis programs give accurate solutions based on some specific initial conditions. However, many times we seek the qualitative behavior of the system; that is, is the system stable for all initial conditions
after a disturbance? Will it keep oscillating? Thus a new solution
must be found for each initial condition and examined, which may
not be even practical. A useful technique of analyzing can be to
study a quantity derived from the system itself—for example, energy
function—and use it to draw conclusions about the system.
E-1
and it is current controlled if we write:
ˆ
v = vi
(E-4)
Same notations apply to capacitors and inductors. For a capacitor
we write:
C(q, v) = 0
or
ˆ ( voltage controlled )
q = qv
ˆ (chargge controlled)
v = vq
(E-5)
DYNAMIC ELEMENTS
In Chap. 2, we defined a dynamic system as the one whose behavior changes with time. Neglecting wave propagation and assuming
that the voltages and currents external to the system are bounded
functions of time, a broad definition can be that a dynamic circuit is
a network of n-terminal resistors, capacitors, and inductors, which
can be nonlinear. We call capacitors and inductors dynamic elements.
We can define the nonlinear resistors, inductors, and capacitors by
the following equations:
R(v, i) = 0
C(q, v) = 0
(E-1)
L(φ, i) = 0
These relations are constituency relations. A nonlinear resistor is
described by the current and voltage and a nonlinear capacitor by
the charge q and voltage v across it. If an element is time varying
we write:
R(v, i, t ) = 0
C(q, v, t ) = 0
(E-2)
L(φ, i, t ) = 0
A resistor is voltage controlled if the current i is a function of the
voltage across it. The constituency relation is written as R(i, v) = 0
and is expressed as:
ˆ
i = iv
(E-3)
and for an inductor:
i = iˆ(φ )
E-2
φ = φˆ (i)
(E-6)
PASSIVITY
Passivity implies that the nonlinear elements dissipate energy; that
is, these do not have a power source. A nonlinear resistor with
constituency relationship i = g(v) is passive if vg(v) ≥ 0 for all v. It
is strictly passive if vg(v) > 0 for all v ≠ 0. It is eventually passive if
there exists a k > 0 such that vg(v) ≥ 0, where | v | > k . It is eventually strictly passive if vg(v) > 0, where | v | > k.
E-3
EQUILIBRIUM POINTS
A dynamic circuit is called autonomous or time-independent if it
does not contain any time-varying elements or sources. A stationary or equilibrium point of a dynamic circuit is defined as that
state of the circuit which does not change with time. In a network
of resistors, capacitors, and inductors, this means that all branch
currents of capacitors are zero and all voltages on inductors are
also zero; that is, a capacitor is open circuited and an inductor is
short circuited, reducing the network to a resistive circuit. To find
the equilibrium points of a dynamic system, find operating points
of the resistive circuit. Then for each capacitor, the branch voltage
at the operating point is found to ascertain all the charges which
satisfy Ci (qi , vi ) = 0 and similarly for inductors to find all the fluxes.
Each operating point of the resistive circuit can correspond to many
equilibrium points of the dynamic circuit.
691
692
APPENDIX E
E-4
STATE EQUATIONS
If we eliminate variables v and i, the state equations can be written as:
dqc
= fc (qc , φl , t )
dt
dφl
= fl (qc , φl , t )
dt
E-7
(E-7)
where qc and φl are the vectors corresponding to charges on capacitors and fluxes in the inductors. If all the capacitors are chargecontrolled and all the inductors are flux controlled—that is,
v = vˆ (q) and i = iˆ(φ )—then the state equations can be written in
terms of capacitor voltage vc and inductor currents il:
vc = g c (qc )
= h c (vc , il , t )
dil
dφ
= ∇ gl (φl ) × l = ∇ g c ( x ) −1 × fl[g c−1(vc ), gl−1(il ), t]
x = gl ( il )
dt
dt
(E-8)
This assumes that ∇ g c , g c−1, ∇ g i , and g i−1 exist.
Even if the state equations exist, there is no guarantee that a
solution exits. In Chap. 2, we described that the first-order state
equations are equal to the order of the system. We assume that solutions to state equations [Eq. (E-9)] exist and are unique for all time,
and f is continuous. A dynamic circuit may have solutions which
escape to infinity in finite time. This will not happen if:
■
There are no loops or cut sets consisting only of capacitors
and/or inductors.
■
All capacitors and inductors are eventually strongly locally
passive.
E-5
All resistors are eventually passive.
STABILITY OF EQUILIBRIUM POINTS
The state equation in Eq. (E-7) can be written as:
x = f ( x )
(E-9)
Equilibrium point is a state x* so that:
x = 0
that is,
V : Rn → R
(E-11)
is a Lyapunov function if:
b(| x |) ≤ V ( x ) ≤ a(| x |)
for all values of x
x = f ( x )
(E-12)
(E-10)
f (x*) = 0
If the state of a circuit is at equilibrium point, then it remains
there for all time. To be more precise, we should consider noise.
A sphere balanced on a pin will become unstable on the slightest
disturbance. Equilibrium point is asymptotically stable, if all initial
conditions nearby do not leave a neighborhood, and converge to
the equilibrium point as the time passes.
E-6 HARTMAN-GROBMAN
LINEARIZATION THEOREM
This theorem1 allows to look at the stability of the equilibrium
point by examining the eigenvalues of the linearization. If x* is a an
equilibrium point, then f(x*) = 0. Consider that Jf(x*), the Jacobian
(E-13)
If V is a differentiable Lyapunov function, so that:
∇ V ⋅ f ( x ) ≤ −c(| x |)
il = gl (φl )
■
LYAPUNOV FUNCTION
The Lyapunov function maps the state of the system x into simple,
usually scalar quantity V(x). Then we observe V(x) evolve with time
and draw conclusions about the system. Energy, like quantity, is
sometimes, used for the Lyapunov function. Let a and b be strictly
increasing functions, so that a(0) = b(0) = 0. A function:
Consider a system:
dvc
dq
= ∇ g c (qc ) × c = ∇ g c ( x ) −1 × fc[g c−1(vc ), gl−1(il ), t]
x = g c ( vc )
dt
dt
= h l (vc , il , t )
matrix of f at x*, does not have purely imaginary eigenvalues. If all
the eigenvalues have negative real parts, then x* is asymptotically
stable; otherwise it is unstable.
(E-14)
for some strictly increasing function c so that c(0) = 0, then the
origin is globally asymptotically stable and all trajectories converge
toward the origin. The construction of V to show stability in this
manner is called the Lyapunov direct method.
E-8
LASALLE’S INVARIANT PRINCIPLE
For an autonomous system, consider Eq. (E-9) and that Eq. (E-11)
is a differentiable function so that V(x) ≥ C for all x and some constant C and:
dV
≡ ∇ V ⋅ f ( x ) ≤ −W ( x ) ≤ 0
dt
(E-15)
for all t > 0 and for some continuous W. Define:
E = [x : W ( x ) = 0]
(E-16)
Then each solution of x(t) of Eq. (E-9) approaches E ∪ {∞}. The V
is still called a Lyapunov function.
E-9
ASYMPTOTIC BEHAVIOR
A dynamic circuit is completely stable if all trajectories converge toward
a stable equilibrium point. In Chap. 2, we could divide the response of
linear systems into a transient or zero-input response and the steadystate solution. The transient response goes to zero if the system is
stable, through some decaying oscillations or asymptotically. This cannot apply to nonlinear systems, but convergence to a steady-state solution irrespective of initial conditions can be defined. Consider that the
state equations exist. If all solutions of state equations, x = f ( x, t ), are
bounded and any two solutions converge toward each other asymptotically, say [x(t) and y(t)] converge toward each other asymptotically:
lim x(t ) − y(t ) = 0
t →∞
(E-17)
then the system has a unique steady-state solution. A dynamic circuit has a unique steady state if:2
■
Capacitors, inductors, and/or voltage sources do not form
any exclusive loop.
■
Capacitors, inductors, and/or current sources do not form
any exclusive cut set.
■
All capacitors and inductors are weakly nonlinear and passive.
■
All resistors are strongly locally passive.
ENERGY FUNCTIONS AND STABILITY
E-10
PERIODIC INPUTS
REFERENCES
Even simple circuits, when driven by periodic inputs, exhibit chaotic behavior. The state trajectories contain frequencies which are
not integral combinations of driving frequencies. A dynamic circuit
will have steady-state waveforms with frequency components only
at integral combination of driving frequencies, if certain conditions
similar to the ones described in Sec. E-9 are met.2
The nonlinear circuits can generate beat frequencies. In Chap. 2,
Example 2-15 shows that beat frequencies are produced in linear
circuits when excited by frequencies close to the resonant frequencies. The same phenomena occur in nonlinear circuits. Given two
sinusoidal inputs, the beat frequency is:
ωa,b = aω1 + bω2
(E-18)
The output can be written as:
y(t ) = f (sin ω1t + sin ω2t )
(E-19)
This can be expanded using Taylor’s series around zero. The ManleyRowe equations describe the relative power in various beat frequency
components. These equations are:
∞
∞
aP
∑ ∑ ω a,b = 0
a =0 b=0
∞
∞
a,b
693
(E-20)
bP
∑ ∑ ω a,b = 0
a,b
a =0 b=0
The energy concepts described in this appendix, though not exhaustive, are relevant to direct stability methods in Chap. 12.
1. P. Hartman, Ordinary Differential Equations, Wiley, New York,
1964.
2. L. O. Chua, Introduction to Nonlinear Network Theory, McGraw
Hill, New York, 1964.
FURTHER READING
L. O. Chua, “Nonlinear Circuits,” IEEE Trans. Circuits Syst., vol. 31,
pp. 69–87, 1984.
D. W. Jordan and P. Smith, Nonlinear Ordinary Differential Equations,
Oxford, London, 1977.
J. P. LaSalle, “An Invariance Principal in Theory of Stability,” in
Differential Equations and Dynamical Systems, J. K. Hale and J. P.
LaSalle, Ed., pp. 277–286, Academic Press, New York, 1967.
J. M. Manley and H. E. Rowe, “Some General Properties of Nonlinear
Elements—Part1. General Energy Relations,” Proc. IEE, vol. 44,
pp. 904–913, Jul. 1956.
This page intentionally left blank
APPENDIX F
STATISTICS AND PROBABILITY
The statistical and probabilistic concepts are used in the insulation
coordination. A brief background is included here.
F-1
MEAN, MODE, AND MEDIAN
The frequency distribution data can be represented by a histogram,
frequency polygon, frequency curve, bar chart, and pie diagrams.
The arithmetic mean for n numbers, x1, x2, . . . xn, is given by:
xm =
∑ fx
∑f
= x m−a
(F-3)
n=1
(F-8)
∑f
The square of the SD, s 2, is called variance. It is also called the second moment about the mean and is denoted by m2. The coefficient
of variance is given by:
s
×100
xm
(F-9)
s=
∑ fd 2 − ∑ fd
∑ f ∑ f
2
(F-10)
(F-4)
Example F-1
For even frequency, there are two middle terms, and the mean of
n/2 and (n/2+1) terms gives the median. Mode is defined as the size
of the variable in a population that occurs most frequently:
Mean − mode = 3(mean − median )
∑ fn ( x n − x m )2
The standard deviation can be found from the following expression:
Median is the measure of the central item of the distribution
when it is arranged in ascending or descending order. For an odd
n, it is given by:
n +1
th item
2
(F-7)
∑f
n
SD = s =
∑ fd
xm = a +
∑f
(F-5)
Geometric mean is defined as:
G = ( x1 × x 2 × ...... × x n )1/ n
n=1
where x1, x2, . . . xn is a set of numbers with frequencies f1, f2, . . . fn.
Standard deviation is defined as square root of the mean of the
square of the deviation from the arithmetic mean:
(F-2)
If a is the assumed arithmetic mean and d is the deviation of the
variate x from a, we can write:
Md =
n
∑ fn x n − x m
(F-1)
n
∑ fd = ∑ f ( x − a ) = x − a∑ f
m
∑f
∑f
∑f
MEAN AND STANDARD DEVIATION
Average deviation or mean deviation is defined as the mean of the
absolute values of the deviations of a given set of numbers from
their arithmetic mean.
Mean deviation =
∑x
If x1 occurs f1 times, x2 occurs f2 times, . . . . and fn occurs n times,
then the arithmetic mean is:
xm =
F-2
(F-6)
Consider the following sample data:
(6, 4) (7, 6) (8, 10) (9, 11) (10, 7) 11, 4) (12, 3)
The first number in the parenthesis is the size, the second its frequency. It is required to find the mean and standard deviation.
