QuickSpecs

HP Managed Power Distribution Units (maPDU)

Overview

HP Managed Power Distribution Units (maPDU)

Looking for a power distribution unit that meets the demands of high temperature operating environments and provides monitoring and switching capabilities?

The HP Managed Power Distribution Unit (maPDU) provides both local and remote power management for your IT racks. An advanced LCD screen provides local monitoring and alert indications, while remote access and configuration are available through secure Web, SNMP, CLI, or Telnet interfaces. Remote outlet monitoring offers ±1% billing grade accuracy while remote switching capabilities support power on/off functionality to remotely reboot equipment or restrict outlet usage. The maPDU features a lowprofile, single-piece design that provides multiple mounting options with ease of access to rear devices for maintenance. It is compatible with all HP 11000 G2 and Intelligent Series racks, as well as with many non-HP racks using standard button and keyhole mounting. Multiple options are available supporting vertical/0U configurations with both single and 3-phase models.

Managed PDU, Half Height Model (H8B49A shown) Managed PDU, Full Height Model (H8B48A shown)

Managed PDU, Full Height Model (H8B50A & H8B51A shown) Managed PDU, Full Height Model (H8B52A shown) c04376673 – DA – 15069 Worldwide — Version 1 — September 29, 2014 Page 1

QuickSpecs

Overview

HP Managed Power Distribution Units (maPDU)

Managed PDU, Full Height Model (H8B53A shown) Managed PDU, Full Height Model (H8B54A shown)

Managed PDU, Full Height Model (H8B55A & H8B56A shown) c04376673 – DA – 15069 Worldwide — Version 1 — September 29, 2014 Page 2

QuickSpecs

Models

HP Managed Power

Distribution Units

(maPDU)

HP Managed Power Distribution Units (maPDU)

Half Height Models

HP 3.6kVA 200-240 Volt Detachable C20 Input (7xC13/1xC19) WW Managed PDU

Full Height Models

HP 2.8kVA 120 Volt L5-30 Input (24x NEMA 5-20) NA/JP Managed PDU

HP 4.9kVA 208 Volt L6-30 Input (20xC13/4xC19) NA/JP Managed PDU

HP 7.3kVA 200-240 Volt IEC309 32A Input (20xC13/4xC19) INTL Managed PDU

HP 8.6kVA 208 Volt L15-30 3 Phase Input (18xC13/6xC19) NA/JP Managed PDU

HP 8.6kVA 208 Volt L21-30 3 Phase Input (20xC13/3xC19/1x NEMA 5-20) NA/JP Managed

PDU

HP 11kVA 400 Volt IEC309 16A 3 Phase Input (21xC13/3xC19) INTL Managed PDU

HP 14.4kVA 208V CS8365C 3 Phase Input (12xC13/12xC19) NA/JP Managed PDU

HP 17.3kVA 208V IEC309 48A 3 Phase Input (12xC13/12xC19) NA/JP Managed PDU

H8B49A

H8B48A

H8B50A

H8B51A

H8B52A

H8B53A

H8B54A

H8B55A

H8B56A c04376673 – DA – 15069 Worldwide — Version 1 — September 29, 2014 Page 3

QuickSpecs

HP Managed Power Distribution Units (maPDU)

Standard Features

Key Features and Benefits

Local and remote power distribution management with billing grade accuracy

 An advanced LCD screen on HP Managed Power Distribution Units (maPDU) provides local monitoring and alert indications.

 Remotely access and configure each maPDU through secure Web, SNMP, CLI, or Telnet

Interfaces with the ability to daisy-chain up to four units to share the same network connection and IP address.

 Remote outlet monitoring within ±1% billing grade accuracy.

 Remote outlet switching provides power on/off capabilities to remotely reboot equipment or restrict outlet usage.

 Supports both Local and LDAP security with multiple access levels to provide enhanced security.

Flexible, simple installation and maintenance

 The HP Managed Power Distribution Unit features a low-profile, single-piece design supporting multiple mounting options and ease of access to rear devices for maintenance.

