Rosemount 3051 Pressure Transmitter - August 2004

Page 1

Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051

Rosemount 3051 Pressure Transmitter HART® AND FOUNDATION™ FIELDBUS PROTOCOLS • Best-in-Class performance, 0.04% High Accuracy option • Industry first five-year stability under actual process conditions • Unmatched Dynamic Performance • Coplanar™ platform enables integrated pressure, flow, and level solutions • Advanced PlantWeb® Functionality

Contents “Product Offering” . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3 “Specifications” . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4 “Product Certifications” . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 11 “HART Protocol”. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 11 “Fieldbus Protocol” . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 14 “Dimensional Drawings”. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 16 “Ordering Information” . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 24 “HART Protocol C1 Option Configuration Data Sheet” . . . . . . . . . . . . . . . . . . . . . . page 38

www.rosemount.com


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051

Setting the Standard for Pressure Measurement Industry’s best total performance, a flexible Coplanar platform, and guaranteed 5- year stability, has made the Rosemount 3051 the standard in pressure measurement. Industry’s best total performance of ±0.15% Total performance is the true measure of “real-world” transmitter performance. Using superior sensor technology and engineered for optimal performance, the 3051 delivers unprecedented ±0.04% reference accuracy, resulting in total operating performance of ±0.15%. Superior total performance equates to reduced variability and improved plant safety.

Coplanar platform enables complete point solutions The versatile Coplanar platform design enables the best process connection for pressure, flow and level applications. Right out of the box, the solution arrives factory calibrated, pressure-tested, and ready to install. Only the 3051 has a flexible design to reduce engineering and inventory costs.

Five year installed stability of ±0.125% Transmitter stability is a critical measure of transmitter performance over time. Through aggressive simulation testing beyond standard IEC 770 testing, the 3051 has proven its ability to maintain performance over a five year period under the most demanding process conditions. Superior transmitter stability reduces calibration frequency to save operation and maintenance costs.

Advanced PlantWeb Functionality Optional functionality includes performance diagnostics and Control Anywhere™. Performance diagnostics such as plugged impulse line detection and statistical process monitoring -go beyond the transmitter to evaluate the performance of the entire measurement system. Control Anywhere provides user-configurable transmitter-resident function blocks, such as PID, Math, and signal characterization.

Unmatched dynamic performance In dynamic applications, speed of measurement is as important as repeatability. The 3051 responds up to eight times faster than the typical pressure transmitter to detect and control variations quickly and efficiently. Superior dynamic response yields more accurate measurements to reduce variability and increase profitability.

Rosemount Pressure Solutions Rosemount 3051S Series of Instrumentation Scalable pressure, flow and level measurement solutions improve installation and maintenance practices.

Rosemount 3095MV Mass Flow Transmitter Accurately measures differential pressure, static pressure and process temperature to dynamically calculate fully compensated mass flow.

Rosemount 305 and 306 Integral Manifolds Factory-assembled, calibrated and seal-tested manifolds reduce on-site installation costs.

Rosemount 1199 Diaphragm Seals Provides reliable, remote measurements of process pressure and protects the transmitter from hot, corrosive, or viscous fluids.

Orifice Plate Primary Element Systems: Rosemount 1495 and 1595 Orifice Plates, 1496 Flange Unions and 1497 Meter Sections A comprehensive offering of orifice plates, flange unions and meter sections that is easy to specify and order. The 1595 Conditioning Orifice provides superior performance in tight fit applications. 2

Annubar® Flowmeter Series: Rosemount 3051SFA, 3095MFA, and 485 The state-of-the-art, fifth generation Rosemount 485 Annubar combined with the 3051S or 3095MV MultiVariable transmitter creates an accurate, repeatable and dependable insertion-type flowmeter.

Compact Orifice Flowmeter Series: Rosemount 3051SFC, 3095MFC, and 405 Compact Orifice Flowmeters can be installed between existing flanges, up to a Class 600 (PN100) rating. In tight fit applications, a conditioning orifice plate version is available, requiring only two diameters of straight run upstream.

ProPlate® Flowmeter Series: Rosemount ProPlate, Mass ProPlate, and 1195 These integral orifice flowmeters eliminate the inaccuracies that become more pronounced in small orifice line installations. The completely assembled, ready to install flowmeters reduce cost and simplify installation.


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051 Product Offering

Rosemount 3051C Differential, Gage, and Absolute See ordering information on page 24. •

Performance up to 0.04% accuracy

Five year installed stability of 0.125%

Coplanar platform enables integrated manifold, primary element and diaphragm seal solutions

Calibrated spans/ranges from 0.1 inH2O to 4000 psi (0,25 mbar to 276 bar)

316L SST, Hastelloy® C276, Monel®, Tantalum, Gold-plated Monel, or Gold-plated 316L SST process isolators

Rosemount 3051T Gage and Absolute See ordering information on page 28. • Performance up to 0.04% accuracy • Five year installed stability of 0.125% • Calibrated spans from 0.3 to 10000 psi (10,3 mbar to 689 bar) • Multiple process connections available •

316L SST and Hastelloy C276 process isolators

Rosemount 3051L Liquid Level See ordering information on page 30. •

Performance up to 0.075% accuracy with 100:1 turndown

Flush, 2-, 4-, and 6-in. extended diaphragms

Multiple fill fluids available

316L SST, Hastelloy C276, or Tantalum wetted materials

3


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051 Specifications

This product data sheet covers both HART and fieldbus protocols unless specified.

PERFORMANCE SPECIFICATIONS(1) Total Performance is based on combined errors of reference accuracy, ambient temperature effect, and static pressure effect.

Rosemount 3051C (Ranges 2–5), Rosemount 3051T (Ranges 1–4) Reference Accuracy ±0.065% of span ±0.04% of span (High Accuracy Option)

DETAILED PERFORMANCE SPECIFICATIONS For zero-based spans, reference conditions, silicone oil fill, SST materials, Coplanar flange (3051C) or 1/2 in.- 18 NPT (3051T) process connections, digital trim values set to equal range points.

Reference Accuracy(1) Stated reference accuracy includes hysteresis, terminal-based linearity and repeatability.

Total Performance ±0.15% of span for ±50 °F (28 °C) temperature changes, up to 1000 psi (6,9 MPa) line pressure (CD only), from 1:1 to 5:1 rangedown. Stability ±0.125% of URL for 5 years for ±50 °F (28 °C) temperature changes, and up to 1000 psi (6,9 MPa) line pressure. Dynamic Performance Total Response Time (Tc) HART output: 100 ms Fieldbus and Profibus output: 152 ms

Rosemount 3051CD Low/Draft Range (Ranges 0–1) Reference Accuracy ±0.10% of span Stability

Rosemount 3051CD, 3051CG Range 0 (CD) ±0.10% of span For spans less than 2:1, accuracy = ±0.05% of URL Range 1 ±0.10% of span For spans less than 15:1, accuracy =

URL ± 0.025 + 0.005  --------------- % of Span  Span Ranges 2-5 ±0.065% of span For spans less than 10:1, accuracy =

URL ± 0.015 + 0.005  --------------- % of Span Span

±0.2% of URL for 1 year

Rosemount 3051L—Liquid Level Reference Accuracy ±0.075% of span

Ranges 2-4 High Accuracy Option, P8 ±0.04% of span For spans less than 5:1, accuracy =

URL ± 0.015 + 0.005  --------------- % of Span Span

Rosemount 3051H—High Process Temperature Reference Accuracy ±0.075% of span Stability ±0.1% of URL for 12 months for Ranges 2 and 3. ±0.2% of URL for 12 months for Ranges 4 and 5.

(1)

4

For FOUNDATION fieldbus transmitters, use calibrated range in place of span.


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051CA Ranges 1-4 ±0.065% of span For spans less than 10:1, accuracy =

URL ± 0.0075  --------------- % of Span  Span Ranges 2-4 High Accuracy Option, P8 ±0.04% of span For spans less than 5:1, accuracy =

URL ± 0.0075  --------------- % of Span  Span

Rosemount 3051 Ambient Temperature Effect per 50 °F (28 °C) Rosemount 3051CD/CG ±(0.0125% URL + 0.0625% span) from 1:1 to 5:1 ±(0.025% URL + 0.125% span) from 5:1 to 100:1 Range 0: ±(0.25% URL + 0.05% span) Range 1: ±(0.1% URL + 0.25% span)

Rosemount 3051CA ±(0.025% URL + 0.125% span) from 1:1 to 30:1 ±(0.035% URL + 0.125% span) from 30:1 to 100:1

Rosemount 3051T

Rosemount 3051H

Ranges 1-4

±(0.025% URL + 0.125% span + 0.35 inH2O)

±0.065% of span For spans less than 10:1, accuracy =

URL ± 0.0075  --------------- % of Span Span Range 5 ±0.075% of span For spans less than 10:1, accuracy =

URL ± 0.0075  --------------- % of Span Span Ranges 2-4 High Accuracy Option, P8 ±0.04% of span For spans less than 5:1, accuracy =

URL ± 0.0075  --------------- % of Span Span Rosemount 3051H/3051L All Ranges ±0.075% of span. For spans less than 10:1, accuracy =

URL ± 0.025 + 0.005  --------------- % of Span  Span

For spans less than 30:1 ±(0.035% URL + 0.125% span + 0.35 inH2O)

Rosemount 3051L See Rosemount Inc. Instrument Toolkit™ software.

Rosemount 3051T ±(0.025% URL + 0.125% span) from 1:1 to 30:1 ±(0.035% URL + 0.125% span) from 30:1 to 100:1 Range 5: ±(0.1% URL + 0.15% span) Range 1: ±(0.025% URL + 0.125% span) from 1:1 to 10:1 ±(0.05% URL + 0.125% span) from 10:1 to 100:1

Line Pressure Effect per 1000 psi (6,9 MPa) Rosemount 3051CD Zero Error (can be calibrated out at line pressure) Range 2 – 3: ±0.05% of URL for line pressures from 0 to 2000 psi (0 to 13,7 MPa) For line pressures above 2000 psi (13,7 MPa), see user manual (Rosemount publication number 00809-0100-4001) Range 0: ±0.125% of URL/100 psi (6,89 bar) Range 1: ±0.25% of URL Span Error Range 2 – 3: ±0.1% of reading Range 0: ±0.15% of reading/100 psi (6,89 bar) Range 1: ±0.4% of reading

Rosemount 3051HD Zero Error (can be calibrated out at line pressure) ±0.1% of URL for line pressures from 0 to 2000 psi (0 to 13,7 MPa) For line pressures above 2000 psi (13,7 MPa), see user manual (Rosemount publication number 00809-0100-4001) Span Error ±0.1% of reading

5


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051 Dynamic Performance 4 - 20 mA (HART protocol)(1) Total Response Time (Td + Tc)(2): 3051C, Ranges 2-5: 100 ms Range 1: 255 ms Range 0: 700 ms 3051T: 100 ms 3051H/L: Consult factory Dead Time (Td) 45 ms (nominal) Update Rate 22 times per second

Rosemount 3051L Fieldbus protocol(3) 152 ms 307 ms 752 ms 152 ms Consult factory 97 ms 22 times per second

With liquid level diaphragm in vertical plane, zero shift of up to 1 inH2O (25,4 mmH2O). With diaphragm in horizontal plane, zero shift of up to 5 inH2O (127 mmH2O) plus extension length on extended units. All zero shifts can be calibrated out. No span effect.

Rosemount 3051T/CA Zero shifts up to 2.5 inH2O (63,5 mmH2O), which can be calibrated out. No span effect.

Vibration Effect All Models

(3) Transmitter fieldbus output only, segment macro-cycle not included.

Measurement effect due to vibrations is negligible except at resonance frequencies. When at resonance frequencies, vibration effect is less than ±0.1% of URL per g when tested between 15 and 2000 Hz in any axis relative to pipe-mounted process conditions.

FIGURE 1. Typical HART Transmitter Response Time

Power Supply Effect

(1) Dead time and update rate apply to all models and ranges; analog output only (2) Nominal total response time at 75 °F (24 °C) reference conditions.

Transmitter 4–20 mA Output vs. Time

All Models

Pressure Released

Less than ±0.005% of calibrated span per volt. Tc

20mA

63.2% of Total Step Change

9.89 mA 4mA

Time

Mounting Position Effects Rosemount 3051C Zero shifts up to ±1.25 inH2O (3,11 mbar), which can be calibrated out. No span effect.

Rosemount 3051H Zero shifts up to ±5 inH2O (127 mmH2O), which can be calibrated out. No span effect.

RFI Effects 3051-3051_17A

Td

Td = Dead Time Tc = Time Constant Response Time = Td +Tc

All Models ±0.1% of span from 20 to 1000 MHz and for field strength up to 30 V/m.