Assume a = 10. To calculate mean and standard deviation,
Table F-1 is constructed. From this table:
∑ f = 45
∑ fd = − 53
∑ fd 2 = 239
695
696
APPENDIX F
TA B L E F - 1
x
Calculation of Mean and Standard Deviation
d=x–a
f
fd
fd 2
6
4
–4
–16
64
7
6
–3
–18
108
8
10
–2
–20
40
9
11
–1
–11
11
10
7
0
0
0
11
4
1
4
4
12
3
2
8
12
∑f = 45
∑fd = −53
∑fd 2 = 239
Assumed mean a = 10
Therefore from Eq. (F-3)
x m = 10 +
∑ fd = 8. 82
∑f
239 − 53
−
= 1 . 98
45 45
2
s=
F-3
SKEWNESS AND KURTOSIS
Skewness is opposite of symmetry. In a symmetrical series, the
mode, the median, and xm are the same. Figure F-1a and b shows
positive and negative skewness. Define coefficient of skewness by:
Mean − mode
s
(F-11)
Measure of kurtosis is given by:
m4
m22
b2 =
(F-12)
where:
m2 =
∑( x − x am )2
∑f
m4 =
∑( x − x am )4
∑f
If b2 = 3, the curve is normal, or mesokurtic. If b2 > 3, the curve is
peaked or leptokurtic; if b2 < 3, the curve is flat-topped or platykuric
(Fig. F-1c).
F-4
CURVE FITTING AND REGRESSION
The purpose of regression is to estimate one of the variables
(dependent variable) from the other (independent variable). If y is
estimated from x by some equation, it is referred to as regression. In
other words, if the scatter diagram of two variables indicates some
relation between these variables will be concentrated around a
FIGURE F-1
Illustration of (a) positive and (b) negative skewness.
(c) Illustration of kurtosis.
STATISTICS AND PROBABILITY
697
Constant b is the slope of the line Eq. (F-14). The least-square line
passes through (xmean, ymean) which is called the centroid of the data.
Slope b is independent of origin of coordinates; that is, for translation
of axis given by: x = x′ + h, y = y′ + k, where h and k are constants. In
Eq. (F-19), x and y can be replaced with x′ and y′.
Similarly, for least-square line of x on y:
x − x mean =
∑( x − x mean )( y − ymean ) ( y − y )
mean
∑( y − ymean ) 2
(F-20)
The least-square line can be written in terms of variance and
covariance. The sample variance and covariance are given by:
FIGURE F-2
d12 + d 22 + + d n2 = a
minimum
(F-13)
A curve meeting these criteria is said to fit the data in the leastsquare sense and is called a least-square regression curve, or simply a
least-square curve—straight line or parabola. The least-square line
imitating the points (x1, y1),..(xn, yn) has the equation:
y = a + bx
(F-14)
The constants a and b are determined from solving simultaneous equations, which are called the normal equations for the leastsquare line:
∑ y = an + b∑ x
∑ xy = a∑ x + b∑ x
(F-15)
2
(∑ y)(∑ x ) − (∑ x)(∑ xy)
n∑ x − (∑ x)
n∑ xy − (∑ x)(∑ y)
b=
n∑ x − (∑ x)
2
2
2
n
S xy =
(F-21)
∑( x − x mean )( y − ymean )
n
In terms of these the least-square lines of y on x and x on y are:
y − ymean =
x − x mean =
S xy
S 2x
S xy
S 2y
( x − x mean )
(F-22)
( y − ymean )
A sample correlation coefficient can be defined as:
r=
S xy
(F-23)
Sx S y
Example F-2
Given the data points (x, y) as:
fit a least-square line with x as independent variable, y as dependent
variable.
Table F-2 shows the various steps pf calculations. Substituting
the values arrived in this Table in Eq. (F-15), we have:
2
a=
∑( y − ymean ) 2
S 2y =
(1, 1), (3, 2), (4, 5), (6, 7), (7, 6), (9, 8), (12, 10), (15, 16)
This gives:
(F-16)
∑( x − x mean )( y − ymean )
∑( x − x 2mean )
where n is the number of samples = 8. Solving these equations, a =
–0.719, b = 0.975. Therefore the least-square line is:
(F-17)
(F-18)
From above we can also write the least-square line as:
8c + 55d = 57
55c + 535d = 543
y − ymean = b( x − x mean )
∑( x − x mean )( y − ymean ) ( x − x )
mean
∑( x − x mean )2
y = − 0 . 719 + 0 . 975 x
If x is considered as the dependent variable and y as the independent variable, then:
This yields:
ymean = a + bx mean
8a + 57b = 55
57a + 561b = 543
2
The constant b can be written as:
=
n
Criteria of fitting a least-square line in a scatter plot.
curve. This curve is called the curve of regression. When the curve
is a straight line it is called a line of regression.
For some given data points, more than one curve may seem to
fit. Intuitively, it will be hard to fit an appropriate curve in a scatter
diagram and variation will exist. Referring to Fig. F-2, a measure of
goodness for the appropriate fit can be described as:
b=
∑( x − x mean ) 2
S 2x =
(F-19)
Solution of which gives, c = 0.507 and d = 0.963.
An application of fitting the least-square line is the scatter plot
of soil resistivity measurements over a given area for grounding grid
designs.
698
APPENDIX F
TA B L E F - 2
x
Fitting the Least-Square Line
y
x2
xy
y2
1
1
1
1
1
3
2
9
6
4
4
5
16
20
25
6
7
36
42
49
7
6
49
42
36
9
8
81
72
64
12
10
144
120
100
15
16
225
240
256
∑x = 57
∑y = 55
∑x 2 = 561
F-4-1 Least-Square Parabola
As an extension of the above least-square example, the equation for
a least-square parabola to fit a set of sample points is given by:
y = a + bx + c2 x
(F-24)
∑ y = na + b∑ x + c∑ x 2
(F-25)
∑ x 2 y = a∑ x 2 + b∑ x 3 + c∑ x 4
If there is linear relation between a dependent variable z and two
linear variables x and y, we seek an equation of the form:
(F-26)
This is called a regression equation of z on x and y. Again, a, b, c can
be determined from the following equations:
∑ z = na + b∑ x + c∑ y
∑ xz = a∑ x + b∑ x 2 + c∑ xy
If p1, p2, p3, . . . , pn are separate probabilities of mutually exclusive
events, then the probability P that any of these events will happen
is given by:
P = p1 + p2 + + p n
P( A ∪ B) = P( A ) + P(B) − P( A ∩ B)
P( AB) = P( A ) × P(B)
(F-27)
P(r ) = n Cr p r q n−r
PROBABILITY
n
m+n
Thus p + q = 1, equal to 100 percent.
(F-33)
(q + p )n = q n + n C1q n−1p + n C2q n−2 p 2 + + n Cr q n−r p r + + p n
(F-34)
(F-28)
and of failure is:
q=
(F-32)
This is (r + 1)th term of (q + p)n.
If the outcome of an event A is m successes and n failures, all these
likely to occur equally (coin toss falling on heads or tails), then the
probability of success is:
m
p=
m+n
(F-31)
This is the multiplication law of probability.
The probability of an event happening r times in n trials is
given by:
∑ yz = a∑ y + b∑ xy + c∑ y2
F-5
(F-30)
The probability of two events happening together is the product of
their probabilities:
F-4-2 Multiple Regression
z = a + bx + cy
∑y 2 = 535
This is the addition law of probability.
If two events A and B are not mutually exclusive, then the
probability of the event that either A or B or both will occur is
given by:
where:
∑ xy = a∑ x + b∑ x 2 + c∑ x 3
∑xy = 543
This is the binomial distribution P(r).
Example F-3 Consider that 10 percent of manufactured cars have
defective seat belts. Determine the probability that out of 10 cars
sold, 2 will have defective seat belts. Here p = 0.1, q = 0.9, n = 10
Probability of zero defective seat belts is:
P(0) = 10 C0 (0 . 1)0 (0 . 9)10 = 0 . 3487
Probability that one seat belt is defective is:
P(1) = 10 C1(0 . 1)1(0 . 9)9 = 0 . 3874
(F-29)
Probability that two seat belts are defective is:
P(2) = 10 C2 (0 . 1)2 (0 . 9)8 = 0 . 1937
STATISTICS AND PROBABILITY
Probability of at most two defective seat belts is:
This is referred as standard normal density function. The corresponding distribution function is:
P(0) + P(1) + P(2) = 0 . 9298
F-6
F(z ) = P( Z ≤ z ) =
BINOMIAL DISTRIBUTION
The binomial distribution is given by Eq. (F-34).
Mean of the distribution = np
(F-35)
Standard deviation SD = s = npq
(F-36)
F-7
The Poisson distribution is a particular limiting form of the binomial distribution, where p or q is very small and n is very large.
Poisson distribution is:
mr e −m
r!
(F-37)
where m is the mean of the distribution.
The SD =
F-8
m =s
variance = m2 = s 2 = m
NORMAL OR GAUSSIAN DISTRIBUTION
p( x ) =
s 2π
2
1 x −m
−
2 s
e
−∞ < x < ∞
2π
∫e
−
z2
2 dz
(F-44)
−∞
A graph of the density function is shown in Fig. F-3.
■
The curve is symmetrical about the y-axis. The mean,
median, and mode coincide at the origin.
The area of the curve is equal to the total number of
observations.
■
f(z) decreases rapidly as z increases numerically. The curve
extends on either side of the origin.
In Fig. F-3, the areas within 1, 2, and 3 standard deviations of the
mean are indicated.
P(− 1 ≤ Z ≤ 1) = 0 . 6827
(F-38)
This is a continuous distribution and plays an important role in
measurement statistics. It is applied in insulation coordination
and lightning statistics (Chaps. 5 and 17). It is derived as the
limiting form of binomial distribution for large values of n and p,
while q is not very small.
As the measurements increase, the curve most commonly fitted
is a bell-shaped curve, called the normal or Gaussian distribution.
The density function for this distribution is given by:
1
z
1
■
POISSON DISTRIBUTION
P(r ) =
699
About 68.27 percent of the values lie between (m – s) and
(m + s)
P(− 2 ≤ Z ≤ 2) = 0 . 9545
About 95.45 percent of the values lie between (m – 2s) and
(m + 2s)
P(− 3 ≤ Z ≤ 3) = 0 . 9973 percent
About 99.73 percent of the values lie between (m – 3s) and
(m + 3s)
The total area under the curve is 1, divided into two equal parts.
The Table F-3 gives the area shown from 0 to z [= (x – m)/s].
(F-39)
where m is the mean and s is the SD.
The distribution is completely defined if the parameters s
and m are known. The corresponding distribution function is
given by:
P( x ) = P( X ≤ x ) =
2
1 x −µ
−
2 σ
e
dx
x
1
σ 2π
∫
(F-40)
−∞
The probability that x takes between values x1 and x2 is given by:
x2
P( x1 < x < x 2 ) =
∫σ
x1
1
2π
e
−
( x −µ )2
2σ 2 dx
(F-41)
If we substitute:
z=
x −µ
σ
(F-42)
where z is the standardized variable corresponding to x, then the
mean of z is 0 and the variance is 1. In such a case the density function becomes:
f (z ) =
1
2π
e
−
z2
2
(F-43)
FIGURE F-3
function.