 Each maPDU can be installed on either side of the rack with outlets facing the back of the rack for easy access and improved clearance.

 Install maPDU units side by side on both sides of the rack with the outlets facing in towards the center of the rack for high density configurations.

 Provides integrated power cord retention on all IEC receptacles that work with standard power cords.

 Add an optional environmental sensor which can measure air temperature and humidity in the front or rear of the rack, sending alerts over the network based on user-defined thresholds.

Compatible With a Wide Range of HP and Non-HP Rack Solutions

 HP Managed Power Distribution Units are designed to provide complete compatibility with HP

11000 G2 and Intelligent Series racks.

 The maPDU is also compatible with a wide range of non-HP racks using standard button and keyhole mounting.

 Designed for vertical/0U rack configurations offering both half and full-height form factors.

 Support for a wide range of load capacities, from 2.8kVA to 17.3kVA, with both single and threephase models.

Billing Grade

Accuracy

Remote Access

Support

All HP Managed Power Distribution Units (maPDU) meet IEC 62053-21, Class 1 standards for ±1% or better accuracy in power monitoring of:

Amperage

Voltage

Wattage

Kilowatts per hour

Accurate outlet and load segment power monitoring improves circuit utilization and provide information that can help balance power throughout the data center to maximize efficiency and cooling.

 Easy to use CLI and web interfaces

 Local and LDAP security with multiple access levels

 HTTP, HTTPS, Telnet/SSH protocols

 IPv4 and IPv6 compatible c04376673 – DA – 15069 Worldwide — Version 1 — September 29, 2014 Page 4

QuickSpecs

Standard Features

 SNMPv1 and SNMPv3 compatible

 Email alert notifications

 User settable alert thresholds

 Event logs

HP Managed Power Distribution Units (maPDU)

Flexible Installation The HP Managed Power Distribution Units (maPDU) are available in two form factors supporting a variety of vertical/0U rack configurations. All HP Managed Power Distribution Units (maPDU) can be mounted to stay completely out of the critical rear maintenance path needed to service IT equipment in the rack. All vertical models use industry standard button and keyhole mounting for simple drop in installation in HP

11000 G2 and Intelligent Series racks, as well as many non-HP racks.

 Mount vertically on either side in the rear of the rack using industry standard button and keyhole mounting.

 Standard mounting faces the outlet towards the rear of the rack. This configuration fully prevents interference in the maintenance zone between rear RETMA rails.

 Using the optional configuration of facing the outlets into the rack, multiple PDUs can be mounted on one side of the rack for higher power density. maPDU Form Factors

NOTE: Facing the outlets into the rack will interfere with the lower few rack U spaces of the rear maintenance zone due to breakers on the PDUs.

 Half Height PDU o Designed to fit in 22U and taller racks o Up to 4 Half Height PDUs can be mounted on one side of a 42U or 47U rack using the optional inward facing configuration.

 Full Height PDUs o Designed for 42U and taller racks.

Environmental monitoring

Warranty

NOTE: When mounted in the standard rear facing configuration only 1 Full Height PDU can be mounted per side of the rack. Up to 2 Half Height PDUs can be mounted per side in the standard rear facing configuration in a 42U or taller rack.

An optional environmental sensor attaches to the HP Managed Power Distribution Units (maPDU) and can measure air temperature and humidity in the front or rear of the rack. The environmental sensor will send alerts over the network based on user defined thresholds.

HP Managed Power Distribution Units (maPDU) are backed by a limited 3-year warranty.

HP Managed Power Distribution Units (maPDU) automatically assume the Care Pack coverage level of any covered ProLiant server in the same rack. c04376673 – DA – 15069 Worldwide — Version 1 — September 29, 2014 Page 5

QuickSpecs

HP Managed Power Distribution Units (maPDU)

Service and Support

HP Care Pack Services Care Pack services provide a range of life cycle support options that let you choose the service levels that meet your business requirements, from basic to mission-critical.