Transient Protection (Option Code T1) All Models: Meets IEEE C62.41, Category B 6 kV crest (0.5 µs - 100 kHz) 3 kV crest (8 × 20 microseconds) 6 kV crest (1.2 × 50 microseconds) Meets IEEE C37.90.1, Surge Withstand Capability SWC 2.5 kV crest, 1.25 MHz wave form General Specifications: Response Time: < 1 nanosecond Peak Surge Current: 5000 amps to housing Peak Transient Voltage: 100 V dc Loop Impedance: < 25 ohms Applicable Standards: IEC61000-4-4, IEC61000-4-5 NOTE: Calibrations at 68 °F (20 °C) per ASME Z210.1 (ANSI)

6


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051

FUNCTIONAL SPECIFICATIONS Range and Sensor Limits TABLE 1. 3051CD, 3051CG, 3051L, and 3051H Range and Sensor Limits Range

Minimum Span

Range and Sensor Limits Lower (LRL)

3051CD(1), CG, L, H

Upper (URL)

3051C Differential

3051C/ Gage

3051L Differential

3051L Gage

3051H Differential

3051H Gage

0

0.1 inH2O (0,25 mbar)

3.0 inH2O (7,47 mbar)

–3.0 inH2O (-7,47 mbar)

NA

NA

NA

NA

NA

1

0.5 inH2O (1,2 mbar)

25 inH2O (62,3 mbar)

–25 inH2O (–62,3 mbar)

–25 inH2O (–62,3 mbar)

NA

NA

NA

NA

2

2.5 inH2O (6,2 mbar)

250 inH2O (0,62 bar)

–250 inH2O (–0,62 bar)

–250 inH2O (–0,62 bar)

–250 inH2O (–0,62 bar)

–250 inH2O (–0,62 bar)

–250 inH2O (–0,62 bar)

–250 inH2O (–0,62 bar)

3

10 inH2O (24,9 mbar)

1000 inH2O (2,49 bar)

–1000 inH2O (–2,49 bar)

0.5 psia (34,5 mbar abs)

–1000 inH2O (–2,49 bar)

0.5 psia (34,5 mbar abs)

–1000 inH2O (–2,49 bar)

0.5 psia (34,5 mbar abs)

4

3 psi (0,20 bar)

300 psi (20,6 bar)

–300 psi (–20,6 bar)

0.5 psia (34,5 mbar abs)

–300 psi (–20,6 bar)

0.5 psia (34,5 mbar abs)

–300 psi (–20,6 bar)

0.5 psia (34,5 mbar abs)

5

20 psi (1,38 bar)

2000 psi (137,9 bar)

– 2000 psi (–137,9 bar)

0.5 psia (34,5 mbar abs)

NA

NA

– 2000 psi (–137,9 bar)

0.5 psia (34,5 mbar abs)

(1) Range 0 only available with 3051CD. Range 1 only available with 3051CD or 3051CG.

TABLE 2. Range and Sensor Limits

1 2 3 4

3051T

Range and Sensor Limits Minimum Span

Upper (URL)

Lower (LRL)

0.3 psia (20,6 mbar) 1.5 psia (0,103 bar) 8 psia (0,55 bar) 40 psia (2,76 bar)

30 psia (2,07 bar) 150 psia (10,3 bar) 800 psia (55,2 bar) 4000 psia (275,8 bar)

0 psia (0 bar) 0 psia (0 bar) 0 psia (0 bar) 0 psia (0 bar)

Range

Range

3051CA

1 2 3 4 5

Range and Sensor Limits Minimum Span

Upper (URL)

Lower (LRL)

Lower(1) (LRL) (Gage)

0.3 psi (20,6 mbar) 1.5 psi (0,103 bar) 8 psi (0,55 bar) 40 psi (2,76 bar) 2000 psi (137,9 bar)

30 psi (2,07 bar) 150 psi (10,3 bar) 800 psi (55,2 bar) 4000 psi (275,8 bar) 10000 psi (689,4 bar)

0 psia (0 bar) 0 psia (0 bar) 0 psia (0 bar) 0 psia (0 bar) 0 psia (0 bar)

–14.7 psig (–1,01 bar) –14.7 psig (–1,01 bar) –14.7 psig (–1,01 bar) –14.7 psig (–1,01 bar) –14.7 psig (–1,01 bar)

(1) Assumes atmospheric pressure of 14.7 psig.

7


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051 Zero and Span Adjustment Requirements (HART and Low Power)

Low Power (Output Code M)

Zero and span values can be set anywhere within the range limits stated in Table 1 and Table 2.

Output

Span must be greater than or equal to the minimum span stated in Table 1 and Table 2. Service Liquid, gas, and vapor applications

4–20 mA (Output Code A)

Three wire 1–5 V dc or 0.8–3.2 V dc (Option Code C2) user-selectable output. Also user selectable for linear or square root output configuration. Digital process variable superimposed on voltage signal, available to any host conforming to the HART protocol. Low-power transmitter operates on 6–12 V dc with no load.

Power Consumption

Output Two-wire 4–20 mA, user-selectable for linear or square root output. Digital process variable superimposed on 4–20 mA signal, available to any host that conforms to the HART protocol. Power Supply External power supply required. Standard transmitter (4–20 mA) operates on 10.5 to 55 V dc with no load. Load Limitations Maximum loop resistance is determined by the voltage level of the external power supply, as described by: Max. Loop Resistance = 43.5 (Power Supply Voltage – 10.5)

3.0 mA, 18–36 mW

Minimum Load Impedance 100 kΩ (Vout wiring)

Indication Optional 5-digit LCD display

Overpressure Limits Rosemount 3051CD/CG • Range 0: 750 psi (51,7 bar)

Load (Ohms)

• Range 1: 2000 psig (137,9 bar) • Ranges 2–5: 3626 psig (250 bar) 4500 psig (310,3 bar) for option code P9 Rosemount 3051CA Operating Region

• Range 1: 120 psia (8,27 bar) • Range 2: 300 psia (20,7 bar) • Range 3: 1600 psia (110,3 bar) • Range 4: 6000 psia (413,7 bar) Rosemount 3051H

Voltage (V dc) Communication requires a minimum loop resistance of 250 ohms. (1) For CSA approval, power supply must not exceed 42.4 V.

• All Ranges: 3626 psig (25 MPa) Rosemount 3051TG/TA • Range 1: 750 psi (51,7 bar) • Range 2: 1500 psi (103,4 bar) • Range 3: 1600 psi (110,3 bar) • Range 4: 6000 psi (413,7 bar)

FOUNDATION fieldbus (output code F) and Profibus (output code W) Power Supply External power supply required; transmitters operate on 9.0 to 32.0 V dc transmitter terminal voltage. Current Draw 17.5 mA for all configurations (including LCD display option)

8

• Range 5: 15000 psi (1034,2 bar) For 3051L or Level Flange Option Codes FA, FB, FC, FD, FP, and FQ, limit is 0 psia to the flange rating or sensor rating, whichever is lower. TABLE 3. 3051L and Level Flange Rating Limits Standard

Type

CS Rating

SST Rating

ANSI/ASME Class 150 285 psig 275 psig ANSI/ASME Class 300 740 psig 720 psig ANSI/ASME Class 600 1480 psig 1440 psig At 100 °F (38 °C), the rating decreases with increasing temperature. DIN PN 10–40 40 bar 40 bar DIN PN 10/16 16 bar 16 bar DIN PN 25/40 40 bar 40 bar At 248 °F (120 °C), the rating decreases with increasing temperature.


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051

Static Pressure Limit Rosemount 3051CD Only Operates within specifications between static line pressures of 0.5 psia and 3626 psig (4500 psig for Option Code P9). Range 0: 0.5 psia and 750 psig Range 1: 0.5 psia and 2000 psig

Burst Pressure Limits Burst pressure on Coplanar, traditional, or 3051H process flange is 10000 psig (69 MPa). Burst pressure for the 3051T is Ranges 1–4: 11000 psi (75,8 MPa) Range 5: 26000 psig (179 MPa)

Failure Mode Alarm Output Code A If self-diagnostics detect a gross transmitter failure, the analog signal will be driven either below 3.75 mA or to 22 mA to alert the user. NAMUR-compliant values (≤ 3.6 mA and ≥ 22.5 mA) are available, option code C4. High or low alarm signal is user-selectable by internal jumper. Output Code M If self-diagnostics detect a gross transmitter failure, the analog signal will be driven either below 0.94 V or above 5.4 V to alert the user (below 0.75 V or above 4.4 V for Option C2). High or low alarm signal is user-selectable by internal jumper. Output Code F and W If self-diagnostics detect a gross transmitter failure, that information gets passed as a status along with the process variable.

Temperature Limits Ambient –40 to 185 °F (–40 to 85 °C) With integral meter: –4 to 175 °F (–20 to 80 °C) Storage –50 to 230 °F (–46 to 110 °C)

TABLE 4. 3051 Process Temperature Limits 3051CD, 3051CG, 3051CA Silicone Fill Sensor(1) with Coplanar Flange –40 to 250 °F (–40 to 121 °C)(2) with Traditional Flange –40 to 300 °F (–40 to 149 °C)(2)(3) with Level Flange –40 to 300 °F (–40 to 149 °C)(2) with 305 Integral Manifold –40 to 300 °F (–40 to 149 °C)(2) (1) Inert Fill Sensor 0 to 185 °F (–18 to 85 °C)(4) (5) 3051H (Process Fill Fluid) D.C.® Silicone 200(1) –40 to 375 °F (–40 to 191 °C) Inert(1) –50 to 350 °F (–45 to 177 °C) Neobee M-20®(1) 0 to 375 °F (–18 to 191 °C) 3051T (Process Fill Fluid) Silicone Fill Sensor(1) Inert Fill Sensor(1)

–40 to 250 °F (–40 to 121 °C)(2) –22 to 250 °F (–30 to 121 °C)(2) 3051L Low-Side Temperature Limits

Silicone Fill Sensor(1) –40 to 250 °F (–40 to 121 °C)(2) Inert Fill Sensor(1) 0 to 185 °F (–18 to 85 °C) (2) 3051L High-Side Temperature Limits (Process Fill Fluid) Syltherm® XLT D.C. Silicone 704® D.C. Silicone 200 Inert Glycerin and Water Neobee M-20 Propylene Glycol and Water

–100 to 300 °F (–73 to 149 °C) 60 to 400 °F (15 to 205 °C) –40 to 400 °F (–40 to 205 °C) –50 to 350 °F (–45 to 177 °C) 0 to 200 °F (–18 to 93 °C) 0 to 400 °F (–18 to 205 °C) 0 to 200 °F (–18 to 93 °C)

(1) Process temperatures above 185 °F (85 °C) require derating the ambient limits by a 1.5:1 ratio (0.6:1 ratio for the 3051H). (2) 220 °F (104 °C) limit in vacuum service; 130 °F (54 °C) for pressures below 0.5 psia. (3) 3051CD0 process temperature limits are –40 to 212 °F (–45 to 100 °C) (4) 160 °F (71 °C) limit in vacuum service. (5) Not available for 3051CA.

With integral meter: –40 to 185 °F (–40 to 85 °C) Process At atmospheric pressures and above. See Table 4

Humidity Limits 0–100% relative humidity

Turn-On Time Performance within specifications less than 2.0 seconds (10.0 s for Profibus protocol) after power is applied to the transmitter

Volumetric Displacement Less than 0.005 in3 (0,08 cm3)

Damping Analog output response to a step input change is user-selectable from 0 to 36 seconds for one time constant. This software damping is in addition to sensor module response time.

9


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051 PHYSICAL SPECIFICATIONS

Rosemount 3051L Process Wetted Parts Flanged Process Connection (Transmitter High Side)

Electrical Connections

Process Diaphragms, Including Process Gasket Surface

1/2–14

• 316L SST, Hastelloy C276, or Tantalum

NPT, PG 13.5, G1/2, and M20 × 1.5 (CM20) conduit. HART interface connections fixed to terminal block.

Extension

Process Connections

• CF-3M (Cast version of 316L SST, material per ASTM-A743), or Hastelloy C276. Fits schedule 40 and 80 pipe.

All Models except 3051L and 3051T

Mounting Flange

1/4–18

NPT on 21/8-in. centers

1/2–14

NPT on 2-, 21/8-, or 21/4-in. centers

• Zinc-cobalt plated CS or SST Reference Process Connection (Transmitter Low Side)

Rosemount 3051L

Isolating Diaphragms

High pressure side: 2-, 3-, or 4-in., ASME B 16.5 (ANSI) Class 150, 300 or 600 flange; 50, 80 or 100 mm, PN 40 or 10/16 flange Low pressure side: 1/4–18 NPT on flange 1/2–14 NPT on adapter Rosemount 3051T 1

/2–14 NPT female. A DIN 16288 Male (available in SST for Range 1–4 transmitters only), or Autoclave type F-250-C (Pressure relieved 9/16–18 gland thread; 1/4 OD high pressure tube 60° cone; available in SST for Range 5 transmitters only).

Electronics Housing Low-copper aluminum or CF-3M (Cast version of 316L SST, material per ASTM-A743). NEMA 4X, IP 65, IP 66

Bolts

316 SST, Hastelloy C276, or Monel material (Monel not available with 3051L or 3051H) Process Flanges and Adapters Plated carbon steel, SST cast CF-8M (cast version of 316 SST, material per ASTM-A743), C-Type cast alloy CW12MW, or Monel cast alloy M30C Glass-filled PTFE or Graphite-filled PTFE

3051CA

3051H

3051L: Syltherm XLT, D.C. Silicone 704, D.C. Silicone 200, inert, glycerin and water, Neobee M-20 or propylene glycol and water

3051T

3051CD/CG

Sensor Module Fill Fluid

Process Fill Fluid (3051L and 3051H only)

Process Isolating Diaphragms

• • • • • •

ASTM A449, Type 1 (zinc-cobalt plated carbon steel) ASTM F593G, Condition CW1 (Austenitic 316 SST) ASTM A193, Grade B7M (zinc plated alloy steel) Monel K-500 Silicone oil (D.C. 200) or Fluorocarbon oil (Halocarbon or Fluorinert® FC-43 for 3051T)

Wetted O-rings

10

Non-Wetted Parts

CF-3M (Cast version of 316L SST, material per ASTM-A743)

Drain/Vent Valves

Isolating Diaphragm Material

• CF-8M (Cast version of 316 SST, material per ASTM-A743)

Coplanar Sensor Module Housing

Process-Wetted Parts

316L SST Hastelloy C276 Monel Tantalum Gold-plated Monel Gold-plated SST

• 316L SST or Hastelloy C276 Reference Flange and Adapter

• •

• • •

• •

• •

3051H: inert, Neobee M-20, or D.C. Silicone 200 Paint Polyurethane Cover O-rings

Shipping Weights

Buna-N

Refer to “Shipping Weights” on page 37


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051 Product Certifications

Approved Manufacturing Locations Rosemount Inc. — Chanhassen, Minnesota USA Emerson Process Management GmbH & Co. — Wessling, Germany Emerson Process Management Asia Pacific Private Limited — Singapore Beijing Rosemount Far East Instrument Co., LTD — Beijing, China

European Directive Information The EC declaration of conformity for all applicable European directives for this product can be found on the Rosemount website at www.rosemount.com. A hard copy may be obtained by contacting an Emerson Process Management representative.