Gaussian or normal distribution graph of the density
700
APPENDIX F
TA B L E F - 3
Area Under the Standard Normal Curve from 0 to z
0
Z
0
1
2
3
4
z
5
6
7
8
9
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
0.0000
0.0398
0.0793
0.1179
0.1554
0.1915
0.2258
0.2580
0.2881
0.3159
0.0040
0.0438
0.0832
0.1217
0.1591
0.1951
0.2291
0.2612
0.2910
0.3186
0.0080
0.0478
0.0871
0.1255
0.1628
0.1985
0.2324
0.2642
0.2939
0.3212
0.0120
0.0517
0.0910
0.1293
0.1664
0.2019
0.2357
0.2673
0.2967
0.3238
0.0160
0.0557
0.0948
0.1331
0.1700
0.2054
0.2389
0.2704
0.2996
0.3264
0.0199
0.0596
0.0987
0.1368
0.1736
0.2088
0.2422
0.2734
0.3023
0.3289
0.0239
0.0636
0.1026
0.1406
0.1772
0.2123
0.2454
0.2764
0.3051
0.3315
0.0279
0.0675
0.1064
0.1443
0.1808
0.2157
0.2486
0.2794
0.3078
0.3340
0.0319
0.0714
0.1103
0.1480
0.1844
0.2190
0.2518
0.2823
0.3106
0.3365
0.0359
0.0754
0.1141
0.1517
0.1879
0.2224
0.2549
0.2852
0.3133
0.3389
1.0
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
0.3413
0.3643
0.3849
0.4032
0.4192
0.4332
0.4452
0.4554
0.4641
0.4713
0.3438
0.3665
0.3869
0.4049
0.4207
0.4345
0.4463
0.4564
0.4649
0.4719
0.3461
0.3686
0.3888
0.4066
0.4222
0.4357
0.4474
0.4573
0.4656
0.4726
0.3485
0.3708
0.3907
0.4082
0.4236
0.4370
0.4484
0.4582
0.4664
0.4732
0.3508
0.3729
0.3925
0.4099
0.4251
0.4382
0.4495
0.4591
0.4671
0.4738
0.3531
0.3749
0.3944
0.4115
0.4265
0.4394
0.4505
0.4599
0.4678
0.4744
0.3554
0.3770
0.3962
0.4131
0.4279
0.4406
0.4515
0.4608
0.4686
0.4750
0.3577
0.3790
0.3980
0.4147
0.4292
0.4418
0.4525
0.4616
0.4693
0.4756
0.3599
0.3810
0.3997
0.4162
0.4306
0.4429
0.4535
0.4625
0.4699
0.4761
0.3621
0.3830
0.4015
0.4177
0.4319
0.4441
0.4545
0.4633
0.4706
0.4767
2.0
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
0.4772
0.4821
0.4861
0.4893
0.4918
0.4938
0.4953
0.4965
0.4974
0.4981
0.4778
0.4826
0.4864
0.4896
0.4920
0.4940
0.4955
0.4966
0.4975
0.4982
0.4783
0.4830
0.4868
0.4898
0.4922
0.4941
0.4956
0.4967
0.4976
0.4982
0.4788
0.4834
0.4871
0.4901
0.4925
0.4943
0.4957
0.4968
0.4977
0.4983
0.4793
0.4838
0.4875
0.4904
0.4927
0.4945
0.4959
0.4969
0.4977
0.4984
0.4798
0.4842
0.4878
0.4906
0.4929
0.4946
0.4960
0.4970
0.4978
0.4984
0.4803
0.4846
0.4881
0.4909
0.4931
0.4948
0.4961
0.4971
0.4979
0.4985
0.4808
0.4850
0.4884
0.4911
0.4932
0.4949
0.4962
0.4972
0.4979
0.4985
0.4812
0.4854
0.4887
0.4913
0.4934
0.4951
0.4963
0.4973
0.4980
0.4986
0.4817
0.4857
0.4890
0.4916
0.4936
0.4952
0.4964
0.4974
0.4981
0.4986
3.0
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
0.4987
0.4990
0.4993
0.4995
0.4997
0.4998
0.4998
0.4999
0.4999
0.5000
0.4987
0.4991
0.4993
0.4995
0.4997
0.4998
0.4998
0.4999
0.4999
0.5000
0.4987
0.4991
0.4994
0.4995
0.4997
0.4998
0.4999
0.4999
0.4999
0.5000
0.4988
0.4991
0.4994
0.4996
0.4997
0.4998
0.4999
0.4999
0.4999
0.5000
0.4988
0.4992
0.4994
0.4996
0.4997
0.4998
0.4999
0.4999
0.4999
0.5000
0.4989
0.4992
0.4994
0.4996
0.4997
0.4998
0.4999
0.4999
0.4999
0.5000
0.4989
0.4992
0.4994
0.4996
0.4997
0.4998
0.4999
0.4999
0.4999
0.5000
0.4989
0.4992
0.4995
0.4996
0.4997
0.4998
0.4999
0.4999
0.4999
0.5000
0.4990
0.4993
0.4995
0.4996
0.4997
0.4998
0.4999
0.4999
0.4999
0.5000
0.4990
0.4993
0.4995
0.4997
0.4998
0.4998
0.4999
0.4999
0.4999
0.5000
Tables of distribution to higher decimal accuracies are available. Note that the area to the right and left becomes 0.5 only at plus and minus infinity.
STATISTICS AND PROBABILITY
F-9
701
WEIBULL DISTRIBUTION
IEC standard1 recommends use of the Weibull distribution to represent the discharge capability of the external insulation. Note that
the Gaussian distribution is unbounded to the right and left and is
defined between plus and minus infinity. From the electrical application point of view there is a probability of flashover even with
minus infinity; that is, when the voltage is zero.
The general expression for Weibull distribution is:
P(V ) = 1 − e
FIGURE F-4
Gaussian distribution of data in Example F-4.
( )
−
V −δ
β
γ
(F-45)
where d is truncation value, b is the scale parameter, and g is the
shape parameter.
Equation (F-45) can be modified to depict the discharge
probability of insulation with a truncated discharge probability
by substituting the truncation value d and the scale factor b.
δ = V50 − Nσ
Example F-4 Consider that in a normal distribution, 40 percent
of the data is under 50 and 5 percent is over 80. What is the mean
and SD.
The graphical construction from the given data is shown in
Fig. F-4. This gives:
z1 =
50 − µ
σ
and
z2 =
80 − µ
σ
From the percentage distribution shown, area between 0 and
z1 = 0.5 – 0.4 = 0.1. From Table F-3, the value of z1 = –0.253
(interpolate)
50 − µ
= − 0 . 253
σ
(F-46)
−1
β = Nσ (ln 2)
γ
where N is the number of conventional deviations between V50 and
V0 of a self-restoring insulation, and s is the conventional deviations of the discharge probability function P(V) of a self-restoring
insulation.
This leads to the modified Weibull function:
V −V50 γ
1+
P(V ) = 1 − 0 . 5 Nσ
(F-47)
The exponent is determined by the condition that:
P(V50 − σ ) = 0 . 16
(F-48)
This gives:
For the percent distribution shown, area between 0 and
z 2 = 0.5 – 0.05 = 0.45. From Table F-3, the value of z 2 = 1.645
(interpolate)
80 − µ
= 1 . 645
σ
Thus m = 53.9989 and SD = s =15.8061.
Example F-5 Consider production of a product where m = 110,
and the standard deviation is 1.0. What percentage of the product
deviation falls between 109 and 111?
z1 =
109 − 110
= −1
1
z2 =
111 − 110
=1
1
ln(1 − 0 . 16)
ln
ln 0 . 5
γ=
ln(1 − (1/N )
For external insulation, it is assumed that no discharge is possible
(withstand probability = 100 percent) at a truncation value:
V0 = V50 − 4σ
(F-50)
Substituting N = 4 in Eq. (F-49) gives g = 4.85, approximated as
percentage. Introduce the normalized variable:
x = (V − V 50 )/σ
(F-51)
The Weibull flashover probability distribution is:
P(V ) = 1 − 0 . 5(
1+
The area between 0 and z1 = area between 0 and z2 = twice the area
between 0 and z2 = 0.683 from the Table F-3. Thus, 68.26 percent
of the product will fall between 109 and 111.
(F-49)
x
4
)
5
(F-52)
The comparison with Gaussian distribution is shown in Fig. F-5a
and b.
702
APPENDIX F
F I G U R E S F - 5 Comparison of Gauss and Weibull functions of disruptive discharge probability of self-restoring insulation. (a) Described on a linear
scale. (b) Described on a Gaussian scale.1
REFERENCE
1. IEC Std. 60071-2, Insulation Coordination, Part-2: Application
Guide, 1996.
FURTHER READING
F. M. Dekking, C. Kraaikamp, H. P. Loupaä, L. E. Meester, A Modern
Introduction to Probability and Statistics (Springer Texts in Statistics),
Springer Verlag, London, 2005.
J. L. Devore, Probability and Statistics for Engineering and Sciences,
Brooks/Cole (Duxbury Press), 2007.
M. R. Spiegel, J. J. Schiller, R. A. Srinivasan, Theory and Problems of
Probability and Statistics, 2d ed., Schaum’s Outline Series, McGraw Hill,
New York, 2000.
APPENDIX G
NUMERICAL TECHNIQUES
We used Laplace transform method in Chap. 2 for solution of
simple circuits, and toward the end of this chapter concluded that
the theoretical analysis methods using Laplace transforms are not
suited to large systems; nonlinearity and saturation cannot be
accounted for. Computerized methods to take account of nonlinearity may use:
■
Piecewise linearization, example of saturation in transformers
(Chap. 14)
■
Exponential segments of arrester models (Chap. 19)
■
One-time step-delay methods—pseudo-nonlinear devices
■
Iterative Newton methods
G-1
NETWORK EQUATIONS
Consider a network of connections as shown in Fig. G-1. For the
inductance branch, nodes 1 and 3, we can write:
v=L
di
dt
(G-1)
In terms of difference equation:
v(t ) + v(t − D t )
i(t ) − i(t − D t )
=L
2
Dt
(G-2)
Dt
(v (t ) − v3 (t )) + hist13 (t − D t )
2L 1
(G-3)
where hist13 term is known from the preceding time step:
hist13 (t − D t ) = i13 (t − D t ) +
i15 (t ) =
1
v (t ) + hist15 (t − τ )
Z 1
Dt
[v (t − D t ) − v3 (t − D t )] (G-4)
2L 1
For the capacitance circuit, we can similarly write:
hist14 (t − D t ) = −i14 (t − D t ) −
2C
(v (t − D t ) − v 4 (t − D t ))
Dt 1
(G-5)
(G-6)
1
hist15 (t − τ ) = − v5 (t − τ ) − i51(t − τ )
Z
where z is the surge impedance and t is the line length/velocity of
propagation. Therefore for node 1, we can write:
1 D t 2C 1
1
2C
Dt
+
+ v1(t ) − v2 (t ) −
v3 (t ) −
v (t )
+
R
L
t
Z
R
L
D
Dt 4
2
2
= i1(t ) − hist13 (t − D t ) − hist14 (t − D t ) − hist15 (t − τ )
(G-7)
For any type of network with n nodes, we can write the general
equation:
Gvt = it − his t
(G-8)
where G is the nxn symmetrical nodal conductance matrix, vt is the
vector of n node voltages, it is the vector of current sources, and
his t is the vector of n known history terms.
Some nodes will have known voltages or may be grounded.
Equation (G-8) can be partitioned into a set of nodes A with known
voltages and a set B with unknown voltages, and the unknown voltages can be found by solving for vAt :
G AA vAt = iAt − his tA − G AB vBt
This can be written as:
i13 (t ) =
For the transmission line, ignoring losses:
G-2
(G-9)
COMPENSATION METHODS
In compensation methods, the nonlinear elements are simulated as
current injections, which are superimposed on linear network after
a solution without the nonlinear elements has been just found.
Figure G-2 shows one nonlinear element across linear network.
The current ikm must satisfy the following two equations:
vkm = v km−0 −R Thev ikm
(G-10)
vkm = f (ikm , dikm /dt, t,....)
(G-11)
where vkm-0 is the solution without nonlinear branch connected.
RThev is the instantaneous equivalent circuit between nodes k and m.
703
704
APPENDIX G
FIGURE G-1
A network around node 1 (for writing node equations).
FIGURE G-3
G-3
FIGURE G-2
One nonlinear element connected to a linear network.
Equation (G-11) is the relationship of the nonlinear branch. To find
Thévenin resistance, a current of 1A is injected into the node k and taken
out from node m. The network equation (G-9) can be written as:
G AA VA = kA
R Thev = rThev−k − rThev−m
(G-13)
Thus the solution proceeds as follows:
Compute node voltages without a nonlinear element
connected, with a repeat solution of Eq. (G-12).
■
From this vector and other known voltages, extract
open-circuit voltage:
(G-14)
■
Solve two scalar equations [Eqs. (G-10) and (G-11)] simultaneously to find ikm. Newton-Raphson method can be used
to solve Eq. (G-11). If Eq. (G-11) is given as a point-by-point,
piecewise linear curve, then intersection of two curves is found
by a search process (Fig. G-3).
■
The final solution is found by superimposition, which is permissible as the rest of the system is linear.
The method can be used to simulate M nonlinear branches with
current sources. M vectors, rThev−1,....rThev−M must be precomputed
and recomputed, whenever switch changes position. The Thévenin
equivalent resistance becomes a M × M matrix, R Thev.
vkm = vkm−0 − R Thev ikm
(G-15)
(G-17)
The flux l being integral over the voltage v = vk – vm
t
λ(t ) = λ(t − D t ) +
∫
v(u )du
(G-18)
t −D t
This is solved by trapezoidal rule of integration, which converts
flux l(t) into linear function of v(t):
λ(t ) =
Dt
v(t ) + hist(t − D t )
2
hist(t − D t ) = λ(t − D t ) +
(G-19)
(G-16)
Dt
v(t − D t )
2
(G-20)
Substituting Eq. (G-19) into Eq. (G-17) produces a resistance relationship by first shifting the origin by + hist(t − D t ) and rescaling
l -axis to v -axis with a multiplication factor of 2/Dt. The v-i characteristics are solved with network equation in a similar way to nonlinear
resistance. Figure G-4a and b shows representation of a linear and
nonlinear inductance. A numerical problem can arise with nonlinear
elements if Dt is too large. Artificial damping or hysteresis can occur.
G-4
PIECEWISE LINEAR INDUCTANCE
As discussed in Chap. 16, the saturation characteristics of transformers can be represented by piecewise linear inductance with two
slopes (Fig. G-5a). Such an inductance can be simulated by two
inductances L1 and Lp in parallel (Fig. G-5b). The flux in Lp is always
computed by integrating voltage vk – vm independent of the switch
position. The switch is closed whenever |λ | ≥ λsaturation and opened
again when |λ | < λsaturation. In EMTP, there is an option to start the
simulation from a user-specified residual flux. A piecewise linear
resistance can be similarly represented (Fig. G-6).
G-5
and:
vA = vA−0 − ( rThev−1,..., rThev−M ) ikm
λ = f (i)
With a known history term:
■
vkm−0 = vk−0 − vm−0
NONLINEAR INDUCTANCE
The simulation shown in Fig. G-3 is straightforward for a nonlinear
resistor defined by vkm = f(ikm). For nonlinear inductance the solution
is not so direct as the nonlinear characteristics are of the form:
(G-12)
where kA is known from right-hand side of Eq. (G-9). It is replaced with
a vector whose components are all zero, except for + 1.0 in row k and
–1.0 in row m. Then one repeat solution is performed with right-hand
side vector which produced a vector rThev. This vector is the difference
of the kth and mth columns of the inverse V matrix G−1
. Then:
AA
Solution of network equation and nonlinear element.