A full range of HP Care Pack hardware and software services are available including:

 Installation and start up

 Education courses

 Extended onsite hardware coverage hours from same business day 13 hours, 5 day to 24 hours,

7 days call window with options including 4-hour response or 6-hour Call To Repair

 Comprehensive range of software technical support for Microsoft, Linux, ProLiant Essentials and

VMWare-based IT solutions helping to deliver high level of application availability. Response times range from 30 mins for critical problems to 2 hours.

 System Management, Performance Services and Mission Critical Support Solution

NOTE: For more information on HP Care Pack services, contact any of our worldwide sales offices or resellers or visit our worldwide Web site on the internet at: http://www.hp.com/hps/carepack

NOTE: For more complete information on HP Services offerings, customers and resellers, please visit us at: http://www.hp.com/hps

NOTE: Additional information regarding worldwide limited warranty and technical support is available at: http://h18004.www1.hp.com/products/servers/platforms/warranty/index.html

c04376673 – DA – 15069 Worldwide — Version 1 — September 29, 2014 Page 6

QuickSpecs

Related Options

HP Environmental

Sensor

HP Managed Power Distribution Units (maPDU)

HP Environmental Sensor for Remote Monitored PDUs

 Hot installable and hot swappable

 User selectable alarm thresholds

 Measure temperature from 32˚F to 158˚F (0˚C to 70˚C) with an accuracy of

±3.6˚F (±2˚C)

 Measures relative humidity from 10% to 90% with an accuracy of ±5%

 Supports normally open and normally closed contact devices

E2D53A

NOTE: The HP Environmental Sensor comes with a 6 foot RJ45-RJ45 cable and can be mounted in various locations within the rack using the supplied Velcro strips or mounting screw. RJ45 cables up to 30 feet (9.1m) long may be used.

NOTE: One environmental sensor may be installed per HP Managed PDU

HP Country specific

C19 PDU Inlet Cords

(required for H8B49A )

HP C19 - Nema L6-20P NA/JP 250V 20Amp High Voltage 3.6m Power Cord

HP C19 - NBR-14136 BR 250V 16Amp 2.5m Power Cord

HP C19 - GB-1002 CN 250V 16Amp 2.5m Power Cord

HP C19 - IS-1293 IN/PK/BD 250V 16Amp 2.5m Power Cord

HP C19 - ISI-32 IL 250V 16Amp 2.5m Power Cord

HP C19 - AS3112-3 AU/NZ 250V 15Amp 3.6m Power Cord

HP C19 - IEC-309 DK/SE/AR 250V 16Amp 3.6m Power Cord

HP C19 - CEE-VII EU 250V 16Amp 3.6m Power Cord

HP C19 - CEI-23-50 IT/CL 250V 16Amp 3.6m Power Cord

HP C19 - SABS-164 ZA 250V 16Amp 3.6m Power Cord

HP C19 - BS-1363/A UK/HK/SG 250V 13Amp 3.6m Power Cord

HP 240 VAC 4.5M Unterminated End NA Power Cord

NOTE: Please refer to the HP ProLiant Power Cables web page for more information on power cable/cord part numbers and descriptions.

HP Jumper Cables HP C13 - C14 WW 250V 10A Gray 0.7m Jumper Cord

HP C13 - C14 WW 250V 10Amp 0.7m Jumper Cord

HP C13 - C14 WW 250V 10Amp 1.4m Jumper Cord

HP C13 - C14 WW 250V 10A Gray 1.37m Jumper Cord

HP C13 - C14 WW 250V 10Amp 1.4m 15 pc Jumper Cord

HP C13 - C14 WW 250V 10Amp 2.0m Jumper Cord

HP C13 - C14 WW 250V 10Amp Flint Gray 2.0m Jumper Cord

HP C13 - C14 WW 250V 10Amp 2.5m Jumper Cord

HP C13 - C14 WW 250V 10Amp 3.0m Jumper Cord

HP C13 - C14 WW 250V 10A Gray 3.0m Jumper Cord

HP C20 - C13 WW 250V 15Amp 2.0m Jumper Cord

HP C19 - C20 WW 250V 16Amp Flint Gray 1.20m Jumper Cord

HP C19 - C20 WW 250V 16Amp Flint Gray 2.0m Jumper Cord

HP C19 - C20 WW 250V 16Amp 2.5m Jumper Cord

HP 200-250V 10A C15 to C14 .76m Jumper Cable

NOTE: Please refer to the HP ProLiant Power Cables web page for more information on power cable/cord part numbers and descriptions.