HART PROTOCOL Hazardous Locations Certifications North American Certifications FM Approvals E5

Explosion-Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition-Proof for Class II, Division 1, Groups E, F, and G. Dust-Ignition-Proof for Class III, Division 1. T5 (Ta = 85 °C), Factory Sealed, Enclosure Type 4X

I5

Intrinsically Safe for use in Class I, Division 1, Groups A, B, C, and D; Class II, Division 1, Groups E, F, and G; Class III, Division 1 when connected per Rosemount drawing 03031-1019; Non-incendive for Class I, Division 2, Groups A, B, C, and D. Temperature Code:T4 (Ta = 40 °C), T3 (Ta = 85 °C), Enclosure Type 4X For input parameters see control drawing 03031-1019.

ATEX Directive (94/9/EC) All 3051 transmitters comply with the ATEX Directive.

European Pressure Equipment Directive (PED) (97/23/EC) 3051CA4; 3051CG2, 3, 4, 5; 3051CD2, 3, 4, 5 (also with P9 option); 3051HD2, 3, 4, 5; 3051HG2, 3, 4, 5; 3051PD2, 3; and 3051PG2, 3, 4, 5 Pressure Transmitters — QS Certificate of Assessment - EC No. PED-H-20 Module H Conformity Assessment

Canadian Standards Association (CSA) E6

Explosion-Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition-Proof for Class II and Class III, Division 1, Groups E, F, and G. Suitable for Class I, Division 2 Groups A, B, C, and D for indoor and outdoor hazardous locations. Enclosure type 4X, factory sealed

C6

Explosion-Proof and intrinsically safe approval. Intrinsically safe for Class I, Division 1, Groups A, B, C, and D when connected in accordance with Rosemount drawings 03031-1024. Temperature Code T3C. Explosion-Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition-Proof for Class II and Class III, Division 1, Groups E, F, and G. Suitable for Class I, Division 2 Groups A, B, C, and D hazardous locations. Enclosure type 4X, factory sealed For input parameters see control drawing 03031-1024.

All other 3051/3001 Pressure Transmitters — Sound Engineering Practice

Transmitter Attachments: Diaphragm Seal - Process Flange - Manifold — Sound Engineering Practice

Electro Magnetic Compatibility (EMC) (89/336/EEC) All 3051 Pressure Transmitters meet all of the requirements of IECEN61326 and NAMUR NE-21

Ordinary Location Certification for Factory Mutual As standard, the transmitter has been examined and tested to determine that the design meets basic electrical, mechanical, and fire protection requirements by FM, a nationally recognized testing laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).

11


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051 European Certifications

Japanese Certifications

I1

E4

ATEX Intrinsic Safety and Dust Certification No.: BAS 97ATEX1089X II 1 GD EEx ia IIC T5 (–60 ≤ Ta ≤ +40 °C) EEx ia IIC T4 (–60 ≤ Ta ≤ +70 °C) Dust Rating: T80 °C (–20 ≤ Ta ≤ 40 °C) IP66 1180

JIS Flame-Proof Ex d IIC T6 Certificate

Description

C15850

3051C/D/1 4–20 mA HART — no meter 3051C/D/1 4–20 mA HART — with meter 3051T/G/1 4–20 mA HART, SST, Silicon — no meter 3051T/G/1 4–20 mA HART, Hastelloy C276, Silicon — no meter 3051T/G/1 4–20 mA HART, SST, Silicon — with meter 3051T/G/1 4–20 mA HART, Hastelloy C276, Silicon — with meter

C15851

TABLE 5. Input Parameters C15854

Ui = 30V Ii = 200 mA Pi = 0.9W Ci = 0.012 µF

C15855 C15856

Special Conditions for Safe Use (X): When the optional transient protection terminal block is installed, the apparatus is not capable of withstanding the 500V insulation test required by Clause 6.4.12 of EN50020:1994. This must be taken into account when installing the apparatus. N1

ATEX Type n and Dust Certification No.: BAS 00ATEX3105X II 3 GD EEx nL IIC T5 (–40 ≤ Ta ≤ +70 °C) Ui = 55 Vdc max Dust rating: T80 °C (–20 ≤ Ta ≤ 40 °C) IP66 Special Conditions for Safe Use (X): When the optional transient protection terminal block is installed, the apparatus is not capable of withstanding a 500V r.m.s. test to case. This must be taken into account on any installation in which it is used, for example by assuring that the supply to the apparatus is galvanically isolated.

E8

ATEX Flame-Proof and Dust Certification No.: KEMA 00ATEX2013X EEx d IIC T6 (–50 ≤ Ta ≤ 65 °C) EEx d IIC T5 (–50 ≤ Ta ≤ 80 °C) Dust rating T90 °C, IP66 1180 Vmax = 55 V dc

II 1/2 GD

Special Conditions for Safe Use (X): This device contains a thin wall diaphragm. Installation, maintenance, and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.

12

C15857

I4

JIS Intrinsic Safety Ex ia IIC T4 Certificate

Description

C16406

3051CD/CG

Australian Certifications I7

SAA Intrinsic Safety Certification No.: AUS Ex 1249X Ex ia IIC T4 (Tamb = 70 °C) Ex ia IIC T5 (Tamb = 40 °C) IP66 When connected per Rosemount drawing 03031-1026 TABLE 6. Input Parameters Ui = 30V Ii = 200 mA Ii = 160 mA (output code A with T1) Pi = 0.9W Ci = 0.01 µF Ci = 0.042 µF (output code M) Li = 10 µH Li = 1.05 mH (output code A with T1) Li = 0.75 mH (output code M with T1) Special Conditions for Safe Use (X): The apparatus may only be used with a passive current limited power source Intrinsic Safety application. The power source must be such that Po ≤ (Uo * Io) / 4. Modules using transient protection in the terminal assembly (T1 transient protection models) the apparatus enclosure is to be electrically bonded to the protective earth. The conductor used for the connection shall be equivalent to a copper conductor of 4 mm2 minimum cross-sectional area.


Product Data Sheet 00813-0100-4001, Rev FA August 2004

E7

Rosemount 3051

SAA Explosion-Proof (Flame-Proof) Certification No.: AUS Ex 03.1347X Ex d IIC T6 (Tamb = 40 °C) Ex d IIC T5 (Tamb = 80 °C) DIP A21 T6 (Tamb = 40 °C) DIP A21 T5 (Tamb = 80 °C) IP66 Special Conditions for Safe Use (X): It is a condition of safe use for transmitter enclosures having cable entry thread other than metric conduit thread that the equipment be utilized with an appropriate certified thread adaptor.

N7

SAA Type n (Non-sparking) Certification No.: AUS Ex 1249X Ex n IIC T4 (Tamb = 70 °C) Ex n IIC T5 (Tamb = 40 °C) IP66 Special Conditions for Safe Use (X): Where the equipment is installed such that there is an unused conduit entry, it must be sealed with a suitable blanking plug to maintain the IP40 degree of protection. Any blanking plug used with the equipment shall be of a type which requires the use of a tool to effect its removal. Voltage source shall not exceed 60V ac or 75V dc.

Combinations of Certifications Stainless steel certification tag is provided when optional approval is specified. Once a device labeled with multiple approval types is installed, it should not be reinstalled using any other approval types. Permanently mark the approval label to distinguish it from unused approval types. K5

E5 and I5 combination

KB

K5 and C6 combination

KD

K5, C6, I1, and E8 combination

K6

C6, I1, and E8 combination

K8

E8 and I1 combination

K7

E7, I7, and N7 combination

13


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051 FIELDBUS PROTOCOL Hazardous Locations Certifications North American Certifications

IA

FM Approvals E5

Explosion-Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition-Proof for Class II, Division 1, Groups E, F, and G. Dust-Ignition-Proof for Class III, Division 1.

Ui = 17.5 V Ii = 380 mA Pi = 5.32 W Ci = ≤ 5 µF Li = ≤ 10 µH

Intrinsically Safe for use in Class I, Division 1, Groups A, B, C, and D; Class II, Division 1, Groups E, F, and G; Class III, Division 1 when connected per Rosemount drawing 03031-1019; Non-incendive for Class I, Division 2, Groups A, B, C, and D.

Special Conditions for Safe Use (X): The device is not capable of withstanding the 500V insulation test required by Clause 6.4.12 of EN50020:1994. This must be taken into account when installing the apparatus.

Temperature Code:T4 (Ta = 40 °C), T3 (Ta = 85 °C), Enclosure Type 4X For input parameters see control drawing 03031-1019.

Canadian Standards Association (CSA) E6

C6

European Certifications I1

ATEX Intrinsic Safety and Dust Certification No.: BAS 98ATEX1355X II 1 GD EEx ia IIC T4 (Tamb = –60 to +60 °C) Dust Rating: T70 °C (Tamb –20 to 40 °C) IP66 1180 TABLE 7. Input Parameters Ui = 30V Ii = 300 mA Pi = 1.3 W Ci = 0 µF Special Conditions for Safe Use (X): The device is not capable of withstanding the 500V insulation test required by Clause 6.4.12 of EN50020:1994. This must be taken into account when installing the apparatus.

14

N1

Explosion-Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition-Proof for Class II and Class III, Division 1, Groups E, F, and G. Suitable for Class I, Division 2 Groups A, B, C, and D for indoor and outdoor hazardous locations. Enclosure type 4X, factory sealed Explosion-Proof and intrinsically safe approval. Intrinsically safe for Class I, Division 1, Groups A, B, C, and D when connected in accordance with Rosemount drawings 03031-1024. Temperature Code T3C. Explosion-Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition-Proof for Class II and Class III, Division 1, Groups E, F, and G. Suitable for Class I, Division 2 Groups A, B, C, and D hazardous locations. Enclosure type 4X, factory sealed For input parameters see control drawing 03031-1024.

II 1 G

TABLE 8. Input Parameters

T5 (Ta = 85 °C), Factory Sealed, Enclosure Type 4X I5

ATEX FISCO Intrinsic Safety Certification No.: BAS 98ATEX1355X EEx ia IIC T4 (Tamb = –60 to +60 °C) IP66 1180

ATEX Type n and Dust Certification No.: BAS 98ATEX3356X II 3 GD EEx nL IIC T5 (Tamb = –40 to +70 °C) Ui = 40 Vdc max Dust rating: T80 °C (Tamb = –20 to 40 °C) IP66 Special Conditions for Safe Use (X): The device is not capable of withstanding the 500V insulation test required by Clause 6.4.12 of EN50020:1994. This must be taken into account when installing the apparatus.

E8

ATEX Flame-Proof and Dust Certification No.: KEMA 00ATEX2013X EEx d IIC T6 (Tamb = –50 to 65 °C) EEx d IIC T5 (Tamb = –50 to 80 °C) Dust rating T90 °C, IP66 1180 Vmax = 55 V dc

II 1/2 GD

Special Conditions for Safe Use (X): This device contains a thin wall diaphragm. Installation, maintenance, and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Japanese Certifications E4

Rosemount 3051 E7

JIS Flame-Proof Ex d IIC T6 Certificate C15852 C15853 C15858 C15859 C15860 C15861

Description 3051C/D/1 FOUNDATION Fieldbus — no meter 3051C/D/1 FOUNDATION Fieldbus — with meter 3051T/G/1 FOUNDATION Fieldbus, SST, Silicon — no meter 3051T/G/1 FOUNDATION Fieldbus, Hastelloy C276, Silicon — no meter 3051T/G/1 FOUNDATION Fieldbus, SST, Silicon — with meter 3051T/G/1 FOUNDATION Fieldbus, Hastelloy C276, Silicon — with meter

Special Conditions for Safe Use (X): It is a condition of safe use for transmitter enclosures having cable entry thread other than metric conduit thread that the equipment be utilized with an appropriate certified thread adaptor. N7

Australian Certifications I7

TABLE 9. Input Parameters

Special Conditions for Safe Use (X): The apparatus may only be used with a passive current limited power source Intrinsic Safety application. The power source must be such that Po ≤ (Uo * Io) / 4. Modules using transient protection in the terminal assembly (T1 transient protection models) the apparatus enclosure is to be electrically bonded to the protective earth. The conductor used for the connection shall be equivalent to a copper conductor of 4 mm2 minimum cross-sectional area.