NEWTON-RAPHSON METHOD
Newton-Raphson method is extensively used in power-system load
flow and is best suited for system of nonlinear equations. To illustrate,
NUMERICAL TECHNIQUES
FIGURE G-4
FIGURE G-5
FIGURE G-6
(a) Representation of a linear inductor and (b) nonlinear inductor.
(a) Two-piece representation of a nonlinear inductance. (b) Circuit implementation of nonlinear inductance.
(a) Piecewise resistor. (b) Voltage source representation. (c) Current source representation.
consider that the elements are nonlinear resistances. Equation (G-15)
is rewritten as:
vkm − vkm−0 + R Thev ikm = 0
(G-21)
ikm can be replaced with a diagonal matrix f (vkm ) whose elements
are i-v characteristics of M nonlinear resistances, the nonlinear
resistance represented by a power function of the form:
v
i = p
vref
705
q
(G-22)
where p, vref, and q are constants and the voltage region is divided
into segments. Thus, we write:
ikm = f (vkm )
(G-23)
Applying Newton-Raphson method to Eq. (G-21)
−
df
R Thev km + U D vkm = vkm−0 − vkm − R Thev f (vkm )
dvkm
(G-24)
where the matrix on the left-hand side (Jacobian matrix), and the
matrix on the right-hand side are solved with appropriate answers
706
APPENDIX G
from the last iteration step h – 1. The improved solution is found by
solving the system of linear equations:
h
h−1
vkm
= vkm
+ D vkm
(G-25)
In Eq. (G-24), [dfkm /dvkm ]− is diagonal matrix of i-v characteristics,
and it destroys the symmetry of the Jacobian. To maintain symmetry
the Jacobian can be multiplied by inverse matrix [dfkm /dvkm−]−1 and
solve the equation for variable Dx.
−
−1
df
km
Dx = v
R
− vkm − R Thev f (vkm )
+
km−0
Thev dvkm
(G-26)
The Jacobian is now symmetric.
The diagonal elements of [dfkm /dvkm]–1
–
are reciprocals of [dfkm /dvkm]. After Dx has been found, the voltage
corrections are:
D vkm =
D x km
dfkm /dvkm
(G-27)
G-6 NUMERICAL SOLUTION OF LINEAR
DIFFERENTIAL EQUATIONS
In Chap. 2, we showed that a linear differential equation can be put
in the state variable form:
x = Ax + g(t )
(G-28)
The closed-form solution of Eq. (G-28), which carries from the
state of the system at t − D t to t, is:
t
x(t ) = e ADt[x(t + D t )]+
∫
e A(t−u )g(u )du
(G-29)
polynomials are of higher degree. The so-called topological formula
approach4 to computing these network functions involves finding the
trees of a network and then computing the sum of corresponding
tree-admittance branches. The number of trees may run into millions
for a network of only 20 nodes and 40 branches. The computation
of the roots of polynomials P(s) and Q(s) is “hazardous” because these
roots may be extremely sensitive to errors in coefficients. The polynomial approach is not matched to the network analysis tasks which
the computer is called upon to handle. The eigenvalue approach is
much better suited and gives the theoretical information that Laplace
transform methods are designated to provide.5
G-8
TAYLOR SERIES
The matrix exponential e ADt can be approximated by Taylor series:
e ADt = U + D tA +
D t 2 2 D t 3 3 ......
A +
A +
2!
3!
The method runs into eigenvalue problem: When matrix A has
a large eigenvalue, which means a small time constant, the time
step Dt must be kept small in order to permit rapid convergence of
Eq. (G-33).5 In stiff systems, there are large differences in the magnitudes of eigenvalues and the largest eigenvalues produce ripples,
which are not of interest. The method of using Eq. (G-33) becomes
numerically unstable for a given number of terms if Dt is not sufficiently small to trace uninteresting small ripples. The method
becomes identical with fourth-order Runge-Kutta method if fifth
and higher-order terms are neglected in Eq. (G-33).
A rational approximation of the transition matrix is provided by
E. J. Davison:6
Dt
D t 2 2 D t 3 3
e ADt = U −
A+
A −
A
2
4
12
−1
Dt
D t 2 2 Dt 3 3
A+
A +
A
U +
12
2
4
(G-34)
t −D t
where the matrix e ADt is called the transition matrix. It is transformed into a diagonal matrix, whose elements are evaluated using
eigenvalues li of matrix A and matrix of eigenvectors (modal
matrix M) of A. An efficient method of finding eigenvalues is QR
transformation,1 and for finding eigenvectors the “inverse iteration
scheme”,2 which has been modified by J. E. Van Ness.3 The diagonalized matrix is:
M −1e ADt M = e ΛDt
(G-30)
where Λ is the diagonal matrix of eigenvalues li. Once the diagonal
elements are found these can be converted back to:
e ADt = Me ΛDt M −1
(G-31)
Equation (G-31) becomes:
t
x(t ) = Me ΛDt M −1[x(t − D t )]+
∫
Me Λ(t−u )M −1g(u )du (G-32)
A lower-order approximation, which is numerically stable for
all Dt, neglects second- and higher-order terms of Eq. (G-34)
Dt
e ADt = U −
A
2
G-7
LAPLACE TRANSFORM
Laplace transform involves ratio of polynomials and the poles and
zeros thereof. The task of computing the coefficients of polynomials in a network function of P(s)/Q(s) is not only time consuming but
also prone to serious numerical inaccuracies, especially when the
−1
Dt
A
U +
2
(G-35)
This is identical with trapezoidal rule of integration discussed next.
G-9
TRAPEZOIDAL RULE OF INTEGRATION
Write Eq. (G-28) as an integral equation:
t
x(t ) − x(t − D t ) +
∫ ( Ax(u) + g(u))du
(G-36)
t −D t
By using linear interpolation on x and g between t – Dt and t, assuming x is known at t:
x(t ) = x(t − D t ) +
t −D t
The convolution integral can be evaluated in closed form for many
types of functions g(t).
(G-33)
+
Dt
A ( x(t − D t ) + x(t ))
2
Dt
( g(t − D t ) + g(t ))
2
(G-37)
Linear interpolations imply that the area under the integral in
Eq. (G-36) are approximated by trapezoidals (Fig. G-7), and
therefore the name “trapezoidal rule of integration.” The method
is identical with central difference quotients:
x(t − D t ) + x(t ) g(t − D t ) + g(t )
x(t ) − x(t − D t )
(G-38)
=A
+
Dt
2
2
NUMERICAL TECHNIQUES
FIGURE G-7
707
Trapezoidal rule of integration.
This can be written as:
Dt
Dt
Dt
A x(t ) = U +
A x(t − D t ) + ( g(t − D t ) + g(t ))
U −
2
2
2
(G-39)
This equation when premultiplied by [(U − D t )( A /2)] gives the
approximate transition matrix of Eq. (G-35). Working with trapezoidal rule of integration requires solution of linear, algebraic equations in each time step. If Dt is not changed, and so long the network
modifications occur because of switching and nonlinear effects,
the matrix [(U − D t )( A /2)]−1 for the system of equations remains
unchanged. It is therefore best to triangularize this matrix once at
the beginning and again whenever network changes occur.
The trapezoidal rule applied to the state equations results in the
same answers as the trapezoidal rule applied to individual branch
equations, which are then assembled into node equations [Eq. (G-7)].
The trapezoidal rule is of lower-order accuracy than many other
methods, however, it is numerically stable, which is more important
in power system transient analysis.
−1
G-10
The method can be used for the solution of ordinary differential
equations.
(G-40)
The fourth-order method seems to be widely used. Starting from the
known value x(t − D t ), the slope is calculated at point (Fig. G-8a):
D x (1)
= f ( x(t − D t ))
Dt
t − Dt
(G-41)
This is used to obtain an approximate value of x(1) at the midpoint 1.
1
x (1) = ( x(t − D t )) + D x (1)
2
(G-42)
Now the slope is recalculated at mid-point 1 (Fig. G-8b):
Dx
= ( f ( x (1) ))
Dt
(2 )
t−
Dt
2
(G-43)
This is used to obtain a second approximate value x(2) at mid-point 2.
x (2 ) = ( x(t − D t )) + 1 D x (2 )
2
Fourth-order Runge-Kutta method.
Then the slope is evaluated third time, now at mid-point 2 (Fig. G-8c):
D x ( 3)
= ( f ( x (2 ) )), t − D t
Dt
2
(G-45)
This is used to get an approximate solution at point 3:
x ( 3) = ( x(t − D t )) + 1 D x ( 3)
2
(G-46)
Finally, the slope is evaluated for a fourth time at point 3 (Fig. G-8(d)):
RUNGE-KUTTA METHODS
x = f ( x, t )
FIGURE G-8
(G-44)
Dx(4)
= [( f ( x ( 3) )), t]
Dt
(G-47)
From these four slopes the final value at t is obtained by using their
weighted averages:
x(t ) = x(t − D t ) +
D t D x (1)
D x (2 )
D x ( 3) D x ( 4 )
+2
+2
+
6 Dt
Dt
Dt
Dt
(G-48)
The fourth-order Runge-Kutta formula is identical with fourthorder Taylor series expansion of of the transition matrix, if the differential equations are linear, at least for the autonomous systems
with g(t) = 0 in Eq. (G-8), which becomes:
D x (1)
= A( x(t − D t ))
Dt
Dt
x (1) = U +
A ( x(t − D t )) (G-49)
2
The second slope is:
D x (2 )
D t 2
= A +
A ( x(t − D t ))
2
Dt
(G-50)
and
Dt
D t 2 2
x (2 ) = U +
A+
A ( x(t − D t ))
2
4
(G-51)
708
APPENDIX G
Equation (G-56) is a second-order corrector formula. To start
an iteration process, a predicator formula is needed. This can be
obtained by midpoint rule:
x (0 ) = x(t − 2D t ) + 2D t( f [x(t − D t ), t − D t )
FIGURE G-9
Simpson’s rule.
Then the third slope becomes:
D x ( 3)
D t 2 D t 2 3
= A +
A +
A ( x(t − D t ))
Dt
2
4
(G-52)
and
D t 2 2 D t 3 3
x ( 3) = U + D tA +
A +
A ( x(t − D t ))
2
4
(G-53)
The fourth slope is calculated as:
Dx(4)
Dt2 3 Dt3 4
= A + D tA 2 +
A +
A ( x(t − D t ))
Dt
2
4
The difference in step 3 is used to (a) decide whether step size Dt
should be reduced, and (b) improve prediction of the next step. It
is generally better to shorten the time step Dt, then to use corrector formula repeatedly in step 2. It is assumed that the difference
between the predicted and corrected values changes slowly over
the time step.
In addition to second-order methods, there are higher-order
methods, and fourth-order predictor-corrector methods seem to be
used more often. Amongst these methods are Meline’s method and
Hamming’s method; the latter is usually more stable numerically.
The convergence and numerical stability of corrector formulas are
more important than those of the predicator formulas. These two
should be of the same order in error terms. There are different
classes of predictors: Adams-Bashforth predictors, obtained by
integrating Newton backward interpolation formulas, Meline-type
formulas, obtained by an open Newton-Cotes forward integrating
formula, and others. Formulas requiring values at t – 2Dt are not
self-starting; Runge-Kutta methods are sometimes used to build
enough history points.
G-12 RICHARDSON EXTRAPOLATION AND
ROMBERG INTEGRATION
(G-54)
Finally, the new value is obtained as:
Dt2 2 Dt 3 3 Dt 4 4
x(t ) = U + D tA +
A +
A +
A ( x(t − D t ))
2
6
24
(G-55)
which is the Taylor series approximation of the transition matrix
in Eq. (G-33). If A = 0, that is, if x is simply the integral over
the known function g(t), the fourth-order Runge-Kutta method is
identical with Simpson’s rule of integration, in which the curve is
approximated as a parabola going through three known points in
t − D t, t − D t /2, and t (Fig. G-9). The Runge-Kutta method is subject to instability if Dt is not chosen small enough.
G-11
Instead of using higher-order methods, the second-order trapezoidal
rule is used more than once in the interval between t – Dt and t to
improve the accuracy. Assume that normal step size Dt is used to
find x(1) at t from Fig. G-10. Now repeat the integration with the
step size Dt/2, and perform two integration steps to obtain x(2). With
these two values an intelligent guess can be made as to where the
solution will end up if the step size were decreased more and more.
This extrapolation toward Dt = 0, is called Richardson extrapolation
and gives a better answer.
1
x(t ) = x (2 ) + ( x (2 ) − x (1) )
3
(G-58)
The accuracy can be further improved by repeating the integration between t – Dt and t with 4, 8, 1, …. intervals. The corresponding extrapolation formula for Dt → 0 is known as Romberg
integration.
PREDICTOR-CORRECTOR METHODS
These methods can again be used for ordinary differential equations. Apply trapezoidal rule to state equation [Eq. (G-40)]:
x (h ) = x(t − D t ) +
(G-57)
Dt
( f [x(t − D t ), t − D t]) + f ( x (h−1), t ) (G-56)
2
In the general time-varying or nonlinear case, the direct solution
is not possible. Here h indicates iteration step. The iteration works
as follows:
1. A predicator formula is used to obtain a predicted guess for
solution at time t.
2. The corrected solution is found in iteration step h = 1, 2, . . .
by inserting the approximate solution.
3. If the difference x (h ) − x (h−1) is small, then integration from
t − D t to t is completed, otherwise return to step 2.
FIGURE G-10
Richardson’s extrapolation.
NUMERICAL TECHNIQUES
REFERENCES
1. J. G. F. Francis, “The QR Transformation,” Computer Journal,
vol. 4, pp. 332–345, 1961.
2. J. H. Wilkinson, The Algebraic Eigenvalue Problem, Oxford
University Press, London, 1965.
3. J. E. Van Ness, “The Inverse Iteration Method for Finding
Eigenvectors,” IEEE Trans. Automatic Control, vol. AC-14,
pp. 63–66, Feb. 1969.
4. S. Seshu and M. B. Reed, Linear Graphs and Electrical Networks,
Addison-Wesley, Reading, MA, 1961.
709
5. F. H. Branin, “Computer Methods of Network Analysis,”
Proc. IEEE, vol. 55, pp. 1787–1801, Nov. 1967.
6. E. J. Davidson, “A High Order Crank-Nicholson Technique for
Solving Differential Equations,” Computer Journal, vol. 10,
pp. 195–197, Aug. 1967.
FURTHER READING
EMTP Theory Book, EMTP user Group, www.emtp.org.
A. Ralston, A First Course in Numerical Analysis, McGraw Hill,
New York, 1965.
This page intentionally left blank
INDEX
A
ABCD parameters, 68
of transmission line models, 67
Acceleration error, 47
Ac resistance, 677, 678
Active filters, 425
Adaptive protection, 24–27
Adjustable speed drives, 397, 399
AESOPS, 321
AGC, 325, 358, 361
Air clearances, 465, 466
based upon BIL, 466
based upon switching surge, 466
Alternate lightning protection systems (for
structures), 598
Analogue computers (TNAs), 3
Application, capacitors with nonlinear
loads, 126
Approximate long line parameters, 79
Arc furnace, 430
harmonic current spectrum, 432
reactive power swings, 431
Arc interruption, 181
arc hysteresis, 182
current zero interruption, 182
deionization, 181
low resistance arc extinction, 181
theories, 182
Cassie’s, 182
Meyer’s, 182
Slepian, 182
volt-amp characteristics, 181
Arcing fault, 558
arc reignition, 558
current, 558
Arcing fault (Cont.):
damage, 558
Artificially derived neutrals, 564
through wye delta transformer, 564–567
through zig-zag transformer, 564, 565
Asymmetry (short-circuit currents), 14,
183
Asymptotes, 52
Asymptotic behavior (stability), 692
converge asymptotically, 692
Attractive radius, 100
Auto transfer
devices for
solid state breakers, 438
static transfer switches, 438
of induction motors, 433
strategies
fast transfer, 434
fault conditions, 436
in-phase transfer, 434
momentary paralleling, 436
residual voltage transfer, 434
of synchronous motors, 437
transients due to, 432
transient torques and currents, 433
Auxiliary equation (differential equations),
650
BFR, 113, 114, 118, 474
BIL/CFO, 100, 453, 459, 460, 463, 465
Binomial distribution, 698, 699
Block diagrams, 41, 42
of state models, 44
Bode plot, 55
closed loop frequency response, 59
construction, 57
relative stability, 58
second order frequency response, 57
of simple functions, 56
Bolted fault, 207
Breakaway points, 52
Breakdown in gases, 200–204
electronegativity of SF6, 201, 483
VI characteristics, 483–484
steamer criteria, 201
Townsend criteria, 201
Breakers. See Circuit breakers
Brushless excitation
of synchronous generator, 343
of synchronous motor, 284, 285
BSL/CFO, 100, 453, 463, 466, 472, 473
Building blocks of excitation systems, 339,
340
Bundle conductors, 681, 682
Bus impedance matrix, 24
Bushing CT, 136
B
Backflashover, 105, 113–117
Back-to-back switching of capacitor
banks, 133–135
Band pass filter, 131
Bandwidth, 21
Bernoulli’s equation, A-5
C
Cable charging currents, 166
Cable constants, 685–687
calculation routines, 688
Debye model, 688
inductance, 686
711
712
INDEX
Cable constants (Cont.):
shunt admittance, 686
zero sequence impedance, 686, 687
Cable models, 87–89, 166–168
Cable types, 85
XLPE, SCLF, HPFF, MIND, oil filled,
85–87
Capacitance current interruption, 144
multiple restrikes, 145
reignitions, 145
three-phase, 147
with restrikes, 145–146
with restrikes and current chopping,
145–146
without restrikes, 145–146
Capacitance of lines, 684
capacitance matrix, 684, 685
Capacitance of transformers, 384
core type, 384
shell type, 384
Capacitance to ground of substations,
468–469
Capacitor banks
arrangements, 150
back-to-back switching, 133–135
frequency of inrush current, 133
inrush current, 133
parallel banks, 136
connections, 150
discharge currents, 136
fusing, 150
grounding, 151–152
harmonic loading, 130
harmonic resonance, 125
inrush current limiting reactors, 135
isolated, 134
at multivoltage levels, 137
overloads due to resonance, 127
propagation and mitigation of
harmonics, 130
sizing to avoid resonance, 126
Capacitor switching, 19–20
control of transients, 147
point of wave switching
(synchronous breakers), 148
reactors, 135
resistance switching, 147
surge arresters, 148
devices for (definite purpose breakers),
134
effect on bushing CTs, 136
transients
effects, 123
energizing a single bank, 123
impact on drive systems, 140
with motors, 140
origin of, 123
peak inrush current, 125
phase-to-phase overvoltages, 139
prior charge, 126
secondary resonance, 136
Carson’s formula, 682–683
CFO. See BIL/BSL/CFO
Chaotic behavior, 693
Characteristic harmonics, 126
Characteristic (surge) impedance, 69
Circuit breakers
arc interruption, 181
arc quenching mediums, 182
arc voltage, 182
asymmetrical current interruption, 183
capacitance of
live tank, 469
dead tank, 469
contact parting time, 182
control of switching OV, EHV breakers,
159, 160
with opening and closing resistors,
175, 176
current interruption with delayed
current zeros, 255–257
current zero breaker, 182
effect of power factor, 257
dc component, 183, 184
dead time, 297
definite purpose
for capacitor switching, 134
for TRV, 192
failure modes of
dielectric failure, 202, 204
thermal failure, 202, 203
generator breakers, 182, 255
asymmetry factor, 257
close and latch, 258
IEEE standard, 255
interrupting duty, 183
interrupting time, 183
K factor, 134
multibreaks per pole, 197
grading capacitors, 197
grading capacitors-ferroresonance, 197
opening time, 183
operating mechanisms
double motion principle, 204
double pressure designs, 204
puffer type, 204
self blast, 204
out-of-phase closing for, 173
prestrikes, 200
reignitions, 184
restrikes, 184
stresses in
current, 204, 205
RRRV, 204, 205
voltage, 204, 205
synchronous, 147, 148, 173, 174
tripping delay, 183
Clairaut’s equation, 649
Clarke’s transformations, 81, 82, 209
Classification of transients, 1
with respect to frequency groups, 1, 2
with respect to time duration, 2
Classification of voltage stresses, 155
Closed loop frequency response, 59
Closing and reclosing of transmission
lines, 158–161
trapped charge, 161
Coefficient of grounding (COG), 224,
226, 557
Cogging and crawling of induction
motors, 439, 440
Compensation methods, 703, 704
Compensation of lines, 169, 171, 172
Compensator, 36
lag, 36
lead, 36
lead lag, 36
Complementary function (differential
equations), 650
Complex conjugate roots, 33
Construction of sequence networks, 210
Continuous system frequency response, 38
Control systems, 33
Controller, 35
Convolution theorem, 666
Corona, 79, 105
ground level electrical fields, 80
ground level magnetic fields, 80
loss, 80
noise, 79
radio and television noise, 80
Correlation coefficient, 697
Coupled coils, 7, 244
Criteria for lightning protection of
structures (IEC), 589
Critical clearing angle, 295, 296
Cumulative probability, 95
CIGRE/IEEE curves, 98
Current injection methods, 189
Current interruption (ac)
asymmetry, 183
capacitive current, 144–146
chopping, 145, 146, 197, 198
dc component, 183, 184
first pole to clear, 185, 186
inductive current, 197, 198
prestrikes, 200
recovery voltage, 184
reignition, 145, 184, 185
restrikes, 184
RRRV, 184
TRV. See Transient recovery voltage
Current interruption in dc circuits, 615
arc lengthening principle, 615
dc arc characteristics, 615
HVDC breakers, 616
rheostatic breaker, 615
volt-amp characteristics of steady arc,
615, 616
Current limiting fuses, 551
peak arc voltage, 552
limitation of, 553
peak let-through current, 552
INDEX
Current limiting fuses (Cont.):
with surge arresters, 552
division of energy between surge
arrester and fuse, 553
Curve fitting and regression,
696, 697
D
Damped natural frequency, 33
Damping and attenuation, 79
Damping coefficient, 33
Damping ratio, 33
Dart leader-multiple flashes, 93
Data required for stability study,
301, 302
Dc component (of short-circuit current),
13, 14, 183, 184
decay of, 243
Dc short-circuit current sources, 605
Dc systems, 605
industrial and commercial, 617–618
shipboard, 618
Dc transient, 13
Definite purpose breakers
capacitor switching, 134
TRV, 192
Deionization, 181
Delay time, 49
Diagonalization (of a matrix), 77, 449,
679, 680
of transmission line matrix, 680
decoupling using symmetrical
components, 680
Dielectrics, 455
insulation resistance, 455
loss angle, 455
recovery characteristics, 455
Difference equations, 29, 675
solution of, 675
state variable form, 676
Differential equations, 3, 11, 15, 647
auxiliary equation, 650
Bernoulli’s equation, 648
Clairaut’s equation, 649
complementary function, 649, 650
calculation of, 650
steady state solution, 649
transient response, 649
degree of, 647
differential coefficient, 647
exact, 648
first order, 11
forced and free response, 649, 650
frequency domain discrete time
response, 39
higher order equations, 651
homogeneous, 647, 654
linear, 648
numerical solution of, 706
order, 647
Differential equations (Cont.):
particular integral, 649
calculation of, 651
general solution with multiple roots, 653
second order, 15
simultaneous, 655
weighting function, 650
Digital simulation, 3
Dimensioning of lighting protection
systems, 590–592
Direct lightning strokes, 104
Direct stability methods, 328–331
BCU method, 329–330
controlling u.e.p method, 329
equilibrium point, 328
global stable equilibrium point, 328
network preservation methods, 329
network reduction methods, 329
stability boundary, 329
stable and unstable manifolds, 328
Discharge currents of parallel capacitors,
136
Disconnecting three-phase capacitors,
147
Discrete Fourier Transform (DFT), 632
Discrete time systems, 28
Discrete unit impulse, 670
Discrete unit step, 670
Displacement power factor, 423–424
Dissipation array systems (DAS), 600–602
Distortion by mode propagation, 78
Double frequency TRV, 189–191
Double line-to-ground fault, 215
Doubling effect, 13
dq axis, 237, 238
dq0 (0dq) axis, 246
DSTATCOM, 641
Duality models (of transformers), 389,
391
Dynamic elements, 691
Dynamic system state equations, 317, 318
linearization of, 318
E
Earth fault factor, 224–225
Eddy current loss (transformers), 367
Effect of harmonics, 127
Eigenvalues, 209
and stability, 317, 318
Eigenvectors, 209
Electronegativity, 200
ELF fields (effect on humans), 2, 602
emf sources, 602
levels, 602
monitoring and survey, 602
screening, 602
WHO position, 602
EMF of pulsation (transformer EMF), 244
EMF of rotation, 245
EMF of three-phase windings, 272
713
EMTP, 3
models (see each chapter and also models)
simulations (see examples in each chapter)
TACS, 3, 61
type programs, 3
Energy functions and stability, 691
constituency relations, 691
dynamic elements, 691
equilibrium points, 691
stability of equilibrium points, 692
passivity, 691
state equations, 692
Equal area criteria of stability, 295, 296
critical clearing angle, 296
Equivalent circuits (see each chapter)
Exact differential equations, 648
Excitation systems (of synchronous
machines), 333
building blocks of, 339, 340
fast response, 337
normal response, 337
per unit systems, 337
nonreciprocal, 337
reciprocal, 337
reactive capability curve, 333–335
steady state stability curves, 336
saturation characteristics of exciter, 340
ac exciter, 341–342
dc exciter, 340–341
stability of
open and closed loop response, 338
types of, 343
ac exciter AC2A, 346–347
dc exciter DC1A, 344
static exciter ST1A, 344–345
UEL/URAL limits, 335
windup and nonwindup limits, 342–343
gating function, 343
Exponential cosine wave, 191
Exponential damping, 14
F
FACTS, 414–423
custom power, 414
NGH-SSR damper, 422
STATCOM/STATCON, 415–416
VI characteristics, 417
static series synchronous compensator
(SSSC/SPFC), 416–418
synchronous voltage source, 414–415
active and reactive power control,
414–415
unified power controller (UPFC),
419–422
Factors effecting stability, 297–298
Failure modes of circuit breakers, 202–204
Fall of potential (outside a grounding