HP Mounting Brackets HP Vertical PDU 10K G2 Mounting Kit

NOTE: Allows HP Basic and Managed Power Distribution Units (maPDU) vertical models to be mounted in HP 10000 G2 series racks and in the HP V142 rack. This bracket is not needed for mounting in the HP 11000G2 or Intelligent Series racks. PDUs may interfere

AF593A

AF592A

AF584A

AF582A

AF583A

AF577A

AF581A

AF576A

AF580A

AF579A

359615-031

E7806A

A0K03A

142257-B28

142257-006

A0K04A

142257-007

A0K02A

AF573A

142257-002

142257-003

A0K06A

AF590A

AF575A

AF574A

295633-B22

E7807A

H6L32A c04376673 – DA – 15069 Worldwide — Version 1 — September 29, 2014 Page 7

QuickSpecs

Related Options

HP Managed Power Distribution Units (maPDU) with the rear maintenance zone when using these brackets.

c04376673 – DA – 15069 Worldwide — Version 1 — September 29, 2014 Page 8

QuickSpecs

HP Managed Power Distribution Units (maPDU)

Technical Specifications

Model Selection Matrix - HP Managed Power Distribution Units (maPDU)

Half Height Vertical Models

Model Part

Number

Input

Voltage

Current

(Maximum)

Load

Capacity

Input Connection Output

Circuit

Breaker

N/A

Outlet

Connections

3.6kVA PDU H8B49A

Part

Number

100-240V

Input

Voltage

16A

Current

(Maximum)

3680VA

@ 230V

Load

Capacity

Detachable cord with

IEC 320-C20 inlet

NOTE: Model H8B49A includes an IEC320-C20 power inlet and does not include an inlet power cord. Customers may choose from multiple HP country specific C19 PDU inlet cords that are listed in the “Related Options” section of this quickspec.

Full Height Vertical Models

Model Input Connection Output

Circuit

Breaker

7 x IEC C13

1 x IEC C19

Outlet

Connections

2.8kVA PDU H8B48A 100-127V 24A 2880VA

@ 120V

10ft(3m) cord with

NEMA L5-30P

2 x 20A 24 x NEMA 5-20R

4.9kVA PDU H8B50A

7.3kVA PDU H8B51A

8.6kVA PDU H8B52A

8.6kVA PDU H8B53A

200-240V 24A

200-240V 32A

200-240V

3 Phase

Delta

120/208V

3 Phase WYE

24A

24A

4992VA

@ 208V

7360

@ 230V

8646VA

@ 208V

8646VA

@ 208V

10ft(3m) cord with

NEMA L6-30P

2 x 20A

10ft(3m) cord with

IEC 60309 32A 3-wire

2 x 16A

10ft(3m) cord with

NEMA L15-30P

3 x 20A

10ft(3m) cord with

NEMA L21-30P

3 x 20A

20 x IEC C13

4 x IEC C19

20 x IEC C13

4 x IEC C19

18 x IEC C13

6 x IEC C19

20 x IEC C13

3 x IEC C19

1 x NEMA 5-20R

11kVA PDU H8B54A

14.4kVA PDU H8B55A

17.3kVA PDU H8B56A

200-240/

346-415V

3 Phase WYE

200-240V

3 Phase

Delta

200-240V

3 Phase

Delta

16A

40A

48A

11040VA

@ 230V

14410VA

@ 208V

10ft(3m) cord with

IEC 60309 16A 5-wire

N/A

10ft(3m) cord with

CS8365C 50A 4-wire

6 x 20A

17292VA @

208V

10ft(3m) cord with

IEC 60309 60A 4-wire

Watertight

6 x 20A

21 x IEC C13

3 x IEC C19

12 x IEC C13

12 x IEC C19

12 x IEC C13

12 x IEC C19

NOTE: Please refer to the HP ProLiant Power Cables web page for more information on power cable/cord part numbers and descriptions.