SAA Type n (Non-sparking) Certification No.: AUS Ex 1249X Ex n IIC T4 (Tamb = 70 °C) Ex n IIC T5 (Tamb = 40 °C) IP66 Special Conditions for Safe Use (X): Where the equipment is installed such that there is an unused conduit entry, it must be sealed with a suitable blanking plug to maintain the IP40 degree of protection. Any blanking plug used with the equipment shall be of a type which requires the use of a tool to effect its removal. Voltage source shall not exceed 60V ac or 75V dc.

SAA Intrinsic Safety Certification No.: AUS Ex 1249X Ex ia IIC T4 (Tamb = 60 °C) IP66 When connected per Rosemount drawing 03031-1026. Ui = 30 V Ii = 300 mA Pi = 1.3 W Ci = 0 µF Li = 0 µH

SAA Explosion-Proof (Flame-Proof) Certification No.: AUS Ex 1347X Ex d IIC T6 (Tamb = 40 °C) Ex d IIC T5 (Tamb = 80 °C) DIP A21 T6 (Tamb = 40 °C) DIP A21 T5 (Tamb = 80 °C) IP65

Combinations of Certifications Stainless steel certification tag is provided when optional approval is specified. Once a device labeled with multiple approval types is installed, it should not be reinstalled using any other approval types. Permanently mark the approval label to distinguish it from unused approval types. K5

E5 and I5 combination

KB

K5 and C6 combination

KD

K5, C6, I1, and E8 combination

K6

C6, I1, and E8 combination

K8

E8 and I1 combination

K7

E7, I7, and N7 combination

15


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051 Dimensional Drawings 3051 Exploded View

Certification Label

Span and Zero Adjustments(1) (Standard) Electronics Housing

Terminal Block Cover O-ring Cover Electronics Board

Nameplate Sensor Module Housing Rotation Set Screw (180째 Maximum Housing Rotation without Further Disassembly)

Coplanar Flange

Drain/Vent Valve

Process O-Ring

Flange Adapter O-Ring Flange Alignment Screw (Not Pressure Retaining)

Flange Adapters

3031B08A

Flange Bolts

1) Span and Zero Adjustments are not available with fieldbus or profibus protocols.

16


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051 3051C Coplanar Flange Dimensional Drawing (Differential Pressure Transmitter Shown)

5.0 (127) 4.3 (110) 0.75 (20) Clearance for Cover Removal

0.75 (20) Clearance for Cover Removal

1/2–14 NPT Conduit Connection Conduit (Two Places, Connection Other (Two Sizes Places, Available) Other

Certification Label

4.1 (105)

Terminal Connections

Transmitter Circuitry

7.17.1 (181) (181 8.2 (209)

Nameplate Drain/Vent Valve Coplanar Flange Process Connection Per IEC 61518 2.126 (54) ±0.012 in. Connection Centers

6.4 (163)

3051-3031A06A, B06A

Housing Rotation Set Screw

¼–18 NPT on Coplanar Flange for Pressure Connection without the Use of Flange Adapters

1/2–14 NPT on Optional Flange Adapters. Adapters can be rotated to give connection centers of 2.00 (51), 2.126 (54), or 2.25 (57).

Coplanar Flange Mounting Configurations with Optional Bracket (B4) for 2-in. Pipe or Panel Mounting 2.8 (72)

4.3 (110)

5/16 ⫻

PANEL MOUNTING

2.8 (71) 7.1 (181)

11/2 Bolts for Panel Mounting (Not Supplied)

3/8–16

× 11/4 Bolts for Mounting to Transmitter

6.2 (156)

2.8 (71)

1.1 (28) 3.4 (85)

4.8 (120)

6.0 (152)

3.3 (83)

3051-3031A04H,I04A,M04A,L04A,J04A

PIPE MOUNTING

2-inch U-Bolt for Pipe Mounting

Dimensions are in inches (millimeters)

17


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051

Traditional Flange Mounting Configurations with Optional Brackets for 2-in. Pipe or Panel Mounting Traditional Flange Panel Mounting Bracket (option B2/B8)

Traditional Flange 2-in. Pipe Mounting Bracket (option B1/B7/BA)

10.1 (257)

4.2 (106)

Impulse Piping

2.7 (67)

1.1 (28)

3051-3031J19D, I19C, E19C, C19A

3.8 (95) 5/16

x 7/8 Bolts for Panel Mounting (Not Supplied)

9.6 (243)

2.7 (67)

6.2 (158) 2.81(71)

1.4 (33)

PANEL MOUNTING BRACKET

PIPE MOUNTING BRACKET

4.6 (116)

Traditional Flange (Options H2–H7) Dimensional Drawing 5.0 (127) 4.3 (110) 0.75 (20) Clearance for Cover Removal

1/2–14 NPT Conduit Connection (Two Places Other Sizes Available)

Housing Rotation Set Screw

Transmitter Circuitry

Terminal Connections

Certification Label

4.1 (105)

7.9 (202)

Nameplate /4–18 NPT on Traditional Flange for Pressure Connection Without the Use of Flange Adapters. Connection Per IEC 61518 2.126 (54) ±0.12 in. Connection Centers

1.7 (43)

2.126 (54)

/2–14 NPT on Optional Flange Adapters. Adaptors Can Be Rotated to Give Connection Centers of 2.00 (51), 2.126 (54), or 2.25 (57).

Dimensions are in inches (millimeters)

18

Drain/ Vent Valve 1.1 (28)

3.4 (87)

1.1 (28)

3051-3031E30A, D30B

1

1


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051 3051T Dimensional Drawings 1/2–14

NPT Conduit Connection (Two Places, Other Sizes Available)

5.0 (127) 4.3 (110)

Certification Label 4.1 (105)

0.75 (20) Clearance for Cover Removal

0.75 (20) Clearance for Cover Removal

Transmitter Circuitry

Terminal Connections

7.2 (183) 3051-3051TC6A, TB6A

Nameplate Housing Rotation Set Screw

3051T Typical Mounting Configurations with Optional Mounting Bracket Pipe Mounting

Panel Mounting 4.3 (110)

2.9 (72)

5.1 (130)

6.2 (156) 2.8 (71)

3.5 (90)

6.3 (160)

4.8 (120) 6.9 (175)

3051-3051TA4A, TB4A, TC4A

2 (50)

Dimensions are in inches (millimeters)

19


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051

3051H Pressure Transmitter Exploded View and Dimensional Drawings Secondary Filled System

Sensor Module

High Side Process Flange

3051-3051HB2G

Process Isolating Diaphragm Low Side Process Flange Drain/Vent Valve Flange Bolts 1/2–14 NPT Conduit Connection (Two Places, Other Sizes Available)

5.0 (127) 4.3 (110)

0.75 (19) Clearance for Cover Removal

Transmitter Circuitry

4.1 (105)

Certification Label

0.75 (19) Clearance for Cover Removal Terminal Connections

Nameplate

9.0 (228)

Housing Rotation Set Screw

10.8 (275)

1.2 (30) 1

1

/2–18 NPT on Process Flange for Pressure Connection Without the Use of Mounting Adapters

1.1 (28)

/2–14 NPT on Optional Mounting Adapters. Adapters Can Be Rotated to Give Adapter Connection Centers of 2.00 (51), 2.126 (54), or 2.25 (57).

Dimensions are in inches (millimeters)

20

3.4 (86)

3051-3051i01A, H01B

Drain/Vent Valve


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051

3051H Mounting Brackets for 2-in. Pipe and Panel Mount (Option Code B5/B6)

PIPE MOUNTING CONFIGURATIO

Impulse Piping

2.7 (67)

0.7 (16) 4.4 (109)

2.7 (67)

3051-3031G19A, F19B, 3051HB3A, HA3B

Supplied for Attaching Bracket to Transmitter

7/16–20⫻3/4 Bolts

PANEL MOUNTING CONFIGURATION

Impulse Piping

Dimensions are in inches (millimeters)

21


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051 3051L Dimensional Drawings 2-in. Flange Configuring (Flush Mount Only) Certification Label

3- and 4-in. Flange Configuration Certification Label

4.1 (105)

4.1 (105)

Serrated Face Gasket Surface

1 (25)

Housing Rotation Set Screw

E F E

D

Lower Housing Gasket

A

1

1/2–14

/2–14 NPT Mounting Adapter (optional)

Extension 2, 4, or 6 (51, 102, or 152) Optional Flushing Connection Ring (LOWER HOUSING)

NPT Mounting Adapter (optional)

A

1 /2–14 NPT Conduit Connections (optional)

1 (25)

6.5 (165)

5.0 (127) 4.3 (110)

Transmitter Circuitry 0.75 (19) Clearance for Cover Removal

Terminal Connections 0.75 (19) Clearance for Cover Removal

5.14 (131)

7.1 (181) 8.2 (209)

Flushing Connection Nameplate Diaphragm Assembly and Mounting Flange

B

C 1

/4–18 NPT on Flange for Pressure Connection without the Use of Mounting Adapters

Dimensions are in inches (millimeters)

22

Drain/Vent Valve

3051-3031B27A, 27B, 27C, 3031B27D, C27E

F E


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051

TABLE 10. 3051L Dimensional Specifications Except where indicated, dimensions are in inches (millimeters). Bolt Circle Diameter

Outside Diameter

No. of Bolts

Bolt Hole Diameter

Exten. Diam.(1) D

O.D. Gask. Surf. E

Proc. Side F

Class

Pipe Size

Flange Thickness

ASME B 16.5 (ANSI) 150

2 (51) 3 (76) 4 (102) 2 (51) 3 (76) 4 (102) 2 (51) 3 (76) DN 50

1.12 (28) 1.31 (33) 1.31 (33) 1.25 (32) 1.50 (38) 1.62 (41) 1.12 (28) 1.37 (35) 26 mm

4.75 (121) 6.0 (152) 7.5 (191) 5.0 (127) 6.62 (168) 7.88 (200) 5.0 (127) 6.62 (168) 125 mm

6.0 (152) 7.5 (191) 9.0 (229) 6.5 (165) 8.25 (210) 10.0 (254) 6.5 (165) 6.62 (168) 165 mm

4 4 8 8 8 8 8 8 4

0.75 (19) 0.75 (19) 0.75 (19) 0.75 (19) 0.88 (22) 0.88 (22) 0.75 (19) 0.88 (22) 18 mm

NA 2.58 (66) 3.5 (89) NA 2.58 (66) 3.5 (89) NA 2.58 (66) NA

3.6 (92) 5.0 (127) 6.2 (158) 3.6 (92) 5.0 (127) 6.2 (158) 3.6 (92) 5.0 (127) 4.0 (102)

2.12 (54) 3.5 (89) 4.5 (114) 2.12 (54) 3.5 (89) 4.5 (114) 2.12 (54) 3.5 (89) 2.5 (63)

DN 80 DN 100 DN 100

30 mm 30 mm 26 mm

160 mm 190 mm 180 mm

200 mm 235 mm 220 mm

8 8 8

18 mm 22 mm 18 mm

65 mm 89 mm 89 mm

5.4 (138) 6.2 (158) 6.2 (158)

3.7 (94) 4.5 (114) 4.5 (114)

ASME B 16.5 (ANSI) 300 ASME B 16.5 (ANSI) 600 DIN PN 10–40 DIN PN 25/40 DIN PN 10/16

(1) Tolerances are 0.040 (1,02), –0.020 (0,51)

23


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051 Ordering Information TABLE 11. 3051C Differential, Gage, and Absolute Pressure Transmitters — = Not Applicable

• = Applicable

Model

Transmitter Type (Select One)

CD

CG

CA

3051CD 3051CG 3051CA

Differential Pressure Transmitter Gage Pressure Transmitter Absolute Pressure Transmitter

• — —

— • —

— — •

0(2) 1 2 3 4 5 Code A M(3)

F W

Code 2 3(4) 4 5 7(4) 8(4) 0

3051CG(1)

CD

CG

CA

–3 to 3 inH2O/0.1 inH2O (–7,5 to 7,5 mbar/0,25 mbar) –25 to 25 inH2O/0.5 inH2O (–62,2 to 62,2 mbar/1,2 mbar) –250 to 250 inH2O/2.5 inH2O (–623 to 623 mbar/6,2 mbar) –1000 to 1000 inH2O/10 inH2O (–2,5 to 2,5 bar/25 mbar) –300 to 300 psi/3 psi (–20,7 to 20,7 bar/0,2 bar) –2000 to 2000 psi/20 psi (–137,9 to137,9 bar/1,4 bar)

Not Applicable

Not Applicable

–25 to 25 inH2O/0.5 inH2O (–62,2 to 62,2 mbar/1,2 mbar) –250 to 250 inH2O/2.5 inH2O (–623 to 623 mbar/6,2 mbar) –407 to 1000inH2O/10in H2O (–1,01 to 2,5 bar/25 mbar) –14.7 to 300 psi/3 psi (–1,01 to 20,7 bar/0,2 bar) –14.7 to 2000 psig/20 psi (–1,01 to 137,9 bar/1,4 bar)

0 to 30 psia/0.3 psia (0 to 2,1 bar/20,7 mbar) 0 to 150 psia/1.5 psia (0 to 10,3 bar/0,1 bar) 0 to 800 psia/8 psia (0 to 55,2 bar/0,55 bar) 0 to 4000 psia/40 psia (0 to 275,8 bar/2,8 bar) Not Applicable

CD

CG

CA

CD

CG

CA

• • • • • • •

• • • • • • •

• • • • • • •

CD

CG

CA

• • • • • •

• • • • • •

• • • — • •

• •

• •

• •

CD

CG

CA

• •

• •

• —

3051CA

Output 4–20 mA with Digital Signal Based on HART Protocol Low-Power, 1–5 V dc with Digital Signal Based on HART Protocol (See Option C2 for 0.8–3.2 V dc) FOUNDATION fieldbus Profibus — PA Materials of Construction Process Flange Type Flange Material Coplanar SST Coplanar Alloy C Coplanar Monel Coplanar Plated CS Coplanar SST Coplanar Plated CS Alternate Flange—See Options on page 25

Drain/Vent SST Hastelloy C276 Monel SST Hastelloy C276 Hastelloy C276

Code

Isolating Diaphragm

2(4) 3(4) 4 5 6 7 Code

316L SST Hastelloy C276 Monel Tantalum (Available on 3051CD and CG, Ranges 2–5 only. Not available on 3051CA) Gold-plated Monel (Use in combination with O-ring Option Code B.) Gold-plated SST

A B Code 1 2

24

3051CD

O-ring Glass-filled PTFE Graphite-filled PTFE Fill Fluid Silicone Inert fill (Halocarbon)


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051

TABLE 11. 3051C Differential, Gage, and Absolute Pressure Transmitters — = Not Applicable Code A B C D J K L M Code A01 D01

Housing Material

Conduit Entry Size

Polyurethane-covered Aluminum Polyurethane-covered Aluminum Polyurethane-covered Aluminum Polyurethane-covered Aluminum SST SST SST SST

½–14 NPT M20 × 1.5 (CM20) PG 13.5 G½ ½–14 NPT M20 × 1.5 (CM20) PG 13.5 G½

• = Applicable

PlantWeb Functionality Regulatory control suite: PID, arith, signal char, integ, etc.; requires FOUNDATION fieldbus Diagnostics suite, Plugged Impulse Line and SPM diagnostics; requires FOUNDATION fieldbus

Code

Alternate Flange Options (Requires Materials of Construction Code 0)

H2 H3(4) H4 H7(4) HJ HK HL FA FB FC FD FP FQ

Traditional Flange, 316 SST, SST Drain/Vent Traditional Flange, Alloy C, Hastelloy C276 Drain/Vent Traditional Flange, Monel, Monel Drain/Vent Traditional Flange, 316 SST, Hastelloy C276 Drain/Vent DIN Compliant Traditional Flange, SST, 7/16 in. Adapter/Manifold Bolting DIN Compliant Traditional Flange, SST, 10 mm Adapter/Manifold Bolting DIN Compliant Traditional Flange, SST, 12mm Adapter/Manifold Bolting (Not available on 3051CD0) Level Flange, SST, 2 in., ANSI Class 150, Vertical Mount Level Flange, SST, 2 in., ANSI Class 300, Vertical Mount Level Flange, SST, 3 in., ANSI Class 150, Vertical Mount Level Flange, SST, 3 in., ANSI Class 300, Vertical Mount DIN Level Flange, SST, DN 50, PN 40, Vertical Mount DIN Level Flange, SST, DN 80, PN 40, Vertical Mount

Code

Integral Mount Manifold Options (Requires Materials of Construction Code 0)

S5 Code S4

S3

Code S1 S2 Code S7 S8 S0 S9

Assemble to Rosemount 305 Integral Manifold (specified separately, see the Rosemount 305 and 306 Integral Manifolds PDS (document number 00813-0100-4733)) Integral Mount Primary Elements (Optional) Factory Assembly to Rosemount Primary Element (Annubar or Rosemount 1195 Integral Orifice) (With the primary element installed, the maximum operating pressure will equal the lesser of either the transmitter or the primary element. Option is available for factory assembly to range 1–4 transmitters only) Factory Assembly to Rosemount 405 Primary Element Diaphragm Seal Assemblies (Optional) NOTE: Standard flange and adapter bolts are austenitic 316 SST. One Diaphragm Seal (Direct Mount or Capillary Connection Type) Two Diaphragm Seals (Direct Mount or Capillary Connection Type) Optional All Welded Diaphragm Seal Systems (for high vacuum applications) NOTE: Standard flange and adapter bolts are austenitic 316 SST. One Diaphragm Seal, All-Welded System (Capillary Connection Type) Two Diaphragm Seals, All-Welded System (Capillary Connection Type) One Diaphragm Seal, All-Welded System (Direct Mount Connection Type) Two Diaphragm Seals, All-Welded System (One Direct Mount and One Capillary Connection Type)

CD

CG

CA

• • • • • • • •

• • • • • • • •

• • • • • • • •

CD

CG

CA

• •

• •

• •

CD

CG

CA

• • • • • • • • • • • • •

• • • • • • • • • • • • •

• • • • • • • • • • • • •

CD

CG

CA

CD

CG

CA

CD

CG

CA

• •

• —

• —

CD

CG

CA

• • • •

• — • —

• — • —

25


Product Data Sheet

Rosemount 3051 TABLE 11. 3051C Differential, Gage, and Absolute Pressure Transmitters — = Not Applicable Code B4 B1 B2 B3 B7 B8 B9 BA BC Code E5 I5 K5 I1(5) N1(5)

E8 E4(5) I4 C5(6)

00813-0100-4001, Rev FA August 2004

• = Applicable

Mounting Bracket Options Coplanar Flange Bracket for 2-in. Pipe or Panel Mounting, all SST Traditional Flange Bracket for 2-in. Pipe Mounting, CS Bolts Traditional Flange Bracket for Panel Mounting, CS Bolts Traditional Flange Flat Bracket for 2-in. Pipe Mounting, CS Bolts B1 Bracket with Series 300 SST Bolts B2 Bracket with Series 300 SST Bolts B3 Bracket with Series 300 SST Bolts SST B1 Bracket with Series 300 SST Bolts SST B3 Bracket with Series 300 SST Bolts Hazardous Locations Certification Options FM Explosionproof Approval FM Non-incendive and Intrinsic Safety Approval FM Explosionproof and Intrinsic Safety Approval ATEX Intrinsic Safety and Dust Certification ATEX Type N and Dust Certification ATEX Flame-proof and Dust Certification JIS Flame-proof Certification JIS Intrinsic Safety Certification (Only available with HART Option Code A) Measurement Canada Accuracy Approval (Limited availability depending on transmitter type and range.

CD

CG

CA

• • • • • • • • •

• • • • • • • • •

• • • • • • • • •

CD

CG

CA

• • •

• • •

• • •

CD

CG

CA

• • •

• • •

• • •

CD

CG

CA

• •

• •

• •

Contact an Emerson Process Management representative) C6 K6(5) KB K7 K8(5) KD(5)

I7 E7 N7 IA Code L4 L5 L6 Code M5 M6

26

CSA Explosion-proof and Intrinsic Safety Approval CSA and ATEX Explosion-proof and Intrinsic Safety Approval (combination of C6 and K8) FM and CSA Explosion-proof and Intrinsic Safety Approvals (combination of K5 and C6) SAA Flame-proof and Intrinsic Safety Approvals (combination of I7, N7, and E7) ATEX Flame-proof and Intrinsic Safety Approvals (combination of I1 and E8) CSA, FM, and ATEX Explosion-proof and Intrinsic Safety Approval (combination of K5, C6, I1, and E8) SAA Intrinsic Safety Certification SAA Flame-proof Certification SAA Type N Certification ATEX Intrinsic Safety for FISCO; for FOUNDATION fieldbus protocol only Bolting Options Austenitic 316 SST Bolts ASTM A 193, Grade B7M Bolts Monel Bolts Meters (Optional) LCD display for Aluminum Housing (Housing Codes A, B, C, and D only) LCD display for SST Housing (Housing Codes J, K, L, and M only)


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051

TABLE 11. 3051C Differential, Gage, and Absolute Pressure Transmitters — = Not Applicable Code Q4 Q8

• = Applicable

Other Options Calibration Data Sheet Material Traceability Certification per EN 10204 3.1.B (Only available for the sensor module housing and

CD

CG

CA

• • •

• • •

• • •

• • • • • •

• • • • — •

• • • • — •

Coplanar or traditional flanges and adapters (3051C), and for the sensor module housing and low-volume Coplanar flange and adapter (3051C with Option Code S1))

Q16 QP QS J1(6)(7) J3(6)(7) T1 C1(6) C2(6) C3 C4(6)(8) CN(6)(8) P1 P2 P3 P4 DF D7 D8 D9 P8 P9 V5(9)

Surface finish certification for sanitary remote seals Calibration certification and tamper evident seal Quality Certification for safety Local Zero Adjustment Only No Local Zero or Span Adjustment Transient Protection Terminal Block Custom Software Configuration (Completed CDS 00806-0100-4001 required with order) 0.8–3.2 V dc Output with Digital Signal Based on HART Protocol (Output Code M only) Gage Calibration (3051CA4 only) Analog Output Levels Compliant with NAMUR Recommendation NE 43 Analog Output Levels Compliant with NAMUR Recommendation NE 43 Alarm Configuration–Low Hydrostatic Testing Cleaning for Special Service Cleaning for <1 PPM Chlorine/Fluorine Calibrate at line pressure (Specify Q48 on order for corresponding certificate) 1/2 -14 NPT flange adapter(s)— Material determined by flange material Coplanar Flange Without Drain/Vent Ports Ceramic Ball Drain/Vents JIS Process Connection—RC ¼ Flange with RC ½ Flange Adapter 0.04% accuracy to 5:1 turndown (Range 2-4) 4500 psig Static Pressure Limit (3051CD Ranges 2–5 only) External Ground Screw Assembly

Typical Model Number:

3051CD

2

A

2

2

A

1

A

B4

(1) 3051CG lower range limit varies with atmospheric pressure. (2) 3051CD0 is available only with Output Code A, Process Flange Code 0 (Alternate Flange H2, H7, HJ, or HK), Isolating Diaphragm Code 2, O-ring Code A, and Bolting Option L4. (3) Not available with hazardous locations certification Options Codes I1, N1, E4, K6 and K8. (4) Materials of Construction comply with recommendations per NACE MR0175/ISO 15156 for sour oil field production environments. Environmental limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments. (5) Not available with Low Power code M. (6) Not available with Fieldbus (output code F) or Profibus (output code W). (7) Local zero and span adjustments are standard unless Option Code J1 or J3 is specified (8) NAMUR-Compliant operation is pre-set at the factory and cannot be changed to standard operation in the field. (9) The V5 option is not needed with the T1 option; external ground screw assembly is included with the T1 option.

27


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051 TABLE 12. 3051T Gage and Absolute Pressure Transmitter Model

Transmitter Type

3051T Code

Pressure Transmitter Pressure Type

G A Code

Gage Absolute Pressure Ranges (Range/Min. Span) 3051TG(1) –14.7 to 30 psi/0.3 psi (–1,01 to 2,1 bar/20,7 mbar) –14.7 to 150 psi/1.5 psi (–1,01 to 10,3 bar/103,4 mbar) –14.7 to 800 psi/8 psi (–1,01 to 55,2 bar/0,55 bar) –14.7 to 4000 psi/40 psi (–1,01 to 275,8 bar/2,8 bar) –14.7 to 10000 psi/2000 psi (–1,01 to 689,5 bar/138 bar) Output

1 2 3 4 5 Code A

3051TA 0 to 30 psia/0.3 psia (0 to 2,1 bar/20,7 mbar) 0 to 150 psia/1.5 psia (0 to 10,3 bar/103,4 mbar) 0 to 800 psia/8 psia (0 to 55,2 bar/0,55 bar) 0 to 4000 psia/40 psia (0 to 275,8 bar/2,8 bar) 0 to 10000 psia/2000 psia (0 to 689,5 bar/138 bar)

Code

4–20 mA with Digital Signal Based on HART Protocol Low-Power 1–5 V dc with Digital Signal Based on HART Protocol (See Option Code C2 for 0.8–3.2 V dc Output) (Not available with hazardous certification Option Codes I1, N1, E4, K6 or K8) FOUNDATION fieldbus Profibus — PA Process Connection Style 1/2–14 NPT Female G½ A DIN 16288 Male (Available in SST for Range 1–4 only) Coned and Threaded, Compatible with Autoclave Type F-250-C (Only available in SST for Range 5) Isolating Diaphragm Process Connection Wetted Parts Material

2(2) 3(2) Code

316L SST Hastelloy C276 Fill Fluid

1 2 Code

Silicone Inert (Fluorinert® FC-43) Housing Material

A B C D J K L M Code

Polyurethane-covered Aluminum Polyurethane-covered Aluminum Polyurethane-covered Aluminum Polyurethane-covered Aluminum SST SST SST SST PlantWeb Functionality

A01 D01 Code

Regulatory control suite: PID, arith, signal char, integ, etc.; requires FOUNDATION fieldbus Diagnostics suite, Plugged Impulse Line and SPM diagnostics; requires FOUNDATION fieldbus Integral Mount Manifold (Optional)

M

F W

Code 2B 2C 2F

S5

316L SST Hastelloy C276

Conduit Entry Size ½–14 NPT M20 × 1.5 (CM20) PG 13.5 G½ ½–14 NPT M20 × 1.5 (CM20) PG 13.5 G½

Code

Assemble to Rosemount 306 Integral Manifold (specified separately, see the Rosemount 305 and 306 Integral Manifolds PDS (document number 00813-0100-4733)) (Requires 1/2-in. process connection code 2B) Remote Diaphragm Seals Assemblies (Optional)

S1 Code

One remote diaphragm seal (Direct Mount or Capillary Connection Type) (Requires Process Connection Style code 2B) Mounting Brackets (Optional)

B4

28

Bracket for 2-in. Pipe or Panel Mounting, All SST


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051

TABLE 12. 3051T Gage and Absolute Pressure Transmitter Code E5 I5 K5 C5 C6 K6(3) KB K7 K8(3) KD(3) I7 E4(3) E7 N7 I1(3) N1(3)

E8 DW IA Code

Hazardous Locations Certifications (Optional) FM Explosion-proof Approval FM Non-incendive and Intrinsic Safety Approval FM Explosion-proof and Intrinsic Safety Approval Measurement Canada accuracy approval (Limited availability depending on transmitter type and range. Contact an Emerson Process Management representative) CSA Explosion-proof and Intrinsic Safety Approval CSA and ATEX Explosion-proof and Intrinsic Safety Approval (combination of C6 and K8) FM and CSA Explosion-proof and Intrinsic Safety Approvals (combination of K5 and C6) SAA Flame-proof and Intrinsic Safety Approvals (combination of I7, N7, and E7) ATEX Flame-proof and Intrinsic Safety Approvals (combination of I1 and E8) CSA, FM, and ATEX Explosion-proof and Intrinsic Safety Approval (combination of K5, C6, I1, and E8) SAA Intrinsic Safety Certification JIS Flame-proof Certification SAA Flame-proof Certification SAA Type N Certification ATEX Intrinsic Safety and Dust Certification ATEX Type N and Dust Certification ATEX Flame-proof and Dust Certification NSF drinking water approval ATEX Intrinsic Safety for FISCO; for FOUNDATION fieldbus protocol only Other Options

Q4

Calibration Data Sheet Material Traceability Certification per EN 10204 3.1.B NOTE: This option applies to the process connection only. Q16 Surface finish certification for sanitary remote seals QP Calibration certification and tamper evident seal QS Quality certification for safety J1(4)(5) Local Zero Adjustment Only J3(4)(5) No Local Zero or Span Adjustment M5 LCD display for Aluminum Housing (Housing Codes A, B, C, and D only) M6 LCD display for SST Housing (Housing Codes J, K, L and M only) T1 Transient Protection Terminal Block C1(4) Custom Software Configuration (Completed CDS 00806-0100-4001 required with order) C2(4) 0.8–3.2 V dc Output with Digital Signal Based on HART Protocol (Output Code M only) C4(4)(6) Analog Output Levels Compliant with NAMUR Recommendation NE 43, 27-June-1996. CN(4)(6) Analog Output Levels Compliant with NAMUR Recommendation NE 43: Low Alarm Configuration P1 Hydrostatic Testing P2 Cleaning for Special Service P3 Cleaning for <1 PPM Chlorine/Fluorine P8 0.04% accuracy to 5:1 turndown (Range 1-4) V5(7) External Ground Screw Assembly Typical Model Number: 3051T G 5 F 2A 2 1 A B4 Q8

(1) 3051TG lower range limit varies with atmospheric pressure. (2) Materials of Construction comply with recommendations per NACE MR0175/ISO 15156 for sour oil field production environments. Environmental limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments. (3) Not available with low-power Option Code M. (4) Not available with fieldbus (output code F) or Profibus protocols (output code W). (5) Local zero and span adjustments are standard unless Option Code J1 or J3 is specified. (6)

NAMUR-Compliant operation is pre-set at the factory and cannot be changed to standard operation in the field.

(7) The V5 option is not needed with T1 option; external ground screw assembly is included with the T1 option.

29


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051 TABLE 13. 3051L Flange-Mounted Liquid Level Transmitter Model

Transmitter Type

3051L Code

Flange-Mounted Liquid Level Transmitter

2 3 4 Code A M

F W

Pressure Ranges (Range/Min. Span) –250 to 250 inH2O/2.5 inH2O (–0,6 to 0,6 bar/6,2 mbar) –1000 to 1000 inH2O/10 inH2O (–2,5 to 2,5 bar/25 mbar) –300 to 300 psi/3 psi (–20,7 to 20,7 bar/0,2 bar) Output 4–20 mA with Digital Signal Based on HART Protocol Low-Power 1–5 V dc with Digital Signal Based on HART Protocol (See Option Code C2 for 0.8–3.2 V dc Output) (Not available with hazardous certification Option Codes I1, N1, E4, K6, and K8) FOUNDATION fieldbus Profibus – PA

High Pressure Side Code G0 H0 J0 A0 A2 A4 A6 B0 B2 B4 B6 C0 C2 C4 C6 D0 D2 D4 D6 E0 F0

30

Diaphragm Size

Material

Extension Length

2 in./DN 50 2 in./DN 50 2 in./DN 50 3 in./DN 80 3 in./DN 80 3 in./DN 80 3 in./DN 80 4 in./DN 100 4 in./DN 100 4 in./DN 100 4 in./DN 100 3 in./DN 80 3 in./DN 80 3 in./DN 80 3 in./DN 80 4 in./DN 100 4 in./DN 100 4 in./DN 100 4 in./DN 100 3 in./DN 80 4 in./DN 100

316L SST Hastelloy C276 Tantalum 316L SST 316L SST 316L SST 316L SST 316L SST 316L SST 316L SST 316L SST Hastelloy C276 Hastelloy C276 Hastelloy C276 Hastelloy C276 Hastelloy C276 Hastelloy C276 Hastelloy C276 Hastelloy C276 Tantalum Tantalum

Flush Mount Only Flush Mount Only Flush Mount Only Flush Mount 2 in./50 mm 4 in./100 mm 6 in./150 mm Flush Mount 2 in./50 mm 4 in./100 mm 6 in./150 mm Flush Mount 2 in./50 mm 4 in./100 mm 6 in./150 mm Flush Mount 2 in./50 mm 4 in./100 mm 6 in./150 mm Flush Mount Only Flush Mount Only


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051

TABLE 13. 3051L Flange-Mounted Liquid Level Transmitter Code M A B N C D P E X F G Y H J Z L Q R S V K T U W Code A C D H G N P

Mounting Flange Size 2 in. 3 in. 4 in. 2 in. 3 in. 4 in. 2 in. 3 in. 2 in. 3 in. 4 in. 2 in. 3 in. 4 in. 2 in. 3 in. DN 50 DN 80 DN 100 DN 100 DN 50 DN 80 DN 100 DN 100

ASME B 16.5 (ANSI) or DIN Flange Rating Class 150 Class 150 Class 150 Class 300 Class 300 Class 300 Class 600 Class 600 Class 150 Class 150 Class 150 Class 300 Class 300 Class 300 Class 600 Class 600 PN 10-40 PN 40 PN 40 PN 10/16 PN 10-40 PN 40 PN 40 PN 10/16

Material CS CS CS CS CS CS CS CS SST SST SST SST SST SST SST SST CS CS CS CS SST SST SST SST

Process Fill-High Pressure Side

Temperature Limits

Syltherm XLT D. C. Silicone 704 D. C. Silicone 200 Inert (Halocarbon) Glycerine and Water Neobee M-20 Propylene Glycol and Water

–100 to 300 °F (–73 to 135 °C) 60 to 400 °F (15 to 205 °C) –40 to 400 °F (–40 to 205 °C) –50 to 350 °F (–45 to 177 °C) 0 to 200 °F (–17 to 93 °C) 0 to 400 °F (–17 to 205 °C) 0 to 200 °F (–17 to 93 °C)

Low Pressure Side Code

Configuration

Flange Adapter

Diaphragm Material

Sensor Fill Fluid

11 21 22 2A 2B 31 Code

Gage Differential Differential Differential Differential Remote Seal

SST SST SST SST SST SST

316L SST 316L SST Hastelloy C276 316L SST Hastelloy C276 316L SST

Silicone Silicone Silicone Inert (Halocarbon) Inert (Halocarbon) Silicone (Requires Option Code S1)

A

O-ring Material Glass-filled PTFE

31


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051 TABLE 13. 3051L Flange-Mounted Liquid Level Transmitter Code A B C D J K L M Code A01 D01

Conduit Entry Size ½–14 NPT M20 × 1.5 (CM20) PG 13.5 G½ ½–14 NPT M20 × 1.5 (CM20) PG 13.5 G½

PlantWeb Functionality Regulatory control suite: PID, arith, signal char, integ, etc. (requires Foundation fieldbus) Diagnostics suite, Plugged Impulse Line and SPM diagnostics (requires Foundation fieldbus)

Code

Diaphragm Seal Assemblies (Optional)

S1 Code

One Diaphragm Seal (requires low pressure side Option Code 31 capillary connection type)

E5 I5 K5 I1(1) N1(1)

E8 E4(1) C6 K6(1)

KB K7 K8(1) KD(1) I7 E7 N7 IA Code L5 Code M5 M6

32

Housing Material Polyurethane-covered Aluminum Polyurethane-covered Aluminum Polyurethane-covered Aluminum Polyurethane-covered Aluminum SST SST SST SST

Hazardous Locations Certification Options FM Explosion-proof Approval FM Non-incendive and Intrinsic Safety Approval FM Explosion-proof and Intrinsic Safety Approval ATEX Intrinsic Safety and Dust Certification ATEX Type N and Dust Certification ATEX Flame-proof and Dust Certification JIS Flame-proof Certification CSA Explosion-proof and Intrinsic Safety Approval CSA and ATEX Explosion-proof and Intrinsic Safety Approval (combination of C6 and K8) FM and CSA Explosion-proof and Intrinsic Safety Approvals (combination of K5 and C6) SAA Flame-proof and Intrinsic Safety Approvals (combination of I7, N7, and E7) ATEX Flame-proof and Intrinsic Safety Approvals (combination of I1 and E8) CSA, FM, and ATEX Explosion-proof and Intrinsic Safety Approval (combination of K5, C6, I1, and E8) SAA Intrinsic Safety Certification SAA Flame-proof Certification SAA Type N Certification ATEX Intrinsic Safety for FISCO; for FOUNDATION fieldbus protocol only Bolt for Flange and Adapters (Optional) ASTM A 193, Grade B7M Bolts Meter Options LCD display for Aluminum Housing (Available with Housing codes A, B, C, and D only) LCD display for SST Housing (Available with Housing codes J, K, L, and M only)


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051

TABLE 13. 3051L Flange-Mounted Liquid Level Transmitter Code Q4

Other Options

Code

Calibration Data Sheet Material Traceability Certification per EN 10204 3.1.B (Available with the diaphragm, upper housing, Coplanar flange, adapter, sensor module housing, lower housing/flushing connection, and extension) Calibration certification and tamper evident seal Local Zero Adjustment Only No Local Zero or Span Adjustment Transient Protection Terminal Block Custom Software Configuration (Completed CDS 00806-0100-4001 required with order) 0.8–3.2 V dc Output with Digital Signal Based on HART Protocol (Available with Output code M only) Analog Output Levels Compliant with NAMUR Recommendation NE 43 Analog Output Levels Compliant with NAMUR Recommendation NE 43: Alarm Configuration–Low Ceramic Ball Drain/Vents External Ground Screw Assembly Diaphragm /Size Lower Housing Flushing Connections

F1 F2 F3(6) F4(6) F7 F8 F9 F0

Ring Material SST SST Hastelloy C276 Hastelloy C276 SST SST Hastelloy C276 Hastelloy C276

Q8

QP J1(2)(3) J3(2)(3) T1

C1(2) C2(2) C4(2)(4) CN(2)(4)

D8 V5(5)

Number 1 2 1 2 1 2 1 2

Size 1/4 1/4 1 /4 1/4 1 /2 1/2 1/2 1 /2

2 in. • • • • • • • •

3 in. • • • • • • • •

4 in. • • • • • • • •

Typical Model Number: (1) Not available with low-power Option Code M (2) Not available with fieldbus (output code F) or profibus protocols (output code W). (3) Local zero and span adjustments are standard unless Option Code J1 or J3 is specified. (4) NAMUR-Compliant operation is pre-set at the factory and cannot be changed to standard operation in the field. (5) The V5 option is not needed with the T1 option; external ground screw assembly is included with the T1 option. (6) Not available with Option Codes A0, B0, and G0.

33


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051 TABLE 14. 3051H Pressure Transmitter for High-Temperature Processes — = Not Applicable Model 3051HD 3051HG Code 2 3 4 5

• = Applicable

Transmitter Type (Select One)

HD

HG

Differential Pressure Transmitter for High-Temperature Processes Gage Pressure Transmitter for High-Temperature Processes 3051HD 3051HG

• —

— •

HD

HG

• •

• •

–250 to 250 inH2O/2.5 inH2O (–0,62 to 0,62 bar/6,2 mbar) –1000 to 1000 inH2O/10 inH2O (–2,5 to 2,5 bar/25 mbar) –300 to 300 inH2O/3 psi (–747 to 747 mbar/0,2 bar) –2000 to 2000 psi/20 psi (–138 to 138 bar/1,4 bar)

–250 to 250 inH2O/2.5 inH2O (–0,62 to 0,62 bar/6,2 mbar) –407 to 1000 inH2O/10in H2O (–1,01 to 2,5 bar/25 mbar) –14.7 to 300 psi/3 psi (–1,01 to 20,7 bar/0,2 bar) –14.7 to 2000 psig/20 psi (–1,01 to 138 bar/1,4 bar)

NOTE: 3051HG lower range limit varies with atmospheric pressure.

Code A

• •

• •

Code

HD

HG

2 7(1) Code

Process Flange Material SST SST Process Isolating Diaphragm

• • HD

• • HG

2 3(1) 5 Code

316L SST Hastelloy C276 Tantalum O-ring Material

• • • HD

• • • HG

A Code

Glass-Filled PTFE Process Fill Fluid

• HD

• HG

D H N Code

D.C. 200 Silicone Inert Neobee M-20 Sensor Module Isolator Material

• • • HD

• • • HG

2 Code

SST Sensor Module Fill Fluid

• HD

• HG

1 2 Code

Silicone Inert (Halocarbon) Housing Material

• • HD

• • HG

A B C D J K L M Code

Polyurethane-covered Aluminum Polyurethane-covered Aluminum Polyurethane-covered Aluminum Polyurethane-covered Aluminum SST SST SST SST PlantWeb Functionality

• • • • • • • •

• • • • • • • •

A01 D01 Code

Regulatory control suite: PID, arith, signal char, integ, etc.; requires FOUNDATION fieldbus Diagnostics suite, Plugged Impulse Line and SPM diagnostics; requires FOUNDATION fieldbus Integral Mount Primary Elements (Optional)

HD

HG

M

F W

S4

34

Output 4–20 mA with Digital Signal Based on HART Protocol Low-Power 1–5 V dc with Digital Signal Based on HART Protocol (See Option Code C2 for 0.8–3.2 V dc Output) (Not available with hazardous certification Option Codes I1, N1, E4, K6, and K8) FOUNDATION fieldbus Profibus – PA Process Connection Drain/Vent SST Hastelloy C276

Conduit Entry Size ½–14 NPT M20 × 1.5 (CM20) PG 13.5 G½ ½–14 NPT M20 × 1.5 (CM20) PG 13.5 G½

Factory Assembly to Rosemount Primary Element (Diamond II+Annubar/Rosemount 1195 Integral Orifice) (With the primary element installed, the maximum operating pressure will equal the lesser of either the transmitter or the primary element. Option is available for factory assembly to range 1–4 transmitters only)


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051

TABLE 14. 3051H Pressure Transmitter for High-Temperature Processes — = Not Applicable

• = Applicable

Code

Mounting Bracket Options

HD

HG

B5 B6 Code

Universal Mounting Bracket for 2-in. Pipe or Panel Mount, CS Bolts Universal Mounting Bracket for 2-in. Pipe or Panel Mount, SST Bolts Hazardous Locations Certification Options

• • HD

• • HG

FM Explosion-proof Approval FM Non-incendive and Intrinsic Safety Approval FM Explosion-proof and Intrinsic Safety Approval ATEX Intrinsic Safety and Dust Certification ATEX Type N and Dust Certification ATEX Flame-proof and Dust Certification JIS Flame-proof Certification CSA Explosion-proof and Intrinsic Safety Approval CSA and ATEX Explosion-proof and Intrinsic Safety Approval (combination of C6 and K8) FM and CSA Explosion-proof and Intrinsic Safety Approvals (combination of K5 and C6) SAA Flame-proof and Intrinsic Safety Approvals (combination of I7, N7, and E7) ATEX Flame-proof and Intrinsic Safety Approvals (combination of I1 and E8) CSA, FM, and ATEX Explosion-proof and Intrinsic Safety Approval (combination of K5, C6, I1, and E8) SAA Intrinsic Safety Certification SAA Flame-proof Certification SAA Type N Certification ATEX Intrinsic Safety for FISCO; for FOUNDATION fieldbus protocol only FM FISCO Intrinsic Safety; for FOUNDATION fieldbus protocol only Bolt for Flange and Adapter Options

• • • • • • • • • • • • • • • • • • HD

• • • • • • • • • • • • • • • • • • HG

Austenitic 316 SST Bolts Meter Options

• HD

• HG

LCD display for Aluminum Housing (Available with Housing codes A, B, C, and D only) LCD display for SST Housing (Available with Housing codes J, K, L, and M only) Other Options

• • HD

• • HG

• • • •

• • • •

• • • • • • • • • • •

• • • • • • • • • • •

E5 I5 K5

I1(2) N1(2)

E8 E4(2) C6 K6(2)

KB K7

KB(2) KD(2)

I7 E7 N7 IA IE Code L4

Code M5 M6

Code

Calibration Data Sheet Material traceability certification per EN 10204 3.1.B Calibration certification and tamper evident seal J1(3) Local Zero Adjustment Only (Local zero and span adjustments are standard unless Option Code J1 or J3 is specified.) J3(3) No Local Zero or Span Adjustment (Local zero and span adjustments are standard unless Option Code J1 or J3 is specified) T1 Transient Protection Terminal Block C1(3) Custom Software Configuration (Completed CDS 00806-0100-4001 required with order) C2(3) 0.8–3.2 V dc Output with Digital Signal Based on HART Protocol (Output Code M only) C4(3)(4) Analog Output Levels Compliant with NAMUR Recommendation NE 43 CN(3)(4) Analog Output Levels Compliant with NAMUR Recommendation NE 43: Alarm Configuration–Low P1 Hydrostatic Testing P2 Cleaning for Special Service P3 Cleaning for <1 PPM Chlorine/Fluorine 1/2–14 NPT flange adapters—SST DF D8 Ceramic Ball Drain/Vents V5(5) External Ground Screw Assembly Typical Model Number: 3051HG 2 A 2 2 A H 2 1 A B5 Q4

Q8 QP

(1) Materials of Construction comply with recommendations per NACE MR0175/ISO 15156 for sour oil field production environments. Environmental limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments. (2) Not available with low-power Option Code M. (3) Not available with fieldbus (output code F) or profibus protocols (output code W). (4) NAMUR-Compliant operation is pre-set at the factory and cannot be changed to standard operation in the field. (5) The V5 option is not needed with the T1 option; external ground screw assembly is included with the T1 option.

35


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051 OPTIONS

Optional Diaphragm and Sanitary Seals

Standard Configuration

Refer to Product Data Sheet 00813-0100-4016 or 00813-0201-4016. for additional information.

Unless otherwise specified, transmitter is shipped as follows:

Output Information(1)

ENGINEERING UNITS Differential/Gage: Absolute/3051T: 4 mA (1 V dc)(1): 20 mA (5 V dc): Output: Flange type: Flange material: O-ring material: Drain/vent: Integral meter: Alarm(1): Software tag:

Output range points must be the same unit of measure. Available units of measure include: inH2O (Range 0, 1, 2, and 3) psi (Range 4 and 5) psi (all ranges) 0 (engineering units above) Upper range limit Linear Specified model code option Specified model code option Specified model code option Specified model code option Installed or none Upscale (Blank)

inH2O@4 °C(1) ftH2O mmH2O@4 °C(1) g/cm2

only(1)

• Output Information • Transmitter Information • LCD display Configuration • Hardware Selectable Information • Signal Selection Refer to the “HART Protocol C1 Option Configuration Data Sheet” on page 38.

Tagging (3 options available) • Standard SST hardware tag is wired to the transmitter. Tag character height is 0.125 in. (3,18 mm), 56 characters maximum. • Tag may be permanently stamped on transmitter nameplate upon request, 56 characters maximum. • Tag may be stored in transmitter memory (30 characters maximum). Software tag is left blank unless specified.

Commissioning tag (fieldbus only) A temporary commissioning tag is attached to all transmitters. The tag indicates the device ID and allows an area for writing the location.

Optional Rosemount 305 or 306 Integral Manifolds Factory assembled to 3051C and 3051T transmitters. Refer to the following Product Data Sheet (document number 00813-0100-4733) for additional information. Optional Three-Valve Manifolds (Packaged Separately)

LCD display M5

Digital Meter, 5-Digit, 2-Line LCD

• Direct reading of digital data for higher accuracy • Displays user-defined flow, level, volume, or pressure units • Displays diagnostic messages for local troubleshooting Digital Meter with 316 Stainless Steel Cover

• For use with stainless steel housing option (housing codes J, K, and L)

Local Span and Zero Adjustment(2) Transmitters ship with local span and zero adjustments standard unless otherwise specified. • Non-interactive external zero and span adjustments ease calibration • Magnetic switches replace standard potentiometer adjustments to optimize performance J1

Local Zero Adjustment Only(1)

J3

No Local Zero or Span Adjustment(1)

Transient Protection T1

Integral Transient Protection Terminal Block

• Integral transient protection terminal block • Meets IEEE Standard 587, Category B 1 kV crest (10 ⫻ 1 000 microseconds) 3 kV crest (8 ⫻ 20 microseconds) 6 kV crest (1.2 ⫻ 50 microseconds) • Meets IEEE Standard 472, Surge Withstand Capability SWC 2,5 kV crest, 1 MHz wave form • Applicable standards: IEC 801-4, 801-5

Bolts for Flanges and Adapters • Options permit bolts for flanges and adapters to be obtained in various materials • Standard material is plated carbon steel per ASTM A449, Type 1 L4

Austenitic 316 Stainless Steel Bolts

• Part No.1151-0150-0001: 3-Valve Manifold, Carbon Steel

L5

ASTM A 193, Grade B7M Bolts

• Part No. 1151-0150-0002: 3-Valve Manifold, 316 SST

L6

Monel Bolts

(2)

Not applicable to fieldbus.

36

Not applicable to fieldbus.

Pa kPa torr atm

(1) Not available on low power or previous versions.

M6

If Option Code C1 is ordered, the customer may specify the following data in addition to the standard configuration parameters.

(1)

psi bar mbar kg/cm2

• 90-degree rotation capability for easy viewing

(1) Not applicable to fieldbus.

Custom Configuration HART protocol

inH2O inHg mmH2O mmHg


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051C Coplanar Flange and 3051T Bracket Option B4

Bracket for 2-in. Pipe or Panel Mounting

• For use with the standard Coplanar flange configuration • Bracket for mounting of transmitter on 2-in. pipe or panel • Stainless steel construction with stainless steel bolts

Rosemount 3051 Shipping Weights TABLE 15. Transmitter Weights without Options Transmitter

Add Weight In lb (kg)

3051C 3051L 3051H 3051T

6.0 (2,7) Table 16 on page 37 13.6 (6,2) 3.0 (1,4)

Rosemount 3051H Bracket Options B5

Bracket for 2-in. Pipe or Panel Mounting

• For use with the 3051H Pressure Transmitter for high process temperatures • Carbon steel construction with carbon steel bolts B6

B5 Bracket with SST Bolts

• Same bracket as the B5 option with Series 300 stainless steel bolts.

Traditional Flange Bracket Options B1

Bracket for 2-in. Pipe Mounting

• For use with the traditional flange option • Bracket for mounting on 2-in. pipe • Carbon steel construction with carbon steel bolts • Coated with polyurethane paint B2

Bracket for Panel Mounting

• For use with the traditional flange option • Bracket for mounting transmitter on wall or panel • Carbon steel construction with carbon steel bolts • Coated with polyurethane paint B3

Flat Bracket for 2-in. Pipe Mounting

• For use with the traditional flange option • Bracket for vertical mounting of transmitter on 2-in. pipe • Carbon steel construction with carbon steel bolts • Coated with polyurethane paint B7

B1 Bracket with SST Bolts

• Same bracket as the B1 option with Series 300 stainless steel bolts B8

B2 Bracket with SST Bolts

• Same bracket as the B2 option with Series 300 stainless steel bolts B9

B3 Bracket with SST Bolts

• Same bracket as the B3 option with Series 300 stainless steel bolts BA

Stainless Steel B1 Bracket with SST Bolts

• B1 bracket in stainless steel with Series 300 stainless steel bolts BC

Stainless Steel B3 Bracket with SST Bolts

TABLE 16. 3051L Weights without Options Flange 2-in., 150 3-in., 150 4-in., 150 2-in., 300 3-in., 300 4-in., 300 2-in., 600 3-in., 600 DN 50/PN 40 DN 80/PN 40 DN 100/ PN 10/16 DN 100/ PN 40

Flush lb. (kg)

2-in. Ext. lb (kg)

4-in. Ext. lb (kg)

6-in. Ext. lb (kg)

12.5 (5,7) 17.5 (7,9) 23.5 (10,7) 17.5 (7,9) 22.5 (10,2) 32.5 (14,7) 15.3 (6,9) 25.2 (11,4) 13.8 (6,2) 19.5 (8,8) 17.8 (8,1)

— 19.5 (8,8) 26.5 (12,0) — 24.5 (11,1) 35.5 (16,1) — 27.2 (12,3) — 21.5 (9,7) 19.8 (9,0)

— 20.5 (9,3) 28.5 (12,9) — 25.5 (11,6) 37.5 (17,0) — 28.2 (12,8) — 22.5 (10,2) 20.8 (9,5)

— 21.5 (9,7) 30.5 (13,8) — 26.5 (12,0) 39.5 (17,9) — 29.2 (13,2) — 23.5 (10,6) 21.8 (9,9)

23.2 (10,5)

25.2 (11,5)

26.2 (11,9)

27.2 (12,3)

TABLE 17. Transmitter Options Weights Code J, K, L, M J, K, L, M M5 M6 B4 B1 B2 B3 B7 B8 B9 BA, BC B5 B6 H2 H3 H4 H7 FC FD FA FB FP FQ

Option Stainless Steel Housing(T) Stainless Steel Housing (C, L, H, P) LCD display for Aluminum Housing LCD display for SST Housing SST Mounting Bracket for Coplanar Flange Mounting Bracket for Traditional Flange Mounting Bracket for Traditional Flange SST Bracket for Traditional Flange Mounting Bracket for 3051H Traditional Flange Traditional Flange Traditional Flange Traditional Flange Level Flange—3 in., 150 Level Flange—3 in., 300 Level Flange—2 in., 150 Level Flange—2 in., 300 DIN Level Flange, SST, DN 50, PN 40 DIN Level Flange, SST, DN 80, PN 40

Add lb (kg) 3.9 (1,8) 3.1 (1,4) 0.5 (0,2) 1.25 (0,6) 1.0 (0,5) 2.3 (1,0) 2.3 (1,0) 2.3 (1,0) 2.9 (1,3) 2.4 (1,1) 2.7 (1,2) 2.6 (1,2) 2.5 (1,1) 10.8 (4,9) 14.3 (6,5) 10.7 (4,8) 14.0 (6,3) 8.3 (3,8) 13.7 (6,2)

• B3 bracket in stainless steel with Series 300 stainless steel bolts

37


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051

HART Protocol C1 Option Configuration Data Sheet ★ = Default Value(1) CONFIGURATION DATA SHEET

Customer: _____________________________________________ P.O. No.: _____________________________________________ Model No.: _____________________________________________ Line Item: _____________________________________________ SST Tag No.: _________________________________________________________________________________________________ Software Tag: |__|__|__|__|__|__|__|__|

OUTPUT INFORMATION: (Software Selectable) 4 mA (1, 0.8 Volts) = ___________________ 0 ★ 20 mA (5, 3.2 Volts) = __________________ Upper Range Limit ★

Pressure Units =

Output = Damping(4)=

□ inH2O(2)★ □ inHg □ mbar □ Atm

□ psi (3) ★ □ bar □ Torr □ kg/cm2

□ Pa □ kPa □ mmH2O □ mmHg

□ Linear ★

□ Square Root (For DP transmitters only)

□ 0.00 sec. □ 0.80 sec.

□ 0.05 sec. □ 1.60 sec.

□ 0.10 sec. □ 3.20 sec.

□ ftH2O □ g/cm2 □ inH2O at 4 °C(5) □ mmH2O at 4 °C (5)

□ 0.20 sec. □ 12.8 sec.

□ 0.40 sec.★ □ 25.6 sec.

TRANSMITTER INFORMATION: (Software Selectable) Descriptor(4): |__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|(16 characters) Message(4): |__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__|__| (32 characters) Date(4): □ Day

□/□ □ □/□ □ Month

Local Span and Zero:

Year

□Enabled ★

□ Disabled

(1) Default values may be different outside the U.S. A. Consult an Emerson Process Management Representative for details. (2) inH20 for CD/CG ranges 1-3 (3) psi for CD/CG range 4 and 5, all CA ranges (4) C1 option required for configuration of this parameter. (5) Not available with low power output.

38


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051

LCD display CONFIGURATION (Software Adjustable – M5 or M6 option must be specified in model number) Meter Display Type(4):

□ Eng. Units only □ % of Range only □ Custom Display only

□ Alternate Eng. Units &% of Range ★ □ Alternate Eng. Units & Custom Display(5) □ Alternate % of Range & Custom Display(5)

Custom Display Configuration: (must be filled out if Custom Display is selected as meter type) Decimal Point Position (fixed)— indicate decimal point location:

X X X★ X X

Enter Lower Range Value (Decimal point must be in the same position as specified above.)

(circle sign)

+

□ □ □ □ □

+000.00 ★

Enter Upper Range Value (Decimal point must be in the same position as specified above.)

(circle sign)

+

□ □ □ □ □

+100.00 ★

*

Custom Units—spaces consume A-Z, 0-9, /, , %, blank

□□□□□

%RNGE ★

Custom Display Transfer Function (Independent of Analog Output)

□ Linear ★

□ Square Root

HARDWARE SELECTABLE INFORMATION Alarm Option: Transmitter Security:

High Off

Low On

Note: Specify C4 Option in model structure when ordering NAMUR-compliant alarm and saturation limits.(5)

SIGNAL SELECTION: (Software Selectable)

4–20 mA with simultaneous digital signal based on HART protocol★ Burst mode of HART digital process variable (4) Burst mode output options:

Primary variable in engineering units Primary variable in percent of range All dynamic variables in engineering units and the primary variable mA value Multidrop Communication(4)(6)

Choose transmitter address(7) (1-15): _______________

(4) C1 option required for configuration of this parameter. (5) Not available with low power output. (6) This option fixes the transmitter analog output at 4mA. (7) Default address is 1 if multidrop communication is selected.

39


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051 3051C Differential/Gage Pressure Transmitter Range Limits Range 1 Span

Range 2 Span

Range 3 Span

Range 4 Span

Range 5 Span

Units

min

max

min

max

min

max

min

max

min

max

inH2O inHg ftH2O mmH2O mmHg psi bar mbar g/cm2 kg/cm2 Pa kPa torr atm

0.5 0.03678 0.04167 12.7 0.93416 0.01806 0.00125 1.2454 1.26775 0.00127 124.545 0.12545 0.93416 0.00123

25 1.8389 2.08333 635.5 46.7082 0.903 0.06227 62.2723 63.3875 0.0635 6227.23 6.2272 46.7082 0.06146

2.5 0.18389 0.20833 63.553 4.67082 0.0902 0.00623 6.22723 6.33875 0.00635 622.723 0.62272 4.67082 0.00615

250 18.389 20.8333 6355 467.082 9.03183 0.62272 622.723 633.875 0.635 62160.6 62.2723 467.082 0.61460

10 0.73559 0.83333 254 18.6833 0.36127 0.02491 24.9089 25.355 0.0254 2490.89 2.49089 18.6833 0.02458

1000 73.559 83.3333 25421 1868.33 36.127 2.491 2490.89 2535.45 2.54 249089 249.089 1868.33 2.458

83.040 6.1081 6.9198 2110.95 155.145 3 0.20684 206.843 210.547 0.21092 20684.3 20.6843 155.145 0.20414

8304 610.81 691.997 211095 15514.5 300 20.6843 20684.3 21054.7 21.0921 2068430 2068.43 15514.5 20.4138

553.60 40.720 46.13 14073 1034.3 20 1.37895 1378.95 1406.14 1.40614 137895 137.895 1034.3 1.36092

55360 4072.04 4613.31 1407301 103430 2000 137.895 137895 140614 140.614 13789500 13789.5 103430 136.092

When using a HART communicator, Âą5% adjustment is allowed on the sensor limit to allow for unit conversions.

3051L/3051H Pressure Transmitter Range Limits Range 2 Span

Range 3 Span

Range 4 Span

Units

min

max

min

max

min

max

min

max

inH2O inHg ftH2O mmH2O mmHg psi bar mbar g/cm2 kg/cm2 Pa kPa torr atm

2.5 0.18389 0.20833 63.553 4.67082 0.0902 0.00623 6.22723 6.33875 0.00635 622.723 0.62272 4.67082 0.00615

250 18.389 20.8333 6355 467.082 9.03183 0.62272 622.723 633.875 0.635 62160.6 62.2723 467.082 0.61460

10 0.73559 0.83333 254 18.6833 0.36127 0.02491 24.9089 25.355 0.0254 2490.89 2.49089 18.6833 0.02458

1000 73.559 83.3333 25421 1868.33 36.127 2.491 2490.89 2535.45 2.54 249089 249.089 1868.33 2.458

83.040 6.1081 6.9198 2110.95 155.145 3 0.20684 206.843 210.547 0.21092 20684.3 20.6843 155.145 0.20414

8304 610.81 691.997 211095 15514.5 300 20.6843 20684.3 21054.7 21.0921 2068430 2068.43 15514.5 20.4138

553.60 40.720 46.13 14073 1034.3 20 1.37895 1378.95 1406.14 1.40614 137895 137.895 1034.3 1.36092

55360 4072.04 4613.31 1407301 103430 2000 137.895 137895 140614 140.614 13789500 13789.5 103430 136.092

When using a HART communicator, Âą5% adjustment is allowed on the sensor limit to allow for unit conversions.

40

Range 5 Span


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051 3051T Gage and Absolute Pressure Transmitter Range Limits

Range 1 Span Units inH2O inHg ftH2O mmH2O mmHg psi bar mbar g/cm2 kg/cm2 Pa kPa torr atm

Range 2 Span

Range 3 Span

Range 4 Span

min

max

min

max

min

max

8.30397

831.889

41.5198

4159.45

221.439

22143.9

0.61081 0.69199 211.10 15.5145 0.3 0.02068 20.6843 21.0921 0.02109 2068.43 2.06843 15.5145 0.02041

61.0807 69.3241 21130 1551.45 30 3.06843 2068.43 2109.21 2.10921 206843 206.843 1551.45 2.04138

3.05403 3.45998 1054.60 77.5723 1.5 0.10342 103.421 105.461 0.10546 10342.1 10.3421 77.5726 0.10207

305.403 345.998 105460.3 7757.23 150 10.3421 10342.11 10546.1 10.5461 1034212 1034.21 7757.26 10.2069

16.2882 18.4533 5634.66 413.72 8 0.55158 551.581 561.459 0.56246 55158.1 55.1581 413.721 0.54437

min

1628.82 1845.33 563466 41372 800 55.1581 55158.1 56145.9 56.2456 5515811 5515.81 413721 54.4368

Range 5 Span

max

1107.2 81.441 92.2663 28146.1 2068.6 40 2.75791 2757.91 2807.31 2.81228 275791 275.791 2068.6 2.72184

min

110720 8144.098 9226.63 2814613 206860.0 4000 275.7905 275790.5 280730.6 281.228 27579054 27579.05 206859.7 272.1841

55360 4072.04 4613.31 1407301 103430 2000 137.895 137895 140614 140.614 13789500 13789.5 103430 136.092

max 276799 20360.2 23066.6 7036507 517151 10000 689.476 689476 703067 701.82 68947600

68947.6 517151 680.46

When using a HART communicator, Âą5% adjustment is allowed on the sensor limit to allow for unit conversions.

3051C Absolute Pressure Transmitter Range Limits Range 1 Span

Range 2 Span

Range 3 Span

Range 4 Span

Units

min

max

min

max

min

max

min

max

inH2O inHg ftH2O mmH2O mmHg psi bar mbar g/cm2 kg/cm2 Pa kPa torr atm

8.30397 0.61081 0.69199 211.10 15.5145 0.3 0.02068 20.6843 21.0921 0.02109 2068.43 2.06843 15.5145 0.02041

831.889 61.0807 69.3241 21130 1551.45 30 2.06843 2068.43 2109.21 2.10921 206843 206.843 1551.45 2.04138

41.5198 3.05403 3.45998 6.35308 1055.47 1.5 0.10342 103.421 105.27 0.10546 10342.1 10.3421 77.5726 0.10207

4151.98 305.403 345.998 635.308 105547 150 10.342 10342.1 105.27 10.546 1034210 1034.21 7757.26 10.207

221.439 16.2882 18.4533 5634.66 413.72 8 0.55158 551.581 561.459 0.56246 55158.1 55.1581 413.721 0.54437

22143.9 1628.82 1845.33 563466 41372 800 55.1581 55158.1 56145.9 56.2456 5515811 5515.81 413721 54.4368

1107.2 81.441 92.2663 28146.1 2068.6 40 2.75791 2757.91 2807.31 2.81228 275791 275.791 2068.6 2.72184

110720 8144.098 9226.63 2814613 206860.0 4000 275.7905 275790.5 280730.6 281.228 27579054 27579.05 206859.7 272.1841

When using a HART communicator, Âą5% adjustment is allowed on the sensor limit to allow for unit conversions.

41


Product Data Sheet 00813-0100-4001, Rev FA August 2004

Rosemount 3051

Rosemount, Annubar, ProPlate, and the Rosemount logotype are registered trademarks of Rosemount Inc. PlantWeb is a registered trademark of one of the Emerson Process Management group of companies. Complete Point Solutions, Coplanar and Multivariable are trademarks of Rosemount Inc. HART is a registered trademark of the HART Communications Foundation. Hastelloy is a registered trademarks of Haynes international, Inc.. Monel is a registered trademark of the Special Metals Corporation group of Companies. Syltherm 800, Dow Corning, and D.C. are registered trademarks of Dow Corning Co. Teflon is a registered trademark of E.I. du Pont de Nemours & Co. Neobee M-20 is a registered trademark of Stephan Chemical Co. The 3-A symbol is a registered trademark of the 3-A Sanitary Standards Symbol Council. FOUNDATION fieldbus is a registered trademark of the Fieldbus Foundation. Fluorinert is a registered trademark of 3M Company. All other marks are the property of their respective owners. Rosemount Model 3051 Smart Pressure Transmitters may be protected by one or more of the following U.S. Patent Nos. 4,370,890; 4,466,290; 4,612,812; 4,791,352; 4,798,089; 4,818,994; 4,833,922; 4,866,435; 4,926,340; 4,988,990; and 5,028,746. Mexico Patentado No. 154,961. May depend on model. Other foreign patents issued and pending.

Emerson Process Management Rosemount Inc. 8200 Market Boulevard Chanhassen, MN 55317 USA T (U.S.) 1 800 999 9307 T (International) (952) 906 8888 F (952) 949 7001 www.rosemount.com

Emerson Process Management GmbH & Co. Argelsrieder Feld 3 82234 Wessling Germany T 49 (8153) 9390 F 49 (8153) 939172

¢00813-0100-4001;¤ © 2004 Rosemount Inc. All rights reserved.