grid), 581–582
influence of buried pipelines, 583
Fault decrement curve, 243
714
INDEX
Faults, symmetrical and unsymmetrical, 207
analysis (using symmetrical
components), 211–220
detection in high resistance grounded
systems, 560, 561
decrement curve (of generator), 243
double-line-to-ground, 215
line-to-ground, 213, 214
matrix methods, 221–224
symmetrical, 207
three-phase, 215, 216
unsymmetrical, 207
Feed back transfer function, 35
Ferranti effect, 74
Ferroresonance, 169, 391–393
capacitance limits for, 393
parallel, 393
series, 393
Final value theorem, 662
Finite element methods, 577–579
First order pulse transients, 14
First order transients, 11
First pole-to-clear factor, 185–186
Flicker, 429–430
arc furnace loads, 430–431
control of, 432
TCR/SVC/STATCOM, 432
frequency range/voltage variations,
429
IEC flicker meter, 429
planning and compatibility levels,
429–430
plt, pst, 429
SCVD, 430
Forced response, 18, 649
Formation of clouds, 91
electrification mechanisms, 91
lifted condensation level (LCL), 91
theories, 91
tripole structure, 91–92
Forward transfer function, 35
Fourier transform, 5, 669
correspondence with Laplace transform,
667
Free response, 649
Frequency
dependent models. See Models
of flux pulsations, 441
natural, 17, 184, 442, 444
of steady state excitation, 446
TRV, 184
resonant, 17, 21, 49, 126, 410
oscillatory, 318
scan, 127
subsynchronous, 441
subharmonic, 411
Frequency dependent modeling, 2
transformer models, 365
transmission line models, frequency
dependent, 688
Frequency of direct strokes on T-lines,
102
electrogeometric model, 102–103
Eriksson’s model, 102–103
ground flash density, 98
protective shadow of structure, 102
Frequency domain response, 49
gain margin, 49
phase margin, 49
G
Gain of a system, 38
Gate function, 663
Gaussian distribution, 699, 700
General feed-back theory, 35
Generalized machine theory, 265
Generalized wave equations, 77
Generators (synchronous), 234
behavior on terminal short-circuit, 239
calculation procedures of transients, 249
circuit equations, unit machine, 244, 245
circuit model, 248, 249
connections of
step up (utility), 235
bus connected (industrial), 235
damper circuits, 241, 242
decoupled circuits dq axes, 248–249
equations for terminal short-circuit, 254
equivalent circuits during fault, 241–243
fault decrement curve, 243
on infinite bus, 257–263
harmonics, rotation of, 127
I 22 t ratings, 235
block circuit diagram, 260, 261
manufacturer’s data, 255
conversion from, 255
model-steady state, 252–253
negative sequence capability, 235
NEMA short-circuit capability, 235
Park’s transformation, 246–247
Park’s voltage equation, 247, 248
reactances
leakage, 237
negative sequence, 237
Potier, 237, 239
quadrature axis, 237
saturation of, 238
subtransient, 237
synchronous, 237
transient, 237
zero sequence, 237
reactance matrix, 246, 247
transformation of, 247
reactive capability curve of, 333–335
SCR, 336, 337
short-circuit at no-load, 253–254
short-circuit withstand, 235
symmetrical short-circuit, 253–254
terminal short-circuit, 239
Generators (synchronous) (Cont.):
three-phase terminal fault, 235
time constants
armature, 239
open circuit, 238
subtransient, short-circuit, 238
transient short-circuit, 238
typical data of 240
Geomagnetic storms, 3, 391–392
Geometric mean distance, 678
Geometric mean radius GMR, 678
GIC model (of transformers), 391, 392
GIS, 477
breakdown in, 480
disconnector induced transients, 477–479
external transients, 461
insulation coordination in, 487–488
surge arresters for, 488
modeling of transients in, 484
switching induced transients, 480
effect of operating voltage, 480
TEV/TGPR, 481
effect of capacitance at entrance, 482
effect of ground straps, 482
effect of grounding grid, 482
transient electromagnetic fields, 483
trapped charges, 480
Gorges phenomena, 283
Ground flash (lightning), 92
density, 98
Grounding grids
behavior under lightning impulse, 583–584
impulse response, 584
transient behavior of, 594
conductors (grid), 573
decrement factor (of grounding
current), 574
finite element method, 577–579
grid current, 574
grid resistance, 573, 574
limitations of simplified equations, 574
Grounding systems, 557–558
bonding, 579–581
COG, 156, 224, 226, 557
of low voltage industrial distributions,
557–558
multiple grounded systems, 495
equivalent circuit of, 497
NEC requirements, 497
NESC requirements, 498
lightning surge dissipation, 498
PEN, 496
reactance grounding, 564
resistance grounding, 560
high resistance, 560–563
high resistance fault localization,
alarms, 561
high resistance–advantages,
limitations, 561–562
low resistance, 560
INDEX
Grounding systems (Cont.):
resonant grounding, 564
sequence components
effectively grounded systems, 557
ungrounded systems, 557, 563
solid grounding, 561
arc fault, 561
arc fault current, 561
arc fault damage, 561
ungrounded systems, 563
artificially derived neutrals, 564
overvoltages, insulation stresses,
563–564
zig-zag transformer, 565
of utility, 557
Grounding systems for electrical safety, 569
criteria, 569
fall of potential outside grid, 581–582
GPR, 569
influence of buried pipelines, 583, 584
voltage induced on buried pipelines,
584
maximum grid current, 574
maximum step and touch voltages, 574
mesh and transfer voltages, 571
shock duration, 570
soil resistivity, 571, 572
measurements, 571
Wenner’s method, 571
split factor (current), 571
programs for calculations of SMECC,
PATHS, 573
worst ground fault current, 571
Grounding, variable drive systems, 567
common mode voltages, 568
insulation stresses, 569
GTO, IGCT, MOS, MTO thyristors, 401
controlled series capacitor, 408–411
H
Half power frequencies, 21
Harmonics, 126
analysis of, 136
classification of, 126
displacement power factor, 423, 424
distortion power, 423
effects of, 126, 127
emission
arc furnaces, 430, 432
GCSC, 413, 414
switch mode power supplies, 518
TCR, 406
three level converter, 402–403
three-phase bridge (CSI), 397–398
form factor, 398
generation of, 397
nonlinear loads, 397
harmonic load flow, 131
interharmonics, 397
Harmonics (Cont.):
mitigation of, 130
active filters, 425
phase multiplication, 399
single tuned filter, 131
noncharacteristics, 397
nonlinear loads, 397
propagation of, 130
pulse number, 397
rotation of, 127
resonance, 126
frequency scan, 127
ripple content, 398
spectrum, 127
subharmonics, 397
TDD, 131
Hartman-Grobman linearization theorem,
692
Heavyside shifting theorem, 652
Higher order differential equations, 651
Homogeneous equations, 647, 654
Hurwitz stability criteria, 40
HVDC breakers, 616
advantages, 618, 619
asynchronous link, 618
synchronous link, 618
artificial current zero, 616
configurations, operating modes, 619–620
control and operation of, 624
reactive power requirements, 625
earth return, 620
harmonics (dc side), 620
HVDC transmission, 618
line commutated CS1, 620–621
MRTB, 616, 621
short-circuit ratio, 625
impact of low short-circuit ratio, 625
terminal layout, 620
typical thyristor waveforms, 622
VSC-based HVDC, HVDC-light, 625,
627
Hysteresis
loop, 375
loss, 367
model, 375–377
I
IEC TRV profiles, 193–195
IGCT, 401
I 22 t capability (of generators), 235
Image conductors, 682
Impact of trapped charge, 161
Impedance forms, 9
Impulse function, 663
Impulse response (of grounding systems),
584
Inductance capacitance excited by dc
source, 7
Induction generators, 271
715
Induction motors, 265–271
cogging and crawling of, 439–440
harmonic synchronous torques, 440,
441
currents and torques on re-switching,
433, 434
double cage rotors, 269, 270
model with saturation, 270, 271
negative sequence characteristics,
273, 274
equivalent circuit, 274
short-circuit transients, 274
ac component, 274
dc component, 274
short-circuit time constant, 274
time constant dc decay, 274
stability on voltage dips, 271, 273
starting considerations, 278
starting methods, 274–278
starting transients, 279
study of, 279
steady state operation, 267–269
sudden loss of voltage, 433
decay of residual voltage, 434–435
tooth ripples, 441
torque equation, 268, 269
torque matrix, 269
torque slip characteristics, 272
torque speed characteristics, NEMA
designs, 272
transient and steady state models,
265–269
Inertia constant (H), 298
Infinite line, 74
Inherent TRV, 187
Initial TRV, 197
Initial value theorem, 662
Instantaneous power theory, 424, 425
Insulation breakdown, 456
consequences of, 458
effect of gas density, 457
in liquid dielectrics, 458
in solid dielectrics, 458
in vacuum, 457
Insulation characteristics, 459
BIL/BSL, 459
nonstandard waveform, 461
phase-to-ground withstand, 459
phase-to-phase withstand, 459
standard switching impulse, 460
VI characteristics, 461
front chopped, 461
tail chopped, 461
Insulation coordination, 453, 466, 467
air clearances, 465
atmospheric effects/pollution, 453
contamination severity, 454
BFR, 474
flashover of gaps in parallel, 465
of GIS, 487, 488
716
INDEX
Insulation coordination (Cont.):
of industrial systems, 468
minimum time to breakdown, 465
Monte-Carlo method, 474
MTBF, 474
open breaker position, 474
probabilistic concepts, 462–464
nonrestorable insulation, 463
nonstandard atmospheric conditions,
464
risk of failure, 470, 471
statistical safety factor, 471
SWV/SOV, 470
SFOV, 469
Brown’s method, 473
deterministic method, 472
phase peak and case peak methods,
472
simplified approach, 474, 475
SSFOR, 473
Brown’s method, 473
of substations, 468
of transmission lines, 467
Insulating materials, 453
heat resistance, 455
non-self-restoring, 453, 463
relative permittivity of, 687
self-restoring, 453
CFO, 453, 466
thermal aging, 456
Insulators, 454
creepage distance (IEC), 454
tests, 454
salt fog/Kieselghur/wet
contamination, 454
Interarea oscillations, natural damping,
317
Internal LPS systems (IEC), 594–595
Interrupting time (breakers), 183
Interruption of ac currents. See Current
interruption (ac)
Interruption of capacitance current,
200
Inverse Laplace transform, 659
by residue method, 666, 667
Inverse z-transform, 672
by partial fractions, 674
by residue method, 674, 675
Isolated cable switching, 166
J
Jacobian matrix, 323, 705
Jury array, 40
K
K factor (of circuit breakers), 134
Keraunic level, 98, 99
Kirchoff’s laws, 25
Kurtosis, measurement of, 696
L
Lagrange’s equation, 655
Laplace transform, 5, 10, 12, 34, 659, 706
convolution theorem, 666
correspondence with Fourier transform,
667
of a derivative, 661
of an integral, 661
method of partial fractions, 659
periodic function, 665
properties, 659
ramp signal, 616
second shifting theorem, 663
solution of differential equations, 662
simultaneous equations, 662
of tf(t) and (1/t)f(t), 662
unit step function, 663
LaSalle’s invariant principle, 692
Lattice diagrams, 71
Least square line, 697
Least square parabola, 698
regression curve, 697
Lightning discharge, 92
dart leader, 93
ground flash, 92
multiple flashes, 93
return stroke, 93
stepped leader, 92
Lightning parameters, 94
CIGRE approximations, 112
cumulative distribution, 95
cumulative probability, 95
Gaussian distribution, 463, 464, 699,
700
log-normal function, 94
ground flash density, 98
Keraunic level, 98
median values, 95
variations, 98
Lightning protection of structures, 587
according to NFPA 780, 594
class I materials, 597
class II materials, 597
of ordinary structures, 596
risk assessment, 595
tolerable lightning frequency, 596
alternate technologies, 598
coaxial cables, 602
ionizing terminals, 600
laser beam systems, 600
lightning prevention systems (DAS),
600–602
multi-photon ionization, 600
sharp versus blunt terminals, 598
criteria for protection, 589
lightning flashes to earth, 589, 590
LPS types, 589
dimensioning of lightning protection
systems, 590
positioning of air terminals, 592
Lightning protection of structures,
dimensioning of lightning protection
systems (Cont.):
rolling sphere radius (IEC), 592
step and touch voltages, 594
internal LPS systems (IEC), 594–595
parameters of lightning current (IEC),
587–590
risk assessment according to IEC, 588
calculations, 589
probability of fire, 589
probability of spark, 589
Lightning strokes, 98. See also
Transmission lines
frequency of direct strokes, 102
on ground close to T-lines, 107
induced lightning voltages, 108, 468
on ground wires, 107
on OH lines, 99
attractive radius, 100
striking distance, 100
shielding, 108–114
SFFOR, 108, 109
on towers, 104
Line commutated CSI, 620, 622
dc voltage, 622
operating angles, 623
Line insulation for switching surges, 159
Line-to-ground fault, 211, 213
Linear and nonlinear systems, 5
Linear approximation, 30
Linear differential equations, 650
Linear systems time domain analysis, 6
Linearization of dynamic systems, 30, 260
state equations, 317
Linearized small signal model (of
synchronous machine), 353
Load frequency control (LFC), 358
dead band, 361
speed governing, 361
Load models, 324, 325
bottom up approach, 324
component based, 324
exponential, 325
measurement based, 324
quadratic expressions, 325
sequential load method of analysis, 325
top down approach, 324
Load rejection, 168, 169
Local mode oscillations, 317
Loop and nodal matrix methods, 24
Lumped circuits, 5
Lumped and distributed parameters, 5
Lyapunov function, 692
M
Manley-Rowe equations, 693
Mason’s signal flow gain formula, 41
Maximum switching overvoltages (lines
and cables), 166
INDEX
Maximum system voltage, 155, 156
Mean, mode and median, 695
Mean and standard deviations, 695
Mesh and transfer voltages (grounding
systems), 570–571
Metal oxide gapless surge arresters,
529
alpha equation, 529
construction and operation, 529
duty cycle voltage, 532
energy absorption capability, 529
equivalent circuit, 531
lightning and switching surge discharge
currents, 533, 534
MCOV, 531, 532
pressure relief current, 529
response to lightning surges, 534, 536
switching surge capability, 531
switching surge durability, 537, 538
TOV, 532–533
Method of partial fractions, 659, 660
Modal analysis, 77
M matrix, 77
modes three phase lines, 78
modes single phase lines, 78
Models (also see each chapter)
of cables, 87
P model, 87
FDQ model, 87
of classical stability, 299–300
of electrical arc, 182
of electronic equipment and FACTS,
397–425
of excitation systems, 343–347
frequency dependent, 2
of GIS equipment, 484–485
of GIS transients, 484–487
of grounding systems, 557–585
induction motors, 265
with saturation, 270–271
steady state and transient, 265–270
of lightning surges, 545
of prime movers, 358
of PSS, 352–355
of surge arresters, 544, 545
of synchronous generators (for stability)
ANSI/IEEE models, 306
E″ model, 305
E′q model, 304
linearized small signal, 355, 356
steady state, 252, 253
of transformers
frequency dependent, 365
high frequency, 383–384
hysteresis loop, 375–377
modeling guidelines, 366
of transformers EMTP
BECATRAN, 377–379
FDBIT, 380, 381
Hysdat, 375, 376
Satura, 373–375
Models (also see each chapter) (Cont.):
of transmission lines, 65
CP model, 81–82
EMTP, 81
FD model, 82
P model, 81
for transient studies, 81
Modified Arnoldi’s method, 321
Monte-Carlo method, 474
Multiloop circuit, 34
Multiple reflections, 184
N
Natural frequency. See Frequency
Negative feedback, 35
Negative sequence components, 208
Negative sequence impedance network,
210, 212
NERC, 633
Network reduction, 8
NGH-SSR damper, 422
Nonlinear resistors, inductors, and
capacitors, 691, 704
Normal distribution, 699
Normalized damping curves, 25, 26
Norton current equivalent, 7
Numerical techniques, 302, 703
compensation methods, 703
modified Euler, 303
network equations, 703
general equation, 703
Newton-Raphson method, 704, 705
Jacobian matrix, 705
predicator-corrector methods, 708
second order corrector formula,
708
Richardson extrapolation, 708
Romberg integration, 708
Runge-Kutta method, 303, 707, 708
solution of differential equations, 706
trapezoidal rule of integration, 706, 707
Nyquist diagram, 60, 61
O
On-line security assessment 361, 362
SSA, DSA, 362
Opening time of breakers, 183
Operating chart of a generator, 335
Oscillatory stability, 354
Other sources of transients, 3
Out of phase closing, 173
breaker duties, 173
stresses, 173
Out of phase synchronizing, 449
delayed current zero, 449, 450
Overvoltages
closing and reclosing of transmission
lines, 158–161
trapped charges, 161
717
Overvoltages (Cont.):
control of (discussions and examples
throughout the book)
closing resistors, 175, 176
current limiting reactors, 135, 147
line compensation, 173
power frequency overvoltage factor, 161
snubber circuits, 370
surge arresters, 143, 173, 525
surge capacitors, 547
synchronous operation (point of
wave switching), 148, 173, 174
transient overvoltage factor, 161
voltage regulators, 517
diagrammatic representation, 156
due to ground faults, 224
due to resonance, 164–165
IEC classification of, 156, 157
lightning, 155
phase-to-ground, 162
phase-to-phase, 162
power frequency, 155, 156
self excitation of induction motors,
143, 145
switching, 155, 159
temporary, 156
capacitor switching, 123
due to faults, 156
ferroresonance, 156, 169, 171
line-to-ground fault, 224–226
load rejection, 156, 168–169
off loading of generators, 156
transformer energization, 368–370
transformer energization with
capacitors, 137–139
P
Paschens curve, 457
Parallel compensated line, 199
Parallel RLC circuit, 18–20
Park’s transformation, 246, 247
voltage equation, 247, 248
Partial differential equations, 655
complementary function, 656
nonhomogeneous linear, 656
particular integral, 656
solution of, 656, 657
Passivity, 691
Pathfinder project, 110
PCC (point of common coupling), 131
PEALS, 321
Period (time duration) short-circuit
current, 241
steady state current, 241, 243
subtransient current, 241, 243
transient current, 241, 243
Periodic function, 665
Periodic inputs, 693
chaotic behavior, 693
Manley-Rowe equation, 693
718
INDEX
Phase-constant, 69
Phase portrait, 27
Phase shift–transformer windings, 219,
220
Piecewise linear inductance, 704
Piecewise linearization, 703
Point of wave switching, 148
Positive sequence component, 208
Potential coefficient matrix (transmission
lines), 685
Power Electronics, 397
converters for FACTS, 401–402
FACTS controllers, See FACTS
FC-TCR, 405–406
V-Q curve, 407
GCSC, 413–414
nonlinear loads, 397
Pulse width modulation, 404–405
SVC, 405
SVG, 405
TCR, 405
TSC, 405
TSC-TCR, 406–407
VI Characteristics, 408
three level converter, 402–404
harmonic voltages, 468
three phase bridge, 397
commutation and overlap angle,
399–400
form factor, 398
harmonics, 398
pulse number, 397
ripple content, 398
voltage source bridge, 401
Power factor (displacement) of a
controller, 423, 424
distortion power, 423
Fryze theory, 423
Kusters and Moore theory, 423
Power frequency overvoltage factor, 159
Power invariance (in symmetrical
components), 210
Power quality problems, 516
for computers, 520
mitigation of, 516, 517
Power system stability, 293
classical stability model, 299, 300
limitations of, 301
classification of, 293
rotor angle, 293
static stability, 294
voltage instability, 293, 294
data required for analysis, 291, 302
direct methods, 328, 331
Eigenvalues, 317, 318
characteristic vectors, 317
equal angle criteria, 295
critical clearing angle, 295, 296
factors affecting, 297, 298
large perturbations, 293, 294
load shedding, 305, 307
Power system stability (Cont.):
numerical techniques
modified Euler, 303
Runge-Kutta, 303
out of step protection, 309
impedance swing plot, 309
proximity to instability, 323
shortest distance to instability, 323–324
small signal instability, 317
control mode oscillations, 317
inter-area oscillations, 317
local mode oscillations, 317
simulations of (AESOPS), 321
swing equation, 298
synchronous generator models for,
304–306
Power system stabilizers, 352
model PSS1A, 354
model PSS2A, 355, 356
oscillatory stability, 354
positive damping, 354
small signal generator model with, 356
tuning of, 355
Predicator-corrector methods, 708
Prestrikes, circuit breakers, 200
Probability, 698
binomial distribution, 699
mutually exclusive elements, 698
normal or Gaussian distribution, 699
bell shaped curve, 699
Poisson distribution, 699
standard normal density function, 700
Weibull distribution, 701
Property of decomposition, 6
Pull-in torque, 283
Pulsating torque, 281, 283
Pulse width modulation, 404
PV control of a generator, 353
Q
Quadrature axis (synchronous machines),
237, 238
equivalent circuits, 241, 242
reactances, 237, 238
time constants, 238, 239
two reaction theory, 237
Quality factor (Q), 21
Recovery voltage, 184
parallel compensated line, 199
RRRV, 184
Reflection at transition points, 71
Reflection coefficient, 71
Reignition (in circuit breakers), 145, 184
Relative stability, 58, 59
Representation of sources, 6, 7
Resistance grounding, 560
high resistance, 560
low resistance, 560
Resistance switching, 146–148, 175
Resistivity, 557, 570
of natural soil, 557, 570
of surface materials, 571
Resonance, 21, 126
parallel, 21, 22
series, 21, 22
Resonant frequency, 7, 21, 49, 126, 410
resonant peak, 49
Resonant grounding, 564
Restrikes (in circuit breakers), 184
restriking voltage, 184
Return stroke, 93
Richardson extrapolation, 708
RL circuit, ac excitation, 12
RLC circuit
critically damped, 17
excited by ac, 17
excited by dc, 15, 16
overdamped, 17
underdamped, 17
Rod gaps, 525, 526
Romberg integration, 708
Root locus analysis, 50
angle and magnitude, 51
asymptotes, 52
breakaway points, 52
characteristic equation, 50
departure and arrival angles, 52
number of loci, 52
open loop transfer function, 51
procedure for construction/stability, 52, 55
s or z plane, 50
Rotor angle stability, 293
Routh’s criteria of stability, 39
characteristic equation, 39
Runge-Kutta methods, 707
transition matrix, 708
R
Rational algebraic expression, 35
Reactance grounding, 564
Reactance matrix (of synchronous
generators), 246, 247
Reactive power flow, 321
critical reactance, 321, 322
PQ characteristics, 321–323
voltage collapse, 323
voltage-reactive power stability, 323, 324
Reciprocating compressors, 441–444
S
s-plane, 33, 38
Saturation characteristics of exciters, 340, 342
Second order difference equations, 29
Second order step response, 21
Second order transients, 15
critically damped, 15
dc excitation, 15
over-damped, 15
under-damped, 15
INDEX
Secondary resonance, 136
overvoltages due to, 136, 137
Sequence components. See Symmetrical
components
Sequence impedances
of network components, 210
construction of, 210
Sequential load method of analysis, 325
Series capacitors, 408–410
GTO controlled (GCSC), 413, 414
subsynchronous resonance, 411–413
SF6 gas, 200
breakdown in, 200, 201, 433–434
decomposition products, 203
electronegativity, 200
insulating properties, 201–203
Shielding of transmission lines, 108
shielding designs, 110
shielding angles, 112
shielding critical angle, 110
SFFOR, 108
Short-circuit currents (transients)
calculations of
ANSI/IEEE, IEC methods, 255, 256
computer based, 224
dynamic simulation, EMTP, 207
matrix methods, 221–224
symmetrical components method,
211–221
sources of, 207
contributions from static converters,
207
symmetrical, 207
unsymmetrical, 207
double-line-to-ground fault, 216
line-to-line fault, 213, 214
single line-to-ground fault, 211, 213, 214
Short-circuit currents in dc systems, 695
approximation function, 605
charged capacitor, 614
IEC method, 614
dc motors and generators, 608–610
IEC method, 610, 611
steady state resistance, 609
transient resistance, 608
lead acid battery, 605, 606
IEC method, 607
inductance of battery cells, 605
internal resistance of battery cells, 606
matrix methods, 615
quasi steady state curve, 606
rectifier, 611, 612
IEC method, 612–614
initial rate of rise of current, 611
total short-circuit current, 514
Short-circuit ratio (SCR), 336, 337
Short-line fault, 195–197
saw tooth wave, 196
Signal flow graphs, 41
Simpson’s rule, 708
Simultaneous differential equations, 655
Single tuned filter, 131
Slepian theory, 182
Smart grids, 631
adaptive protection, 633
overtripping, 633
dynamic state of grid, 631
COMTRADE, 632
DCA, 632
FACTS, 631
MMPR, 632
PDC (phase data concentration),
632, 633
PMUs, 632, 633
PMU measurements, 633
SCADA, 632
SIPS, 632
WAMS, 631–632
total vector error (TVE), 632
SoFT, 2
Soil resistivity, 571, 572
Solid state breakers, 438, 439
Solidly grounded, 557
effectively grounded, 557
Solution of difference equations, 675
state variable form, 676
SPD characteristics, 507
clamping voltage, 508
joule rating, 508
response time, 508
sparkover voltage, 508
surge current capacity, 507
SSSC/SPFC, 416–419
Stability. See also Power system stability
of discrete time systems, 38
of equilibrium points, 692
of excitation systems, 338
of induction motors on voltage dips,
271–273
relative, 58, 59
rotor angle, 293, 294
small signal, 317–321
static, 294, 295
of synchronous motors on voltage dips,
286–287
voltage, 321–323
Standard normal density function, 699, 700
Starting methods of motors, 274–278
auxiliary motor, 278
capacitor, 278
full voltage, 275
Krondroffer, 276
low frequency, 278
part winding, 278
reactor, 276
STATCOM/STATCON, 415, 416
State equations, 692
for stability, 302
numerical solution of, 302
State variable method, 1–8
state diagrams of differential equations,
45
719
State variable representation, 25–28, 30
discrete system model, 30
state and output equations, 26
Static and dynamic systems, 6
Static transfer switches, 438, 439
Statistical studies, 175–179
Statistics, 695
coefficient of variation, 695
curve fitting and regression, 696–697
correlation coefficient, 697
variance and covariance, 695, 697
least square line, 697
parabola, 698
regression curve, 696, 697
mean mode and median, 695
mean and standard deviation, 695
standard variation, 695
skewness and kurtosis, 696
Steady state error, 47
Steam turbine fast valving, 298
Steam turbines-abnormal frequency
operation, 448–449
Steamer criterion, 201
Stepped leader, 92–93
Striking distance, 100
analytical expressions of, 100
Subsynchronous resonance, 441
Surge arresters, 525
application considerations, 541, 542
effect of lead length, 539
separation distance, 539–540
applications, 525, 543
expulsion type, 526
ideal, 525
insulation coordination with, 542
metal oxide type, 529
models of, 544–546
ratings, 527–529
reflections from other equipment,
540
valve type, silicon carbide, 526, 527
preinsertion gap, 527
Surge arresters—applications, 541
graphical coordination curve, 544
insulation coordination with, 542
insulation withstand, 543
protection levels, 543
protective ratios, 543
three-point method, 542
Surge capacitors, 173
Surge impedance (characteristic
impedance), 69, 78, 161
of cables, 78
loading, 74
of transmission lines, 78
Surge protection
of ac motors, 545
connected directly to OH lines, 547
motor insulation, 546
of capacitor banks, 548
specific considerations, 548–549
720
INDEX
Surge protection (Cont.):
of generators, 547
of vacuum contactors, 546
Surge protection—computers/electronics, 517
CBEMA curves, 520
ITI curves, 520
power quality for, 520
semiconductor failure, 518
Surge protection—LV systems, 495
exposure levels, 499
high/medium, 499, 500
grounding and bonding requirements
(NEC), 498
high frequency cross interference, 498
location categories A, B, and C, 502, 503
ground lightning stroke (IEC), 504, 505
modes of protection, 495, 496
multiple grounded systems
equivalent circuit of, 495, 496
surge voltages, 499
lightning/switching, 499
test wave shapes, 500–502
Surge protection devices, 505
connections of, 512
lattice circuit, 514
parallel connection, 514
series hybrid, 514, 515
shunt connection, 513
snubber circuit, 514
failure modes of, 512
gas tubes, 508, 509
MOVs, 509, 512
SADs, 512
typical applications of, 520, 522
Surge protection devices—LV systems
(SPD), 507
secondary surge arresters, 507, 596
TVSS, 507
application of, 507
Surge voltage distribution
across transformer windings, 389, 390
Surges transferred through transformers,
384–389
SVC, 405
FC-TCR, 405
TSC-TCR, 406, 407
Swing equation, 298, 302
Switch mode power supply, 518
Switching devices for capacitor banks, 134
definite purpose breakers, 134
Switching transients, 155
of capacitor banks, 147
control of, 147
impact on drive systems, 140, 143, 144
origin, 123
phase-to-phase overvoltages, 139
disconnecting three-phase capacitor
bank, 147
line insulation for, 157
of transformers with capacitors, 137–139
withstand capability of insulation, 157, 158
Symmetrical components, 185, 208–210
characteristics of, 209, 210
decoupling balanced systems, 680
decoupling unbalanced systems, 680
impedance transformation, 209
negative sequence, 208
positive sequence, 208
power invariance, 210
transformation matrices, 208
zero sequence, 208, 210–211
Symmetrical line at no load, 75
Sympathetic inrush, 14–23
Synchronous closing, 173
Synchronous generators. See Generators
Synchronous induction motors, 279
Synchronous motors, 278–287
brushless excitation, 284
cylindrical rotor, 279
driving reciprocating compressors,
441–442
compressor factor, 442
current pulsations, 442
forced oscillations, 445, 446
natural frequency of oscillations,
442, 444
Gorges phenomena, 283
pulsating starting torque, 281
salient solid pole, 279
stability of, 285
current and power characteristics, 286
effect of excitation controllers, 285–287
starting characteristics, 280, 281, 283
synchronizing transients, 284
V-curves, 282
Synchronous operation, 173–174
Synchronous switching, 174
Synchronous voltage source, 414, 415
T
TACS in EMTP, 3, 61
Taylor’s series, 436, 693, 706
Temporary overvoltages, 156–157
Tertiary windings (transformers), 370
Test waves, 500–502
Thermal aging of insulation, 455, 456
Thermal failure mode (of breakers), 203
Three-phase fault, 215
synchronous generators (terminal), 235
Thyristor controlled reactor (TCR), 405, 406
Thyristor switched capacitor (TSC),
405, 406
Time constants (synchronous generators),
238, 239
Time domain response, 49
overshoot, 50
rise time, 50
settling time, 50
time constant, 50
time delay, 50
Time invariance, 5
Tooth ripples, induction motors, 441
Torsional dynamics, 446
analysis, 448, 449
excitation from mechanical systems,
446, 447
spring mass models, 448, 449
steady state excitation, 446
steam turbines, 448
torque pulsation synchronous motors, 447
Total demand distortion (TDD), 131
Tower footing resistance, 104, 105
Tower top potential, 105
Townsend criteria, 200
Transfer function, 33
of discrete-time systems, 38
Transform of time signals, 6
Transformer models, 14
duality, 389–391
EMTP models
BECATRAN, 377–379
FDBIT, 380, 381
Hysdat, 375–376
Satura, 373–375
extended, 373
frequency dependent, 366
GIC, 391
high frequency, 383, 384
Transformers (transient behavior), 365
ANSI categories (withstand curves),
371, 372
core type, 371
eddy current loss, 367
electromagnetic forces, 370, 371
equivalent circuit (tap changing), 367, 377
T and P circuits, 377
hysteresis loss, 367
Steinmetz exponent, 367
inrush current, 368, 369
magnetically coupled coils, 244
leakage and mutual inductance, 244
voltage equation, 244
matrix representation, 371, 373
part-winding resonance (internal
ringing), 365, 369
phase shift in windings, 219, 220
of negative sequences, 219
reliability, 394, 395
sequence impedances, 210
shell type, 211, 212
Transient analysis programs, 3
Transient behavior
of grounding systems, 594
of induction motors, 265
of synchronous motors, 265
of transformers, 365
Transients—Classifications, 1, 2
Transients in LV systems, 495
Transients in transformers, 365
harmonics and dc component, 369
inrush current, 369, 370
oscillating neutrals, 370
INDEX
Transients in transformers (Cont.):
surge voltage distribution, 389
sympathetic inrush, 382
transient voltage impacts, 368–370
electromagnetic forces, 370–371
Transient models. See Models
Transient recovery voltage (TRV), 183–185
ANSI/IEEE standards, 191–192
breakers rated equal to or less than
100 kV, 191
breakers rated > 100 kV, 191
in capacitive and inductive circuits,
188–189
composite exponential, 191
definite purpose circuit breakers (TRV),
192
double frequency, 189
first pole to clear factor, 185–186
IEC profiles, 193–195
four parameter, 193
two parameter, 194
inherent (ITRV), 187
initial TRV, 197
one-minus cosine wave, 191
oscillatory, 194
single frequency, 186
control of short line TRV, 197
short line fault (triangular), 195
terminal fault, 186
Transmission lines, 65
approximate long line parameters, 79
attenuation constant, 69
backflashover, 113–114, 118, 474
characteristic impedance, 69
charging of, 158
closing of, 158
compensation, 168
degree of, 171
corona, 79
damping and attenuation, 79
direct strokes, 104
frequency, 102
EMTP models, 81
Ferranti effect, 74
infinite line, 74
long line wave equations, 67
lossless line, 77
modal analysis, 77
parallel compensation, 199
phase constant, 69
phase-to-ground overvoltage, 162, 164
phase-to-phase overvoltage, 162, 164
propagation modes, 78
three-phase line, 78
two-phase line, 78
reclosing of, 158, 159
reflection coefficient, 71
SFFOR, 108
shielding of, 108
surge impedance loading, 74
symmetrical line, 75
Transmission lines (Cont.):
traveling waves, 185
lattice diagrams, 71–72
tuned line, 74
velocity of propagation, 70
wavelength, 70
Transmission line constants, 677
ac resistance, 677, 678
internal, 678
proximity effect, 677
skin effect function, 677
variations of positive and negative
sequence, 688
bundle conductors, 681
reduced matrix, 681
Carson’s formula, 682
approximations to, 682
capacitance, 684
capacitance matrix, 684, 685
diagonalization, 685
potential coefficient matrix,
685
composite conductors, 679
inductance, 679
GMD, 678
GMR, 678
impedance matrix, 680
decoupling using symmetrical
components, 680
diagonalization, 680
inductance, 678
external, 678
internal, 678
three-phase line, 678
rotation matrix, 678
overall impedance matrix, 679
three-phase line with ground
conductors, 680
reduction of, 681
transposed line, 678
zero sequence impedance, 686, 687
Trapezoidal rule of integration,
706
Tripping delay (breakers), 183
TSC-TCR, 406, 407
Two-port networks, 8
TVSS, 507, 508
Types of excitation systems, 337,
343–347
Types of structures (for lightning
protection), 587, 594
U
UEL/URAL limit, 335
Underfrequency load shedding, 361
Underground cables, 85, 87
Unique steady state solution, 692
Unit machine, 244–245
circuit equations, 245
Unit step function, 15, 663
721
Ungrounded systems, 563, 564
COG, 563
overvoltages, 563
sequence impedances, 563
Unsymmetrical faults, 207
UPFC, 419, 422
UPS, 519
V
Variance and covariance, 697
Velocity error, 47
Velocity of propagation, 70
Very fast transients (VFT), 477
categorization of, 477
disconnector induced, 477–479
overvoltages, 480
maximum stresses, 480, 481
speed of operation, 480
Voltage
common mode (grounding of drive
systems), 567, 568
maximum system, 155
medium, high EHV, 155
nominal, 155–156
recovery, 184
restriking, 184
step, touch, transfer, mesh. See Grounding
transient recovery (TRV). See TRV
Voltage dips—motor starting, 278–279
Voltage instability, 293–294
large disturbance, 293–294
small disturbance, 294
Voltage notching, 399, 401
Voltage quality, 516
sags, 516
swells, 516
Voltage source three-phase bridge, 401–402
classifications, 155
4-quadrant operation, 403
three-level converter, 402–404
Voltage stability, 321
collapse of voltage, 322
critical reactance, 321, 322
limits of, 322
PQ characteristics, 323, 323
volt-reactive power problem, 325
Voltage stresses, 155
Voltage unbalance, 274
effect on induction motor loading, 274
negative sequence current, 274
Volt-amp characteristics steady arc, 615, 616
W
Wave equations, 67
generalized, 77
Wavelength, 69
Weibull distribution, 465, 701
general expression, 701
shape and scale parameters, 701
truncation value, 701
722
INDEX
Weighting function, 650
Wind generators, 639
direct coupled induction, 640
doubly fed induction, 640
full size converter induction, 640
synchronous, 640
Wind power stations (farms), 634
behavior under faults, 639, 640
FERC, 640
low-voltage ride through, 640
computer models, 642–644
cube law, 636
Beltz limit, 636
factor cp, 637
DOE/NREL, 634
drive train, 635
direct drive approach, 635
nacelle, 636
PM generator, 636, 640
energy conversion, 635
upwind rotor, 635
floating wind turbines, 645
operation, 638
feather the blades, 638
speed control, 638
yaw control, 638
Wind power stations (farms) (Cont.):
power electronics, 640
harmonics, 642
reactive power control, 641
short-circuit limitations (of
converters), 641
wild ac, 640
rotor blades, 636
towers, 636
Windup and non-windup limits, 342, 343
Worst case ground fault current, 571
Wye-delta transformation, 9
Wye-wye transformer, 370
phenomena of oscillating neutrals, 370
X
X/R ratios
of power systems, 13
of short-circuit of a rectifier, 611
of synchronous generators, 256, 257
effect on short-circuit asymmetry,
258, 259
Y
Ybus matrix, 24, 127
Z
Z-matrix (bus impedance matrix),
24, 25
Z-transform, 669
convolution, 672
definition, 669
discrete unit impulse, 670
discrete unit step, 670
important sequences, 673
initial and final value theorem,
671, 672
properties, 670
shifting property, 671
sampled discrete function, 669
of two-sided non-casual sequence,
670
Zero sequence impedance, 208,
686–687
of cables, 686, 687
of synchronous generators, 237
of transformers, 211, 212
of transmission lines, 686
of zig-zag transformer, 564, 565
Zig-zag transformer (for grounding),
564, 565