Disclaimer: HP makes no recommendations regarding power connector manufactures. Please consult a licensed professional to determine the best connector or receptacle for your specific needs. c04376673 – DA – 15069 Worldwide — Version 1 — September 29, 2014 Page 9

QuickSpecs

HP Managed Power Distribution Units (maPDU)

Technical Specifications

Operational Temperature (NA and NA/JPN models) 32° to 140° F (0° to 60° C)

Operating Temperature (INTL and WW models)

Operating Relative Humidity (%)

Operating Elevation

Storage Temperature

Storage Relative Humidity (%)

Storage Elevation

Input Plug Length (attached cord units)

Conformance Standards

32° to 131° F (0° to 55° C) with an 8A maximum load/outlet

32° to 113° F (0° to 45° C) with outlet fully loaded

10% to 90%

0 to 10,000 ft (0 to 3048 m)

-4° to 140° F (-20° to 60° C)

5% to 95%

0 to 30,000 ft (0 to 9144 m)

120 inches (304.8 cm)

NA/JPN models: UL or CSA, CB Test + FCC, ICES, VCCI

INTL models: CE, TUV, KC, EAC, +KCC, ACMA, Ukraine

WW Models: UL or CSA, CB Test + CE, TUV, EAC, FCC, ICES, KCC, KC, VCCI,

ACMA, Ukraine

2.05 x 35.5 x 2.09 in (5.2 x 90.2 x 5.3 cm) Mechanical Dimensions (WxHxD) - Half Height model

(H8B49A)

Mechanical Dimensions (WxHxD) - Full Height models

(H8B50A/H8B51A/H8B53A/H8B54A)

2.05 x 66.5 x 2.09 in (5.2 x 168.9 x 5.3 cm)

Mechanical Dimensions (WxHxD) - Full Height models

(H8B48A/H8B52A/H8B55A/H8B56A)

Unit Weight

2.05 x 66.5 x 2.56 in (5.2 x 168.9 x 6.5 cm)

H8B48A: 11.55 lbs (5.24 kg); H8B49A: 4.06 lbs (1.84 kg);

H8B50A: 11.75 lbs (5.33 kg); H8B51A: 10.85 lbs (4.92 kg);

H8B52A: 13.74 lbs (6.23 kg); H8B53A: 13.23 lbs (6.00 kg)

H8B54A: 10.14 lbs (4.60 kg); H8B55A: 21.91 lbs (9.94 kg);

H8B56A: 23.08 lbs (10.47kg)

Kit Contents - All Managed PDUs All models ship with:

 Mounting buttons or hardware

 Tie wraps for cable retention

 6ft RJ45-RJ45 communications cable

 6ft RJ45-DB9 Serial cable

 Documentation

Environment-friendly

Products and Approach

End-of-life

Management and

Recycling

Hewlett-Packard offers end-of-life HP product return, trade-in, and recycling programs in many geographic areas. For trade-in information, please go to: http://www.hp.com/go/green . To recycle your product, please go to: http://www.hp.com/go/green or contact your nearest HP sales office. Products returned to HP will be recycled, recovered or disposed of in a responsible manner.

The EU WEEE directive (2002/95/EC) requires manufacturers to provide treatment information for each product type for use by treatment facilities. This information (product disassembly instructions) is posted on the Hewlett Packard web site at: http://www.hp.com/go/green . These instructions may be used by recyclers and other WEEE treatment facilities c04376673 – DA – 15069 Worldwide — Version 1 — September 29, 2014 Page 10

QuickSpecs

HP Managed Power Distribution Units (maPDU)

Technical Specifications

as well as HP OEM customers who integrate and re-sell HP equipment.

© Copyright 2014 Hewlett-Packard Development Company, L.P.

The information contained herein is subject to change without notice.

The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein.